Operating Instructions Type 8222 ELEMENT
Contents
1. Diagnostic M Sensor Temperature 14 lecivate I4 Yes No M M Tb Temperature 4 READ War hi 4 PIINPUT I Warn lo 4 INPUT Erhi 4 PINPUT P Err lo 4 INPUT To be warned when the fluid temperature is too low or too high activate monitoring of the fluid temperature in the function activate then set a temperature range in C outside of which the transmitter generates a warning event and displays the and A icons set a temperature range in C outside of which the transmitter generates an error event and displays the and icons When a warning or error event is generated by the transmitter go into the Info menu to read the cause of the event generation and or go into the Sensor function of the Diagnostic menu to read the measured temperature value MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 then check whether the built in Pt1000 is working correctly by measuring a fluid with a known temperature If the Pt1000 is faulty return the device to B rkert if the Pt1000 is not the cause of the problem check the process The warning event may also be associated with one or other or both transistor outputs See chap 9 11 10 function Output TR1 or Output TR2 c 25 a5 The error event may also be associated w
2. 12 PACKAGING TRANSPORT NOTE Damage due to transport Transport may damage an insufficiently protected device Transport the device in shock resistant packaging and away from humidity and dirt Do not expose the device to temperatures that may exceed the admissible storage temperature range Protect the electrical interfaces using protective plugs 13 STORAGE NOTE Poor storage can damage the device MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Store the device in a dry place away from dust Storage temperature 10 to 60 C 62 English Type 8222 ELEMENT A x x burkert Disposal of the product FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 14 DISPOSAL OF THE PRODUCT Dispose of the device and its packaging in an environmentally friendly way NOTE Damage to the environment caused by products contaminated by fluids Keep to the existing provisions on the subject of waste disposal and environmental protection o Note Comply with the national and or local regulations which concern the area of waste disposal 63 16 m Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Disposal of the product MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 64 a ia
3. 30 8 9 3 Using the navigation button sa cese sah a sada rda N 31 z 9 4 Using the dynamic functions nseaenennneunrennnenneunnsennnunnennnunnnunnnennennnnennnnnnnnnnunnnunnnunnnnnnnunnnnnnnnnnunnnennnnnnnnnnennnnnnnennnnn 32 4 9 5 Example for the input of a numerical value 7 33 E 9 6 Example for browsing in a menu 33 8 9 7 Description of the display een 34 E 9 7 1 Description of icoris ANd LEDs nr ntt retenir tenter terere tei 34 5 9 7 2 When switching ori the device tnt raster tena 35 g 9 8 Read level 35 S 9 9 Accessing the Settings level unsneoneennnenneunnsennennnennnennnennnunnennnzunnunnnunnnunnnennnnnnnnnnnnnnennnunnnnnnnennnnnnnnnnunnnennnunnnnnnnnnnenn 36 8 9 10 Menu structure of the Settings level unsnnsenonenneennnennnunnennnnunnunnnenneunnnennnnnnnnnnunnnennnunnennnnunnnnnnnnnnunnnennnunnnnnnnnnnenn 37 5 9 11 Parameters ES 40 9 11 1 Transferring data from one device to another sse net
4. PVAR choose the process value to be tested VALUE enter a process value selected from the PVAR function above to check output behaviour 9 15 Information menu 9 15 1 Reading the cause of events linked to icons See chap 9 9 to access the Info menu Info M Error 4 MESSAGE G Waning M MESSAGE Maintenance M PMESSAGE Smiley gt MESSAGE The function allows for reading a short description of the reason why the following icons are displayed by the transmitter ERROR WARNING MAINTENANCE SMILEY 9 or z n gb See also If you encounter problems at chap 10 3 9 15 2 Reading the software versions See chap 9 9 to access the Info menu Info 4 Software versions 4 q Sensor I READ The function allows for reading the software version of the acquisition conversion board Main for the process values and of the sensor board Sensor MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 56 English Type 8222 ELEMENT burkert Maintenance and troubleshooting FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 10 MAINTENANCE AND TROUBLESHOOTING 10 1 Safety instru
5. special INPUT v Stop temp INPUT Processing Calibrate the sensor using one of the following methods CALIBRATION calibrate the conductivity sensor by determining its specific C constant See details on next page This calibration updates the last calibration date Last cal date function of the CALIB INTERVAL sub menu hereafter CELL CONSTANT enter the cell constant marked on the sensor nameplate or read the last cell constant determined by using the function Calibration above This input does not update the last calibration date Last cal date function of the CALIB INTERVAL sub menu hereafter CELL CST TDS enter the TDS factor suited to your process The TDS factor allows for calculating the amount of Total Dissolved Solids TDS in ppm depending on the measured conductivity The default TDS factor is 0 46 NaCl CALIB INTERVAL read the date of the last calibration function Last cal date and set the periodicity of cali brations in days function Interval the transmitter generates a maintenance event by displaying the M icon and a warning message each time a calibration is due Set function Interval to 0000 days to ignore the function 2 77 9 11 10 See also If you encounter problems at chap 10 3 TEACH SPECIAL define the temperature compensation graph specific to your process The graph thus dete
6. Symbolised by y 7 in this manual 7 Symbolised by q a in this manual Fig 28 Using the navigation button You want to browse in Read level next screen er m previous screen access the Settings level display the Param menu y for at least 2 sec from any screen of the Read level browse in the menus of the Settings level m V J next menu T ciy previous menu 4 access the menu displayed 31 1 6 burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Operating and cornrnissioning MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 32 You want to Press brovvse in the menu functions BER AN next function AS n previous function select the highlighted function browse in the dynamic functions bar MEAS BACK ABORT OK YES NO next function gt il previous function GE confirm the highlighted dynamic function modify a numerical value increment the figure selected allocate the or sign to the numerical value move the decimal point 9 4 You want to pus to the extreme left of the numerical value then a until the desired sign is displayed n EP to the extreme right of the numerical value then gt until the decima
7. aa A aaia a Ro y is t s 8 o 5 5 DESCR PT ON A E 9 o 3 5 1 Area of pplicolionunsa bada a l a baq as l 9 o o 2 5 2 GOMerall CESK OM toe 9 b 5 2 1 Design a a aaa 9 5 8 5 2 2 H LTD L S H s y sini 9 ER E 5 3 Description of the name plate nunnenennaeunnunnnennnunnnennnunnnnnnunnnunnnennennnnennnnnnnnnnunnnunnnunnnnnnnunnnnnnnnnnunnnennnnnnnnnnennnnnnnennnnn 10 a 5 4 Available VErSlOMS viccassessccascsescesscostsssstesscesiecactscecautesecascccnctesnccecesatdacesteveszedsteadvcasrontusiaiadtenstaaiecsestaeatentiemeninamicininesitas 10 Lu 8 6 TECHNICAL DATA c n s n 12 gt z 6 1 enini aaa een 12 8 6 2 Conformity to standards and directives asasan 12 8 6 3 General technical data une a ad A a n a na dee 12 2 6 3 1 Mechanical data a RE NR E FR VERE RE dI z 6 3 3 Sensor SPSCIICATIONS citer terere 00 16 6 3 4 Electrical data een 16 6 3 5 Data of connectors and 165 2 entente treten teen tette treten tenens 17 7 ASSEMBLY 18 rx EE Dvd me 1
8. AC2 fi Display of the highest and Max lowest values of the process 1 450 mS cm value chosen Min 1 200 mS cm dz Reset Yes No Reset To choose the process values to be displayed see chap39 11 The display of the lowest and highest values in the Read level is deactivated by default To activate the feature and choose the process values see chap 9 1 1 6 35 English Type 8222 ELEMENT burkert Ww FLUID CONTROL SYSTEMS Operating and COMMISSIONING 9 9 Accessing the Settings level Any display of the Read level A P n Displa aram raram Outputs MEAS BACK Param EZ Display Outputs MEAS BACK Calibration 4 ra Outputs Calib Sensor E MEAS BACK Calibration Menu A Diagnostic Sensor Diagnostic OK MEAS BACK T I Outputs Sensor MEAS BACK lnfo fi Error d d y 77 H info MEAS BACK ormation Menu 1 Info Maintenance 1t d imm d MEAS BACK MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Default code 0000
9. it INPUT v 2 Polar slope lActvate 4 Yes No 1 gt Polarization 4 r Warn hi INPUT E LMErr hi 4 NPUT 5 x blTemperature 4 P Activate 46 lYes No 5 Temperature 14 READ E Warn hi INPUT gt Warn lo 4 INPUT iz Err hi 4 IINPUT e N Erio 4 INPUT o e e z 39 English burkert Type 8222 ELEMENT FLUID CONTROL SYSTEMS Operating and commissioning Test gt System 4 Code 4 o 4 4 9 o 0 nn To Outputs I 1AC1 IINPUT T ylAC 8 9INPUT 1 4 TR2 4 MOFE ON _ Sensor I Pvar I Conds m ylCondR _ TDSppm _p Value 4 IINPUT Info K Error 4 MESSAGE Maring kt MESSAGE Mainten K MESSAGE Smiley iv MESSAGE Software 8 READ Sensor It READ 9 9 11 Parameters Menu 9 11 1 Transferring data from one device to another See chap 9 9 to access the Parameters menu The function is only possible with a display module with software version V2 and a transmitter
10. nnenneennnonneunnnenrennnennnunnnunnnunnennnnunnnnnnennnunnnennnunnnnnnnunnnnnnennnunnnennnnnnnnnnnnnnnnnnennnunnnennnunn 57 s 10 3 If you encounter problems nn 58 Ti ACCESSOR ES L DU 62 12 PACKAGING TRANSPORT abdal uz duse ouai Ceci al alaqa b 62 13 SIORA QE re a bn sbb mb s b nb m b 62 14 DISPOSAL OF a ya aa 63 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS About this manual 1 ABOUT THIS MANUAL This manual describes the entire life cycle of the device Please keep this manual in a safe place accessible to all users and any new owners This manual contains important safety information Failure to comply with these instructions can lead to hazardous situations This manual must be read and understood 1 1 Symbols used DANGER Warns you against an imminent danger Failure to observe this warning can result in death or in serious injury WARNING Warns you against a potentially dangerous situation Failure to observe this warning can result in serious injury or even death CAUTION Warns you against a possible risk Failure to observe this warning can result in substantial or minor injuries NOTE Warns you against material damage Failure to observe this warning may resul
11. 16 burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Technical data 6 TECHNICAL DATA 6 1 Conditions Ambient temperature 10 to 60 C Air humidity 85 96 non condensated Protection rating IP65 and IP67 with connectors plugged in and tightened and electronic module cover fully screwed down 6 2 Conformity to standards and directives The device conforms to the CE directives through the following standards EMC EN 61000 6 2 EN 61000 6 3 Vibration EN 60068 2 6 Shock EN 60068 2 27 Type of fluid Pressure complying with article 3 of S3 from 97 23 CE directive Acc to the 97 23 CE pressure directive the device can only be used in the following cases depending on max pressure pipe diameter and fluid Conditions Fluid group 1 81 3 a Fluid group 2 1 3 a or DN 32 and PNxDN x 1000 Fluid group 1 8 1 3 b or DN gt 25 and PNxDN x 2000 Fluid 2 8 1 3 b UL 61010 1 CAN CSA C22 2 n 61010 1 MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 6 3 1 Mechanical data Part The UL devices conform to the following standards 6 3 General technical data Material Box seals stainless steel 1 4561 PPS EPDM Cover seal PC EPDM Display module M12 fixed connector PC PBT nickel plated brass Fixed connector holder stainless steel 1 4404 31
12. Measurement range 0 05 uS cm to 20 uS cm Type of fluid ultra pure water pure water Conductivity sensor C 0 1 Measurement range 0 5 uS cm to 200 uS cm Type of fluid pure water industrial wastewater Conductivity sensor C 1 Measurement range 5 uS cm to 10 mS cm Type of fluid industrial wastewater wastewater MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 6 3 4 Electrical data Power supply Version with 3 outputs 14 36 V DC filtered and regulated Version with 4 outputs 12 36 V DC filtered and regulated 16 English Type 8222 ELEMENT Technical data FLUID CONTROL SYSTEMS Characteristics of the power source not supplied of the UL versions limited energy source in accordance to UL 61010 1 paragraph 9 3 or Class 2 source in accordance to standards 1310 1585 and 60950 1 Current consumption Version with 3 outputs Version with 4 outputs 25 mA max at 14 V DC 5 mA max at 12 V DC Current consumption with loads on the transistors 1A max Power consumption 40 W max Protection against polarity reversal yes Protection against voltage spikes yes Protection against short circuits yes transistor outputs Transistor output NPN sink or PNP source depending on software setting open collector 700 mA max 0 5 A max per transistor if both transistor outputs a
13. Power supply 12 36 VDC Pipes in plastic Fig 1 Equipotentiality skeleton diagram with pipes in plastic MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 24 English Type 8222 ELEMENT x x burkert Installation FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 8 3 3 Wiring a version with a single M12 fixed connector Transistor output 1 2 OV E V 14 36 V DC 4 1 Transistor output 2 Fig 15 Pin assignment of the male fixed connector on a version with a single male M12 fixed connector Pin of the M12 female cable available as an accessory order code 438680 Colour of the wire 1 brown 2 white 3 blue 4 black 5 grey Load 1 solenoid valve for instance Load 2 solenoid valve for instance Power supply 14 36 VDC Fig 16 NPN wiring of both transistor outputs software setting NPN sink see chap 9 11 8 on a version with 1 fixed connector Load 1 solenoid valve for instance OX brown black grey 2 blue Load 2 solenoid valve for instance Power supply 14 36 V DC Fig 17 PNP wiring of both transistor
14. with a PVDF nut see Fig 4 and Fig 6 with a PVC nut see Fig 4 and Fig 5 The fluid temperature may be restricted by the pressure of the fluid and the material of the S022 adapter 20 to 100 C Oto 50 C Max fluid pressure PN16 The fluid pressure may be restricted by the temperature of the fluid and the material of the adapter S022 see Fig 4 Fig Stand Fig 6 15 iei aTe i10 Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Technical data Conductivity measurement Measurement range 0 05 uS cm to 10 mS cm Resolution 1 nS cm Measuring error 3 of the measured value Recommended min divergence of the conductivity 2 9o of the full scale e g for the sensor with C 0 1 range associated to the 4 20 mA signal range from 100 to 104 uS corresponds to the 4 20 mA output current Temperature probe Pt1000 integrated in the conductivity sensor Temperature measurement Measurement range 40 C to 130 C Resolution 0 1 C Measuring error 1 C Recommended min divergence of the temperature range 10 C e g range 10 to 20 C corresponds to the associated to the 4 20 mA signal 4 20 mA output current Temperature compensation none or according to a predefined graph NaCl or ultra pure water or according to a graph defined especially for your process 6 3 3 Sensor specifications Conductivity sensor C 0 01
15. 20mA choose the value of the process value previously selected associated with a current of 20 mA for each current output Functions 4mA and 20mA are used to define the measurement range for the process value associated with the current on the 4 20 mA output P and P are the values associated with a current of 4 mA or 20 mA respectively MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 If P is higher than P the signal is inverted and the range P P corresponds to the range for the 20 4 mA current gt 2 Process value chosen 44 Fig 32 4 20 mA current depending on the process value selected English Type 8222 ELEMENT burkert Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 FILTER choose the level of damping for the fluctuations of the current value for each current output Three damping levels are proposed slow fast or none The damping for the current outputs is similar to the damping of the display See Fig 31 DIAGNOSMODE choose to emit a current of 22 mA on the current output selected when an error event related to diagnostics see chap 9 1 3 2 9 13 3 and 9 1 3 4 is generated by the transmitter or allow the current output to operate normally choose none p N DEM See also If you encounter problems in chap 10 3 9 11 10 Setting the
16. English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Operating and COMMISSIONING an The setting has no effect on a version with one fixed connector if the sole current output is wired See Fig 18 The vviring mode is the same for all outputs If you choose sink NPN the current outputs must be wired in sinkink mode and the transistor outputs in NPN mode f you choose source PNP the current outputs must be vvired in sourcing mode and the transistor outputs in PNP mode See the vviring for the outputs in chap 8 3 9 11 9 Setting the parameters of the current outputs See chap 9 9 to access the Parameters menu The 2nd current output AC2 is only available on a version with 2 fixed connectors Param 4 Outputs 1 4 2 4 4 Cond8 CondR TempC TempF TDSppm blAmA Jt INPUT yl20mA 8 NPUT m Filter l Slow East None tt gt DiagnosMode _ 4 None L 22mA PVAR choose a process value impedance in Q cm conductivity in S cm temperature in C temperature in F or total dissolved solids in ppm associated with current output 1 resp current output 2 4mA choose the value of the process value previously selected associated with a current of 4 mA for each current output
17. MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 activate monitoring of the fluid conductivity in the function activate then set a conductivity range outside of which the transmitter generates a warning event and displays the and A icons set a conductivity range outside of which the transmitter generates an error event and displays the and icons When the transmitter generates a warning or error event go into the Info menu to read the cause of the event generation 52 and or go into the Sensor function of the Diagnostic menu to read the measured conductivity value English Type 8222 ELEMENT burkert Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 if necessary clean and or recalibrate the conductivity sensor if necessary check the process The warning event may also be associated with one or other or both transistor outputs See chap 9 11 10 function Output TR1 or Output TR2 The error event may also be associated with one or other or both current outputs See chap 9 11 9 function Output AC1 or Output AC2 See also If you encounter problems at chap 10 3 ACTIVATE choose whether or not to activate monitoring of the fluid conductivity CONDUCTIVITY read the fluid conductivity measured in real time
18. WARN HI enter the fluid conductivity value above which a warning event is generated WARN LO enter the fluid conductivity value below which a warning event is generated ERR HI enter the fluid conductivity value above which an error event is generated ERR LO enter the fluid conductivity value below which an error event is generated 9 13 3 Monitoring the polarisation slope See chap 9 9 to access the Diagnostic menu A malfunction in your process or the conductivity sensor may be shown by too high a polarisation slope The function allows for monitoring the polarisation slope and configure the behaviour of the device if the max thresholds are exceeded Diagnostic 4 Sensor Polar slope amp Activate 4 Yes No 4 M lPolarization 14 READ gt Warn hi 4 yVIINPUT Err hi 4 INPUT To be warned when the polarisation slope is too high activate monitoring of the polarisation slope in the function activate then set a polarisation slope value above which the transmitter generates a warning event and displays the icons and set a polarisation slope value above which the transmitter generates an error event and displays the icons and When a warning or error event is generated by the transmitter go into the Info menu to rea
19. burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT 9102 LO 6L peiuud ueqebeble p ss l i TH 5 1219 3 uoisj9A NA GEZLLLOOOL NYIN 65 Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS 9102 LO 6L peiuud ueqebeble p ss l i TH 5 1219 3 uoisj9A NA GEZLLLOOOL NYIN 66 burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT 9102 LO 6L peiuud ueqebeble p ss l i TH 5 1219 3 uoisj9A NA GEZLLLOOOL NYIN 67 Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS 9102 LO 6L peiuud ueqebeble p ss l i TH 5 1219 3 uoisj9A NA GEZLLLOOOL NYIN 68 9102 LO 6L peiuud ueqeDeBieJj p ss l i TH SNVIS 3 uoisj9A NA SEZLLLOOOL NYIN burkert FLUID CONTROL SYSTEMS S o 2 o o c a 7 D o o 9 www burkert com
20. If PVar CondR If PVar CondR If PVar CondR If PVar TempF If PVar TempC If PVar TDSppm p Unit MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Contrast Pix 96 Backlight Pox 96 37 English burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Operating and cornrnissioning MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 38 Param Outputs 4 p source PNP On a version with 2 transistor outputs I MlAC1 AC2 PVar CondS I CondR 4mA 4 INPUT 20mA 4 INPUT Filter 4 None Fast Slow DiagnosMode 4 None 22 L TR1 TR2 Pvar Conds I CondR gt Tempe gt TempF t gt TDSppm p warning Mode gt Hysteresis Window Low K INPUT High INPUT Contact t Normally open p Normal closed Delay
21. See chap 9 10 for the detailed menu functions 36 English Type 8222 ELEMENT bi urkert Operating and commissioning FLUID CONTROL SYSTEMS 9 10 Menu structure of the Settings level See chap 98 to access the Settings level If an upload has been done with this display Download Downl Yes No module T Upload 4 Upload Yes No Date I 9 NY YYY MMIDD X Param System K Up Download HH MM 4 code 14 9 0 Reset Yes No Code Ly Factory reset Display gt Line1 Line2 K lLine1 Line2 4 Enabled Disabled 4 45 lCondR Tempe lfempF 4 5 If PVar CondS MmS cm CondS cm If PVar CondR ylkO em If PVar CondR If PVar CondR TempF PRc TempC If PVar TDSppm Filter 4 gt iNone_ Past _plSlow Min Max 8 lstatus 4 lEnabled P Disabled I PVar If PVar CondS If PVar CondS
22. connectors Load 1 solenoid valve for Load 2 solenoid valve for instance instance Power supply 12 36 V DC Fig 23 PNP wiring of both transistor outputs software setting PNP source see chap 9 11 8 on a version with 2 fixed connectors 27 5 burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Installation First 4 20 mA input at external device Power supply blue Second 4 20 mA input at external device 12 36 V DC Fig 24 Wiring of both current outputs in sinking mode software setting NPN sink see chap 9 11 8 on a version with 2 fixed connectors First 4 20 mA input at external device with 2 fixed connectors Power supply MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 brown Second 4 20 mA input at external device Fig 25 Wiring of both current outputs in sourcing mode software setting PNP source see chap 9 11 8 on a version 1 4 20mA input at external device EIE 12 36 V DC Power supply 2 44 2
23. M12 5 point male fixed connector One version of the 8222 transmitter with 2 transistor outputs and two 4 20 mA outputs operates on a 3 wire System and requires a power supply of 12 36 V DC For such a version electrical connection is done via an M12 5 point male fixed connector and an M12 5 point female fixed connector 5 2 2 Conductivity sensor The transmitter 8222 is fitted with a sensor measuring the conductivity The sensor is pined together with the electronic module and cannot be dismantled The sensor itself comprises a Pt1000 temperature probe and 2 electrodes in stainless steel for sensors with a C constant of 0 01 or 0 1 in graphite for sensors with a C constant of 1 0 The conductivity of a fluid is the capacity of this fluid to conduct electrical current thanks to the ions in the fluid An alternating voltage is applied to the electrode terminals the current measured is directly proportional to the conductivity of the solution English Type 8222 ELEMENT burkert x FLUID CONTROL SYSTEMS Descri ption 5 3 Description of the name plate 8222 Conductivity Transmitter Type of transmitter and parameter measured Supply 14 36VDC 40W Max Output 1x4 20mA 2xTrans 1A Max Electrical power supply and power consumption Cell C 1 00 Range 5 10000 uS cm Process Temp 0 50 C Output specifications PN 16 Bar burkert Made in France 2 NPN PNP1 Cell constant and measuring range of
24. The module can be fitted in 4 different positions at 90 intervals MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Fully push in the module and turn to the right to lock it Fig 9 Mounting the display module 19 English n Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Assem bly 7 5 Removing the display module Unscrew the cover see chap 7 2 Turn the module by ca 20 to the left Once unlocked the module is raised slightly by the spring action Remove the module from its housing Fig 10 Removing the display module MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 20 tare iia Type 8222 ELEMENT burkert Installation FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 8 INSTALLATION 8 1 Safety instructions DANGER Risk of injury due to high pressure in the installation Stop the circulation of fluid cut off the pressure and drain the pipe before loosening the process connections Risk of injury due to electrical voltage Shut down and isolate the electrical power source before carrying out work on the system Observe all applicable accident protection and safety regulations for electrical equipment Risk of injury due to high fluid temperatures Use safety gloves t
25. burkert com MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 English Type 8222 ELEMENT burkert Description FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 5 DESCRIPTION 5 1 Area of application The 8222 transmitter is intended for the measurement of the conductivity Thanks to two fully adjustable tran sistor outputs the transmitter can be used to switch a solenoid valve activate an alarm and thanks to one or two 4 20 mA current outputs establish one or two control loops 5 2 General description 5 2 1 Design The 8222 transmitter comprises A sensor for measuring physical parameters comprising 2 electrodes which measure an impedance in Ohm a Pt1000 temperature probe measuring a resistance An acquisition conversion module for the process values measured acquisition of the impedance measured in Ohm conversion of the measured impedance into conductivity units acquisition of the resistance measured and conversion into temperature A display module with browse button used to read and or configure the parameters of the device The display module is available as an accessory One version of the 8222 transmitter with 2 transistor outputs and a 4 20 mA output operates on a 2 wire system and requires a power supply of 14 36 V DC For such a version electrical connection is done via an
26. chap 9 9 to access the Parameters menu Display J4 Linet 7 Line2 Param Yu Enabled Disabled M Conds CondR Tempe M TDSppm Unit gt uS cm mS cm Rem yikO cm Macem Filter 4 Fast M Slow If PVar CondS If PVar CondS If PVar CondR If PVar CondR If PVar CondR If PVar TempF If PVar TempC If PVar TDSppm PVAR choose the process value to be displayed on the line selected UNIT choose the unit for the process value displayed FILTER choose the filter level for the measurement values displayed on the line selected Three filter levels are proposed slow fast or none Fig 31 Filter curves 5 burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Operating and cornrnissioning MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 9 11 6 Displaying of the lowest and highest values measured See chap 9 9 to access the Parameters menu Param Display 4 Min Max 4 14 lDisabled 4 5 CondR remp remp 4 If PVar CondS mS cm If
27. m Param Sensor 4 it None A Linear 0 000 1 pure wat Special Linear temperature compensation choice Linear The linear temperature compensation may be sufficiently precise for your process whenever the temperature of your process is always gt 0 C Enter a compensation value between 0 00 and 9 99 C English Type 8222 ELEMENT x x burkert Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Use the following graph and equation to calculate the average value of the compensation coefficient o according to a temperature range AT and the associated conductivity range Ay AX 1 x QO x 25 T TPC AT Xos 9 12 Calibration menu 9 12 1 Activating deactivating the Hold function See chap 9 9 to access the Calibration menu Calib 4 System 4 Hold 4 Hold Disable g _ Hold Enable 1 o The Hold mode is automatically deactivated when the transmitter restarts after a power interruption if the Hold mode was activated at the moment of the power cut off The Hold mode is used to carry out maintenance work without interrupting the process To activate the HOLD mode enter the HOLD function choose enab
28. parameters of the transistor outputs mde See chap 9 9 to access the Parameters menu Param Outputs 1 TR2 4 CondS CondR Hm TempF MTDSppm Warning Mode Hysteresis Window INPUT High INPUT gt Low gt gt Contact Normally open Normally closed lnilni b Delay INPUT PVAR choose a process value impedance in cm conductivity in S cm temperature in C temperature in F output 2 f the selected transistor output is linked to the warning event the transistor switches as soon as such an event is generated by the transmitter See also If you encounter problems at chap 10 3 HIGH enter the high switching threshold value for transistor output 1 or transistor output 2 See Fig 33 and Fi 34 CONTACT choose the type of off position normally open NO or normally closed NC of transistor output 1 or transistor output 2 See Fig 33 and Fig 34 DELAY choose the value of the time delay prior to switching for each transistor output Switching only occurs if one of the thresholds high or low functions High or Low is exceeded for a duration longer than this time delay See Fig 33 and Fig 34 The time delay before switching is applicable to bot
29. seen trente E tas tentat E 48 9 12 5 Entering an offset for the temperature measurement sse 52 9 13 DiagnosticImenua az anada a an tita so bas l ba da s d ay s asc pu secet nde ces tassa C umi dadina 52 5 9 13 1 Modifying the Diagnostic menu access code tentent ntn ttnnen 52 5 9 13 2 Monitoring the fluid conductivity entrent tette er nennen rcnt 52 9 13 3 Monitoring the polarisation slope essent tenente enn 53 amp 9 13 4 Monitoring the fluid temperature iniia 54 i 9 14 Test menu x TUTUN NUHUN NUNUNMNUUNMHU HU TT HuHuTuuu immun mm uu n xuuu 55 9 9 14 1 Modifying the Test menu access 8 55 3 9 14 2 Checking the outputs TUNCONS isisisi enasini ian e aE 55 3 9 14 3 Checking the outputs 55 z EA EMI f ldur oli 105 X X0V0555 56 8 9 15 1 Reading the cause of events linked to icons 56 s 9 15 2 Reading the software versions iiini 56 5 10 MAINTENANCE AND TROUBLESHOOTING 57 i 10 1 Safety instructions M 57 10 2 Cleaning of the transmitter
30. the 1 65 67 W44LP D ida 3 0V Ir N m l 00559610 A NPN PNP2 Temperature range of the fluid 8 conductivity Nominal pressure of the fluid Allocation of the pins on the M12 fixed connectors Construction code Order code 10 Serial number 11 Protection rating Fig 1 Name plate of the 8222 transmitter 5 4 Available versions The following versions of the 8222 conductivity transmitter are available These references include the electronic module and the conductivity sensor The display module is available as an accessory See chapter il 1 Electrical Cell Nut connection constant material 14 36 V DC 2 transistors Male 5 pin M12 C 1 1x4 20mA fixed connector Order code 559610 559638 559612 559622 559614 559624 Voltage supply Outputs 559616 559626 559618 MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 10 English Type 8222 ELEMENT Description FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Voltage supply Outputs Electrical connection Cell constant 12 36 V DC 2 transistors Male 5 pin M12 C 1 2 x 4 20 mA fixed connector female 5 pin M12 fixed connector UL Order code material no 559611 yes 559639 yes 559623 yes 559625 559617 559627 yes 562395 562397 11
31. the related output does not react according to the measured physical value Test 4 Outputs AC1 4 y NPUT m T 2 4 INPUT L a TRI 4 OFFON TR2 K4 9OFF ON ACT check that current output 1 is working correctly by entering a current value and then selecting OK AC2 check that current output 2 is working correctly by entering a current value and then selecting OK TR1 check that transistor output 1 is working correctly by selecting the status of the transistor ON or OFF then OK TR2 check that transistor output 2 is working correctly by selecting the status of the transistor ON or OFF then OK 9 14 3 Checking the outputs behaviour See chap 9 9 to access the Test menu The H icon is displayed in place of the icon as soon as the check for the correct working of an output has started During the check the related output does not react according to the measured physical value The feature allows for simulating the measurement of the process value to check if the outputs are correctly configured 55 English Type 8222 ELEMENT burkert ws FLUID CONTROL SYSTEMS Operating and COMMISSIONING Test 4 9 Sensor 4 4 45 T Ti CondR 8 _p TDSppm Value
32. 0mA input at external device Fig 26 NPN wiring of both transistor outputs and wiring of both current outputs in sinking mode on a version with 2 fixed connectors software setting NPN sink see chap 9 11 8 28 ietellSje Type 8222 ELEMENT Installation burkert MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 1 4 20mA input at external sse 2 44 20mA input at external device device Power supply Fig 27 PNP wiring of both transistor outputs and wiring of both current outputs in sourcing mode on a version with 2 fixed connectors software setting PNP source see chap 9 17 8 29 16 Type 8222 ELEMENT burkert we FLUID CONTROL SYSTEMS Operating and COMMISSIONING 9 OPERATING AND COMMISSIONING 9 1 Safety instructions WARNING Risk of injury due to nonconforming adjustment Nonconforming adjustment could lead to injuries and damage the device and its surroundings The operators in charge of adjustment must have read and understood the contents of this manual n particular observe the safety recommendations and intended use The device installation must only be adjusted by suitably trained staff WARNING Danger due to nonconforming commissioning Nonconforming commissioning could lead to inj
33. 4 INPUT Sensor 4 Comp M None E I P lLinear 0 00096 NaCl plUltra pure wat Special Calib System Hold Hold Disabled m 22 Hold Enabled Code ro Confirm code_ gt o Outputs 6 AC1 AC2 4mA INPUT 20mA INPUT English Type 8222 ELEMENT bi n urkert Operating and commissioning FLUID CONTROL SYSTEMS Sensor Probe 4 4 8 RESULT Cell constant_ INPUT t p Cell cst TDS_ 4 INPUT interval Last cal date 4 plinterval D INPUT special _ Start temp INPUT Stop temp v INPUT Processing Temperature 4 Diagnostic 9 System Code 270 4 Confirm code K 1o I 1 S v 5 Q 5 Sensor 4 Conductivity 14 laectvate I4 Yes No 2 M ylConductiviy 1 READ E lVVarn hi 4 INPUT g War lo 4 INPUT o Erhi 4 INPUT 2
34. 6L 12 English Type 8222 ELEMENT Technical data FLUID CONTROL SYSTEMS Part Material Screws stainless steel Tightening nut PVC or PVDF Conductivity sensor PVDF in contact with the fluid Pt1000 stainless steel 1 4571 316Ti in contact with the fluid Electrodes sensor C 1 graphite sensor C 0 1 or C 0 01 Nickel plated brass Stainless steel Electrodes Graphite C 1 Temperature sensor stainless steel 316Ti C21 stainless steel 316Ti C 0 1 or 0 01 Fig 2 Materials used in the 8222 transmitter MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 13 16 burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Technical data MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 14 Fig 3 Fig 8 7 6 5 4 3 2 1 0 gt i T 0 80 100 120 ToO P psi 232 217 6 203 188 6 174 159 6 145 130 6 116 101 6 87 72 5 58 43 5 29 14 A application range of a 8222 with a PVDF nut B application range of a 8222 with a PVC nut The measures have been made at an ambient tem perature of 60 C P F
35. 8 7 2 Unscrewing the COVETL v s v s z dad daz da Ra BZ a ay a a du q ida za bay a daa ip a an aaxasinuzabai dakD slab n mbus d 18 1 English burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT 7 3 MOUNTING the Covet sisina aana adanadan anaia a adala 19 7 4 Mounting the display module nsuasonennaeonrunnnenneunnnenneunnnnnnunnnunnnenneunnnennnnnnnnnnunnnunnnunnnnnnnunnnnnnennnunnnennnnnnnnnnnnnnnnnnennenn 19 7 5 Removing the display module 5 ai 20 8 INSTALLATION ze wn Sg 21 8 1 Safety instructions EE EE M 21 8 2 Installation onto the pipe eae rre ernaann 22 8 3 UI p 23 8 3 1 Assembling the male or female connector accessories see chap 11 23 8 3 2 Equipotentiality of the installation tentent tentent tenete tenente nene 24 8 3 3 Wiring a version with a single M12 fixed connector sse 25 8 3 4 Wiring a version with 2 M12 fixed 26 5 s 9 OPERATING AND COMMISSIONING enssssennnssenunseenunseennnsennunsennunsennunsennunsnnnunsennunsnnnnnsnnnnnsnnnunsnnnnennnunsnnnnnsnnnnennnnennnunennnn 30 t 9 1 Safety MS TICE S REDEEM 30 8 9 2 Operating levels
36. MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Type 8222 ELEMENT Conductivity meter Leitf higkeits Messger t Conductivimetre Operating Instructions Bedienungsanleitung Manuel d utilisation burkert FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 We reserve the right to make technical changes without notice Technische Anderungen vorbehalten Sous r serve de modifications techniques 2008 2013 B rkert SAS Operating Instructions 1304 3 EU ML 00560330 Original FR Type 8222 ELEMENT burkert 6 3 2 General technical data Contents FLUID CONTROL SYSTEMS 1 ABOUT TH S MANUAL 4 1 1 Symbolsused 4 1 2 Validity of the manual l aaa s ar a a anna a ya na s enden 4 1 3 Definition of the word 4 2 INTENDED USE a nern 5 2 1 CCP c 5 3 BASIC SAFETY INFORMATION e 6 4 GENERAL INFORMATION eer wvR 8 5 ME COMMAG Ec 8 amp 4 2 Warranty r 8 o a 4 3 lnformation on the internet
37. PVar CondS Q cm If PVar CondR ylkO em If PVar CondR MMo cm If PVar CondR p Unit EC em If PVar TempF If PVar TempC If PVar TDSppm STATUS choose to display choice Enabled or not display choice Disabled the highest and lowest mea sured values of the process value chosen in PVAR hereafter since the latest reset PVAR choose the process value which highest and lowest measured values are displayed in the Read level UNIT choose the preferred unit in which the lowest and highest measured values are displayed 9 11 7 Setting the display contrast and brightness See chap 9 9 to access the Parameters menu On a version with one M12 fixed connector do not increase the default setting of the display brightness parameter Backlight Param Display 4 Contrast 4 96 Backlight Pox 96 T mn Set each percentage using 27 and CONTRAST choose the display contrast level as a 96 BACKLIGHT choose the light intensity of the display as a 96 on a version with 2 fixed connectors only ee 9 11 8 Choosing the output wiring mode See chap 9 9 to access the Parameters menu Param 4 Outputs kt HW Mode 4 _ sink NPN 43
38. and end values is less than 8 C Enter the value of the end of the temperature range for which the compensation graph must be determined Processing 1 234 mS Ad es eme d o During measurement the fluid temperature must pass 25 C mmerse the sensor in the solution and progressively reheat from T to T if T lt 25 C lt T from 25 C to T if 25 C lt T T from T to 25 C if T lt T lt 25 C The rise in temperature must be slow because of the inertia of the temperature sensor Avoid the formation of bubbles on the conductivity sensor Probe Probe v x A BACH Error teach Cal Result a as EAC time too long Save Yes No 5 8 C The message Error TeachTime too long Atthe end of processing The message Error Temp may be displayed during the graph definition you are requested to save span at least 8 C is displayed It signals either the calculated graph or not if the difference between the range start and end values is that the fluid has been heated too slowly less than 8 C 25 minutes elapsed between 2 measuring points or that the fluid temperature has not passed 25 C 51 English Type 8222 ELEMENT burkert we FLUID CONTROL SYSTEMS Operating and COMMISSIONING 9 12 5 Entering an offset for the temperature measurement See chap 9 9 to access the Calibr
39. angerous situations To avoid injury take care to prevent any unintentional power supply switch on to carry out the installation and maintenance work by qualified and skilled staff with the appropriate tools to guarantee a set or controlled restarting of the process after a power supply interruption to use the device only if in perfect working order and in compliance with the instructions provided in the user manual to observe the general technical rules during the planning and use of the device not to use this device in explosive atmospheres not to use this device in an environment incompatible with the materials from which it is made MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 not to make any external modifications to the device Do not paint or varnish any part of the device not to use fluid that is incompatible with the materials of which the transmitter is made not to subject the device to mechanical loads e g by placing objects on top of it or by using it as a step English Type 8222 ELEMENT Basic safety information FLUID CONTROL SYSTEMS NOTE Chemical compatibility of materials in contact with the fluid Systematically check the chemical compatibility of the component materials of the transmitter and the fluids likely to come into contact with it for example alcohols strong or concentrated acids aldehydes alkaline c
40. ation menu The temperature transmitted by the Pt1000 probe may be corrected This correction value is the temperature offset Calib gt Sensor 4 Temperature _ INPUT Enter the temperature offset E input limits 5 C 9 13 Diagnostic menu 9 13 1 Modifying the Diagnostic menu access code See chap 9 9 to access the Diagnostic menu Diagnostic System 4 Code lo 4 P Confirm code 4 9 o v Enter the new Confirm the new code code Default access code to the Diagnostic menu 0000 9 13 2 Monitoring the fluid conductivity See chap 9 9 to access the Diagnostic menu A malfunction in your process or the conductivity sensor may be indicated either by too low or too high a fluid conductivity or by an incorrect conductivity measurement The function allows for monitoring the fluid conductivity and configure the behaviour of the device if the param etered ranges are exceeded Diagnostic 4 Sensor Conductivty l Activate 4 Yes No M 4 _ Conductivity 16 y READ Warn hi 146 yINPUT Warn lo 4 INPUT I MErr hi INPUT Err lo 4 IINPUT To be warned when the fluid conductivity is too low or too high
41. ctions DANGER Risk of injury due to high pressure in the installation Stop the circulation of fluid cut off the pressure and drain the pipe before loosening the process connections Risk of injury due to electrical voltage Shut down and isolate the electrical power source before carrying out work on the system Observe all applicable accident protection and safety regulations for electrical equipment Risk of injury due to high fluid temperatures Use safety gloves to handle the device Stop the circulation of fluid and drain the pipe before loosening the process connections Risk of injury due to the nature of the fluid Respect the regulations on accident prevention and safety relating to the use of aggressive fluids WARNING Risk of injury due to non conforming maintenance Maintenance must only be carried out by qualified and skilled staff with the appropriate tools Ensure that the restart of the installation is controlled after any interventions 10 2 Cleaning of the transmitter Activate the HOLD mode see chap 9 12 1 and go into the Calibration menu in order not to interrupt the process during cleaning Always use a cleaning product compatible with the materials from which the device is made When cleaning the electrodes ensure that you do not scratch their surface Avoid dry storage of graphite electrodes during long interruptions in measurement in order not to increase the re
42. d or the fluid conductivity has been activated the alternative icons in this position are associated with see chap 9 13 2 9 13 3 0 13 4 9 15 11 and 10 3 The device is measuring The alternative icons in this position are MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 34 English Type 8222 ELEMENT A x xn burkert Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 9 7 2 When switching on the device When the device is switched on or the display module mounted on the electronic module the display indicates the software version of the display The display then shows the first screen in READ level N lo ye a Sooo burkert N 1 423 mS cm TempC 23 8 C ar T p e N Fig 30 Display indications when powering on the device 9 8 Read level First view of the Read CondS level 1 423 mS cm TempC 55 C rent outputs Zoom on the value in Conds the first line 1 423 5 EZ Zoom on the value 1 of the first current T output 1 8 3 mA Zoom on the value in the TempC second line o C 55 Zoom on the value of the second cur rent output 7 5 mA Jt
43. d the cause of the event generation and or go into the Sensor function of the Diagnostic menu to read the polarisation slope value if necessary clean and or recalibrate the conductivity sensor if necessary check the process 53 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Operating and COMMISSIONING The warning event may also be associated with one or other or both transistor outputs See chap 9 11 10 function Output TR1 or Output TR2 The error event may also be associated with one or other or both current outputs See chap 9 11 9 function Output AC1 or Output AC2 See also If you encounter problems at chap 40 3 ACTIVATE choose whether or not to activate monitoring of the polarisation slope POLARIZATION read the current polarisation slope value WARN HI enter the polarisation slope value above which a warning event is generated ERR HI enter the polarisation slope value above which an error event is generated 9 13 4 Monitoring the fluid temperature See chap 9 9 to access the Diagnostic menu A malfunction in your process or the built in temperature probe may be shown either by too low or too high a fluid temperature or by an incorrect temperature measurement The function allows for monitoring the fluid temperature and configure the behaviour of the device if the param etered ranges are exceeded
44. enerates a current of 4 mA measure the current emitted by the 4 20 mA output using a multimeter and enter the value given by the multimeter in the function AC1 4mA or AC2 4mA 20mA adjust the current output 1 or current output 2 for 20 mA When the 20mA function is selected the transmitter generates a current of 20 mA measure the current emitted by the 4 20 mA output using a multimeter and enter the value given by the multimeter in the function AC1 20mA or AC2 20mA 9 12 4 Calibrating the sensor DANGER Risk of injury due to electrical voltage Observe all applicable accident protection and safety regulations for electrical equipment Risk of injury due to the nature of the fluid Respect the regulations on accident prevention and safety relating to the use of aggressive fluids See chap 9 9 to access the Calibration menu English Type 8222 ELEMENT burkert Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 INPUT 5 INPUT INPUT Last cal date M MREAD Interval INPUT Start temp Calib 4 Sensor 4 4 17 Cell constant lCell cst TDS interval
45. essary Cal Result The transmitter displays the cell 1 00000 constant as calibration result D Probe Save or not the calibration result by Error out of Cal Result choosing Yes or No BACK range Save Yes No The message Error out of range signals that the cell constant is out of the authorized range lt 0 008 or gt 12 this may be due to either MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 a mistake made when entering the conductivity or the conductivity sensor which is not able to measure the solution conductivity Define the temperature compensation graph specific to your process Teach special function in the Probe menu 50 English MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Type 8222 ELEMENT m burkert Operating and COMMISSIONING FLUID CONTROL SYSTEMS Calib 4 Sensor 4 Probe it Teach special 4 9 7 Start temp E Enter the value for the start of the temperature range for which the compensation graph must be determined The fluid temperature range T T must be entered in such a way that the difference between T and T is greater than 8 C The message Error Temp span at least 8 C is displayed if the difference between the range start
46. ggressive fluids The 8222 transmitter is inserted into a fitting installed on the pipe Select an appropriate position on the pipe prefer A mounting to install a 8222 with sensor C 0 1 or C 0 01 _ Direction of the fluid Fig 11 Mounting positions in the pipe Mount the display module see chap 74 to calibrate and adjust the transmitter Check that seal A is set on the cover and that it is not damaged Replace the seal if necessary Carefully insert the transmitter into the fitting MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 22 Type 8222 ELEMENT Installation FLUID CONTROL SYSTEMS Position the transmitter in such a way that the markings located on either side of the electronics box are parallel to the pipe Tighten the nut on the fitting Fig 12 Installation into a fitting 8 3 Wiring DANGER Risk of injury due to electrical voltage Shut down and isolate the electrical power source before carrying out work on the system Observe all applicable accident protection and safety regulations for electrical equipment o Use a high quality electrical power supply filtered and regulated Make sure the installation is equipotential See chap 8 3 2 8 3 1 Assembling the male or female connector accessories see chap 41 Unscrew the nut 1
47. ghted Line displayed by using unction N Contrast The arrow indicates that some more functions are available which can be M EAS ABORT OK displayed by using z ynamic functions accessible through lt 8 and gt see chap 9 44 L 33 English Type 8222 ELEMENT burkert wv FLUID CONTROL SYSTEMS Operating and COMMISSIONING 9 7 Description of the display 9 7 1 Description of icons and LEDs ee 204 Wa burkert N Yellow LED shows that Green LED shows that transistor 1 is switched E the device is energized CcCondS Em 0 000uS cm iA TempC 23 8 C H ar Red LED shovvs an error see chap Yellovv LED shovvs that transis tor 1 is svvitched Yellovv LED shovvs that transistor 2 is svvitched Yellovv LED shovvs that Red LED shovvs an error transistor 2 is svvitched see 10 3 Fig 29 Position of the icons and description of the LEDs The LEDs of the display module are duplicated on the electronic board that is located under the display module these LEDs become visible when the transmitter is not equipped with the display module Meaning and alternatives Sensor in good condition fluid conductivity and fluid temperature within the set ranges If the monitoring of the conductivity and or the fluid temperature an
48. h output thresholds 45 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Operating and COMMISSIONING MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 46 Hysteresis operating The change of status is done when a threshold is detected increasing measured value threshold high function High to be detected decreasing measured value threshold low function Low to be detected NO NC contact contact ON gt ON Fe Y process value process value gt gt Low High Low High Y OFF Fig 88 Hysteresis operating Window operating The change of status occurs whenever one of the thresholds is detected NO NC contact contact ON ON process value 2 Process value Lovv High Lovv High OFF Le OFF Fig 34 Window operating NO Normally open NC Normally closed 9 11 11 Choosing the type of temperature compensation See chap 9 9 to access the Parameters menu This menu is used to deactivate the temperature compensation choice none or choose the type of temperature compensation to determine the conductivity of the fluid according to a linear percentage choice linear See below or according to a predefined graph NaCl or ultra pure water The compensation graph NaCl is valid for the 10 to 80 C temperature range and a concentration of 0 2
49. he device are proper transport storage and installation as well as careful operation and maintenance Only use the device as intended 2 1 Restraints Observe any existing restraints when the device is exported MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 16 Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Basic safety information 3 BASIC SAFETY INFORMATION This safety information does not take into account any contingencies or occurrences that may arise during assembly use and maintenance of the device the local safety regulations that the operator must ensure the staff in charge of installation and maintenance observe AN Danger due to high pressure in the installation Stop the circulation of fluid cut off the pressure and drain the pipe before loosening the process connections Danger due to electrical voltage Shut down and isolate the electrical power source before carrying out work on the system Observe all applicable accident protection and safety regulations for electrical equipment Danger due to high fluid temperatures Use safety gloves to handle the device Stop the circulation of fluid and drain the pipe before loosening the process connections Danger due to the nature of the fluid Respect the regulations on accident prevention and safety relating to the use of aggressive fluids A Various d
50. he periodicity of the cali brations is set within the INTERVAL function of the CALIB INTERVAL menu Go into the Sensor function of the Diagnostic menu to read the measured fluid temperature chap 9 13 4 if necessary check whether the built in Pt1000 is working correctly by mea suring a fluid with a known temperature If the Pt1000 is faulty return the device to B rkert if the Pt1000 is not the cause of the problem check the process Calibrate the con ductivity sensor chap 9 12 4 sistor outputs are operating depending on the set thresholds English 61 Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Accessories 11 ACCESSORIES ATTENTION Risk of injury and or damage caused by the use of unsuitable parts Incorrect accessories may cause injuries and damage the device and the surrounding area Use only original accessories and original replacement parts from B rkert Accessory Display module Black blank cover with EPDM seal Transparent cover with EPDM seal Calibration solution 300 ml 5 uS Calibration solution 300 ml 15 uS Calibration solution 300 ml 100 5 Calibration solution 300 ml 706 uS Calibration solution 300 ml 1413 uS 5 pin female M12 connector to be wired 5 pin female M12 female connector moulded on shielded cable 2 m 5 pin male M12 connector to be wired 5 pin male M12 connector moulded on shielded cable 2 m
51. ith one or other or both current outputs See chap 9 11 9 function Output AC1 or Output AC2 See also If you encounter problems at chap 1 0 3 English Type 8222 ELEMENT burkert Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 ACTIVATE choose whether or not to activate monitoring of the fluid temperature TEMPERATURE read the fluid temperature measured in real time through the built in Pt1000 WARN HI enter the fluid temperature value above which a warning event is generated WARN LO enter the fluid temperature value below which a warning event is generated ERR HI enter the fluid temperature value above which an error event is generated ERR LO enter the fluid temperature value below which an error event is generated 9 14 Test menu 9 14 1 Modifying the Test menu access code See chap 9 9 to access the Test menu Test 4 System 4 Code 6 it Confirm code 4 lo T TU Enter the new code Confirm the new code Default access code to the Test menu 0000 9 14 2 Checking the outputs functions See chap 9 9 to access the Test menu o The M icon is displayed in place of the 7 icon as soon as the check for the correct working of an output has started During the check
52. l point is in the desired place Using the dynamic functions Choose go back to the READ level without validating the modifica tions made dynamic function MEAS validate the input go back to the parent menu dynamic function OK dynamic function BACK abort the current operation and go back to the parent menu dynamic function ABORT answer the question asked dynamic function YES or NO istellSje Type 8222 ELEMENT burkert Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 9 5 Example for the input of a numerical value Modify each digit of the numerical value using 6 to increase the digit selected 62 Calib Temp VE Select the digit at to decrease the digit the extreme left of selected the numerical value Select the digit at the extreme with then right of the numerical value with allocate the or sign to the MEAS ABO RT OK gt then move the decimal point numerical value with with gt 42 lt E 1 bos 9 6 Example for browsing in a menu Title of the current menu sub menu or function The icon identifies the current menu Param s g The arrow indicates that some more Li net functions are available which can be Highi
53. led validate by OK In practice when the device is in Hold mode the toi icon is displayed in place of the fi icon the current emitted on each 4 20 mA output is fixed at the value of the last measurement of the process value associated with each output each transistor output is fixed at the status acquired at the moment the Hold function is activated the device is in Hold mode until the HOLD function is deactivated To deactivate the HOLD mode enter the HOLD function choose disabled validate by OK 47 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Operating and COMMISSIONING MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 48 9 12 2 Modifying the Calibration menu access code See chap 9 9 to access the Calibration menu Calib 4 System 4 Code Io I Corfim code 4 02 di qu Enter the new Confirm the new code code Default access code to the Calibration menu 0000 9 12 3 Adiust the current outputs VVARNING Risk of iniury due to vvrong adiustment p ERA See chap 9 9 to access the Calibration menu Calib Outputs PhAC17AC2 AmA M PINPUT i i 20mA INPUT 4mA adjust the current output 1 or current output 2 for 4 mA When the 4mA function is selected the transmitter g
54. luid pressure T Fluid temperature Fluid temperature pressure dependency of the 8222 with a PVC or PVDF nut English Type 8222 ELEMENT Technical data burkert FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 P bar aos O P PIONDOO NDWRUD n o 232 1217 6 C Metal 2 503 188 6 174 159 6 0 20 20 40 60 T C P Fluid pressure T Fluid temperature Fig 5 Fluid temperature pressure dependency of the 8222 with a PVC nut and a metal PVC or PP S022 adapter P 161 bar B Metal 1 1 1 1 1 PVC PP PP OCANWAKRTONWDOO NWOH 232 P psi 7 6 203 188 6 174 159 6 145 130 6 116 101 6 87 72 5 58 43 5 29 14 0 20 20 40 60 80 100 120 140 T C P Fluid pressure T Fluid temperature Fig 6 Fluid temperature pressure dependency of the 8222 with a PVDF nut and a metal PVC or PP S022 adapter 6 3 2 General technical data Pipe diameter DN25 to DN110 DN15 to DN20 under specific conditions Type of fitting Adapter S022 Nut between the 8222 and the fitting G 1 1 2 internal thread Max fluid temperature
55. ng m S PT Missing The connection to the Check that the nut on e Pt1000 probe is lost between the sensor thresholds holder and the elec tronic module is cor rectly screwed Send the device back to B rkert ON 22 depending S PT The fluid temperature Switch the power on Regulation is not being correctly supply off then on thresholds measured again The process is stopped if the error persists return the device to B rkert English Type 8222 ELEMENT Maintenance and troubleshooting FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Transistor output Current output Icon Message dis played in the Info menu Possible cause Recommended action 22mA __ depending on thresholds S RTC Clock The clock is faulty The process continues gt Return the device to Burkert if the clock is essential 22 mA _ depending on thresholds TR EE Fact Read TR EE User Read Parameter reading error Switch the power supply off then on again if the error persists set the device back if the error persists return the device to B rkert 22mA depending on thresholds TR COM Measure The acquisition con version module of the process values is faulty The process is stopped Switch the power su
56. o handle the device Stop the circulation of fluid and drain the pipe before loosening the process connections Risk of injury due to the nature of the fluid Respect the regulations on accident prevention and safety relating to the use of aggressive fluids WARNING Risk of injury due to non conforming installation 3 m electrical and fluid installation can only be carried out by qualified and skilled staff with the appropriate tools Install appropriate safety devices correctly rated fuse and or circuit breaker Respect the assembly instructions for the fitting used Risk of injury due to unintentional switch on of power supply or uncontrolled restarting of the installation Avoid unintentional activation of the installation Guarantee a set or controlled restarting of the process subsequent to any intervention on the device Protect this device against electromagnetic interference ultraviolet rays and when installed out doors the effects of the climatic conditions 2 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Installation 8 2 Installation onto the pipe DANGER Risk of injury due to high pressure in the installation Stop the circulation of fluid cut off the pressure and drain the pipe before loosening the process connections Risk of injury due to the nature of the fluid Respect the regulations on accident prevention and safety relating to the use of a
57. ompounds esters aliphatic compounds ketones halogenated aromatics or hydrocarbons oxidants and chlorinated agents NOTE Elements Components sensitive to electrostatic discharges This device contains electronic components sensitive to electrostatic discharges They may be damaged if they are touched by an electrostatically charged person or object In the worst case scenario these compon ents are instantly destroyed or go out of order as soon as they are activated To minimise or even avoid all damage due to an electrostatic discharge take all the precautions described in the EN 61340 5 1 and 5 2 norms Also ensure that you do not touch any of the live electrical components MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS General information 4 GENERAL INFORMATION 4 1 Contact To contact the manufacturer of the device use following address B rkert SAS Rue du Giessen BP 21 F 67220 TRIEMBACH AU VAL The addresses of our international branches can be found on the Internet at www burkert com 4 2 Warranty conditions The condition governing the legal warranty is the conforming use of the 8222 in observance of the operating con ditions specified in this manual 4 3 Information on the internet You can find the user manuals and technical data sheets regarding the type 8222 at www
58. on the body 4 Insert the cable into the nut 1 the cable clamp 2 and the seal 3 and then into the body 4 Strip 20 mm of the cable Out the central wire earth so that its length is equal to 11 5 mm Expose 5 5 mm of the wires on the stripped cable Tighten the terminal block 5 wired to the body 4 MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Tighten the connector nut 1 Fig 13 M12 multi pin connector not provided 23 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Installation 8 3 2 Equipotentiality of the installation To ensure the equipotentiality of the installation power supply device medium Connect together the various earth spots in the installation to eliminate the potential differences that may occur between different earthes Observe faultless grounding of the shield of the power supply cable Special attention has to be paid if the device is installed on plastic pipes because there is no direct earthing possible Proper earthing is performed by earthing together the metallic devices such as pumps or valves that are as close as possible to the device Power supply 12 36 V DC Fig 14 Equipotentiality skeleton diagram with pipes in metal Devices such as valves 6 pumps
59. outputs software setting PNP source see chap 9 11 8 on a version with 1 fixed connector 25 16 Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Installation MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 26 4 20 mA input at external 4 20 mA input at external device device 14 36 V DC 14 36 V DC j Power supply Power supply Fig 18 Possible connections of the current output whatever the software setting NPN sink or PNP source see chap 9 dn 8 on a version with 1 fixed connector 4 20 mA input at external device white Y b eae rown e blue grey Power supply 14 36 V DC Fig 19 NPN wiring of both transistor outputs and wiring of the current output in sinking mode software setting NPN sink see chap 9 77 8 on a version with 1 fixed connector 4 20 mA input at external device 4 4 14 36 V DC Power supply Fig 20 PNP wiring of both transistor outputs and wiring of the current ou
60. pply off then on again if the error persists return the device to B rkert 22mA depending on thresholds MR Ele UserWrite Parameter saving error Switch the power supply off then on again Save the settings again gt if the error persists set the device back GAS if the error persists return the device to B rkert OFF 4 20 mA depending on thresholds A S RTC Reinit The date and time are lost because the device has not been powered up for at least 5 days The message is only displayed at the first powering up Set the date and time again see chap 9 11 2 feed the transmitter for at least 4 hours so that the date and time are battery fed for 5 days English 59 burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Maintenance and troubleshooting MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 60 Current output Transistor output Message dis played in the Info menu Possible cause Recommended action 22 mA depending on thresholds E Conductivity The fluid conductivity is out of range The message is dis played if the moni toring of the fluid conductivity has been activated depending on the set thresholds ERR LO and ERR HI Go into the Sensor function of the Diagnostic menu to read the measu
61. r mined and memorised is used by the transmitter when you choose Special in the Comp function in the menu Param Sensor see chap 9 11 11 See details on next page 49 English Type 8222 ELEMENT burkert ww FLUID CONTROL SYSTEMS Operating and COMMISSIONING Calibrate the conductivity sensor Calibration function in the Probe menu Calibration consists in determining the C constant specific to each conductivity sensor using a solution with a known conductivity SSeS aZ o s n order not to interrupt the process activate the HOLD function see chap 9 12 1 Before each calibration correctly clean the electrodes with a suitable product Set the periodicity of calibrations in the Interval function in the sub menu Calib interval see previous page each time a calibration is due the transmitter generates a maintenance event and a warning message Calib I4 Sensor 4 Probe j4 Calibration Immerse the clean conductivity sensor in the solution with a known conductivity if the Hold mode is deactivated the transmitter alter nately displays the measured temperature of the solution the NN utut of the solution Calibration Ian _ Enter the conductivity of 5 5 023 uS cm 1 pue the reference solution used 5 000 uS cm marked on the bottle VOKD Change the unit if nec
62. re wired NPN output 0 2 36 V DC PNP output supply voltage Current output Response time 10 90 Version with 1 current output Version with 2 current outputs 4 20 mA sink NPN sink or source PNP source depending on software setting 150 ms default value max loop impedance 1100 at 36 V DC 610 at 24 V DC 180 Q at 14 V DC max loop impedance 1100 O at 36 V DC 610 at 24 V DC 100 O at 12 V DC 6 3 5 Number of fixed connectors Data of connectors and cables Type of connector 1 male M12 fixed connector cable 5 pin female M12 connector not supplied For the M12 connector with order code 917116 use a shielded diameter 3 to 6 5 mm wire cross section max 0 75 mm MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 1 male M12 fixed connector and 1 female M12 fixed connector cable 5 pin female M12 connector not supplied and 5 pin male M12 connector not supplied For the M12 connector with order code 917116 use a shielded diameter 3 to 6 5 mm wire cross section max 0 75 mm 17 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS Assem bly 7 ASSEMBLY 7 1 Safety instructions WARNING Risk of injury due to non conforming assembly The device must only be assembled by qualified and skilled staff with the appropriate tools Risk of inju
63. red fluid temperature chap 9 13 2 If necessary clean and or recalibrate the con ductivity sensor ON 22 mA depending E Polarization The polarisation slope is Go into the Sensor on too high function of the Diag O thresholds icai nostic menu to read The message is dis i s played if the monitoring the polarisation of the polarisation slope value chap 9 13 3 has been activated If necessary clean and depending on the set or recalibrate the con threshold ERR HI see ductivity sensor chap 9 13 3 ON 22 mA depending amp E Temperature The fluid temperature is Go into the Sensor on out of range function of the thresholds Diagnostic menu to The message is dis played if the monitoring of the fluid temperature has been activated depending on the set thresholds ERR LO and ERR HI see exem read the measured fluid temperature chap 9 13 4 If necessary check whether the built in Pt1000 is working correctly by measuring a fluid with a known temperature If the Pt1000 is faulty return the device to B rkert If the Pt1000 is not the cause of the problem check the process if the DIAGNOSMODE function of the Output AC1 or Output AC2 menu is set to 22 mA see chap 9 11 9 else the current output delivers a standard current between 4 and 20 mA transistor outputs are operating depending on the se
64. ry due to unintentional switch on of power supply or uncontrolled restarting of the installation Avoid unintentional activation of the installation Guarantee a set or controlled restarting of the process subsequent to any intervention on the device 7 2 Unscrewing the cover NOTE The tightness of the transmitter is not guaranteed when the cover is removed Prevent the projection of liquid inside the housing The transmitter may be damaged if a metal component comes into contact with the electronics Prevent contact of the electronics with a metal component screwdriver for example To unscrew the cover use your hand or a tool which can be used as a lever taking care not to scratch the glass Turn the cover until fully unscrewed MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Fig 7 Unscrewing the cover 18 English Type 8222 ELEMENT Assem bly FLUID CONTROL SYSTEMS 7 3 Mounting the cover Check that there is a seal on the cover and that it is not damaged Replace it if necessary Grease the seal if necessary using a component compatible with the seal material Fully tighten by hand to guarantee tightness Fig 8 Mounting the cover 7 4 Mounting the display module Unscrew the cover see chap 7 2 Set the display module at an angle of ca 20 in relation to the desired position
65. sponse time when they are next used Regularly clean the electrodes on the conductivity sensor with a suitable product depending on how dirty they are Please feel free to contact your B rkert supplier for any additional information 57 English burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Maintenance and troubleshooting MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 58 10 3 If you encounter problems Transistor output Current output Message dis played in the Info menu Possible cause Recommended action 22mA __ depending on thresholds Sensor not found The connection to the measurement module is interrupted Switch the power supply off then on again if the error persists return the device to B rkert depending on thresholds Read S EE Fact Read Factory data is lost The process continues but the accuracy of the device is modified Switch the power supply off then on again if the error persists return the device to B rkert ON 22mA depending m SEE User User data for the sensor Switch the power on Read is lost supply off then on thresholds y again check the sensor S EE User parameters in all the Write Sensor menus then save them again if the error persists return the device to B rkert ON 22mA dependi
66. t in damage to the device or system o Indicates additional information advice or important recommendations p gn Refers to information contained in this manual or in other documents Indicates a procedure to be carried out MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 1 2 Validity of the manual The manual describes the devices from V2 software version of the acquisition conversion module for the mea sured process values Check this sofware version on the device in the menu Info Software Versions Main 1 3 Definition of the word device The word device used within this Quickstart refers to the conductivity meter type 8222 ELEMENT English Type 8222 ELEMENT A x xn burkert Intended use FLUID CONTROL SYSTEMS 2 INTENDED USE Kerr a EEE Eee Use of the conductivity transmitter that does not comply with the instructions could present risks to people nearby installations and the environment The 8222 transmitter is intended for the measurement of the conductivity This device must be protected against electromagnetic interference ultraviolet rays and when installed out doors the effects of climatic conditions This device must be used in compliance with the characteristics and commissioning and use conditions specified in the contractual documents and in the user manual Requirements for the safe and proper operation of t
67. t thresholds English Type 8222 ELEMENT Maintenance and troubleshooting burkert FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Transistor output Current output Message dis played in the Info menu Possible cause Recommended action 4 20 mA Switched W Conductivity The fluid conductivity is out of range The message is displayed if the monitoring of the fluid conductivity has been activated depending on the set thresholds WARN LO and WARN HI Go into the Sensor function of the Diagnostic menu to read the measured fluid temperature chap 9 13 2 If necessary clean and or recalibrate the conductivity sensor 4 20 mA Switched 2 W Polarization The polarisation slope is too high The message is displayed if the monitoring of the polarisation slope has been activated depending on the set threshold WARN HI Go into the Sensor function of the Diag nostic menu to read If necessary clean and or recalibrate the conductivity sensor Switched OFF 4 20 mA Switched W Temperature M Calib Date The fluid temperature is out of range The message is displayed if the monitoring of the fluid temperature has been activated depending on the set thresholds WARN LO and WARN HI see A calibration of the con ductivity sensor is due T
68. te tentent 40 9 11 2 Setting the date and times er o HERR RU RR E saa 41 9 11 3 Modifying the PARAM menu access 86 AR tentent tentent trente tnnt 41 9 11 4 Restoring the default parameters of the Read level and the 6 2 6 41 9 11 5 Setting the data displayed in the READ level seen 42 9 11 6 Displaying of the lowest and highest values 43 9 11 7 Setting the display contrast and brightness 43 English Type 8222 ELEMENT burkert FLUID CONTROL SYSTEMS 9 11 8 Choosing the output wiring mode AAA R R tentent tente trente tentent 43 9 11 9 Setting the parameters of the current outputs Rene 44 9 11 10 Setting the parameters of the transistor outputs 45 9 11 11 Choosing the type of temperature compensation sesenta 46 9 12 Calibration menu 47 9 12 1 Activating deactivating the Hold sse tentent tentent tentes 47 9 12 2 Modifying the Calibration menu access code sse tentent tnnt 48 9 12 3 Adjust the current outputs ttr een nat Eee Redde 48 9 12 4 Calibrating the sensor sess
69. tput in sourcing mode software setting PNP source see chap 9 11 8 on a version with 1 fixed connector 8 3 4 Wiring a version with 2 M12 fixed connectors Transistor output 1 Transistor output 2 l 2 2 oO oo OV a l V V 2 OV 4 4 Current output 1 Current output 2 Male fixed connector Female fixed connector Fig 21 Pin assignment of the male and female M12 fixed connectors English Type 8222 ELEMENT x x burkert Installation FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Connect the power supply for the transmitter to the male fixed connector the supply is then transferred internally to pins 1 and 3 of the female fixed connector in order to ease wiring of the load to the female fixed connector Pin of the M12 female cable available as an accessory order code 438680 Colour of the wire 1 brown white 2 3 4 5 Pin of the M12 male cable available as an accessory order code 559177 Colour of the wire 1 brown 2 white 3 blue 4 black 5 grey Load 1 solenoid Load 2 solenoid valve for valve for instance instance Power supply 12 36 V DC Fig 22 NPN wiring of both transistor outputs software setting NPN sink see chap 9 11 8 on a version with 2 fixed
70. unction The parameters transferred are used by the device as soon as the message Download OK is displayed UPLOAD upload data from the transmitter to the display module 9 11 2 Setting the date and time See chap to access the Parameters menu Param System 4 Date YYYY MM DD _ Time 8 y HH MM DATE set the date input format year month day in the form YYYY MM DD TIME set the time input format hours minutes endes 9 11 3 Modifying the PARAM menu access code See chap 9 9 to access the Parameters menu Param I4 System Code 0 I4 Confirm code 4 9 o Enter the new Confirm the new code code Default access code to the Parameters menu 0000 9 11 4 Restoring the default parameters of the Read level and the outputs See chap 9 9 to access the Parameters menu Param 146 lSystem 4 Factory Set 14 lExecute Reset Yes No Choose Yes to restore the default parameters Choose Nor to keep the current parameters 41 English burkert FLUID CONTROL SYSTEMS Type 8222 ELEMENT Operating and cornrnissioning MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 42 9 11 5 Setting the data displayed in the READ level See
71. uries and damage the device and its surroundings Before commissioning make sure that the staff in charge have read and fully understood the contents of the manual n particular observe the safety recommendations and intended use The device installation must only be commissioned by suitably trained staff 9 2 Operating levels The device has 2 operating levels Read level This level is used to read the measured values of 2 process values selected in the Parameters menu to read both the lowest and highest values of the chosen process value that have been measured by the device since the latest reset this feature is not active by default to reset both the lowest and highest values of the chosen process value if the feature has been activated to read the current values emitted on the 4 20 mA outputs Settings level This level comprises 5 menus MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Menu title Related icon Param see chap 9 11 Calib see chap 9 12 Diagnostic see chap 9 13 Test see chap 9 14 bc 30 English Type 8222 ELEMENT Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 Menu title Related icon Info see chap 9 15 9 3 Using the navigation button Symbolised by 4 in this manual
72. with a V2 software version of the acquisition conversion module for the measured process values On the transmitter check the sofware version of the acquisition conversion module for the measured process values in the menu Info Software Versions Main The software version of the display module is displayed when the display module is energized MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 o The DOWNLOAD function is only available if an UPLOAD has been successfully performed Never interrupt an upload or download procedure else the transmitter may be damaged Param 4 System 14 Download Download I Downl Yes No Upload 4 Upload Yes No 40 English Type 8222 ELEMENT burkert Operating and commissioning FLUID CONTROL SYSTEMS MAN 1000111235 EN Version E Status RL released freigegeben printed 19 01 2015 The following data can be transferred from one device to another device of the same type user settings in the menu PARAM except the date the time the contrast level and the brightness of the display user settings in the menu DIAGNOSTIC TDS factor set by the user in the menu Calib Sensor Probe Cell cst TDS the access codes to the menus DOWNLOAD transfer the data previously uploaded into the display module using the UPLOAD f