Home

User's Manual CPS1000E-DE

image

Contents

1. Over Load Output Off Load exceed the rating of EPS Battery Missing In Line Mode Battery Missing High Temperature Output Off Low Battery Output Off Insufficient battery capacity Over Charge or AVR Error In Line Mode battery is overcharged or AVR is faulty Short Output Off Output Short Circuit Protection Line Input Output Error Output Off incorrect Input Output connection Cold Start Battery High Voltage Output Off the battery voltage is too high during cold start Copyright 2010 CyberPower Systems Inc Solution load to rating of Check total confirm the EPS Turn the EPS off check battery wiring and presence of battery Check fans function and air vent clearances Recharge the battery Inform service agents Check the EPS output to see if there is a short circuit Check Input connection Output Check the reason for battery over voltage 12 Problem Outlet does not provide power to equipment The EPS does not perform expected runtime The EPS will not turn on 13 TROUBLESHOOTING Possible Cause Circuit breaker has tripped due to an overload Batteries are discharged Unit has been damaged by a surge or spike Batteries are not fully charged Batteries are degraded The on off switch is designed to prevent the damage that rapidly turns it off and on The unit is not connected to an AC outlet The battery
2. Please refer to EPS Status Inquiry and Functions Setup section for more details AC Outlets The unit has two UK type outlets for connected equipment to ensure temporary uninterrupted operation during a power failure Max Output of is 10A Max Output wattage is 700W Note Maximum cord length is 10 meters and the cable O D must be 14AWG or greater AC Inlet AC input terminals Note The O D of the distribution cables must be 14AWG or greater DC Inlet Battery input terminals Note Maximum battery wiring cable length is 2 meters and the cable O D must be 4AWG or greater 8 Battery Switch Turn on off the battery switch and the battery source will be connected disconnected to the EPS unit The unit will only charge in the ON position 9 AC Output Circuit Breaker Located on the back of the EPS the circuit breaker serves to provide overload and fault protection 10 AC Input Circuit Breaker Located on the back of the EPS the circuit breaker serves to provide overload and fault protection 11 Battery Input Wiring Fault LED Battery input wiring fault LED will illuminate to indicate the wiring polarity is reversed 12 Bypass Switch Bypass switch provides the bypass for charge only In charger only mode AVR and battery backup will not work CPS1000E 5 Copyright 2010 CyberPower Systems Inc CPS1000E DE INSTALLATION GUIDE Note The installation must be done by professionals STEP1 Remove the
3. When the icons blink the value of each item can be changed by slightly pressing the toggle Step 4 To save the value and return to general mode press and hold the toggle for 4 seconds Note If the machine is left idle for over 30 seconds during setup it will turn off the backlight and return to general mode automatically Note If user wants to return to general mode without saving changes there are two methods 1 Wait for the backlight to turn off 2 Press and hold the Display toggle for 10 seconds Copyright 2010 CyberPower Systems Inc CPS1000E DE FAULT WARNING DISPLAY AND ALARM 1 Overheat Protection The EPS output will be interrupted After 30 seconds the machine shuts down and the LCD display output voltage is zero 2 Over Load Protection The EPS output will be interrupted After 30 seconds the machine shuts down and Over Load Icon lights on the LCD display 3 Battery Missing You should hear a long beep and Battery Indicator flashes 4 Low Battery Protection The EPS output will be interrupted After 30 seconds the machine shuts down and the LCD display output voltage is zero 5 following table shows each corresponding warning message on the LCD display and the alarm reacts during the machine shut down T LCD Warning Display Alarm Over Load Icon Constant tone Battery Icon Flash Beep Once Zero Output Constant tone Voltage Can Not Start Up None Condition
4. and battery backup mode 3 RUNTIME Meter This meter displays the run time estimate of the EPS with the current battery capacity and load Note This function of specified models cannot work 4 NORMAL MODE Icon This icon will illuminate when the EPS is working under normal conditions 5 ON BAT On Battery Icon When a severe brownout or blackout this icon appearing and an alarm two short beeps activated indicate that the EPS is working via its batteries Once the batteries are running out of power for a period of time an alarm two short beeps will appear continuously If this occurs it is recommended that save your files and turn off your equipment manually as soon as possible 6 SILENT MODE Icon This icon appearing indicates that the buzzer does not beep in the silent mode until the low battery capacity 7 OVER LOAD Icon This icon appearing and an alarm activated indicate that the overload condition To relieve the overload unplug your equipment from the EPS outlets until the icon disappears and the alarm stops being activated 8 LOAD CAPACITY Load CAPACITY is also shown on the bar chart equal 25 load capacity for each segment 9 BATTERY VOLTAGE BATT VOLTAGE indicates the voltage of battery 9 Copyright 2010 CyberPower Systems Inc CPS1000E DE EPS STATUS INQUIRY AND FUNCTIONS SETUP GENERAL MODE a Press the Display button to check the status of the EPS Items Unit Input Voltage V Output Vol
5. cover from the back of the machine Make sure both the POWER SW and the BATTERY SW are turned off and the Bypass SW is disabled 51000 STEP2 Connect the AC OUTPUT connections STEP3 5 Connect the batteries to the BATTERY INPUT Connect red positive battery cable to the red positive connectors on the EPS and external batteries Connect black negative battery cable to the black negative connectors on the EPS and external batteries WIRING FAULT LED will illuminate to indicate the wiring polarity is reversed Copyright 2010 CyberPower Systems Inc 6 CPS1000E DE STEP4 Connect the AC power source to AC INPUT Make sure AC power is off first IO STEP5 Turn on the BATTERY SW on the back of the machine STEP6 Turn on the Power Switch on the front panel The Power On Indicator and the LCD Display will blink 4 times Press the Display toggle Selected Switch once The output voltage showing on the LCD Display should be 220V This completes the start up process DISPLAY CPS1000E 7 Copyright 2010 CyberPower Systems Inc CPS1000E DE Press and hold the Display toggle switch for 4 seconds The machine will begin self test and enter Battery Mode for 10 seconds befor
6. AUTION Please use only VDE tested CE marked power cables to connect the loads to the EPS CAUTION When installing the equipment ensure that the sum of the leakage current of the EPS and the connected equipment does not exceed 3 5mA CAUTION Do not disconnect the mains cable on the EPS or the building wiring socket outlet shockproof socket outlet during operations since this would remove the protective ground of the EPS and of all connected loads DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT DO NOT use in any circumstance that would affect operation and safety of any life support equipment any medical applications or patient care DO NOT USE WITH OR NEAR AQUARIUMS reduce the risk of fire or electric shock do not use with or near an aquarium Condensation from the aquarium can cause the unit to short out DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR HEAT DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS S HOUSING Copyright 2010 CyberPower Systems Inc 2 SAFETY EN62040 1 1 EMI Conducted Emission IEC EN 62040 2 Category C2 Radiated Emission IEC EN 62040 2 Category C2 Harmonic Current IEC EN61000 3 2 Voltage Fluctuations and Flicker IEC EN61000 3 3 EMS IEC EN61000 4 2 IEC EN61000 4 3 IEC EN61000 4 4 EFT IEC EN61000 4 5 lightning surge IEC EN61000 2 2 Immunity to low frequency signals ESD RS M em ag poe CPS1000E DE 3 Copyright 2010 CyberPowe
7. CyberPower yDETs Quality Value User s Manual CPS1000E DE CyberPower Europe CyberPower Systems B V Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 0 40 2348170 Fax 31 0 40 2340314 Website http eu cyberpowersystems com E mail sales cyberpower eu com 01 0000151 00 CPS1000E DE Content SAFETY AND EMC INSTRUCTIONS 2 INSTALLING YOUR EPS eene nent 4 UNPACKING LI M MI RM SU E E 4 AUTOMATIC VOLTAGE REGULATOR 4 HARDWARE INSTALLATION GUIDE een 4 BASICOBERATIONES 22222222222 5 DESGRIPBION s 5 6 REPLACING THE BATTERY 8 DEFINITIONS FOR ILLUMINATED LOD 9 EPS STATUS INQUIRY AND FUNCTIONS 10 GENERAL 10 RM 10 FAULT WARNING DISPLAY AND 12 TROUBLESHOOTING oo 13 TECHNICAL SPECIFICATIONS 14 1 Copyright 2010 CyberPower Systems Inc CPS1000E DE SAFETY AND EMC INSTRUCTIONS This manual contains important safety
8. e returning to Line Mode Make sure the self test is ready or see the Definitions for illuminated LCD on page 9 for a list of alarm code definitions After ensuring the machine works normally reassemble the back cover The installation is now complete When the external battery needs to be maintained or replaced remember to turn the machine off Once off remove the AC power source and switch off the BATTERY SW before maintenance or replacing the batteries When the work is complete please start from Step 3 to re install the machine REPLACING THE BATTERY CAUTION Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery Battery service should only be done by qualified professionals CAUTION Use only the specified type and number of external batteries Please see the technical specifications for replacement batteries CAUTION The battery may present a risk of electrical shock Do not dispose of battery a fire as it may explode Follow all local ordinances regarding proper disposal of batteries Lead acid batteries should be recycled CAUTION not open or mutilate the batteries Released electrolyte is harmful to skin and eyes and may be toxic CAUTION The external battery cabinet must be provided with 100A 12V for models CPS1000E CAUTION Abaittery can present a high risk of short circuit current and electrical shock Take the following precautions before replacing the battery 1 Remove all
9. ic Voltage Compensation works automatically based on the system voltage settings d Static Frequency Tolerance There are 6 settings 1 2 4 6 8 1096 and the default setting is 10 Function description The settings may be adjusted to the quality of the electricity in use Copyright 2010 CyberPower Systems Inc 10 CPS1000E DE e Slew Rate Also called Dynamic Frequency Tolerance There are 5 different settings 0 25 0 5 1 2 4 Hz Sec The default value is 4Hz sec Function description Slew Rate indicates the tolerance of a device in accepting frequency variances The lower Slew Rate results in less tolerance but better protection for the connected loads f Low Battery Shutdown Voltage This function adjusts the EPS shutdown point according to the battery voltage The default setting is 10V with load g Mode Select The standard mode setting 2 and the robust mode setting 1 are provided to select Using the generators is suggested to select the robust mode setting 1 and using the computers is suggested to select the standard mode setting 2 The settable items are sorted by unit as in the following table Items Unit Delay Time Min Charging Current Nominal Output Voltage V Static Frequency Tolerance Slew Rate Low Battery Shutdown Voltage V Mode Select None Here displays the firmware version It can not be configured Firmware Version Step 3 Press and hold the toggle for 4 seconds
10. ical Dimensions L W H mm Weight Kg Agency Certificated Copyright 2010 CyberPower Systems Inc m O L Z O gt gt o 79 m gt zi O Z o CPS1000E DE 1000VA 700W AVR Double Boost amp Single Buck 140 300Vac 45 65Hz auto sensing Single Phase 0 40 LOAD Pure Sine Wave at 220Vac 5 40 100 LOAD Trapezoidal Wave at 220 5 Configurable for 220 230 240Vac 50 60 Hz 1 On Utility Circuit Breaker On Battery Internal Current Limiting lt 10 ms Typical Schuko Type 2 12V x 100Ah x 1 12V Sealed Maintenance Free Lead Acid Battery Fuse amp Relay Yes Yes Power On LCD Display On Battery Low Battery Overload 32 F to 104 F 0 C to 40 C 0 to 90 Non Condensing 153 208 241 8 2 CE SONCAP 14 CPS1000E DE CyberPower Here Quality Value For more information contact us at CyberPower Europe CyberPower Systems Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 0 40 2348170 Fax 31 0 40 2340314 Website http eu cyberpowersystems com E mail sales cyberpower eu com Entire contents copyright 2010 CyberPower Systems Inc All rights reserved Reproduction in whole or in part without permission is prohibited 15 Copyright 2010 CyberPower Systems Inc
11. instructions Please read and follow all instructions carefully during installation and operation of the unit Read this manual thoroughly before attempting to unpack install or operate your Emergency Power System EPS CAUTION prevent the risk of fire or electric shock install in a temperature and humidity controlled indoor area free of conductive contaminants Please see specifications for acceptable temperature and humidity range CAUTION To reduce the risk of electric shock do not remove the cover except to service the battery There are no serviceable parts inside except for the battery CAUTION 5 must be connected to an AC power outlet with circuit breaker protection Do not plug into an outlet that is not grounded If you need to de energize this equipment turn off and unplug the unit CAUTION To avoid electrical shock turn off the unit and unplug it from the AC power source before servicing EPS replacing the external battery or installing equipment CAUTION reduce the risk of fire only connect the EPS to a circuit with 10 amperes maximum branch circuit over current protection in accordance with the CE requirement CAUTION The building wiring socket outlet shockproof socket outlet must be easily accessible and close to the EPS CAUTION Please use only VDE tested CE marked mains cable e g the mains cable of your equipment to connect the EPS to the building wiring socket outlet shockproof socket outlet C
12. is worn out Mechanical problem Copyright 2010 CyberPower Systems Inc CPS1000E DE Solution First turn the EPS off and unplug at least one piece of equipment Wait 10 seconds reset the circuit breaker by pressing the button and then turn the EPS on Recharge the unit for at least 4 hours Contact CyberPower Systems about replacement batteries at service cyberpower eu com Recharge the battery by leaving the EPS plugged in Contact CyberPower Systems about replacement batteries at service cyberpower eu com Turn the EPS off Wait 10 seconds and then turn the EPS on The unit must be connected to a 220 230 240V outlet Contact CyberPower Systems about replacement batteries at service cyberpower eu com Contact CyberPower Systems via phone or visit our website at eu cyberpowersystems com CPS1000E DE Capacity VA Capacity Watts Operation Technology AC Input Input Voltage Range Input Frequency Range AC Output Number of Phase On Battery Typical Output Voltage Nominal Output Voltage Configuration Note On Battery Output Frequency Overload Protection Transfer Time Output Receptacles External Battery Voltage x Recommended Rating x Quantity External Battery Rating External Battery Type External Battery Protection Hot Swappable External Battery Extended Runtime Status Indication Indicators Audible Alarms Environmental Operating Temperature Operating Relative Humidity Phys
13. r etc The warranty prohibits the use of extension cords outlet strips and surge strips 4 Press the power switch to turn the unit on The power on indicator light will illuminate and the unit will beep once 5 If an overload is detected an audible alarm will sound and the unit will emit one long beep correct this turn the EPS off and unplug at least one piece of equipment from the battery power supplied outlets Wait 10 seconds Make sure the circuit breaker is depressed and then turn the EPS on 6 To maintain optimum battery charge performance make the EPS plugged into an AC outlet at all times Enabling the switch provides the bypass for charge only Copyright 2010 CyberPower Systems Inc 4 CPS1000E DE BASIC OPERATION DESCRIPTION G Power Switch Used as the master on off switch for equipment connected to the battery power supplied outlets 2 Power On Indicator 10 This LED is above the power switch It illuminates when the utility condition is normal and the EPS outlets are providing power free of surges and spikes Multifunction LCD Readout High resolution and intelligent LCD display shows all the EPS information with icons and messages For more information please check the DEFINITIONS FOR ILLUMINATED LCD INDICATORS section LCD Display Toggle Selected Switch Users can monitor EPS status and set up functions using the toggle The buzzer on off can also be controlled by the toggle switch
14. r Systems Inc CPS1000E DE INSTALLING YOUR EPS UNPACKING Inspect the EPS upon receipt The box should contain the following EPS unit x 1 User manual x 1 Power Cord x 1 AUTOMATIC VOLTAGE REGULATOR Utility power is inconsistent The EPS increases low voltage to computer safe 220 volts The EPS automatically provides battery backup External battery connection required if the voltage drops below 140 volts or exceeds 300 volts HARDWARE INSTALLATION GUIDE 1 Your new EPS may be used immediately upon receipt However recharging the external battery for at least 8 hours is recommended to ensure that the battery s maximum charge capacity is achieved Charging time varies with capacity and a 100Ah or great battery is recommended To recharge the external battery simply leave the unit plugged into an AC outlet Your EPS is equipped with an auto charge feature When the EPS is plugged into an AC outlet the external battery will automatically recharge The unit will charge when Battery Switch is ON whenever Power Switch is ON or OFF 2 DO NOT use with medical or life support equipment DO NOT use with or near aquariums as condensation may cause the unit to short out 3 After connecting the hard wires plug the EPS into a 2 pole 3 wire grounded receptacle wall outlet Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands e g air conditioner copie
15. tage V Load Capacity Battery Voltage V b Press and hold the Display toggle for 4 seconds e f the machine is in the Battery Mode it enters the silent mode Press again for 4 seconds it will return to normal buzzer mode e If the machine is in the Line Mode it proceeds to Self Test c If the Display toggle remains untouched for over 30 seconds the LCD backlight will turn off automatically SET UP MODE Step 1 Hold the Display toggle for 10 seconds to enter the EPS set up Mode LCD icon 1 2 lights indicate Set Up Mode Step 2 By pressing the Display toggle users can switch between setup functions User configurable functions are as follows a Delay Time The time delay between switching from Battery Mode to Line Mode There are 9 different settings The default setting is 0 minute Function description The machine will switch from Battery Mode to Line Mode after the AC power transmission reaches stability within the preset delay time b Charging Current The function adjusts the battery charging current according to the capacity of the connected batteries It can be configured for 0 25 50 75 and 100 The default setting is 25 100 indicates that charging current is about 15Amps C Nominal Output Voltage Configures the correct electricity voltage supplied in the area country where the EPS will be used 220V 230V and 240V may be selected The system default setting is 220V Function description AVR Dynam
16. watches rings or other metal objects 2 use tools with insulated handles 3 Do not lay tools or metal parts on top of battery or any terminals 4 Wear rubber gloves and boots 5 Determine if the external battery is inadvertently grounded If grounded remove the source of ground CONTACT WITH GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK Copyright 2010 CyberPower Systems Inc g CPS1000E DE DEFINITIONS FOR ILLUMINATED LCD 9 ii n n LOAD CAP INPUT OUTPUT TIME The LCD Display indicates a variety of EPS en um NNI operational conditions All descriptions apply 4 m when the EPS is plugged into an AC outlet and 2 17 4 turned on or when the EPS is on battery d ZEN o AES o ION 06 1 INPUT VOLTAGE Meter This meter measures the AC voltage that the EPS is receiving from the utility wall outlet The EPS is designed through the use of automatic voltage regulation to continuously supply connected equipment with stable 220 output voltage In the event of a complete power loss severe brownout or over voltage the EPS will rely on its external battery to supply consistent 220 output voltage The Input Voltage Meter can be used as a diagnostic tool to identify poor quality input power 2 OUTPUT VOLTAGE Meter This meter measures the AC voltage that the EPS is providing to the computer It displays normal line mode AVR mode