Minisensor User guide
Contents
1. Dimension mm Installation Clip on assembl Surface mounting GAmm Data subject to change without notice For more information visit our website www helvar com 3 Connection e Maximum connection Up to 4 ballasts per Minisensor Combinations are found from the following table Example connection Ch A 2pcs Ch B 1pcs Channel BLACK N Lead color Ye pl Gr Rad bert nem gt SWITCH CONTROL optional RED O DIGIDIM 1 SWITCH CONTROL k O y 2 optional j EL si S No of ballasts Reception areas Presence detector PIR Orientation PIR 3 0m 4 5m Constant light sensor Infrared IR control 100 gt lt N D 63 T 3 0m 7 0m 4 Data subject to change without notice For more information visit our website www helvar com Key press Minisensor All given key combinations are reset supposed to be pressed for 10 seconds Page 6 Constant light Page 8 PIR Page 9 Quick functionality guide functionality guide Last level Page 11 Change Enable Disable level Enable Disable Delay time Enable Disable 3 amp 4 NG V V V 0 1 amp 1 V 0 1 amp 2 0 1 amp 3 Selects long Alters short 0 1 a
2. Minisensor Table of contents of contents Introduction nana annaen 3 Dimensions 3 lastalla M reren 3 Connection eeir 4 Reception areas nen 4 Quick functionality guide 5 Out of box operation eeeee 6 Initial configuration Minisensor reset 6 Infrared IR control 7 Constant light channel A 8 Presence detector PIR 9 PIR delay time setting last level function 11 Recommendations 12 Fault finding 2s44 nnen 12 Technical spesifications 13 Appendixes Recommended programming sequence A Programming examples B 2 Data subject to change without notice For more information visit our website www helvar com Introduction The Helvar Minisensor is a two channel luminaire mounted component containing three integrated sensors t Presence detector PIR f ja J Constant light sensor Infrared IR receiver The two separate channels A amp B enable scene setting amp lighting control The constant light sensor only adjusts the output from channel A where as presence detection amp infrared control affect both channels The Minisensor is only compatible with the Helvar EL si electronic DALI ballast range Sensor set up amp programming is achieved using the Helvar Digidim infrared remote control
3. lower the light level of channel A to the desired level e Simultaneously press amp hold 2 amp 4 or W to raise or lower the light level of channel B to the desired level e Press amp hold for 10 seconds the desired remote control scene button 1 2 3 or 4 where you would like the scene to be stored The operation is confirmed by flashing the lamps Repeat the above for up to 4 scenes buttons 1 to 4 Notes e Scene is a combination of light levels of channel A and B that can be recalled by the press of a button e Storing scenes on buttons 1 to 4 will replace any previously stored preset light levels Data subject to change without notice For more information visit our website www helvar com 7 Constant light channel A Enable constant light function only possible through initial configuration minisensor reset e Simultaneously press amp hold 3 amp 4 for 10 seconds e The operation is confirmed by flashing the lamps Note This also resets all scenes Disable constant light function Change and store constant light level Ensure that the constant light function is enabled as above e Simultaneously press amp hold 0 1 amp 1 for 10 seconds e The operation is confirmed by flashing the lamps Select the overall desired light level See Infrared IR control section Simultaneously press amp hold
4. subject to change without notice For more information visit our website www helvar com Infrared IR control IR control A 0 1 ON OFF key Toggles the lighting between 100 and OFF CG B 1 2 3 or A key e Recall of stored scene or preset level for the selected key C A key B e Single push Switches channel A amp B on to minimum level if lights were off Steps up channel A amp B by one step if lights were on A Press amp hold Dims up channel A amp B from minimum if lights were off Dims up channel A amp B from last level if lights were on D D V key e Single push Steps down channel A amp B by one step if lights were on e Press amp hold Dims down channel A amp B from last level if lights were on If Constant light has been enabled and programmed the Minisensor will set the lights to the Constant light level after a short period of time Modify and store preset light levels Use the remote control 4 or W keys to adjust the lighting of channel A amp B to the desired level e Press amp hold for 10 seconds the desired remote control scene button 1 2 3 or 4 where you would like the preset level to be stored The operation is confirmed by flashing the lamps Modify and store scenes channel A amp B e Simultaneously press amp hold 1 amp 4 or W to raise or
5. 0 1 for 10 seconds The operation is confirmed by flashing the lamps Notes Only the light level of channel A will vary in order to try to keep the stored overall constant light level Constant light will not switch lighting on or off The stored constant light level is not affected by the PIR e The stored constant light level is not affected by switching the lights off The stored constant light level is equal to the PIR ON level 8 Data subject to change without notice For more information visit our website www helvar com Presence detector PIR detector PIR Enable PIR only possible through initial configuration minisensor reset Simultaneously press amp hold 3 amp 4 for 10 seconds e The operation is confirmed by flashing the lamps Note This also resets all scenes Disable PIR Enable Manual ON Automatic OFF feature with 20min delay time Simultaneously press amp hold 0 1 amp 2 for 10 seconds The operation is confirmed by flashing the lamps e Simultaneously press amp hold 0 1 amp 2 for 10 seconds e Simultaneously press amp hold 0 1 amp 4 for 10 seconds Note This must be done before setting the PIR delay time If you require a different delay time please see PIR delay 10 second time settings instructions Simultaneously press amp hold 0 1 amp 2 for 10 se
6. conds Simultaneously press amp hold 0 1 amp 3 for 10 seconds Note This must be done before setting the PIR delay time If you reguire a different delay time please see PIR delay 10 second time settings instructions Disable Manual ON Automatic OFF feature only possible through initial configuration minisensor reset Simultaneously press amp hold 3 amp 4 for 10 seconds The operation is confirmed by flashing the lamps Note This also resets all scenes 10 second Notes Manual ON Automatic OFF feature PIR will not switch the lights on when movement is detected but will switch them off if no movement is detected e Regardless of other light level commands e g changes in the constant light level an enabled PIR will switch the lights to the PIR OFF scene if no movement is detected within its programmed delay time Data subject to change without notice For more information visit our website www helvar com 9 Presence detector PIR detector PIR Set PIR ON scene Select the overall desired light level See Infrared IR control section 10 second e e Simultaneously press amp hold 0 1 for 10 seconds e The operation is confirmed by flashing the lamps Note This also sets the Constant light level Select the overall desired light level See Infrared IR control section 10 second e e Simultaneously
7. gs installed 25 IR address group See notes 85 e Constant light sensor enabled Constant light level must be programmed See Constant light section amp e Constant light level is measured and updated every 5 seconds d PIR enabled e No movement detected delays After 20 minutes switch to minimum light level After an additional 20 seconds switch lights off IR receiver enabled e Last level recall function disabled Basic lighting scenes stored 10 seconds e 100 scene 1 75 scene 2 e 50 scene 3 25 scene 4 100 PIR ON light level scene 1 PIR LOW Light Level scene e 0 PIR OFF light level scene Notes Set the rotary switch of the remote control in battery compartment to an address group 0 F All Minisensors will respond to Digidim remote controls set to address O or D If more than one remote control will be used to control different Minisensors in the same area the remote controls must be addressed to different groups 1 9 A B C E or F The Minisensor will then respond to its corresponding remote control only 3 e Always point the remote control directly at the Minisensor to be N configured EN Take care that no other minisensor is in the IR reception area unless they are supposed to belong to the same address e Point at the minisensor to be addressed and press 3 amp 4 for 10 seconds or until lights flash 6 Data
8. mp 4 Selects short Alters long or W 0 1 0 1 amp A 0 1 amp Y Key press combinations Manual on automatic off see above Enable Disable Delay times V E once delay 20min E twice delay 30min E thrice delay 45min E four times delay 60min D once delay 20s D twice delay 1min D thrice delay 5min D four times delay 10min Practical configuration example enclosed in appendix B example 2 Data subject to change without notice For more information visit our website www helvar com 5 Qut of box operation Upon first application of power the Minisensor operates according to the programmed memory of the EL si ballast If the ballast has no program then the IR buttons AT e and 0 1 On Off will be active Channel control is also active This allows the control of channels A amp B please see section IR control for more information To program default scenes 1 4 and to activate further features please see the Initial configuration section for more information Use the Helvar Digidim infrared remote control for configuration Initial configuration Minisensor reset default settings Simultaneously press amp hold 3 amp 4 for 10 seconds to install initial settings The operation is confirmed by flashing the lamps Settin
9. or cannot be directly connected to the DALI interface Fault e No Operation No response to scene buttons on the remote control Lights do not dim Constant light does not operate e No response to IR Lights do not switch on from PIR Lights do not switch off from PIR e PIR switches light off very quickly Fault finding finding Possible causes Incorrect connection No power applied to the ballast e Preset levels are not installed carry out reset Scenes programmed to off e Batteries flat e Flat weak batteries in IR No scenes or levels preset e Sensor is positioned in line with direct lighting natural or artificial e Constant light function is disabled Check batteries in IR e Ensure correct addressing of remote control unit e PIR Manual ON Automatic OFF is enabled e PIR is disabled e PIR is disabled e PIR OFF scene is not programmed to off Minisensor is in test mode 12 Data subject to change without notice For more information visit our website www helvar com Technical specifications specifications Constant light sensor Reception area 100 Measuring range 50 1000 lux IR receiver Frequency 36kHz Presence detector Detection area 4 5 x 3 0m mounting height 3 0m Electric data Internal communication with Helvar EL si electronic ballast Operation conditions Ambient temperature range 0 C to 50 C St
10. orage temperature range 10 C to 70 C Relative humidity 90 maximum non condensing Conformity amp Standards Safety Only valid if sensor is mounted in the same fitting as the ballasts Safety EN61347 2 11 EN61347 1 EN60598 1 IP rating 44 Isolation 4kV Finish White thermoplastic Protection Single insulation Wire length Max from Minisensor to furthest ballast 15m Note e The Minisensor is not designed for installation outside of a luminaire Data subject to change without notice For more information visit our website www helvar com 13 Recommended programming seguence Appendix A Always start the programming by carrying out the Minisensor Initial configuration Then select Yes or No for each step and follow the instructions on referred pages Initial es Alter levels Yes Set scenes Change PIR delay time Page 7 Page 11 Enable Manual on automatic off Disable Page 9 PIR 9 Page 9 Program Program pp Page 10 Constant light Page 8 light levels levels Disable Constant light 14 Data subject to change without notice For more information visit our website www helvar com Programming examples Appendix B Energy saving lighting with Presence detector and Constant light features Lights will go off in 20 minutes when no movement is detected in
11. press amp hold 0 1 STAT for 10 seconds e The operation is confirmed by flashing the lamps Select the overall desired light level See Infrared IR control section 10 seconds e Notes e Simultaneously press amp hold 0 1 amp W for 10 seconds e The operation is confirmed by flashing the lamps Regardless of other light level commands e g changes in the constant light level an enabled PIR will switch the lights to the PIR OFF scene if no movement is detected within its programmed delay time PIR scenes can be any combination of light levels of channels A amp B 10 Data subject to change without notice For more information visit our website www helvar com PIR delay time setting Last level function Time setting also enables last level functionality e If last level function is enabled and the lights are swiched on from the mains switch the lights will turn on to the level they were at before switch off If the lights were already OFF when the mains was switched off they will remain off after the mains is switched on e Last level function can be turned off by carrying out Initial configuration Minisensor reset To change the PIR delay time please follow the seguence described in the following tables To select short PIR delay times Press and hold keys Delay to low level Delay from low level to OFF Notes are emis 1 OM 83 Tor 10s Tosa OR amp S for 0
12. s imne 20miues ON amp S for 5 minutes 20minus ON amp S for 10 minutes 2050008 To select long PIR delay times Press and hold keys Delay to low level Delay from low level to OFF Tomarstfortos RECH On 89 for 10s ON amp A for 10s 01 amp A Tor 105 Each step of the sequence is confirmed by flashing the lamps If you need to choose a shorter time than already in use you must start the sequence from the beginning Test setting This mode should only be used to test the functionality during installation In test mode the Constant light response time is 20 times quicker than in normal operation and should only be used for demonstration or test purposes Data subject to change without notice For more information visit our website www helvar com 11 1 1 Plan programming carefully to avoid having to unnecessarily reset the Minisensor See appendix A e Ensure that the Minisensor is located out of view of direct light to ensure correct operation of the constant light sensor and IR e Position the Minisensor in a area of combined natural artificial light for best operation of the constant light feature If multiple sensors are installed care should be taken to ensure the sensing areas of the Minisensors do not cross and interfere with each other e Only connect a Helvar Minisensor to the Digidim input of a Helvar EL si ballast The Minisens
13. sly press amp hold 0 1 amp 3 for 10 seconds x x ii Simultaneously press amp hold 0 1 amp 4 for 10 seconds 7 gt SS gt iii Simultaneously press amp hold 0 1 amp 4 for 10 seconds e Data subject to change without notice For more information visit our website www helvar com HELVAR Oy Ab Yritt j ntie 23 FIN 03600 Helsinki Tel 358 9 56541 Fax 358 9 5654 9600 www helvar com Germany Helvar Merca GmbH Carl Zeiss Strasse 12 D 63322 R dermark Germany Tel 49 6074 92090 Fax 49 6074 920923 United Kingdom Helvar Merca Limited Hawley Mill Hawley Road Dartford Kent DA2 7SY United Kingdom Tel 44 1322 282 258 Fax 44 1322 282 259 F13 102 1D 13 01 05 Italy Helvar Merca S r l Via W Tobagi 26 1 I 20068 Peschiera Borromeo Milan Italy Tel 39 02 55 30 10 33 Fax 39 02 55 30 10 32 Sweden Helvarmerca AB Bultgatan 40B S 44240 KUNG LV Sweden Tel 46 303 246 950 Fax 46 303 588 75 Contact
14. the room Lights will go on if being off when movement is detected Lighting level will remain the same despite the changes in the natural light 1 Reset the minisensor page 6 Press and hold keys 3 amp 4 simultaneously for 10 sec or until the lights flash 2 Change and store the constant light level page 8 i Select the desired overal light level with AT W buttons ii Press key 0 1 for 10 secondsf or until the lights flash to store the light level Ji gt Energy saving lighting with Constant light and Automatic off manual on features Manual switch on only Lights will go off in 30 minutes when no movement is detected in the room Lighting level will remain the same despite the changes in the natural light 1 Reset the minisensor page 6 Press and hold keys 3 amp 4 simultaneously for 10 sec or until the lights flash G BO 2 Change and store the constant light level page 8 i Select the desired overal light level with AT WY buttons ii Press key 0 1 for 10 seconds or until the lights flash to store the light level IE gt 3 Enable Manual ON Automatic OFF feature page 9 i Simultaneously press amp hold 0 1 amp 2 for 10 seconds Aa N ii Simultaneously press amp hold 0 1 amp 4 for 10 seconds a gt o 4 Change the PIR delay time to 30 minutes page 11 i Simultaneou
Download Pdf Manuals
Related Search
Related Contents
HOBBES 256652A cable network tester F p. 3 GB p. 15 D p. 27 NL p. 40 I p. 52 E p. 64 P p. 76 第84期定時株主総会招集ご通知 Kingston Technology ValueRAM 8GB DDR3-1600MHz ECC Kat. Nr. 35.1093 Bedienungsanleitung Instruction Manual CLIPS User's Guide 6 Hilti 3476075 Use and Care Manual Copyright © All rights reserved.