Contents
1. This is the safety ground for the drive that is required by code One of these points must be connected to adjacent building steel girder joist a floor ground rod or bus bar Grounding points must comply with national and local industrial safety regulations and or electrical codes 4 1 4 Motor Ground The motor ground must be connected to one of the ground terminals on the drive 4 1 5 Ground Fault Monitoring As with all inverters a leakage current to earth can exist The Optidrive is designed to produce the minimum possible leakage current whilst complying with worldwide standards The level of current is affected by motor cable length and type the effective switching frequency the earth connections used and the type of RFI filter installed If an ELCB Earth Leakage Circuit Breaker is to be used the following conditions apply e A Type B Device must be used e The device must be suitable for protecting equipment with a DC component in the leakage current e Individual ELCBs should be used for each Optidrive 4 1 6 Shield Termination Cable Screen The safety ground terminal provides a grounding point for the motor cable shield The motor cable shield connected to this terminal drive end should also be connected to the motor frame motor end Use a shield terminating or EMI clamp to connect the shield to the safety ground terminal 4 2 Wiring Precautions Connect the Optidrive according to section 4 3 ensuring that motor t
2. DARE www invertek co uk OPTIDRIVE lt p AC Variable Speed Drive 0 75kW 160kW 1HP 250HP 200 480 Volt 1 amp 3 Phase Installation Operating Instructions s gt G Wes A B LA aee l PY JA 1 K i OPTIDRIVE T d ous wr wre 00 2 pss 10000 Optidrive P2 Easy Start Up Guide AC Supply Connection Supply Voltage 3 Phase Units Connect L1 L2 L3 PE 200 240 Volts 10 1 Phase Units Connect L1 L2 PE 380 380 Volts 10 A ml Fuses or MCB Fuses or MCB o Check the Drive Rating Information on page 37 Help Card Display Keypad Operation can be found on page16 Control Terminals 000000000000 Sac 2000 es I I l Safe Torque Off STO Run Stop 10K Speed Pot Link the terminals as shown Close the switch to through the emergency stop run enable open circuit contacts to stop Motor Cable For correct cable size see Technical Data on page 37 Observe the maximum permissible motor cable length For Motor cable lengths gt 50 metres an output filter is recommended Use a screened shielded cable Motor Connection Check for Star or Delta Connection Enter the Motor Nameplate Data into the drive Parameters as follows Motor Rated Voltage P1 07 Motor Rated Current P1 08 Motor Rated Frequency P1 09 Motor Rated Speed Optional P1 10 www invertek co uk Optidr
3. Fault Occurs When Running If operating in Vector mode P4 01 0 or 1 reduce the speed loop gain in P4 03 04 Drive has tripped on overload after Check to see when the decimal points are flashing drive in overload and either increase delivering gt 100 of value in P1 08 for acceleration rate or reduce the load a period of time Check motor cable length is within the limit specified for the relevant drive in section 10 4 Ensure the motor nameplate parameters are correctly entered in P1 07 P1 08 and P1 09 If operating in Vector mode P4 01 0 or 1 also check the motor power factor in P4 05 and ensure an autotune has been successfully completed for the connected motor Check the load mechanically to ensure it is free and that no jams blockages or other mechanical faults exist PS ErP Instantaneous over current on drive Refer to fault 3 above output TA Over voltage on DC bus The value of the DC Bus Voltage can be displayed in PO 20 A historical log is stored at 256ms intervals prior to a trip in parameter PO 36 This fault is generally caused by excessive regenerative energy being transferred from the load back to the drive When a high inertia or over hauling type load is connected If the fault occurs on stopping or during deceleration increase the deceleration ramp time P1 04 or connect a suitable brake resistor to the drive If operating in Vector Mode reduce the speed loop gain P4 03 If operating in PID control ensure that ramp
4. S WIMINJOIN s_ Iuel N u uw uw E N ER 150 Output Current Nominal Output Current Optional Brake Resistor Input Recommended Current NIN ER O O N D E O R Rrj P N N N UU NINININININIOJO 37 5 36 pP B S RirRr R ININ N EEES NINININININIOININ U 58 5 CEES 08 135 165 225 270 3 Amps AA 4 37 5 36 585 MI 91 5 108 m 240 30 e The maximum motor cable length stated applies to using a shielded motor cable When using an unshielded cable the maximum cable length limit may be increased by 50 When using the Invertek Drives recommended output choke the maximum cable length may be increased by 100 e The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor terminals depending on the motor cable length and inductance The rise time and peak voltage can affect the service life of the motor Invertek Drives recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life e For UL compliant installation use Copper wire with a minimum insulation temperature rating of 70 C UL Class CC or Class J Fuses e Data values shown in Italics are provisional www invertek co uk 38 Optidrive ODP 2 User Guide Revision 1 00 11 Troubleshooting 11 1 Fault messages Fault Code No Description gt Corrective Action no rt Ft Displaye
5. 3 Phase Input kW Model Number HP Model Number Frame With Filter With Filter Current A Size ODP 2 24075 3KF42 0 75 ODP 2 24010 3HF42 ODP 2 24150 3KF42 15 ODP 2 24020 3HF42 2 41 2 ODP 2 24220 3KF42 ODP 2 24400 3KF42 ODP 2 34055 3KF42 ODP 2 34075 3KF42 75 ODP 2 W34100 3HF42_ 10 18 3 ODP 2 34110 3KF42 2 2 Drive model numbers IP55 200 240V 10 3 Phase Input kW Model Number HP Model Number With Filter With Filter Current A ODP 2 42055 3KF4N 5 5 ODP 2 32075 3HF4N 7 5 25 4 ODP 2 42075 3KF4N 5 ODP 2 42110 3KF4N pp 2 42150 3HFAN 15 46 4 ODP 2 52150 3KF4N ODP 2 52185 3KF4N ODP 2 62022 3KF4N ODP 2 62030 3HF4N_ 30 9 6 ODP 2 62030 3KF4N pP 2 62040 3HFAN 4 140 6 ODP 2 62037 3KF4N P 2 62050 3HF4N 50 1580 6 ODP 2 62045 3KF4N ODP 2 62060 3HF4N_ 60 180 ODP 2 72055 3KF4N 7 ODP 2 72075 3KF4N 7 ODP 2 72090 3KF4N ODP 2 72125 3HF4N 125 312 7 380 480V 10 3 Phase Input kW Model Number HP Model Number Output E kW tes HP With Filter With Filter Current A 11 N ER N O g gt alala lwlwlnlilele ajajan NOIN nA ODP 2 44110 3KF4N ODP 2 44150 3HF4N 25 15 4 61 50 ODP 2 64045 3KFAN 45 ODP 2 64060 3HF4N_ 60 90 ODP 2 64055 3KFAN 55 ODP 2 64075 3HF4N 75 1o ODP 2 64090 3KFAN 90 ODP 2 64150 3HF4N 150 180 www invertek co uk Optidrive ODP 2 User Guide Revision 1 01 3 Mechanical Installation 3 1 General e The O
6. DISPLAY A cia 19 5 9 Resetting Parameters to Factory Default Settings AA ee A 19 SIO Termina CONTON merisea ia ener pir rte nn Sele ni Se E ene ene Te ne rt eee ES 20 pel Oy Keyp CONTO a 21 5 12 Operating in Sensorless Vector Speed Control MOdeC ccccccccsssccccessccccensccceeeccessuecessnecessueeceseaeeessauecesaueeessaseessaeeesees 21 6 Parameters ninio Iii A EE EE Ea 22 6 1 Parameter SEK OVE Winston Seite 22 6 2 Parameter Group L Basie Fara meter Si n was E E T E E NE 22 To Digital input FUNCTIONS ista sini a o a aiat 24 TL DieltallaputCcontieuration Parameter Pl id 24 3 Extended Parameters ainne E E coat 26 8 1 Parameter Group 24 Extended parameter e 26 8 2 Parameter Group 3 PID COTON eieiei a eaa a a a an 30 8 3 Parameter Group 4 High Performance Motor Control iii daa 31 8 4 Parameter Group 5 Communication Parameters ssessssssessesseesresresseeseesresresseosresreeresseoseosreereoeseoseesresreeseoseesreseeseesree 32 8 5 Parameter Group O Monitoring Parameters Read Only ooooccccnnnnncnononccnnnnnononanoconnnnnnononarononnnnononanorononnnnnnanironnnns 33 9 Serial COMMUNICATIONS visesesicacssvevesacdccevecsusvercusvesweuesteeanesvancbecscoveaveietuew elec diesen teuseuenaestenenvetseses 35 gle RS ASS COMMMUMI CALI a E A E E E A EO T 35 g2 Mog pu R CAMA CA a 35 TO Technical Dt ca EE ia 37 OAs SENVIFON Nal 37 VOZ ANPUEVO IL TANG CS tn til 37 10 35 Maximam supp ratings to
7. and follow all information regarding transport storage installation and use of the Optidrive including the specified environmental limitations Do not perform any flash test or voltage withstand test on the Optidrive Any electrical measurements required should be carried out with the Optidrive disconnected Electric shock hazard Disconnect and ISOLATE the Optidrive before attempting any work on it High voltages are present at the terminals and within the drive for up to 10 minutes after disconnection of the electrical supply Always ensure by using a suitable multimeter that no voltage is present on any drive power terminals prior to commencing any work Where supply to the drive is through a plug and socket connector do not disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fault current which normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used must comply with Directive 98 37 EC Safety of Machinery In particular the machine manufacturer is responsible for providing a main switch and ensuring the electrical eq
8. bi directional keypad mode is enabled 5 2 Changing Parameters Procedure Display shows Power on Drive GE oP lt Press and hold the for gt 2 seconds PEDOL Press the A Key P Uc P l 09 etc can be used to select the desired parameter Select the required parameter e g P1 02 Press the button and keys to adjust the value e g set to 10 ww Press the key The parameter value is now adjusted and automatically stored Press the key for gt 2 seconds to return to operating mode www invertek co uk 16 Optidrive ODP 2 User Guide Revision 1 00 5 3 Advanced Keypad Operation Short Cuts Function When Display shows Example Display shows P 1 10 The next highest A Parameter group is es selected Px XX Fast Selection of Parameter Groups Note Parameter Group Access must be enabled P1 14 101 Display shows Pe 01 Display shows P2 gb The next lowest v Parameter group is Bran selected Display shows P l 01 Display shows P l I0 The first parameter of a A v group is selected Press Display shows P l 01 When editing P1 01 Display shows 50 0 The parameter is set to ry v the minimum value ee Display shows 0 0 When editing P1 10 Select lowest Group Parameter Any numerical value Whilst editing a parameter value Set Parameter to minimum value D G D 8 Display shows O Press Y Display shows O Any numerical value Press
9. drive systems Safety requirements Electrical thermal and energy EN 61800 3 2 Ed 2004 Adjustable speed electrical power drive systems EMC requirements and specific test methods EN 55011 2007 Limits and Methods of measurement of radio disturbance characteristics of industrial scientific and medical ISM radio frequency equipment EMC EN60529 1992 Specifications for degrees of protection provided by enclosures Electromagnetic Compatibility All Optidrives are designed with high standards of EMC in mind All versions suitable for operation on Single Phase 230 volt and Three Phase 400 volt supplies and intended for use within the European Union are fitted with an internal EMC filter This EMC filter is designed to reduce the conducted emissions back into the supply via the power cables for compliance with harmonised European standards It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC legislation of the country of use Within the European Union equipment into which this product is incorporated must comply with the EMC Directive 2004 108 EC When using an Optidrive with an internal or optional external filter compliance with the following EMC Categories as defined by EN61800 3 2004 can be achieved 1 Phase 230 Volt No additional filtering required Input Use shielded motor cable ODP 2 x2xxx xxBxx 3 Phase 400 Volt Use External Filter OD Fx34x
10. ensure isolation of the main supply from line inputs Wait ten 10 minutes for the capacitors to discharge to safe voltage levels Failure to observe this precaution could result in severe bodily injury or loss of life Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install adjust operate or service this equipment Read and understand this manual and other applicable manuals in their entirety before proceeding Failure to observe this precaution could result in severe bodily injury or loss of life 4 1 1 Grounding Guidelines The ground terminal of each Optidrive should be individually connected DIRECTLY to the site ground bus bar through the filter if installed Optidrive ground connections should not loop from one drive to another or to or from any other equipment Ground loop impedance must confirm to local industrial safety regulations To meet UL regulations UL approved ring crimp terminals should be used for all ground wiring connections The drive Safety Ground must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connections should be checked periodically 4 1 2 Protective Earth Conductor The Cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductor 4 1 3 Safety Ground
11. fuses may be required The operating time of the fuses must be below 0 5 seconds e Where allowed by local regulations suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilised in place of fuses providing that the clearing capacity is sufficient for the installation e When the power supply is removed from the drive a minimum of 30 seconds should be allowed before re applying the power A minimum of 5 minutes should be allowed before removing the terminal covers or connection e The maximum permissible short circuit current at the Optidrive Power terminals as defined in IEC60439 1 is 100kA www invertek co uk 13 Optidrive ODP 2 User Guide Revision 1 01 e An optional Input Choke is recommended to be installed in the supply line for drives where any of the following conditions occur o The incoming supply impedance is low or the fault level short circuit current is high o The supply is prone to dips or brown outs o An imbalance exists on the supply 3 phase drives o The power supply to the drive is via a busbar and brush gear system typically overhead Cranes e Inall other installations an input choke is recommended to ensure protection of the drive against power supply faults Part numbers are shown in the table Supply Frame Size AC Input Inductor 230 Volt OD IL221 IN 1 Phase OD IL321 IN 400 Volt OD IL 243 IN 3 Phase OD IL 343 IN 4 4 Operation of 3 Phase drives from a Single Phase Supply A sp
12. input 3 aaa aac O Stop O Stop Normally Open N O Normally Open N O O Selected Speed Ref C Run Fwd C Run Rev Close to increase speed Close to reduce speed C Preset speed 1 Normally Open N O Normally Closed N C Normally Open N O O Selected Speed Ref Close to run Fwd Open to Stop Close to run Rev A see Neletelice C Preset speed 1 The Selected Speed Reference referred to in the above table is determined by the value set in P1 12 Control Mode P1 12 control Mode Selected Speed Reference O Terminal Mode Analog input 1 1 Keypad Mode uni directional Digital Potentiometer 2 Keypad Mode bi directional Digital Potentiometer O Selected Speed Ref C Preset speed 1 4 3 User PID mode PID controller output 4 Fieldbus Control Speed reference via Fieldbus 5 Slave Mode Speed reference via Optibus Note If a motor thermistor is to be connected this must be selected in P2 33 www invertek co uk 25 Optidrive ODP 2 User Guide Revision 1 01 8 Extended Parameters 8 1 Parameter Group 2 Extended parameters Par Parameter Name O O Z O O Minimum Maximum Default Units P2 02 Preset JogFrequency Speed2 Pto Pros 100 Hz Rpm P2 03 Preset JogFrequency Speed3 Pto Pros 250 Hz Rpm P2 05 Preset JogFrequency Speed5 __ o Pto Pros 00 Hz Rpm P2 06 Preset JogFrequency Speed6 Pio2 Pros 00 Hz Rpm P2 07 Preset JogFrequency Speed7 P
13. removed the drive output is immediately disabled and the motor will coast freewheel to stop If the load can continue to rotate due to inertia and the drive may possibly be re enabled whilst the motor is still rotating the spin start function P2 26 should be enabled In this mode the drive brake transistor where fitted is disabled 2 Ramp To Stop When the enable signal is removed the drive will ramp to stop with the rate controlled by P1 04 as described above The Optidrive Brake chopper is also enabled in this mode 3 Coast to Stop When the enable signal is removed the drive output is immediately disabled and the motor will coast freewheel to stop If the load can continue to rotate due to inertia and the drive may possibly be re enabled whilst the motor is still rotating the spin start function P2 26 should be enabled The drive brake chopper is enabled in this mode however it will only activate when required during a change in the drive frequency setpoint and will not activate when stopping P1 06 Energy Optimiser 9091 90 o Only active when enhanced V F motor control mode is selected P4 01 2 0 Disabled 1 Enabled When enabled the Energy Optimiser attempts to reduce the overall energy consumed by the drive and motor when operating at constant speeds and light loads The output voltage applied to the motor is reduced The Energy Optimiser is intended for applications where the drive may operate for some p
14. to display the motor power Press again to return to speed display To stop the motor disable the drive by opening the control switch terminals 1 2 If the enable disable switch is opened the drive will decelerate to stop at which time the display will show SEoP www invertek co uk oe Optidrive ODP 2 User Guide Revision 1 00 Keypad Control To allow the Optidrive to be controlled from the keypad in a forward direction only set P1 12 1 5 12 Connect the drive to the supply ensuring the correct voltage and fusing circuit breaker protection see section 10 4 Connect the motor to the drive ensuring the correct star delta connection for the voltage rating see section 4 6 Apply the mains power to the drive then enter the motor data from motor nameplate P1 07 motor rated voltage P1 08 motor rated current P1 09 motor rated frequency Connect the Drive Hardware Inhibit STO circuit as follows see section 4 7 for further details o Link Terminal 1 to Terminals 13 STO o Link Terminal 9 to Terminal 12 STO Connect a control switch between the control terminals 1 and 2 ensuring that the contact is open drive disabled Enable the drive by closing the switch between control terminals 1 amp 2 The display will show SEoP Press the D key The display shows H O D Press A to increase speed The drive will run forward increasing speed until A is released Press M to decrease speed The drive will decrease speed
15. trips being generated are reduced P3 12 PID Feedback Value Display Scaling Factor 0 000 50 000 OO Seas Applies a scaling factor to the displayed PID feedback allowing the user to display the actual signal level from a transducer e g 0 10 Bar etc P3 13 PID Feedback Wake Up Level Mie 100 00 Sets a programmable level whereby if the drive enters standby motor whilst operating under PID control the selected feedback signal must fall below this threshold before the drive will return to normal operation P3 14 Reserved Parameter EA ee EA No Function www invertek co uk Optidrive ODP 2 User Guide Revision 1 00 8 3 Parameter Group 4 High Performance Motor Control Incorrect adjustment of parameters in menu group 4 can cause unexpected behaviour of the motor and any connected machinery It is recommended that these parameters are only adjusted by experienced users P4 01 Parameter Name Minimum Maximum Default Units Motor Control Mode AA AO eee Selects the motor control method An autotune must be performed if setting O or 1 is used 0 Speed Control with Torque Limit vector 1 Torque Control with Speed Limit vector 2 Speed Control Enhanced V F Motor Parameter Auto tune Enable 0 1 0o J When set to 1 the drive immediately carries out a non rotating autotune to measure the motor parameters for optimum control and efficiency Following completion of the autotune th
16. until M is released The rate of deceleration is limited by the setting in P1 04 Press the O key The drive will decelerate to rest at the rate set in P1 04 The display will finally show SEoP at which point the drive is disabled To preset a target speed prior to enable press the Y key whilst the drive is stopped The display will show the target speed use the A amp M keys to adjust as required then press the Y key to return the display to SE OP Pressing the key will start the drive accelerating to the target speed To allow the Optidrive to be controlled from the keypad in a forward and reverse direction set P1 12 2 Operation is the same as when P1 12 1 for start stop and changing speed Press the lt gt key The display changes to H 0 0D Press A to increase speed The drive will run forward increasing speed until A is released Acceleration is limited by the setting in P1 03 The maximum speed is the speed set in P1 01 To reverse the direction of rotation of the motor press the key again Operating in Sensorless Vector Speed Control Mode Optidrive P2 can be programmed by the user to operate in Sensorless Vector mode which provides enhanced low speed torque optimum motor speed regulation regardless of load and accurate control of the motor torque In most applications the default Voltage Vector control mode will provide adequate performance however if Sensorless Vector operation is required use the following proc
17. 20 200 0 100 0 hal Adjustable Threshold 1 Lower Limit Analog Output 2 Relay Output 2 eo pato O Used in conjunction with some settings of Parameters P2 13 amp P2 18 NO UN bb WN F O CON OU BWN FE OO www invertek co uk 27 Optidrive ODP 2 User Guide Revision 1 01 P2 21 Display Scaling Factor 30 000 30 000 0 000 Display Scaling Source SS ES E Se P2 21 amp P2 22 allow the user to program the Optidrive to display an alternative output unit scaled from an existing parameter e g to display conveyer speed in metres per second based on the output frequency This function is disabled if P2 21 is set to O If P2 21 is set gt 0 the variable selected in P2 22 is multiplied by the factor entered in P2 21 and displayed whilst the drive is running with a c to indicate the customer scaled units P2 22 Options 0 Motor Speed 1 Motor Current 2 Analog Input 2 Zero Speed Holding Time oo eee eid Determines the time for which the drive EETETEVETT E frequency is held at zero when stopping before the drive a is disabled P2 24 Effective Effective Switching Frequency Frequency Drive Rating Dependent Effective power stage switching frequency The range of settings available and factory default parameter setting depend on the drive power and voltage rating Higher frequencies reduce the audible ringing noise from the motor and improve the output current waveform at the e
18. 4 Mechanical dimensions IP20 Units aros 200 en sa oa tes Sor n ao e 2a 5s Ome 1008 a 261 10 28 206 969 ojo 6 026 205 aa 131 sas 80 315 55 022 10 039 Control Terminal Torque Settings All Sizes 0 8 Nm 7 Ib in Power Terminal Torque Settings All Sizes 1 Nm 8 85 lb in www invertek co uk Optidrive ODP 2 User Guide Revision 1 00 3 5 Guidelines for Enclosure mounting IP20 Units e Installation should be in a suitable enclosure according to EN60529 or other relevant local codes or standards e Enclosures should be made from a thermally conductive material e Where vented enclosures are used there should be venting above the drive and below the drive to ensure good air circulation see the diagram below Air should be drawn in below the drive and expelled above the drive e Inany environments where the conditions require it the enclosure must be designed to protect the Optidrive against ingress of airborne dust corrosive gases or liquids conductive contaminants such as condensation carbon dust and metallic particles and sprays or splashing water from all directions e High moisture salt or chemical content environments should use a suitably sealed non vented enclosure The enclosure design and layout should ensure that the adequate ventilation paths and clearances are left to allow air to circulate through the drive heatsink Invertek Drives recommend the followin
19. AN Open Communication Error Counter a This parameter is incremented every time an error occurs on the CAN Open communication link This information can be used for diagnostic purposes www invertek co uk 34 Optidrive ODP 2 User Guide Revision 1 00 9 Serial communications 9 1 RS 485 communications Optidrive P2 has an RJ45 connector on the front of the control panel This connector allows the user to set up a drive network via a wired connection The connector contains two independent RS485 connections one for Invertek s Optibus Protocol and one for Modbus RTU Both connections can be used simultaneously The electrical signal arrangement of the RJ45 connector is shown as follows RS 485 Modbus RTU RS 485 Modbus RTU The Optibus data link uses the same communication protocol as is used for IrDA communication This is used for the Master Slave function refer to the Optidrive P2 Advanced User Guide for further information Up to 62 slaves can be connected to one master drive The Modbus interface allows connection to a Modbus RTU network as described below 9 2 Modbus RTU Communications 9 2 1 Modbus Telegram Structure The Optidrive P2 supports Master Slave Modbus RTU communications using the 03 Read Holding Registers and 06 Write Single Holding Register commands Many Master devices treat the first Register address as Register 0 therefore it may be necessary to convert the Register Numbers detail in sec
20. D Control Par Parameter Name Minimum Maximum Default Units P3 01 PID Proportional Gain 01 300 to PID Controller Proportional Gain Higher values provide a greater change in the drive output frequency in response to small changes in the feedback signal Too high a value can cause instability PID Integral Time Constant A S00 A A PID Controller Integral Time Larger values provide a more damped response for systems where the overall process responds slowly PID Differential Time Constant oe cy LOA l o S S PID Differential Time Constant 1 Inverse Operation Use this mode if an increase in the motor speed should result in a decrease in the feedback signal PID Reference Setpoint Source Select SS 2 Selects the source for the PID Reference Setpoint 0 Digital Preset Setpoint P3 06 is used 1 Analog Input 1 Setpoint 2 Analog Input 2 Setpoint PID Digital Reference Setpoint A IO coe eee ee When P3 05 0 this parameter sets the preset digital reference setpoint used for the PID Controller P3 07 PID Controller Output Upper Limit P3 08 100 0 100 0 Limits the maximum value output from the PID controller P3 08 PID Controller Output Lower Limit 00 Treo Too Limits the minimum output from the PID controller PID Output Limit Control ASA A PID Operating Mode A SiS O Direct Operation Use this mode if an increase in the motor speed should result in an increas
21. No additional filtering required Input Use screened motor cable ODP 2 x4xxx xxAxx For motor cable lengths greater than 100m an output dv dt filter must be used please refer to the Invertek Stock Drives Catalogue for further details Vector Speed and Torque control modes may not operate correctly with long motor cables and output filters It is recommended to operate in V F mode only for cable lengths exceeding 50m Note All rights reserved No part of this User Guide may be reproduced or transmitted in any form or by any means electrical or mechanical including photocopying recording or by any information storage or retrieval system without permission in writing from the publisher Copyright Invertek Drives Ltd 2011 All Invertek Optidrive P2 units carry a 2 year warranty against manufacturing defects from the date of manufacture The manufacturer accepts no liability for any damage caused during or resulting from transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installation incorrect adjustment of the operating parameters of the drive incorrect matching of the drive to the motor incorrect installation unacceptable dust moisture corrosive substances excessive vibration or ambient temperatures outside of the design specification The local distributor may offer different terms and conditions at t
22. Speed Reference Displays the setpoint being received by the drive from the currently active Fieldbus interface PO 08 PID Reference Setpoint Displays the setpoint input to the PID controller PO 09 PID Feedback Level Displays the Feedback input signal to the PID controller PO 10 PID Controller Output Displays the output level of the PID controller Applied Motor Voltage Displays the instantaneous output voltage from the drive to the motor Output Torque Displays the instantaneous output torque level produced by the motor Trip History Log LY Displays the last four fault codes for the drive Refer to section 11 1 for further information Motor Magnetising Current Id Displays the motor magnetising Current providing an auto tune has been successfully completed Motor Rotor Current Iq Displays the motor Rotor torque producing current providing an auto tune has been successfully completed DC Bus Voltage Ripple Level Displays the level of ripple present on the DC Bus Voltage This parameter is used by the Optidrive for various internal protection and monitoring functions Motor Stator resistance Rs Displays the measured motor stator resistance providing an auto tune has been successfully completed Motor Stator Inductance Ls Displays the measured motor stator inductance providing an auto tune has been successfully completed Motor Rotor Resistance Rr Displays the measured motor rotor resist
23. UF if the signal level falls below 3mA r 4 20 4 to 20mA Signal the Optidrive will ramp to stop if the signal level falls below 3mA E 20 54 20 to 4mA Signal the Optidrive will trip and show the fault code 4 2UF if the signal level falls below 3mA r 20 54 20to 4mA Signal the Optidrive will ramp to stop if the signal level falls below 3mA P2 34 Analog Input 2 Scaling Ea 500 0 100 0 Scales the analog input by this factor e g if P2 30 is set for 0 10V and the scaling factor is set to 200 0 a 5 volt input will ee in the drive running at maximum speed P1 01 Analog Input 2 Offset 500 0 500 0 00 Sets an offset as a percentage of the full scale range of the input which is applied to the analog input signal E Start Mode Select Automatic Restart__ SeeBelow Allto D Defines the behaviour of the drive relating to the enable digital input and also configures the Automatic Restart A Ed9E r Following Power on or reset the drive will not start if Digital Input 1 remains closed The Input must be closed after a power on or reset to start the drive AUEo Following a Power On or Reset the drive will automatically start if Digital Input 1 is closed AUEo Ito AUEo 5 Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The drive must be powered down to reset the counter The numbers of restart attempts are counted and if the drive fails to start on the final att
24. Whilst editing a parameter value Adjusting individual digits within a parameter value Individual parameter digits can be adjusted Display shows iD Press Y Display shows iD Press Display shows ig ETC 5 4 Drive Operating Displays Display Status StoP Drive mains power applied but no Enable or Run signal applied AUto Motor Autotune in progress H x x Drive running display shows output frequency Hz Whilst the drive is running the following displays can be Drive running display shows motor current Amps SS selected by briefly pressing the button on the drive Drive Running display shows motor power kW Each press of the button will cycle the display through to the C xx Drive Running display shows customer selected units see next selection parameters P2 21 and P2 22 Fec 24 Drive mains power not present external 24 Volt control power supply present only I nh Output power hardware inhibited Safe Torque Off function activated External links are required to the STO inputs terminals 12 and 13 as shown in section 4 8 Control Terminals Connection Diagram P dEF Parameters reset to factory default settings U dEF Parameters reset to User default settings For drive fault code displays refer to section 11 1 on page 39 www invertek co uk 17 Optidrive ODP 2 User Guide Revision 1 01 5 5 Keypad Layout and Function Optional OLED Keypad IP55 Units only For IP55 drives an option
25. al Multi Language OLED display keypad may be specified at the time of order option code Tx OLED Display Main Displayed Parameter Shows which of the selectable parameters is currently being shown on the main display e g Motor Speed Motor Current etc STOP of kV 400V Operating Information Provides a real time display of key operating information e g output current and power Start Button When in Hand mode used to Start the drive Stop Reset Button Used to reset a tripped drive When in Hand mode used to Stop the drive Oi a eee 5 6 Drive Operating Displays INHIBIT or kV 400V an ES 400V Displayed when the Safe Torque Displayed when the drive power Off function is activate is applied motor stopped Maximum speed limit P1 01 01 3ph Output Frequency 23 7 Hz Drive operating display showing output information T250 0 Control Keypad Provides access to the drive parameters and also allows control of the drive when Hand operation is selected Navigate Button Used to display real time information to access and exit parameter edit mode and to store parameter changes Up Button Used to increase speed in real time mode or to increase parameter values in parameter edit mode Down Button Used to decrease speed in real time mode or to decrease parameter values in parameter edit mode 01 fg Under voltage U Volt 0 02kWW Press STOP key to reset Drive tri
26. ance providing an auto tune has been successfully completed DC Bus Voltage Displays the instantaneous DC Bus Voltage internally within the drive Drive Temperature Displays the Instantaneous Heatsink Temperature measured by the drive Time Remaining to next service PO 11 PO 12 PO 13 PO 14 PO 15 PO 16 PO 17 PO 18 PO 19 PO 21 Displays the number of hours remaining on the service time counter before the next service is due Operating Time Accumulated With Heatsink Temperature Above 80 C HH MM SS Displays the amount of time in hours and minutes that the Optidrive has operated for during its lifetime with a heatsink temperature in excess of 80 C This parameter is used by the Optidrive for various internal protection and monitoring functions Operating Time Accumulated With Ambient Temperature Above 80 C Displays the amount of time in hours and minutes that the Optidrive has operated for during its lifetime with an ambient temperature in excess of 80 C This parameter is used by the Optidrive for various internal protection and monitoring functions Rotor Speed Estimated or Measured DN In Vector control mode this parameter displays either the estimated rotor speed of the motor if no encoder feedback is present or the measured rotor speed if an optional Encoder Feedback Interface Option is fitted www invertek co
27. cable P1 14 P2 40 101 Allows access to Parameter Groups 0 5 www invertek co uk 23 Optidrive ODP 2 User Guide Revision 1 01 7 Digital Input Functions 7 1 Digital Input Configuration Parameter P1 13 Digital Input 1 Digital Input 2 Digital Input 3 Analog Input 1 Analog Input 2 Terminal 2 Terminal 3 Terminal 4 Terminal 6 Terminal 10 User defined User defined User defined O Forward O Selected Speed Ref O Preset speed 1 C Reverse C Preset speed 1 2 C Preset speed 2 Off Off S Off ene oa Off n O n O n On O O Forward O Selected Speed Ref N External trip C Reverse C Preset speed 1 RAOR O trip C Run Digital input 3 O Forward ese ue eae External trip a ee Digital input 3 Por off PresetSpeed1 O Forward O Decel ramp 1 P1 04 Sr REVEIRE DECE Tampa Digital input 3 ooo o off PresetSpeed1 O Forward a a E O Selected Speed Ref Pa a eet ta 10 O Stop O Forward Normally Open N O Normally Open N O O Selected Speed Ref C Run C Reverse Close to increase speed Close to reduce speed C Preset speed 1 www invertek co uk 24 Optidrive ODP 2 User Guide Revision 1 00 C Run Fwd C Run Rev C Preset speed 1 2 C Preset speed 2 B is O a O Stop O Stop External trip C Run Fwd C Run Rev O trip C Run Pp On 0n_ Preset Speed a O O O O 17 On Digital input 3 O Stop d ESEL eeN O Decel ramp 1 P1 04 ae bd ee PUN fone cane Digital
28. cy gt 0 0 Logic 1 when the motor runs above zero speed Output Frequency gt Limit Logic 1 when the motor speed exceeds the adjustable limit Output Current gt Limit Logic 1 when the motor current exceeds the adjustable limit Motor Torque gt Limit Logic when the motor torque exceeds the adjustable limit Analog Input 2 Signal Level gt Limit Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit Note When using settings 4 7 parameters P2 16 and P2 17 must be used together to control the behaviour The output will switch to Logic 1 when the selected signal exceeds the value programmed in P2 16 and return to Logic O when the signal falls below the value programmed in P2 17 8 Output Frequency Motor Speed O to P 01 9 Output Motor Current O to 200 of P1 08 10 Motor Torque 0 to 200 of motor rated torque 11 Output Motor Power 0 to 150 of drive rated power P2 12 Analog Output 1 Terminal 8 Format u 0 10 Ss NO UB WN RO U D ID 0to10V U ID 0 10 to OV A D 2g0 0 to 20mA A 20 0 20 to OmA A 4 20 4 to 20mA A 20 4 20 to 4mA www invertek co uk 26 Optidrive ODP 2 User Guide Revision 1 00 P2 13 Analog Output 2 Terminal 11 Function Select a a a Digital Output Mode Logic 1 24V DC Drive Enabled Running Logic 1 when the Optidrive is enabled Running Drive Healthy Logic 1 When no Fault condition exists on the drive At Target Frequ
29. d 15 will be linked together Drive Enabled Running Logic 1 when the motor is enabled Drive Healthy Logic 1 when power is applied to the drive and no fault exists At Target Frequency Speed Logic 1 when the output frequency matches the setpoint frequency Output Frequency gt 0 0 Hz Logic 1 when the drive output frequency to the motor is exceeds 0 0Hz Output Frequency gt Limit Logic 1 when the motor speed exceeds the adjustable limit Output Current gt Limit Logic 1 when the motor current exceeds the adjustable limit Output Torque gt Limit Logic 1 when the motor torque exceeds the adjustable limit Analog Input 2 Signal Level gt Limit 1 Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit Note When using settings 4 7 parameters P2 16 and P2 17 must be used together to control the behaviour The output will switch to Logic 1 when the selected signal exceeds the value programmed in P2 16 and return to Logic O when the signal falls below the value programmed in P2 17 P2 16 Adjustable Threshold 1 Upper Limit Analog Output 1 Relay Output 1 P2 17 200 0 100 0 P2 17 Adjustable Threshold 1 Lower Limit Analog Output 1 Relay Output 1 OO P2 16 ae Used in conjunction with some settings of Parameters P2 11 amp P2 15 P2 18 User Relay 2 Output User Relay 2 Output Terminals 17 8 18 Function select 17 amp 18 Function User Relay 2 Output Terminals 17 8 18 Func
30. d in PO 13 if no faults are recorded in the log HES Brake channel over current Ensure the connected brake resistor is above the minimum permissible level for the drive refer to the ratings shown in section 10 4 Check the brake resistor and wiring for possible short circuits DL br 02 Brake resistor overload The drive software has determined that the brake resistor is overloaded and trips to protect the resistor Always ensure the brake resistor is being operated within its designed parameter before making any parameter or system changes To reduce the load on the resistor increase deceleration the time reduce the load inertia or add further brake resistors in parallel observing the minimum resistance value for the drive in use 03 Instantaneous over current on drive Fault Occurs on Drive Enable output Check the motor and motor connection cable for phase phase and phase earth short Excess load on the motor circuits Check the load mechanically for a jam blockage or stalled condition Ensure the motor nameplate parameters are correctly entered P1 07 P1 08 P1 09 If operating in Vector mode P4 01 0 or 1 also check the motor power factor in P4 05 and ensure an autotune has been successfully completed for the connected motor Reduced the Boost voltage setting in P1 11 Increase the ramp up time in P1 03 If the connected motor has a holding brake ensure the brake is correctly connected and controlled and is releasing correctly
31. ds Drive Internal Cooling Fan Total Operating Time Displays the total operating time of the Optidrive internal cooling fans The first value shown is the number of hours Pressing the Up key will display the minutes and seconds This is used for scheduled maintenance information P0 37 P0 38 Ae Ambient Temperature Log 30s PO 40 Motor Current Log 256ms The above parameters are used to store the history of various measured levels within the drive at various regular time intervals prior to atrip The values are frozen when a fault occurs and can be used for diagnostic purposes see section for further information PO 41 Critical Fault Counter Over Current SF Critical fault counter Over Voltage Critical fault counter Under Voltage PO 44 Critical fault counter Over Temperature Critical fault counter Brake Transistor Over Current PO 46 Critical fault counter Ambient Over Temperature These parameters contain a record of how many times certain critical faults have occurred during a drives operating lifetime This provides useful diagnostic data Reserved EA Reserved Parameter Reserved o Reserved Parameter Modbus RTU Communication Error Counter ea aaa This parameter is incremented every time an error occurs on the Modbus RTU communication link This information can be used for P0 47 P0 48 PO 49 diagnostic purposes C
32. e Excessive voltage boost levels may result in increased motor current and temperature and force ventilation of the motor may o be required An automatic setting RUE o is also possible whereby the Optidrive will automatically adjust this parameter based on the motor parameters measured during an autotune P1 12 Primary Command Source Mode 0 6 o S S 0 Terminal Control The drive responds directly to signals applied to the control terminals 1 Uni directional Keypad Control The drive can be controlled in the forward direction only using an external or remote Keypad 2 Bi directional Keypad Control The drive can be controlled in the forward and reverse directions using an external or remote Keypad Pressing the keypad START button toggles between forward and reverse 3 PID Control The output frequency is controlled by the internal PID controller 4 Fieldbus Control Control via Modbus RTU if no fieldbus interface option is present otherwise control is from the fieldbus option module interface 5 Slave Mode The drive acts as a Slave to a connected Optidrive operating in Master Mode 6 CAN bus Control Control via CAN bus connected to the RJ45 serial interface connector P1 13 Digital Inputs Function Select Defines the function of the digital inputs depending on the control mode setting in P1 12 See section 7 1 for more information P1 14 Extended Menu Access Code Parameter Access Control The following settings are appli
33. e in the feedback signal 0 Digital Output Limits The output range of the PID controller is limited by the values of P3 07 amp P3 08 1 Analog Input 1 Provides a Variable Upper Limit The output range of the PID controller is limited by the values of P3 08 the signal applied to Analog Input 1 2 Analog Input 1 Provides a Variable Lower Limit The output range of the PID controller is limited by the signal applied to Analog Input 1 amp the value of P3 07 3 PID output Added to Analog Input 1 Value The output value from the PID Controller is added to the speed reference applied to the Analog Input 1 P3 10 PID Feedback Signal Source Select A A O eS 0 Analog Input 2 1 Analog Input 1 P3 11 Maximum PID Error to Enable Ramps 00 250 00 Defines a threshold PID error level whereby if the difference between the setpoint and feedback values is less than the set threshold the internal ramp times of the drive are disabled Where a greater PID error exists the ramp times are enabled to limit the rate of change of motor speed on large PID errors and react quickly to small errors Setting to 0 0 means that the drive ramps are always enabled This parameter is intended to allow the user to disable the drive internal ramps where a fast reaction to the PID control is required however by only disabling the ramps when a small PID error exists the risk of possible over current or over voltage
34. e parameter automatically returns to 0 E Vector Speed Controller Proportional Gain 400 0 Sets the proportional gain value for the speed controller when operating in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 Higher values provide better output frequency regulation and response Too high a value can cause instability or even over current trips For applications requiring best possible performance the value should be adjusted to suit the connected load by gradually increasing the value and monitoring the actual output speed of the load until the required dynamic behaviour is achieved with little or no overshoot where the output speed exceeds the setpoint In general higher friction loads can tolerate higher values of proportional gain and high inertia low friction loads may require the gain to be reduced P4 04 Vector Speed Controller Integral Time Constant 0 000 1 000 0 100 Sets the integral time for the speed controller Smaller values provide a faster response in reaction to motor load changes at the risk of introducing instability For best dynamic performance the value should be adjusted to suit the connected load low Motor Power Factor Cos PERRO O ore ES E When operating in Vector Speed or Vector Torque motor control modes this parameter must be set to the motor nameplate power factor P4 06 TorqueControlReference LimitSource 0 5 0 _ When P4 01 0 this parameter de
35. ecial function of Optidrive P2 allows all drives designed for operation on 3 phase supplies to be operated on a single phase supply of the correct rated voltage at up to 50 of the nominal capacity For Example Model Number ODP 2 64450 3KA4N can be operated on a single phase supply 380 480 volts with the maximum output current limited to 45 Amps The supply should be connected to the L1 and L2 terminals of the drive 4 5 Drive and Motor Connection e The motor should be connected to the Optidrive U V and W terminals using a suitable 3 or 4 core cable Where a 3 core cable is utilised with the shield operating as an earth conductor the shield must have a cross sectional area at least equal to the phase conductors when they are made from the same material Where a 4 core cable is utilised the earth conductor must be of at least equal cross sectional area and manufactured from the same material as the phase conductors e The motor earth must be connected to one of the Optidrive earth terminals e For compliance with the European EMC directive a suitable screened shielded cable should be used Braided or twisted type screened cable where the screen covers at least 85 of the cable surface area designed with low impedance to HF signals are recommended as a minimum Installation within a suitable steel or copper tube is generally also acceptable e The cable screen should be terminated at the motor end using an EMC type gland allowing connec
36. edure Ensure advanced parameter access is enabled by setting P1 14 101 Enter the motor nameplate details into the relevant parameters as follows P1 07 Motor Rated Voltage P1 08 Motor Rated Current P1 09 Motor Rated Frequency Optional P1 10 Motor Rated Speed Rpm o P4 05 Motor Power Factor Select Sensorless Vector control mode by setting P4 01 0 Ensure that the motor is correctly connected to the drive Carry out a motor data Autotune by setting P4 02 1 O O O OO The Autotune will begin immediately when P4 02 is set regardless of the status of the drive enable signal Whilst the autotune procedure does not drive or spin the motor the motor shaft may still turn slightly It is not normally necessary to uncouple the load from the motor however the user should ensure that no risk arises from the possible movement of the motor shaft It is essential that the correct motor data is entered into the relevant drive parameters Incorrect parameter settings can result in poor or even dangerous performance www invertek co uk 21 Optidrive ODP 2 User Guide Revision 1 01 6 Parameters 6 1 Parameter Set Overview The Optidrive P2 Parameter set consists of 6 groups as follows e Group 0 Read Only Monitoring Parameters e Group 1 Basic Configuration Parameters e Group 2 Extended Parameters e Group 3 PID Control Parameters e Group 4 High Performance Motor Control Parameters e Group 5 Field Bus Parameters When the Opt
37. eference used by the drive in conjunction with P4 06 P4 08 Minimum Motoring Torque Limit a P4 07 es eT Active only in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 Sets a minimum torque limit whereby the when the Optidrive is enabled it will always attempt to maintain this torque on the motor at all times whilst operating NOTE This parameter should be used with extreme care as the drive output frequency will increase to achieve the torque level and may exceed the selected speed reference P4 09 Generator Mode Max Torque Limit Maximum Regenerative Torque DAA 200 0 200 0 Active only in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 Sets the maximum regenerating torque allowed by the Optidrive P4 10 V F Characteristic Adjustment Frequency ao P1 09 a ra aa When operating in V F mode P4 01 2 this parameter in conjunction with P4 11 sets a frequency point at which the voltage set in P4 11 is applied to the motor Care must be taken to avoid overheating and damaging the motor when using this feature P4 11 V F Characteristic Adjustment Voltage es P1 07 NN Used in conjunction with parameter P4 10 P4 12 Reserved Parameter A O A ee No Function www invertek co uk 31 Optidrive ODP 2 User Guide Revision 1 01 8 4 Parameter Group 5 Communication Parameters Par Parameter Name Minimum Maximum Default P5 01 Drive Fie
38. empt the drive will fault with and will require the user to manually reset the fault P2 37 Keypad Mode Restart Speed PS EE oo This parameter is only active when P1 12 1 or 2 When settings O to 3 are used the drive must be started by pressing the Start key on the keypad When settings 4 7 are used the drive starting is controlled by the enable digital input 0 Minimum Speed Following a stop and restart the drive will always initially run at the minimum speed P1 02 1 Previous Operating Speed Following a stop and restart the drive will return to the last keypad setpoint speed used prior to stopping 2 Current Running Speed Where the Optidrive is configured for multiple speed references typically Hand Auto control or Local Remote control when switched to keypad mode by a digital input the drive will continue to operate at the last operating speed 3 Preset Speed 8 Following a stop and restart the Optidrive will always initially run at Preset Speed 8 P2 08 4 Minimum Speed Terminal Enable Following a stop and restart the drive will always initially run at the minimum speed P1 02 5 Previous Operating Speed Terminal Enable Following a stop and restart the drive will return to the last keypad setpoint speed used prior to stopping 6 Current Running Speed Terminal Enable Where the Optidrive is configured for multiple speed references typically Hand Auto control or Local Remote control when switched t
39. ency Speed Logic 1 when the output frequency matches the setpoint frequency Output Frequency gt 0 0 Logic 1 when the motor runs above zero speed Output Frequency gt Limit Logic 1 when the motor speed exceeds the adjustable limit Output Current gt Limit Logic 1 when the motor current exceeds the adjustable limit Output Toque gt Limit Logic when the motor torque exceeds the adjustable limit Analog Input 2 Signal Level gt Limit Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit Note When using settings 4 7 parameters P2 16 and P2 17 must be used together to control the behaviour The output will switch to Logic 1 when the selected signal exceeds the value programmed in P2 16 and return to Logic O when the signal falls below the value programmed in P2 17 8 Output Frequency Motor Speed 0 to P 01 9 Output Motor Current O to 200 of P1 08 10 Motor Torque 0 to 200 of motor rated torque 11 Output Motor Power 0 to 150 of drive rated power P2 14 Analog Output 2 Terminal 11 Format u 0 18 ESS NO UB WN FE O U D 10 0to10V U 10 B 10to OV A G 20 0 to 20mA A 20 0 20to OmA A 4 20 4to 20mA A 20 94 20 to 4mA P2 15 User Relay 1 Output Terminals 14 15 amp 16 Function select Poe O E A Selects the function assigned to Relay Output 1 The relay has three output terminals Logic 1 indicates the relay is active and therefore terminals 14 an
40. er rating the drives are designed for direct connection to the following supplies Model Number Supply Voltage Phases Frequency I 200 240 Volts 10 m a 299 240 Vols 10 5g goirs 5 380 480 Volts 10 For all power ratings above 2 2kW in 230V and all power ratings in 400V operation on a single phase supply is possible with a 50 derating of the output current capacity See section 4 4 for details All Optidrive P2 units have phase imbalance monitoring A phase imbalance of gt 3 will result in the drive tripping For input supplies which have supply imbalance greater than 3 typically the Indian sub continent amp parts of Asia Pacific including China Invertek Drives recommends the installation of input line reactors Alternatively the drives can be operated as a single phase supply drive with 50 derating 10 3 Maximum supply ratings for UL compliance Maximum supply voltage Maximum supply short circuit current All the drives in the above table are suitable for use on a circuit capable of delivering not more than the above specified maximum short circuit Amperes symmetrical with the specified maximum supply voltage For more details about the drive power rating size information please refer to the latest Optidrive brochure 10 4 Output Power and Current ratings The following tables provide the output current rating information for the various Optidrive P2 models Invertek Drives always recommend that select
41. eriods of time with constant speed and light motor load whether constant or variable torque P1 07 Motor Rated Voltage Drive Rating Dependent This parameter should be set to the rated nameplate voltage of the motor Volts P1 08 Motor Rated Current Drive Rating Dependent This parameter should be set to the rated nameplate current of the motor P1 09 Motor Rated Frequency 50 60 This parameter should be set to the rated nameplate frequency of the motor P1 10 Motor Rated Speed iC 0 300 O Rm This parameter can optionally be set to the rated nameplate rpm of the motor When set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip compensation function and the Optidrive display will now show motor speed in estimated rpm All speed related parameters such as Minimum and Maximum Speed Preset Speeds etc will also be displayed in Rpm Note When the drive is operated with the optional Encoder Feedback Interface this parameter must be set to the correct nameplate Rpm of the connected motor www invertek co uk 22 Optidrive ODP 2 User Guide Revision 1 00 P1 11 V F Mode Voltage Boost 00 DriveRating Dependent Voltage boost is used to increase the applied motor voltage at low output frequencies in order to improve low speed and starting torqu
42. erminal box connections are correct There are two connections in general Star and Delta It is essential to ensure that the motor is connected in accordance with the voltage at which it will be operated For more information refer to section 4 6 Motor Terminal Box Connections It is recommended that the power cabling should be 4 core PVC insulated screened cable laid in accordance with local industrial regulations and codes of practice 4 3 Incoming Power Connection e For 1 phase supply power should be connected to L1 L L2 N e For 3 phase supplies power should be connected to L1 L2 and L3 Phase sequence is not important e For compliance with CE and C Tick EMC requirements a symmetrical shielded cable is recommended e A fixed installation is required according to IEC61800 5 1 with a suitable disconnecting device installed between the Optidrive and the AC Power Source The disconnecting device must conform to the local safety code regulations e g within Europe EN60204 1 Safety of machinery e The cables should be dimensions according to any local codes or regulations Guideline dimensions are given in section 10 4 e Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line according to the data in section 10 4 The fuses must comply with any local codes or regulations in place In general type gG IEC 60269 or UL type T fuses are suitable however in some cases type aR
43. fines the source for the maximum output torque limit When P4 01 1 this parameter defines the source for the torque reference setpoint 0 Fixed Digital The torque controller reference limit is set in P4 07 1 Analog Input 1 The output torque is controlled based on the signal applied to Analog Input 1 whereby 100 input signal level will result in the drive output torque being limited by the value set in P4 07 2 Analog Input 2 The output torque is controlled based on the signal applied to Analog Input 2 whereby 100 input signal level will result in the drive output torque being limited by the value set in P4 07 3 Fieldbus The output torque is controlled based on the signal from the communications Fieldbus whereby 100 input signal level will result in the drive output torque being limited by the value set in P4 07 4 Master Slave The output torque is controlled based on the signal from the Invertek Master Slave whereby 100 input signal level will result in the drive output torque being limited by the value set in P4 07 5 PID Controller Output The output torque is controlled based on the output of the PID controller whereby 100 input signal level will result in the drive output torque being limited by the value set in P4 07 P4 07 Maximum Motoring Torque Limit P4 08 500 0 200 0 When operating in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 this parameter defines the maximum torque limit or r
44. g minimum sizes for drives mounted in non ventilated metallic enclosures Drive X Y Z Recommended Size Above amp Either Between airflow Below Side Note Dimension Z assumes that the drives are mounted side by side with no clearance Typical drive heat losses are 3 of operating load conditions Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times 3 6 Mounting the Drive IP20 Units o IP20 Units are intended for installation within a control cabinet e When mounting with screws O O O O Using the drive as a template or the dimensions shown above mark the locations for drilling Ensure that when mounting locations are drilled the dust from drilling does not enter the drive Mount the drive to the cabinet backplate using suitable M5 mounting screws Position the drive and tighten the mounting screws securely e When Din Rail Mounting Frame Size 2 Only O O O Locate the DIN rail mounting slot on the rear of the drive onto the top of the DIN rail first Press the bottom of the drive onto the DIN rail until the lower clip attaches to the DIN rail If necessary use a Suitable flat blade screw driver to pull the DIN rail clip down to allow the drive to mount securely on the rail To remove the drive from the DIN rail use a suiatble flat blade screwdrive to pull the release tab downwards and lift the botto
45. heir discretion and in all cases concerning warranty the local distributor should be contacted first The contents of this User Guide are believed to be correct at the time of printing In the interest of a commitment to a policy of continuous improvement the manufacturer reserves the right to change the specification of the product or its performance or the contents of the User Guide without notice This User Guide is for use with version 0 30 Firmware User Guide 1 01 Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date information the information contained in this User Guide should be used for guidance purposes only and does not form the part of any contract www invertek co uk Optidrive ODP 2 User Guide Revision 1 00 1 o A dasa N 6 ki ponant sae y INTO F MACONDO A a tenn cds 6 2 General Information and Ratings ccccccccscsccccccscsccccccccsceccccecscececcccscnceccececsceceececscecessecscsceseeees 7 Zi Drive model numbers IP20 tati a iria acia 7 22 DEV Model numbers IPSS in 7 3 Mechanical Installation 8 SL CG dd o dle 8 322 Berorelastalla conil 8 33 Ulecompliantinstala ON Sd dt 8 3 4 Mechanical dimensions and Mounting I1P20 UNITS ssn aa E T 8 3 5 Mechanical dimensions and mounting IP55 UNITS saros eer eE E AEE EET A ES TAE A 10 3 6 Guidelines for Enclosure mounting IP20 Units oocccccccnnccnnncnnnccnnnnnnancnn
46. idrive is reset to factory defaults or is in its factory supplied state only Group 1 Parameters can be accessed In order to allow access to parameters from the higher level groups P1 14 must be set to the same value as P2 40 Default setting 101 With this setting parameter groups 1 5 can be accessed along with the first 38 parameters in Group 0 6 2 Parameter Group 1 Basic Parameters Par Parameter Name gt gt gt gt gt gt gt gt gt gt gt gt gt gt gt gt Minimum Maximum Default Units P1 01 Maximum Frequency Speed Limit P1 02 500 0 50 0 60 0 Hz Rom Maximum output frequency or motor speed limit Hz or rpm If P1 10 gt 0 the value entered displayed is in Rom P1 02 Minimum Frequency Speed Limit PEA P1 01 is Hz Rpm Minimum speed limit Hz or rpm If P1 10 gt 0 the value entered displayed is in Rom P1 03 Acceleration Ramp Time Acceleration ramp time from O to base speed P 1 09 in seconds P1 04 Deceleration Ramp Time Deceleration ramp time from base speed P1 09 to standstill in seconds When set to zero fastest possible ramp time without trip is activated P1 05 Stop Mode AA A el A 0 Ramp To Stop When the enable signal is removed the drive will ramp to stop with the rate controlled by P1 04 as described above In this mode the drive brake transistor where fitted is disabled 1 Coast to Stop When the enable signal is
47. ing Factor 500 0 500 0 100 0 Used in conjunction with P2 28 a Analog Input 1 Terminal 6 Format S UO 10 U D ID 0 to 10 Volt Signal Uni polar U 10 0 10 to O Volt Signal Uni polar ID 10 10 to 10 Volt Signal Bi polar A 0 20 0 to 20mA Signal E 4 20 4to 20mA Signal the Optidrive will trip and show the fault code 4 2UF if the signal level falls below 3mA r 4 20 4 to 20mA Signal the Optidrive will ramp to stop if the signal level falls below 3mA E 20 4 20 to 4mA Signal the Optidrive will trip and show the fault code 4 2UF if the signal level falls below 3mA r 20 94 20 to 4mA Signal the Optidrive will ramp to stop if the signal level falls below 3mA P2 31 Analog Input 1 Scaling Sco 500 0 100 0 Scales the analog input by this factor e g if P2 30 is set for 0 10V and the scaling factor is set to 200 0 a 5 volt input will cat in the drive running at maximum speed P1 01 uo Analog Input 1 Offset 500 0 500 0 00 Sets an offset as a percentage of the full scale range of the input which is applied to the analog input signal www invertek co uk Optidrive ODP 2 User Guide Revision 1 00 Analog Input 2 Terminal 10 Format SCS Below uco U D 10 0 to 10 Volt Signal Uni polar U 10 0 10 to O Volt Signal Uni polar PEtc Eh Motor PTC Thermistor Input A D 20 0 to 20mA Signal E 4 20 4 to 20mA Signal the Optidrive will trip and show the fault code 4 2
48. ion of the correct Optidrive is based upon the motor full load current at the incoming supply voltage 200 240 Volt 10 1 Phase Input 3 Phase Output Nominal Fuse Nominal 150 Input Or Output Output Current MCB Current Current type B 60 secs e The maximum motor cable length stated applies to using a shielded motor cable When using an unshielded cable the maximum cable length limit may be increased by 50 When using the Invertek Drives recommended output choke the maximum cable length may be increased by 100 e The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor terminals depending on the motor cable length and inductance The rise time and peak voltage can affect the service life of the motor Invertek Drives recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life e For UL compliant installation use Copper wire with a minimum insulation temperature rating of 70 C UL Class CC or Class J Fuses www invertek co uk 37 200 240 Volt 10 3 Phase Input 3 Phase Output Nominal Input Current Optidrive ODP 2 User Guide Revision 1 01 Nominal Output Current 150 Output Current 60 secs Optional Brake Resistor Recommended l 6 45 100 100 N U1 ER o NI N N Oju m e N UN O NIOlS ER N N N ER ER ER N m N N U Ui Blwlwlrlole Na IN TR
49. it Supply or external 24 Volt Power Supply Run Enable AN A Drive Healthy Fwd Reverse Analog Preset Speed Programmable Relay Output I Drive Running Programmable Analog Inputs A Programmable Analog Output Output Speed Output Current External Safety Circuit for Safe Torque Off function 4 9 Control Terminal Connections Main Terminal Strip 6 All input4 Digital 8 to 30V DC Analog Input 1 10 to 10V O 4 to 20mA or 24VDC Digital A ovo conmo A A AA AA A A 8 AO1 Outputt t Analog Digital Output Oto 10V 4 to 20mA or 24VDC Digital o o ovotcommon S o OV return for the 24V Safe STO Additional Terminal Strip www invertek co uk 15 Optidrive ODP 2 User Guide Revision 1 01 5 Managing the Keypad The drive is configured and its operation monitored via the keypad and display 5 1 Keypad Layout and Function Standard LED Keypad Used to display real time information to NAVIGATE access and exit parameter edit mode and to store parameter changes Used to increase speed in real time mode or to UP increase parameter values in parameter edit mode Used to decrease speed in real time mode or DOWN to decrease parameter values in parameter edit mode Optidrive P Used to reset a tripped drive RESET l When in Keypad mode is used to Stop a STOP running drive When in keypad mode used to Start a stopped START drive or to reverse the direction of rotation if
50. ive P2 Easy Start Up Guide Display Keypad Operation can be found on page 16 Control Terminals Based on Factory settings I 1 aa Safe Torque Off STO Link the terminals as shown above through the emergency stop circuit contacts AC Supply Connection 200 240 Volts 10 380 380 Volts 10 L3 L2 L1 Run Stop 10K Pot Close the switch to run enable Open the switch to stop Fuses or MCB l Motor Cable Check drive D ME For correct cable size see Rating info on Technical Data on page 37 Page 37 j Observe the maximum permissible motor ma cable length For Motor cable lengths gt 50 metres an output filter is recommended Use a screened shielded cable The shield should be bonded to earth at both ends A Motor Connection Check for Star or Delta Connection Enter the Motor Nameplate Data into the drive Parameters as follows Motor Rated Voltage P1 07 Motor Rated Current P1 08 Motor Rated Frequency P1 09 Motor Rated Speed Optional P1 10 www invertek co uk Optidrive ODP 2 User Guide Revision 1 01 Declaration of Conformity Invertek Drives Ltd hereby states that the Optidrive ODP 2 product range conforms to the relevant safety provisions of the Low Voltage Directive 2006 95 EC and the EMC Directive 2004 108 EC and has been designed and manufactured in accordance with the following harmonised European standards EN 61800 5 1 2003 Adjustable speed electrical power
51. lace dust and swarf from drilling may lead to damage The entry of conductive or flammable foreign bodies should be prevented Flammable material should not be placed close to the drive Relative humidity must be less than 95 non condensing Ensure that the supply voltage frequency and no of phases 1 or 3 phase correspond to the rating of the Optidrive as delivered Never connect the mains power supply to the Output terminals U V W Do not install any type of automatic switchgear between the drive and the motor Wherever control cabling is close to power cabling maintain a minimum separation of 100 mm and arrange crossings at 90 degrees Ensure that all terminals are tightened to the appropriate torque setting Do not attempt to carry out any repair of the Optidrive In the case of suspected fault or malfunction contact your local Invertek Drives Sales Partner for further assistance www invertek co uk Optidrive ODP 2 User Guide Revision 1 00 2 General Information and Ratings 2 1 Drive model numbers IP20 200 240V 10 1 Phase Input HP M kW Model KW ode HP Output Frame With Filter With Filter Current A Size ODP 2 22075 1KF42 ODP 2 22010 1HF42 ODP 2 22150 1KF42 ODP 2 22020 1HF42 ODP 2 22220 1KF42 ODP 2 22030 1HF42 200 240V 10 3 Phase Input kW Model Number KW HP Model Number HP Output Frame With Filter With Filter Current A Size 2 2 380 480V 10
52. ldbus Address Sets the fieldbus address for the Optidrive Did CAN Open Baud Rate Sets the baud rate when CAN Open communications are used ad Modbus RTU Baud Rate Sets the baud rate when CAN Open communications are used P5 04 Modbus Data Format Sets the expected Modbus telegram data format as follows n 1 No Parity 1 stop bit n e No parity 2 stop bits D Odd parity 1 stop bit E Even parity 1 stop bit Communications Loss Timeout Sets the watchdog time period for the communications channel If a valid telegram is not received by the Optidrive within this time period the drive will assume a loss of communications has occurred and react as selected below Communications Loss Action Controls the behaviour of the drive following a loss of communications as determined by the above parameter setting 0 Trip amp Coast To Stop 1 Ramp to Stop Then Trip 2 Ramp to Stop Only No Trip 3 Run at Preset Speed 8 P5 07 Fieldbus Ramp Control Selects whether the acceleration and deceleration ramps are control directly via the Fieldbus or by internal drive parameters P1 03 and P1 04 O Disabled Ramps are control from internal drive parameters 1 Enabled Ramps are controlled directly by the Fieldbus P5 08 Fieldbus Process Data Word 4 Output Select 0 4 0 When using an optional fieldbus interface this parameter configures the parameter source for the 4 process data word transferred from the drive to the netwo
53. local Invertek Drives Sales Partner P P Lo55 14 Input Input phase loss trip o loss trip Drive intended for use with a 3 Drive intended for use with a 3 phase supply one input phase has been disconnected or lost supply one input phase has been disconnected or lost h O Instantaneous over current on canas mA to fault 3 above output www invertek co uk Optidrive ODP 2 User Guide Revision 1 01 Description Corrective Action Internal memory fault Parameters not saved defaults reloaded A a rerio ourIDLAuhvsed itor O 4 20mA Signal Lost The reference signal on Analog Input 1 or 2 Terminals 6 or 10 has dropped below the romero E imum tested of ma chee the signa source and wing othe Ope termina Internal memory fault Parameters not saved defaults reloaded agan problem fear reer to your OL Authorseditibwor Fault Code Eh FLE No dALA F 4 20F dREA E U dEF User Parameter Defaults User Parameter defaults have been loaded Press the Stop key F PEc Motor PTC Over Temperature The connected motor PTC device has caused the drive to trip FAn F Cooling Fan Fault Check and if necessary replace the drive internal cooling fan 23 Ambient Temperature too High The measured temperature around the drive is above the operating limit of the drive Ensure the drive internal cooling fan is operating Ensure that the required space around the drive as shown in sections O and 3 8 has been 0 hERE obse
54. m of the drive away from the rail first www invertek co uk Optidrive ODP 2 User Guide Revision 1 01 3 7 Mechanical dimensions IP55 Units pe a A SS ee a A Se E a A COI E A O O A a wo o 0 teas 03 16 8 035 ao ous an orm 00 aan as 0107 75 025 Ts 500 2126 515 2028 520 2047 8 0 315 270 1063 235 9252 175 689 425 0167 75 0295 6 ees 3408 830 3268 s40 3307 10 0 394 330 1299 330 1299 200 7878 55 0207 12 0433 Control Terminal Torque Settings All Sizes 0 8 Nm 7 Ib in Power Terminal Torque Settings Frame Size 4 1 2 1 5Nm Frame Size 5 2 5 4 5 Nm Frame Size 6 8 Nm Frame Size 7 8 Nm www invertek co uk 10 Optidrive ODP 2 User Guide Revision 1 00 3 8 Guidelines for mounting IP55 Units e Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 10 1 e The drive must be mounted vertically on a suitable flat surface e The minimum mounting clearances as shown in the table below must be observed e The mounting site and chosen mountings should be sufficient to support the weight of the drives X Y Above amp Either Below Side A a fo Typical drive heat losses are approximately 3 of operating load conditions Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times e Usi
55. ng the drive as a template or the dimensions shown above mark the locations required for drilling e The drive should be mounted using M8 Frame Sizes 4 amp 5 or M10 Frame Sizes 6 7 mounting bolts www invertek co uk 11 Optidrive ODP 2 User Guide Revision 1 01 3 9 Removing the Terminal Cover 3 9 1 Frame Size 4 3 9 2 Frame Size 5 Using a suitable flat blade Y i Using a suitable flat blade screwdriver rotate the two s screwdriver rotate the four retaining screws indicated until the retaining screws indicated until screw slot is vertical the screw slot is vertical Terminal Cover Release Screws 3 9 3 Frame Size 6 Remove the two screws indicated lift the cover forwards and off To refit the cover slide the top locating lugs upwards under the top cover then re fasten the lower cover screws www invertek co uk Optidrive ODP 2 User Guide Revision 1 00 4 Electrical Installation 4 1 Grounding the Drive This manual is intended as a guide for proper installation Invertek Drives Ltd cannot assume responsibility for the compliance or the non compliance to any code national local or otherwise for the proper installation of this drive or associated equipment A hazard of personal injury and or equipment damage exists if codes are ignored during installation This Optidrive contains high voltage capacitors that take time to discharge after removal of the main supply Before working on the drive
56. nnnnnccnnnononocnnnnonanocnnnnnnarnnnnonnnonnnnonanrnnnnnnonnnnnnnnss 9 3 7 GUIdElINES TOP MOUNTING IPS SU 11 38 REMOVING the Termina kGOVE israr a A A T EEO 12 4 Electrical Instala tonns R a 13 A Gouan o R 13 EZ WIE Precaution Sorun en Er T E EETA ENI ETS A EEEE E teas 13 43 INCOMINSPOWer CONMECUON eaaa a A A A AE 13 4 4 Operation of 3 Phase drives from a Single Phase SUDD porrno a a E E A T 14 AS DAvVednd Motol CORNER E tldia 14 46 Motor Lenminal BOX CONNECTIONS arere NON a ad adnate T aes 14 AT Co trol Terminal WV UNG A A AA A bean A E a 15 48 Control Terminals Connection Diaeta eenei a 15 49 Control Terminal Connecuons nd dd T 15 5 Managing the CY DAO nda rl one cucinsuaieusemueeqesueinec neti amesuabinnous sacha ea cdeleubeweeseensancuuenieuss 16 5 1 Keypad Layout and Function Standard LED Keypad ccccccsssccccssececceesceeeesceeseseccseuscesaasecssuecesseueeessaesessaseesaaeeesaes 16 S27 CHANGING PROMESA ta 16 5 3 Advanced Keypad Operation Short Cuts cccccccccssssccccssscccesecccsenecccsenscecaeeeceseeeeessuecesseneceseaeseessaeeessescessasesssgecessaaseess 17 gAs Drive Operatina DIS ia ne ee ee eee renee ere 17 5 5 Keypad Layout and Function Optional OLED Keypad IP55 Units Only ccccccccooocnccnnnoncnnnanncnnnnnnnnnnnonononononononnnnnos 18 She Mame O a o 5 oe ee eee 18 97 Accessing and Changing Parameter Valles valve O E T O 18 5 6 Changing the bansuage on the OLED
57. o 1 to enable the drive Set to O to stop the drive Bit 1 Fast stop request Set to 1 to enable drive to stop with 2 deceleration ramp Bit 2 Reset request Set to 1 in order to reset any active faults or trips on the drive This bit must be reset to zero once the fault has been cleared Bit 3 Coast stop request Set to 1 to issue a coast stop command Command Speed Reference Setpoint must be sent to the drive in Hz to one decimal place e g 500 50 0Hz Command Torque Reference Setpoint must be sent to the drive in to one decimal place e g 2000 200 0 Command Ramp times R W This register specifies the drive acceleration and deceleration ramp times used when Fieldbus Ramp Control is selected P5 08 1 irrespective of the setting of P1 12 The a o R W R W input data range is from O to 60000 0 00s to 600 005 This register contains 2 bytes The Lower Byte contains an 8 bit drive status word as follows Bit O O Drive Disabled Stopped 1 Drive Enabled Running Bit 1 O Drive Healthy 1 Drive Tripped The Upper Byte will contain the relevant fault number in the event of a drive trip Refer to section 11 1 for a list of fault codes and diagnostic information Output frequency of the drive to one decimal place e g 123 12 3 Hz Analog 2 Level Pre Ramp Speed Reference Measured DC Bus Voltage in Volts Measured Heatsink Temperature in C 9 2 3 Modbus Parameter Access All User Adjustable parameters Groups 1 t
58. o 5 are accessible by Modbus except those that would directly affect the Modbus communications e g e P5 01 Communication Protocol Select e P5 02 Drive Fieldbus Address P5 03 Modbus RTU Baud Rate e P5 04 Modbus RTU Data Format All parameter values can be read from the drive and written to depending on the operating mode of the drive some parameters cannot be changed whilst the drive is enabled for example When accessing a drive parameter via Modbus the Register number for the parameter is the same as the parameter number E g Parameter P1 01 Modbus Register 101 Modbus RTU supports sixteen bit integer values hence where a decimal point is used in the drive parameter the register value will be multiplied by a factor of ten E g Read Value of P1 01 500 therefore this is 50 0Hz For further details on communicating with Optidrive using Modbus RTU please refer to your local Invertek Sales Partner www invertek co uk 36 Optidrive ODP 2 User Guide Revision 1 00 10 Technical Data 10 1 Environmental Ambient temperature range Operational 10 50 C IP20 Units 40 C IP55 Units Storage 40 C 60 C Max altitude for rated operation 1000m Derating above 1000m to 4000m max 1 100m Relative Humidity lt 95 non condensing Note Drive must be Frost and moisture free at all times Installation above 2000m is not UL approved 10 2 Input voltage ranges Depending upon model and pow
59. o keypad mode by a digital input the drive will continue to operate at the last operating speed 7 Preset Speed 8 Terminal Enable Following a stop and restart the Optidrive will always initially run at Preset Speed 8 P2 08 Mains Loss Ride Through Stop Control A es Controls the behaviour of the drive in response to a loss of mains power supply whilst the drive is enabled 0 Mains Loss Ride Through The Optidrive will attempt to continue operating by recovering energy from the load motor Providing that the mains loss period is short and sufficient energy can be recovered before the drive control electronics power off the drive will automatically restart on return of mains power 1 Coast To Stop The Optidrive will immediately disable the output to the motor allowing the load to coast or free wheel When using this setting with high inertia loads the Spin Start function P2 26 may need to be enabled 2 Fast Ramp To Stop The drive will ramp to stop at the rate programmed in the 2 d deceleration time P2 25 Parameter Access Lock aes O A ra 0 Unlocked All parameters can be accessed and changed 1 Locked Parameter values can be displayed but cannot be changed P2 40 Extended Parameter Access Code Definition oe 9999 a Defines the access code which must be entered in P1 14 to access parameter groups above Group 1 www invertek co uk 29 Optidrive ODP 2 User Guide Revision 1 01 8 2 Parameter Group 3 PI
60. p display showing trip condition Maximum speed limit 10 0 P1 O1 1250 0 10 0 Hold navigate button in for gt 1 Use up and down keys to scrollto Presss release navigate button Use up and down keys to edit sec required parameter when required parameter shown parameter value www invertek co uk 18 Optidrive ODP 2 User Guide Revision 1 00 5 8 Changing the Language on the OLED Display Select Language ltaliano gt Espa ol Deutsch Hold down the Start Navigate and Use the Up and Down arrows to Up keys for gt 1s select a language Press the Navigate button to select 5 9 Resetting Parameters to Factory Default Settings LED Display Press and hold the Keys for at least 2 seconds The display will show P dEF Press the UY key OLED Display Load default parameters Hold down the Up Down Start and Stop keys for gt 2s Press STOP key to reset The display shows P Def Drive is returned to User Standard settings Press the Stop key www invertek co uk 19 Optidrive ODP 2 User Guide Revision 1 01 5 10 Terminal Control When delivered the Optidrive is in the factory default state meaning that it is set to operate in terminal control mode and all parameters have the default values as indicated in section 6 20 Connect the drive to the supply ensuring the correct voltage and fusing circuit breaker protection see section 10 4 Connect the motor to the drive ensuring the correct star del
61. ptidrive should be mounted in a vertical position only on a flat flame resistant vibration free mounting using the integral mounting holes or DIN Rail clip Frame Size 2 only e The Optidrive must be installed in a pollution degree 1 or 2 environment only e Donot mount flammable material close to the Optidrive e Ensure that the minimum cooling air gaps as detailed in section O and 3 8 are left clear e Ensure that the ambient temperature range does not exceed the permissible limits for the Optidrive given in section 10 1 e Provide suitable clean moisture and contaminant free cooling air sufficient to fulfil the cooling requirements of the Optidrive 3 2 Before Installation e Carefully Unpack the Optidrive and check for any signs of damage Notify the shipper immediately if any exist e Check the drive rating label to ensure it is of the correct type and power requirements for the application e Store the Optidrive in its box until required Storage should be clean and dry and within the temperature range 40 C to 60 C 3 3 UL Compliant Installation Note the following for UL compliant installation e The drive can be operated within an ambient temperature range as stated in section 10 1 e For IP20 units installation is required in a pollution degree 1 environment e For IP55 units installation in a pollution degree 2 environmant is permissible e UL Listed ring terminals lugs must be used for all bus bar and grounding connections 3
62. r UL compliant det 37 VO 4 gt Output POWEr ANG CUENCA UNES sio dad 37 11 TroubleshOO TINE a 39 VI aE mess aE a aanseuineeg E E ee anss 39 www invertek co uk Optidrive ODP 2 User Guide Revision 1 01 1 Introduction 1 1 Important safety information Please read the IMPORTANT SAFETY INFORMATION below and all Warning and Caution information elsewhere Danger Indicates a risk of electric shock which if not Danger Indicates a potentially hazardous situation AN avoided could result in damage to the equipment and other than electrical which if not avoided could result possible injury or death in damage to property This variable speed drive product Optidrive is intended for professional incorporation into complete equipment or systems as part of a fixed installation If installed incorrectly it may present a safety hazard The Optidrive uses high voltages and currents carries a high level of stored electrical energy and is used to control mechanical plant that may cause injury Close attention is required to system design and electrical installation to avoid hazards in either normal operation or in the event of equipment malfunction Only qualified electricians are allowed to install and maintain this product System design installation commissioning and maintenance must be carried out only by personnel who have the necessary training and experience They must carefully read this safety information and the instructions in this Guide
63. rk master during cyclic communications 0 Output Torque 0 to 2000 O to 200 0 1 Output Power Output power in kW to two decimal places e g 400 4 00kW 2 Digital Input Status Bit O indicates digital input 1 status bit 1 indicates digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heatsink Temperature 0 to 100 0 to 100 C Reserved Parameter No Function www invertek co uk 32 Optidrive ODP 2 User Guide Revision 1 00 8 5 Parameter Group 0 Monitoring Parameters Read Only PO 01 Analog Input 1 Applied Signal Level Displays the signal level applied to analog input 1 Terminal 6 after scaling and offsets have been applied Analog Input 2 Applied Signal Level Displays the signal level applied to analog input 2 Terminal 10 after scaling and offsets have been applied Digital Input Status E Displays the status of the drive inputs starting with the left hand side digit Digital Input 1 etc PO 04 Pre Ramp Speed Controller Reference Displays the set point reference input applied to the drive internal speed controller Torque Controller Reference Displays the set point reference input applied to the drive internal torque controller PO 06 Digital Speed Reference Motorised Pot Displays the value of the drive internal Motorised Pot used for keypad speed reference PO 07 Fieldbus Communication
64. rrectly connected and free from faults Check that the power rating corresponds to the power rating of the connected drive Modbus comms fault A valid Modbus telegram has not been received within the watchdog time limit set in P5 06 Check the network master PLC is still operating Check the connection cables Increase the value of P5 06 to a suitable level CAN Open comms trip A valid CAN open telegram has not been received within the watchdog time limit set in P5 06 Check the network master PLC is still operating Check the connection cables Increase the value of P5 06 to a suitable level Fault Check the module is correctly inserted Check the module is correctly inserted 82 P2MAN IN www invertek co uk 40
65. rved and that the cooling airflow path to and from the drive is not restricted Increase the cooling airflow to the drive Reduce the effective switching frequency setting in parameter P2 24 Reduce the load on the motor drive 24 Maximum Torque Limit Exceeded The output torque limit has exceeded the drive capacity or trip threshold Reduce the motor load or increase the acceleration time 25 Output Torque Too Low Active only when hoist brake control is enabled P2 18 8 The torque developed prior to releasing the motor holding brake is below the preset threshold Contact your local Invertek Sales Partner for further information on using the Optidrive P2 in hoist applications oF E CN Only visible when an encoder Encoder Speed Error The error between the measured encoder feedback speed and the connected and free from faults Check the windings for correct resistance and balance Measured motor stator resistance is too large Ensure the motor is correctly connected and free from faults Check that the power rating corresponds to the power rating of the connected drive Measured motor inductance is too low Ensure the motor is correctly connected and free Autotune Failed from faults Measured motor inductance is too large Ensure the motor is correctly connected and free from faults Check that the power rating corresponds to the power rating of the connected drive Measured motor parameters are not convergent Ensure the motor is co
66. s are active by reducing P3 11 07 Under voltage on DC bus This occurs routinely when power is switched off If it occurs during running check the incoming supply voltage and all connections into the drive fuses contactors etc Heatsink over temperature The heatsink temperature can be displayed in PO 21 A historical log is stored at 30 second intervals prior to a trip in parameter PO 38 Check the drive ambient temperature Ensure the drive internal cooling fan is operating Ensure that the required space around the drive as shown in sections O and 3 8 has been observed and that the cooling airflow path to and from the drive is not restricted Reduce the effective switching frequency setting in parameter P2 24 Reduce the load on the motor drive EA over 10 C in order to start the drive di been loaded E Er iP E trip requested on control input terminals Some settings of P1 13 require a normally closed contactor to provide an external means of tripping the drive in the event that an external device develops a fault M a motor thermistor is connected check if the motor E too hot cs D re external devices Excessive DC Ripple The DC Bus Ripple Voltage level can be displayed in parameter PO 22 A historical log is stored at 20ms intervals prior to a trip in parameter PO 39 Check all three supply phases are present and within the 3 supply voltage level imbalance tolerance Reduce the motor load If the fault persists contact your
67. ta connection for the voltage rating see section 4 6 Apply the mains power to the drive then enter the motor data from motor nameplate P1 07 motor rated voltage P1 08 motor rated current P1 09 motor rated frequency Connect the Drive Hardware Inhibit STO circuit as follows see section 4 7 for further details o Link Terminal 1 to Terminals 12 STO o Link Terminal 9 to Terminal 13 STO Connect a control switch between the control terminals 1 and 2 ensuring that the contact is open drive disabled Connect a potentiometer 1kQ min to 10 kQ max between terminals 5 and 7 and the wiper to terminal 6 With the potentiometer set to zero switch on the supply to the drive The display will show SEoP Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz H 0 0 with the potentiometer turned to minimum Turn the potentiometer to maximum The motor will accelerate to 50Hz 60Hz for HP drives the default value of P1 01 under the control of the acceleration ramp time P1 03 If the potentiometer is turned to minimum the motor will decelerate to OHz the default minimum speed set in P1 02 under the control of the deceleration ramp P1 04 The output speed can be adjusted anywhere between minimum and maximum speed using the potentiometer To display motor current Amps briefly press the Navigate key Press again
68. tion O by subtracting 1 to obtain the correct Register address The telegram structure is as follows Master Telegram Length Slave Response Slave Address Function Code 03 1 Register Address No Of Registers CRC Checksum fd E Command 06 Write Single Holding Register Master Telegram Length Slave Response Length www invertek co uk 35 Optidrive ODP 2 User Guide Revision 1 01 9 2 2 Modbus Control amp Monitoring Registers The following is a list of accessible Modbus Registers available in the Optidrive P2 e When Modbus RTU is configured as the Fieldbus option P5 01 0 factory default setting all of the listed registers can be accessed e Registers 1 and 2 can be used to control the drive providing that Modbus RTU is selected as the primary command source P1 12 4 e Register 3 can be used to control the output torque level providing that o The drive is operating in Vector Speed or Vector Torque motor control modes P4 01 1 or 2 o The torque controller reference limit is set for Fieldbus P4 06 3 Register 4 can be used to control the acceleration and deceleration rate of the drive providing that Fieldbus Ramp Control is enabled P5 08 1 e Registers 6 to 24 can be read regardless of the setting of P1 12 Number Write Command Control Word R W Command control word used to control the Optidrive when operating with Modbus RTU The Control Word bit functions are as follows Bit O Run Stop command Set t
69. tion select Selects the function assigned to Relay Output 2 The relay has two output terminals Logic 1 indicates the relay is active and therefore terminals 17 and 18 will be linked together Drive Enabled Running Logic 1 when the motor is enabled Drive Healthy Logic 1 when power is applied to the drive and no fault exists At Target Frequency Speed Logic 1 when the output frequency matches the setpoint frequency Output Frequency gt 0 0 Hz Logic 1 when the drive output frequency to the motor is exceeds 0 0Hz Output Frequency gt Limit Logic 1 when the motor speed exceeds the adjustable limit Output Current gt Limit Logic 1 when the motor current exceeds the adjustable limit Output Torque gt Limit Logic 1 when the motor torque exceeds the adjustable limit Analog Input 2 Signal Level gt Limit 1 Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit Hoist Brake Control The relay can be used to control the motor holding brake on a hoist Contact your local Invertek Sales Partner for further information on using this feature Note When using settings 4 7 parameters P2 19 and P2 20 must be used together to control the behaviour The output will switch to Logic 1 when the selected signal exceeds the value programmed in P2 19 and return to Logic O when the signal falls below the value programmed in P2 20 P2 19 Adjustable Threshold 1 Upper Limit Analog Output 2 Relay Output 2 P2
70. tion to the motor body through the largest possible surface area e Where drives are mounted in a steel control panel enclosure the cable screen may be terminated directly to the control panel using a suitable EMC clamp or gland as close to the drive as possible e For IP55 drives connect the motor cable screen to the internal ground clamp 4 6 Motor Terminal Box Connections Most general purpose motors are wound for operation on dual voltage supplies This is indicated on the nameplate of the motor This operational voltage is normally selected when installing the motor by selecting either STAR or DELTA connection STAR always gives the higher of the two voltage ratings Incoming Supply Voltage Motor Nameplate Voltages Connection 230 230 400 Delta 400 400 690 400 230 400 www invertek co uk 14 Optidrive ODP 2 User Guide Revision 1 00 4 7 Control Terminal Wiring e All analog signal cables should be suitably shielded Twisted pair cables are recommended e Power and Control Signal cables should be routed separately where possible and must not be routed parallel to each other e Signal levels of different voltages e g 24 Volt DC and 110 Volt AC should not be routed in the same cable e Maximum control terminal tightening torque is 0 5Nm 4 8 Control Terminals Connection Diagram Control Terminal Designations and Default Function Assignments ETE Programmable Relay Output 24 Volt Control Circu
71. to Pros 00 Hz Rpm P2 08 Preset Jog Frequency Speed 8 P1 02 P1 01 00 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P1 13 If P1 10 0 the values are entered as Hz If P1 10 gt O the values are entered as Rpm Setting a negative value will reverse the direction of motor rotation P2 09 Skip Frequency Centre Point CST Pa Po 00 Hz Rpm P2 10 Skip Frequency Band Width 00 P101 00 Hz Rpm The Skip Frequency function is used to avoid the Optidrive operating at a certain output frequency for example at a frequency which causes mechanical resonance in a particular machine Parameter P2 09 defines the centre point of the skip frequency band and is used conjunction with P2 10 The Optidrive output frequency will ramp through the defined band at the rates set in P1 03 and P1 04 respectively and will not hold any output frequency within the defined band If the frequency reference applied to the drive is within the band the Optidrive output frequency will remain at the upper or lower limit of the band P2 11 Analog Output 1 Terminal 8 Function Select A A AA Digital Output Mode Logic 1 24V DC Drive Enabled Running Logic 1 when the Optidrive is enabled Running Drive Healthy Logic 1 When no Fault condition exists on the drive At Target Frequency Speed Logic 1 when the output frequency matches the setpoint frequency Output Frequen
72. uipment complies with EN60204 1 The level of integrity offered by the Optidrive control input functions excluding the Safe Torque Free Input for example stop start forward reverse and maximum speed is not sufficient for use in safety critical applications without independent channels of protection All applications where malfunction could cause injury or loss of life must be subject to a risk assessment and further protection provided where needed The STOP function does not remove potentially lethal high voltages ISOLATE the drive and wait 10 minutes before starting any work on it Never carry out any work on the Drive Motor or Motor cable whilst the input power is still applied The Optidrive can be programmed to operate the driven motor at speeds above or below the speed achieved when connecting the motor directly to the mains supply Obtain confirmation from the manufacturers of the motor and the driven machine about suitability for operation over the intended speed range prior to machine start up Do not activate the automatic fault reset function on any systems whereby this may cause a potentially dangerous situation The Optidrive ODP 2 has an Ingress Protection rating of IP20 or IP55 depending on the model IP20 units must be installed in a suitable enclosure Optidrives are intended for indoor use only When mounting the drive ensure that sufficient cooling is provided Do not carry out drilling operations with the drive in p
73. uk 33 Optidrive ODP 2 User Guide Revision 1 01 Energy Consumption kWh Meter kWh Displays the amount of energy consumed by the drive in kWh When the value reaches 1000 it is reset back to 0 0 and the value of PO 27 MWh meter is increased Energy Consumption MWh Meter MWh Displays the amount of energy consumed by the drive in MWh Software Version and Checksum Eo 3 Displays the software version of the drive Drive Type PEA Displays the type details of the drive Drive Serial Number oa Displays the unique serial number of the drive PO 27 PO 28 PO 31 Drive Lifetime Operating Time HH MM SS Displays the total operating time of the drive The first value shown is the number of hours Pressing the Up key will display the minutes and seconds Drive Run Time Since Last Trip 1 Displays the total operating time of the drive since the last fault occurred The first value shown is the number of hours Pressing the Up key will display the minutes and seconds Drive Run time Since Last Trip 2 Displays the total operating time of the drive since the last fault occurred The first value shown is the number of hours Pressing the Up key will display the minutes and seconds Drive Run Time Since Last Disable Displays the total operating time of the drive since the last Run command was received The first value shown is the number of hours Pressing the Up key will display the minutes and secon
74. xpense of increased drive losses 2nd Deceleration Ramp Time 0 00 300 000 Seconds This parameter allows an alternative deceleration ramp down time to be programmed into the Optidrive which can be selected by digital inputs dependent on the setting of P1 13 or selected automatically in the case of a mains power loss if P2 38 2 When set to 0 0 the drive will coast to stop Spin Start Enable f EN A E O Disabled 1 Enabled When enabled on start up the drive will attempt to determine if the motor is already rotating and will begin to control the motor from its current speed A short delay may be observed when starting motors which are not turning P2 27 Standby Mode Timer oo 2500 00 Seconds This parameter defines time period whereby if the drive operates at minimum speed for at least the set time period the Optidrive output will be disabled and the display will show 5EndbY The function is disabled if P2 27 0 0 Slave Speed Scaling Control pp o yo TC Active in Keypad mode P1 12 1 or 2 and Slave mode P1 12 5 only The keypad reference can be multiplied by a preset scaling factor or adjusted using an analog trim or offset O Disabled No scaling or offset is applied 1 Actual Speed Digital Speed x P2 29 2 Actual Speed Digital Speed x P2 29 Analog Input 1 Reference 3 Actual Speed Digital Speed x P2 29 x Analog Input 1 Reference Slave Speed Scal
Download Pdf Manuals
Related Search
Related Contents
Husqvarna FS 524 Chainsaw User Manual Guía de operación 3136 アースバーセット 〔RD89〕 取扱説明書 Thin-R TR/BGM BBA Cert PDF Manual de usuario de Key Rig - M Circular Externa CE - Superintendencia de Sociedades Targus Click-In WorkZone Explorer - User's Guide 医療機器産業ビジョ ンに関する懇談会 (第2回) での意見 Copyright © All rights reserved.