Home

USER GUIDE

image

Contents

1. as a cover 2 le Se Fan SEEN 2 i 5 Front of unit Vents bottom view Vents on evaporator cover yA SA A AR GANS NSE Front of unit 1 Airflow and Product Loading 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVIC Interior Shelves REMOVING AND INSTALLING GLASS SHELVES Adjusting Interior Shelves Models equipped with glass shelves have an adjustable mounting system To adjust or simply remove shelves for cleaning follow the instructions below 1 Remove all product from shelf 2 Coming from underneath the shelf lift both the front and rear of the glass 3 Carefully slide shelf out of unit being careful not to scratch the interior liner 4 Installation is the reverse of removal Adjusting Shelf Height Shelf height may be adjusted to accommodate a broad range of product To alter your shelf spacing follow the instructions below 1 Remove the 4 Shelf clips from the shelf clip holes 2 Move shelf clips as a group to the desired shelf height 3 Insert shelf clips into the holes of the desired shelf height Be certain shelf clip is fully seated into shelf clip hole Clip gt x Holes Clips MUST be installed with the ribbed side down Failure to do so may result in shelf or unit damage NOTI
2. SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE e SERVIC Door Swing For models that are installed adjacent to a wall 1 4 6 mm clearance is recommended from wall on hinge side to allow the door to open 90 Allow for additional space for any knobs or pulls installed on the integrated panel frame Units have a zero clearance when installed adjacent to cabinets Wall 1 4 6 mm Sake 0 Door Swing Space Required A For any Knobs or Pulls Door Swing 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE e SERVIC Door Stop 3 Once cover is removed slide hinge pin into hole as shown Pin should slide into place stopping the door at Your U Line unit was shipped to you with the optional 90 90 if the pin does not go into the hole shown hold pin the door less than 90 open and try again Your unit s door s will open 115 straight from the factory If you would like the door stop at 90 follow these instructions NOTICE If your unit is already undercounter it will need to be moved out to access the hinge With the 90 stop pin in place you will not be able to replace the hinge cover 1 Open door approximately 90 4 To fully seat the pin tap it lightly with a hammer 5 Carefully slide your u
3. Warra nty Claims warranty status We also accept the following information to verify warranty status The following information defines the parameters for filing a warranty claim e New Construction Occupancy Documents e Valid serial number needed Closing P e Closing Paperwor e Valid model number needed lig e Final Billing Remodel e Narda or equivalent form or submitted online at Noting all of the following on the warranty claim will be www u line com considered proof of purchase hard copy will not be required e 60 day submittal deadline from date of completed service e Name of the selling Dealer e Only one repair or unit per warranty claim y p P i e Date of purchase installation e Refrigerant should be labeled and included on the labor e Order or Invoice number if available submittal e Description of document reviewed i e store receipt e Door and water level adjustments are covered 30 days i closing paperwork etc from install date Parts and labor claims are paid separately Indicate part numbers and description for parts used in the warranty repair Include the purchase invoice and name of the parts supplier used to procure the parts Serial Number Requirements 14 30911 12 XXXX Year Month A typical serial number is shown above The first two digits of the first segment 14 represents the production year The number between the dashes 12 represents the p
4. 1 Align slots in grille plinth strip base fascia rail with Slide grille p screw heads in base of unit Push grille plinth strip base fascia rails towards the center of the unit and set rails over screw head inth strip base fascia into position Using included 7 64 Allen wrench tighten grille plinth strip base fascia lock screws Th O ADJUSTING GRILLE PLINTH STRIP BASE FASCIA The grille plinth strip base fascia has an automatic vertical plane adjustment and can also be adjusted on its horizontal plane as well To adjust your grille plinth strip base fascia to match your surrounding furniture follow th instructions below Grille Skirt Loosen but do not remove the lock screws on the inside of the grille plinth strip base fascia rails Lock screws are located on the inside of each grille plinth strip base fascia rail The grille plinth strip base fascia can be extended horizontally by pulling out a maximum of 1 1 2 38 mm Do not exceed 1 1 2 38 mm Secure the lock screws after adjusting The grille plinth strip base fascia skirt may be manually adjusted to the height of your floor Simply raise or lower the skirt as needed Grille Plinth Installation 1 USER GUIDE U LINE u line com
5. RE SELECT MODEL 3018R A ULINE b amp o e O Down NOTICE Before altering model selection U Line customer service must be notified Failure to notify customer service will result in voiding of the manufacturer warranty Re Select Model allows the units model information to be modified Changing the units model completely reprograms available zones relay assignments DC output assignments etc To access Re Select Model 1 Press to select Re Select Model 2 Press To alter model setting 3 Press to select Model and press Model will begin to flash 4 Press B or amp to scroll through each available model 5 Press to confirm To exit Re Select Model press E to select Return to Menu and press to confirm Control Operation Service 7 USER GUIDE LINE u line com U SAF ETY e INSTALLATION amp INT EGRATION OP Fan Delay Up Select RETURN TO MENU FAN DELAY FAN DELAY ON 1 FAN DELAY OFF 2 S 6 U LINE H Down The Fan Delay menu option allows the modification of fan run times during and after a cooling cycle In order to allow time for the evaporator to properly cool the evaporator fan is delayed from starting with the cooling cycle for a given amount of time In order to remove as much warmth as possible from the cabinet the evaporator fan will continue to ru
6. u line com WELCOME TO U LINE Congratulations on your U Line purchase Your product comes from a company with over five decades and three generations of premium modular ice making refrigeration and wine preservation experience U Line continues to be the American leader delivering versatility and flexibility for multiple applications including residential light commercial outdoor and marine use U Line s complete global product collection includes modular Wine Cellars Drinks Cabinets Clear Ice Machines Glass amp Solid Door Refrigerators Drawer Models and Freezers U Line has captivated those with an appreciation for the finer things with exceptional functionality style inspired innovations and attention to even the smallest details We are Known and respected for our unwavering dedication to product design quality and selection U Line is headquartered in Milwaukee Wisconsin with a west coast office located in Laguna Beach California and European support in Dublin Ireland U Line has shipped product to five continents for over two decades and is proud to have the opportunity to ship to you PRODUCT INFORMATION Looking for additional information on your product User Guides Quick Reference Guides CAD Drawings Compliance Documentation and Product Warranty information are all available for reference and download at u line com under Documentation PROPERTY DAMAGE INJURY CONCERNS In the unlikely event property damage or
7. Beverage Drinks 38 3 34 65 1 18 Market Fresh 38 3 34 40 1 4 Root 50 10 45 55 7 12 Pantry 42 5 34 70 1 21 Many food types have an optimum storage temperature Storing your food properly will help maintain its freshness and flavor The Food Storage Chart contains food types and their respective optimum storage temperatures Food Storage Chart Mode Food Types Deli Meats Fish Cheeses Dairy Butter Garlic Oils Nuts Condiments Market Fresh Fruits Vegetables Berries Lettuce Pantry Dry Goods Breads Baking Items Spices Seasonings Root Root Vegetables Potatoes Onions Lemon Lime Melon Peppers Beans Cucumber Cut Vegetables QUICK CHILL Quick chill is designed to quickly pull warm beverages and foods down to optimum storage temperature It is important to only initiate quick chill modes when the Refrigerator or Wine Captain have been fully loaded with warm product Failure to follow this notice could result in food or beverages that are cooled to a point below optimum or frozen The following chart lists modes which include the quick chill feature and the time which quick chill will run Mode Run Time Deli 5 Hours Beverage Drinks 4 Hours arket Fresh 4 Hours Root 1 Hour Pantry 4 Hours To initiate quick chill 1 Press to select the desired mode setting 2 Press until the temperature set point reads
8. EGRATION OP If you think your U Line product is malfunctioning read the CONTROL OPERATION section to clearly understand the function of the control If the problem persists read the NORMAL OPERATING SOUNDS and TROUBLESHOOTING GUIDE sections below to help you quickly identify common problems and possible causes and remedies Most often this will resolve the problem without the need to call for service IF SERVICE IS REQUIRED If you do not understand a troubleshooting remedy or your product needs service contact U Line Corporation directly at 1 800 779 2547 When you call you will need your product Model and Serial Numbers This information appears on the Model and Serial number plate located on the interior of your product or can be accessed through Help in the Customer Menu NORMAL OPERATING SOUNDS All models incorporate rigid foam insulated cabinets to provide high thermal efficiency and maximum sound reduction for its internal working components Despite this technology your model may make sounds that are unfamiliar Normal operating sounds may be more noticeable because of the unit s environment Hard surfaces such as cabinets wood vinyl or tiled floors and paneled walls have a tendency to reflect normal appliance operating noises Listed below are common refrigeration components with a brief description of the normal operating sounds they make NOTE Your product may not contain all the
9. I I 0 For ease of installation the anti tip bracket is pre installed in the top mount position 1 Completely slide the unit into its position in the cabinet Be certain unit height is properly adjusted See GENERAL INSTALLATION 2 Open door completely Make certain door clears surrounding cabinetry ERATING INSTRUCTIONS MAINT NANC 2S RVIC SIDE MOUNT Left Hinged Cabinet Right Hinged Cabinet Side mount position is used when you are unable to mount the bracket to the underside of your countertop 1 Remove the pre installed anti tip bracket from the top mount position and align the bracket to the hinge side of the unit as shown above 2 Reinstall the 2 8x5 8 screws into the plate using a 2 Phillips head screwdriver 3 Completely slide the unit into its position in the cabinet Be certain unit height is properly adjusted See GENERAL INSTALLATION 4 Open door completely Make certain door clears surrounding cabinetry Using a 3 32 2 50 mm drill bit drill 3 pilot holes 5 8 16 mm deep into bottom of counter top Use the anti tip bracket as a template Install 3 8x5 8 screws into the plate using a 2 Phillips head screwdriver Using a 3 32 2 50 mm dr
10. Inspect wire harness from main control board for pinch points or damage Repair split or pinched cabling Amb Thrm Short nspect thermistor cable for pinch points or damage Replace if necessary Inspect wire harness from main control board for pinch points or damage Repair split or pinched cabling Temp Hi 6H f excessive frost is also noted nspect evaporator fan for proper Inspect refrigeration system inspect door and door gasket for operation Reference the System Diagnosis proper seal and alignment Guide Temp Hi 12H f excessive frost is also noted nspect evaporator fan for proper Inspect refrigeration system relay operation inspect door and door gasket for operation Reference the System Diagnosis proper seal and alignment Guide Temp Lo 6H nspect main control for proper nspect refrigeration system relay operation Reference the System Diagnosis Guide Temp Lo 12H nspect main control for proper nspect refrigeration system Reference the System Diagnosis Guide Door Open 5M Verify door closes properly nspect cable arm verify presence of magnet verify proper operation and movement or arm Inspect reed switch wiring Troubleshooting Extended 3 USER GUIDE U LINE u line com SAFETY INSTALLATI
11. MAINTENANCE e SERVIC This appliance is intended to be used in household and similar applications such as e Staff kitchen areas in shops office and other working environments e Farm houses and by clients in hotels motels and other residential type environments e Bed and breakfast type environments e Catering and similar non retail applications Safety and Warning 2 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC Disposal and Recycling A DANGER RISK OF CHILD ENTRAPMENT Before you throw away your old refrigerator or freezer take off the doors and leave shelves in place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulations regarding the disposal and recycling of refrigeration appliances and follow these steps completely 1 Remove all consumable contents from the unit 2 Unplug the electrical cord from its socket 3 Remove the door s drawer s Disposal and Recycling 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE SERVIC Environmental Requirements This model is intended for indoor interior applications only and is not to be used in installations that a
12. OFF FAN DELAY EXIT SCROLL DOWN TO EXIT TOUCH AND RELEASE TO EXIT SERVICE MODE HONOM MODE od EXIT Control Operation Service 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INT SERVICE MENU In addition to a feature rich customer menu the 3000 series also offers a service menu with the ability to fine tune and monitor unit operation To initiate the Service menu hold both amp and for 5 seconds Actual Temps Up EGRATION e OPERATING INSTRUCTIONS MAINTENANC e SERVICE The All Errors option keeps record of any system errors When an error occurs it is recorded to all errors The number next to the error indicates the number of recorded instances Errors in the log may not be currently active The error log memory is non volatile and is persistent should power be lost and restored to the unit See below for a list of logged errors and their respective descriptions ID Description Solution No Unit lost Unplug the communication cable Comm communication to from the user interface Check the display the black to red conductors Select ooking for 5 VDC If voltage is present replace the user 4 gt RETURN TO MENU ACTUAL TEMPS ZONE 2 C U LINE f amp EVAP C BGA interface If no voltage is present check for 5 VDC at the main board where the communication cable plugs onto Down The Ac
13. Quick The quick chill feature will then begin for the period of time dictated by the mode type To cancel quick chill simply select a set point other then quick Control Operation 2 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC Interior Lighting Your U Line 3000 Series unit uses a state of the art LED lighting system The 3036 model dual zone s lighting can be independently controlled or set as a group Up B yea LIGHTING eel U LINE Lonwmboor mo J 3 polie Down U Select Lighting 1 To begin press to enter the lighting menu 2 Press B or to cycle through each available brightness setting Low Medium or High 3 Press to cycle through each available timer setting Selections include On With Door On 3 Hours On 6 Hours or On 24 Hours 4 To exit press or simply wait for the menu to time out Error Notification The 3000 model series continuously monitors a series of inputs and parameters to ensure proper and efficient operation of your unit Should the system detect a fault an error notification will be displayed on the user interface See below for a list of errors NOTE Singe zone models will not use L left or R right zone indicators in error notification ID Description Solution No Comm Unit lost Disconnect and
14. This would put excessive stress on the hinge system Alignment and Adjustment Procedure 1 Open door and remove gasket near the hinges 2 Using a T 25 Torx Bit loosen each pair of Torx head screws on both the upper and lower hinge plates 3 Square and align door as necessary 4 Tighten Torx head screws on hinge 5 Reinstall gasket into the channel starting at the corner Door Adjustments 1 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINT 3 Using T 25 Torx bit loosen screw 1 and remove screw 2 on top and bottom hinge Slide and remove the door from unit Completely remove screw 1 on top and bottom 4 Remove caps from screw heads on opposite side 2 on top and 2 on bottom Using 2 Phillips bit remove the 4 underlying screws Reinstall the screws and caps on the opposite side 5 Partially install screw 1 in the outer most holes on top and bottom Rotate door 180 align hinge over screw 1 and slide seat into position Reinstall screw 2 on top and bottom Tighten both screws and install hinge cover Align and adjust the door Align and adjust the door see DOOR ALIGNMENT AND ADJUSTMENT NANCE e SERVIC Door Adjustments 2 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAIN First Use All U Line controls
15. When ordering a non warranty part you will need an open account and tax exemption on file at U Line Another option would be to visit www u line com to locate an authorized parts distributor in your area Ordering Replacement Parts 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE System Diagnosis Guide REFRIGERATION SYSTEM DIAGNOSIS GUIDE System Suction Suction Compressor Condenser Capillary Evaporator Wattage Condition Pressure Line Discharge Tube Normal Normal Slightly below Very hot Very hot Warm Cold Normal room temperature Overcharge Higher than Very cold may Slightly warm Hot to warm Cool Cold Higher than normal frost heavily to hot normal Undercharge Lower than Warm near Hot Warm Warm Extremely cold Lower than normal room near inlet normal temperature Outlet below room temperature Partial Somewhat Warm near Very hot Top passes Room Extremely cold Lower than Restriction lower than room warm Lower temperature near inlet normal normal vacuum temperature passes cool cool or Outlet below near room colder room temperature temperature due to liquid backing up Complete In deep Room Room Room Room No refrigeration Lower than Restriction vacuum temperature temperature temperature temperature normal cool cool cool cool No Gas 0 PSIG to 25 Room Cool to hot Room R
16. become blurred Rust not cleaned up promptly can penetrate the surface of the stainless steel and complete removal of the rust may not be possible ERATING INSTRUCTIONS MAINTENANCE e SERVIC Integrated Models To clean integrated panels use household cleaner per the cabinet manufacturer s recommendation INTERIOR CLEANING Disconnect power to the unit Clean the interior and all removed components using a mild nonabrasive detergent and warm water solution applied with a soft sponge or non abrasive cloth Rinse the interior using a soft sponge and clean water Do not use any solvent based or abrasive cleaners These types of cleaners may transfer taste to the interior products and damage or discolor the lining DEFROSTING Under normal conditions this unit does not require manual defrosting Minor frost on the rear wall or visible through the evaporator plate vents is normal and will melt during each off cycle If there is excessive build up of 1 4 6 mm or more manually defrost the unit Ensure the door is closing and sealing properly High ambient temperature and excessive humidity can also produce frost DO NOT use an ice pick or other sharp instrument to help speed up defrosting These instruments can puncture the inner lining or damage the cooling unit DO NOT use any type of heater to defrost Using a heater to speed up defrosting can cause personal injury and damage to the inner lini
17. communication to reconnect power to the display unit Contact Customer Care if persistent L R Zone T Left or right zone Contact Customer Open thermistor circuit Care open Amb Thrm Open Ambient thermistor Contact Customer circuit open Care L R Zone T Left or right zone Contact Customer Short thermistor circuit Care shorted Amb Thrm Short Ambient thermistor Contact Customer circuit shorted Care L R Temp Hi Left or right zone Verify door is closed 6H temperature 10 and sealing Contact over set point for Customer Care if over 6 hours persistent L R Temp Hi Left or right zone Verify door is closed 12H temperature 10 and sealing Contact over set point for Customer Care if over 12 hours persistent L R Temp Lo Left or right zone Verify door is closed 6H temperature and sealing Contact 10 under set point Customer Care if for over 6 hours persistent L R Temp Lo Left or right zone Verify door is closed 12H temperature and sealing Contact 10 under set point Customer Care if for over 12 hours persistent L R Door Left or right door Verify door is closed Open 5M switch open for and sealing Contact more then 5 Customer Care if minutes persistent Control Operation 3 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGR
18. i operation Sealed system issue all available relays are displayed only a portion are used Temp Hi Zone temperature Is condenser coil clean Is 12H 10 C over set condenser fan operating Check MPENI point for over 12 zone thermistor for correct ID Description Solution hours resistance Verify thermistor Mull Mullion Heater Not Used connections are clean and intact Check zone valve Cond Condenser Fan Not Used operation Sealed system issue Def Defrost Valve Not Used Temp Lo Zone temperature Verify thermistor connections 6H 10 C under set are clean and dry Verify Pan Pan neaten Not Sea point for over 6 thermistor resistance Verify Comp Compressor Used hours correct operation of zone valve Temp Lo Zone temperature Verify thermistor connections 12H 10 C under set are clean and dry Verify i i i point for over 12 thermistor resistance Verify NOTE The Cond Condenser Fan will switch state with hours correct operation of zone valve the compressor relay however the condenser fan is Door Door switch open Check door switch magnet reed actually powered through a DC output Condenser fan Open 5M for more then 5 switch alignment when door is in N T i lt minutes closed position Check reed status can be viewed through the Output service menu switch connection at the harness option and the main board To access Relay Status To access All Errors follow the steps below 1 Use to select R
19. A DANGER Danger means that failure to follow this safety statement will result in severe personal injury or death Warning means that failure to follow this safety statement could result in serious personal injury or death Caution means that failure to follow this safety statement may result in minor or moderate personal injury property or equipment damage GENERAL PRECAUTIONS Use this appliance for its intended purpose only and follow these general precautions with those listed throughout this guide ERATING INSTRUCTIONS MAINTENANCE SERVIC This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with this appliance A DANGER This unit contains R600a Isobutane which is a flammable hydrocarbon It is safe for regular use Do not use sharp objects to expedite defrosting Do not service without consulting the R600a specifications section included in the User Guide Do not damage the refrigerant circuit A DANGER Do not use electrical appliances inside the food storage compartment of this appliance Keep ventilation openings in the appliance enclosure or in the built in structure clear of
20. and closes the circuit which turns the light and display off When the door is open the reed pulls away from the contact and opens the circuit If the door is left open for longer than 5 minutes the switch will trigger an error code and set an audible warning Magnet Away From Switch Magnet Close To Switch Door Open Door Closed Switch Open Switch Closed Troubleshooting Extended 4 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OP Relay Toggle Up Select 4 gt RETURN TO MENU RELAY TOGGLE MULL OFF ra fa U LINE amp COND_OFF Down Relay toggle is used to manually switch the state of each relay to test for proper operation In addition to the AC relays DC outputs may also be toggled Relay toggle can also be used to force the unit into a particular state For example to force a 3018 3045 into a cooling cycle activate Comp F1 and F3 ID Description Type Mull ullion Heater Not Used AC Cond Fan Not Used AC Def Defrost Valve Not Used AC LVLV Left Valve Not Used AC RVLV Right Valve Not Used AC Pan Pan Heater Not Used AC Comp Compressor AC F1 Evaporator Fan DC F2 Evaporator Fan Not Used DC F3 Condenser Fan DC L1 Cabinet Lighting DC L2 Cabinet Lighting Not Used DC To access Relay Toggle 1 Press amp to select Relay Toggle 2 Press 3 Press B and amp to scroll through
21. are preset at the factory Initial startup requires no adjustments NOTICE U Line recommends allowing the unit to run overnight before loading with product When plugged in the unit will begin operating under the factory default setting Follow the on screen prompt for language selection and temperature units To turn the unit off press and hold for 5 seconds and release The display will show a countdown to switching the unit off To power your unit on simply press and the unit will immediately switch on NANC S RVIC First Use 1 USER GUIDE LU LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC Control Operation Up Zone Toggle ae 50 F T U LINE 5 Can be displayed in Celsius Down CONTROL FUNCTION GUIDE Power U Select Lighting FUNCTION COMMAND DISPLAY OPTIONS OFF Press and hold Display will count down from 5 to off ON Press and release Unit will come on immediately Press and release to scroll through Press to select one of 5 modes see table Select mode g the modes below Adjust temp Press to select mode Press 4 or al to set temperature Press 4D to confirm temperature or wait 5 seconds Adjust lighting Press to adjust lighting Press B or to set low medium or high Light ON OFF with door Press
22. control board is very robust and is rarely the cause of system issues It is important to fully diagnose the board for any suspected failures before attempting to remove the board for replacement or service Follow the guidelines below to fully test and diagnose the main control Power Fault If the unit does not or seems to not power on follow the flow chart below to help diagnose the issue Before beginning it is important to first verify the unit is not simply set to sabbath mode Check Voltage Alert Customer At Wall Outlet 7 No Voltage of power Failure Voltage AE MEn Conteo No Voltage R Voltage Input Voltage Check Fuse F1 Replace No Continuity For Continuity Fuse Continuity Connect Test Display To J5 Inspect Customer UI Operating 4 Cycle Power And P 9 and Data Cable Check For Operation A Not Operating Is the door open The Is the Reed Raiza keen Display will not activate Yes Switch Operating No ain while the door is closed Properly No Yes No Open Door Is the UI Now Replace Main Functional Board Yes Troubleshooting Extended 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OP Testing The Main Control If the main control
23. or condenser Troubleshooting 3 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OP Warranty U LINE CORPORATION LIMITED WARRANTY PRODUCTS OUTSIDE THE UNITED STATES AND CANADA L U Line Corporation U Line warrants each U Line product to be free from defects in materials and workmanship for a period of two years from the date of purchase During the two year warranty period for all U Line products U Line shall be responsible for the labor costs performed by a U Line authorized company incurred in connection with the replacement of any defective part All other charges including transportation charges for replacements under this warranty and labor costs not specifically covered by this warranty shall be the responsibility of the purchaser This warranty extends only to the original purchaser of the U Line product The Product Registration Card included with the product should be promptly completed and mailed back to U Line or you can register on line at www u line com A proof of purchase may be required The warranty listed above does not apply to floor display models The warranty for these models shall be 30 days from the date of retail purchase and only if U Line s Product Registration Card included with the unit is completed and mailed back or electronically submitted to U Line This 30 day warranty does not apply to cosmetic damages A proof of purchase ma
24. reflected on the main screen Changes to the evap set point alter the temperature the evaporator needs to meet during a defrost cycle To access Set Points 1 Press to select Set Points 2 Press 3 Press 6B and amp to scroll through available set points To change set point 4 Press 9 the selected set point will begin to flash 5 Press B or amp to modify the value 6 Press to confirm setting Control Operation Service 6 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OP To exit the Set Points menu press E to select Return to Menu and press to confirm Factory Default Up Select B gt RETURN TO MENU FACTORY DEFAULT U LI N E RESTORE B EH Me Me amp e Down Factory Default will restore all settings to their factory default To access Factory Default 1 Press amp to select Factory Default 2 Press To restore settings to their factory default 3 Press to select Restore and press 4 Restore will change to Restoring while settings are restored When restoration is complete Restoring will return to Restore To exit Factory Default press E to select Return to Menu and press to confirm ERATING INSTRUCTIONS MAINTENANCE SERVICE Re Select Model Up Select 4 RETURN TO MENU 4d
25. to have light on off with door Press and release to scroll through timer settings Press 4 or to scroll through menu Customer menu Press and hold for 5 seconds Mode Set Point Temperature Range F C F C Deli 36 2 34 40 1 4 Beverage Drinks 38 3 34 65 1 18 Market Fresh 38 3 34 40 1 4 Root 50 10 45 55 7 12 Pantry 42 5 34 70 1 21 Control Operation 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC U SELECT CONTROL Digital Display The 3000 Series units are controlled by a feature rich advanced OLED display control unit The control panel allows adjustment to temperature set point access to Energy Saver Mode internal temperature readings and many other features ADJUSTING TEMPERATURE SETTINGS Up Zone Toggle Select B Root 50 F wW Power U Select Lighting u LINE Can be displayed in Celsius Down Each zone has a series of Mode Settings with a default value for each setting Each Mode Setting can be further customized by fine tuning the temperature set point See the chart below for a description of each mode and mode temperature ranges Mode selection will vary by model Mode Settings Chart Setting Default F C Range F C Deli 36 2 34 40 1 4
26. 1 USER GUIDE LINE u line com U ETY e INSTALLATION amp INT SAF EGRATION OP Product Liability Important Note Service or repairs must not be performed on any unit suspected to be involved in a property damage situation If a unit has been altered or repaired in the field prior to U Line s evaluation any claim for damage may be declined Field service technicians are authorized to make an initial assessment If in the service technician s judgment the damage is the result of a product defect the product would be removed and returned to U Line in an unaltered condition The dealer would then be authorized to permanently replace the end user s product at no cost to the end user Please call U Line immediately at 1 800 779 2547 to initiate the Return Authorization and product exchange process If the service technician determines the damage is the result of installation issues water connection drain etc the consumer would be notified and the correction could be made by the servicer or installer without requiring removal of the product In this case the claim for damages should be directed to the original installer On U Line Clear Ice product equi the drain pump must be returned pped with a drain pump along with the unit regardless of the drain pump manufacturer To complete the damage claim process for the customer please forward the following to U Line via fax 1 414 354 569
27. 3 5 16 84 mm to 4 5 16 110 mm based on your grille plinth strip base fascia height 1 1 2 38 mm Ae 1 25 mm 2 Finish or stain your grille plinth strip base fascia panel to match your surrounding furniture Finish front back and edges to prevent warping Carefully follow the manufacturer s recommendations for finish application and cure times gt T RE me 3 Apply double sided tape to the backside of the ne integrated grill plinth strip base fascia Use the diagram below for reference U Line recommends 3M VHB tape a high strength bonding tape Apply Tape To Shaded Area sf DDA A Y 4 Remove backing paper from double sided tape 5 Carefully align grille plinth strip base fascia over integrated panel and press into position Integrated Grille Plinth Dimensions 1 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OP Integrated Panel Installation 1 Fully open door gt 2 Starting at corner pull gasket away from door 3 Continue to pull gasket free from gasket channel 4 Upon removal lay gasket down on a flat surface 5 The panel should be aligned with the outside edge opposite the hinge and high enough to align with the highest point in the door Align Top Of Panel With Highest Point Of Door Align Panel Against Door Edge First NOTICE D
28. 4 Remove and replace fan Take special care to properly route fan wire NOTICE Fan must be oriented to pull air in through lower evaporator cover vents and push air out at fan mounting location 15 Installation is the reverse of removal 16 Care must be taken to assure the bottom of the evaporator cover is reinstalled behind the front edge of the train trough 17 Use sealant gum to seal any openings at rear of unit before replacing rear cover 18 Reinstall unit taking care to level space and secure as found NANCE SERVICE Remove Fan and Cover 2
29. 6 email onlineservice u line com or mail Pictures of the damage U Line product property damage and installation supply and drain connections if applicable e A brief description of the damages and product service history if possible Damage estimates NANC e SERVICE ERATING INSTRUCTIONS MAINT e A Return Authorization Number reference provided by U Line and customer name when submitting information For shipping Use an OEM shipping carton U Line will provide if needed or packaging can be reused from the replacement unit and clearly mark the Return Authorization Number on the carton before returning the product When the unit is ready for pickup contact U Line at 1 800 779 2547 and U Line will make arrangements for a freight collect shipment Upon return to U Line the product will be evaluated within ten business days No service company is authorized to make these evaluations in place of U Line U Line Customer Care staff will review the engineering evaluation and notify the customer of a valid claim or provide denial details 8900 N 55th Street e Milwaukee WI 53223 T 1 414 354 0300 F 1 414 354 354 5696 Website www u line com Right product Right place Right temperature Since 1962 Product Liability 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVICE
30. ATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC CUSTOMER MENU The 3000 Series of U Line undercounter refrigeration appliances contains a feature rich customer menu The Customer Menu allows access to a series of advanced features including Energy Saver Mode Sabbath Mode actual temperature readings as well a method to restore factory defaults 3000 Series Customer Menu Up Select WELCOME TO THE O CUSTOMER MENU USE UP DOWN ARROWS TO KY SCROLL SETTINGS yr Oj Down 1 To access the Customer Menu hold for 5 seconds 2 Press amp or amp to scroll through available selections 3 Press to enter selected sub menu 4 To exit Customer Menu press to scroll to the bottom of the display and press to select Exit Actual Temps Select RETURN TO MENU ACTUAL TEMPS BINTEMP 1 6 f 3 U LINE o No TEME 55 Can be displayed in Celsius Down The Actual Temps option displays the actual temperature of each zone and evaporator as well as ambient temperature 1 To view actual temperature select Actual Temps from the Customer Menu 2 Press B or to scroll through available information 3 To return to the Customer Menu press Energy Saver Mode Up Energy Saver Mode Indicator Select Sk mee Sl ICE PRODUCTION 12m remaining X U LINE Down Energy Saver Mode reduces overall energ
31. CE All 4 shelf clips for each shelf must be installed at the same height for shelf stability 4 Reinstall shelf Cleaning Shelves Shelves may be cleaned in a soapy warm water solution A general household disinfectant may be used if necessary Be sure to completely dry your shelf before reinstalling Interior Shelves 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC Refrigerator Bins Crisper REFRIGERATOR BIN INSTALLATION amp REMOVAL Refrigerator bins are easily removed for cleaning and sanitizing To remove your bin follow the instructions below 1 Fully extend the bin you wish to remove from the cabinet 2 Lift the front lip of the bin and raise the bin off the racks 3 Lift the rear of the bin off its seat on the rack 4 Pull the bin up and away from the racks To Reinstall 5 Fully extend the empty rack from within the cabinet 6 Set the rear of the bin over the rear of the slide 7 Seat the front of the bin down and onto the slide rack 8 Push the bin back into the cabinet Cleaning Bins may be cleaned in a soapy warm water solution A general household disinfectant safe for plastics may be used if necessary Be sure to completely dry your bin before reinstalling NO
32. ON amp INT THERMISTORS Thermistors are used for various temperature readings Thermistors provide reliable temperature readings using a resistance which varies based on surrounding temperatures If a faulty thermistor is suspected it may be tested using an accurate ohmmeter In an ice water bath 32 F resistance should measure 16 1 kilohms 5K OHMS 77 16 1K OHMS 32 F ambient THERMISTOR FAILURE Limp Mode Data Table EGRATION OP ERATING INSTRUCTIONS e MAINTENANCE SERVICE Mode ON OFF Beverage Drinks 0 min 45 min Market Fresh 10 min 45 min Root 5 min 90 min Pantry O min 45 min Deli 0 min 45 min Zone Thermistor If the zone thermistor fails the unit will continue to operate in a timed limp mode which varies by model The unit will otherwise operate normally The error will be displayed in the error log Evaporator Thermistor If the evaporator thermistor fails the unit will rely on a preset defrost time during defrost cycles The unit will otherwise operate normally Evaporator thermistor errors will be displayed in the error log Always assure that all thermistor connections are clean and dry Whenever opening a thermistor connection be sure to apply a fresh dab of die electric grease REED SWITCH A reed switch is used to monitor door state When the door is closed magnetic force pulls the reed to its contact
33. RATING INSTRUCTIONS e MAINTENANCE SERVIC NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three prong polarized receptacle that has been placed by a qualified electrician The unit requires a grounded and polarized 230 VAC 50 Hz 8A power supply normal household current An individual properly grounded branch circuit or circuit breaker is recommended A GFCI ground fault circuit interrupter is usually not required for fixed location appliances and is not recommended for your unit because it could be prone to nuisance tripping However be sure to consult your local codes See CUTOUT DIMENSIONS for recommended receptacle location Electrical 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE e SERVIC Cutout Dimensions CUTOUT DIMENSIONS PREPARE SITE Your U Line product has been designed exclusively for a built in installation When built in your unit does not require additional air space for top sides or rear However the front grille plinth strip base fascia must NOT be obstructed Preferred location for electrical outlet is in adjacent cabinet 33 7 8 860 mm J ET 610mm The Modular 3000 Series units are engineered with a 886 mm a 178 mm v
34. RIGHT DOOR OPEN MONITORS THE STATE OF DC OUTPUTS AE UUTE OUTPUTS evap amp condenser fans 0 100 and lighting off low med high bs 5 EVAD CAN Oe OFFSETS ARE USED TO ADJUST OR CORRECT THERMISTOR READINGS RETURN TO MENU OFFSETS CORRECTED VALUES MAY BE VIEWED THROUGH THE CUSTOMER MENU RIGHT ZONE 18 C RIGHT EVAP 17 C SELF TEST IS USED TO DIAGNOSE THE BOARD IF NO ERRORS ARE PRESENT ao ey SELF TEST NO ERRORS WILL BE DISPLAYED THE MAIN BOARD IS FUNCTIONING PROPERLY NO ERRORS DIFFERENTIALS ARE USED TO DETERMINE AT WHAT TEMPERATURE THE UNIT RETURN TO MENY DIFFEREN CYCLES O SETTING IS 2 DIFFERENTIAL gt LEFT 16 C eee etre THE SET POINTS MENU IS USED TO MODIFY BOTH THE ZONE AND EVAP SET POINTS SSO SUITE THE EVAP SET POINT IS USED DURING DEFROST IT MUST REACH 42 F 6 C gt LERT ZONE 124C RETURN TO MENU FACTORY DEFAULTS FACTORY DEFAULT IS USED TO RESTORE ALL SETTINGS TO THE FACTORY PERN ONEAN DEFAULT FOR THE SELECTED MODEL gt RESTORE RE SELECT MODEL IS USED TO MODIFY THE MODEL INFORMATION CHANGING RETURN TO MENU RESELECT MODEL NNE E THE MODEL COMPLETELY REPROGRAMS AVAILABLE ZONES gt 3090WCWC FAN DELAY ALLOWS MODIFICATION OF FAN RUN TIMES BOTH AT THE START RETHRN TONEN FAN DELAY OEO OF A COOLING CYCLE AND AT THE END AFTER THE COMPRESSOR STOPS m FAN i DELAY Orne d RANDOMLY SCROLLS THROUGH ZONES MODES TEMPERATURES AND OTHER RETURNTO MENU SHOWROOM MODE FEATURES TOUCH AND HOLD TO EXIT SHOWROOM MODE gt
35. TALLATION 1 Plug in the power electrical cord 2 Gently push the unit into position Be careful not to entangle the cord 3 Re check the leveling from front to back and side to side Make any necessary adjustments The unit s top surface should be approximately 1 8 3 mm below the countertop 4 Install the anti tip bracket 5 Remove the interior packing material and wipe out the inside of the unit with a clean water dampened cloth General Installation 1 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE e SERVIC Integrated Panel Dimensions Integrated Frame Dimensions INTEGRATED FRAME 3 4 BACK SURFACE MUST HAVE AMPLE FLAT SURFACE 1 TO MOUNT OVERLAY FRAME FLAT AND WITHOUT 20 mm INTERFERENCE Y NOTICE aa A Due to differences in surrounding cabinetry the 23 3 8 panel may not perfectly align with door The 594 mm procedure below is designed to provide a finished integrated panel that seamlessly integrates with surrounding cabinetry Panel Preparation A full integrated door panel completely covers the door frame and provides a built in appearance lt gt 2 3 4 MIN 70 mm MIN 30 762 mm NOTICE The door panel must not weigh more than 20 Ibs 10 kg It is important to ensure that all drilled holes are drilled to the correct depth in order to avoid splits in the wood when hardwa
36. TICE Bins are NOT dishwasher safe Refrigerator Bins Crisper 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OP Cleaning EXTERIOR CLEANING Stainless Models Stainless door panels and handles can discolor when exposed to chlorine gas pool chemicals saltwater or cleaners with bleach Keep your stainless unit looking new by cleaning with a good quality all in one stainless steel cleaner and polish monthly For best results use Claire Stainless Stee Polish and Cleaner which can be purchased from U Line Corporation Part Number 173348 Comparable products are acceptable Frequent cleaning will remove surface contamination that could lead to rust Some installations may require cleaning weekly Do not clean with steel wool pads Do not use stainless steel cleaners or polishes on any glass surfaces Clean any glass surfaces with a non chlorine glass cleaner Do not use cleaners not specifically intended for stainless steel on stainless steel surfaces this includes glass tile and counter cleaners If any surface discoloring or rusting appears clean it quickly with Bon Ami or Barkeepers Friend Cleanser and a nonabrasive cloth Always clean with the grain Always finish with Claire Stainless Steel Polish and Cleaner or comparable product to prevent further problems Using abrasive pads such as Scotchbrite will cause the graining in the stainless steel to
37. TURN TO MENU 4 ZONE 1 F 7 one Evae Can be displayed in Celsius Down NOTICE Customer care MUST be notified and approve of any changes to the differential before they are made Failure to notify customer care will void the warranty ERATING INSTRUCTIONS MAINTENANCE SERVICE Offsets are used to adjust or correct thermistor readings Offset values are added to the current thermistor reading and are then used by the control board to determine cooling and defrost cycle times Offsets have a range of 10 C Corrected values may be viewed through the customer All Temps menu or TTY output To access Offsets 1 Press to select Offsets 2 Press 3 Press B and amp to scroll through available thermistors To change offset 4 Press oF the selected thermistor will begin to flash 5 Press B or to modify offset value 6 Press to confirm setting To exit the Offset menu press E to select Return to Menu and press to confirm Self Test Up RETURN TO MENU SELF TEST NO ERRORS try RELAY TOGGLE Down Control Operation Service 5 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OP Self test is used to initiate a self diagnostic report Any system faults will be displayed under Self test If no errors are present no errors will be displayed and the main control board is functioning pro
38. USER GUIDE SAF ETY e INSTALLATION amp INT U LINE RIGHT PRODUCT RIGHT PLACE RIGHT TEMPERATURE SINCE 1962 Modular 3000 Series EGRATION e OP ERATING INSTRUCTIONS e MAINT NANC RVIC e 3060RDC e 60cm Drinks Cabinet USER GUIDE LINE u line com SAF ETY e INSTALLATION amp INT EGRATION OP ERATING INSTRUCTIONS e MAINTENANCE e SERVIC Tip Click on any section below to jump directly there Contents Safety Intro Safety and Warning Disposal and Recycling Installation Environmental Requirements Electrical Cutout Dimensions Product Dimensions Side by Side Installation Anti Tip Bracket General Installation Integrated Panel Dimensions le Plinth Dimensions Integrated G Integrated Panel Installation Grille Plinth Installation Door Swing Door Stop Door Adjust Operating Instructions First Use Control Operation Sabbath Mode Airflow and Product Loading Interior Shelves Refrigerator Bins Crisper Maintenance Cleaning Cleaning Condenser Extended Non Use Service Troubleshooting Warranty Service Extended Wire Diagram Product Liability Warranty Claims Ordering Replacement Parts System Diagnosis Guide Compressor Specifications Troubleshooting Extended Control Quick Guide Thermistor Defrost Remove Fan and Cover USER GUIDE U LINE
39. Wooden Insert Integrated Panel Dimensions 2 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE SERVIC Handleless Integrated Frame Dimensions 1 8 S lt 3 mm y a Top Design 1 4 6 mm h A 7 8 22 mm Ref y 2 3 8 R 5 8 R 16 mm eoim 23 3 8 gt 594 mm 2 3 4 70 mm y X Insert Notch 2 3 4 70 mm Wooden Insert Notch Depth 1 8 3 mm Top Detail Cutout for Frame Units 28 13 16 732 mm gt lt 3 4 20 mm Wooden Insert Dimensions 23 3 8 He 594 mm _ gt gt lt 1 8 3 mm fF oY 9 _Y Integrated Panel Dimensions 3 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE e SERVIC EXTENDED INTEGRATED FRAME NOTICE Due to differences in surrounding cabinetry the panel may not perfectly align with door The procedure below is designed to provide a finished panel that seamlessly integrates with surrounding cabinetry Panel Preparation An extended integrated panel can be used to maintain alignment with an adjacent extended cabinet height or a reduced toe kick grille application 1 Cut the panels to the dimensions listed in the appropriate diagram on the next page 2 Optional Stain or finish panel to desired stain or color Be sure to clos
40. ariety of adjustment features to help ensure a seamless installation Adjustable doors leveling legs and grille will 10 mmo assist in fine tuning the installation as 23 5 8 600 mm All 3000 Series models fully integrate into overlay face frame inset or European frameless cabinet styles Unit can NOT be installed behind a closed cabinet door U Line products are designed and manufactured to be seamlessly installed in the specified cutout openings shown and variance to the floors or cabinetry must be accounted for in your installation Cutout Dimensions 1 USER GUIDE LU LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC Product Dimensions 23 7 16 590 mm 3 5 8 to 4 5 8 92 mm to 118 mm pO 23 5 8 600 mm 33 11 16 to 34 11 16 856 mm to 881 mm Includes 3 4 20 mm integrated panel Product Dimensions 1 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OP Side by Side Installation OTHER SITE REQUIREMENTS Side by Side Installation Units must operate from separate properly grounded electrical receptacles placed according to each unit s electrical specifications requirements Cutout width for a side by side installation is the total of the widths listed under Cutout Dimensions in each unit s Installat
41. ary Tighten screws upon completion 12 Starting at the corners re install the gasket into the gasket channel in the frame Make sure the gasket is fully seated Integrated Panel Installation 2 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OP Grille Plinth Installation REMOVING AND INSTALLING GRILLE PLINTH STRIP BASE FASCIA Disconnect electrical current to the unit before removing the grille plinth strip base fascia When using the unit the grille plinth strip base fascia must be installed Edges of sheet metal may be sharp Removing the grille plinth strip base fascia 1 Disconnect electrical current to unit 2 Using the included 7 64 Allen wrench loosen but do not remove both grille plinth strip base fascia lock screws See below LJ TEEL 2s Grille Mounting Screws 3 Gently pull grille plinth strip base fascia away from unit until it stops 4 Push grille plinth strip base fascia rails towards the center of the unit to lift rails off lock screws E gt Grille Rail 5 Pull grille plinth strip base fascia free from unit ERATING INSTRUCTIONS MAINT NANC eS RVIC Installing the grille plinth strip base fascia
42. bient temperature and excessive humidity can also produce frost Unit Develops Condensation on External Surfaces decreas oisture will dissi ie The unit is exposed to excessive humidity pate as humidity levels Troubleshooting 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS e MAINTENANCE e SERVICE Problem Possible Cause and Remedy ID Description Solution Digital Display Ensure the unit is not in Showroom Mode L R Temp Hi Left or right zone Verify door is closed Functions But Momentarily unplug or interrupt power 6H temperature 10 and sealing Contact Unit Does Not supply to the unit over set point for Customer Care if Cool over 6 hours persistent Digital Display Door indicates the door may be opened L R Temp Hi Left or right zone Verify door is closed Shows an Error too long Ensure the door is closing 12H temperature 10 and sealing Contact properly For other error codes contact over set point for Customer Care if U Line Customer Service over 12 hours persistent Product Is Because product in contact with the rear wall L R Temp Lo Left or right zone Verify door is closed Freezing may freeze ensure no product is touching 6H temperature 10 and sealing Contact the rear wa
43. components listed ERATING INSTRUCTIONS MAINT NANC e SERVICE e Compressor The compressor makes a hum or pulsing sound that may be heard when it operates e Evaporator Refrigerant f may sound like boiling liquid e Condenser Fan Air moving through a condenser be heard owing through an evaporator may e Automatic Defrost Drain Pan Water may be heard dripping or running into the drain pan when the unit is in the defrost cycle e Solenoid Valves An occasional clicking sound may be heard as solenoid valves are operated TROUBLESHOOTING GUIDE A DANGER ELECTROCUTION HAZARD Never attempt to repair or perform maintenance on the unit before disconnecting the main electrical power Troubleshooting What to check when problems occur Closed Problem Possible Cause and Remedy Digital Display Ensure power is connected to the unit and Light Do Not If the unit is cooling it may be in Sabbath Work mode Interior Light f the unit is cooling it may be in Sabbath Does Not mode or manually set to off Illuminate Light Remains on Lighting may be set to on reset to with When Door Is door Unit Develops Frost on Internal Surfaces Frost on the rear wall is normal and wi during each off cycle melt f there is excessive build up of 1 4 or more manually defrost the unit Ensure the door is closing and sealing properly High am
44. down This will help prevent water from getting onto customer s floor The defrost duration is dependent upon usage or climate Typically defrosting is needed approximately every 6 weeks Defrost 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVICE Remove Fan and Cover 3 Disconnect power to the unit CONVECTION COOLING This unit is equipped with an advanced convection cooling system Convection cooling stabilizes cabinet temperature cools product faster and increases energy efficiency 4 Remove rear cover from unit 5 Disconnect fan electrical connection at rear of unit 6 Remove insulating foam from refrigerant line pass Evaporator Fan through hole as needed to gain clearance for fan plug The evaporator fan is responsible for circulating warm air from the refrigeration zone past the evaporator and back 7 Remove internal shelving into the refrigerated zone 8 Remove rear shelf clips fronts can remain The evaporator fan is factory set to have a 1 minute delay at the beginning of a cooling cycle This delay gives the 9 evaporator time to cool properly before warm air is passed over it The fan will continue to run for an additional 2 minutes at the end of a cooling cycle Fan delay times can 10 Remove two evaporator cover screws from top of be modified through the service menu evaporator plate Remove
45. e plinth strip base fascia See GRILLE PLINTH INSTALLATION 2 Clean the condenser coil using a soft brush or vacuum cleaner 3 Install the grille plinth strip base fascia Me Oe Cleaning Condenser 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE SERVIC Extended Non Use VACATION HOLIDAY PROLONGED SHUTDOWN The following steps are recommended for periods of extended non use 1 Remove all consumable content from the unit 2 Disconnect the power cord from its outlet socket and leave it disconnected until the unit is returned to service 3 If ice is on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open to prevent formation of mold and mildew Open door a minimum of 2 50 mm to provide the necessary ventilation WINTERIZATION If the unit will be exposed to temperatures of 40 F 5 C or less the steps above must be followed For questions regarding winterization please call U Line at 1 800 779 2547 Damage caused by freezing temperatures is not covered by the warranty Extended Non Use 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INT Troubleshooting BEFORE CALLING FOR SERVICE
46. each relay or DC output 4 Press to toggle 5 To exit the Relay Toggle menu press O to select Return to Menu and press amp to confirm ERATING INSTRUCTIONS e MAINTENANCE SERVICE CONVECTION COOLING All 3000 series units are equipped with an advanced convection cooling system Convection cooling stabilizes cabinet temperature cools product faster and increases energy efficiency Evaporator Fan The evaporator fan is responsible for circulating warm air from the refrigeration zone past the evaporator and back into the refrigerated zone The evaporator fan is factory set to have a 1 minute delay at the beginning of a cooling cycle This delay gives the evaporator time to cool properly before warm air is passed over it The fan will continue to run for an additional 2 minutes at the end of a cooling cycle Fan delay times can be modified through the service menu Evaporator fan operation is also determined by door switch state If the door switch circuit opens the fan will stop When the door switch circuit is closed the fan will either continue running with the cooling cycle or if not currently cooling the fan will run for 1 minute to circulate air and clear any condensation that may have appeared on glass doors and shelves OTE If the unit is set to sabbath mode the evaporator fan will no longer respond to the state of the door switch In order to operate efficiently the evaporator fa
47. egrated Panel Dimensions 5 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OP Extended Integrated Frame Dimensions ERATING INSTRUCTIONS e MAINTENANCE SERVIC BACK SURFACE MUST HAVE AMPLE FLAT SURFACE INTERFERENCE 3 4 TO MOUNT OVERLAY FRAME FLAT AND WITHOUT 20 mm Y 23 3 8 594 my k 2 3 4 MIN 70 mm MIN A 32 7 8 to 33 7 8 834 mm to 860 mm Integrated Frame A minimum of 1 25 mm is required from the floor to the bottom of the extended integrated panel frame for proper ventilation NOTICE The minimum border thickness for a 30 762 mm tall integrated frame is 2 3 4 70 mm The top bottom border of the frame must account for any additional length Integrated Panel Dimensions 6 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE e SERVIC Integrated Grille Plinth INTEGRATED GRILLE PLINTH STRIP BASE FASCIA DIMENSIONS Dimensions o E PREPARE AND INSTALL INTEGRATED GRILLE S5 PLINTH STRIP BASE FASCIA ae 1 Use the dimensions provided in the diagram to cut and 2E m h gt shape your integrated grille plinth strip base fascia panel Recommended panel thickness is between 1 4 6 mm and 3 8 9 mm Height will vary from
48. elay Status 1 Press amp to select All Errors gt Bree 2 Press 3 Press B and amp to scroll through available information 3 Press B and amp to scroll through available information To exit the Relay Status simply press to exit To clear the error log press to select Clear Errors and press to confirm To exit the Actual Temps menu press E to select Return to Menu and press to confirm Control Operation Service 3 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OP Relay Toggle Up Select gt RETURN TO MENU RELAY TOGGLE MULL OFF JP COND OFF 6 U LINE H Down Relay toggle is used to manually switch the state of each relay to test for proper operation In addition to the AC relays DC switches may also be toggled Relay toggle can also be used to force the unit into a particular state For example to force a 3036 into a cooling cycle activate LVLV Comp F1 and F3 ID Description Solution Mull Mullion Heater Not Used AC Cond Fan Not Used AC Def Defrost Valve Not Used AC Pan Pan heater Not Used AC Comp Compressor AC F1 Evaporator Fan DC F3 Condenser Fan DC L1 Zone Lighting DC To access Relay Toggle 4 Press EI to select Relay Toggle 5 Press 6 Press B and to scroll through each relay and DC output 7 Press to toggle To exit the Relay T
49. ely follow the instructions provided by the manufacturer 3 Optional Install handles and hardware NOTICE The door panel must not weigh more than 20 Ibs 10 kg It is important to ensure that all drilled holes are drilled to the correct depth in order to avoid splits in the wood when hardware is installed Appliance will need up to 34 1 2 876 mm to the under side of the counter to leave room for leveling adjustments When applying an integrated frame to a unit ensure that both sides are finished in order to prevent warping In some installations the panel may be visible through the glass while the door is open Integrated Panel Dimensions 4 USER GUIDE U LINE u line com SAF Panel can extend beyond the door frame A minimum of 1 25 mm from ETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANC Front Side Integrated Panel Integrated Frame Integrated Panel U Line Unit 3 5 16 89 mm 3 5 16 89 mm gt 3 5 16 to to gt 89 mm 4 5 16 114 mm 4 5 16 114 mm Front Extended Integrated Panel Extended Integrated Frame the floor is required for proper sf B j j 3 5 16 89 ventilations a o e K mm O 1 25 mm Side eS RVIC Integrated Panel y U Line Unit 1 25 mm 4 3 5 16 89 mm to FF Int
50. gain and the unit will immediately switch on retaining the presets from before it entered showroom mode To exit the showroom mode menu press amp to select Return to Menu and press amp to confirm Control Operation Service 8 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OP Thermistors Thermistors are used for various temperature readings Thermistors provide reliable temperature readings using a resistance which varies based on surrounding temperatures If a faulty thermistor is suspected it may be tested using an accurate ohmmeter THERMISTOR FAILURE Zone Thermistors If the zone thermistor in the unit fails the unit will continue to cool in a back up mode to preserve the integrity of the contents The unit will cycle on for ten minutes then shut down for forty five minutes The process will repeat until the problem is corrected All other functions of the unit will continue to operate normally Evaporator Thermistors If an evaporator thermistor fails the unit will rely on a preset defrost timer during defrost cycles The unit will otherwise operate normally The error will be displayed in the service mode Error Log This unit has two thermistors Thermistor one is located along the right hand side wall inside of the unit and is used to maintain temperature within the unit Thermistor two is located on the back of the evaporator and is used for defrost pur
51. ill bit drill 3 pilot holes 5 8 16 mm deep into cabinetry frame using the anti tip bracket as a template Install 3 8x5 8 screws into the plate using a 2 Phillips head screwdriver Anti Tip Bracket 1 USERAGUIDE U LINE u line com ERATING INSTRUCTIONS e MAINTENANCE SERVIC SAFETY e INSTALLATION amp INTEGRATION OP General Installation LEVELING INFORMATION 1 Use a level to confirm the unit is level Level should be placed along top edge and side edge as shown S 2 Ifthe unitis not level remove grille and adjust legs as necessary Use included tool to adjust the height of the rear legs gt 0 6 A Ke ka T Rotate Front Legs to Adjust we f p Rotate Clockwise to raise rear leg Rotate Counter Clockwise to lower leg 3 Confirm the unit is level after each adjustment and repeat the previous steps until the unit is level INSTALLATION TIP If the room floor is higher than the floor in the cutout opening adjust the rear legs to achieve a total unit rear height of 1 8 3 mm less than the opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gently tipped into the opening Adjust the front legs to level the unit after it is correctly positioned in the opening INS
52. ion Guide Each door can be opened individually one at a time without interference However to ensure unobstructed door swing opening both doors at the same time 1 4 6 4 mm of space needs to be maintained between the units j 1 4 6 mm ERATING INSTRUCTIONS e MAINTENANCE SERVIC Hinge by Hinge Installation Mullion When installing two units hinge by hinge 13 16 22 mm is required for integrated models Additional space may be needed for any knobs pulls or handles installed j 13 16 22 mm Stainless steel models which include the standard stainless handle will require 4 9 16 116 mm to allow both doors to open to 90 at the same time ei 116 mm Side by Side Installation 1 USERAGUIDE U LINE u line com SAF ETY e INSTALLATION amp INTEGRATION OP Anti Tip Bracket The the anti tip bracket must be installed to prevent unit from tipping when doors are fully opened or excess weight is placed on the front of the unit The anti tip bracket has multiple mounting options Mounting will depend on your particular cabinet configuration Locate 3 8x5 8 screws included with your unit TOP MOUNT 0 I I I t l
53. is suspected of being faulty the following procedure should be performed to verify main control for functionality Relay amp DC Outputs One of the primary functions of the main control is to operate the multiple relay and DC outputs during each cycle Verify proper operation of these relays using the following procedure 1 Enter Relay Toggle through the service menu NOTICE Frequently toggling the compressor relay could force the compressor into overload The compressor will automatically deactivate during an overload and will remain deactivated until the overload switch cools This could take some time It is important to allow the compressor at least 5 minutes off time between relay cycles 2 Toggle the relay Its related component should activate deactivate with the switching of the relay Inputs The main control monitors a number of thermistor inputs and switch states during operation It would be unlikely that an error in reading an input would be at the board level Always attempt to replace the faulty switch or thermistor input with a Known working sample to verify proper board operation ERATING INSTRUCTIONS e MAINTENANCE SERVICE Other Suspected Main Control Faults If other components have been ruled out as being faulty but the unit continues to have operating issues it is most likely due to a configuration error Configuration errors can be cleared by restoring the unit to its fac
54. l settings High Medium Low and Off To select a new sound level enter the Sound Level Menu from the Customer Menu 1 Press to select the current sound level 2 Press The current setting will begin to flash 3 Press amp or amp to select a different level A 4 Press amp to confirm your choice Fahrenheit Celsius Up ie 5 U LINE DEGREES F We o Down Temperature and set point information can be displayed in either Fahrenheit or Celsius To change from Fahrenheit to Celsius enter the Fahrenheit Celsius Menu from within the Customer Menu 1 Press amp to select Degrees 2 Press The selection will begin to flash 3 Press B or to select between F Fahrenheit or C Celsius 4 Press to confirm your choice Control Operation 5 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC Factory Default Up Select S 4 RETURN TO MENU 4d FACTORY DEFAULT RESTORE A ULINE amp amp g Down Factory Default will restore all settings to their factory default To access Factory Default 1 Press amp to select Factory Default 2 Press To restore settings to their factory default 3 Press E to select Restore and press O 4 Restore will change to Rest
55. lect Sabbath Mode from the Customer Menu by pressing 5 Press to select Off 6 Press Off will begin to flash 7 Press 4 or amp to change Off to On 8 Press to confirm your selection The Display will fade out as the unit enters Sabbath Mode Sabbath Mode remains active until 5 is quickly pressed and released Sabbath Mode 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE e SERVIC Airflow and Product Loading NOTICE The unit requires proper airflow to perform at its highest efficiency Do not block the front grille internal fans or vents at any time or the unit will not perform as expected When loading your unit leave space between the internal fans or vents and product loaded Anything blocking the required airflow circulation will result in uneven temperature distribution in the cabinet and can also freeze product Do not install the unit behind a door When properly loaded your U Line unit will store up to 172 12 oz 330 ml cans or 114 12 oz 330 ml bottles For optimal airflow leave approximately two inches of Space around the fan and one inch around the back wall and lower vents Door Removed For Illustration Purposes QUODUCDO00UGUDUCB0UUDU0D0000 Internal Air Flow And Unit Ventilation Diagram Fan top view
56. ll under set point for Customer Care if Adjust the temperature to a warmer set over 6 hours persistent pa L R Temp Lo Left or right zone Verify door is closed Product Is Not Air temperature does not indicate product 12H temperature 10 and sealing Contact Cold Enough temperature under set point for Customer Care if Adjust the temperature to a cooler set point over 12 hours persistent Ensure unit is not located in excessive L R Door Left or right door Verify door is closed ambient temperatures or in direct sunlight Open 5M switch open for and sealing Contact Ensure the door is closing and sealing more then 5 Customer Care if properly minutes persistent found at the bottom of the unit Ensure t of any dirt or lint build up nsure nothing is blocking the front grille the condenser coil is clean and free ERROR NOTIFICATION The 3000 model series continuously monitors a series of inputs and parameters to ensure proper and efficient operation of your unit Should the system detect a fault an error notification will be displayed on the user interface See below for a list of errors NOTE Single zone models will not use L left or R right zone indicators in error notification ID Description Solution No Comm Unit lost Disconnect and communication to reconnect power to the display unit Contact Cu
57. n at the end of the cooling cycle for a given amount of time Fan Delay On Fan Delay On is the amount of time in minutes the fan will be delayed from starting from the beginning of a cooling cycle Fan Delay Off Fan Delay Off is the amount of time in minutes the fan will continue to run at the end of a cooling cycle To access Fan Delay 1 Press amp to select Fan Delay 2 Press To alter fan settings 3 Press to select either Fan Delay On or Fan Delay Off and press The chosen option will begin to flash 4 Press B or O to change settings 5 Press to confirm NANC e SERVICE ERATING INSTRUCTIONS MAINT To exit Fan Delay press E to select Return to Menu and press amp to confirm Showroom Mode Up RETURN TO MENU SHOWROOM MODE OFF amp U LINE H gt Down Showroom displays a number of features and allows the unit to be powered on without running the cooling system To toggle showroom mode 1 Press to select Showroom Mode 2 Press 3 Press to select Off and press off will begin to flash 4 Press B or amp to toggle between off and on 5 Press to confirm If set to on showroom mode will begin immediately To exit showroom mode press and hold for 5 seconds and release The display will show a countdown to switching the unit off Press O a
58. n blade and vents should be unobstructed and free of any dust buildup Troubleshooting Extended 5 USER GUIDE U LINE u line com SAF ETY e INSTALLATION amp INT EGRATION OP Control Operation Service TO ENTER THE MAIN SERVICE MENU ERATING INSTRUCTIONS MAINT TO GO TO NEXT SUB MENU ITEM NANC e SERVICE PRESS AND HOLD FOR 5 SECONDS 4 AND SCROLL YOU MUST ARROW UP TO RETURN TO MENU TOUCH AND RELEASE TO RETURN TO THE MAIN MENU ENTER amp EXIT THROUGH SERVICE MENU SUB MENU ITEM ACTUAL TEMPS MENU ALL ERRORS RELAY STATUS REVIEW ACTUAL TEMPS SHOWS TEMPERATURES WITHOUT OFFSETS EACH ZONE HAS AN cm ACTUALTEMPS EVAP AND AIR THERMISTOR EACH UNIT HAS AN AMBIENT THERMISTOR WEEE UA eae DISPLAYS THE NUMBER OF TIMES AN ERROR HAS OCCURRED MALL ERRORS REVIEW ERROR LOG OR SCROLL TO THE END TO ERASE THE ERROR CODES p NO COMM B DISPLAYS THE CURRENT STATUS OF THE RELAYS ON THE BOARD SEY See PEPAY STATUS not all relays are used on all models E ON RELAVTOCGLE ALLOWS THE RELAYS TO BE TOGGLED ON OFF TO CHECK RELAY amp COMPONENT SE cee YOU CAN TURN ON MULTIPLE RELAYS TO CHECK A ZONE COMP FAN ETC gt NUU OFF RETURN TO MENU INPUTS DISPLAYS DOOR SWITCH STATE TEST INPUT AND USB STATE S GEE noon COED
59. ng Cleaning 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE e SERVIC NOTICE The drain pan was not designed to capture the water created when manually defrosting To prevent water from overflowing the drain pan and possibly damaging water sensitive flooring the unit must be removed from cabinetry To defrost 1 Disconnect power to the unit 2 Remove all products from the interior 3 Prop the door in an open position 2 in 50 mm minimum 4 Allow the frost to melt naturally 5 After the frost melts completely clean the interior and all removed components See INTERIOR CLEANING 6 When the interior is dry reconnect power and turn unit on Cleaning 2 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE SERVIC Cleaning Condenser INTERVAL EVERY SIX MONTHS To maintain operational efficiency keep the front grille plinth strip base fascia free of dust and lint and clean the condenser when necessary Depending on environmental conditions more or less frequent cleaning may be necessary Disconnect electric current to the unit before cleaning the condenser NOTICE DO NOT use any type of cleaner on the condenser unit Condenser may be cleaned using a vacuum soft brush or compressed air 1 Remove the grill
60. ng cabinetry and due to differences in cabinetry may not align perfectly with the door The appliance will need up to 34 1 2 876 mm to the underside of the counter to leave room for leveling adjustments A single prepared frame with insert must not weigh more than 20 Ibs 10 kg Integrated Frame Preparation 1 Cut the main panel to the appropriate dimensions below For details see the drawings on the next page ERATING INSTRUCTIONS e MAINTENANCE e SERVIC 3 Prepare the insert s that will back up the handleless design Wooden Insert Cut 1 8 3 mm thick wooden insert s to the dimensions below Wooden insert width Wooden insert depth 23 3 8 594 mm 3 1 2 89 mm Main panel width Main panel depth 23 3 8 594 mm 28 13 16 732 mm 2 Create the top design for the handleless feature and the 1 8 3 mm notch for the insert s indicated on the Top Detail drawing on the next page x Wooden Insert ie Top Design and Insert Notch an Main Panel Cutout Integrated Frame 4 Optional Stain or finish frame and wooden insert to desired stain or color Be sure to closely follow the instructions provided by the manufacturer NOTICE If finishing panel or wooden insert all sides must be finished to prevent warping 5 Attach the insert to the frame Wood glue or equivalent adhesive should be used to attach insert to frame Attach
61. nit back in place NOTICE The pin can be removed to return the door swing back to its original 115 swing by tapping the pin out from the bottom of the hinge 2 Remove hinge cover by lifting top and bottom of hinge CLOSER cover and sliding the cover inwards to remove from The door hinge has a self closing feature that engages hinge when the door is open approximately 6 150 mm about 25 Door Stop 1 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE e SERVIC Door Adjustments DOOR ALIGNMENT AND ADJUSTMENT Z Align and adjust the door if it is not level or is not sealing properly If the door is not sealed the unit may not cool T 25 Torx Screw properly or excessive frost or condensation may form in the interior NOTICE Properly aligned the door s gasket should be firmly in contact with the cabinet all the way around the door no gaps Carefully examine T 25 Torx Screw the door s gasket to ensure that it is firmly in contact with the cabinet Also make sure the door gasket is not pinched on the hinge side of the door REVERSING THE DOOR 1 Open door A CAUTION 2 Remove top hinge cover by lifting top and bottom flaps and slide inwards Repeat on bottom hinge Do not attempt to use the door to raise or pivot your unit
62. ny other theory of liability Warranty 6 2014 Rev H Warranty 2 U LINE USER GUIDE u line com e SERVICE NANC RATING INSTRUCTIONS MAINT GRATION OP TY e INSTALLATION amp INT SAF Wire Diagram ATEGWASSV Aove 02z ama WV so AYO YAMOd 4 522 mous ASL LIMA asm qa 8 1H91M g d YYLNIN ASL DY O o ofe LOH 5 ale E NY4 YISNIANOD YOSSIdWOD OL ond AWD OD z 3 ale ie YOLYYOdYAJ c gS y O af LHDI1 1 1 LIOA 5 MOTIJA M N3399 10 NIJYD ith 5 o Sll ONNOY yonvuo o S YOSSJYdNOD OL wa ofo sovz 022 ama yYva ale dWAL LNJISWV ASLI 3LIHM 2 Se alg SIHDLIMS HOO 9 4 ale HDLIMS YOO 1 1 Aov2 022 ama yva ofo ASL ALIHM DNAd TWHLN3N oie at duvog ale S AWIL dvAa A A gfe dWAL INOZ J P ToulLNoD PAA LOA 062 022 ee ooo0000j OO9O9D OO0000 Oo YOSSAYdWOD O gt Dv swa O NaaHD SS TaNnoud aovz 0zz 1a Yva s ASL ALIHM AW144 Wwuinan F 0 ama Hon QVOTYSAO NadO WVYDVIC ONIMIM Y 8rEzY Wire Diagram
63. oard If connections are valid replace Zone T Short circuit shorted EF U LINE H RETURN TO MEN ALL ERRORS NO COMM 0 ZONE T OPEN 0 the thermistor Evap T Evaporator Check thermistor connection to Short thermistor circuit harness for moisture or Down short corrosion Also check connection where thermistor harness attaches to main board If connections are valid replace the thermistor Control Operation Service 2 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVICE ID Description Solution Relay Status Amb Ambient Check thermistor connection to Up Thrm thermistor circuit harness for moisture or Select Short shorted corrosion Also check connection where thermistor harness attaches to main board If connections are valid replace the thermistor amp gt RETURN TO MENU RELAY STATUS U LINE H MULL COND DEF LVLV RTA OFF OFF OFF _ OFF Temp Hi Zone temperature Is condenser coil clean Is 6H 10 C over set condenser fan operating Check point for over 6 zone thermistor for correct Down hours resistance Verify thermistor connections are clean and Relay status displays the current state of each relay While intact Check zone valve
64. obstruction Do not store explosive substances such as aerosol cans with flammable propellant in this appliance Requirement for an external switch in the fixed wiring is specified Safety and Warning 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OP Use care when moving and handling the unit Use gloves to prevent personal injury from sharp edges If your model requires defrosting DO NOT use medical devices or other means to accelerate the defrosting process DO NOT use an ice pick or other sharp instrument to help speed up defrosting These instruments can puncture the inner lining or damage the cooling unit DO NOT use any type of heater to defrost Using a heater to speed up defrosting can cause personal injury and damage to the inner lining NOTICE Do not lift unit by door handle Never install or operate the unit behind closed doors Be sure front grille plinth strip base fascia is free of obstruction Obstructing free airflow can cause the unit to malfunction and will void the warranty Failure to clean the condenser every six months can cause the unit to malfunction This could void the warranty Allow unit temperature to stabilize for 24 hours before use Do not block any internal fans Use only genuine U Line replacement parts Imitation parts can damage the unit affect its operation or performance and may void the warranty ERATING INSTRUCTIONS
65. oggle menu press B to select Return to Menu and press to confirm ERATING INSTRUCTIONS MAINTENANCE SERVICE Input Status Up Select gt RETURN TO MENU INPUT STATUS DOOR OPEN JE IN2 OPEN 6 U LINE H Down Input status displays the current state of each available input ID Description Type Door Door Switch Open Closed Test Input Factory Test Input Open To access Input Status 1 Press amp to select Input Status 2 Press 3 Press B and amp to scroll through available information To exit the Input Status menu press amp to select Return to Menu and press to confirm Control Operation Service 4 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OP Outputs Up Select gt RETURN TO MENU 4d OUTPUTS EVAP FAN 0 wy CONDENSER FAN 0 ca o S 6 U LINE H Down Outputs is used to monitor the state of DC outputs ID Description States Evap Fan Evaporator Fan 0 100 Condenser Fan Condenser Fan 0 100 Light Zone Lighting Off Low Med High To access Outputs 1 Press to select Outputs 2 Press 3 Press B and amp to scroll through available information To exit the Input Status menu press E to select Return to Menu and press to confirm Offsets Up Select gt RE
66. oom No refrigeration Lower than temperature temperature temperature normal cool cool cool System Diagnosis Guide 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVICE Compressor Specifications A DANGER Electrocution can cause death or serious injury Burns from hot or cold surfaces can cause serious injury Take precautions when servicing OVERLOAD PROTECTOR STARTING RELAY RELAY COVER CAPACITOR this unit Electrical Relay and Overload Protector Disconnect the power source EMX20CLC Refrigerant R600a 3 z Voltage 220 240 VAC Do not stand in standing water when working 9 Frequency 50 Hz around electrical appliances Run Cap 2UF 380 VAC Start Winding 34 9 Ohm at 77 F 25 C Make sure the surfaces you touch are not hot or Run Winding 47 8 Ohm at 77 F 25 C frozen ff LRA 1 9A FLA 0 3 A Do not touch a bare circuit board unless you are Starting Device TSD wearing an anti static wrist strap that is Overload 4TM110KFBYY 53 grounded to an electrical ground or grounded water pipe All resistance readings are 10 Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and S pins To measure the run winding resistance measure across the C and R pins Also check S to R and y
67. oring while settings are restored When restoration is complete Restoring will return to Restore To exit Factory Default press amp to select Return to Menu and press to confirm Help Up Select RETURN TO MENU a i Model 3045WC T U LINE 1 800 779 2547 Down To access the Help Menu select Help from the Customer Menu Press B or amp to scroll through available information The Help screen displays the following e Model e U Line contact information e Software version Serial Number To exit the Help menu press E to select Return to Menu and press to confirm Control Operation 6 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVIC Sabbath Mode Up Select 4 gt RETURN TO MENU SABBATH MODE OFF ww U LINE amp Down This unit offers a Sabbath mode for users who require this functionality during Sabbaths Sabbath mode disables system responses to user initiated activities and all external functions including lighting display and audible alarms The unit will still maintain internal temperatures and set points To enable Sabbath Mode 1 Open the unit s door to activate the display 2 To access the Customer Menu hold for 5 seconds 3 Press 4 or to scroll through available selections 4 Se
68. ou should get the sum of the run and start windings To ensure the windings are not shorted check the S and R to ground Compressor Specifications 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OP Troubleshooting Extended SPECIFIC ERRORS AND ISSUES The technically advanced diagnostic capabilities of the electronic controls utilized on the 3000 series units allows for easy and thorough trouble shooting Navigation of the control is the key and is explained in the CONTROL OPERATION section of the manual along with control button layout control function descriptions a service mode menu and service menu selection explanations Verification of temperature and thermistor performance can be identified by directly viewing actual temperature readings in the service mode Component failure issues can be identified through service mode menu selection Relay Toggle Individual components can be switched on and off to check for both proper function of a specific component and also delivery of supply voltage to the components through the relays and DC outputs located on the relay power board Included in this section is some diagnostic tips and as always if additional help is required please contact the U Line Corp Customer Care Facility at 1 800 779 2547 for assistance ERATING INSTRUCTIONS e MAINTENANCE SERVICE MAIN CONTROL The main
69. perly The main control board is extremely robust and should rarely require service Most issues are external to the control Reference troubleshooting for more information To access Self Test 1 Press to select Self Test 2 Press 3 Press B and amp to scroll through available information To exit the Self Test Press J to select Return to Menu and press amp to confirm Differentials Up Select niet U LINE amp Can be displayed in Celsius Down Differentials are used to determine the maximum variation from set point and have a range of O through 10 The table below shows the effect of differentials on cooling cycles with a set point of 45 F 7 C NOTE Air temperature does not reflect product temperatures Differential Cycle Start F C Cycle End F C 0 45 7 43 6 1 46 8 43 6 2 46 8 41 5 3 48 9 41 5 4 50 10 39 4 5 50 10 37 3 ERATING INSTRUCTIONS MAINTENANCE SERVICE The graph below shows a unit s cooling cycle over time with various differentials m 1 Differential 2 Differential 3 Differential Set Points Up RETURN TO MENU SET POINTS ZONE 3 C T Rep E Down The Set points menu contains options to modify both the Zone and Evap set points Changes to the zone set point will be
70. personal injury is suspected related to a U Line product please take the following steps 1 U Line Customer Care must be contacted immediately at 1 800 779 2547 2 Service or repairs performed on the unit without prior written approval from U Line is not permitted If the unit has been altered or repaired in the field without prior written approval from U Line claims will not be eligible SERVICE INFORMATION Answers to Customer Frequently Asked Questions are available at u line com under Customer Care or you may contact our Customer Care group directly contact information below GENERAL INQUIRIES SERVICE amp PARTS ASSISTANCE U Line Corporation Monday Friday 8 00 am to 5 30 pm UTC GMT 5 8900 N 55th Street T 1 800 779 2547 ilwaukee Wisconsin 53223 USA F 1 414 354 5696 onday Friday 8 00 am to 4 30 pm UTC GMT 5 Service Email onlineservice u line com T 1 414 354 0300 Parts Email onlineparts u line com F 1 414 354 7905 Email sales u line com u line com CONNECT WITH US f wW D Q rub in S Y blog Designed engineered and assembled in WI USA Introduction 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OP Safety and Warning NOTICE PLEASE READ all instructions before installing operating or servicing the appliance SAFETY ALERT DEFINITIONS Throughout this guide are safety items labeled with a Danger Warning or Caution based on the risk type
71. poses Thermistor connections must be kept clean A thermistor connection that has become corroded can cause resistance values from the thermistor to change as they pass through a dirty connection to the board It is for that reason that we apply die electric grease to all of our thermistor connections Die electric grease will help to keep thermistor connections clean and dry If you change a thermistor in the unit please re apply die electric grease to the connection If you encounter a dirty thermistor connection you should replace the thermistor and the thermistor harness ERATING INSTRUCTIONS MAINT Thermistor Resistance Data NANCE SERVICE Temp F Temp C ae Sy 4o 40 tesis7 31 35 121795 22 30 88766 13 25 65333 4 20 48614 5 15 36503 14 10 27681 23 5 21166 Oooo To o T oa 41 5 12696 y so io ost 59 15 7855 6 2 6246 77 25 5000 86 30 4029 95 35 3266 104 40 2665 113 45 2186 122 50 1803 131 55 1495 140 60 1247 149 65 1044 167 75 743 5 Thermistor 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVICE Defrost These units are manual defrost To defrost unit remove ice bucket Turn unit off Use toweling inside to absorb water as it melts
72. re is installed 1 Cut the panels to the dimensions listed in the diagram below 2 Optional Stain or finish panel to desired stain or color Be sure to closely follow the instructions provided by the manufacturer 3 Optional Install handles and hardware NOTICE When applying an integrated frame to a unit ensure that both sides are finished in order to prevent warping In some frame installations the panel may be visible through the glass while the door is open Integrated Frame Integrated Pane Dimensions 1 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OP HANDLELESS INTEGRATED FRAME The following procedure is designed to provide a finished handleless frame for a 24 600 mm door that seamlessly integrates with its surrounding cabinetry NOTE Many cabinet manufacturers provide a ready solution for a handleless integrated design that can be easily applied to your U Line 3000 Series model Consult your cabinet manufacturer for applicable design and installation details The cabinet manufacturer s solution to this design and integration detail will often result in an integrated frame solution wherein the size of the frame may result in a height dimension taller than what we specify This can be achieved provided the additional height is positioned above the appliance door NOTICE The integrated frame aligns with the surroundi
73. re open exposed to natural elements This unit is designed to operate between 50 F 10 C and 90 F 32 C Higher ambient temperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of direct sunlight and away from heat generating equipment In climates where high humidity and dew points are present condensation may appear on outside surfaces This is considered normal The condensation will evaporate when the humidity drops Damages caused by ambient temperatures of 40 F 4 C or below are not covered by the warranty Environmental Requirements 1 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OP Electrical SHOCK HAZARD Electrical Grounding Required Never attempt to repair or perform maintenance on the unit until the electricity has been disconnected Never remove the round grounding prong from the plug and never use a two prong grounding adapter Altering cutting or removing power cord removing power plug or direct wiring can cause serious injury fire loss of property and or life and will void the warranty Never use an extension cord to connect power to the unit Always keep your working area dry If the detachable type electric supply cord is damaged it must be replaced by an equivalent cord available from the manufacturer or its service agent E
74. roduction month In most cases warranty status can be verified by the production date information within the serial number e Alternatively a Proof of Purchase or equivalent may submitted with the warranty claim to document Warranty Claims 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVICE Ordering Replacement Parts Parts may be ordered on line by Fax or on the phone See our contact information below www U LineService com with service login FAX Number 1 414 354 5696 Phone Number 1 800 779 2547 NOTICE Use only genuine U Line replacement parts The use of non U Line parts can reduce speed of ice production cause water to overflow from ice maker mold damage the unit and void the warranty Warranty parts will be shipped at no charge after U Line confirms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U Line requires the return of original parts we will inform you when the parts order is taken This requirement will be noted on your packing list A prepaid shipping label will be included with the replacement part Please enclose a copy of the parts packing list and any labor claims with your return Please be sure the model and serial numbers are legible on the paperwork Tag the part with the reported defect
75. stomer Care if persistent L R Zone T Left or right zone Contact Customer Open thermistor circuit Care open Amb Thrm Open Ambient thermistor Contact Customer circuit open Care L R Zone T Left or right zone Contact Customer Short thermistor circuit Care shorted Amb Thrm Short Ambient thermistor Contact Customer circuit shorted Care CHECKING PRODUCT TEMPERATURE To check the actual product temperature in the unit 1 Partially fill a plastic nonbreakable bottle with water Insert an accurate thermo Tighten the bott Place the bottle in the desi e cap securely meter red area for 24 hours Avoid opening the unit during the testing period Troubleshooting 2 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVICE 6 After 24 hours check the temperature of the water If required adjust the temperature control in a small increment see CONTROL OPERATION Causes which affect the internal temperatures of the cabinet include e Temperature setting e Ambient temperature where installed e Installation in direct sunlight or near a heat source e The number of door openings and the time the door is open e The time the internal light is illuminated This mainly affects product on the top rack or shelf e Obstruction of front grille
76. thermistor cover Evaporator fan operation is also determined by door switch state If the door switch circuit opens the fan will stop When the door switch circuit is closed the fan will either continue running with the cooling cycle or if not currently cooling the fan will run for 1 minute to circulate air and clear any condensation that may have appeared on glass doors and shelves Evaporator Cover Screws Note If the unit is set to sabbath mode the evaporator fan will no longer respond to the state of the door switch In order to operate efficiently the evaporator fan blade and vents should be unobstructed and free of any dust buildup 11 Grasp evaporator cover pull forward and up as bottom of cover is installed behind the front edge of the drain trough Evaporator Fan Replacement Should the evaporator fan need to be replaced follow the 12 While pulling the evaporator cover clear of the unit it steps below may be necessary to use your free hand to manipulate the fan plug end through the pass through hole 1 Remove any product from the unit 2 Uninstall unit Remove Fan and Cover 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINT 13 Remove the 4 screws mounting the fan shroud to the evaporator plate I lt m _ ee w eS i x E gt Air Flow 1
77. tory default setting Factory defaults may be restored through the service menu Precautions must be taken while working with live electrical equipment Be sure to follow proper safety procedures while performing tests on live systems Troubleshooting Extended 2 USER GUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS e MAINTENANCE SERVICE FAULT SYSTEM DIAGNOSIS GUIDE Error Solution 1 Solution 2 Solution 3 No Comm nspect Customer UI and Data Cable if defective replace entire door Zone T Open nspect zone thermistor nspect main control wire harness connection Replace if necessary for splits or breaks Repair split or cut cabling Evap T Open nspect evaporator thermistor nspect main control wire harness connection Replace if necessary for splits or breaks Repair split or cut cabling Amb Thrm Open Zone T Short nspect ambient thermistor connection Replace if nspect thermistor cable for pinch points or damage Replace if necessary necessary nspect main control wire harness for splits or breaks Repair split or cut cabling nspect wire harness from main control board for pinch points or damage Repair split or pinched cabling Evap T Short nspect thermistor cable for pinch points or damage Replace necessary
78. tual Temp option in the service menu will display raw thermistor readings without calculating offsets 1 Press amp to select Actual Temps 2 Press 3 Use B and amp to scroll through available thermistor connections are valid replace readings To exit the Actual Temps menu press E to select Return to Menu and press amp to confirm All Errors Up Error ID Number Of Occurrences the pins for the red and black conductors If 5 VDC is not present replace the main control board If 5 VDC is present replace the communication cable Zone T Zone thermistor Check thermistor connection to Open circuit open harness for moisture or corrosion Also check connection where thermistor harness attaches to main board If connections are valid replace the thermistor Evap T Evaporator Check thermistor connection to Open thermistor circuit harness for moisture or open corrosion Also check connection where thermistor harness attaches to main board If the thermistor Amb Ambient Check thermistor connection to Thrm thermistor circuit harness for moisture or Open open corrosion Also check connection where thermistor harness attaches to main board connections are valid replace the thermistor Zone thermistor Check thermistor connection to harness for moisture or corrosion Also check connection where thermistor harness attaches to main b
79. ue to differences in floor construction or surrounding cabinetry the panel may not sit flush with the top of the door ERATING INSTRUCTIONS e MAINTENANCE e SERVIC 6 Secure integrated eu panel to door using Clamp clamps A robust tape may also be used U Line recommends the use of bar clamps to secure the panel to the door If using Wood tape be certain the Panel tape will not damage panel upon removal Door Drawer fi inish 7 Using a 7 64 Bar 3 mm drill bit drill Clamp 6 pilot holes into the wood panel 1 2 12 mm deep using the holes in the door frame as a guide NOTICE It is important to ensure that all drilled holes are drilled to the correct depth in order to avoid splits in the wood when hardwood is installed 8 Locate 6 of the 6x 1 1 2 38 mm screws provided with your unit 9 Using a Phillips screwdriver place one screw into each of the 6 pilot holes and screw down Do not overtighten screws 10 Ensure the screws sit flush against the bottom of the channel 1 Integrated Panel Integrated Panel 7 Integrated Panel Installation 1 USERAGUIDE U LINE u line com SAFETY e INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS e MAINTENANCE e SERVIC 11 Remove clamps from door NOTICE If panel requires additional adjustment after removing clamps slightly loosen each screw and adjust panel as necess
80. untry specific listing of importers please visit www u line com intl In no event shall such notification be received later than 30 days after the expiration of the applicable warranty period U Line may require that defective parts be returned at your expense to the importer or directly to U Line located in Milwaukee Wisconsin USA for inspection Any action by you for breach of warranty must be commenced within two years after the applicable warranty period If any applicable national law provides for a minimum mandatory warranty period that is longer than the aforementioned period of two years from the date of purchase such longer period shall apply THIS LIMITED WARRANTY IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE ALL OF WHICH ARE DISCLAIMED U Line s sole liability and your exclusive remedy under this warranty is set forth in the paragraphs above U Line shall have no liability whatsoever for any incidental consequential or special damages arising from the sale use or Warranty 1 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION e OPERATING INSTRUCTIONS MAINTENANCE SERVICE nstallation of the product or from any other cause whatsoever whether based on warranty express or mplied or otherwise based on contract tort or a
81. y be required The following conditions are excluded from this limited warranty damage caused by outdoor use as these units are not suitable for outdoor use use of cleaners other than the recommended stainless steel cleaners and U Line Clear Ice Maker cleaner installation charges damages caused by disasters or acts of God such as fire floods wind and lightning damages incurred or resulting from shipping improper installation unauthorized modification or misuse abuse of the product customer education calls food loss and spoilage door and water level adjustments ERATING INSTRUCTIONS MAINTENANCE SERVICE except during the first 30 days from the date of installation defrosting the product adjusting the controls door reversal and cleaning the condenser U Line products are designed to operate in ambient temperatures between 10 C and 32 C unless otherwise noted in the product manual Exposure to temperatures outside this range may cause degradation of performance and issues such as lower ice production or spoiled contents that are not covered under the terms of this warranty as a result of that exposure U Line product may not be subjected to temperatures below 5 C without following the winterization and vacation shutdown procedures in the user guide If a product defect is discovered during the applicable warranty period you must promptly notify your country importer For a co
82. y consumption by altering user set point differential lighting and tone settings When in Energy Saver Mode a small leaf icon will be displayed on the main screen 1 To enter Energy Saver Mode first select Energy Saver from the Customer Menu 2 Press to select Off in the menu wy 3 Press 4 Press B or amp to change the selection from Off to On 5 Press amp to confirm your selection 6 To return to the Customer Menu press and select Return to Menu 7 To cancel Energy Saver Mode simply return to the Customer Menu select Energy Saver and change On to Off Control Operation 4 USER GUIDE U LINE u line com SAFETY INSTALLATION amp INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVIC Languages Up Select 4 RETURN TO MENU LANGUAGES LU LI N E gt ENGLISH Down The U Line 3000 Series of models supports a number of display languages including English Spanish French and German 1 To change display language select Languages from the Customer Menu 2 Press amp to select English 3 Press English will begin to flash 4 Press B or amp to cycle through the available languages 5 Press amp to confirm your choice Sound Level B RETURN TO MENU 4d SOUND LEVEL dD U LINE N e HIGH Down Audible alarms and alert tones support four different Sound Leve

Download Pdf Manuals

image

Related Search

Related Contents

2 Drücken Sie  Russell Hobbs MAX-I-SWANN SW-U-WC202P User's Manual  DS_LEADER Hasty_Catalog_USAR_EN_ZCL08.264.EN.2  Déclaration de conformité selon la directive 97/23 CE    Wheel Accessory Products Catalog  Zanussi FM11B Use & Care Manual  Manual - Webstaurant Store  American Power Conversion BK400EI User's Manual  399 Español Tabla de contenido  

Copyright © All rights reserved.
Failed to retrieve file