Home

User Manual - Badger Meter, Inc.

image

Contents

1. Stem Measure Insertion Depth From Here Figure 8 Installation for hot tap models Stem length H1 is intended for use in nominal pipe diameters from 1 1 2 10 in H2 is for nominal pipe diameters from 12 36 in and stem length H3 is for nominal pipe diameters from 36 in and up However pipe with extra thick walls existing linings or unusual tapping hardware may require longer length sensors For these consult the factory The preferred method of installation is by means of a saddle with NPT outlet On steel pipelines weld on type fitting may be substituted 1 Attach the saddle to a section of pipe that has at least 10 diameters of straight pipe ahead and five diameters of straight pipe behind the saddle Drill a minimum 1 1 8 in diameter hole in the pipe 2 Remove the sensor assembly from the mounting hardware by loosening the hex cap over the stem collar and the cover to the mounting adapter and detaching the assembly Set aside taking care not to damage impeller shaft assembly 3 If pipe is drained drill a 1 1 8 in minimum hole into pipe and install a saddle or welded fitting onto the pipe If pipe is under pressure a tapping machine will be needed Install the saddle onto the pipe and thread the 1in NPT end of the valve into the saddle using pipe joint compound
2. 3 Minimum recommended straight run distance Choose location along the pipe where there is straight pipe for a distance of 10 pipe diameters upstream and 5 pipe diameters downstream of the sensor Pipe bends valves other fittings pipe enlargements and reductions or anything else that would cause a flow disturbance should not be present in this length of pipe The recommended tap location around the circumference of a horizontal pipe is on top If trapped air or debris will interfere then the sensor should be located around the pipe from the top preferably not more than 45 degrees from top dead center The sensor should never be located at the bottom of the pipe as sediment may collect there Locations off top dead center cause the impeller friction to increase which may affect performance at low flow rates Any circumferential location is correct for installation in vertical pipes Insertion depth is critical to accuracy The algorithm used to convert impeller motion into flow was developed through flow tests in an independent calibration laboratory The impeller must be located in the same position in the pipe as it was in the calibration test for the impeller frequency to accurately describe the same liquid velocity Detailed installation instructions on the following pages include methods for ensuring correct insertion depth Alignment of the sensor is also important The impeller shaft
3. ET H1 19 H2 21 gt H3 27 7 85 eco 1 2 27 32 O EN Pipe Sizes for reference only Depending on pipe material tapping saddle or existing hardware longer sensor length may be required Contact Factory Figure 9 Hottap sensor dimensions 4 Attach the tapping adapter Badger Meter Data Industrial Part A 1027 to the top of the valve make sure O ring is properly seated in the O ring groove in the top of the ball valve assembly It is recommended at this point that the valve be opened and the A 1027 be connected to a water or AIR Source to pressure test the saddle and valve threaded joint Once the pipe is drilled any leaks in this area would require that the pipe be drained to repair Page8 SEN UM 0021 5 EN 09 November 2014 Mechanical Installation 5 Any tapping machine with a 1 in MNPT pipe thread with an arbor less than 1 in O D capable of holding a 1 00 in Hole Saw and with at least 7 in of travel The SDI ball valve is manufactured oversized with a 1 00 in bore and the SDI sensor is almost interference fit requiring that the hole being drilled also be 1 00 in For this reason the 7 8 in drill bit normally recommended for drilling through a 1 in ball va
4. Impeller Impeller SDI Series Data Industrial Insert Style Flow Sensors gt Badger Meter SEN UM 00215 EN 09 November 2014 User Manual SDI Series Insert Style Flow Sensors CONTENTS 140010 0 c 210 z aa EE EEE EE EE EE eae 3 15 ca ahead cea Rad ce do RR wad 3 Electronic OUtputs 22272218 aa oes naa let sa OT Dd toT a ide dad 3 Standard Frequency 4 py qu A HE 3 Analog 252 te set a oro AE GRAS FAT FR ee don GA do Ga Ate 3 Scaled Pulse Output ness une RADU AE S ERK Re OMG 3 Bidirectional Flow Analog 3 Bidirectional Flow Scaled Pulse Output 4 Display c 2o de dover Gla Os BAGS Ban glad Sa keke a eae Wand Bare woe d 06 4 Mechanical installation ic 5 ce ea ete ala lw Ge ae a eee ala kake ee aaa ead hate a sed 5 Installation for Direct Insert 5 4 6 Iristallationfor Hot Tap Models rarase ARE K FERGE SEE ERAS EEE ORS aR BE 8 Elect
5. Attach SDI 43 Power to positive terminal of power supply 4 Attach SDI 4 and SDI 5 Direction to the device receiving the directional signal This connection is not polarity sensitive and when active provides a solid state switch closure for a maximum load of 100 mA amp 30V AC or 40V DC Analog output wired as current sourcing sharing SDI s 24V DC power supply 1 Attach SDI 46 Loop to Analog input terminal of device receiving this 4 20 mA signal 2 Attach SDI 7 Loop to SDI 3 Sharing terminal with 24V DC Supply 3 Attach SDI 2 Loop to Analog Input Common sometimes labeled Loop Analog output wired as current sourcing with separate 24V DC power supply 1 Attach SDI 46 Loop to Analog input terminal of device receiving this 4 20 mA signal sometimes labeled Loop 2 Attach SDI 7 Loop to 24V DC Supply terminal 3 Attach 24V DC Supply terminal to the Analog Input Common sometimes labeled Loop Page 12 SEN UM 00215 EN 09 November 2014 Programming Bidirectional Scaled Pulse Output Option 6 in the ordering matrix This option provides programmable scaled pulse output signal proportional to flow rate and contact closure to indicate the direction of flow All programming is accomplished as previously mentioned The user can program the unit for pipe size flow scale and the direction of flow This is a six wire option 1 Attach SDI 1 Shield t
6. Software controlled Draw 330 pA typical current of 2 0 mA 5 0 mA lt 5 0 mA 12V DC or 24V AC 3 5 20 5 mA Pulse Units For direction 100 Short Circuit Current 50 mA typical n a gt 100 gt 100 Output Frequency 800 Hz max n a Scaled by customer n a Scaled by customer 5 mS below Adjustable 50 mS to Adjustable 50 mS to Output Pulse Width n a 5 0 seconds in n a 5 0 seconds in 100 Hz 50 mS increments 50 mS increments Output Isolation n a n a Opto isolated Opto isolated Opto isolated Operating Voltage n a 8 25V DC n a 8 25V DC n a Analog Units Output Response nia Varies with Varies with n Time programmable filter programmable filter Page 26 SEN UM 00215 EN 09 November 2014 INTENTIONAL BLANK PAGE November 2014 SEN UM 00215 EN 09 Page 27 SDI Series Insert Style Flow Sensors Control Manage Optimize Trademarks appearing in this document are the property of their respective entities Due to continuous research product improvements and enhancements Badger Meter reserves the right to change product or system specifications without notice except to the extent an outstanding contractual obligation exists O 2014 Badger Meter Inc All rights reserved www badgermeter com The Americas Badger Meter 4545 West Brown Deer Rd PO Box 245036 Milwaukee WI 53224 9536 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Ang
7. cannot be ejected from the pipe if the cover is secured to the valve Check to make sure all joints are tight 15 Insert the flow sensor stem into the pipe by pushing against the top of the electronics housing with a slight twisting motion until the stem collar meets the cover The force required to push the sensor into the pipeline is approximately 20 of the line pressure Be aware of the close spacing between the diameter of the flow sensor the bore of the ball valve and the hole in the pipe If the sensor stops or catches before the stem collar meets the cover apply a gentle rocking twisting motion to the sensor to continue its travel 16 While holding the flow sensor collar against the cover thread the hex cap onto the cover to hold the flow sensor in place but do not tighten 17 Align the flow sensor with the pipe by using the flat side cover of the electronics housing as a guide Place a straightedge along the cover and rotate the sensor until the straightedge is parallel to the pipe 18 Tighten the hex to the cover to approximately 10 ft lb The hex cap holds the sensor alignment and depth but performs no sealing functions DO NOT OVER TIGHTEN 19 Pressurize pipeline and check for leaks Pipe SDI Flow Sensor Straight Edge Parallel to Pipe Page 10 Figure 12 Level the sensor SEN UM 00215 EN 09 November 2014 ELECTRICAL INSTALLATION Electrical Installation Ac
8. may be required Consult Factory hardware longer sensor length may be required Consult Factory Combination for gt 180 F Service Figure 1 SDI series direct insert ordering matrix Figure 2 SDI series hot tap ordering matrix Display Options All models except the standard frequency output version may also be equipped with a display Integrated into the NEMA 4 housing the 8 digit LCD may be programmed to show rate of flow flow total or toggle between the two Bidirectional models also show flow direction Page 4 SEN UM 00215 EN 09 November 2014 Mechanical Installation MECHANICAL INSTALLATION The accuracy of flow measurement for all insert type flow measuring devices is highly dependent on proper location of the sensor in the piping system Irregular flow velocity profiles caused by valves fittings and pipe bends can lead to inaccurate overall flow rate indications even though local flow velocity measurement may be accurate sensor located in the pipe that is partially full or where it can be affected by air bubbles floating debris or sediment may not achieve full accuracy and could be damaged Data Industrial flow sensors are designed to operate reliably under adverse conditions but the following recommendations should be followed to ensure maximum system accuracy 1 DATA INDUSTRIAL SDI Series Sensor 54 10 x Pipe Dia Y amp 5x Pipe Dia 3
9. must be perpendicular to the flow for accuracy Alignment instructions are also included on the following pages 15 3 4 gt I 4 23 _ gt Per ANSI ASME B1 20 1 1993 R1992 0 660 Handtight Engagement Wrench Makeup Pipe Sizes for reference only Depending on pipe material tapping saddle or existing hardware longer sensor length may be required Contact Factory Figure 4 Direct insertion sensor dimensions November 2014 SEN UM 00215 EN 09 Page 5 Mechanical Installation Installation for Direct Insert Models These instructions are for the installation of flow sensors into piping systems that are not under pressure at the time of installation If the line must be tapped under pressure hot tap style sensor must be used See following section for hot tap installation instructions The insertion depth and alignment of the sensor are critical to the accuracy of the flow measurement The impeller must be at the same location in the pipe as it was during calibration Data Industrial provides sensors with different stem lengths Longer stems are intended for use in larger diameter pipes and shorter stems for use in smaller pipelines However stem length has no affect on the operation of the sensor provided that the impeller is positioned correctly in the pipe Direct i
10. the pipe size from the pull down menu if the pipe size is not present then select custom or check for an updated pipe dat table on the Data Industrial web site Step 5 Enter 4mA flow rate This is normally zero Step 7 For models with LCD Display Option select the desired LCD Configuration from the pull down menu If Model has no display then skip to Step 410 Step 49 If the Flow direction label requires changing see Note 3 Step 410 Press Send to transmit calibration data to the SDI Sensor NOTE 1 Load Save N Advanced Params Exit EE Pipe TE file vers Flow Flow Sensor Calibration 0 55 10 x Rate usas Total EET o e Edit Custom r Loop Settings 4 Low Setting 4ma Press to retrieve calibration data from SDI the sensor frequency to flow rate They are unique to each pipe size material NOTE 2 be obtained by contacting Data Industrial NOTE Page 16 SEN UM 00215 EN 09 Step 2 Select total units from the pull down values See Note 1 Step 4 If custom was selected in step 3 then click the custom button and see Note 2 Step 6 Enter 20mA flow rate Step 8 Select Active Direction Press to reset all parameters back to factory defaults Send must be pressed to send this data to the SDI Step 11 Press to exit parameters screen and to go back to the main screen Press
11. 0 0 065 2 1 2 in 2 625 Insertion Depth 0 95 0 97 0 98 Customer Ref 1 29 32 1 29 32 1 29 32 Wall 0 109 0 090 0 072 0 045 3 125 Insertion Depth 1 19 1 21 1 23 1 25 Customer Ref 2 3 16 2 3 16 2 3 16 2 3 16 Wall 0 134 0 110 0 095 0 058 4in 4 125 Insertion Depth 1 54 1 56 1 57 1 60 Customer Ref 2 9 16 2 9 16 2 17 32 2 17 32 Wall 0 192 0 140 0 122 0 083 6 125 Insertion Depth 172 1 75 1 76 1 79 Customer Ref 2 25 32 2 3 4 2 3 4 2 3 4 A blank cell No data at time of printing Table A3 Customer Reference Number Ductile Iron Because of the variety of iron pipe classes sizes and wall thicknesses consult the factory for customer reference number Pipe amp Schedule or pipe amp I D or Pipe O D and wall thickness is required November 2014 SEN UM 00215 EN 09 Page 21 Customer Reference Number Tables Table A4 Customer Reference Number PVC AWWA C900 Size O D Description CL100 Wall 0 192 1 1 2 in 1 625 Insertion Depth 1 77 Customer Ref 2 27 32 Wall 0 276 2 in 2 125 Insertion Depth 1 90 Customer Ref 3 1 16 Wall 0 362 2 1 2 in 2 625 Insertion Depth 2 50 Customer Ref 3 23 32 Wall 0 444 3 in 3 125 Insertion Depth 3 06 Customer Ref 4 3 8 Wall 0 528 4 in 4 125 Insertion Depth 3 64 Customer Ref 5 1 16 For other types of pipe not listed above consult the factory Pipe O D amp Schedule or pipe amp I D
12. 224082 1 224082 0 029050 0 029050 1 463673 1 463673 zin K 4 254704 4 254704 4 158287 4 158287 3 705163 3 705163 3 315944 3 315944 Offset 1 040171 1 04017 1 265404 1 265404 2 073017 2 073017 2 362615 2 362615 T K 6 703921 6 703921 6 571415 6 571415 5 831518 5 831518 5 122780 5 122780 i Offset 8 690330 8 690330 8 020263 8 020263 4 525378 4 525378 1 645774 1 645774 iin T K 9 810699 9 810699 9 631116 9 631116 8 862069 8 862069 8 129755 8 129755 i i Offset 4 373516 4 373516 4 521076 4 521076 5 253952 5 253952 6 129664 6 129664 UM 10750 K 15 558041 15 558041 15 359217 15 359217 14 116608 14 116608 12 779132 12 779132 Offset 2 693802 2 693802 2 681251 2 681251 2 693176 2 693176 2 904373 2 904373 K 22 687525 22 687525 22 492687 22 492687 20 707010 20 946699 18 603270 19 990417 Offset 5 074024 5 074024 4 969576 4 969576 4 099617 4 206793 3 302154 3 798262 T 14000 K 28 113718 28 113718 27 254274 27 819418 25 581423 25 581423 22 940674 25 043200 Offset 8 609697 8 609697 7 977566 8 390513 6 819905 6 819905 5 212368 6 469292 EN K 38 108196 38 108196 37 184074 37 856899 34 538799 35 847870 31 076347 34 538799 i Offset 17 436071 17 436071 16 524164 17 186449 14 010489 15 235909 10 962554 14 010489 T 18000 K 49 922424 49 922424 48 850674 49 631184 45 024284 47 297367 40 637650 45 771198 Offset 30 346106 30 346106 29 092361 30 003992 24 739450 27 301405 20 013815 25 573288 20000 K
13. 59 821514 59 821514 59 821514 59 459480 54 939907 57 568302 51 637486 56 066704 Offset 3 372809 3 372809 3 372809 3 378817 3 459857 3 411363 32 381599 3 438600 se K 72 009399 72 009399 71 246956 71 640358 69 712502 60 582455 j Offset 3 211272 3 211272 3 219100 3 215024 3 235763 3 360413 m 57000 K 84 054832 84 054832 83 653954 83 653954 78 190941 82 090302 71 628067 80 530304 Offset 3 126430 3 126430 3 128100 3 128100 3 158703 3 135363 3 215150 3 143800 K 95 504044 94 701706 Zoin 26 000 Offset m m 3 111093 E 3 110163 E mi m K 108 363754 107 546707 ni 28 000 Offset m 3 165831 gt 3 160163 m m m 30000 K 122 276558 122 276558 121 457077 121 457077 120 625305 E _ 4 Offset 3 306300 3 306300 3 295768 3 295768 3 285363 CS Carbon Steel SS Stainless Steel Estimations are based on nominal I D from standard ASME B36 10 and B36 19 Standard Schedule A blank cell No data at time of printing November 2014 SEN UM 00215 EN 09 Page 23 K amp Offset Tables Table B2 Estimated K amp Offset Copper Tube Type Size O D K L M DMW Orr 27r S 2 1 2in 2625 one 2 sm ams ofa in 412 ofset aume EE Torn ES A blank cell No data at time of printing Table B3 Estimated K amp Offset Ductile Iron Because of the v
14. Details to see and offset numbers for the selected pipe The K and offset are factors used to convert Press Custom to enter K and offset numbers for pipe material not listed in pull down menu The numbers may Press Change Label to change flow direction label Enter up to 20 characters such as From Pump November 2014 Bidirectional Scaled Pulse Output Models Step 1 Select rate units from the pull down values Step 43 Select the pipe size from the pull down menu if the pipe size is not present then select custom or check for an updated pipe dat table on the Data Industrial web site Step 5 Select the pulse output type that is required If raw pulse is selected skip Step 6 Step 7 For models with LCD Display Option select the desired LCD Configuration from the pull down menu If Model has no display then skip to Step 10 Step 9 If the Flow direction label requires changing see Note 3 Step 410 Press Send to transmit calibration data to the SDI Sensor Parameters Load SaveN Advanced Params Exit Rate Total unis Flow Sensor Calibration Pipe data file version 0 55 Scaled Pulse Output Dual Pulse Pulse Direction Ld Raw Pulse Press to retrieve calibration data from SDI Programming Step 42 Select total units from the pull down values See Note 1 Step 4 If custom was selected in step 3 then click the custom b
15. are and select the appropriate COM PORT as shown in the dialog box below Takni Gleges celect m new port 5 Open the Parameters Screen as shown below Data Industrial SDI Version 1 00 Main Configuration Reset Totals Help Select Com Port Device gt Auto Refresh Time gt To go to the calibration settings screen select parameters from either place shown sdi analog display Offline November 2014 SEN UM 00215 EN 09 Page 13 Programming a Industrial SDI Version 1 00 Main Configuration Reset Totals Help Select Com Port Device 4 Auto Refresh Time gt fa To go to the calibration settings screen select parameters from either place shown Data Industrial Corp c 2001 sdi bidi analog display Offline 6 Program using the following screens as reference Single Direction Analog Output Models Step 1 Parameters Select rate units from the pull down Sm Step 42 values Select total units from the Flow mm ull down values Step 3 000 Rate Paes colons Select the pipe size from the pull down menu if the pipe size is not See Note 1 present then custom must be selected or check for an updated pipe dat table on the Data Industrial Flow ensor Calibratien Step 4 If custom was selected step 3 then click the custom button website Pipe da
16. ariety of iron pipe classes sizes and wall thicknesses consult the factory for customer reference number Pipe amp Schedule or pipe amp I D or Pipe O D and wall thickness is required Table B4 Estimated K amp Offset PVC Municipal C900 Schedules Size O D 100 K 4in 4 800 Offset K 6in 6 900 Offset K 8 in 9 050 Offset K 10 in 11 100 Offset K 12in 13 200 Offset For other types of pipe not listed above consult the factory Pipe O D amp Schedule or pipe O D amp I D or Pipe O D and wall thickness is required A blank cell No data at time of printing Page 24 SEN UM 00215 EN 09 November 2014 Specifications SPECIFICATIONS Wetted Materials Sensor stem mounting adapter isolation valve and nipple 316 Stainless steel Sensor Tip Polyphenylene sulfide PPS O rings Bearings Shaft See ordering matrix Maximum Temperature Ratings Fluid Measured 300 F 135 C continuous service Operating Temperature Electronics 150 F 65 C Operating Temperature LCD 150 F 65 C Maximum Pressure Rating 1000 psi 100 F 900 psi 200 F 750 psi 300 Recommended Design Flow Range 0 33 20 ft s Initial flow detection below 0 25 ft s Pressure Drop 0 5 psi or less 10 ft s for all pipe sizes 1 5 in diameter a
17. cess the wiring terminals by removing the side cover wiring diagram is on the side cover under the gasket Use care when replacing the side cover Make sure that the gasket is in place DO NOT REMOVE CIRCULAR COVER from top of sensor You may disturb the seal and label alignment A moisture absorbing silica pack has been placed inside the electronics housing during assembly Leave it in place after making the wire connections Standard Frequency Pulse Output Option 0 in the ordering matrix 123 Analog 4 20 mA Output 1 Shield 2 Sensor Common 3 Sensor Signal Option 1 in the ordering matrix 123 OOOO E 1 Shield 2 Loop 3 Loop This two wire sensor is intended for connection to Data Industrial monitors and transmitters or other devices that supply 10 24V DC excitation voltage and accept frequencies from 0 1000 Hz 1 Attach the sensor shield terminal 1 to the shield terminal on the transmitter used for maximum protection from interference 2 Attach the sensor common terminal 2 to the common terminal on the transmitter 3 Attach the sensor signal terminal 3 to the signal terminal on the transmitter This option provides a programmable 4 20 mA signal proportional to flow rate All programming is accomplished as previously men
18. custom or check Step 4 for an updated pipe dat table on the Pip Details Data Industrial web site If custom was selected in step 3 then click the custom button and see Note 2 Flow Sensor Calibration en 4 Pipe data file version 0 56 Edit Custom Scaled Pulse Qutput Step 5 a Enter the number of units per 5 pulse and select the pulse Step 6 width required For models with LCD Display Option select the desired LCD Configuration from the pull down menu If Model has no display then skip to Step 7 ER PEEL Step 47 Press to reset all parameters Press Send to transmit calibration back to factory defaults Send data to the SDI Sensor must be pressed to send this y data to the SDI Step 8 Press to exit parameters screen and to go back to the Press to retrieve calibration main screen data from SDI NOTE 1 Press Details to see and offset numbers for the selected pipe The and offset are factors used to convert the sensor frequency to flow rate They are unique to each pipe size material NOTE 2 Press Custom to enter K and offset numbers for pipe material not listed in pull down menu The numbers may be obtained by contacting Data Industrial November 2014 SEN UM 00215 EN 09 Page 15 Programming Bidirectional Analog Output Models Step 1 Select rate units from the pull down values Step 43 Select
19. eceiving this 4 20 mA signal 2 Attach SDI 7 Loop to 24V DC terminal of device receiving the 4 20 mA Signal This option provides a programmable opto isolated solid state switch closure with internal solid state fuse protection All programming is accomplished as previously mentioned The user can program the unit for pipe size flow scale and the direction of flow This is a six wire option 1 Attach SDI 1 Shield to Earth Ground or Power Supply Common This provides maximum power and signal EMI protection Attach SDI 42 Power to the negative terminal of a nominal 12 24V AC DC Power Supply See data sheet for current draw and voltage limits Attach SDI 43 Power to positive terminal of power supply Attach SDI 4 Pulse to the Input pulse of the receiving device Attach SDI 5 Pulse to the Input pulse of the receiving device This option provides a programmable 4 20 mA signal proportional to flow rate and a contact closure to indicate the direction of flow All programming is accomplished as previously mentioned You can program the unit for pipe size flow scale and the direction of flow This is a six wire option 1 Attach SDI 1 Shield to Earth Ground or Power Supply Common This provides maximum power and signal EMI protection Attach SDI 42 Power to the negative terminal of a nominal 12 24V AC DC Power Supply See data sheet for current draw and voltage limits
20. ect the appropriate COM PORT as shown in the dialog box below 3 Open the Parameters Screen as shown below To calibrate select parameters from either place shown SDI Battery PC Software Version 0 29 I Main Configuration Reset Totals Help Select Com Port 0 000000 Flow Total 0313 Parameters Data Industrial Corp c 2002 Parameters Com Port 1 4 Program parameters using diagram below as a reference Step 1 Enter in a K number found in Table B Step 2 Enter in a offset number found in Table B Step 3 Enter in a Reference number found in Table A Step 6 Optional setting Enter in the gallons pulse and select pulse width Skip this step if not using the Scaled pulse output Step 7 Press Send to transmit calibration data to the SDI Sensor See Note 1 41 501 Battery Parameters Press to retrieve calibration data from SDI Step 4 Select the desired flow rate and total units Step 5 Select the desired display readout mode Press to reset all parameters back to factory defaults Send must be pressed to send this data to the SDI Step 8 Press to exit parameters screen and to go back to the main screen See Note 2 NOTE 1 After the Send button is pressed the unit could take up to 1 1 2 minutes to program the Battery Powered SDI The illustration below shows the programming process bar When the programm
21. elina 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East and Africa Badger Meter Europa GmbH Nurtinger Str 76 72639 Neuffen Germany 49 7025 9208 0 Europe Middle East Branch Office Badger Meter Europe PO Box 341442 Dubai Silicon Oasis Head Quarter Building Wing C Office 209 Dubai UAE 971 4 371 2503 Czech Republic Badger Meter Czech Republic s r o Mafikova 2082 26 621 00 Brno Czech Republic 420 5 41420411 Slovakia Badger Meter Slovakia s r o Racianska 109 B 831 02 Bratislava Slovakia 421 2 44 63 83 01 Asia Pacific Badger Meter 80 Marine Parade Rd 21 06 Parkway Parade Singapore 449269 65 63464836 China Badger Meter 7 1202 99 Hangzhong Road Minhang District Shanghai China 201101 86 21 5763 5412 Legacy Document 872034
22. formation is stored in non volatile memory in the flow sensor This is a four wire option Bidirectional Flow Analog Output This option provides a programmable 4 20 mA signal proportional to flow rate and a contact closure to indicate the direction of flow All programming is accomplished as previously mentioned The user can program the unit for pipe size flow scale and the direction of flow This is a six wire option November 2014 SEN UM 00215 EN 09 Page 3 Electronic Outputs Bidirectional Flow Scaled Pulse Output This option provides the user with a choice of outputs In one case the sensor provides an output scaled to the required number of engineering units on one set of terminals and a contact closure to indicate the direction of flow on another The other choice provides two isolated scaled pulse outputs one for each direction Programming the output choice pipe size output scale and direction of flow by the user are also accomplished by using a PC with Data Industrial software and A 301 connection cable This option also requires six wires SDI Series Direct Insert Ordering Matrix N SDI 0 D1 0 0 0 2 SDI 0 H N 0 0 0 2 0 0 Material Material Stainless Steel PPS Tip 0 Stainless Steel PPS Tip 0 Brass PPS Tip 1 Stainless Steel PEEK Tip Stainless Steel PEEK Tip 2 Type Type Hot Tap for Pipe 1 1 2 thru 10 H1 Direct Insert for Pipe 1 1 2 thru 10 D1 Hot Tap for P
23. he recess of the sensor tip to the A a bottom of the stem collar Insert the metal tab of a tape measure into the of the flow sensor tip Extend the tape up the stem mark the shaft with pencil TI e Slide the collar along the shaft until its bottom surface is at the mark on the stem Tighten the cap screw on the collar When the sensor is reassembled this will set the insertion depth of the sensor Make sure to hold the sensor up tight against the cover when installing onto the valve to prevent the possibility of damaging the impeller by striking the closed ball of the valve Figure 10 Ball valve and pipe saddle November 2014 SEN UM 00215 EN 09 9 Mechanical Installation pod Stem mu Stem Collar Ball Valve Pipe Saddle ref Figure 11 Sensor tip and stem collar 11 Slide the cover down the stem until it stops 12 Attach the sensor to the valve by inserting the impeller end of the stem into the valve until the cover touches the top of the valve The sensor tip and impeller will be in the section of the valve above the ball 13 Tighten the cover against the O ring in the top of the valve This will seal the sensor assembly 14 Open the ball valve again by slowly rotating the handle 90 If the cover was not at the bottom of the sensor stem water pressure from the pipe would now push it out until it stops However the sensor
24. ill seal the sensor assembly Continue to insert the flow sensor stem until the stem collar meets the cover Thread the hex cap onto the mounting adapter but do not tighten Align the flow sensor with the pipe by using the flat cover on the electronics housing as a guide Place a straightedge along the cover and rotate the sensor until the straightedge is parallel with the pipe as shown in Figure 7 Tighten the hex cap over the collar approximately 10 ft lb The hex cap holds the sensor alignment but performs no sealing functions DO NOT OVER TIGHTEN Pressurize pipeline and check for leaks SDI Flow Sensor Pipe Pipe Straight Edge Parallel to Pipe Figure 7 Align the flow sensor with the pipe SEN UM 00215 EN 09 Page7 Mechanical Installation Installation for Hot Tap Models The insertion depth and alignment of the sensor are critical to the accuracy of the flow measurement The impeller must be at the same location in the pipe as it was during calibration Data Industrial provides sensors with three different stem lengths Longer stems are intended for use in larger diameter pipes and shorter stems for use in smaller pipelines However stem length has no affect on the operation of the sensor provided that the impeller is positioned correctly in the center of the pipe Ball Valve Stem Collar Bottom of Housing i Cover
25. ing process bar disappears and the status bar says updated the Battery Powered SDI is programmed NOTE 2 After the Exit button is pressed it takes about 10 seconds to go back to the operating display and refresh flow rate and flow total Page 18 SEN UM 00215 EN 09 November 2014 Programming Programming Process Bar V Status Bar gt ia November 2014 SEN UM 00215 EN 09 Page 19 Customer Reference Number Tables CUSTOMER REFERENCE NUMBER TABLES Table A1 Customer Reference Number Pipe Pipe Schedules Size O D Description 10 10s 40 40s Std 80 SDR21 Wall 0 109 0 109 0 145 0 145 0 200 1 1 2 in 1 900 Insertion Depth 0 58 0 58 0 54 0 54 0 49 Customer Ref 1 9 16 1 9 16 1 9 16 1 9 16 1 9 16 Wall 0 109 0 109 0 154 0 154 0 218 0 113 2in 2 375 Insertion Depth 0 81 0 81 0 77 0 77 0 71 0 81 Customer Ref 1 13 16 1 13 16 1 13 16 1 13 16 1 13 16 1 13 16 Wall 0 120 0 120 0 203 0 203 0 276 0 137 2 1 2in 2 875 Insertion Depth 1 05 1 05 0 97 0 97 0 90 1 04 Customer Ref 2 1 16 2 1 16 2 1 16 2 1 16 2 1 16 2 1 16 Wall 0 120 0 120 0 216 0 216 0 300 0 167 3in 3 500 Insertion Depth 1 37 1 37 1 27 1 27 1 19 1 32 Customer Ref 2 3 8 2 3 8 2 3 8 2 3 8 2 3 8 2 3 8 Wall 0 120 0 120 0 237 0 237 0 337 0 214 4 in 4 500 Insertion Depth 1 70 1 70 1 61 1 61 1 53 1 63 Customer Ref 2 11 16 2 11 16 2 23 32 2 23 32 2 3 4 3 1 8 Wal
26. ipe 12 thru 36 Direct Insert for Pipe 12 thru 36 D2 E E E Pipe 36 and Direct Insert 36 and D3 ect omen p 5 NEMA 4X N Electronic Housing NEMA 4X Output Standard Frequency Pulse 0 Scaled Pulse Analog 4 20mA 1 Bi Directional 4 20 Direction PPS tip Only Scaled Pulse 2 Bi Directional Scaled Pulse PPS tip Only Display Display No Display 0 No Display LCD Option not available with output option 0 O Ring Viton 1 AFLAS 2 0 Shaft Tungsten Carbide Standard 2 Tungsten Carbide Standard 2 Hastelloy C 276 optional consult factory 1 Hastelloy C 276 optional consult factory 4 Zirconia Ceramic optional consult factory 0 Zirconia Ceramic optional consult factory 0 Impeller Impeller SDI Series Hot Tap Ordering Matrix 1 gt Output Standard Frequency Pulse Analog 4 20mA LCD Option not available with output option 0 O Ring Viton 1 AFLAS 2 Shaft Stainless Steel 0 Stainless Steel Bearing Bearing Torlon VESPEL 1 KETRON HPV 2 Torlon X VESPEL 1 KETRON HPV 2 0 Pipe size for reference only Depending on pipe material tapping saddle or existing Pipe size for reference only Depending on pipe material tapping saddle or existing 5 hardware longer sensor length
27. l 0 134 0 134 0 258 0 258 0 375 5in 5 563 Insertion Depth 1 59 1 59 1 63 1 63 1 44 Customer Ref 2 5 8 2 5 8 2 21 32 2 21 32 2 11 16 Wall 0 134 0 134 0 280 0 280 0 432 0 316 6 625 Insertion Depth 1 91 1 91 1 82 1 82 1 73 1 83 Customer Ref 2 29 32 2 29 32 2 31 32 2 31 32 3 1 32 3 1 32 Wall 0 148 0 148 0 322 0 322 0 500 0 410 8in 8 625 Insertion Depth 2 50 2 50 2 39 2 39 2 29 2 40 Customer Ref 3 17 32 3 17 32 3 19 32 3 19 32 3 21 32 3 11 16 Wall 0 165 0 165 0 365 0 365 0 594 0 511 10 in 10 750 Insertion Depth 3 13 3 13 3 01 3 01 2 87 2 98 Customer Ref 4 5 32 4 5 32 4 1 4 4 1 4 4 11 32 4 3 8 Wall 0 180 0 180 0 406 0 375 0 688 0 606 12in 12 750 Insertion Depth 3 72 3 72 3 58 3 60 3 41 3 52 Customer Ref 4 25 32 4 25 32 4 7 8 4 27 32 5 5 Wall 0 250 0 188 0 438 0 375 0 750 14 in 14 000 Insertion Depth 2 03 2 04 1 97 1 99 1 88 Customer Ref 3 5 32 3 3 32 3 9 32 3 1 4 3 1 2 Wall 0 250 0 188 0 500 0 375 0 844 16in 16 000 Insertion Depth 2 33 2 34 2 25 2 29 2 15 Customer Ref 3 7 16 3 13 32 3 5 8 3 17 32 3 7 8 Wall 0 250 0 188 0 562 0 375 0 938 18 18 000 Insertion Depth 2 63 2 64 2 53 2 59 2 42 Customer Ref 3 3 4 3 23 32 3 31 32 3 27 32 4 1 4 Wall 0 250 0 218 0 594 0 375 1 031 20 in 20 000 Insertion Depth 2 93 2 94 2 82 2 89 2 69 Customer Ref 4 1 16 4 1 32 4 9 32 4 1 8 4 19 32 Wall 0 250 0 375 1 125 22 22 000 Insertion Depth 3 23 3 19 2 96 Customer Ref 4 11 32 4 7 16 4 31 32 For sizes ab
28. llows the sensor to be inserted into the pressurized pipeline by hand without the need for an installation tool The mounting hardware holds the sensor firmly in place at the correct depth and alignment ELECTRONIC OUTPUTS Standard Frequency Sensor output is a pulse proportional to flow signal is similar to all 200 Series Data Industrial flow sensors and will interface with all existing Data Industrial transmitters and monitors The power supply to the sensor and the output signal from the sensor is carried on the same two wires Wire connections are made at screw terminals on removable headers inside the NEMA 4X housing Analog Output The Sensor is also available with a two wire loop powered 4 20 mA output The analog output is produced by an on board micro controller for precise drift free signals The unit is programmed from a computer using Windows based software and a Data Industrial A 301 connection cable Units may be pre programmed at the factory or field programmed All information is stored in non volatile memory in the flow sensor Scaled Pulse Output The scaled pulse is produced by an on board micro controller for precise accurate outputs This option may be programmed to produce an isolated dry contact closure scaled to any number of engineering units of measure Sensors may be pre programmed at the factory or field programmed using a Data Industrial A 301 connection cable and a Windows based software program All in
29. lve cannot be used 6 Attach the tapping machine to the tapping adapter Ensure that all connections and seals are tight 7 Slowly open the valve by rotating the handle 90 and lower the cutter past the valve ball to the pipe Drill the 1 nominal hole according to the manufacturer s instructions 8 Withdraw the cutter past the valve ball close the valve and remove the tapping tool 9 Remove the Data Industrial tapping adapter from the top of the valve 10 The sensor rotor assembly is to be located a fixed distance from the center of the pipe To position the impeller at this depth a reference measurement for the pipe size and schedule is used a Lookup the pipe size and schedule number in the Customer Reference Number Tables on page 20 and note the Customer Reference Number Customer Ref NOTE The Customer Reference Number has been calculated using the Ball Valve following formula lt gt Ref Insertion Depth Wall Thickness Cover Thickness b Next measure from the outside wall of the pipe to the top of the installed mounting adapter this is dimension Figure 5 on page 6 c Add this number to the reference measurement The resulting number is dimension C in Figure 6 on page 7 Dimension C Customer Ref Dimension B pipe er h d Dimension C is the distance from t
30. nd up Standard calibration NIST traceable to 1 of rate Accuracy Custom wet calibration NIST traceable to 0 5 of rate Straight Pipe Install sensor in straight pipe section with a minimum distance of 10 diameters upstream and 5 Requirement diameters downstream to any bend transition or obstruction Repeatability 0 596 Enclosure Polypropylene with Viton sealed acrylic cover Meets NEMA 4X specifications Wire Connections All wire connections are made to removable headers with screw type terminals within the electronics housing 1 2 in conduit thread provided Programming All programmable models use Data Industrial A 301 connector cable and SDI Series software 8 character 3 8 in LCD Display optional STN Super Twisted Nematic display Annunciators for rate total input output flow direction for bidirectional models cc ssori s ASDI Programming Kit A1027 Hot Tap Adapter Nipple November 2014 SEN UM 00215 EN 09 Page 25 Specifications Unidirectional Bidirectional Raw Pulse Analog Loop Scaled Pulse Analog Loop Scaled Pulse Option 0 Option 1 Option 2 Option 5 Option 6 Number of Wire Connections 2 2 4 6 6 12 30V 12 30V 12 30V Operating Valtage 40008 is 12 35V DC 12 35V DC 12 35V DC Overvoltage 30V AC 40V DC 30V AC 30V AC 30V AC Protection 40V DC 40V DC 40V DC 40V DC Quiescent Current
31. nsert models are available in one stem length designated D1 They are intended for nominal pipe diameters from 1 1 2 10 in However pipe with extra thick walls existing linings or unusual tapping hardware may require longer length sensors Consult factory For larger pipe sizes hot tap style sensors equipped with an isolation valves are recommended The preferred method of installation is by means of a saddle with 1in NPT outlet On steel pipelines a weld on type fitting may be substituted 1 Attach the saddle to a section of pipe that has at least 10 diameters of straight pipe ahead and five diameters of straight pipe behind the saddle Drill a minimum 1 1 8 in diameter hole in the pipe 2 Remove the sensor assembly from the mounting hardware by loosening the hex cap over the stem collar and the cover to the mounting adapter and detaching the assembly Set aside taking care not to damage impeller shaft assembly 3 Attach the pipe thread end of the mounting adapter to the saddle or weld o let using a pipe joint compound and tighten the joint Do not apply sealing compound to the top thread of the mounting adapter it is sealed with an O ring 4 The sensor rotor assembly is to be located a fixed distance from the center of the pipe To position the impeller at this depth a reference measurement for the pipe size and schedule is used Mounting Adapter I Pipe Saddle ref a Look up the pipe size and schedule number in
32. o Earth Ground or Power Supply Common This LITT 1 Shield provides maximum power and signal EMI protection 2 Attach SDI 2 Power to the negative terminal of a nominal 4 Pulse 12 24V AC DC Power Supply See data sheet for current draw and Joco 5 Pulse B voltage limits 3 ios 3 Attach SDI 3 Power to positive terminal of power supply 4 Attach SDI 4 Pulse to the Input pulse of the receiving device l 5 Attach SDI 5 Pulse to the Input pulse of the receiving device 6 Attach SDI 6 Pulse A to the Input pulse of the receiving device 7 Attach SDI 7 Pulse to the Input pulse of the receiving device PROGRAMMING Programming the Series SDI is accomplished by installing the Data Industrial programming software on a computer and entering data on templates of the Windows based program 1 Load the interface software into the computer 2 Connect the computer to the SDI with the Data Industrial A 301 communications cable to the socket labeled D I C Comm Port taking care to properly align the tab on the plug and socket to maintain polarity Connect the DB9 connector of the Data Industrial A 301 communications cable to the PC COM port of a PC that has the SDI software installed 3 Connect the Series SDI Flow Sensor to a power supply 4 Open the interface softw
33. or Pipe and wall thickness is required Page 22 SEN UM 00215 EN 09 November 2014 K amp OFFSET TABLES K amp Offset Tables For sizes above 30 in consult factory Pipe O D amp Schedule or pipe O D amp I D or pipe O D amp wall thickness is required Table B1 Estimated K amp Offset Pipe Pipe Schedules Size O D 55 555 5 10 5510 CS 40 5540 5 80 SS 80 iiin t K 0 427271 0 427271 0 380552 0 380552 0 341075 0 341075 0 277850 0 277850 Offset 0 080605 0 080605 0 002211 0 002211 0 081460 0 081460 0 226312 0 226312 T pe K 0 673452 0 673452 0 626407 0 626407 0 579615 0 579615 0 514211 0 514211 i i Offset 0 380524 0 380524 0 332296 0 332296 0 282874 0 282874 0 206396 0 206396 Fiian 2875 K 0 965024 0 965024 0 911744 0 911744 0 802796 0 802796 0 716671 0 716671 Offset 0 749072 0 749072 0 667702 0 667702 0 522645 0 52264 0 425526 0 425526 sin K 1 582350 1 582350 1 490176 1 490176 1 277418 1 277418 1 118942 1 118942 Offset 2 113500 2 113500 1 870796 1 870796 1 355648 1 355648 1 022076 1 022076 T TET K 2 091068 2 091068 2 024960 2 024960 1 856175 1 856175 1 621456 1 621456 i Offset 1 399853 1 399853 2 010633 2 010633 4 014395 4 014395 2 219542 2 219542 P m K 2 635261 2 635261 2 544009 2 544009 2 279943 2 279943 2 083741 2 083741 i i Offset 1 524904 1 524904 1
34. ove 30 in consult factory Pipe O D amp Schedule or pipe O D amp I D or pipe amp wall thickness is required A blank cell No data at time of printing Page 20 SEN UM 00215 EN 09 November 2014 Customer Reference Number Tables Table A1 Customer Reference Number Pipe Pipe Schedules Size O D Description 10 105 40 40s Std 80 SDR21 Wall 0 250 0 250 0 688 0 375 1 219 24 in 24 000 Insertion Depth 3 53 3 53 3 39 3 49 3 23 Customer Ref 4 21 32 4 21 32 4 31 32 4 3 4 5 5 16 Wall 0 312 0 375 26 in 26 000 Insertion Depth 3 81 3 79 Customer Ref 5 5 1 32 Wall 0 312 0 375 28 in 28 000 Insertion Depth 4 11 4 09 Customer Ref 5 9 32 5 11 32 Wall 0 312 0 312 0 375 30 in 30 000 Insertion Depth 4 41 4 41 4 39 a Customer Ref 5 19 32 5 19 32 5 5 8 For sizes above 30 in consult factory Pipe O D amp Schedule or pipe O D amp I D or pipe O D amp wall thickness is required A blank cell No data at time of printing Table A2 Customer Reference Number Copper Tube Type Size O D Description K L M DWV Wall 0 072 0 060 0 049 0 042 1 1 2 in 1 625 Insertion Depth 0 48 0 49 0 50 0 51 Customer Ref 1 7 16 1 7 16 1 7 16 1 7 16 Wall 0 083 0 070 0 058 0 042 2in 2 125 Insertion Depth 0 72 0 73 0 74 0 76 Customer Ref 1 11 16 1 11 16 1 11 16 1 11 16 Wall 0 095 0 08
35. r 0 3 feet per second to over 20 fps regardless of the conductivity or turbidity of the liquid The standard frequency output produces a low impedance square wave signal proportional to flow rate that may be transmitted up to 2000 feet without amplification Models are available to measure flow in one or both directions All SDI insert sensors are mounted on the pipe using 1 in tap As with any insert sensor a pipe saddle or weld on fitting is preferred over a service tee because it causes fewer disturbances to the flow MODELS AVAILABLE Direct insert sensor models are installed in piping configurations that are not in service or under pressure Hot tap insert sensor models feature isolation valves and mounting hardware to install or remove the sensor from a pipeline that would be difficult to shut down or drain In a true hot tap installation the sensor is mounted in the pipe under pressure by attaching service saddle or weld on fitting to the pipe and mounting the isolating valve and nipple to the threaded connection hole is then cut in the wall of the pipe through the valve using commercial tapping machine with 1 in size cutter Once the hole is cut the tapping machine is removed and the valve is shut Then the sensor assembly is mounted to the isolation valve and extended into the pipeline to measure flow Even in new construction hot tap sensor may be appropriate for service considerations The small stem diameter a
36. rical Installation s 54 0 sae sed oes oto Kaas gna e RUE s ESA Rex GE SRG seb oe Hae d ale 11 Programming a a sa aa se Ge seg ge rer sa a Ba RR Y 13 Single Direction Analog Output 14 Single Direction Scaled Pulse Output 1 5 4 he 15 Bidirectional Analog Output Models 1 2 mue 16 Bidirectional Scaled Pulse Output 17 Battery Powered SDI 18 Customer Reference Number Tables 4 20 KG Offset Tables mase eek ee Se Ow a ah a aa 23 Specifications ss ac arr SURGE wR a a S ERR ds 25 Page 2 November 2014 Introduction INTRODUCTION The Data Industrial SDI Series impeller flow sensor offers unparalleled performance for liquid flow measurement in closed pipe systems an easy to install economical package Impeller sensors offer a quick response to changes in flow rate and are well suited to flow control and batch type applications in addition to flow monitoring The new four bladed impeller design is rugged non fouling and does not require custom calibration Coupled with the proprietary patented digital detection circuit the sensor measures flows from unde
37. ta file version 0 56 Edit Custom and see Note 2 Step 5 Enter 4mA flow rate This is AnalegLeep Settings normally zero Step 6 Low Setting 4ma I Enter 20mA flow rate ss 2 For models with LCD Display Option select the desired LCD Configuration from the pull down menu If Model ED i has no display then skip to Step 8 Step 8 Press Send to transmit calibration data to the SDI Sensor Press to reset all parameters back to factory defaults Send must be pressed to send this data to the SDI Step 9 Press to exit parameters screen and to go back to the Press to retrieve calibration main screen data from SDI NOTE 1 Press Details to see and offset numbers for the selected pipe The K and offset are factors used to convert the sensor frequency to flow rate They are unique to each pipe size material NOTE 2 Press Custom to enter K and offset numbers for pipe material not listed in pull down menu The numbers may be obtained by contacting Data Industrial Page 14 SEN UM 00215 EN 09 November 2014 Programming Single Direction Scaled Pulse Output Models Stop Select rate units from the pull down Load Save Advanced Params Exit Step 2 values mmm EEE Select total units from the Step Rate x Total caron pull down values 2 5 n S Wl enn e geene OOOO See Note 1 present then select
38. the Customer Reference Number Tables on page 20 and note the Customer Reference Number Customer Ref NOTE The Customer Reference Number has been calculated using the following formula Ref Insertion Depth Wall Thickness Cover Thickness Figure 5 Dimension B Page 6 SEN UM 0021 5 EN 09 November 2014 er Stem Cap Stem Collar Le Cover Mounting Adapter N Pipe Saddle ref Figure 6 Dimension C November 2014 Mechanical Installation b Next measure from the outside wall of the pipe to the top of the installed mounting adapter this is dimension in Figure 5 c Add this number to the reference measurement The resulting number is dimension C in Figure 6 on page 7 Dimension C Customer Ref Dimension d Dimension C is the distance from the recess of the sensor tip to the bottom of the stem collar Insert the metal tab of a tape measure into the recess of the flow sensor tip Extend the tape up the stem and mark the shaft with a pencil e Slide the collar along the shaft until its bottom surface is at the mark on the stem Tighten the cap screw on the collar When the sensor is reassembled this will set the insertion depth of the sensor Attach the sensor to the mounting adapter by gently pushing the flow sensor into the mounting adapter until the cover touches the mounting adapter Tighten the cover against the O ring seal This w
39. tioned You can program the unit for pipe size and flow scale This is a two wire option 1 Attach SDI 1 Shield to Earth Ground or Power Supply Common This provides maximum power and signal EMI protection Analog output wired as current sinking 1 Attach SDI 2 Loop to the Analog input terminal of device receiving this 4 20 mA signal 2 Attach SDI 3 Loop to 24V DC terminal of device receiving the 4 20 mA signal Analog output wired as current sourcing with separate 24V DC power supply 1 Attach SDI 2 Loop to Analog input terminal of device receiving this 4 20 mA signal Sometimes labeled Loop 2 Attach SDI Loop to 24V DC Supply terminal 3 Attach 24V DC Supply terminal to the Analog Input Common Sometimes labeled Loop November 2014 SEN UM 00215 EN 09 Page 11 Electrical Installation Scaled Pulse output Option 2 in the ordering matrix 12345 oo000 1 Shield 2 Power 3 Power 4 Pulse 5 Pulse Bidirectional Analog Output Option 5 in the ordering matrix 1234567 0000 N APRONS Shield Power Power Direction Direction Loop Loop Analog output wired as current sinking 1 Attach SDI 46 Loop to the Analog input terminal of device r
40. utton and see Note 2 Step 6 Enter the number of units per pulse and select the pulse width required Step 8 Select Active Direction Press to reset all parameters back to factory defaults Send must be pressed to send this data to the SDI Step 11 Press to exit parameters screen and to go back to the main screen NOTE 1 Press Details to see and offset numbers for the selected pipe The and offset are factors used to convert the sensor frequency to flow rate They are unique to each pipe size material NOTE 2 Press Custom to enter K and offset numbers for pipe material not listed in pull down menu The numbers may be obtained by contacting Data Industrial NOTE 3 Press Change Label to change flow direction label Enter up to 20 characters such as From Pump November 2014 SEN UM 00215 EN 09 Page 17 Programming Battery Powered SDI Programming Programming the Series SDI is accomplished by installing the Data Industrial programming software on a computer and entering data on templates of the Windows based program 1 Load the interface software into the computer 2 Connect the PC to the SDI with the Data Industrial A 303 communications cable Plug in the RJ11 plug on the A 303 cable to the RJ11 socket on Battery Powered SDI Connect the DB9 connector of the A 303 cable to the PC COM port to a PC that has the SDI software installed Open the interface software and sel

Download Pdf Manuals

image

Related Search

Related Contents

bedienungsanleitung operating instructions notice d  Trabajo de embarque del remolcador: MONTORIOL  Aopen G528 ATX  Samsung Galaxy Tab S (10.5, Wi-Fi) Felhasználói kézikönyv(Lollipop)  Paramétrer un nouveau compte sous Thinderbird  Untitled  

Copyright © All rights reserved.
Failed to retrieve file