image

Contents

1. O E 2 4321 5 LI 1 we TP3 1 wo NA 2 0 Oo 2 0 a 5 D 250 2307 4 5 5225 500mA 115V O OO z OO OOO CON2 CON1 765 4 3 21 87654 3 21 252 5 232 56050 0 gt 2 gt O zD l rOrOmiz 2 a2 25 2 2 2 2550 5 2 gt Q gt 5 2 2 302Z S gt OF26 2 2 2 SW1 1 INPUT VOLTAGE SELECT SW1 2 NO FUNCTION 5 1 3 LOGIC ANALOGUE CONTROL SELECT SW1 4 ALTERNATIVE ALARM LOGIC UNREGULATED VOLTS 5V 4V REFERENCE ov PHASE PULSES TEMERATURE SETPOINT HIGH FERQUENCY THYRISTOR DRIVE P A D RAMP LOCK ULSES STA203 160A 440V 230V
2. 7 Swit Ch 8 Minimising Transformer Inrush 8 9 9 Switching 9 Indicators astern 9 Demand Asien 9 Line 10 Use With The Amot 130 10 11 CALEDON CONTROLS LTD Manual Issue Number R1 STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Page 2 FEATURES Versions for single 3 phase loads Current rating from 80 to 1000 air cooled Operation without derating up to 50 C ambient Low cost 2 line control of 3 phase load Minimum radio frequency emissions Minimum waveform distortion No power factor degradation Simple installation commissioning and maintenance Microprocessor controlled Long life ball bearing fans Compact size only 290mm deep GENERAL DESCRIPTION This range of thyristor stacks is specifically designed for burst fire control of the primary of transformer coupled loads
3. STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Page 5 INSTALLATION GENERAL REQUIREMENTS The following notes are a guide to ensuring sound system design and compliance with the requirements of the European Low Voltage Directive The stacks should be installed in a cabinet requiring a tool to gain access and access should be restricted to suitably trained and qualified personnel Provision should be made to exclude conductive pollution eg graphite dust from the cabinet and to avoid condensation Caledon thyristor stacks are designed with an impulse withstand voltage of 4k V This meets the requirements of IEC and European standards for installation category 3 and supply voltage line to earth up to 300V AC RMS This corresponds to 520V line to line on most distribution systems in which the supply transformer is star connected with earthed star point This does not preclude the use of the stacks in higher voltage systems provided the thyristor devices are suitably rated but precautions may be necessary surge arrestors to limit the expected impulse voltage level to ensure systems compliance with the above standards All the STA series thyristor stacks incorporate integral semiconductor fuses These are intended to provide short circuit protection for the thyristor devices by limiting the peak half cycle surge current and total energy let through They only provide limited protection against long term overload The stack
4. 4 Phase 2 Illuminates when line voltage is present between line 2 and line 3 When the driver supply is first switched on this LED may flash indicating that V 3 In 3 phase 1 leads Will extinguish if the line voltage is not present the line systems only 2 fuse has blown 5 Phase Lock when the stack has successfully synchronised to the line supply The stack synchronises to the voltage between L1 and L3 Will extinguish if phase lock is lost caused by loss of supply phase 1 LED also absent or excessive noise or frequency variation on the supply or if the supply frequency is out of tolerance 6 Enable Illuminates when 1 5 are correct and the external enable is made link across terminals 1 1 and 1 2 7 Demand when the stack is demanding load current More information on the demand signal is provided in the next section 8 Alarm red Iiluminates when the alarm relay is in the alarm state de energised This LED will be illuminated briefly when driver power is first applied and subsequently will illuminate 5 seconds after loss of any of 2 5 An alarm is also generated if the driver power is lost relay de energises If DIL switch 4 is on it will also illuminate on loss of the external enable signal DEMAND SIGNAL The stack operates in burst fire mode ie the load current is either on or off The start of each burst is synchronised to the line voltage
5. CONTROL THERMOCOUPLE FUSE IF LINE 2 Ze of SUPPLY temperature 7 ov TEMPERATURE CONTROLLER ov SOUNDER OROTHER NEUTRAL ALARM DEVICE suy ENABLE SIGNAL CONTROL INPUT HO ALARM COMMON CLOSED IN ALARM ENABLE SIGNAL ov CONTROLLER OVER TEMPERATURE THERMocouPLE CONTROL INPUT ov AMOT 130 ALARM COMMON CLOSED IN ALARM SUPPLY L SUPPLY NEUTRAL LOAD1 SOUNDER HO SUPPLY N OR OTHER NEUTRAL Fig 2 Control Waveforms 1 PHASE TRANSFORMER LOAD LOAD 1 CURRENT LOGIC INPUT 1111 INTERNALY GENERATED DEMAND SIGNAL LOGIC OUTPUT 2 PHASE TRANSFORMER LOAD 2 PHASE TRANSFORMER LOAD PHASE ROTATION A PHASE ROTATION B LOAD 1 LOAD 1 CURRENT CURRENT LOAD 2 LOAD 2 CURRENT CURRENT GENERATE SIGNAL INTERNALY INTERNALY GENERATED DEMAND DEMAND SIGNAL LOGIC OUTPUT LOGIC zao INPUT E L_1 ___ LOGIC OUTPUT T VOLTAGE SELECT OPTIONS 230V 115V STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Fig 3 Control Board Layout
6. switch off may be delayed for a few cycles until a reliable signal is obtained If a reliable signal is not obtained then switch off occurs anyway but the next switch on is set to start in phase angle mode If a phase or the driver supply voltage is lost while the demand signal is high the next switch on is set to start in phase angle mode If a phase or the driver supply is lost while the demand signal is low then no action is taken other than to signal the condition USE WITH THE AMOT 130 The AMOT 130 is a panel mounted over temperature policeman combined with an auto manual station The over temperature policeman may be used to provide independent monitoring of the load temperature and in conjunction with a contactor or under voltage trip on a circuit breaker can provide independent switch off of the load current The auto manual station which is wired between the main temperature controller and the stack control input analogue input only provides a simple means for the operator to switch control of the heater from the automatic controller to a manually operated potentiometer on the instrument An LED bargraph gives visual indication of the level of the power control signal in auto or manual Combining the two functions in one instrument confers a major advantage When an over temperature is sensed the power demand signal is reduced to zero a short time before the alarm relay is operated Thus assuming the thyristors are still f
7. TRANSFORMER COUPLED LOADS Page 8 To gain access undo the two wing nuts which secure the driver lid and slide the lid away from the unit The driver box may then be slid forward and disengaged from the retaining washers The protective earthing cables may be unplugged at the stack end These MUST be replaced when refitting the box The driver supply voltage is defined by the fan voltage and is noted on the stack rating plate It cannot be changed without changing the fans The driver supply transformer is fitted with universal windings and the correct connection is chosen by the position of the connector to the printed circuit card See figure 3 DIL SWITCH A 4 way DIL switch may be used to configure modes of operation When the unit is supplied all 4 switches are OFF The function of the switches is as below 1 Input Range If switched on changes the required input signal from 1 5V to 2 10V 2 Not used 3 Mode Sets the input control signal type When off the required input signal is analogue When on the input signal is logic Note that the chosen signal must also be wired to the appropriate terminal 4 Alarm function If switched on causes the alarm to operate when the external enable signal is lost in addition to the standard alarm conditions MINIMISING TRANSFORMER INRUSH CURRENT To minimise transformer inrush current the point in the mains cycle at which the thyristors are switched on should be optimised A potentiometer start
8. as shown in figure 2 The demand signal is generated internally in response to the external control signal which may be either analogue or logic as defined by the DIL switch setting and the signal connection CALEDON CONTROLS LTD Manual Issue Number R1 STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Page 10 Analogue Control Signal The input signal is 1 5V and a 50 duty cycle is set when the input is at 3V The stack is fully off with an input of 1 2V or less and fully on with an input of 4 8V or more At 50 duty cycle one cycle period is approximately 15 seconds At duty cycles other than 50 the cycle period becomes progressively longer as the duty cycle increases or decreases This enables the average power delivered on the cycle to be modulated over a wide band without having unduly short or off periods Minimum on and off times of 1 second are superimposed on the basic cycle period so that if the control signal is rapidly increased or decreased the load is not switched too rapidly Logic Control Signal The input signal is a voltage which switches the stack either of or on The maximum input voltage is 30V lt 2V the stack is off gt 3V the stack is on The cycle period is set by the switching rate of the external signal except that the minimum on and off times of 1 second will still apply The external cycle period can thus not be less than 2 seconds and in practice must be considerably longer to achieve a
9. loss of phase lock heatsink overtemperature LED Indicators 1 Auxiliary driver power supply present 2 Heatsink temperature within range 3 Presence of load supply voltages 4 Phase lock control system synchronised to load supply voltage 5 Enable 1 4 correct and external enable signal present 6 Demand signal Stack is asking for current to be supplied to load 7 Alarm one of 1 4 is not correct Control Parameters Load burst fire cycle time at 50 duty cycle Burst fire start angle 15 seconds Other cycle times available on request Adjustable 30 90 after zero crossing by potentiometer After loss of power while load current is flowing or change of phase rotation or supply frequency first switch on is ramped over ten cycles in phase angle mode on line 1 to reset transformer magnetisation Notes All units require an auxiliary power supply of 115 or 230V 10 15 50 60 Hz to power the driver card and the fans where applicable This supply does not need to be phase related to the main load supply All units apart from the 80A unit are fan cooled All units are fitted with snubber capacitors MOV transient over voltage protection semiconductor fuses and filter capacitors Above 600A units can be sized to meet your requirements 660V units Note that impulse withstand voltage is restricted to 4kV and filter capacitors are omitted Consult us CALEDON CONTROLS LTD Manual Issue Number R1
10. ENDED POWER CABLE SIZES The following is a guide only as installation conditions will vary A maximum control cabinet temperature of 50 C has been assumed with cables routed in free air in the immediate vicinity of the stack and passing into trunking in groups of three The cable protective fuse or circuit breaker rating has been assumed to be equal to the stack current rating For currents up to 200A a cable with a maximum operating temperature of 85 90 C has been assumed For 315A and above a cable with a maximum operating temperature of 125 C has been assumed We recommend the use of cables with cross linked polyolefin insulation CALEDON CONTROLS LTD Manual Issue Number R1 STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Page 6 STACK RATING CABLE X SECTION STACK RATING CABLE X SECTION 80A 25mm 315A 120mm 125A 50mm 400A 2 120mm 160A 70mm 600A 2 x 120mm 200A 120mm MECHANICAL The stack must be mounted vertically with the fans at the bottom of the unit Allow a minimum of 100mm above and below the stack to allow free airflow The stack is mounted using 4 off M6 6mm diameter screws For fixing centres see the attached drawing For convenience the two bottom screws may be screwed loosely into the bulkhead to which the stack is to be mounted and the stack hooked over them before inserting the upper two screws and tightening WIRING Typical wiring schematics are shown in figure 1 To ensure that the stack ins
11. TA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS OPERATION COVERS For safety reasons the stack should not be operated with the clear polycarbonate cover or the driver box cover removed Additionally the fans direct a proportion of their airflow over the high voltage card and semiconductor fuses and this cooling action particularly of the fuses will be impaired if the cover is removed SWITCHING ON The main and driver power supplies may be switched on in any order The stack will not supply current to the load until all supplies are present The fans will run all the time the driver supply is present LED INDICATORS The normal operation of the stack is displayed on 8 LED lamps whose function is as follows LED Description Function No 1 Power Iiluminates to show that the driver power is present 2 Temperature Iiluminates when all the heatsinks are within the correct temperature band Will extinguish if a heatsink over heats 3 Phasel Illuminates when line voltage is present between line 1 and line 3 When the driver supply is first switched on this LED may flash indicating that In 3 phase 1 leads 14 Will extinguish if the line voltage is not present or the line systems 1 fuse has blown In single phase Illuminates when line voltage is present between line 1 and line 2 systems neutral Will extinguish if the line voltage is not present or the semiconductor fuse has blown
12. USER MANUAL STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS 80A 600A Caledon Controls Ltd Unit 2 Block 4 Castlehill Industrial Estate Carluke Lanarkshire Scotland ML8 5UF Telephone 01555 773355 Fax 01555 772212 CALEDON CONTROLS LTD K620W1R1 DOC January 1997 STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Page 1 Table of Contents Features ioc EEA AE 2 General Pop 2 Rating Plate 2 Safety 3 Table Of Fuse Types 3 Compliance With 3 Specifications or a a 4 Environmental caren dane Sn heen Moin 4 Electrical des cade EE E 4 Control Signal Inputs And 4 5 General Reqiirements isle 5 Recommended Power Cable 512 5 6 estes 6 Commissioning 7 Access Driver
13. angle adjust accessible through a hole in the front cover of the driver box is provided to make this adjustment The optimum point will be just before the peak of the voltage current waveform on the first phase to be switched on This may be monitored on a storage oscilloscope connected to a current transformer the load 1 cable The oscilloscope may be synchronised to the logic output signal from the stack If suitable equipment is not available then the potentiometer should be set to approximately one quarter way from the fully anti clockwise position to the clockwise position To fully observe the load currents if desired two current transformers are required on three phase systems to monitor load 1 and load 2 current The waveforms observed will depend on the phase rotation There are two possible phase rotations here called A and B These are indicated by the flashing phase LED when auxiliary power is first applied If Phase LED is flashing then rotation is A If Phase 2 LED is flashing then rotation is B It is important that the current transformers should both be phased the same when the current waveforms should appear as in figure 2 To optimise the inrush set the controller to 50 duty cycle and rotate the potentiometer slightly between bursts observing the switch on current starting from the fully anti clockwise condition until the optimum point is found Note that the first time the controller fires after powering up
14. e control electronics monitors phase rotation and adjusts accordingly Line 2 Connection STA101 units for single phase load A connection is required to the line supplying the unswitched side of the load for line synchronisation and connection of integral emc capacitors This may be a second line or the supply neutral depending on load connection This connection is made to the terminal marked line 2 adjacent to the load 1 terminal The connector is of the screwless cage clamp type and will accept cables from 0 75mm2 to 4mm cross section To insert the cable insert a small screwdriver in the hole in the terminal adjacent to the cable entry and depress while inserting the cable Release the screwdriver Note that the screwdriver is in electrical contact with the conductor and should not be inserted while the circuit is live If this connection is to a supply line not the neutral then the cable should be protected with a 5A fuse Control Cables All control cables are wired to two connectors on the side mounted control box These connectors are pluggable and may be removed for maintenance purposes etc They are suitable for cables up to 2 5mm cross section It is not specifically necessary to use screened cable for the wiring of control circuits to meet the required emc immunity level We recommend that good wiring practice be followed within the control panel in which the stack is installed taking care to avoid running signal wiri
15. fans running One of the connections to a temperature sensor is faulty Phase 1 LED is not lit The line 1 power is not present the line 1 semiconductor fuse has blown Phase 2 LED is not lit The line 2 power is not present or the line 2 semiconductor fuse has blown Phase 1 and Phase 2 LEDs not lit Line power is not present or line 3 power is not present Phase lock LED is not lit If phase 1 and phase 2 are both lit then the line supply must be very noisy or outside the frequency tolerance or varying rapidly in frequency Enable LED not lit One of the preceding LEDs 15 not lit or the external enable is not made Demand LED will not come on The enable LED is not lit or the control signal is missing or the DIL switch is not set correctly for the type of control signal logic or analogue Semiconductor fuses blow repeatedly The start angle is not set up properly One of the high voltage card fuses under the clear cover has blown This will send DC through the transformer and blow the semiconductor fuse on that line immediately CALEDON CONTROLS LTD Manual Issue Number R1 115V 230V OVERTEMPERATURE SUPPLY CONTROLLER I ESA STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Fig 1 Typical Wiring Schematics L1 L1 L2 L3 gG HBC FUSES 9G HBC FUSES ENABLE CONTACT 115V 230V SUPPLY OVERTEMPERATURE CONTACTOR NEUTRAL NEUTRAL NEUTRAL
16. haust air then passes behind these components Thyristor stacks should not be mounted one above the other as this will significantly derate the upper unit which for rating purposes will be operating in an ambient equal to the exhaust air temperature of the lower unit Heat from the thyristors together with that dissipated by the semiconductor fuses will also raise the temperature of the busbars to which outgoing cables are connected and high temperature cables should be used The cross section of the cables and their ventilation will influence the temperature of the connection studs and the guide below shows recommended minimum cross sections Consideration must be given to fault conditions In particular a short circuited thyristor could result in loss of control of the load current If this could cause a dangerous temperature to arise in the controlled load then an independent means of monitoring and switching off the current must be provided This could take the form of an independent over temperature policeman controlling a contactor or under voltage release on a circuit breaker fitted in the main supply lines This is a requirement of EN 60519 2 Safety in electroheat installations part 2 Particular requirements for resistance heating equipment para 13 3 This standard requires independent protection of electronic controllers and frequently operated contactors Provision for independent isolation of the power circuits must be provided RECOMM
17. in heating applications A typical application example is in high temperature furnaces with low resistance graphite heating elements These stacks switch on near the peak of the voltage waveform thus minimising transient flux and transformer inrush without recourse to phase angle operation This technique enables the control of a 3 phase transformer load by switching only two lines and causes the minimum possible line disturbance waveform distortion and radio frequency emissions Special drive techniques ensure the minimum possible rfi associated with zero crossing commutation of the thyristors enabling the units to be used with confidence in emc compliant systems The driver control circuit is microprocessor controlled and accepts either analogue 1 5V 4 20mA or logic input signals A separate enable input is provided which can be used in conjunction with system interlocks current overload monitor etc A logic output is provided for synchronising other thyristors if required Semiconductor fuses and power supplies are electronically monitored and an alarm relay is provided for system integration These units do not have a current limit facility and are not suitable for use with loads which have a low cold resistance requiring current limiting RATING PLATE INFORMATION The rating plate carries the following information The rated voltage of the main load supply The rated current The correct semiconductor fuse type The rated driver card sup
18. logic input control signal Maximum signal input 30V lt 2V stack is off gt 3V stack is on Use terminal 1 4 for the OV return Note that the stack has minimum on and off timers of 1 second which prevent unduly rapid cycling 1 6 5V An output for use with a 10k ohm potentiometer for manual control of the stack 1 7 Logic Output An output which is synchronised to the switching on of the load current and may be used in conjunction with the logic input of a second stack to synchronise firing See figure 2 Use terminal 1 8 for the OV return 1 8 OV 2 1 Alarm Volt free relay contact together with terminals 2 2 and 2 3 The alarm contacts are rated at 250V AC 30V DC 1A The contacts are unsuppressed Circuits connected to the alarm relay should be protected with a maximum 5A fuse 2 2 Open in Alarm 2 3 Closed in Alarm 2 5 Supply L Driver circuit supply connection The supply voltage is either 115V or 230V AC 50 60Hz as specified in the stack part number and on the rating plate The supply wiring should be protected with a maximum 5A anti surge fuse The supply need not be phase related to the main terminal supply 24 Supply Driver circuit supply neutral return COMMISSIONING ACCESS TO THE DRIVER CARD Access to the driver card is required if the DIL switch settings need changing or to check the driver supply fuse or voltage setting CALEDON CONTROLS LTD Manual Issue Number R1 STA SERIES THYRISTOR STACKS FOR
19. ng parallel to high current or switching circuits as far CALEDON CONTROLS LTD Manual Issue Number R1 STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Page 7 as is reasonably practical If signals are sourced from outside the panel we recommend that screened cable be used outside the panel and the screen earthed at the point of entry to the panel This is most conveniently undertaken using special glands but if pigtails are used these should be earthed to the metalwork as directly as possible If screened cable is used between the entry to the panel and the stack then the screen should be earthed to the metalwork near the stack Incorrect earthing of screened cables can result in worse performance than using non screened cables Terminal Description Application and Wiring Details No 1 1 Enable Signal This terminal must be linked to terminal 1 2 to enable the stack to supply current to the load The link may be performed by a volt free relay contact or an npn open collector pull down and used as a system interlock Loss of this enable signal can be set to cause an alarm see DIL switch settings 1 2 OV 1 3 Control Input This terminal accepts an analogue control signal 1 5V or 2 10V depending on the DIL switch setting Use terminal 1 4 for the OV return A 4 20mA signal may be connected if a 250 ohm burden resistor is connected across the two terminals set DIL switch to 1 5V 1 4 OV 1 5 Logic Input This terminal accepts a
20. ply voltage The stack type number as defined by the following table Controlled Current Voltage Fan and Options Lines Rating Rating Driver Supply 101 Single phase operation 203 2 line control 3 phase 80A 125A 160A 200A 315A 400A 600A 250V 440V 480V 660V 115 230V Fan and driver supply AC 50 60Hz BUS Lid cut outs suitable for busbar connections otherwise rounded slots are provided for cables CALEDON CONTROLS LTD Manual Issue Number R1 STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Page 3 SAFETY INFORMATION Thyristor stacks must never be used as a means of supply isolation as even in the off state lethal leakage currents will flow An independent means of isolation complying with local standards must always be fitted The clear polycarbonate cover provides protection against accidental contact with live parts and must never be removed unless the main supply has been isolated elsewhere Busbars and circuitry on the printed circuit boards under this cover carry the full line voltage The LED indicators must not be taken to indicate that the supply is isolated In the event that the driver supply is switched off or the driver supply fuse is blown the LEDs will not be lit but the main line supply may still be live The lid on the driver box must not be removed unless the driver supply is isolated TABLE OF FUSE TYPES Checking or changing of any fuse must not be attempted unles
21. ratings are co ordinated with standard HBC fuse values and the supply cables should be protected with gG fuses or circuit breakers rated the same as or lower current than the stack All the stacks with fan cooling also incorporate automatically resetting thermal cut outs which monitor the heatsink temperature and ensure that they do not rise to an unsafe temperature The stacks are rated for a maximum ambient operating temperature of 50 C This applies to the ambient air temperature entering the heatsinks at the base of the stack The design of an installation must however take into account the ratings of cables and other switchgear within the cabinet Elevated temperatures also shorten the life of some electronic components notably electrolytic capacitors which dry out A major cause of elevated temperatures in a cabinet containing thyristor stacks is the power dissipated by the thyristor devices which may be approximated in watts as 1 5 to 2 x RMS current x Number of controlled lines The exhaust air temperature from the stack will be higher than ambient by up to 20 C It is not good practice to mount other items of control gear directly in the exhaust airflow In particular the current carrying capability of fuses or circuit breakers will be significantly reduced if this is done A tidy solution is to mount circuit breakers or fuses supplying the stack on a sub chassis mounted forward from the main chassis on which the stack is mounted The ex
22. s both main and driver supplies are isolated To do so is extremely dangerous and may also cause damage to the stack The following semiconductor fuses are used The type numbers indicated are supplied by Bussman The quantity where indicated is per phase Current Rating Fuse Type BS 88 DIN 43653 size 00 80A 110EET 125A 160EET 160A 225 200 315 170 2619 315 2 225 1x 170 2671 400 2 315 600 4x315FM or 2 170M2671 The following fuses are used to protect the control circuits Supply transformer primary fitted on pcb in driver box 115V supply 5 x 20mm 500mA type T 230V supply 5 20mm 250mA type High Voltage isolation tx primary fitted on high voltage board 4off 5 20mm 800mA type COMPLIANCE WITH STANDARDS Low Voltage Directive The stacks are designed to meet the requirements of international standards and are CE marked in compliance with the European Low Voltage Directive The following standards have been applied in whole or in part in the design of these units EN 60947 1 EN61010 1 pr EN50178 Electromagnetic Compatibility The control circuits of the unit meet or exceed the requirements of EN 50 082 part 2 and EN 50 081 part 2 immunity and emissions for industrial environment The thyristor drive circuitry is designed to minimise conducted emissions associated with the load current and additional filtering will not normally be necessary Application notes provide informa
23. suitable turn down ie with a 20 second cycle period the minimum power other than off is 1 20th of full power The switch on and off is controlled via an interrupt on the microprocessor to enable rapid response Thus for example 3 single phase stacks could be used to control an open delta load comprising 3 single phase transformers An analogue control signal could be fed to the master stack and the logic output of that stack fed to the logic input of the other two stacks Each stack would then switch on and off at the correct point in the cycle minimising transformer inrush and maintaining a balanced load LINE SYNCHRONISATION Correct line synchronisation is imperative if transformer inrush current is to be avoided To this end the line voltage signal is passed through an active filter network before being passed to the microprocessor and then a number of strategies are employed by the phase lock algorithm in the presence of noise If the demand signal is off no action is taken If the demand signal is switched from off to on while line noise is present switch on may be delayed for a few cycles until a reliable signal is obtained or if a reliable signal is not obtained phase lock is signalled as lost and the stack is disabled until it is regained If the demand signal is on and noise is detected but there is no requirement to switch off no action is taken If the demand signal is switched from on to off while line noise is present
24. the current on load 1 may be ramped up in phase angle mode This is because for correct operation the point of switch off of the current must also be controlled If the switch off is not controlled an inrush may occur even when the switch on point is correct To prevent such an inrush from potentially blowing a fuse the controller monitors the manner in which the current was last switched off If this was not done synchronously for example because the power failed or the operator threw the main switch while current was being drawn then the controller will ramp the thyristors on line 1 in phase angle mode on the first switch on A similar action is taken if the phase rotation or the supply frequency have changed The status when the driver supply is removed is stored in EEPROM To minimise the number of times this occurs during normal operation power should never be removed from the controller Main load or driver power unless the current demand is zero If the stack is to be transferred from use with one transformer to another then it is important that when the transformer is first fired up the stack should operate in phase angle mode to reset any residual magnetism To ensure this the stack may first be powered without the transformer being connected and a control signal applied so that the stack is demanding load current While load current is being demanded switch off the power to the stack CALEDON CONTROLS LTD Manual Issue Number R1 S
25. tion on system design for compatibility To ensure that the noise limiting characteristics of the drive circuitry operate correctly in 3 phase systems the load currents must be reasonably balanced within 15 CALEDON CONTROLS LTD Manual Issue Number R1 STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS SPECIFICATIONS ENVIRONMENTAL Ambient Operating Temperature Storage Temperature Relative Humidity Pollution IEC 664 Elevation ELECTRICAL Rated Supply Voltage Load Rated Current Supply Frequency Rated Impulse Withstand Voltage IEC 664 CONTROL SIGNAL INPUTS AND OUTPUTS Analogue input control signal Logic input control signal Logic output signal Enable input 5V supply output Alarm relay output Page 4 0 50 C 25 to 70 C 0 95 non condensing Temporary condensation may occur but not normally while equipment is operating Derate current rating 1 per 100 metres above 200 metres 250V 440V 480V 660V 10 50 As ordered Rated current is specified at 50 ambient 50Hz 60Hz 8 4KV 1 5V 4 20mA in conjunction with external 250 ohm burden resistor Max 30V input Switching threshold gt 3V on lt 2V off 12V approx signal synchronised to stack turn on Contact closure npn pull down or link required to enable the stack Available to power 10K potentiometer for manual control Volt free changeover contacts rated 250V AC 1A operate on loss of power load supply
26. ulation is not compromised by the installation where cables associated with different circuits are grouped together the insulation of the cables must be suitable for the voltage of the highest voltage circuit in the group Power Cables Use the guide above in determining cable type and cross section Cables should be connected using crimp terminals Up to 125A stacks have 8mm studs 160A to 315A have 10mm studs 400A upwards have 12mm studs A protective earth connection of suitable cross section should be made to the 8mm stud at the top RHS of the unit Line 3 Connection STA 203 units for 3 phase load The stack controls only 2 of the 3 lines A connection for the third line is however required for line synchronisation and connection of integral emc suppression capacitors This third line is connected to the terminal marked 3 adjacent to the load 1 terminal The connector is of the screwless cage clamp type and will accept cables from 0 75mm to 4mm cross section To insert the cable insert a small screwdriver in the hole in the terminal adjacent to the cable entry and depress while inserting the cable Release the screwdriver Note that the screwdriver is in electrical contact with the conductor and should not be inserted while the circuit is live The cable connected to this terminal should be fused with a 5A fuse Although the main terminals are labelled 1 Line 2 the actual phase rotation is not important as th
27. unctioning correctly the contactor circuit breaker does not have to break the main load current and more importantly in transformer load applications switch off occurs synchronously under control of the thyristor controller CALEDON CONTROLS LTD Manual Issue Number R1 STA SERIES THYRISTOR STACKS FOR TRANSFORMER COUPLED LOADS Page 11 If desired the alarm relay may also be wired to switch off the auxilliary supply to the stack driver circuit This will mean that in over temperature the stack fans are also switched off The AMOT 130 may be used as a simple temperature controller in the event of failure of the main controller or as a night setback controller by turning the setpoint down and placing the control signal in manual By setting the manual power level to an appropriate value the switching required by the over temperature action is reduced to a minimum and smooth temperature control is achieved FAULT FINDING Before attempting to rectify a fault on the unit it is most important that the information in the section headed SAFETY INFORMATION should be read and acted upon The following is a guide to first line fault finding Fault Symptom Possible Cause None of the Driver LEDs light Driver card power supply not present Fans will not be running Fuse on driver card supply fuse has blown Fans will be running Temperature LED is not lit A heatsink has overheated Is the ambient temperature very high Are the

Download Pdf Manuals

image

Related Search

Related Contents

アーマープラスSG テッカマンレイピア 取扱説明書 540.5 KB  White Rodgers 1F80-0471 Thermostat User Manual  LES SOLS NATURELS QUI RESTENT BEAUX  DIVAtech F 32 - Repuestos Ferroli Alicante  電源制御ユニッ ト ST PWーー 5 2 E 取扱説明書  télécharger - Eduscol - Ministère de l`éducation nationale  EnviroMon User's Guide  X-treme Clean - Charterhouse Turf Machinery  Da-Lite ViewShare Tensioned Advantage Electrol 110"  