Home

Installation and operating instructions

image

Contents

1. 22 COMMISSIONING lt a e a enje 23 Setting the eBUS address 24 26 Switching times L l aaa ave uqusqa 27 Parameter list eeej na loo ee ona ponad o ni 28 30 Parameter description 31 36 01 Minimum mixer circuit temperature 31 02 Maximum mixer circuit temperature 31 03 Heating curve gap 31 04 Screed dying e 2c eee NA a 31 05 Configuratio irei pesei SE data aa odd de 32 06 Pump run on time heating circuit 32 07 Proportional range mixer circuit 32 08 Set return temperature 33 09 Maximum cylinder heating time 34 10 BUS feed uden klina gani kare olova 34 11 Hysteresis bypass sensor 35 12 Primary pump blocking 35 13 Primary pump run on time 35 14 Constanttemperature 35 3061892 0111 W IF Safety instructions 3061892_0111 Index Safety instructions 15 ATOff shutdown differential 35 16 ATOn start up differential 36 17 Boiler excess temperature during DHW cylinder heating 3
2. MI 04 2 screed drying temperature For the first two days the set flow temperature will remain constant at 25 C It will then be automatically raised every day at 0 00 h by 5 C up to the maximum mixer circuit temperature MI 02 That temperature will then be held for two days Subseguently the flow temperature is automatically reduced again in 5 C steps per day to 25 C The program seguence is terminated after a further two days 55 50 40 35 30 25 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Screed drying runtime days Attention Agree the time seguence and the maximum flow temperature with the screed contractor otherwise the screed may be dam aged particularly through cracking The screed drying program continues after a power failure The remaining time in days is displayed at the BM 31 WOJIF MI 05 Configuration MI 06 Pump run on time heating circuit MI 07 Proportional range mixer circuit Parameter description The corresponding configuration may subject to the applica tion of the MM have to be selected Up to 11 configurations can be selected For matching wiring diagrams see Electrical connection Configuration 01 Configuration 02 Configuration 03 Configuration 04 Configuration 05 Configuration 06 Configuration 07 Configuration 08 Configuration 09 Configuration 10 Configuration 11 Mixer circuit and cylinde
3. Return control If the actual return temperature falls below the set return tem perature then the mixer bypass is opened further by switching the mixer enabling a greater amount of heating water to flow through the mixer bypass If the actual return temperature rises above the set return temperature then the mixer bypass is closed further by switch ing the mixer restricting the amount of heating water to flow through the mixer bypass Indirect return temperature raising with configuration MOS 7 Configuration 7 includes an indirect return temperature raising to regulate the mixer circuit The indirect return temperature raising is always active when at least one heating or cylinder circuit is active When the actual return temperature drops with indirect return temperature raising the actual return temperature is forced higher for all heating and cylinder circuits through enforcing a higher output This forced higher output has two stages At stage 1 all system mixers are switched to move towards Close and in addition in stage 2 all heating and primary pumps at stage 1 are switched off Falling return temperature RL act lt RL set hysteresis return temperature mixer towards CLOSE RL act lt RL set gt mixer towards CLOSE and all heating circuit pumps OFF Rising return temperature RL act gt RL set t 2 K mixer towards CLOSE RL act lt RL set hysteresis return temperature 4 K no forced actuat
4. Summer mode Central heating off DHW according to the DHW time program Heating mode Setback mode In winter mode two room temperatures can be selected Standard room temperature and setback temperature In the later case the temperature will be reduced to the setback temperature The heating program changes over between heating and setback mode WOJIF Abbreviations Equipment description Mixer circuit pump Mixer motor OPEN Mixer motor CLOSE Output A1 eBUS Fault Abbreviations Equipment description BPF Bypass sensor MKP Mixer circuit pump MKF Mixer circuit sensor MM Mixer motor or PF Buffer sensor Mixer module PK Floating contact as SPLP Cyl primary pump N O LP Primary pump RLF Return sensor BPP Bypass pump SPF Cylinder sensor 3WUV Three way diverter VF Flow sensor valve The mixer module MM contains a mixer circuit controller and the control for a programmable output The mixer circuit controller can be used for the heating flow as well as for the heating return The programmable output either regulates a direct heating circuit a cylinder circuit an air heater ext heat demand an electrical valve for raising the return temperature central heating backup or the bypass pump in conjunction with the return temperature raising Subject to application select the relevant combination of the mixer circuit controller and the programmable output as configuration Parameters can be
5. lt 8 VA Max power consumption mixer motor 30 VA Max power consumption per pump outlet 250 VA Protection according to DIN 40050 IP 30 Protection class according to VDE 0100 lI Permissible ambient temperature in operation 0 to 50 C Permissible ambient temperature during storage 30 to 60 C Data Memory est egoi us sayu tav aag tees EEPROM non volatile a 3061892_0111
6. Heating flow RLF Heating return ZUP MM 1 Connect the feed pump ZUP to the boiler control unit at slot KKP 16 3061892 0111 WOLF Electrical connection Configuration 6 Heating circuit and return temperature raising for soft starting with bypass pump OO 00 0 0 ODLOK Return sensor 9 Bypass WU sensor BPF eBus Boiler AN Gas fired Mixer motor boiler MM Heating circuit Heating flow Heating return 9 Connect the heating circuit pump HKP to the boiler control unit 3061892 0111 17 WOLF Electrical connection Configuration 7 Mixer circuit with indirect return temperature raising for soft starting with bypass pump noe ped NOL mE at ez 230 V 50Hz Mains MKP 2 ji ME DOOD Od ua E E au o nu OO QO OO O mig miz m 9 9 Bypass Flow sen sensor BPF sor mixer Bypass pump circuit BPP 230 VAC ieee WEB Return sen l sor RLF eBus Boiler Le N Gas fired Maximum Mixer motor boiler thermostat MM max TH an 1 LI i Mixer circuit pump MKP Mixer circuit Heating flow Heating return 18 3061892_0111 WOU Electrical connection Configuration 8 Mixer circuit factory setting Li NO N O L1 NOLI 1 2 Poena a MKP M E2 10A Flow L1
7. N PE sensor Power mixer 230 VAC circuit VF ft I L ma i N I 2805 Boiler Maximum EN I Gas fired thermostat boiler max TH L l l l l J Mixer circuit pump MKP Nr Mixer circuit Heating flow Heating return 3061892 0111 19 WOLF Electrical connection Configuration 9 Heating circuit LAINIO De Mee 1 2 E2 230 V 50Hz Mains A1 OW D DIO DOOD 10 A i uN LET s Heating circuit Power pump HKP 230 VAC Boiler Gas fired boiler Heating circuit HKP 7 Heating flow Heating return 1 Whether pump or electrical valve see description Output A1 page 8 20 3061892_0111 WOLF Electrical connection Configuration 10 Cylinder circuit LIND 230 V 50Hz Mains I M ib M o o o Oo OD N D e1 MKP Cylinder sensor L1 N PE NES m SPF Cylinder primary Power pump SPLP 230 VAC Boiler Gas fired boiler DHW cylinder SPF SPLP Heating flow Heating return 1 Whether pump or electrical valve see description Output A1 page 8 3061892 0111 21 WOLF Electrical connection Configuration 11 Air heater circuit external heat demand LIND N e ui N OLI 1 2 230 Naas MKP A1 E2 mene NM ODO 0 DODD OLX Eg I l 10Af i j L1 N PE Primary L Emme Power pump LP Zero volt 230
8. This can result in the floor developing cracks There are four options for integrating an outside temperature sensor into a system a Outside temperature sensor at the boiler at terminal AF Part no 2792021 b Outside temperature sensor at BM address 0 in the wall mounted base at terminal 5 6 Part no 2792021 c Radio clock module with outside temperature sensor connected to the eBUS Part no 2792325 d Wireless outside temperature sensor and wireless receiver connected to the eBUS Part no 2744081 and 2744209 H005VV 3 x 1 0 mm Power supply cable H005WV 3 x 0 75 mm Mixer circuit pump max thermostat H005WV 4 x 0 75 mm Mixer motor H005WV 3 x 0 75 mm Max thermostat electr valve H005WV 2 x 0 5 mm BUS cable During service work isolate the entire system from the power supply otherwise there will be a risk of electrocution 3061892 0111 W IF Electrical connection Configuration overview Subject to the application of the MM there are 11 different connection methods Select the differ ent versions with the configuration parameter MI05 This is found at the second control level Contractor Mixer Configuration 01 Mixer circuit and cylinder circuit page 12 Configuration 02 Mixer circuit and air heater circuit external heat demand page 13 Configuration 03 Mixer circuit and heating circuit page 14 Configuration 04 Mixer circuit and return temperature raising for heating backup page 15 Configurat
9. VAC contact PK N O Boiler Gas fired boiler Air heater circuit a m LP Heating flow Heating return 1 Whether pump or electrical valve see description Output A1 page 8 2 Heat demand for air heater circuit external heat demand 22 3061892_0111 W IF Commissioning Commissioning guidelines Implement the following steps in the order in which they are listed to achieve successful com missioning with regards to addressing and programming all control components and the system configuration Note Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Note 3061892 0111 HG KM MM and SOL parameters are found at control level 2 Contractor Boiler HG Cascade KM Mixer MM Solar SOL in the programming module BM If a cascade module is installed in the system use the commissioning guidelines from the installation and operating instructions of the cascade module Implement the Installation and Electrical connection of all extension and programming modules in accordance with the instructions in the associated manual For further details regarding the setting of the eBUS address DIP switches of the extension and programming modules MM and BM see Setting the eBUS address extension modules Start the system via the system On Off switch mains On Configuration of the extension modules just like mixer module and solar module The configuration of the MM mixer
10. electrical valve see description Output A1 page 8 2 Heat demand for air heater circuit external heat demand 3061892_0111 13 WOLF Electrical connection Configuration 3 Mixer circuit and heating circuit Flow sen nea Heating sor mixer Z circuit pump circuit VF 230 VAC Boiler SE Gas fired Maximum Mixer motor boiler thermostat MM max TH Mixer circuit pump MKP Mixer circuit Heating circuit Heating flow Heating return 1 Whether pump or electrical valve see description Output A1 page 8 14 3061892_0111 WOLF Electrical connection Configuration 4 Mixer circuit and return temperature raising for heating backup N Du A1 10A L1 N PE Power pp LUER I 230 VAC Heating return Return sen I I u LL I I I me esus I Boiler ZLA Gas fired Mixer motor boiler MM Maximum thermostat max TH Mixer circuit pump MKP Mixer circuit Heating flow 3061892 0111 15 WOLF Electrical connection Configuration 5 Return temperature raising for soft starting DODOKJO ODO 10A i I Return L1 N PE sensor RLF Power 230 VAC I I I I Boiler Gas fired Mixer motor boiler MM Supplement heating and DHW circuits with additional mixer modules
11. is transmitted via the BUS and is displayed Fault Fault Cause Remedy code FC52 Max cylinder heating time Max cylinder heating See parameter descrip time exceeded tion 17 09 FC70 Mixer circuit sensor or return Faulty sensor or lead Check sensor and lead sensor fault terminal VF replace if required FC71 Cylinder sensor or buffer Faulty sensor or lead Check sensor and lead sensor bypass sensor fault replace if required terminal E1 FC79 Return sensor or bypass sen Faulty sensor or lead Check sensor and lead sor faulty terminal E2 replace if required FC97 Bypass pump faulty Bypass pump short Check bypass pump circuit check cable and connec Faulty bypass pump tion replace if required cable FC81 EEPROM fault Parameter values out Return to standard values side the valid range by briefly turning OFF and check values FC91 BUS address Two or several acces Check address settings sory controllers have the same BUS address 38 3061892_0111 W IF Changing a fuse Changing a fuse 3061892_0111 Note A Changing a fuse If the MM indicates no function at all and there is no LED display although power is on check the appliance fuse and change it if required If the MM is operated as part of the Wolf control system the display of one of the existing BM programming modules is re tained as this is supplied via the eBUS link to the other control components Prior
12. 2 818 107 277 3 14027 38 2887 73 791 108 270 4 13344 39 2772 74 765 109 262 5 12697 40 2662 75 740 110 255 6 12086 41 2558 76 716 111 248 7 11508 42 2458 77 693 112 241 8 10961 43 2362 78 670 113 235 9 10442 44 2271 79 649 114 228 10 9952 45 2183 80 628 115 222 11 9487 46 2100 81 608 116 216 12 9046 47 2020 82 589 117 211 13 8629 48 1944 83 570 118 205 40 3061892_0111 System example injection control WLJIF LN u lt TigHHHHHH_ SV A0EZ 41 3061892_0111 WOLF System example injection control UP Circulation pump 230 V AC min 0 75 mm Butterfly valve Shut off valve M Mixer 230 V AC min 0 75 mm Gravity brake opening pressure gt 25 mbar Cap valve TW Temperature controller for underfloor heating system 230 V AC VF Flow sensor AF Outside temperature sensor a Erza gt a EV Electrical valve N C 230 V AC min 0 75 mm2 Direct connection of a mixer circuit via injection control 1 Applications The injection control is used if a mixer circuit with pump is to be directly connected i e without low loss header to a gas fired boiler with integral pump The injection control offers many benefits compared to a conventional dual shunt pump control 2 Description The injection control includes an open bypass between flow and return in the mixer circuit that separates the mixer circuit pump from the boiler circuit The mixer equipped wi
13. 6 18 Burner blocked when the return temperature is raised 36 50 Test functioN lt adds saa radii radikala 36 Auxiliary functions e S a i a Cylinder frost protection Anti seizing pump protection a a 37 Anti seizing mixer protection 37 EMISSIONS test k AA pi a as 37 Loading the standard values 37 Faultcodes sadake iaai tkogod waaka saa rji 38 Changing a fus u u u Q ea dla gda pasata nana 39 Sensor resistances u eee dene avion 40 System example injection control 41 43 Specification 2asstrtmaeemes ease 44 A A The following symbols are used in conjunction with these important instructions concerning personal safety as well as operational reliability Safety instructions are instructions with which you must comply exactly to prevent injury and material losses Danger through live electrical components NB Switch OFF the ON OFF switch before removing the cas ing Never touch electrical components or contacts when the ON OFF switch is in the ON position This brings a risk of electrocution which may result in injury or death The main supply terminals are live even when the ON OFF switch is in the OFF position This indicates technical instructions whic
14. Parameters Setting Factory setting Individual range setting og Room influence 1 20 4 209 Frost protection limit 20 10 815 Parallel pump mode 0 1 an Pump stop with room controller off on on m2 Setback stop 40 0 16 214 Maximum DHW temperature 60 80 60 28 Check the description of the parameters room influence frost protection limit pump stop with room controller setback stop and maximum DHW temperature in the BM installation and operating instructions A10 Parallel pump operation Parameter A10 0 Priority mode Priority mode for cylinder heating at the mixer module or primary pump for external heat demand ahead of a heat demand for the mixer output Parameter A10 1 Parallel operation Parallel mode for cylinder heating at the mixer module or external heat demand with a heat demand for the mixer output Note In parallel mode the highest possible flow temperature is applied 3061892 0111 WOLF Parameter list Parameter list This is found at control level 2 Contractor Boiler contractor boiler To safeguard the required flow temperatures for cylinder and central heating at the mixer module set parameters HG08 maximum limit boiler circuit TV max and HG22 maxi mum boiler water temperature TK max to the highest required temperature level Note Parameters HG08 and HG22 do not need to be changed for those heating and cylinder circuits for which the corresponding param
15. R1 R2 R21 COB In conjunction with the Wolf control unit R3 the Settings eBUS addresses of the MM are allocated from 2 to 7 Address 0 HII The functions of each mixer module are determined via the con figuration settings see also electrical connection Address 1 factory setting A s Pake Each system can comprise up to seven mixer circuits and one Address 2 HU direct heating circuit Address3 OO 1 This direct heating circuit can either be connected to the boiler Address4 ga control unit R1 R2 R3 R21 COB or the mixer module config 3 address leni or 9 On systems with KM cascade module the direct heating circuit must be connected to the KM or MM Address6 da In addition each mixer module mixer circuit may be supplemented ES frr with a BM programming module to complete the control The heating circuit is always controlled by the programming module with address 0 a Max expansion with Wolf boiler control unit for wall mounted appliances MGK control unit or Wolf boiler control units R1 R2 R21 COB Wolf boiler I i s MM3 H I e e OF u e o mii MM 4 e m I option HH MM 5 1 om 1 Z I TITA MM 6 I I I I I I I In conjunction with a control unit for Wolf wall mounted boilers or MGK control unit always connect the direct heating circuit to the MM
16. WOIF Installation and operating instructions Mixer module MM Wolf GmbH Postfach 1380 D 84048 Mainburg Tel 49 8751 74 0 Fax 49 8751 741600 Intemet www wolf heiztechnik de 3061892_0111Subject to modifications W IF Index Safety instructions iii si Si SARA ANE NE Gat 3 Standards Regulations kakaa 4 TerminologY uu uuu aan aAa S 5 Abbreviations Equipment description 6 Installation u redni lakat ae pake Veolia rj dasa EDO EEE 7 Electrical connection 2 n inu uh ge Config 1 Mixer circuit and cylinder circuit Config 2 Mixer circuit and air heater circuit 13 Config 3 Mixer circuit and heating circuit 14 Config 4 Mixer circuit and return temperature raising for heating backup 15 Config 5 Return temperature raising for soft starting 16 Config 6 Heating circuit and return temperature raising for soft starting with bypass pump 17 Config 7 Mixer circuit with indirect return temperature raising for soft starting with bypass pump Config 8 Mixer circuit factory setting Config 9 Heating circuit 20 Config 10 Cylinder circuit 21 Config 11 Air heater circuit
17. changed and fault codes as well as sensor values can be displayed at the programming module BM or at the interface module ISM1 with Comfort Soft The MM has an eBUS interface and can therefore be integrated into the Wolf control system 3061892 0111 WOU Installation Mixer module installation Remove the mixer module from the packaging Fit the mixer module directly to the wall Connect an outside temperature sensor to the gas fired boiler Install the outside temperature sensor at a north or north eastern wall at a height of 2 2 5 m from the ground cable grommet pointing downwards Wire up the MM mixer module in accordance with the installation diagram Cable cross section for 230 V min 0 75 mm for 24 V min 0 5 mm Note Never route on site cables leads for outside temperature and flow temperature sensors together with mains cables Einstellung eBUS adresse 0 Fixing holes 10000 00mm 3061892_0111 7 W IF Output A1 Maximum thermostat A Outside temperature sensor Recommended cables and cable cross sections Note A Electrical connection a Electrical valve For wall mounted boilers with integral boiler pumps an electrical valve can be connected to output A1 in case of configuration 1 2 3 9 10 and 11 subject to the integral boiler pump matching the hydraulic design b Heating circuit primary pump F
18. cribed electrical protection values see specification Any damage or loss resulting from technical modifications to Wolf control units is excluded from our liability 3061892 0111 W IF Terminology 3061892_0111 Terminology Heating water temperature The heating water temperature is the radiator flow temperature The higher the heating water temperature the higher the heat transfer to radiators Mixer circuit temperature The mixer circuit temperature is the flow return temperature downstream of the mixer with which underfloor heating systems are supplied Cylinder heating Heating up the DHW cylinder DHW Quick Start The heating water in the boiler will be held at a certain temperature during summer mode to be able to supply hot water as rapidly as possible from the instantaneous water heater of combi boiler that is eguipped with the DHW Ouick Start function The DHW time program switches this function on and off during summer mode Heating program Subject to program selection the heating time program switches the boiler from heating to setback mode or from heating mode to heating off and vice versa Domestic hot water program In a gas fired combi boiler eguipped with the DHW Ouick Start function the DHW time program controls the DHW Ouick Start and for boilers with a DHW cylinder enables disables the cyl inder heating Winter mode Central heating and DHW according to the heating and DHW time program
19. emperature 5 K The set flow temperature then results from the set cylinder temperature excess boiler water temperature during cylinder heating Configuration Ci 4 For raising the return temperature during central heating backup a three way diverter valve is controlled to raise the heating return temperature via a buffer cylinder that has been heated up When the MM is operated as part of the Wolf WRS control system the boilers are blocked when the start conditions have been met If a demand is issued by at least 1 heating circuit or 1 cylinder the three way diverter valve will be switched and the blocking time set in parameter MI 18 lt blocking time for burner blocking starts The burner will be enabled again after the blocking time has expired The burner will be disabled for the set time when the start condi tions have been met whilst the burner is already active Start conditions PF act E1 gt RLF act E2 ATOn 15 Stop conditions PF act E1 lt RLF_act E2 ATOff m 15 When setting a blocking time of 0 s 18 the three way diverter valve will be controlled independently of any heat demand Parameter MI50 enables the individual control of relays MI50 1 Control of relay mixer circuit pump MKP MI50 lt 2 Control of relay mixer motor OPEN MM MI50 lt 3 Control of relay mixer motor CLOSE MM MI50 4 Control of relay outputA1 3061892 0111 W IF Cylinder frost protection Anti
20. esis bypass sensor MI 12 Primary pump blocking Note MI 13 Primary pump run on time MI 14 Constant temperature MI 15 ATOff shutdown differential 3061892_0111 Parameter description With configuration 6 7 the programmable output A1 acts as bypass pump in conjunction with a bypass sensor One condition for starting the bypass pump is that at least one pump pump for heating circuit cylinder or air heater has been enabled in the system Bypass pump ON BPF act lt RL set hysteresis bypass sen sor Bypass pump OFF BPF_act gt RL_set hysteresis bypass sen sor 5 K For starting the primary pump cylinder primary pump configura tion 1 and 10 or for ext heat demand configuration 2 and 11 we differentiate between two cases a Par MI12 0 The primary pump is started immediately after the command is issued b1 Par MI12 1 with configuration 1 and 10 Primary pump ON Boiler flow temperature gt actual cylinder temperature 5 K Primary pump OFF Boiler flow temperature S actual cylinder temperature 2 K b2 Par MI12 1 with configuration 2 and 11 Primary pump ON Boiler flow temperature gt constant temperature 5 K Primary pump OFF Boiler flow temperature lt constant temperature 8 K If a cascade module is also installed in the system instead of the Boiler flow temperature the Actual collector temperature is included in the determination whether the primary pump is s
21. eters for calculating the set flow temperature are left at their factory setting e g set cylinder temperature Parameters HG08 and HG22 will need to be modified if the factory settings for heating and cylinder circuits are changed or if configurations 2 or 11 have been selected at the mixer module For this HG22 only needs to be changed in conjunction with the R1 R2 R3 R21 or COB boiler control unit HG08 settings a Cylinder heating at the mixer module H608 gt set cylinder temperature 77 H601 b External heat demand convector heater at the mixer module configuration 2 or 11 HGOB gt MH HGOI b Heating circuits boiler or mixer module HGUG gt MOO MOI HGOT HG22 settings Hee gt HG08 Parameter list Parameters individual settings HG01 Burner switching differential HG08 Maximum limit boiler circuit TV max HG22 Maximum boiler limit TK max 3061892_0111 29 Parameter list contractor boiler W IF uondo ue se pajsnipe aq O ajqe pue An58J aie sJojoue1ed Bunes Alojpej y oBuey9 JEASU SANDE Jou ojgejsnipe Aljeuondo uX oads juo npouu J1 xiuu eu JO UOHEJNBIJUOL y o joelqns JA Josuas mol ndui sn5ojeuy ZZIW Z2 indu enBojeuy LZIN ja indu enBojeuy OZIN senjen Josuas yndu y Jo Aejdsiq x x x x x x x x
22. h you must observe to prevent material losses and boiler malfunctions W IF Standards and regulations Installation Commissioning Warnings A Maintenance Repair Standards Regulations The boiler and control accessories comply with the following regulations EG Directives 2006 95 EG Low Voltage Directive 2004 108 EG EMC Directive EN Standards EN 60730 1 EN 55014 2 EN 60529 According to DIN EN 50110 1 only qualified electricians may carry outthe installation and commissioning ofthe heating control unit and connected accessories Observe all regulations stipulated by your local power supply utility and all VDE or local regulations DIN VDE 0100 regulations regarding the installation of high voltage systems up to 1000V DIN VDE 0105 100 operation of electrical systems Never remove bypass or disable safety and monitoring equip ment Only operate the system in perfect technical condition Immedi ately remove remedy any faults and damage that may impact on safety Always ensure that cold water is mixed in with hot water when the DHW temperature is set above 60 C or when pasteurising at a temperature in excess of 60 C risk of scalding Regularly check the perfect function of all electrical eguip ment Only gualified personnel may remove faults or repair damage Only replace faulty components or eguipment with original Wolf spare parts Always maintain pres
23. he pulse duration 100 Outside this range the mixer is either not regulated at all AT lt 1 K or is regulated constantly AT gt setting of par MI 07 Within the temperature range the system exerts constant control Adjust the proportional range so that stable regulation is ensured This depends on the runtime of the mixer motor For mixer motors with a short runtime select a wide proportional range and vice versa for mixer motors with longer runtimes select a narrower proportional range Setting information These settings are only approximate guide lines Change factory settings only where reguired Mixer runtime in min 2 3 4 6 740 Temperature window in K par 27 25 14 15 9 10 5 32 3061892 0111 WOOF MI 08 Set return temperature Note 3061892_0111 Parameter description Mixer circuit for return temperature raising with configuration m 25 5 or 6 Configurations 5 and 6 include a mixer circuit control for return temperature raising Return temperature raising with configura tion 5 is active if the boiler assigned to the mixer module as signment by addressing boiler and mixer module is switched by the cascade module burner On The bypass is fully opened at the end of the demand With configuration 6 return temperature raising is always active when at least one heating or cylinder circuit is active The bypass is fully opened when no heating or cylinder circuit is active
24. ing page 19 Heating circuit page 20 Cylinder circuit page 21 Air heater circuit external heat demand page 22 Restart the system after every configuration change Mains On mains Off Switch the mains power OFF and then ON again via the emergency stop switch of the heating system or via an MCB WOLF Electrical connection Configuration 1 Mixer circuit and cylinder circuit Cylinder Flow sen Se sensor SP sor mixer ynder circuit VF Power primary pump 230 VAC SPLP Por me st OD l JE seus Boiler EN I Maximum Mixer motor zale thermostat De max TH re l DHW N J cylinder Mixer circuit Mixer motor pump MKP MM Heating flow Heating return 1 Whether pump or electrical valve see description Output A1 page 8 12 3061892_0111 WOU Electrical connection Configuration 2 Mixer circuit and air heater circuit external heat demand mp i z i z uta MKP A1 E2 m I IO 0 OIO 000M00 1 r 10Af i i Flow sen L1NPE J 00 sor mixer J circuit VF Power Zero volt 230 VAC contact PK pea se i Mmm N O I I m esus Boiler EEE BR Gas fired Maximum Mixer motor boiler thermostat MM max TH Teo I l NZ Air heater circuit Mixer circuit pump MKP Mixer circuit gt Heating flow Heating return Whether pump or
25. ion Hysteresis return temperature 8 K Example of a set return temperature 30 C The set return temperature applies to configuration 5 6 and 7 33 W IF Parameter description Actual return temperature K 45 40 35 30 gt Time Mixer CLOSE Mixer CLOSE and pump OFF P L MI 09 Maximum cylinder heating time MI 10 BUS feed 34 Forced actuation Bypass pump monitoring with configuration m 05 z 6 or 7 To monitor the return temperature a timer is set 30 min each time the bypass pump is started Timer ON RL act lt RL set for gt 30 min gt fault code 97 RL act gt RL set 2 K reset timer and fault code Cylinder heating is deemed to have been completed when the cylinder temperature is gt set cylinder temperature Fault code 52 is issued and the control unit switches over to heating mode for the Max cylinder heating time if cylinder heating is not com pleted within the max cylinder heating time this does not apply to the status heating lt summer mode This cycle continues until the actual cylinder temperature is gt set cylinder temperature or parameter MI09 is set to 0 MI 10 lt 0 BUS feed OFF i e the BUS feed is always switched OFF MI 10 1 BUS feed ON i e the BUS feed is always switched ON MI 10 2 BUS feed Auto i e the mixer module automatically switches the BUS feed ON or OFF 3061892 0111 W IF MI 11 Hyster
26. ion 05 Return temperature raising for soft starting page 16 Applies to single and multi boiler systems cascade in conjunction with R1 R2 R3 R21 boiler control units In this configuration the mixer module acts as return temperature raising facility for one boiler In multi boiler systems return temperature raising reguires a separate mixer module for each boiler On single boiler systems without cascade module set parameter HG06 pump operating mode to 1 1 lt feed pump This is found at control level 2 Contractor Boiler Every mixer module for return temperature raising with configuration 5 must be assigned to a boiler Assignment lt gt via addressing the boiler and mixer module MM a for single boiler systems without cascade module R1 R2 R21 address 0 factory set gt MM address 1 factory set R3 address 0 factory set gt MM address 2 b for single and multi boiler systems with cascade module Boiler 1 R1 R21 address 1 MM address 2 Boiler 2 R1 R21 address 2 MM address 3 Boiler 3 R1 R21 address 3 MM address 4 Boiler 4 R1 R21 address 4 MM address 5 Additional mixer modules up to address 7 can be configured individually Note System examples see also Wolf hydraulic schemes for medium sized boilers 3061892 0111 9 W IF Configuration 06 Note Configuration 07 Note 10 Electrical connection Heating circuit and return temperature raising for soft s
27. les BM MM 26 Setting the eBUS Address of the extension and programming modules MM BM c Max expansion without Wolf boiler control unit or MGK stand ard control unit The MM can also be used as a stand alone mixer circuit control ler if no boiler with eBUS interface is installed The MM can also be used as stand alone mixer circuit controller if no boiler with interface is installed In that case connect an outside temperature sensor to the BM 0 or a DCF receiver with outside temperature sensor to the eBUS System examples see Setting an eBUS interface with Wolf boilers point a Configurations 5 6 and 7 may not be set without a Wolf boiler being installed 3061892_0111 W IF Setting parameters Switching times Switching times The standard setting for all parameters and switching times are fixed and stored in a non volatile memory All changes are permanently stored and will not be lost even if the power fails for several weeks Parameters are set modified via the BM programming module Check the description of operation and setting modifying param eters in the BM installation and operating instructions Mixer circuit The switching times for the mixer are stored in the respective mixer module This is found at the second control level Time program Heating Mixer Heating circuit and cylinder The switching times for the heating circuit and cylinder are stored in the BM programming
28. mixer module In conjunction with a Wolf boiler control unit R1 R2 R21 COB the direct heating circuit can be installed either directly on the boiler or on a mixer module The factory setting provides for the installation of the heating circuit on the boiler If the direct heating circuit is connected to the mixer module set Pump operating mode parameter HG06 to 1 1 feed pump This is found at the second control level Contractor Boiler 24 3061892_0111 Setting the eBUS Address of the extension WLJIF and programming modules MM BM b Max expansion with Wolf boiler control unit R3 HK MK1 MK 2 Wolf boiler 6 EEE sme ki 1 bi un na i mano ka g N o g m 1 option IST oe I I EE j La option i for MK1 r NA MM 3 uno H W MM 4 HE MM 5 EU ore opr option In conjunction with a Wolf boiler control unit R3 the direct heating circuit can either be installed directly on the boiler or on a mixer module The factory setting provides for the installation of the heating circuit on the boiler If the direct heating circuit is connected to the mixer module set Pump operating mode parameter HG06 to 1 1 feed pump This is found at the second control level Contractor Boiler 3061892 0111 25 W IF Commissioning and setting of the eBUS Address of the extension and programming modu
29. module Time Block Switching Mixer Program Block Switching Mixer program time time ON OFF ON OFF Time Mo Su 1 5 00 21 00 Time Mo 1 4 30 20 00 prog 1 2 prog 3 2 3 3 Sa Su 1 6 00 22 00 Tu 1 4 30 20 00 2 2 3 3 Time Mo Fr 1 5 00 7 00 We 1 4 30 20 00 prog 2 2 14 00 21 00 2 3 3 Sa Su 1 6 00 21 00 Th 1 4 30 20 00 2 2 3 3 Fr 1 4 30 20 00 2 3 Sa 1 4 30 20 00 2 3 Vu 1 4 30 20 00 2 3 3061892 0111 27 W IF Parameter list Standard setting Parameter list This is found at the second control level Standard setting Mixer Parameters Setting range Factory setting Individual setting STANDARD TEMP 5 C 30 C 20 C RED TEMP 5 C 30 C 12 C GRADIENT 0 3 0 8 ROOM INFLU OFF ON OFF U S SWITCH 0 C 40 C 20 C ECO RED 10 C 40 C 10 C Parameter list Contractor system Check the BM installation and operating instructions for a descrip tionofthe parameters standard temperature reduced temperature gradient room influence W S changeover and ECO RED System parameters A09 A10 A12 and A14 can only be set in the programming module with address 0 all other system parameters can be found in the associated programming modules These are found at the second control level gt Contractor gt System
30. module and SM2 solar module is made in parameter MI 05 lt mixer module configuration and parameter SOL12 solar module configuration in accordance with the hydraulic scheme See Electrical connection in the mixer module or solar module installation instructions regarding the selection of the correct configuration Programming the Wolf boiler control unit When selecting configuration 5 at the mixer module select pump operating mode 1 at the R1 R2 R3 R21 boiler control unit HG06 1 Programming the following components 1 In BM programming module set parameters such as time day time programs etc 2 Adjust MM and SM extension module parameters according to reguirements Restart the system by means of the system On Off switch switch the mains OFF and then ON again The system is ready for operation after approx 1 min w G SELV If mixers 2 7 are operated programmed by the BM o the status display of the BM will show the Sun and Moon symbols simultaneously as soon as one of the mixers calls for heat 23 Setting the eBUS Address of the extension W JIF and programming modules MM BM Setting the eBUS Address Subject to the installed Wolf boiler up to seven mixer modules of the extension and per system can be connected The MM addresses are assigned programming modules in sequence from 1 to 7 in conjunction with the Wolf control unit MM BM for wall mounted boilers MGK or the Wolf boiler control units
31. or wall mounted boilers with low loss header and for boilers with or without low loss header connect a pump to output A1 in case of configuration 1 2 3 9 10 and 11 If the maximum thermostat is connected to terminals 4 5 or 6 of the MM only the mixer circuit pump will be switched off in case of faults the mixer will no longer close the MKP LED stays on With the injection control the bypass and gravity brake ensure that if there is a fault no heating water enters the mixer circuit even through the pump of the wall mounted boiler Where no hydraulic injection system is used as described on pages 41 43 either A install an electrical valve off in the zero volt state upstream of the mixer circuit pump and connect it electrically in parallel to the mixer circuit pump Application for several mixer circuits In case of faults mixer no longer closes the electrical valve prevents an overheating of the mixing circuit in conjunction with a maximum thermostat or B for gas fired condensing centres connect the maximum ther mostat to terminal E1 of the gas fired condensing centre E1 must then be programmed in accordance with the maximum thermostat see installation instructions The gas fired condensing centre will be blocked as soon as the maximum thermostat opens Application for one mixer circuit Without a maximum thermostat extremely high temperatures may occur in the underfloor heating circuit should the MM develop a fault
32. r circuit Mixer circuit and air heater circuit external heat demand Mixer circuit and heating circuit Mixer circuit and return temperature raising for heating backup Return temperature raising for soft starting Heating circuit and return temperature raising for soft starting with bypass pump Mixer circuit with return temperature raising for soft start with bypass pump Mixer circuit factory setting Heating circuit Cylinder circuit Air heater circuit external heat demand The mixer circuit pump heating circuit pump will run on according to the set value after the mixer circuit heating circuit has been switched OFF Subject to application the mixer circuit control can be configured for the mixer circuit in the heating flow configuration 1 2 3 4 7 8 or for the mixer circuit for return temperature raising configuration 5 6 The mixer circuit temperature is regulated to the set value by means ofthe mixer circuit sensor return temperature sensor mixer circuit in the heating flow mixer circuit for raising the return temperature via terminal VF and a motorised mixer The output of the mixer controller for regulating the mixer motor features P characteristics The P band can be changed for every parameter P range mixer The pulse duration lt activation of mixer motor is directly proportional to the mixer flow deviation AT lt Set Actual Parameter MI 07 determines the temperature deviation for which t
33. seizing pump protection Anti seizing mixer protection Emissions test Loading the standard values 3061892_0111 Auxiliary functions The set cylinder temperature when cylinder heating is blocked is 10 C Cylinder frost protection is activated when the actual cylinder temperature lt set cylinder temperature 5 K The set flow temperature then results from the set cylinder temperature excess boiler water temperature during cylinder heating To prevent the pumps from seizing because of long idle periods the mixer circuit pumps MKP and output A1 will be operated daily for approximately five seconds 12 00 h at the mixer module after they have been idle for more than one day Subject to configuration MI 05 1 2 3 4 7 8 the mixer will be regulated to drive to OPEN for approx 10 seconds daily 12 00 h at the mixer module and then for 20 seconds to CLOSE to prevent the mixer from seizing up if the configuration 5 6 the mixer is driven for 10 seconds to CLOSE followed by 20 seconds to OPEN Emissions test enabled Heating and DHW are enabled until the emissions test has been completed Set DIP 4 to OFF and then back to ON The standard values are now loaded again All LEDs illuminate briefly as confirmation 37 W IF Fault codes When MM recognises a fault the red LED flashes and the mixer module fault code is displayed on the associated BM as well as at the central BM address 0 The following MM fault
34. tarted or stopped The primary pump block must only be activated in the mixer module if at least one Wolf boiler or one cascade module is linked to the mixer module via eBUS The primary pump run on starts after cylinder heating or ext heat demand has been terminated configuration 1 2 10 and 11 The system regulates to the selected set flow temperature and output A1 is regulated in case of an external heat demand via a zero volt contact at input E1 and parameter configuration z 2or 11 External heat demand takes priority over any heat demand from the heating circuits The primary pump run on starts after the external heat demand has terminated The program selector and time channel heating or DHW have no influence Configuration 4 comprises a mixer circuit control and a AT control for central heating backup A condition for central heating backup is that either a heating circuit demands heat or that the cylinder heating ext heat demand is enabled Otherwise central heating backup is always OFF Output 1 ON if PF act gt RL act ATOn Output 1 OFF if PF act lt RL act ATOff 35 W IF MI 16 ATOn start up differential MI 17 Boiler excess tem perature during cylinder heating MI 18 Burner blocked when the return temperature is raised MI 50 Test function 36 Parameter description See MI 15 ATOff shutdown differential Cylinder heating starts when the actual cylinder temperature lt set cylinder t
35. tarting with bypass pump page 17 Applies to single boiler systems without cascade module in conjunction with R1 R2 R3 R21 boiler control units The mixer module with configuration 6 must be assigned to the boiler Assignment gt via addressing the mixer module MM R1 R2 R21 address 0 factory set gt MM address 1 factory set R3 address 0 factory set MM address 2 Additional mixer modules up to address 7 can be configured individually System examples see also Wolf hydraulic schemes for medium sized boilers Mixer circuit with indirect return temperature raising for soft starting with bypass pump page 18 Applies to single boiler systems in conjunction with R1 R2 R3 R21 boiler control units In conjunction with a cascade module configuration 07 must be set at the cascade module In that case configuration 7 must not be assigned at the mixer modules The mixer module with configuration 7 must be assigned to the boiler Assignment gt via addressing the mixer module MM R1 R2 R21 address 0 factory set gt MM address 1 factory set R3 address 0 factory set MM address 2 Additional mixer modules up to address 7 can be configured individually System examples see also Wolf hydraulic schemes for medium sized boilers 3061892_0111 W IF Configuration 08 Configuration 09 Configuration 10 Configuration 11 Notes 3061892_0111 Electrical connection Mixer circuit factory sett
36. th a dummy plug controls the mass flow that is injected into the mixer circuit subject to the flow temperature Benefits of injection control over shunt pump control A hydraulic separation is created thereby preventing the boiler pump and the mixer circuit pump from affecting each other The hydraulic balance is substantially easier to achieve since every consumer circuit requires only one butterfly valve The pump capacity in the mixer circuit is reduced because the mixer pressure drop must be added to the boiler circuit The mixer circuit pump will be switched OFF if in an underfloor heating system an excess tem perature occurs in the mixer circuit No additional solenoid valve like those required for dual shunt pump circuits is required for interrupting the mixer circuit supply Installation requirements Insert a dummy plug into the three way mixer see diagram Size the mixer circuit pipework correctly Pump rate AT Rated output Internal diameter pipework incl bypass up to 17201 h 10K up to 25 kW DN 25 Match up the mixer circuit and any existing consumer circuits with butterfly valves thereby pre venting a shortage of supply for individual consumers 42 3061892 0111 WOIF 230V AC 3061892_0111 System example injection control W JIF Specification Specification Supply voltage Power consumption electronics
37. to opening the casing isolate the mixer module from the power supply 1 Isolate the unit from the power supply Remove the lid from the terminal chamber by undoing both screws 3 Remove the casing top with a screwdriver 4 The fuse is located on the I h side of the PCB below the transformer fine wire fuse 5x20 6 3A M 39 WOLF Sensor resistances NTC Sensor resistances Boiler sensor cylinder sensor solar cylinder sensor outside temperature sensor flow sensor central sensor Temp Resist Temp Resist Temp Resist Temp Resist G Ohm Ohm Ohm C Ohm Ohm k 21 51393 14 8233 49 1870 84 552 20 48487 15 7857 50 1800 85 535 19 45762 16 7501 51 1733 86 519 18 43207 17 7162 52 1669 87 503 17 40810 18 6841 53 1608 88 487 16 38560 19 6536 54 1549 89 472 15 36447 20 6247 55 1493 90 458 14 34463 21 5972 56 1438 91 444 13 32599 22 5710 57 1387 92 431 12 30846 23 5461 58 1337 93 418 11 29198 24 5225 59 1289 94 406 10 27648 25 5000 60 1244 95 393 9 26189 26 4786 61 1200 96 382 8 24816 27 4582 62 1158 97 371 7 23523 28 4388 63 1117 98 360 6 22305 29 4204 64 1078 99 349 5 21157 30 4028 65 1041 100 339 4 20075 31 3860 66 1005 101 330 3 19054 32 3701 67 971 102 320 2 18091 33 3549 68 938 103 311 1 17183 34 3403 69 906 104 302 0 16325 35 3265 70 876 105 294 1 15515 36 3133 71 846 106 285 2 14750 37 3007 7
38. wereg WW uonednSijuog foye J XIW JOJ9BIJUOL Z I A 8 04U09 JE PUNO SI SIUL 3061892 0111 W IF MI 01 Minimum mixer circuit temperature MI 02 Maximum mixer circuit temperature MI 03 Heating curve gap MI 04 Screed drying Fig Flow temperature progress over time during screed dry ing 3061892_0111 9 45 Flow temperature Parameter description This minimum mixer circuit temperature limits the low end of the set mixer circuit flow temperature The maximum mixer circuit temperature limits the set flow tempera ture of the mixer circuit upwards for example to prevent damage to floor coverings This does not however replace a maximum thermostat for shutting down the pump The heating water temperature will be raised by the set value against the mixer circuit temperature If an underfloor heating system is started for the first time in new buildings the set flow temperature may as an option be control led independent of the outside temperature either to a constant value or to control the set flow temperature in accordance with an automatic screed drying program If this function has been enabled setting 1 or 2 it can be termi nated by resetting parameter MI 04 to 0 MI04 0N A MI 04 1 constant temperature mixer circuit The mixer circuit is heated to the set flow temperature The set flow temperature is regulated accurately to the temperature selected in parameter MI 01
39. x x x L 8 1 uonouns 1S9 OSIN PLE so S00 0 Bulste due unas Buunp payoojq saung SLIM x Pe Pe x MOL or o Buneay JapuijA9 Buunp dulej sseoxe Jajiog ZHN a 3 X x x gt s MOL Mo0e tv Jenueseyip dn ue s uO1V OLIM gi 2 z a x a MS 02 2 epuap UMOPJNUS HOLV SLIM S S S sei ii EEE 3 SL De 08 3 OG ounjejeduje JUeSUCD YLIN x x x x x uug UILUQL 0 uun uo uni dund Aewud ELIN X X x x 0 L 0 6unpojg dund AJeuld ZLIN Pe Pe x x 2 OL 9 0 9 0 Josuas ssedAq sisasa SAH LLIM aX aX aX 0X 0X aX aX X aX ox ax Z ony Z 40 o uO I pea sna OLIN x Z 5 z z x UZ u 0 own Buneey 1 pull 9 xe GOIM z Pe Pe x yx x fe pe pe O OG O 08 Do OZ alnjeledule UJnja 8S ZOIN I x x x x x x x x M ZL M 0v MS JeXIW oBUBJ q ZOIN I x x x x x x x UILUG UIIO 0 1N9419 Bune u su uo uny 901 uloatlslslzlgolsiviglzii 8 LL L UONEJNGIJUOD SOIN z Pe Pe x x x x x x 0 z YO 0 Buwup peedos POI x x x x x x MOL M0 MO0 deB enino BuneeH EOIN si 2 X xX X X x xX 3 OG Do 08 Do OZ due pnd419 JSXILU XBIN ZOIN Pe fx x fr fx x x x 9 0 2 08 3 0 due nouo Jexi UI LOIN ILJOLJ6B 8 2Z 9 S E Z L Bum s Bue1 Bunes sayo

Download Pdf Manuals

image

Related Search

Related Contents

Fala Comigo - Editorial Brazil Informatica  说明书 X5 User manual    Four à micro-ondes Microwave oven  More Than An Action-Packed Novel! Includes 7 exciting Programs  Polar FT1/FT2 Manual del usuario  SIMOVERT MASTER DRIVES Apparecchi a giorno (Grandezza K  Scurion ® Manual  資料D - 厚生労働省  

Copyright © All rights reserved.
Failed to retrieve file