K-BUS R KNX/DALI Gateway User manual-Ver. 1

image

Contents

1. The selected DALI device can be removed from the group Gx via the object Telegram value 1 Delete the selected device from Group 1 16 Delete the selected device from Group 16 34 Eee LLL LLL LL LEE LLL LLLI LLL www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway 1byte C W 5 010 DPT_Value_1_Ucount 201 Selected Device Add to Group x 1 16 Channel A The selected DALI device can be added to the group Gx via the communication Telegram value 1 Add the selected device to Group I 16 Add the selected device to Group 16 2bytes CR 202 Selected Device Query Own Groups Channel A The communication object is used to query the group which the selected device belongs Each bit display one of the groups if the object is 0 the selected device does not belong to any group The information is provided in coded format in a 2byte value see table below Bit13 Bit12 Bitll Bit14 Bit10 bio uis Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bitl BitO Bit15 G8 o os E o la lca o G16 GI5 GI4 GI3 GI2 Gl1 G10 G9 Note Group short for G E g bit 6 and bit 10 are 1 other bits are 0 and then the selected device belongs to group 15 and group 3 Table 6 2 communication objects for every DAL
2. 10096 Last brightness value Select Min physical brightness DALI device turns on the lamp in the minimum physical brightness value If this minimum physical brightness value is less than the lower limit brightness value the brightness of the lamp is turned on in the lower limit value The lower limit brightness value can be set by the parameter Min brightness value If the 1094 10096 option is selected DALI device turns on the lamp with the preset brightness value If this 16 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway preset value is less than the lower limit brightness value turn on the lamp with the lower limit brightness value if this preset value is more than the upper limit brightness value turns on the lamp with the upper limit brightness value The lower upper limit brightness value can be set by the parameter Min Max brightness value If the last brightness value option is selected DALI devices light up with the last brightness value what is not 0 and a steady brightness value When the DALI device is in the dimming state the brightness value of this device can t be detected accurately by the Gateway so DALI Gateway just keep the last brightness value of the DALI device in the steady state Note The minimum physical brightness value is determined by the physical properties of DALI device different models o
3. S scene number 0 15 Telegram value Function 0 or 64 Recall scene 1 1 or 65 Recall scene 2 2 or 66 Recall scene 3 15 or 79 Recall scene 16 128 or 192 Store scene 1 129 or 193 Store scene 2 130 or 194 Store scene 3 143 or 207 Store scene 16 Note After the EIB bus voltage failure the modified scene value is stored 211 Recall Scene 1 2 X Y Scene 1 2 bit C W 1 022 DPT Scene AB 212 Recall Scene 3 4 Scene 3 4 bit C W 1 022 DPT Scene AB 213 Recall Scene 5 6 Scene 5 6 bit C W 1 022 DPT Scene AB 214 Recall Scene 7 8 Scene 7 8 bit C W 1 022 DPT Scene AB 215 Recall Scene 9 10 Scene 9 10 bit C W 1 022 DPT Scene AB 37 SSS i www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway 216 Recall Scene 11 12 Scene 11 12 1bit C W 1 022 DPT Scene AB 217 Recall Scene 13 14 Scene 13 14 1bit C W 1 022 DPT Scene AB 218 Recall Scene 15 16 Scene 15 16 bit C W 1 022 DPT Scene AB Via the communication objects the scenes are recalled in the form of 1 bit Telegram value 0 Recall Scene X 1 Recall Scene Y 219 Store scene 1 2 X Y Scene 1 2 bit C W 1 022 DPT Scene AB 220 Store scene 3 4 Scene 3 4 bit C W 1 022 DPT Scene AB 221 Store scene 5 6 Scene 5 6 1bit C W 1 022 DPT Scene AB 222 Store scene 7 8 Scene 7 8 bit C W 1 022 DPT
4. 1 16 Options 1 16 This parameter defines the end scene of the dynamic operation Parameterization of the selected scene is implemented in the Channel A parameter window Parameter End scene hold Time Options 1s 5s 24h This parameter defines the run time of the end scene After the operation time ends the dynamic device switches off 23 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway 5 4 Parameter window Control Parameter window Control can be shown in fig 5 4 Here sets group control and broadcast control DALI Gateway provides 16 groups Every DALI devices can be belonged to 16 different groups at the same time Thus more than one DALI devices can be controlled together via a communication object First of all put the controlled devices into a group when set parameters then the communication object Channel x Selected Group selects a group via its group number And then the devices of the selected group can be individually controlled via a communication object of switch dimming or set brightness value If properties of devices in the same group are different there will be different dimming effects for DALI devices Broadcast Control convenient for DALI gateway to control all DALI devices in the channel including switching relative dimming and set brightness value Note In the group control and broadcast co
5. Start scene 100 End scene Hold time Warning time Time Switch on 5 min 2 min telegram Note Switching a scene is not transition time so the brightness is changed quickly 9 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway When a DALI device is used as staircase lighting the first configure two scenes the start scene and the end scene and then set the parameters of the selected scenes for the DALI device e g brightness value The staircase lighting function is trigged via a 1bit communication object Ax switch If renewed triggering occurs during the operation time of the start scene or the end scene the runtime of the staircase lighting recommences In Dynamic operation mode when the object Ax switch receive a telegram value 0 the device is switched off immediately 4 2 6 Fault monitoring With the DALI Gateway it is possible to monitor four fault statuses ballast fault lamp fault short circuit or over current of DALI communication terminal and auxiliary supply exception These faults can be query via the follow communications Channel x Teleg Fault Ballast s fault of one or more ballast in the channel First of all the communication object Detect Ballasts detects the DALI devices via a telegram 1 then the gateway will query their fault status and send or read the fault status Chann
6. extra voltage supply It is able to use the Engineering Tool Software ETS ETS3 or later with a VD4 file to allocate the physical address and set the parameters The following functions can be set via the application program Switching dimming and set brightness value for each DALI device Scene control can configure up to 16 different scenes for each DALI device And there are two data types 3 www video star com cn marketing Q video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway to recall and store the scenes of the DALI device 1 bit and 1 byte Group control Every DALI devices can be belonged to 16 different groups at the same time And switching dimming and set brightness value for each group Can configure the min brightness value and the max brightness value for each DALI device Sendorresponse various status e g switch brightness auxiliary supply and communication etc Fault detection of lamps and ballasts for DALI devices LED display e g error run init Broadcast control switching dimming and set brightness value for all DALI devices Staircase lighting 2 Technical data Power supply Bus voltage EIB Current consumption EIB Power consumption EIB Auxiliary supply Current consumption Auxiliary supply Power consumption Auxiliary supply DALI Output Channel 21 30V DC lt 12mA 360mW 100 240V AC 50 60Hz 28mA at 220 V AC
7. REUS NOR ERR CUNG o Fea Teva e ER ENVASE VR V DE vob eluate 27 6 Description of communication objects rssnrnrnnvennnvvnnnnvnnnnnnnnnnnennnnnvnnnnnnnnnsnnnnennnnenvnnnsnnnnnnnnnennnnennnnnsvnnnsunnnsunevenen 31 6 1 Communication objects for individual DALI device eese nennen 31 6 2 Communication objects for every DALI device rrrnsnnnnenvnnenvnnenvnnsnvnnenvrnsnnrnennrnsnnnnssvrnsnnnnenvrnsnennesvrnsnnnnesvrnsvnnnernn 32 6 3 Communication objects for Group control esses enne enne nnne nennen nennen neret rnnt 35 6 4 Communication object for Scene control seeseeseseseseeeseeeseeenee enne nnne nnne nnne nennen nette nnne 36 6 5 Communication objects for the entire channel rrsnvrnonvnnnnvnnenvrnnnnrnnrnrnnnnrnennrnnnnenssnrnsnnnnesnrnsnvnnssvrnsnnnnenrnsnneeesnn 38 2 www video star com cn marketing Q video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway 1 General The KNX DALI gateway is designed for an intelligent building control system which is used to connect KNX bus with DALI bus As an interface device it can convert the telegrams from KNX bus into the information that DALI devices can recognize which includes DALI device address and control command and send the information to DALI network and control DALI devices e g switching dimming scene etc And the gateway can also detect fault of DALI device and feed back the
8. a telegram value 1 the DALI gateway first 40 E I IMH www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway queries whether there is no address of DALI devices in the channel if some devices are not address and then the DALI gateway will assign new address which follows the previous address to these devices For example there are 6 DALI devices in the channel and their address is 0 5 if the address of the new installed devices is 4 then you will need disconnect the previous 6 devices from the DALI bus and erase the address 4 of the new devices via the object and then reassign a new address via the object the new device will get the address 6 After finish the assignment you need reconnect previous 6 devices to the DALI bus Telegram value 1 Give DALI devices of no address to assign unused address 0 Erasure address of DALI devices in the channel 234 Device Number Channel A Ibyte CT 5 010 DPT Value 1 Ucount The communication object is used to report the number of the DALI device in the channel after the EIB or DALI bus voltage recovery or update DALI gateway initialization In addition the object can be also used to report the malfunctioning DALI devices If fault of one or more DALI devices is detected via the object detect ballasts the DALI gateway will report the malfunctioning devices in the channe
9. automatically to the EIB bus although the parameters set to On change of status The gateway queries their fault status only once when the object Detect Ballasts receives a telegram value 1 if query again a telegram value 1 need be received again Parameter cycle period between DALI and EIB bus The parameter is used to set whether report the communication status between the EIB bus and the DALI bus Options Yes No With the setting yes if the communication between the EIB bus and DALI bus fails the communication object Teleg Communication will send the telegram 1 to the EIB bus cyclically If the communication is normal a telegram 0 will be sent to the EIB bus and sent only once With yes the follow parameter is visible Parameter period of time This parameter is used to set the interval time between two telegrams that are sent cyclically Options 5s 10s 12h 30 ALLOIELLLLLLLLLLLLLLLLLLLLLLLLILLLLLLLZLLLLLLL ILL nen se www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway 6 Description of communication objects Communication object is the media of devices on the bus communicate with other device that is just communication object can communicate with the bus The role of each communication objects as following Note C in Flag column in the below table means t
10. devices A long operation 2 5s for updating DALI Gateway data A long operation gt 5s for assignment DALI addresses from 0 to 63 5 Guissa 45 C 25 C 55 C 25 C 70 C lt 93 except dewing Max number of Max number of Max number of communication objects group addresses associations 235 250 250 5 www video star com cn marketing Q video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB 3 Dimension and Connection Diagram 3 1 Dimension diagram K BUS U BTDG 01 00 1 Test Set KNX DALI Gateway s ce DALI Output negative pole DALI Output positive pole DALI Test Set button to test DALI devices update DALI Gateway data or assignment DALI addresses Red LED indicates programming the physical address Green LED flashing indicates the application layer works normally Programming button auxiliary power supply terminals Red LED Init ON indicates assigning DALI address from 0 Red LED Init flashing indicates updating DALI Gateway data Red LED Init fast flashing indicates initializing DALI devices or detect DALI devices fault Yellow LED Error ON indicates DALI devices fault Green LED Run ON indicates the Auxiliary supply and operation are normal EIB Bus terminal connection www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB
11. devices into a group when set parameters then the communication object Channel x Selected Group selects a group via its group number And then the selected group can be individually controlled via the following communication objects Channel x Selected Group On Off Channel x Selected Group Rel Dimming Channel x Selected Group Set Value No group is selected after a download or EIB bus voltage recovery The selected group stays selected after auxiliary supply or DALI bus voltage failure and recovery as well as after reallocate DALI addresses If DALI addresses are reallocated the devices of the group may have been changed The brightness of devices in the group are limited by their min and max brightness value 4 2 3 Scene control DALI Gateway provides 16 scenes and different brightness value can be preset for each scene Usually up to 64 scenes can be used in the KNX system but only the first 16 can be used for the DALI Gateway So only use the first 16 scenes when KNX devices control DALI devices via the scene function When a KNX device sends a scene 8 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway telegram to DALI Gateway the DALI devices which belong to the scene will be switched on with parameterized brightness The current brightness value can be also stored in a scene Switching a scene is not transition time so the brightn
12. fault 231 Telegram Communication Channel A 1bit CRT 1 005 DPT Alarm The communication object is used to report the communication status between the EIB bus and the DALI bus If the communication fails the object will send the telegram 1 to the EIB bus cyclically If the communication is normal a telegram 0 will be sent to the EIB bus and sent only once via the object Telegram value Fault of the communication between EIB and DALI 0 No fault 232 Detect Ballasts Channel A bit C W 1 010 DPT Start The communication object is used to detect the fault of ballasts and lamps of all DALI devices in the channel Telegram value 1 detect 0 no function If there are any malfunctioning devices in the DALI bus the LED Error on the DALI gateway will lighting and the object Device Number sends one or more telegrams to report the malfunctioning DALI devices In the case of devices fault the DALI gateway can be still operated normally 233 Assigned DALI Address Channel A 1bit C W 1 002 DPT Bool The communication object is used to assign DALI addresses to DALI devices If the object receives a telegram value 0 the addresses of all DALI devices in the channel will be erased After erased these devices will no longer have address and can not be controlled individually only can be operated via broadcast control If the object receives
13. fault information to KNX bus The KNX DALI gateway can connect up to 64 DALI devices Each DALI device can be switched dimmed or set brightness value via a communication object The DALI address assignment of 64 devices is implemented automatically or manually by the DALI Gateway meanwhile a DALI software tool is provided which is used to modify the DALI devices address and test DALI devices etc This manual provides detailed technical information about the DALI Gateway for users as well as assembly and programming details and explains how to use the gateway by the application examples 1 1 DALI System Introduction There are up to 64 slave units in the same DALI network and each salve units has a Short address A salve unit can be assigned to up to 16 different groups at the same time And host can send the information to all slave units The main features of DALI protocol asynchronous serial communication 1200 baud two wire differential signal a DALI interface can connect 64 salves each salve can be addressed individually but can t perform two way communication simultaneously 1 2 Product and functional overview The KNX DALI gateway is a modular installation device for fast installation in the distribution board on 35 mm mounting rails to DIN EN 60 715 The electrical connection is implemented using screw terminals The connection to the bus is implemented using the supplied bus connection terminal The input need be connected to an
14. gt 3 Van GVS Guangzhou Video star Electronics Industrial Co Ltd J KNX K BUS KNX DALI Gateway User manual Ver 1 BTDG 01 00 1 KNX EIB Intelligent Installation Systems heteet eccct www video star com cn marketing Q video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway Contents IOE EE 1 NE E AEE E E EE E E 3 1 1 DALI System InttodUctiOn nent no ner nett reete ne ene te erneuern ihe kei 3 1 2 Product and functional Overview neret eerie entr eadar ensi eaae ioa spera d ego suas eau vana de nos k e dea ka v aua 3 Eigene 4 3 Dimension and Connection Diagram ssorernnvnnnnnvnnnvvnnnnvnnnnnnennnnennnnnnnnnnnnnnnennnnennnnnsvnnnsnnnnennnnennnnnsvnnnsvnnnsnnnvennnvenener 6 3 1 Dimension diagrami pet 6 3 2 COMMECH OM CA STAI n E AAT E 6 4 Project design and application rtt eon ke VEs nean etu sands dusatsvsucevecesteubisssasesceesvousdsesersuudy 7 4 1 ETC M aa E e Rdn 7 4 2 Overview of the fUnCtionS s sisrrriseisini ineine etre aana EEEN ENEN TR ETRA caede ea REAA oe PNE Re NERA duene 7 42 1 Control of the DALLdEVICGS hausa eiie vadere ex RE ee ek khe eee fa cis ere cd E PEE EE ER 7 422 Group control of DALI d6yV1Ces eee erret ret tete never add Y I NE Rapt io 8 4 23 Scene control iecore irrito regn better ctore E EE de exe
15. object i e the device Ax only can be adjusted its brightness and the Dynamic operation is interrupted 4 Set the brightness via the object Ax Brightness the device Ax can be turned off or on via the object and the Dynamic operation is interrupted 5 3 Parameter window Dynamic The parameters window is only significant if the Dynamic mode has been selected for at least one of the 64 devices in the Channel A parameter window Only one dynamic operation can be defined for each DALI Gateway For the Dynamic operation the scenes used and the run times of the scenes are defined in the window 22 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway L 1 1 5 ENEDALI Gateway BNG 01 00 1 General set Dynamic Channel amp Control Status Start Scene 1 15 Start scene hold time End Scene 1 16 End scene hold time T Fig 5 3 parameter window Dynamic The parameter Start scenes 1 16 Options 1 16 This parameter defines the start scene of the dynamic operation Parameterization of the selected scene is implemented in the Channel A parameter window The parameter Start scene hold Time Options 1s 5s 24h This parameter defines the run time of the start scene After the operation time ends the end scene commences with its own operating time Parameter End Scene
16. process as shown below Brightness Start scene 100 End scene Hold time i Warning time Time Switch on 5 min 2 min telegram Note Switching a scene is not transition time so the brightness is changed quickly in the figure 21 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway 1 1 10 ENX DALI Gateway 1 fold General Channel A Dynamic Control Status Device Number A7 Device A7 Operation Mode Dynamic Dynamic Mode Min brightness value min physical brightness Max brightness value 1 00 Dim period to reach tum on brightness 2s Scene Number i Light scene value no change Send switch status response 1 0BJ Switch Do Send brightness status response DBJ Brightness ne OK Cancel Default Fig 5 2 parameter window Channel A dynamic The parameters of Dynamic operation have described in the Normal operation here no longer repeat to describe them During the Dynamic operation of device Ax if the follow operation is executed 1 Broadcast control then the Dynamic operation will be interrupted 2 Recall scene then the current brightness may be changed but the Dynamic operation is still continued 3 Dimming via the object Ax Relative Dimming the device Ax cannot be turned off or on via the
17. switch status or brightness status of the device is changed the object selected device status or selected device read brightness will send the latest switch status and brightness value to the EIB bus Select no you can use the Object selected device status and selected device read brightness to read the current switch status and brightness value of the selected device Parameter On change of selected device send fault lamp and fault ballast Options Yes No Select yes after selecting a DALI devices when ballasts or lamps status of the device be changed the objects selected device lamp failure or selected device ballast failure will send the latest lamp and ballast status to the EIB bus Select no you can use the object selected device lamp failure and selected device ballast failure to read lamp status and ballast status of the selected device Note First the lamp or ballast fault status of the selected device is detected via the object Detect Ballasts with the telegram value 1 then the gateway will query their fault status and send or response the fault status to EIB bus If via the object selected device lamp failure or selected device ballast failure to query directly their status the response status may be incorrect and the gateway will also not send the status automatically to the EIB bus although the parameter set to yes The gateway queries their fault status only once when t
18. visible which are used to set the brightness value and dimming rate of the selected group DALI Gateway can configure up to 16 different groups but all groups have the same dimming rate Parameter group number 1 16 The parameter is to select the group number you want to configure Options 1 16 Parameter group x power on Value The parameter is to configure the brightness value for the selected group when turning on Options Min physical brightness 10 20 100 When the parameterization value is great than or less than the limit brightness value that DALI device defined in the parameter window 5 2 these DALI devices in the group will turn on with their limit brightness value Parameter Dim period to reach turn on brightness This parameter defines the duration time which a dimming process requires from 046 to 10046 for a group i e dimming rate Options Immediate 0 7s 2s 90s This dimming time only affects dimming commands which are received via the communication object selected group on off or Selected group set value The time in proportion to the percentage of brightness adjustment for example the time is preset to 10s and then the brightness is adjusted from 0 to 50 the duration time will spent 5s The duration time of relative dimming is specified as 8s the time is also in proportion to the percentage of 25 www video star com cn marketing video star com cn Te
19. 5 GVS K BUS KNX EIB KNX DALI Gateway Number Name Object Function Description Group Addresses Length C R T Data Type Priority m2210 Scene 1 16 8 bit scene 1 Byte C F Low E211 Sence 1 2 Recall Scene 1 2 1 bit c 9 Low M212 Sence 3 4 Recall Scene 3 4 1 bit C Low 213 Scene 5 6 Recall Scene 5 6 1 bit CcC Y Low E214 Scene 7 8 Recall Scene 7 8 1 bit C Low H 215 Scene 9 10 Recall Scene9 10 1 bit o Low E216 Scene 11 12 Recall Scene 11 12 1 bit C Low 217 Sence 13 14 Recall Scene 13 14 1 bit c X Low E218 Scene 15 16 Recall Scene 15 16 1 bit E T Low E219 Scene 1 2 Store Scene 1 2 1 bit co f Low E220 Scene 3 4 Store Scene 3 4 1 bit C Low i221 Scene 5 6 Store Scene 5 6 1 bit Eo Low E222 Scene 7 8 Store Scene 7 8 1 bit c 4 Low E223 Sence 9 10 Store Sence 9 10 1 bit C 4 Low E224 Sence 11 12 Store Scene 11 12 1 bit C Low H225 Sence 13 14 Store Scene 13 14 1 bit e F Low H 226 Scene 15 16 Store Scene 15 16 1 bit E T Low Fig 6 4 communication objects for scene control NO Function Object Name Type Flags DPT 210 Control scenes Light scenes 1 16 Ibyte C W 18 001 DPT SceneControl be described below Assuming an byte command binary coding as MXSS SSSS Defined in detail as follows Via the communication object the scenes are recalled and stored in the form of 1 byte The definition of the Ibyte command will M recall the scene with 0 save the scene with 1 X 0
20. I device 6 3 Communication objects for Group control The following communication objects are used to realize the group control of DALI devices such as switch dimming set the brightness value Number Name bject Function Description Group Addresses Length eR TU Data Type Priority Bn Channel Selected Group 1 Byte GEN 8 bit unsigned value DPT Value 1 Ucount Low Gyzo4 Channel Selected Group ON OFF Dbit C W 1 bit DPT Switch Low H 205 Channel Selected Group Rel dimming 4 bit Es MN 3 bit controlled DPT Control Dimming Low 206 Channel Selected Group set value 1 Byte C W 8 bit unsigned value DPT Sealing Low Fig 6 3 communication objects for every DALI device 35 n CLE ram Tel 8620 39338986 www video star com cn marketing video star com cn Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway NO Function Object Name Data type Flags DPT 203 Selected Group Channel A lbyte CR W 5 010 DPT Value 1 Ucount The communication object is used to select the group to be controlled Before the object receives a new telegram value the group will remain the selected state After a download or EIB bus voltage recovery no group is selected Telegram value 1 Group I is selected 16 Group 16 is selected Note the values of 0 and 17 255 deselect i e no group is selected 204 Selected Group ON OFF Channel A bit C W 1 001 DPT Switch The communica
21. IB KNX DALI Gateway The default option is no regardless of whether the DALI devices brightness status change status will not be sent For option only if it change when the brightness status of DALI device is changed by switching dimming scene controlling etc and the status is stable the current status will be sent immediately For option always it is always reported the brightness status to the EIB bus regardless of whether the brightness values change Due to the communication rate of DALI protocol is relatively slow and the number of devices on the DALI bus there will have a certain delay for the brightness status telegram sending 5 2 2 Dynamic operation mode In Dynamic operating mode the parameter settings window of the device Ax is as shown in the following figure the dynamic mode is suitable for the control of the staircase lighting The Dynamic operation is composed of two of the 16 scenes First of all the scenes used and the run times of the scenes are selected in the parameter window 5 3 and then in the parameter window 5 2 to configure the brightness of the selected scenes The Dynamic operation is started via the object Ax Switch with a telegram value 1 when the run time of the start scene has elapsed the end scene commences When the run time of the end scene has elapsed the device will be switched off The end scene is equivalent to a cut out warning The
22. KNX DALI Gateway 4 Project design and application 4 1 Diagram AC230V KNX DALI Gateway DALI ballast AC230V power supply for DALI Gateway only 4 2 Overview of the functions 4 2 1 Control of the DALI devices In DALI Gateway application for control and monitoring of the DALI devices have the following two ways Control of individual DALI device Each of the individual 64 DALI devices can be switched on off dimmed or the brightness can be adjusted with just one Device Ax communication object As follow Device Ax Switch Status Device Ax Relative Dimming Device Ax Brightness value Status Control of every DALI device In addition the DALI Gateway features an address related individual option to control or read every single device First of all the communication object Channel x Selected Device selects a device via its device address Then the selected device can be individually controlled or read via the following communication objects Channel x Selected Device On Off Channel x Selected Device Rel Dimming Channel x Selected Device Set Value Channel x Selected Device Status switch status Channel x Selected Device Read Brightness brightness status Channel x Selected Device Lamp Failure lamp fault status First of all the communication object 7 5 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DA
23. LI Gateway Detect Ballasts detects the DALI device via a telegram 1 then the gateway will query its fault status and send or read the fault status Channel x Selected Device Ballast Failure ballast fault status First of all the communication object Detect Ballasts detects the DALI device via a telegram 1 then the gateway will query its fault status and send or read the fault status Channel x Selected Device Remove From Group Channel x Selected Device Add to Group Channel x Selected Device Query Own Group For example we want to control the device A4 First of all the communication object Channel x Selected Device selects the device via its device address 5 Then it can be directly controlled or monitored with the related communication objects such as switch dimming monitored its status etc In any case just one device can be selected No device is selected after a download or EIB bus voltage recovery The selected device stays selected after auxiliary supply or DALI bus voltage failure and recovery as well as after reallocate DALI addresses If DALI addresses are reallocated the selected device may have been changed 4 2 2 Group control of DALI devices DALI Gateway provides 16 groups Every DALI devices can be belonged to 16 different groups at the same time Thus more than one DALI devices can be controlled together via a communication object First of all put the controlled
24. PT_Switch This communication object is used to switch DALI device If the object receives a telegram value 1 the DALI device will be turn on with the preset value if it receives a value of 0 it will be turned off At the same time the communication object also sends the current switch state to EIB bus if the brightness value is greater than 0 the object sends a telegram 1 to the bus if the brightness value is 0 sends a 0 to the bus The specific sending way is defined by the parameter Send the switch status response please refer to the description of the parameters in section 5 2 1 Telegram value 1 on 0 off 31 EHr m3 gt 5J G enes www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway Ax Relative Dimming x 0 63 4bit C W 3 007 DPT_Control Dimming 64 127 Relative Dimming This object is used to dim up or down the brightness of DALI device The brightness will be dimed down when the object value is from 1 to 7 During this range smaller amplitude of dimming down with larger value that means it will be dimed down to the biggest amplitude with 1 while to the smallest amplitude with 7 and 0 means stop dimming It will be dimed up when the object value is from 9 to15 During this range smaller amplitude of dimming up with larger value that means it will be dimed up to t
25. S K BUS KNX EIB KNX DALI Gateway Parameter Permit lamp to be turned on via dim telegram This parameter sets whether it can turn on the DALI device through the relative dimming function in the case of the brightness value of DALI device is 0 Options No Yes If set to yes DALI device can be turned on by the communication object of the relative dimming when this DALI device is off If set to no DALI device cannot be turned on by the communication object of the relative dimming when this DALI device is off Parameter Permit lamp to be turned off via dim telegram This parameter sets whether it can turn off the DALI device through the relative dimming function in the case of the brightness value of DALI device is not 0 Options No Yes When this DALI device is on if yes is selected DALI device can be turned off via the communication object of the relative dimming if no is selected DALI device cannot be turned off and the brightness value only can be adjusted to the minimum brightness value Note The above two parameters have no effect to the relative dimming of group control and broadcast control I e in the case of group control and broadcast control the DALI device can be turned on or off via the relative dimming function no matter what the brightness of the device is Parameter Dim period to reach turn on brightness This parameter defines the duration time which a dimming process requires from 0 to 100
26. Scene AB 223 Store scene 9 10 Scene 9 10 1bit C W 1 022 DPT Scene AB 224 Store scene 11 12 Scene 11 12 bit C W 1 022 DPT Scene AB 225 Store scene 13 14 Scene 13 14 bit C W 1 022 DPT Scene AB 226 Store scene 15 16 Scene 15 16 bit C W 1 022 DPT Scene AB Via the communication objects the scenes are stored in the form of 1 bit The current brightness values f the DALI devices can be stored to the scene X Y After stored the scene will use the new brightness values to turn on the DALI devices Telegram value 0 Store scene X Store scene Y Note After the EIB bus voltage failure the modified scene value is stored Table 6 4 communication objects for scene control 6 5 Communication objects for the entire channel Number Name bject Function Description Group Addresses Length C R W T U Data Type Priority 207 Channel On Off 1 bit C r 1 bit DPT_Switch Low H 208 Channel Relative Dimming 4 bit ps p s 3 bit controlled DPT Control Dimming Low E209 Channel A Set Brightness Value 1 Byte C y 8 bit unsigned value DPT_Scaling Low Inn za Channel Telegr Fault Ballist s 1 bit C Ro TI Low H 228 Channel Telegr Fault 230 VAC 1 bit CR T Low H 229 Channel Telegr Fault Lamp s 1 bit Cok Eo Low H 230 Channel Telegr Electric Short Circuit 1 bit E Ro T Low E231 Channel A Telegr Communication 1 bit E Ke f Low H 232 Channel Detect Ballasts 1 bit Ce E NE ss 1 bit DP
27. T_Start Low E233 Channel A Assign DALI Address 1 bit C P s 1 bit DPT_Bool Low E234 Channel Device Number 1 Byte pe MENS 8 bit unsigned value DPT Value 1 Ucount Low Fig 6 5 communication objects for the entire channel 38 FMM www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway NO Function Object Name Data type Flags DPT 207 On Off Channel A bit C W 1 001 DPT Switch The communication object is used to switch all DALI devices in the channel If the object receives a telegram value 1 all DALI devices will be turned on with the preset value of broadcast control and they will be turned off with 0 Telegram value 1 on 0 off 208 Relative Dimming Channel A Abit C W 3 007 DPT_Control Dimming This object is used to dim up or down the brightness of all DALI devices The usage is similar to the object 64 209 Set Brightness Value Channel A Ibyte C W 5 001 DPT Scaling The communication object is used to turn on or off all DALI devices in the channel by receiving a brightness value If the received value is greater than 0 then all devices are turned on if the received value is 0 then all devices are turned off Telegram value 0 255 0 100 227 Telegram Fault Ballast s Channel A bit CRT 1 005 DPT Alarm The value of the communication object
28. The progress makes the gateway know status of the DALI devices in the channel and need be executed when DALI devices are changed or added on the DALI bus If the new DALI devices have not DALI address it will be assigned an address while initialization If the new installed devices have already an address then the system will not assign address to it again no matter its address is repeated or not By pressing the test button 25s to initialize DALI devices in the channel and assign automatically DALI addresses to the DALI devices from 0 The more devices the longer time for assigning the address during this process other operations are ignored and the DALI Gateway will not deal with the telegrams of EIB bus Assign DALI address manually If you need to add new DALI devices in the process of installation you will need to connect new DALI devices on the DALI channel individually and assign DALI addresses to them via the object assigned DALI address First of all The DALI Gateway will erase the existed address of the new installed devices via the object assigned DALI address to receive a telegram value 0 and then these devices will no longer have address Secondly the DALI Gateway will assign new address which follows the previous address for these devices via the object assigned DALI address to receive a telegram 1 For example there are 6 DALI devices and their address is 0 5 if the address of the new installed devices is 4 Then i
29. a eue peque uev AEE A ly evevedueidabecde 8 A UE SM ire ies TERT 9 4 2 5 Staircase lighting Dynamic operation mode sss ener nnne nnne rennen 9 Z ALKON 10 4 2 7 Behaviour on EIB or DALI voltage recovery urrnrrrnrrvnrnrnrvrnnvennvanrverrvnnnversenrvennvennvensrnnnransrervrervansvessvensvenseenver 10 A28 WEBD DISplay MC E 10 42 9 Manual operation test function i cssccsss sccssecssscssscssccsnsansssecevizessceosesvocossnsdeepsavsvecossxosecopevsdanstansdeassaredsconsvessees 12 4 3 nor deretter eee eieren 13 5 Parameter setting description in the ETS eessnvvrnnvvnnnnvnnnnvnnnnnnennnnnsnnnnnnnnnsnnnnennnnenvnnnsnnnnsnnnnennnnennnnnsvnnnsunnnsnnnvenen 13 5 1 Parameter window General Joke teet ee esta one rede Drs Puede Ve UAR us EE ar vue evt Lx e ev ERE Leu DR ER LER 13 5 2 Parameter window Channel A srerenrerenverenvenenversnvenenvrsenvesenvessnnesenvessnvesennsvsnnssesnsssnnssennsssnnssesnsssnnssesnsssnnssssnsssnnssennn 15 5 21 Normal operation Mode T M 16 5 22 Dynamic operation mode 5 otro fete ette itr n ee Ie atecvnansceastessieasssvessconesecsstaapecoussanesseeseaesiers 21 5 3 Parameter window Dyna oit ette etched teretes tae e rnit E E aina 22 5 4 Parameter Window Contolera epshin rae aedi nea eoe pna trade de nene Yep deae eR eub vede nest nad agas 24 5 5 Parameter window Status 1 ain cie itae cha sire vie ee aia a rhe res alene
30. allasts fault when one or more ballast don t work the gateway will report the exception Options Only on read request On change of status With the setting only on read request the object value Teleg Fault Ballast s can only be sent when requested With the setting On change of status the current status is sent automatically when it is changed Parameter Send telegram lamp fault This parameter is used to report whether there is one or more lamps exception when there are one or more lamps not working or not connected then the gateway will report the exception Options Only on read request 29 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway On change of status With the setting only on read request the object value Teleg Fault Lamp s can only be sent when requested With the setting On change of status the current status is sent automatically when it is changed Note First the lamps or ballasts fault status of the DALI devices in the channel are detected via the object Detect Ballasts with the telegram value 1 then the gateway will query their fault status and send or response the fault status to EIB bus If via the object Teleg Fault Ballast s or Teleg Fault Lamp s to query directly their status the response status may be incorrect and the gateway will also not send the status
31. alue the device will remain the selected state After a download or EIB bus voltage recovery no device is selected Telegram value Device AO is selected 64 Device A63 is selected Note the values of 0 and 65 255 deselect i e no device is selected 193 Selected Device On Off Channel A bit C W 1 001 DPT_Switch The communication object is used to switch the selected DALI device If the object receives a telegram value 1 the selected DALI device will be turned on with the preset value of the device and it is turned off with 0 Telegram value 1 on 0 off 194 Selected Device Rel Dimming Channel A 4bits C W 3 007 DPT_Control Dimming This object is used to dim up or down the brightness of the selected DALI device The usage is similar to the object 64 195 Selected Device Set Value Channel A Ibyte C W 5 001 DPT Scaling The communication object is used to turn on or off the selected DALI device by receiving a brightness value If the received value is greater than 0 then the device is turned on if the received value is 0 then the device is turned off Telegram value 0 255 0 100 33 LLEESELLL LLLIILLLILLLLLLLLLLLLLLLLLLILLLLZOLILLILLLZLLLLLLLLLLLLLLLLLL LL Ma weiSOowh se sm www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gate
32. and max load 6W at 220 V AC and max load Max 64 DALI devices Distance between gateway and DALI device Cable cross section 0 5mm 0 75 mm 2 1 mm 1 5 mm Connections EIB KNX DALI output and Auxiliary supply Operating display Programming button red LED Green LED flashing Yellow LED Error 116m 174 m 232m 300m Bus connection terminal red black 0 8 mm single core Screw terminal Wire Range 0 5 2 5mm Torque 0 5N m For assignment of the physical address The application layer works normally For displaying DALI devices fault constant light 4 www video star com cn marketing Q video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Housing Temperature range Ambient conditions Design Housing colour Installation Dimension Weight KNX DALI Gateway Red LED Init Green LED Run Test Set button IP 20 EN 60 529 Operation Storage Transport Max air humidity Modular installation device MDRC Plastic housing grey On 35mm DIN Rail to EN 60 715 90 mm x72mm x64mm 0 3KG Application program DALI Gateway I fold For assignment DALI addresses constant light For updating data of DALI Gateway flashing light For initializing mode or detect DALI devices fault fast flashing light For displaying the Auxiliary supply and operation are normal A short operation lt 2s for on off all DALI devices to test some unconnected DALI
33. e DALI devices are detected via the communication object Detect Ballasts the LED will also turn off The LED is the symbol that the DALI Gateway can be operated normally Error Yellow LED The LED will turn on in the event of short circuit or over current of DALI communication terminal ballast fault or lamp fault As soon as DALI communication terminal occur short circuit or over current the LED will turn on immediately When it returns to normal the LED will turn off immediately In addition when the DALI devices are detected via the communication object Detect Ballasts if there is one or more DALI devices e g lamp ballast fault in the channel the LED will also turn on When all fault DALI devices are restored and are detected via the communication object Detect Ballasts again the LED will turn off Init Red LED The LED shows that the DALI Gateway is performing the follow operations LED constant lighting When the DALI Gateway is assigning automatically DALI address for the DALI devices in the channel the LED turns on and the LED Run turns off After finishing the assigning of address the LED turns off and the LED Run turns on LED flashing per 300ms When press test button 2s 5s to update the data of the DALI Gateway the LED flashes When the DALI Gateway querys status of the DALI device on DALI bus voltage recovery the LED flashes When the DALI Gateway querys status of the DALI device on EIB bu
34. el x Teleg Fault 230 VAC fault of auxiliary supply Channel x Teleg Fault Lamp s fault of one or more lamp in the channel First of all the communication object Detect Ballasts detects the DALI devices via a telegram 1 then the gateway will query their fault status and send or read the fault status Channel x Teleg Electric Short Circuit short circuit or over current of DALI communication terminal 4 2 7 Behaviour on EIB or DALI voltage recovery The DALI Gateway is composed of the DALI bus and the EIB bus and the power supply of DALI bus is provided by auxiliary supply So the DALI Gateway will only work normally when connecting the auxiliary supply and the EIB power supply After EIB or DALI bus voltage recovery the DALI Gateway performs relevant options such as report the switch state and current brightness value of DALI devices in the channel as well as the number of DALI device 4 2 8 LED Display Run Green LED The LED will turn on if the auxiliary supply is normal and will constant light if the auxiliary supply and the 10 Eee Ln LLL LEE LLL LLLI O O www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway gateway communication with KNX bus are normal When the DALI Gateway initializes the DALI devices in the channel e g auto allocation DALI addresses or the EIB bus voltage failure the LED will turn off And when th
35. ess value of the scene is directly transferred Recall store scene with 1 bit telegram or 8 bit telegram 4 2 4 Broadcast control In the broadcast control mode all the DALI devices in the channel can be switched on off dimmed or the brightness together with just one communication object As follow Channel x On Off Channel x Relative Dimming Channel x Set Brightness value If the brightness values of DALI devices are non uniform the transition time of brightness are also non uniform The brightness of devices are limited by their min and max brightness value 4 2 5 Staircase lighting Dynamic operation mode A staircase lighting function with a cut out warning time can be parameterized in the dynamic operating mode of DALI Gateway For example the staircase lighting function of a device is composed of two scenes see follow figure the start scene is 9 its run time is 5min and its brightness value is 100 The end scene is 10 its run time is 2min and its brightness value is 40 When the staircase lighting function is triggered via a telegram value 1 the start scene 9 is run and brightness to 100 After the operating time Smin of the start scene has elapsed the end scene 10 commences with brightness 40 and its operation time 2min The device is switched off after the operation time of the end scene The cut out warning is implemented with the end scene Process diagram is as follows Brightness
36. f DALI devices have different physical properties then what the minimum brightness value to support is different Parameter Min brightness value This parameter is used to set the minimal brightness value the lower limit brightness value of DALI devices Ax Options min physical brightness 5926 10 7096 If the minimum brightness value is less than the minimum physical brightness value then the light will be turn on with the minimum physical brightness value as its lower limit value this is determined by the technical performance of DALI device Parameter Maximum brightness value This parameter is used to set the maximum brightness value the upper limit brightness value of DALI devices Ax Options 30 40 100 The minimum amp maximum brightness value limit the whole light output of DALI device Ax the brightness of DALI device only can be adjusted within this range The brightness value which is not in this range can not be output such as 1 100946 belong to entire range the minimum value is 40 the maximum value is 90 then its output range is 4096 9096 If the brightness value is 92 it will not be output The brightness starts to dim up directly from the minimum value under off Note when set parameters the upper limit brightness value must be greater than the lower limit brightness value 17 5 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GV
37. for the selected DALI device Ax x 0 63 Parameter Operating mode This parameter sets the operating mode of DALI devices Ax x 0 63 Options Normal Dynamic Normal mode used to control the general lighting system it can be set the rate of dimming the brightness value of switches relative dimming setting the brightness value for each DALI devices it also can be assigned to multiple scenes group control etc a preset brightness value can be called via scene function The group control is that more than one DALI devices belong to a same group via parameter settings and then control them via a communication object e g switch dimming or set brightness value Dynamic mode is used to control staircase lighting DALI device changes the brightness values according to the period to achieve Staircase lighting function such as open staircase lighting the output delay for a period of time and turns off automatically In the case of dynamic mode the DALI devices do not support the group control and the selected device control but support broadcast control recall or store scenes relative dimming and set brightness value 5 2 1 Normal operation mode Parameter Brightness value when turned on This parameter sets the switch brightness value of DALI devices Ax x 0 63 When the object Ax Switch receives the telegram ON DALI device will turn on the lights in this brightness value Options Min physical brightness 10 2096
38. g and set brightness value of all devices in the channel via these objects With yes option the following two parameters are visible which are used to set the brightness value and dimming rate of the broadcast control Parameter All device power on Value The parameter is to configure the brightness value for all devices in the channel when turning on via the object on off Options Min physical brightness 10 20 100 When the parameterization value is great than or less than the limit brightness value that DALI device defined in the parameter window 5 2 these DALI devices in the channel will turn on with their limit brightness value Parameter Dim period to reach turn on brightness 26 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway This parameter defines the duration time which a dimming process requires from 0 to 100 for broadcast control i e dimming rate Options Immediate 0 7s 2s 90s This dimming time only affects dimming commands which are received via the communication object on off or set brightness value The time in proportion to the percentage of brightness adjustment for example the time is preset to 10s and then the brightness is adjusted from 0 to 50 the duration time will spent 5s The duration time of relative dimming is specified as 8s the time is also in proportion to the
39. hat the object has a normal link to the bus W means the object value can be modified via the bus R means the value of the object can be read via the bus T means that a telegram is transmitted when the object value has been modified U means that value response telegrams are interpreted as a write command the value of the object is updated Because the baud rate of DALI protocol is only 1200 it is relatively slow so a same group address should not be used to link multiple communication objects and only allowing up to seven objects link with a same group address or else it may cause control exception 6 1 Communication objects for individual DALI device The following communication object only applies to the 64 DALI devices in the channel A Each device has a separate switch object relative dimming objects and set brightness value object a single DALI device can be controlled through these objects Number Name bject Function Description Group Addresses Length C R W T VU Data Type Priority Ho AD Switch Switch Status 1 bit pow UT 1 bit DPT_Switch Low mjes AD Relative Dimming Relative Dimming 4 bit c oy 3 bit controlled DPT Control Dimming Low T128 AD Brightness Brightness value Status 1 Byte C 8 T 8 bit unsigned value DPT Scaling Low Fig 6 1 communication objects for individual DALI device NO Function Object Name Data type Flags DPT 0 63 Switch status Ax switch x 0 63 Ibit C W T 1 001 D
40. he biggest amplitude with 9 while to the smallest amplitude with 15 and 8 means stop dimming The object value and the corresponding brightness percentage Object value 0 1 2 3 4 5 6 7 Dim down Unchanged stop dimming 255 100 128 50 64 25 32 12 16 6 8 3 41 Object value 8 9 10 11 12 13 14 15 Dim up Unchanged stop dimming 255 00 128 50 64 25 32 1296 16 6 8 3 4 1 128 191 Brightness value status Ax Brightness x 0 63 lbyte C W T 5 001 DPT_Scaling The communication object is used to turn on or off the DALI device by receiving a brightness value If the received value is greater than 0 then the device is turned on if the received value is 0 then the device is turned off At the same time the communication object will also send the current brightness state to the EIB bus The specific sending way is defined by the parameter Send brightness status response please refer to the description of the parameters in section 5 2 1 Telegram value 0 255 0 100 Table 6 1 communication objects for individual DALI device 6 2 Communication objects for every DALI device The following communication objects can be used to control the selected DALI device directly via switch dimming and set brightness value as well as add the selected device to a group or delete it from a group which it belongs 32 T ess www video
41. he group you want to set and you can set up to 16 groups options 1 16 Parameter device Ax belong to Group y y 1 16 This parameter is used to add the device Ax to the group you want to set Options Yes No Select yes the DALI Devices Ax added to the group is set Select No not added Object selected device remove from Group and object selected device Add to Group to modify the group DALI devices belong to and it will be saved when EIB or DALI bus power off Parameter Send switch status response Obj Switch Options No Only if it change Always The default option is no regardless of whether the DALI devices switch status change status will not be sent For option only if it change when the switch status of DALI device is changed by switching dimming scene controlling and the status is stable the current status will be sent immediately For option always it is always reported the switch status to the EIB bus regardless of whether the brightness values change Due to the communication rate of DALI protocol is relatively slow and the number of devices on the DALI bus there will have a certain delay for the switch status telegram sending Parameter Send brightness status response Object Brightness Options No Only if value change Always 20 EET www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX E
42. he object Detect Ballasts receives a telegram value 1 if query again a telegram value 1 need be received again Parameter Enable Send Fault telegrams This parameter is to configure whether send the fault status reports to the EIB bus when the DALI gateway or 28 Eee LL LLL LLL LLL LLLI LLL HJ www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway the connected DALI devices occur exception Options Yes No Select yes the following parameters are visible the gateway will send fault reports automatically when the status are changed or on request or on query Parameter Send telegram 230 VAC fault Options Only on read request On change of status With the setting only on read request the object value Teleg Fault 230 VAC can only be sent when requested With the setting On change of status the current status is sent automatically when it is changed Parameter Send telegram short circuit Options Only on read request On change of status With the setting only on read request the object value Teleg Electric short circuit can only be sent when requested With the setting On change of status the current status is sent automatically when it is changed Parameter Send telegram ballast fault This parameter is used to report whether the b
43. i e dimming rate adjusted the lighting by a gentle gradient Options Immediate 0 7s 2s 90s This dimming time only affects dimming commands which are received via the communication object Ax switch or Ax brightness The time in proportion to the percentage of brightness adjustment for example the time is preset to 10s and then the brightness is adjusted from 0 to 50 the duration time will spent 5s 18 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway The duration time of relative dimming is specified as 8s the time is also in proportion to the percentage of brightness adjustment But recalling a scene is not the dimming time so the brightness value of the scene is directly transferred In the dynamic mode the staircase lighting is turned on via the object Ax switch with recalling scenes so it is also not the dimming time Note Due to differences between the DALI devices there are some differences for dimming time Scene settings of DALI device Each DALI device can be configured with 16 different scenes the following two parameters are used to configure the scenes of DALI devices Ax Parameter Scene Number The parameter is to select the scenes to be set options 1 16 The follow parameter is used to preset brightness value corresponding to the scene Parameter Light scene value This parameter def
44. ines brightness value of the selected scene Options OFF 10 100 No change Selecting off the DALI device is switched off Selecting 10 100 the DALI device is switched on with the brightness value Selecting no change the current brightness of this DALI device will not be influenced when a scene is recalled i e the device is not part of the scene Note With the no change setting if the scene is stored via EIB the scene parameterizations no change are lost this means all DALI device are members in the scene If a scene is modified the new scene will be stored when EIB or DALI bus power off After bus voltage recovery the new scene can be recalled In the dynamic mode the staircase lighting is turned on via the object Ax switch with recalling scenes if selecting no change the brightness of the device will be unchanged 19 Eee Lu LL LL LLL LL LLLI LLL MH www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway Group control settings of DALI device Each DALI devices can be assigned to as many as 16 different groups we can operate switching dimming and the brightness value setting of the each group of DALI Gateway The parameter window 5 2 only sets the groups devices belonging to As to if enabled the group control please refer to the parameter settings of window 5 4 Parameter Group Number The parameter is to select t
45. is updated and sent when the ballasts fault status in the channel is changed or sent on request depending on the parameter setting fig 5 5 Telegram value 1 Fault of one or more ballasts in the channel 0 No fault 228 Telegram Fault 230 VAC Channel A 1bit CRT 1 005 DPT Alarm The value of the communication object is updated and sent when a fault status of auxiliary supply for the DALI gateway is changed or sent on request depending on the parameter setting fig 5 5 Telegram value 1 Fault of auxiliary supply 0 No fault 39 IN www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway 229 Telegram Fault Lamp s Channel A 1bit CRT 1 005 DPT Alarm The value of the communication object is updated and sent when the lamps fault status in the channel is changed or sent on request depending on the parameter setting fig 5 5 Telegram value 1 Fault of one or more lamps in the channel 0 No fault 230 Telegram Electric Short Circuit Channel A bit CRT 1 005 DPT Alarm The value of the communication object is updated and sent when the fault status of DALI communication terminal is changed or sent on request depending on the parameter setting fig 5 5 Telegram value 1 Fault e g short circuit or over current of DALI communication terminal 0 No
46. l 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway brightness adjustment Note Due to differences between the DALI devices there are some differences for dimming time In the case of the brightness values of DALI devices are non uniform in a group the transition time of brightness are also non uniform and the brightness of some devices may be not changed via relative dimming to achieve consistency of brightness Therefore the relative dimming range of group is 0 100 and is not affected by the limit brightness values of DALI devices but the output brightness value of DALI device is affected by the limit brightness values For example due to the limitation of the maximum brightness the current brightness of some devices only can be adjusted up to 90 but actually adjusted to 95 for the group then when the group receives a dimmed down telegram e g 12 the brightness values of devices will dim down to 83 but for devices of brightness less than 83 their brightness will remain unchanged This note applies not only to group control but also to broadcast control Parameter Enable all devices lighting This parameter defines whether to activate the Broadcast Control of DALI Gateway Options No Yes If select yes broadcast control is enabled and the objects on off relative dimming and set brightness value used to broadcast Control will be visible And you can operate switching dimmin
47. l to the EIB bus via the object if there are multiple malfunctioning devices the DALI gateway will send multiple telegrams continuously to the EIB bus each telegram displays a malfunctioning device But after repair the fault the object is no report Assuming an Ibyte command binary coding as MXSS SSSS If MX is 0 SSSSSS show the number of all DALI devices in the channel If MX is not 0 SSSSSS show the fault device number M I Fault of lamp of the DALI device X 1 Fault of ballast of the DALI device E g the telegram 135 1000 0111 show lamp fault of the device number A6 Table 6 5 communication objects for the entire channel 41 IEREEEEEUEEEIENILLSLLLLLLLLLLLLLMFQFLALLLMLLLLLLLLLLLLLLLLLLLILLLLIZLLNLL1LLLLLLLL IMMLLLLLLLLLILn e www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465
48. ntrol if the brightness values of DALI devices are non uniform the transition time of brightness are also non uniform 1 1 10 ERX DALI Gateway 1 fold General Control Channel Dynamic pe Status Group Number 1 16 Group 1 power on value Dim period to reach turn on brightness Enable All Devices Lighting All Device Power on Value Dim period to reach tum on brightness L o J Cancel Ji Default Fig 5 4 parameter window control Parameter Enable lighting groups 1 16 This parameter sets whether enable Group control for the DALI devices in the channel Options No Yes 24 SSS ene www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway cc n If select yes the group control is enabled and the objects selected group selected group on off selected group Rel dimming and Selected group set value used to group control will be visible First the communication object Selected Group selects a group via group number And then the devices of the selected group can be individually controlled via a communication object of switch dimming or set brightness value How to put the devices assign to a group please refer to Group control settings of DALI device in the parameter window 25 2 With yes option the following three parameters are
49. percentage of brightness adjustment 5 5 Parameter window Status This window is used to set various status reports such as Switch brightness status report for the selected device the fault report of lamps or ballasts auxiliary supply exception report short circuit or over current of DALI communication terminal and communication exception report between KNX and DALI 1 1 10 KENX DALI Gateway 1 fold General Status Channel Dynamic On change of selected device Control send status on off and value n change of selected device send Fault Lamp and Fault Ballast no no Enable Send Fault telegrams yes Send telegram 230 VAC Fault only on read request Send telegram Short circuit only on read request Send telegram Ballast Fault only on read request Send telegram Lamp Fault only on read request Cycle Period between DALI and EIB bus no Cancel Default www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway Fig 5 5 parameter window status The follow two parameters are used to detect various states of individual DALI device such as switch brightness lamp or ballast Provided that first select the DALI device to be detected Parameter On change of selected device send status on off and Value Options Yes No Select yes after selecting a DALI devices when the
50. ponding device number of each device You can also test them via the DALI software tool Third to configure parameters for the DALI devices and download the parameters to the DALI gateway Finally to update data of the DALI gateway by pressing the test button 2s 5s Then you can operate these DALI devices during this if there is some problems with the brightness you will need to download the configured parameters again Note if you do not operate according to the above steps the DALI device may not be controlled according to the preset brightness value 5 Parameter setting description in the ETS 5 1 Parameter window General In the General parameter window these parameters are effective for all DALI devices connected to DALI Gateway 13 T ep www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway 1 1 10 ENX DALI Gateway 1 fold Genes Bener Channel Dynamic Reaction on DALI or EIB max binges value Control bus voltage fail Ding Status Reaction on DALI or EIB bus voltage recovery OFF Fig 5 1 parameter window General Parameter Reaction on DALI or EIB bus voltage failure This parameter defines the action of the connected DALI devices in the channel after DALI or EIB bus voltage failure Options No change Max brightness value Min brigntness value Off The Max brightness value and
51. r each device number such as switching dimming setting the brightness value the rate of dimming scene group control work mode etc Parameters of up to 64 devices can be set and the parameters of each device are the same but you can configure to the different application according to your required The following parameters will be described an example of a device L 1 1 10 KNX DALI Gateway 1 fold General Channel A Channel Dynamic E Device Number v Status Device A10 Operation Mode normal Brightness value when turn on 90 Min brightness value min physical brightness Max brightness value 100 Permit lamp to be tum on via Dimm telegram Permit lamp to be turn off via Dimm telegram Dim period to reach turn on brightness Scene Number Light scene value Group Number Device 410 belongs to Group 1 Send switch status response DBJ Switch Send brightness status response 0BJ Brightness CC Caer s Fig 5 2 parameter window Channel A normal 15 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GYS K BUS KNX EIB KNX DALI Gateway Parameter Device Number This parameter is used to select the device number what you want to configure the DALI device Options A0 Al A2 A63 A0 A63 correspond to the Device A0 to Device A63 The following parameters
52. s voltage recovery the LED flashes LED flashing per1 00ms After a download when the DALI Gateway initialize the DALI devices in the channel the LED flashes and the LED Run turns off After finish initialization the LED turns off and the LED Run turns on When the DALI devices are detected via the communication object Detect Ballasts the LED flashes 11 SSS ee www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway 4 2 9 Manual operation test function There is a test button in the front of DALI Gateway After the connection of the DALI devices the devices and the correct wiring can be verified by the test button without connection to the EIB bus According to the time of pressing the test button there can complate different functions By pressing the test button 20ms 2s all DALI devices can be switched on or off in the channel to verify whether the DALI devices can be operated normally Meanwhile when the DALI devices is switched on it is possible that the DALI Gateway will send the switch and brightness statuses to EIB bus The brightness of devices are limited by the max brightness value of parameter settings By pressing the test button 2s 5s to update the data of the DALI Gateway and the DALI Gateway will query the switch and brightness status of the DALI devices as well as detect whether the DALI devices have address
53. star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway Number Name bject Function Description Group Addresses Length GJER We ETA UI Data Type Priority E192 Channel Select Device 1 Byte D R 4 5 8 bit unsigned value DPT Value 1 Uc Low E193 Channel Selected Device On Off 1 bit CS 1 bit DPT_Switch Low e194 Channel Seleceted Device Rel Dimming 4 bit Coe ik Se 3 bit controlled DPT_Control_Dimming Low m95 Channel Selected Device Set Value 1 Byte 8 bit unsigned value DPT_Scaling Low 22195 Channel Selected Device Status 1 bit CE TZ 1 bit DPT_Switch Low tier Channel Selected Device Read Brightnes 1 Byte COR I 8 bit unsigned value DPT_Scaling Low Eji Channel Selected Device Lamp Failure 1 bit CR T Low 199 Channel Selected Device Device Failure 1 bit C E T Low e200 Channel Selected Device Remove From Gr 1 Byte C Yo 8 bit unsigned value DPT Value 1 Uc Low E201 Channel Selected Device Add to Group 1 Byte E o eng e em 8 bit unsigned value DPT Value 1 Uc Low E202 Channel A Selected Device Query Own Grou 2 Byte t Low Fig 6 2 communication objects for every DALI device NO Function Object Name Data type Flags DPT 192 Device select Channel A Ibyte C R W 5 010 DPT Value 1 Ucount The communication object is used to select the DALI device to be controlled Before the object receives a new telegram v
54. t will disconnect the previous 6 devices from the DALI bus and erase the address 4 of the new devices and then it will be reassigned a new address of 6 After finish the assignment you need reconnect previous 6 devices to the DALI bus While the DALI devices are no address it can be controlled via a short operation of test button or the broadcast control You had better assign DALI address to new devices via the test software tool 12 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway Note While assigning address if two DALI devices share with the same random address are assigned at the same time they will be possibly assigned the same DALI address Under this circumstance you will need to assign the address individually for these two DALI devices Refer to the previous paragraph 4 3 Operating Steps For a new installation project or modified project you need to perform the folllow operating steps First to verify whether all DALI devices in the channel can be operated normally by pressing the test button 20ms 2s Secondly to initialize DALI devices in the channel and assign automatically DALI addresses to the DALI devices from 0 by pressing the test button gt 5s After assigning the address you can test the devices in the channel via the ETS3 EST4 software such as via object switch status need to be configured via ETS and the corres
55. the Min brightness value of the corresponding DALI device can be parameterized in the Channel A parameter window The off setting switches all DALI devices off The no change setting leaves the brightness of the device unchanged in the event of a voltage failure In the case of dynamic operation mode the time functions are not carried out i e the brightness of the device is not unchanged Parameter Reaction on DALI or EIB bus voltage recovery This parameter defines the action of the connected DALI devices in the channel after DALI or EIB bus voltage recovery or after a download Options No change Max brightness value 14 www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB KNX DALI Gateway Min brigntness value Off The Max brightness value and the Min brightness value of the corresponding DALI device can be parameterized in the Channel A parameter window The off setting switches all DALI devices off The no change setting leaves the brightness of the device unchanged In addition the DALI Gateway can send the switch status and the brightness status of the DALI devices to the EIB bus if status response is enabled after DALI or EIB bus voltage recovery or after a download 5 2 Parameter window Channel A This window is setting for parameters of each DALI device selecting the device number it will appear the corresponding parameters fo
56. tion object is used to switch the DALI devices in the selected group If the object receives a telegram value 1 the DALI devices will be turned on with the preset value of the select group and they will be turned off with 0 Telegram value 1 on 0 off 205 Selected Group Rel Dimming Channel A 4bits C W 3 007 DPT Control Dimming This object is used to dim up or down the brightness of the DALI devices in the selected group The usage is similar to the object 64 206 Selected Group Set Value Channel A byte C W 5 001 DPT Scaling The communication object is used to turn on or off the DALI devices in the selected group by receiving a brightness value If the received value is greater than 0 then the devices are turned on if the received value is 0 then the devices are turned off Telegram value 0 255 0 100 Table 6 3 communication objects for every DALI device 6 4 Communication object for Scene control Every DALI device can configure up to 16 different scenes The following communication objects can be used to recall and store the scenes of the DALI device and there are two object types 1 bit and 1 byte The realization of function is the same either via Ibit or via lbyte just according to the actual application to choose a more suitable object type 36 SSS enes www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 3933846
57. way 196 Selected Device Status Channel A bit CRT 1 001 DPT Switch The value of the communication object is updated and sent when the switch status of the selected device is changed or sent on request depending on the parameter setting fig 5 5 Telegram value 1 on 0 off 197 Selected Device Read Brightness Channel A Ibyte CRT 5 001 DPT Scaling The value of the communication object is updated and sent when the brightness status of the selected device is changed or sent on request depending on the parameter setting fig 5 5 Telegram value 0 255 0 100 198 Selected Device Lamp Failure Channel A bit CRT 1 005 DPT Alarm The value of the communication object is updated and sent when the lamp fault status of the selected device is changed or sent on request depending on the parameter setting fig 5 5 Telegram value 1 Fault of the lamp of the selected device or not connected 0 No fault 199 Selected Device Ballast Failure Channel A bit CRT 1 005 DPT Alarm The value of the communication object is updated and sent when the ballast fault status of the selected device is changed or sent on request depending on the parameter setting fig 5 5 Telegram value 1 Fault of the ballast of the selected device 0 No fault 200 Selected Device Remove from Group x 1 16 Channel A Ibyte C W 5 010 DPT_Value_1_Ucount