ADM1D V1.0 – 5/32A User manual

image

Contents

1. A CAUTION During reparation and maintenance do not touch the meter connecting clamps directly with your bare hands with metal blank wire or other material as you will have the chance of an electricity shock and a possible chance for health damage gt Turn off and lock out all power supplying the energy meter and the equipment to which it is installed before opening the protection cover to prevent the hazard of electric shock DMMeteringg 2007 A WARNING VV WV meter gt Maintenance or repair should be performed by qualified personnel familiar with applicable codes and regulations Use insulated tools to maintain or repair the meter Make sure the protection cover is in place after maintenance or repair Case is sealed failure to observe this instruction can result in damage for Problem Check Solution No light for the Power supply indicator Is AC power supply connected to the meter Is the 1 and 4 connecting correct Maybe there is a fault in the inside circuit Check switch or circuit breaker and fuse or thermal cut off Reinstall terminal screws on the 1 and 4 Make sure all screws are fixed Than there should be a 230V 50Hz AC voltage between the terminal screws on the 1 and 4 when power supply is input Please contact your technical supporter to replace this meter No light for the consumption indicator Is the load running Is the ope
2. 1 3 Performance criteria Operating humidity Storage humidity Operating temperature Storage temperature International standard Accuracy class Protection against penetration of dust and water Insulating encased meter of protective class 1 4 Specifications Nominal voltage Un Operational voltage Insulation capabilities AC voltage withstand Impulse voltage withstand Basic current Ib Maximum rated current Imax Operational current range Over current withstand Operational frequency range Internal power consumption Test output flash rate RED LED Pulse output rate pins 20 amp 21 Power supply indicator Green LED Consumption indicator RED LED Data display mode Data save 1 5 Basic errors 0 05Ib Cosp 1 0 1Ib Cos 0 5L Cos 0 8C 0 1Ib Imax Cos 1 0 21b Imax Cos 0 5L Cos 0 8C 1 6 Description Case moov Security hasp DMMeteringg 2007 Terminal block Protection cover lt 75 lt 95 10 C 50 C 30 C 70 C IEC 62053 21 1 IP51 II 230V AC 161 300V AC 2KV for 1 minute 6KV 1 2uS waveform 5A 32A 0 25A 32A 960A for 0 01s 50Hz 10 lt 2W 10VA 2000 impulses per kWh 0 5Wh imp 2000 pulses per kWh 0 5Wh imp Meter is connected and working OK Flashing at load running 7 1 digits for LCD display The data can be stored more than 20 years when power cut 1 5 1 5 1 5 1 0 1 0 1 0 Register LCD displ
3. Installation maintenance and repair should only be done by qualified personnel Never break the seals and open the front cover as this might influence the functionality of the meter and will avoid any warranty gt Do not drop or allow physical impact to the meter as there are high precision components inside that may break or render the meter measuccure inarate VV Exclusion of liability We have checked the contents of this publication and every effort has been made to ensure that the descriptions are as accurate as possible However deviations from the description cannot be completely ruled out so that no liability can be accepted for any errors or omissions contained in the information given The data in this manual is checked regularly and the necessary corrections are included in subsequent editions We are grateful for any improvements that you care to suggest Subject to technical modifications without notice Copyright Copyright DMMetering March 2007 All rights Reserved It is prohibited to pass on or copy this document or to use or disclose its contents without our express permission Any duplication is a violation of the law and subject to criminal and civil penalties All rights reserved particularly in the event of a patent award or utility model registration Registered trademarks DMMetering is registered trademark of Inepro Industries Ltd member of the Inepro Group The other names appearing in this manual may
4. Ra 0 5 Wh imy Q R 05 Whiimp LEO ce b Indication for reverse use When the meter is in the wrong connects with the incoming line and the outgoing line that is the incoming line is connected to the position for the outgoing line and DMMeteringg 2007 the outgoing line is connected to the position for incoming line it will happen reverse The LCD display will show HELP 1 and the current total energy circularly to indicate the user for the wrong connection The period of circular display is 3 seconds F c a m Doni om 2 pan UN zy mr p eel LX zv 230V 5 32 A 5 Hz 230V 5 32 A 50Hz C RZ 0 5 inp C R08 Wim JEO ce LEIO ce Pulse output The ADM1D V1 0 DIN rail energy meter is equipped with a pulse output which is fully separated from the inside circuit That generates pulses in proportion to the measured energy for remote reading purposes and accuracy testing The pulse output is a polarity dependant passive transistor output requiring an external voltage source for correct operation For this external voltage source the voltage Ui should is 5 27V DC and the maximum input current Iimax is 27mA DC To connect the impulse output connect 5 27V DC to connector 20 anode and the signal wire S to connector 21 cathode The meter pulses 2000 per kWh 0 5Wh imp 1 10 Troubleshooting
5. be trade names the use of these names by third parties for their own purposes may infringe the rights of the owners 1 2 Foreword Thank you for purchasing the DMMetering ADM1D V1 0 DIN rail single phase two wire energy meter The DMMetering ADM1D V1 0 energy meter is the most advanced type electronic kWh meter available at the market With the DMMetering product range we have introduced a large scale of energy meters on the market suitable for 110V AC to 400V AC 50 or 60Hz Besides the normal energy meters we also developed our own pre paid meters with chip card chip card re loaders and a complete PC management control system For more information on other product please contact our sales department at salesgdmmetering com or info inepro com hk Although we produce the DMMetering ADM1iD V1 0 meter according to IEC 62053 21 and our quality inspection is very accurate there might always be a possibility that your product shows a fault or failure for which we do apologize Under normal conditions your product should give you years of benefit and pleasure In case there is problem with the energy meter you should contact your dealer immediately All energy meters are sealed with a special seal Once this seal is broken there is no possibility to claim for warranty Therefore NEVER open an energy meter or break the seal of the energy meter The warranty time is 6 months after installation and only valid for construction faults DMMeteringg 2007
6. DMMetering ADM1D V1 0 5 32A DIN rail single phase two wire energy meter 1 1 Safety instruction 1 2 Foreword 1 3 Performance criteria 1 4 Specifications 1 5 Basic errors 1 6 Description 1 7 Dimensions 1 8 Installation 1 9 Operating 1 10 Troubleshooting 1 11 Technical support User manual DMMeteringg 2007 1 1 Safety instructions Information for Your Own Safety This manual does not contain all of the safety measures for operation of the equipment module device because special operating conditions and local code requirements or regulations may necessitate further measures However it does contain information which must be read for your own personal safety and to avoid material damages This information is highlighted by a warning triangle and is represented as follows depending on the degree of potential danger Caution Means hazard of electric shock and failure to take the necessary safety precautions will Warning Means that failure to observe the instruction can result in death serious injury or considerable material damage A result in death serious injury or considerable material damage Qualified personnel Commissioning and operation of the equipment module device described in this manual may only be performed by qualified personnel Qualified personnel in the sense of the safety information contained in this manual are persons who are authorized to commiss
7. act your technical supporter to replace this meter Pulse output rate wrong Maybe there is a fault in the inside circuit Please contact your technical supporter to replace this meter 1 11 Technical support For questions about one of our products please contact DMMetering dealer in your in your region Your local DMMetering distributor Email support dmmetering com www dmmetering com Inepro Industries Ltd Room 3208 Central Plaza 18 Harbour Road Wan Chai Hong Kong Fax 852 2911 1200 www inepro com hk info inepro com hk RoHS COMPLIANT pamm 2002 95 EC DMMeteringg 2007
8. ay Material Window of register Case Terminal block Protection cover 1 7 Dimensions Height Width Depth Weight D m 230 522 AS0Hz 0 5 o eju luo c OO o U DMMeteringg 2007 PC inflammable retarding PA inflammable retarding PA inflammable retarding PA inflammable retarding i ous V A8joul YMY Vct eseu O LA QV yug xew i AZZ xew i OS swog dui 3 116 mm 17 5 mm 59 mm 0 12 Kg net gt o m a LAI sz Lr o for 2 x o ES A 4 e MMM i CQ 4 py m 1 8 Installation DMMeteringg 2007 CAUTION gt Turn off and lock out all power supplying the energy meter and the equipment to which it is installed before working on it gt Always use a properly rated voltage sensing device to confirm that power is off AN WARNING Installation should be performed by qualified personnel familiar with applicable codes and regulations Use isolated tools to install the meter Fuse or thermal cut off or single pole circuit breaker can t be fitted on the supply line and not the neutral line Caseis sealed failure to observe this instruction can result in damage for meter We recommend that the connecting wire whi
9. ch is used to connect meter to outside circuit should be sized according to local codes and regulations for the ampacity of the circuit breaker or over current device used in the circuit An external switch or a circuit breaker should be installed on the inlet wire which will be used as a disconnection device for the meter And there it is recommendation that the switch or circuit breaker be near the meter so that it is convenience for the operator The switch or circuit breaker should comply with the specifications of the building electrical design and all local regulations This meter can be installed indoor directly or in a meter box which is waterproof outdoor subject to local codes and regulations To prevent tampering secure the meter with a padlock or a similar device The meter has to be installed against a wall which is fire resistant The meter has to be installed in a good ventilated and dry place The meter has to be installed in a protection box when placed in dangerous or dusty environment The meter can be installed and used after being tested and sealed with a letter press printing The meter can be installed on a 35mm DIN rail The meter should be installed in an available height so that it is easy to read When the meter is installed in an area with frequent surges due to e q thunderstorms welding machines inverters etc protect the meter with Surge Protection Devices After finishing installation the meter must be seale
10. d to prevent tampering Connection of the wires should be done in accordance with the underneath connection diagram 20 Gy L 3 j P 1 SO 6 ne 21 7 1 Inlet phase line 4 Inlet neutral line 3 Outgoing phase line 6 Outgoing neutral line 20 and 21 Pulse output contact 1 9 Operating Working indication There is a LED which has two colors green and red while burning in the front panel of ADM1D V1 0 When the meter works normally this LED will display green When meter is going wrong or no power supply the LED will turn off Consumption indication There is a LED which has two colors green and red while burning in the front panel of ADM1D V1 0 When consumption happens the LED will flash and display red The more quickly LED flash the more consumption there is For this LED the flash rate is 2000 impulses per kWh 0 5Wh imp Reading the meter ADM1D V1 0 is equipped with a white backlight LCD display During the normal working hours the meter will be burning this white backlight all the time LCD display will show the following energy data and indication message a Current total energy When the meter is in normal working it will display only 7 1 energy data with The unit is kWh These data can not be reset to zero by the user Example Total energy is 4574899 1 kWh kWh 5 14898 230V 5 32 A 50Hz
11. ion start up ground and label devices systems and circuits according to safety and Regulatory standards Use for the intended purpose The equipment device module may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by DMMetering Proper handling The prerequisites for perfect reliable operation of the product are proper transport proper storage installation and assembly as well as proper operation and maintenance When operating electrical equipment certain parts of this equipment automatically carry dangerous voltages Improper handling can therefore result in serious injury or material damage Use only isolated tools Do not connect while circuit is live hot Do not connect the meter to a 3 phase 400VAC network Place the meter only in dry surroundings Do not mount the meter in an explosive area or exposed to dust mildew and insects Make sure the used wires are suitable for the maximum current of this meter Make sure the AC wires are connected correctly before activating the current voltage to the meter Do not touch the meter connecting clamps directly with your bare hands with metal blank wire or other material as you will have the chance of an electricity shock and a possible chance for health damage Make sure the protection cover is placed after installation Vv VV VVVV WV DMMeteringg 2007
12. rating power too low Maybe there is a fault in the inside circuit Only when load is running this LED will flash If the operating power is too low the spacing interval of the flashes will take some more time so this is why it seems like the LED isn t burning Please contact your technical supporter to replace this meter The register can t run DMMeteringg 2007 Is there a power supply inside the meter Is the operating power too low Maybe there is a fault in the inside circuit Check that the power supply indicator is burning If the operating power is too low the spacing interval of the pulses will take some more time this is why it seems like that the register can t run Please contact your technical supporter to replace this meter DMMeteringg 2007 Continue Problem Check Solution LCD backlight can t lit Is there a power supply inside the meter Maybe there is a fault in the inside circuit Check if the power supply indicator is burning Please contact your technical supporter to replace this meter No pulse output Is DC power supply connected to the meter Is the connecting correct Maybe there is a fault in the inside circuit Check the external voltage source Ui is 5 27V DC Check correct connecting connect 5 27V DC to connector 20 anode and the signal wire S to connector 21 cathode Please cont