Home

Automation System TROVIS 5100 Ventilation

image

Contents

1. v A BE13 BE1O BE7 BAA BA5 Speed 1 Speed 2 Fl F F8 F AE1 AE2 IEZI ESSE AEA AE3XAE4 AE3 Note The position of the cooling coil does not appear on the controller s display as in the above schematics Specifications in parentheses can be selected as an alternative System code number 9 Control of heat recovery unit HRU heating coil cooling coil and humidifier humidifying and dehumidifying Two control circuits temperature and hu midity control Humidifying or humidifying and dehu midifying operation configurable see section 3 3 3 Summer compensation see section 5 5 2 Fan operation 2 speed see section 5 3 3 EB 5177 EN 47 Function descriptions 5 Function descriptions The following descriptions assume that you are familiar with the operation of the control ler and that you know how to set function blocks their parameters as well as other 5 1 Control method You need to determine which control meth ods are to be used after you have deter mined the system code number You can choose between Supply air temperature control Exhaust air temperature control Exhaust air temperature cascade control Room temperature control or Room temperature cascade control 5 1 1 Supply air temperature control The sensor input F1 is the control variable input by default Alternatively the supply air temperature can also be guided over the ana log input AE1 to the controlle
2. VA VOR VS C 0152034 7506077 809 TON 12 13 1415 16 15118 19 20 21 22 23 24 gt START STOP Vfl V2 Yes 9 071525904 0506 7 RS 9 19 1112 13 1141516 17518 19 20 21722 23 24 x I gt START STOP Q Vl Y2 3 Operation Comments Press the arrow key until the symbol for the system times of use appears on the display Press the enter key 1 7 appears on the display Use the arrow keys to select for which day s you want to change the times of use 1 7 all days 1 5 Monday to Friday 6 7 Saturday and Sunday or 1 2 7 Mon day Tuesday Sunday In this example 1 7 is to be set Note When 1 7 1 5 or 6 7 are selected the times of use for the days selected are reset to the default settings Therefore do not use this menu to check the programmed time schedules Use just the menu for the individual days 1 2 7 instead EBSI77EN 27 Operation Press h or V h or VV 28 EB5177 EN Display shows 0123 45 6 7 8 9 IO TI 12 13 14 15 16 17 18 19 20 21 22 23 24 BERR Eee USEIN LILI Wl 22 MS Ol 2 3 455607 78 79 109 1 12 1901415 1601771919 20721122 29 24 DL LULILI VAY ZS OM 2 3456 7 38 9 JONI 2 ISAS 1617 18 191201 21 22 23 24 oF IIIT IL LILI 2 Y wA WS 0123 4 56 7 8 9101112 1214 15 16 17 18 1920 21 22 23 24 is ILITI I ULILI Wl WA WS Control levels Comments Press the enter key The starting time for the first
3. Heating Controlled variable System deviation Fig 21 Output signals for example in Anl 6 humidifying and dehumidifying EB 5177EN 65 Function descriptions Outputs 5 3 16 Air volume control Co4Fb04 Fb20 Co5Fb18 21 Y4 The control output Y4 can be used to control the speed of the fans and the air volume based on the air quality Activate for this Co4Fb04 and allocate an analog input for measuring the air quality L in function block Co5 Fb18 Fb21 The following parameters must additionally be set The function block parameter Minimum air volume flow in function block CoAFbO4 and if applicable for cascade control Factor of change Kp Air quality set point in the PAA level IF the air quality falls below the parameter Air quality set point the air volume is increased based on the Minimum air volume flow When an exhaust air cascade control or a room temperature cascade control is used the controller can be programmed so thot the air volume is increased when the supply air temperature limit is reached to eliminate the system deviation as quickly as possible This function has priority over the air quality con trol After the system deviation has been bal anced out the air quality control is enabled again You can activate this function by set ting Factor of change Kp not equal to O Example Exhaust air temperature set point 22 C Current exhaust air temperature 24 C Factor
4. Scope of the ventilation controller The TROVIS 5177 Ventilation Controller is designed for controlling and monitoring air handling systems ranging from simple air heaters right up to complex ventilation and air conditioning systems that contain heating coils mixed air chambers cooling coils humidifiers and heat recovery units These mounting and operating instructions will enable you to operate the switches and keys of this controller as well as give an explanation of the electrical connection and mounting procedure Also the extensive possi bilities for configuration and parameterization are described Please note that changes in configuration and parameterization require specialized knowl edge on ventilation technology After the controller has been connected to the power supply it is basically ready for opera tion Since the controller functions according to time schedules make sure the time and date are set before start up Refer to page 22 onwards for step by step instructions on how to set the time and date The controller also saves information on con figuration and parameters in a memory thot can function for a long time without a power supply Only the time and date need to be reset after a power failure The controller contains default setting to oper ate the ventilation system from 07 00 to 22 00 hours If the two speed fans are acti vated the default setting for time of use between 10 00 and 15 00 hours
5. EBSI77EN 137 Customer data Parameter Info level InF5 Range of values Public holidays max 20 days Vacations Starting date Finishing date Parameters in PA7 level Parameter max 10 vacation periods Range of values Station address Parameters in PAQ level Parameter 1 20 Range of values Station number to 247 Baud rate 150 to 9600 Cyclic initialization O 10255 Modem dialing interval 1 to 255 Modem timeout 1 to 255 Number of dialing attempts to control station 0 to 99 Phone number of control station fax Phone number of alternative recipient Access number D1 or E Plus network Mobile phone number Station identification 138 EB 5177 EN O to 9 P pause end Customer data Parameter Info level InF5 Range of values Public holidays max 20 days Vacations Starting date Finishing date Parameters in PA7 level Parameter max 10 vacation periods Range of values Station address Parameters in PAQ level Parameter 1 20 Range of values Station number to 247 Baud rate 150 to 9600 Cyclic initialization O 10255 Modem dialing interval 1 to 255 Modem timeout 1 to 255 Number of dialing attempts to control station 0 to 99 Phone number of co
6. Use the arrow key until the parame ter that you want to change appears on the display In the example it is the supply air temperature day set point Press the enter key to activate the parameter PA starts to blink on the display Control levels Press or V s both Display shows 0215203054526 728292 10112 1914516 17 18 1920 21222324 o 1 21 3545207 8 9 1011 12 13 14 15 16 17 18 9 20 2222324 Operation Comments Use the arrow keys to set the new value for the parameter Note The longer you press an arrow key the quicker the value changes Press the enter key to confirm the new value The next parameter appears on the display In the example it is supply air temperature night set point It may be another parameter as it depends on the configuration Repeat the instructions in the gray box to change other parameters if need be Press both arrow keys simulta neously The next PA level appears Note If End appears on the display you can also press the enter key IF PA is not shown this means a parameter is activated Press the enter key first EBSI77EN 2 Operation Control levels Display shows Comments 2 OM 25 EASE 8 9310 2 13 ASe nl 2021222324 Press the changeover key to exit the Hu configuration level Leo El II Vil 12 EY Setting the time and date Press Display shows Comments e O i 2 3 AL Sy 66 7 8 9 IO Hl 12 13 14 15 1617 18 19202
7. 60 Heat recovery unit Y2 Co2Fb21 0 4 63 Humidifier Y2 YA Co4Fb21 2 oos 64 Cooling coil Y3 2 sag a dk x oo OE EU 3 3 RR AA 65 Air volume control CoAFbOA Fb20 Co5Fb18 21 Y4 65 Request for externally required signal over LON Co1FbO1 66 Time functions ss 68 Summer deactivation n 68 Summer time operation PA 2 llle 68 Automatic summer time winter time changeover Co5Fb16 69 Public holidays and vacations PA5 lll 69 Time schedules times of use PA4 PA5 69 Control functions 2 ooh 70 System start up mode 2 1 a 70 Summer compensation PA5 2 2 llle 7 Outdoor temperature controlled supply air control 7 Sustained room temperature CobFb05 02 72 Night purge Co5Fb17 a 73 Air quality control via the mixed air chamber Co5Fb18 21 PA 73 Supply air temperature limit Co5FbO1 Co5Fb18 PAS 2 74 Return air temperature limit Co5Fb04 PA1 0 74 Variable return air temperature maximum limit PA 2 75 Supply air humidity limit Co5FbO6 Fb19 PA5 2 2 aaa 75 Controller reaction when faults occur ee 76 Sensor failure and malfunctions 00088 ee 76 5 6 2 5 7 5 7 1 WN 573 6 1 7 1 7 52 7 2 1 22 r 7 4 7 4 1 7 4 2 8 8 9 10 11 Appendix A Appendix A 1 Appendix A 2 Appendix A 3 A
8. Request for externally required signal 66 Automatic operation 7 Automatic reversal PIR Losses yee Bw ee 64 Mixed air chamber Automatic summer time winter time change OVER 69 98 B Boucle 2446245 uade Zaa Mead 83 Binary inputs External demand for fan speed 2 54 External demand for operation 54 Binary output dependent on Y3 58 Fault alarm oufput 60 C Chillr 59 Circulotion pump Heat recovery HRU 59 Heating coil 57 Condensation detection Configuration levels 31 Control method 48 52 setting see setting of system code number Control signal limit 70 Cooling coil 4 Cyclic initiolizotion 120 E Enabling fan speed 2 57 Exhaust air cascade control 52 Exhaust air humidity control Exhaust air temperature cascade control 49 Exhaust air temperature control 48 External correction of the humidity set point External demand for fan speed 2 54 External demand for operation External temperature set point correction 56 F Fanspeed 57 Fan speed 2 dependent on air quality 57 58 Times oFuse 9 Fault alarm output 60 Frost protection Heating coil 77 P
9. EBSI77EN 89 Electrical connection 10 Electrical connection N Caution For the wiring and connection of the controller you are required to observe the regula tions of the Association of German Electrical Engineers VDE and your local power sup plier For this reason this type of work must be carried out by a specialist Caution The 0 to 10 V inputs of the controller are not DC isolated from the control out puts If actuators and active sensors are used which are supplied from the same operating voltage source either all the actuators or all the sensors must be DC isolated If these in structions are not followed the controller may be destroyed Notes concerning the electric wiring Use separate cables for the 230 V supply lines and the signal lines To improve the noise immunity keep a minimum distance of 10 cm between these cables This dis tance also applies to the cables inside the control cabinet Use separate cables for the digital signals bus lines and the analog signals sensor cables analog outputs We recommend that shielded cables be used for analog signal lines in systems with a high level of electromagnetic noise Ground the shield at the control cabinet Surge protection measures 90 If signal lines are routed outside of build ings or over long distances you are re quired to provide appropriate surge pro tection measures Theses are imperative when bus lines are used The shield of sign
10. ll corresponding to VDE 0106 Degree of contamination 2 corresponding to VDE 0110 Overvoltage category ll corresponding to VDE 0110 Humidity rating F corresponding to VDE 40040 Noise immunity Corresponding to EN 50082 Part 1 Noise emission Corresponding to EN 50081 Part 1 Weight Approx 0 6 kg EB5177 EN 93 EB 5177 EN Configuration level Col for heating coil Lists of function blocks Appendix A Lists of function blocks Appendix A 1 Configuration level Co1 for heating coil Fb Function WE Anl Comments O1 Request for externally OFF 0 9 ON Request for externally required signal required signal parameters see p 66 Flow requirement MIN O to 120 90 C Flow requirement MAX O tol 20 90 C Change when Y1 MIN O to1 00 10 C Change when Y1 MAX O to 100 90 C interlockable 12 On off output for OFF 0 9 ON BA7 activated deactivated depending on Y1 heating coil at BA7 parameters see p 59 Activating value START O to100 30 Deactivating value STOP 0 to100 10 interlockable only when Col Fb13 OFF 13 Three step output for OFF O ON BA6 Operating action CLOSING BA7 Operating heating coil at BA6 action OPENING parameters Valve running time TY BAZ 12 30 45 240 90 sec see p 60 only when Co1 Fb12 OFF 21 Operating action of OFF 0 6 POPEO LM cuore heating coil 91 Appendix A 2 C
11. 70 80 490 100 4110 4120 694 757 825 896 971 1010 1050 1132 1219 1309 1402 1500 1601 1706 1815 1925 Hygrometer Hygrometer for supply air humidity and exhaust air humidity Type 5232 5 duct hygrometer Hygrometer for room humidity Type 5242 5 Differential pressure switch for fan operation feedback Type 5335 Temperature monitor thermostat for system frost protection Type 5312 2 EBSI77EN 129 Customer data Info level InF5 Appendix E Customer data Station Operator Responsible SAMSON office System code number Function block settings Col ON OFF Options selected function block parameters Flow requirement MIN AA 90 C Flow requirement MAX AA 90 C Change when Y1 MIN 10 C Change when Y1 MAX 90 C Activating value START O to 100 30 Deactivating value STOP 0 to100 10 Valve running time TY 12 30 45 240 90 sec Fb ON OFF Options selected function block parameters ON OFF Options selected function block parameters BE10 BE7 SIEIG FALL 130 EB 5177 EN Customer data ON OFF Info level InF5 Options selected function block parameters OFF Enabling the cold storage at outdoor temperature START 18 C ON SEQ Activating value START 30 26 Deactivating value STOP 10 Par Minimum activated time START MIN 600 sec Minimum deactivated time STOP
12. ON are kept regardless of the input variables If is activated EBSI77EN 9 Operation Activating manual mode Press Slide the mode switch A to Display shows ORI 2 AS OOA 20222232A IJ I Slide the selec tion switch for manual opera tion B to the output that you want lo change 10 EB 5177 EN Manual mode Comments The display remains unchanged Press enter key until Hand appears on the display Press the enter key The state of the selected output and the associated symbol blinking in the schematics appear on the display This example shows Y1 heating coil as the selec tion switch B is positioned at Y1 Y Control signal Y1 Y2 Control signal Y2 Y3 Control signal Y3 YA Control signal YA Q Pump s D Fans The associated symbol blinks on the display Note appears when this output is not connected Manual mode Operation Press Display shows Comments 0123 4 5 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 Activate the output observing Switch on pumps fan increase con trol signal Switch off pumps fan reduce con trol signal Note For two speed fans you can select On1 On2 or OFF When the selection switch B is set to the pump symbol and several pumps are controlled e g with Anl 3 use the enter key to select another pump The symbol of the selected pump blinks on the display when the pump is switched off just yi Y2 v3 t
13. bers Anl 1 and Anl 4 to Anl 9 This summer compensation function lets the set points for supply air exhaust air and room temperatures be shifted in a linear man ner by means of two coordinates For this purpose the following parameters must be defined in PA5 Summer compensation when the outdoor temperature is greater from this outdoor temperature onwards the temperature set point is raised Set point at an outdoor temperature of 32 C determines the gradient of the characteristic curve Function descriptions Example In an air conditioning system the exhaust air temperature set point is be raised when the outdoor temperature is greater than 25 C At 32 C the exhaust air temperature set point should be 26 C Exhaust air temperature set point mI Summer compensation when the outdoor temperature is greater 25 C Set point at an outdoor temperature ot 32 C 26 C Supply air temperature maximum limit 30 C 5 5 3 Outdoor temperature controlled supply air control The functionality of the summer compensa tion see section 5 5 2 can also be used for an outdoor temperature controlled supply air temperature control e g with system code number Anl 0 The parameter Summer com pensation when the outdoor temperature is greater PA5 determines from which outdoor Set point C Fig 24 Summer compensation temperature the Supply air temperature set point is to be reduced The parameter Set point at an outd
14. implemented by a PID control algorithm with adjustable Mixed air temperature set point Outputs The output Y2 is adapted to the dynamics of the mixed air chamber with the parameters Kp Mixed air chamber TN Mixed air cham ber and Ty Mixed air chamber PA2 The parameter Minimum outdoor air rate PA2 guarantees a minimum proportion of outdoor air The operating action of the control output Y2 can be reversed The default setting is an out door air rate of 0 to 100 which corre spond to a control signal of O to 10 V By Function descriptions activating the function block Co2 Fb21 the operating action is reversed an outdoor air rate 0 to 100 corresponds to 10 to 0 V On feedforwarding the outdoor temperature the summer time operation function is taken into account see section 5 4 2 By additionally feedforwarding the exhaust temperature the automatic reversal of the operating action takes effect Outdoor temperature controlled mixed air chamber Control signal 18 24 Outdoor temperature Fig 19 Outdoor temperature controlled mixed air chamber You can achieve the outdoor tempera ture controlled mixed air temperature control by deactivating Co5 FbO7 and then selecting At For the outdoor temperature controlled mixed air chamber two outdoor temperature basic values are determined with the parameters Mini mum outdoor air rate when the outdoor temperature is lower and 100 5 outdoor when the
15. 19 1 4 12 16 17 18 1920 21 22 23 2 the function blocks to deter mine the selectable functions available in the controller You will need to enter the key code before changing some Fig 2 How the function blocks are shown on the display The ventilation controller has various configu ration levels Co levels in which functions are grouped according to their area of activ ity Each configuration level consists of func tion blocks The configuration levels are des ignated Col to Co9 and the function blocks FbOO to Fb23 You can activate or deactivate of the function blocks For var ious function blocks you must also set the function block s parameters Refer to Appendix A for a list of func tion block parameters At first the functions are deter mined by the system code number and the control method It also determines the parameters in the param eter levels PA1 to PAY On activating the Co level the activated func tion blocks are indicated at the top of the dis play by the squares located to the bottom right of each function block number see Fig 2 VAL Y2 Ve If you want to change the function blocks proceed as follows 1 Find out which function block you need in the Appendix A noting the index of the Co level 2 Access the configuration level and then the required Co level as described in the section below Accessing a Co level Accessing a Co level from the operating level gt Pr
16. Cyclic initialization 0 255 min See p 84 Parameter der Ebene PA9 Modbus Symbols with default settings Parameters Parameter name After pressing range of values the enter key 0123 45 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 Modem dialing interval for calls to the control station 1 255 min See p 84 Modem timeout 1 255 min See p 84 Number of dialing attempts to control station 0 99 See p 84 Phone number of control station GLT or its fax max 23 characters O 9 P pause end of phone number See p 84 EBSI77EN 12 Parameters Symbols with default settings Parameter der Ebene PA9 Modbus Parameter name After pressing range of values the enter key 01234567 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 DUTY YS 122 EB 5177 EN Phone number of the alternative recipient max 23 characters O 9 P pause end of phone number See p 84 Access number D1 or Eplus network max 23 characters O 9 P pause end of phone number Only when an error message is sent to a mobile phone See p 82 Mobile phone number max 23 characters O 9 P pause end of phone number Only when an error message is sent to a mobile phone See p 82 Station identification optionally with connection to a
17. If you want a different time schedule for these setting you must change the times of use Refer to page 26 for details on how to change these settings If you require more information on a certain topic use the subject index at the end of these instructions EBSI77EN 5 6 Safety instructions Safety instructions An Assembly start up and operation of this device may only be performed by trained and experienced personnel familiar with this product Proper transportation and storage are assumed The controller is intended for use in elec trical power installations For wiring and maintenance you are required to observe the relevant safety regulations In automatic operating mode time con trolled operation the device ensures thot all protective functions that are vital for the system are monitored Safety features such as frost protection monitoring and EB 5177 EN excess temperature protection however are not active in the following cases de fective controller and failure of function defective sensors or sensors that are not connected or have not been deactivated lack of operating voltage to the controller The installation and electrical wiring de scribed in these instructions should only be performed by authorized personnel Changing function blocks and their pa rameters see Appendix A requires spe cialized knowledge of ventilation systems and should only be performed by trained staff Opera
18. case you have selected Anl 6 8 or 9 see the next step on how to proceed YA EZ For Anl 6 8 9 the control method for the humidifier control circuit now appears on the display The cooling coil and humidifier blink Set the con trol method in the same way as described for the temperature control cir cuit When selecting using the arrow keys a difference is made between humidifying and dehumidifying operation mode or just humidifying opera tion mode When the latter applies just the humidifier blinks on the display Display shows Comments Press the changeover key to change to operating level VV Ve Control levels 3 3 3 Control method You can choose between the following con trol methods for all systems Supply air temperature control Exhaust air temperature control Exhaust air temperature cascade control Room temperature control or Room temperature cascade control For systems Anl 8 and 9 air conditioning systems the control method needs to be set for the temperature control circuit as well as for the humidity control circuit For the humid ity circuit you can choose between Supply air humidity control Exhaust air humidity control Exhaust air humidity cascade control Room humidity control or 3 3 4 Parameter levels PA1 to PA9 In the parameter levels PA1 to PAY you can change parameters which have been enabled by the configuration The parame Operation Room humidity cascade c
19. following functions able Changeover key lets you change between the main levels operating and configuration levels Reset key resets all parameters in the parameter level to their default settings The set point can be increased or reduced with the aid of this switch Set point is reduced by 1 K per raster No change in set point Set point is increased by 1 K per raster Manual mode Operation 3 1 5 Arrow keys and enter key H qm SV Arrow keys let you scroll within lev M els select parameters and function blocks as well as increase and reduce values gt Enter key lets you activate levels parameters function blocks as well as confirm changed values 3 2 Manual mode N Note In manual mode the user can set the outputs anyway as required On selecting the man ual mode all limit temperatures and logical links ceased to be in force The user has ab solute control and takes on responsibility for interaction between all the outputs and the resulting consequences As soon as you set the mode switch to the you have changed the output variables over S switch position all operating states of the manual mode these states are maintained controller outputs are frozen i e the con until you exit the manual mode trol signals as well as the switching states of The system frost protection is guaranteed pro the binary outputs from automatic operation vided that the function block Co5 Fb15
20. greater than the value set under Tem perature difference to outdoor tempera ture The night purge can be set to start at 0 00 h at the earliest 4 00 h at the latest depending on the programmed system times of use The controller must be pro grammed to start the night purge at the latest possible point in time see example It is lim ited to two hours at the maximum If the room temperature falls below the room tem perature limit value determined under Finish night purge the night purge is ended early Example Start of time of use 7 00 h 2 Night purge from 4 00 h Start of time of use 5 00 h 2 Night purge from 3 00 h 5 5 6 Air quality control via the mixed air chamber Co5Fb18 21 PA The air quality control via the mixed air chamber function is available in the systems code numbers Anl 2 Anl 4 and Anl 8 pro vided an analog input for air quality L has been configured in the function block Co5Fb18 21 The control signal Y2 is formed from two control signals that exist internally and originate from the temperature control circuit and the air quality control cir cuit If the measured air quality falls below the value Air quality set point PAA the out door air rate determined until then just by the temperature control circuit is increased dependent on the control parameters Kp Air quality control and TN Air quality control PAA Under optimal conditions i e the Air quality set point is exceeded the o
21. interface to allow it to com municate with a control station A complete control system can be set up using an appro priate software for visualization and commu nication All functions and parameters of the serial interface are set in the Co level and PA level Two types of operation with a modem for a dedicated line or a dial up line are possible over the RS 232 C serial interface Serial interface o9 Operation with a dial up modem The controller only communicates with the control system when faults occur The controller works autonomously Fault alarms can be sent directly to the control station or over SMS text messaging to a mobile phone or over fax Operation with a dedicated line The controller and control system commu nicate with one another constantly over the bus Direct connection of a ventilation controller over RS 232 to a PC is also conceivable Operation with a dial up modem Fig 27 Network structure EBSI77EN 8 Serial interface Co9 Operation with a dial up modem 7 2 Operation with a dial up modem 7 2 1 Configuring the controller interface Carry out the following instructions depend ing on whether the ventilation controller is to send alarms when faults occur over a dial up Error message to a control station Define the following function blocks in CO9 1 Fb0 and Fb10 OFF 2 FbOO and FbO1 ON 3 Activate or deactivate Fb02 and Fb03 Error message to a mobile pho
22. outdoor tempera ture is greater PA2 which results in a characteristic curve for controlling the mixed air chamber The parameter Minimum outdoor air rate PA2 guarantees the required minimum proportion of the outdoor air The summer time operation see section 5 4 2 is always available with this operation mode EB 5177EN 63 Function descriptions Outputs 5 3 13 Heat recovery unit Y2 Co2 Fb21 The heat recovery unit is controlled from the The default setting is a heat recovery capac control output Y2 It is implemented by a PID ity of O to 100 which corresponds to a con control algorithm with the parameters trol signal from O to 10 V By activating the Kp HRU TN HRU and Ty HRU PA2 function block Co1 Fb21 the operating The operating action of the control output Y2 action is reversed HRU capacity O to 100 can be reversed then corresponds to 10 to O V Control signal Control variable Fig 20 Output signals for example in Anl 5 5 3 14 Humidifier Y2 YA Co4Fb21 The humidifier is controlled in system code Kp Humidifier TN Humidifier and Ty Humidi number Anl 6 from the control output Y2 and fier PA4 in system code numbers Anl 8 and 9 from The operating action of the humidifier can be YA The allocation of the control output Y2 to reversed The default setting is a humidifier the humidifier shown in the controller display capacity of O to 100 which corresponds to does not apply to s
23. p 51 and room humidity cas cade control on p 52 fan operation dependent on room hu midity on p 75 Humidity set point slave loop O to 100 rH Anl 6 8 9 with cascade control only See exhaust air or room humidity cascade control on p 52 Kp Humidity master loop 0 1 to 99 9 Anl 6 8 9 with cascade control only See exhaust air or room humidity cascade control on p 52 or See exhaust air or room humidity cascade control on p 52 E517 EN 117 Parameters Symbols with default settings Parameters set in PA5 level Parameter name range of values After pressing the enter key 0123 45 6 7 8 9 101112 13 4 15 16 17 18 19 2021 22 23 24 o 0123 45 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 START STOP PA nc gg VA Y AS e 0123 45 6 7 8 9 101112 13 14 15 16 17 18 19 20 21 22 23 24 PA 118 EB 5177 EN Supply air humidity minimum limit 0 to 100 rH Anl 6 8 9 with feedforwarding of supply air humidity See supply air humidity limit on p 75 Supply air humidity maximum limit O to 100 rH Anl 6 8 9 with feedforwarding of supply air humidity only See supply air humidity limit on p 75 Times of use In blocks or individual days 1 7 Monday Sunday 1 5 Monday Friday 6 7 Saturday and Sunday Two time schedules with ad justable star
24. separate times of use for the system in the parameter level PAS and for fan speed 2 in PAA The time schedules can be set in a block for Monday to Sunday 1 7 for Monday to Fri day 1 5 for Saturday and Sunday 6 7 or individually for each day 1 2 7 Mon Tues Sun You can enter two times of use within a day over START times and STOP times In this way the system can be switched on for example early in the morn ing first time of use and then again in the afternoon second time of use If you need just one continuous time of use period for example the ventilation system is to run from the morning until the evening set the same time for the start of the second time period and the end of the first time period The default settings for the times of use of the ventilation system is daily between 07 00 h to 12 00 h and between 12 00 h and 22 00 h The fan speed 2 is set to run daily between 10 00 h and 12 00 h and between 12 00 h and 15 00 h by default Refer to page 26 ff for detailed instructions on how to determine the times of use Note When 1 7 1 5 or 6 7 are selected the times of use for the days selected are re set to the default settings Therefore do not use this menu to check the programmed time schedules To check time schedules use just the menu for the individual days 1 2 7 in the PA4 or PAS level instead EB 5177EN 69 Function descriptions 5 5 Control functions 5 5 System star
25. signal limit for Y1 The Control signal limit for Y1 only has any effect when the system start up mode is active With the temperature sensor F4 the value set under Refurn air temperature maxi mum limit or Return air temperature max imum limit coordinate 1 is the set point for the warm up of the heating coil dur ing the start up phase Y1 varies corre sponding to the system deviation All other control outputs also the control output Y2 of an independent mixed air tem perature control usually do not run a con trol signal during the system start up phase The control output Y2 is enabled when the fans are enabled Before the control output Y3 cooling coil can be enabled the Pump advance running time for start up must be run through a second time In the supply air control circuit the Supply air temperature maximum limit is set at first as the set point Within five minutes this value is led linearly to the current supply air set point Note An active system start up mode is indi cated in the operating level by the symbol Xt blinking on the display During this operating phase neither the master loop set points nor the slave loop set points can be shown on the display appears at the corresponding places as well as at the times of non use on the display in the InF levels Control functions 5 5 2 Summer compensation PA5 The function is basically available for all sys tems with a cooling coil System code num
26. temperature F return air temperature HRU F6 supply air humidity EB 5177 EN ane ef AE LU PI rr TRE s s SS Thy LISTS OF TUNCHION DIOCKS Conti guration leve Fb Function WE Anl Comments 07 FZ mixed air or out going air temperature F7 exhaust air humid ity or room humidity O8 F8 potentiometer for temperature set point O9 F9 potentiometer for outdoor air rate F9 potentiometer for humidity set point 13 External demand for operation with BE13 see p 54 15 System frost protection with BET1 see p 77 16 Automatic summer time winter time changeover see p 69 EB 5177 EN Contiguration leve Function Night purge see p 73 02 of Tunctions affecting all sys Assignment of analog input AE 0 to10 V see p 54 Assignment of analog input AE2 0 to10 V see p 54 Assignment of analog Input AE3 O t010 V see p 54 Assignment of analog input AEA O to10 V see p 54 Locking settings see p 78 Lists of function blocks EB 5177 EN Lists of function blocks Appendix A 6 Configuration level Co for sensor initialization Fb Function WE Sensor selection see p 53 Sensor input F1 deviating from FbOO Sensor input F2 deviating from FbOO Sensor input F3 deviating from Fb00 Sensor input FA deviating from Fb00 Sensor input F5 deviati
27. temperature sensor and a return air temperature sensor exist it is possi ble to vary return air temperature limit as shown in Fig 26 Set the two coordinates for the following parameters in PAT for the upper variable limit of the return air temperature Return air temperature maximum limit co ordinate 1 Outdoor temperature coordinate 1 Return air temperature maximum limit co ordinate 2 Outdoor temperature coordinate 2 Outdoor temperature Additionally set the parameters Return air temperature minimum limit and Return air temperature limit factor The gray shaded area in Fig 26 indicates the permissible return air temperatures If the Return air temperature maximum limit is exceeded by the amount x the set point for cascade control the set point of the exhaust air or room temperature is reduced by the amount x multiplied with the Refurn air temperature limit factor 5 5 10 Supply air humidity limit Co5Fb06 Fb19 PA5 A humidity sensor must be configured for sup range within which the supply air humidity ply air humidity control Activate the function block Co5Fb06 or Co5Fb19 and select AE2 F Set the following parameters in the PAS level Supply air humidity minimum limit Supply air humidity maximum limit For exhaust air or room humidity control these two parameters restrict the humidity may vary If it leaves this range the devia tion is included in the system deviation to pre vent any further d
28. the system start up mode This causes the fans to be switched on after a delay if required External demand for fan speed 2 Co4 Fb03 BE10 BE7 You can select the function for external demand for fan speed 2 by activating Co4 Fb03 Following this you must determine whether the binary input BE10 or BE7 54 B5177 EN switches the fan to speed 2 The binary input performs then the following function If the system is running and a time of use for the fan speed 2 PA4 does not exist Inputs BE10 7 ON Speed 2 is switched on BE10 7 Off Speed 2 is switched off IF the system is switched off the binary input only allows a preliminary choice After the system is switched on either due to the time of use starting or due to an external demand for operation the following settings are possible Speed 1 switched on when BE10 7 OFF or Speed 2 switched on when Fan operation feedback Co4 FbO1 BE12 Activate the function block CoA Fb01 to allow the operation feedback of the fans to be evaluated with the binary input BE12 If the floating BE2 input makes contact after the fans are enabled and the delay time has elapsed i e the fans are not running the ventilation system is switched off The func tion block parameter Delay time can be set to max 180 seconds STOP blinks on the dis play when the controller is in the operating level First when the next time of use starts a new attempt to start is made auto
29. time of use appears in this example 07 00 h The clock and PA start to blink on the display Use the arrow keys to set when the first time of use period should start 6 00 h in the example Note You can only enter this time in 30 minute steps The time set is shown at the top of the display as black squares one square equals one hour Press the enter key to confirm the new starting time Now the time when the first time of use finishes appears on the display 12 00 h in the example Use the arrow keys to set when the first time of use period should finish 14 00 the example Control levels Press Display shows X QC wumumummamumununa LIT FOILI START Vl V2 Nes OW 203 4 05056 7809 TOM IA IS 12 ISNI 18 19720 21722023 24 m a m START STOP J m Gum ems l V until VAl V2 Nes Operation Comments Press the enter key to confirm the new finishing time Now the time when the second time of use starts appears on the display 14 00 h in the example which the same time when the first time of use period finishes Repeat the procedure to set the sec ond time of use to start at 19 00 h and finish at 23 00 h Follow the instructions in the gray box Then 1 5 appears on the display Note If you need just one continu ous time of use period set the same time for the start of the second time period and the end of the first time period Press the arrow key until the same
30. 0 C BEEN 0 we Only with supply air temperature control lt geen iod MAL NA NGS See p 48 Exhaust air temperature day set point O to 40 C Only with exhaust air temperature control or exhaust air tem perature cascade control See p 48 49 112 EB 5177 EN Parameters set in PA5 level Symbols with default settings Parameters Parameter name After pressing range of values the enter key 0123 45 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 Room temperature day set point O to 40 C With room temperature control or room temperature cascade control See p 50 p 75 Temperature set point slave loop O to 50 C Only with cascade control See p 49 50 Kp Temperature master loop 0 1 to 99 9 Only with cascade control See p 49 50 or See p 49 50 EBSI77EN 113 Parameters Symbols with default settings Parameters set in PA5 level Parameter name After pressing range of values the enter key 0123 45 6 7 8 9 10111213 14 15 16 17 18 19 20 21 22 23 24 114 EB 5177 EN Supply air temperature night set point O to 50 C Only with supply air temperature control See p 48 Exhaust air temperature night set po
31. 00 Q and 100 potenti ometer setting 2000 Q External correction of the humidity set point Co5 Fb09 In all air conditioning systems the humidity set point can be determined at the input F9 with a potentiometer For this activate the function block Co5 FbO9 The humidity set point is then determined between 20 rH 56 EB5177 EN potentiometer setting 1000 Q and 20 rH potentiometer setting 2000 Q provided the supply air limit of the supply air humidity control permits it Outputs 5 3 Outputs Function descriptions 5 3 1 Circulation pump control for the heating coil BA3 The circulation pump of the heating coil is controlled by the binary output BAS If the system goes into operation due to the time schedule of the ventilation with the system start up mode the circulating pump is switched on before the time of use starts at the time set under Pump advance running time for start up PA1 this limit value and the control signal Y1 is 0 for approximately three minutes the cir culation pump is switched off First when Y gt 0 26 it is activated again At the start of a time of non use system deac tivation the circulation pump of the heating coil is switched off after three minutes lag time provided there is no demand for opera Without the system start up mode the circula tion from the functions stand by monitoring tion pump is activated at the earliest when the time of use begins In
32. 1 222924 Press the changeover key The parameter level PA1 appears on the display VL until Press the arrow key until PA5 appears on the display 22 tB5177 EN Control levels Press Display shows P 9 ONES EQ 5 B OTM WH WGI WW IS IS 20 2 22 2524 1 31 LI m I G II YAl V2 Ne I L o V YA 12 VS Operation Comments Press the enter key The first parame ter of parameter level PAS is shown the time 10 24 h in this example Press the enter key to activate the time to change it The time and PA start to blink on the display Use the arrow keys to set the new time Press the enter key to confirm the new time The date now appears on the display EBSI77EN 23 Operation Press Display shows gt lt C O18253 455672 F8 2310 2 13 14 15 T IZ 18 Io 20 21 22 2324 Aor Vl WA iG 24 EB5177EN Control levels Comments Press the enter key to activate the date to change it The date and PA start to blink on the display Use the arrow keys to set the new date Press the enter key to confirm the new date The year now appears on the dis play 1999 in this example Press the enter key to activate the year to change it The year and PA start to blink on the display Control levels Operation Press Display shows Comments N Or VL C OMI 2 SANS F Rz ES Fo ONM 82113 1435 7318 o 201222 2322 Use the arrow keys to set the new cl EN MEM year Pre
33. 100 Assignment AE3 F2 Lower measuring range value MIN 40 C Upper measuring range value MAX 50 C F3 Lower measuring range value MIN 40 C Upper measuring range value MAX 50 C PS Lower measuring range value MIN 40 C Upper measuring range value MAX 50 C L Lower measuring range value MIN 0 Upper measuring range value MAX 100 Assignment AE4 F3 Lower measuring range value MIN 40 C Upper measuring range value MAX 50 C Lower measuring range value MIN 0 rH Upper measuring range value MAX 100 rH Lower measuring range value MIN 0 Upper measuring range value MAX 100 132 EB 5177 EN Info level InF5 ON OFF Customer data Options selected function block parameters Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PIC Pt 1000 Pt100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PIC Pr 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PIC Pt 1000 Pt
34. 100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PIC Pr 1000 Pr100 4 20 mA 0 20 mA Ni 1000 ni200 ntC PtC Pt 1000 Pr100 4 20 mA 0 20 mA ON OFF Options selected function block parameters Terminal Terminal EB 5177 EN 133 Customer data Info level InF5 ON OFF Options selected function block parameters SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL SIEIG FALL ON OFF Options selected function block parameters 134 EB 5177 EN Info level InF5 Parameter settings Parameters in PAT level Parameter Customer data Range of values Start up mode when the outdoor temp is lower O to10 Pump advance running time for start up O t015 Control signal limit for Y1 O to100 Pump ON when the outdoor temperature is lower 50 to10 Date when summer deactivation is enabled Date when summer deactivation is disabled Outdoor mean temperature 0 to 30 Return air temperature minimum limit O to 100 Return air temperature maximum limit O to 100 Return air temperature maximum limit Coordinate 1 O to 100 Outdoor temperature Coordinate 1 50 to 20 Return air temperature maximum limit Coordinate 2 O to 100 Outdoor temperature
35. 3 5 9 only See heat recovery unit on p 4 Appendix B 3 Parameters set in PA3 level Symbols with default settings Parameter name After pressing range of values the enter key 01234596 7 8 9 1011121314 15 16 17 18 19 20 21 22 23 24 Kp Cooling coil 0 1 to 99 9 TN Cooling coil 60 1 to 999 sec T 5 Ty Cooling coil to 999 sec Ke Anl 1 and 4 to 9 only AX ERIT bs Ya WE WS See cooling coil control output on p 4 EB5177EN 109 Parameters Parameters set in PM level Appendix B 4 Parameters set in PA4 level Symbols with default settings Parameter name After pressing range of values the enter key 012 34 56 7 8 9 101112 13 14 15 16 1 18 19202122 23 24 110 EB 5177 EN Air quality set point O to 100 Only with feedforwarding of air control See air quality control via mixed air chamber on p 73 fan speed dependent on the air quality on p 58 air volume dependent on the air quality on p 66 Differential gap of speed 2 gt 1 5 to 30 Only with feedforwarding of air control in systems with 2 speed fans See fan speed dependent on the air quality on p 58 K Air quality control 0 1 to 99 9 TN Air quality control 60 1 to 999 sec Only with feedforwarding of air control in Anl 2 4 8 all other systems with variable air volume control See Air quality c
36. 5 Exhaust air room humidity control ee ee 5l Exhaust air or room humidity cascade control 52 DUIS Gee eae Oe 2 2 ee S as RR EEG SUSPEN S 53 Setting the type of sensor Co6 FbOO Fb13 sss 53 Calibrating the sensor Co6 Fb23 llle 53 Analog inputs Co5 Fb18 Fb21 oll 54 Binary IDE 4 s Q u soe gt XR a Ql UR REO ARM PS Xu G S s 54 Analog inputs 2 een 56 OOUIDU S 4554 2 839 9 3 2x Sm amp Q PORE S W HES Go S 57 EBSI77EN 1 5 9 1 5 9 2 9 9 9 5 3 4 5 9 9 5 3 6 550 7 5 3 0 59 7 5 9 10 5 9 11 25 9 12 5 9 19 5 9 14 550 15 5 9 16 23 17 5 4 5 4 1 5 4 2 5 4 3 5 4 4 5 4 5 5 9 95 9 5 9 2 5 9 9 5 5 4 9 9 5 5 6 9 5 7 5 5 8 5 5 9 5 5 10 5 6 5 6 1 2 EB5177 EN Circulation pump control for the heating coil BA3 57 Enabling fan speed 1 BA4 ee 57 Enabling fan speed 2 Co4 FbO2 BA5 2 57 Enabling the cold storage Co3 Fb12 BA6 0 58 Binary output dependent on Y3 Co3 Fb12 BA6 58 Controlling the chiller Co3 Fb12 BA6 lll 59 Circulation pump control for the HRU BA7 59 On off output of heating coil Col Fb12 BA7 59 Three step output for heating coil Col Fb13 BA6 BA7 60 Fault alarm output BAT llle 60 Heating coil Y1 CoTFb21 2l 60 Mixed air chamber Y2 Co5 FbO7 Co2 Fb21 PA2 2 2
37. 9 The master loop has a P control response with adjustable Exhaust air humidity set point or Room humidity set point and Kp Humidity master loop PA5 The supply air control is implemented by a PID control algorithm with adjustable Humidity set point of the slave loop set point of the supply air humidity PAS The humidity control circuit can be used either just for humidifying or for humidifying and dehumidifying by involving the cooling coil in sequence to the humidifier The requirements of the humidity control circuit for dehumidifying and the temperature con trol circuit for cooling are converted inter 52 EB5177 EN nally into one common control signal Y3 for the cooling unit Each output can be adapted to the dynamics of the corresponding system components by means of the Kp TN and Ty control parameters PA3 PA4 that are adjustable The set point of the supply air humidity con trol circuit is shifted depending on the system deviation in the exhaust air or room humidity control circuit Each deviation in humidity by the amount x shifts the supply air humidity set point by the amount x multiplied by the parameter Kp Humidity master loop within the range Supply air humidity minimum limit and Sup ply air humidity maximum limit Example Exhaust air humidity set point 60 rH Current exhaust air humidity 54 rH Humidity set point of the slave loop 70 rH Kp Humidity master loop 2 5 Supply air humidity m
38. A7 BA7 Type 5257 6 Room Sensor with remote TROVIS 5177 control mw GND TD DTR DCD RD RTS 21 sr his sn Bs ho GND RS 232 AA Analog output ST Fan speed 1 AE Analog input ST2 Fan speed 2 BA Binary output Ig Room temperature BE Binary input W Temperature set point F Sensor or potentiometer input Y Control output GND Ground Fig 30 Electrical connection 02 EB 5177 EN 11 Technical data Technical data 10 configurable inputs for Pt 100 and PTC sensors Pt 100 and Pt 1000 sensors or binary messages e g system ON fans speed 2 fan operation feedback and frost protection 3 inputs F8 F9 and F10 just for potentiometers 1000 to 2000 Q or binary messages 4 inputs for O to 10 V Ri 18kQ for connecting active tempera ture humidity and air quality sensors temperature measuring range adjustable Outputs Analog outputs Binary outputs 4 continuous action outputs O to 10 V load gt 5 kQ 1 for fault indication floating max 50 V 100 mA 5 for pumps fans and chiller floating Loading capacity max 230 V AC 3 A cos y 0 6 min 230 V AC 10 mA 24 V AC 50 mA Interfaces RS 232 interface for connection to a modem LON free topology Operating voltage 230 V 10 15 75 power 8 VA Ambient temperature O to 40 C operation 20 to 60 C transportation and storage Degree of protection IP 40 corresponding to IEC 529 Class of protection
39. Automation System TROVIS 5100 Ventilation Controller TROVIS 5177 Mounting and Operating Instructions EB 5177 EN Firmware version 1 05 f EN Edition September 2000 C Contents Scope of the ventilation controller 5 Safety instructions llle eee OperGhOl e s sa Q z S Q OR S WR S Q eS 9 9 9 OF Y bodie ue 7 Operating controls on frontpanel 2 ee 7 Mode switch A ooo 7 Selection switch for manual operation B i n 8 Changeover key and reset key C D lll 8 Set point correction switch F 2 a 8 Arrow keys and enter key H 1 a aaa 0200000 9 Manual operation mode 2 aaa llle 9 Control levels a aa 12 Info levels 2 14 Changing system code number llle 16 Control method 4442544468864 oe eee ooo 9 335 19 Parameter levels PA toPA9 2 oen 19 Keycod s key v e w POA Pee 5 30 Configuration levels Co and function blocks Fb 31 Description of systems 0 eee eee ee eee 34 Function descriptions 2 2 2 ee ee s s s se s es 48 Control method 2 2 48 Supply air temperature control 2 a 48 Exhaust air temperature control a 48 Exhaust air temperature cascade control iin 49 Room temperature control 2 2l 50 Room temperature cascade control ee 50 Supply air humidity control llle
40. Control of cooling coil heating coil and humidifier humidifying and dehumidifying Two control circuits temperature and hu section 3 3 3 midity control Summer compensation see section 5 5 2 Humidifying or humidifying and dehu Fan operation 2 speed or O to 10 V see midifying operation configurable see section 5 3 3 EB 5177 EN 43 Description of systems Control levels d Ex ON Ext speed 2 gt u 7 t ii A A L f Lu k QD M Y A l BE12 BE13 BEIO BE7 BAA BAS BAA BAS Speed Speed 2 Fo Fl F8 RES F2 AE2 AE1 AE4 AE3 AE3 Specifications in parentheses can be Y3 YA selected as an alternative Fig 12 System code number 7 System code number 7 Cooling coil control Summer compensation see section 5 5 2 section 5 3 3 Fan operation 2 speed or O to 10 V see 44 EB 5177 EN Control levels Description of systems Vl Ext ON Ext speed 2 ma ev 4 Xx ru a ares Set point T Set pnt rH Z Toe 4 po ly l 8 ig e LAN Aig q D OXH OX OX I I d BE11 BE12 BE13 BEIO BE7 BA3 BA6 BAA BA5 Speed 1 Speed 2 F3 FA FI F FB F9 V FZ F5 F7 F2 AE2 AET AE2 AE4 AE3 AE4 AE3 Specifications in parentheses can be Y2 Yi Y3 Y4 selected as an alternative Fig 13 System code number 8 System code number 8 Control of mixed air c
41. Coordinate 2 50 to 40 Return air temperature limit factor Oto 10 Kp Heating coil Ty Heating coil Ty Heating coil Parameters in PA2 level Parameter 0 1 to 99 9 to 999 lo 999 Range values Mixed air temperature set point 10 to 30 Minimum outdoor air rate O to 100 Min outdoor air rate when outdoor temp is lower 10 to 50 100 outdoor air when the outdoor temp is greater 10 to 50 Summer time operation when the outdoor temp is greater 0 to 40 EB 5177 EN 135 Customer data Parameter Info level InF5 Range values Kp Mixed air chamber TN Mixed air chamber Ty Mixed air chamber oTi Ino 2999 tio 77 Heat recovery temperature 1 tolO Kp Heat recovery Ty Heat recovery Ty Heat recovery Parameters in PA3 level Parameter 0 1 to 99 9 1 to 999 o 999 Range volues Kp Cooling coil TN Cooling coil Ty Cooling coil Parameters in PAA level Parameter 0 1 to 99 9 1 to 999 lo 999 Range values Air quality set point O to 100 Differential gap of speed 2 gt 1 5 to 30 K Air quality control TN Air quality control O l lo 99 9 to 999 Kp Humidifier TN Humidifier Ty Humidifier 0 1 to 99 9 110 299 lc Times of use for fan speed 2 Start 1 Start 2 Monday Tuesday Wednesday Thursday Friday S
42. EN 125 Operating level Info level InF4 Appendix C 4 Info level InF4 Display shows Parameter After pressing the enter key 01234 5 6 7 8 9 10111213 14 15 16 17 18 19 20 21 22 23 24 Measured air quality Fans ON OFF or with two speed fans ON1 ON2 OFF or with speed controlled fans 0 100 Control signal output of humidifier 126 EB 5177 EN Info level InF5 Appendix C 5 Info level InF5 Display shows Operating level After pressing the enter key Parameter D OJ 2945 6 8 1M IS 14 151617 89202 222324 0 l E L LI EJ II Vfl VW Ys ae jode 012345267 8 9 101112131415 1617 18 19 20 21 22 23 24 EEE E Supply air temperature Set point s with supply air temperature control Depending on the system code number and the control method press the arrow key for further current values Observe the arrow on the dis play Binary inputs Binary outputs bin A Activated binary inputs are in same as binary inputs dicated by squares that appear under the number at the top of the display EB 5177 EN 127 Resistance values of temperature sensors Info level InF5 Appendix D Resistance values of temperature sensors Resistance thermometers with Pt 1000 measuring element Use the resistance values listed in the table for Pt 100 and multiply them by 10 Sensor for outdoor temperature Type 5227 for outside walls of bu
43. IRU oc Be eee ae ee arisa ee aa 77 Outdoor temperature sensor 77 78 Return air temperature sensor 78 Stand by monitoring 77 Syslem 77 Function block parameter CHGNGING S syz x5232355 553 32 Function blocks 31 EB 5177 EN 139 H Heat recovery 64 Healing coil 0 Humidifier _ 4 Installation Panel mounting 88 Wallmounting 88 K Keycode 30 L Locking settings 78 i9 ys 79 M Malfunctions 7 Manual operation 7 Mixed air chamber 6 Automatic reversal 6 Independent mixed air temperature con HG a sanee ve pouene ad eneo ness 62 Sequential operation 6 Modbus addressing 102 Modem dialing interval 84 121 N Night purge 00006 73 O On off output for heating coil 59 Operating action Control output Y2 Outdoor air rofe 61 Operating level Operation feedback gp PR 55 Outdoor air damper 57 Outdoor air rate Operating action 61 Outdoor mean temperature 68 Outdoor temperature overlON 79 Outdoor temperature sensor 70 Outdoor temperature controlled supply ai
44. M ESAME SE 30 112 150455 6 lZ 1812 20 2lF22 23 24 Press changeover key The parame ter level PA1 appears on the display or V until Press arrow keys until Anl appears on the display In addition to Anl the current system code number appears This example shows 1 16 EB 5177 EN Control levels Press Display shows Pd 012345267 8 9 1011121314 1516 17 18 19 20 21 22 23 24 t orb nnn TY 2 EY or V II Vl 12 VS Operation Comments Press enter key to activate the system code number to change it Anl starts to blink on the display Select the system code number you require using the arrow keys Every time you press the key the schemat ics depicting the system change on the display Confirm the new system code num ber with the enter key Anl no longer blinks on the display However the system elements start to blink as well as one or two arrows lo indicate the control method This example shows supply air control Use the arrow keys to select a differ ent control method Each control method is shown by the arrows on the right hand side in supply air duct exhaust air duct or both in the room or in the room and supply air duct this example shows room control EBSI77EN 17 Operation Press 18 EB5177 EN Control levels Display shows Comments 012345675 s11umansivimo2222 Press enter key to confirm the control method Col appears on the dis play If this is not the
45. MIN 600 sec Deactivate cooling at Y1 gt STOP 50 ON OFF Options selected function block parameters Delay time START 180 sec Speed 2 BA4 BA5 ON or BA4 OFF BA5 OFF Delay time 0 sec BE10 or BE7 Minimum air flow volume MIN AA 25 95 Factor of change Kp 0 0 only with cascade control ON OFF Options selected function block parameters Lon Lon2 13 EB 5177 EN Mixed air temperature control Sequential operation with outgoing air temperature Sequential operation with exhaust air temperature Outdoor temperature controlled mixed air chamber operation Customer data Info level InF5 ON OFF Options selected function block parameters Enable night purge START 24 C Finish night purge STOP 18 C Temperature difference to outdoor temperature 5 C Assignment AE Fl Lower measuring range value MIN 40 C Upper measuring range value MAX 50 C 3 Lower measuring range value MIN 40 C Upper measuring range value MAX 50 C L Lower measuring range value MIN 0 Upper measuring range value MAX 100 Assignment AE2 F3 Lower measuring range value MIN 40 C Upper measuring range value MAX 50 C F Lower measuring range value MIN 0 rH Upper measuring range value MAX 100 rH L Lower measuring range value MIN 0 Upper measuring range value MAX
46. PAT level Return air temperature minimum limit Return air temperature maximum limit Return air temperature limit factor These parameters limit the temperature range within which the return air temperature may vary in standard operation If the return air temperature moves towards these limits the set point is corrected for the cascade control the set point of the exhaust air or room temperature In the range Return air temperature minimum limit the set point is directly raised by the amount x multiplied by the Return air temperature limit factor for every amount x that the return air tempera ture falls below In the range Return air tem perature maximum limit the set point is 4 B5177 EN directly lowered by the amount x multiplied by the Return air temperature limit factor for every amount x that the return air tempera ture exceeds The supply air temperature limit function has priority Example Return air temperature minimum limit 20 C Return air temperature limit factor z20 Current return air temp 7 C Supply air temperalure set point 30 Supply air temperature maximum limit 40 C Supply air temperature set pointcalculated 36 C Control functions Function descriptions 5 5 9 Variable return air temperature maximum limit PA 1 Return air temperatur Coordinate 1 Coordinate 2 Minimum limit Fig 26 Variable return air temperature maximum limit IF an outdoor
47. Symbols with default settings Parameters set in PA5 level Parameter name After pressing range of values the enter key 0123 45 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 116 EB5177 EN or set point at an outdoor temperature of 32 C Exhaust air temperature See summer compensation on p 71 or set point at an outdoor temperature of 32 C Room temperature See summer compensation on p 71 Supply air humidity set point 0 to 100 rH Anl 8 9 only only with supply qir humidity control See supply air humidity control on p 51 Exhaust air humidity set point O to 100 rH Anl 6 8 9 only Only with exhaust air humidity control or exhaust air humid ity cascade control See exhaust air humidity control and exhaust air humidity cascade control on p 31 Parameters set in PA5 level Symbols with default settings Parameters Parameter name After pressing range of values the enter key 01234567 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 Room humidity set point O to 100 rH Only Anl 6 8 9 with room humidity control or room humid ity cascade control or fan operation dependent on room hu midity See room humidity control on
48. a PID control algorithm with adjustable Exhaust air humidity set point or Room humidity set point PAS The humidity control circuit can be used just for humidifying or for humidifying and dehu midifying depending on the control method In humidifying and dehumidifying mode the cooling coil is controlled in sequence to the humidifier The requirements of the humidity control circuit for dehumidifying and the tem perature control circuit for cooling are con verted internally into a common control sig nal Y3 for the cooling coil Each output can be adapted to the dynamics of the corre sponding system components by means of the Kp TN and Ty control parameters PA3 PAA that are adjustable A manual set point correction has an unre stricted effect on the control by the shifting the set point EB5177 EN 5 Function descriptions Control method 5 1 8 Exhaust air or room humidity cascade control The exhaust air or room humidity cascade control is only selectable for system code numbers 6 8 and 9 The sensor input F7 is the control variable input for exhaust air or room humidity and the sensor input F6 is the control variable input for supply air humidity by default Alternatively you can also change to the ana log input AEA for the exhaust air or room humidity by selecting F7 in function block Co5 Fb21 as well as change to the analog input AE2 for the supply air humidity by selecting F in the function block Co5 Fb1
49. al lines that are routed EB 5177 EN inlet or outlet using a large surface con tact Connect the central grounding point using a cable with 2 10 mm on the shortest route to the PE grounding con ductor Equip the inductances in the control cabi net e g contactor coils with suitable in terference suppressors RC elements Control cabinet elements with high field strengths e g transformers or frequency converters should be shielded by means of separators that have good chassis ground outside buildings must have current carry ing capacity and must be grounded on both sides The surge diverters must be installed ot the control cabinet inlet Connecting the controller Connect the controller as shown in Fig 30 It is important to observe the system code num ber and the configuration Open the casing to connect the wiring as described in sec Connecting sensors Connect cables with a minimum cross section of 2 x 0 5 mm to the terminal strip of the Connecting actuators and pumps Guide cables suitable for damp locations with a minimum cross section of 1 5 mm to the terminal strip of the controller according Electrical connection tion 9 Make holes to feed through cables at the marked locations on the top bottom or back of the rear casing Insert the enclosed grommets casing rear panel to the wiring plan EBSI77EN 9 Electrical connection BA3 BA3 BA4 BA4 BA5 BA5 BA BA B
50. al status again the set point correction is reset For analysis of condensation detection acti vate Co3 Fb01 Following this select either binary input BETO or BE7 for this function Should only one of the inputs be available 5 2 5 Analog inputs Inputs for selection the input BE10 F10 or BE7 F7 is already in use for another function Addi tionally determine whether the controller is to react to a make contact setting StEIG or to a break contact setting FALL External temperature set point correction Co5 Fb08 The set point can be changed either at the set point correction switch F or at a potentiome ler connected to input F8 Activate the func tion block Co5 Fb08 for the F8 input A correction is possible in the range from 5 K potentiometer setting 1000 Q to 5 K potentiometer setting 2000 Q provided the supply air temperature limit determined by the supply air temperature control permits it The potentiometer F8 and the set point correc tion switch both have an effect on the temper ature set points The set point is changed at the correction switch in 1 K steps from one to the next switch position External setting of the outdoor air rate Co5 Fb09 PA2 The outdoor air rate can be determined at the input F9 with a potentiometer For this activate the function block Co5 Fb09 The out door air rate is then determined between the value Minimum outdoor air rate PA2 poten tiometer setting 10
51. ameters set in PAT level Parameter name range of values After pressing the enter key 01234567 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 START PA START STOP PA 104 EB 5177 EN Pump ON when the outdoor temperature is lower 50 to 10 C Only for Anl 0 to 6 8 9 with feedforwarding of outdoor temperature See stand by monitoring on p 77 stand by control on p 78 Date when summer deactivation is enabled Anl 0 to 9 For Anl 7 only when Fb10 ON See summer deactivation on p 68 and night purge on p 73 Date when summer deactivation is disabled See summer deactivation on p 68 and night purge on p 73 Outdoor mean temperature O to 30 C See summer deactivation on p 68 and night purge on p 73 Parameters set in PAT level Symbols with default settings Parameters Parameter name range of values After pressing the enter key 0123 4 5 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 START PA e ei Wl W2 X63 0123 45 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 START Return air temperature minimum limit O to 100 C Only for Anl O to 6 8 9 with return air sensor See return air temperature limit on p 74 and stand by control on p 78 Return air temperature maximu
52. at recovery unit designed as a Fan operation 2 speed or 0 to 10 V see cross flow heat exchanger section 5 3 3 Frost protection for HRU see section 5 7 1 EB 5177EN 39 Description of systems Control levels ir 5 JL T Ex ON Ext speed 2 Tul OX X I I BE11 BE12 BE13 BE1O BE7 BA3 BA6 BA4 BA5 Speed Speed 2 F3 F7 F4 FI F8 F9 F5 F2 AE2 AE1 AEA AE3 AE3 Specifications in parentheses can Y2 y Y3 Y4 be selected as an alternative Fig 8 System code number 4 System code number 4 Control of mixed air chamber heating coil and cooling coil Summer compensation see section 5 5 2 temperature control see section 5 3 12 Summer time operations section 5 4 2 Automatic reversal of operating action for Sequence operation of heat mixed air chamber see section 5 3 12 ing damper cooling or sequence opera Fan operation 2 speed or 0 to 10 V see tion of heating cooling and mixed air section 5 3 3 40 EB5177 EN Control levels Antifreeze required in HRU BE1 1 BA4 BA7 BA3 BAS F FA AE2 M2 YI Y3 Fig 9 System code number 5 BE12 Description of systems Ex ON Ext speed 2 BE13 BEIO BE7 BAA BA5 Speed 1 Speed 2 F F8 F5 2 AE1 AE4 AE3 AE3 Specifications in parentheses can be YA selected as an alternative System code number 5 Control of heat recovery unit HRU heating coil and cooling coil S
53. ata function Rated operation 11 Cooling coil blocks 7 Stand by operation 12 Humidifier 2 Public holidays reduced operation blinking 13 Control outputs 3 Vacations 8 Frost protection operation 14 Supply air temperature 4 Mixed air chamber 9 Heat recovery humidity 5 Error 10 Heating coil l9 Room temperature humidity Front view Front view o TROVIS 5177 DH 955 B8 eno Ag J FETTE D 4 Yi Y2 Y3 F HCE A Mode switch C Changeover key F Set point correction switch B Selection switch for manual D Reset key G Display operation E Socket for memory module H Enter keys SAMSON AG MESS UND REGELTECHNIK Weism llerstraBe 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Phone 49 69 4009 1507 Internet http www samson de EB 5177 EN S 2000 09
54. ating the sensor Co Fb23 The values measured by all the connected sensors can be calibrated within a small toler ance range To calibrate the sensors pro ceed as follows Activate Fb23 in Co level This is only possible after the key code has been entered Use the arrow key to select the func tion block for the sensor you want to calibrate e g Fb03 for outdoor sensor F3 Note Fb number matches the input numbers see Fig 30 p 92 Press enter key twice The tempera ture appears on the display Press the enter key The indicated a twice temperature starts to blink Use arrow keys to set new value i or gt Press enter key to confirm this volue End appears on the display Press the enter key The next Fb appears on the display If required calibrate further sensor inputs Do not forget to deactivate Fb23 when you have finished calibrating all the sensors Note Values from the sensor calibration are not reset to default settings after a reset or after the system code number has been changed EB 5177 EN 53 Function descriptions 5 2 3 Analog inputs Co5 Fb18 Fb21 You can assign the four analog inputs AE1 to AEA to temperature sensors humidity sensors or an air quality sensor Refer to the system diagrams in section 4 for possible assign ments They are listed underneath the resis tance sensors in parentheses If you want to use analog inputs activate the correspond ing function blo
55. aturday Sunday 136 EB 5177 EN In blocks or individual days two times of use with start and stop times Info level InF5 Parameters in PA5 level Parameter Customer data Range of values Supply air temperature day set point O to 50 Exhaust air temperature day set point 0 to 40 Room temperature day set point 0 to 40 Temperature set point slave loop O to 50 Kp Temperature master loop 0 1 to 99 9 Supply air temperature night set point O to 50 Exhaust air temperature night set point 0 to 40 Room temperature night set point 0 to 40 Supply air temperature minimum limit O to 50 Supply air temperature maximum limit O to 50 Sustained room temperature 0 to 20 Summer compensation when the outdoor temperature is greater 50 to 40 Set point at an outdoor temp of 32 C 0 to 40 Supply air humidity set point O to 100 Exhaust air humidity set point O to 100 Room humidity set point O to 100 Humidity set point slave loop O to 100 Kp Humidity master loop O llo 229 Supply air humidity minimum limit O to 100 Supply air humidity maximum limit O to 100 Times of use Monday Tuesday Wednesday Thursday Friday Saturday Sunday In blocks or individual days two times of use with start and stop times
56. aximum limit Humidity set point of the slave loop calculated 80 rH 80 rH Inputs 5 2 Inputs The assignment of the inputs depends on the system code number and the control method See section 4 for this assignment in the sys tem diagrams Alternatively you can also assign analog inputs to the resistance sen sors The four analog inputs O to 10 V are suitable for active temperature humidity and Function descriptions air quality sensors Sensors which are required for the selected control methods are always activated You must determined separately all the other sen sors as well as the functions of the binary inputs by configuring them 5 2 1 Setting the type of sensor Co FbOO Fb13 The ventilation controller can process signals either from Pt 100 sensors and PTC sensors or from Pt 100 sensors and Pt 1000 sensors Select which type of sensor is to used in func tion block FbOO Fb00 OFF means Pr 100 and PTC sensors are used FbOO ON means Pt 100 and Pt 1000 sensors are used IF some of the sensor inputs are not the same as the assignment set in FbOO the function blocks 01 to 13 for the sensor inputs F1 to F13 must be activated see Fig 30 on page 92 On activating the sensor inputs the type of sensor must be selected The fol lowing appears n1000 Ni1000 ni200 ntC PIC P1000 Pt 1000 Pr100 4 20 mA 0 20 mA Connect 50 Q resistance in parallel for a cur rent signal 5 2 2 Calibr
57. ck Fb18 Fb21 before assign ing the sensors The following options appear on the display Supply air temperature F1 Exhaust air temperature F2 AE1F1 AE3F2 5 2 4 Binary inputs Inputs Outdoor temperature F3 AE2F3 Room temperature F5 AE3F5 Supply air humidity F AE2F6 Exhaust air or room humidity F7 AEAF7 Air quality L AE1L After assigning an analog input the lower range MIN and upper range MAX of the measuring range appear on the display You can change both of these values Refer to the configuration table in Appendix A on page 99 for the measuring ranges External demand for operation Co5 Fb13 BE13 BE10 If you activate the function block Co5 Fb13 you can start the operation of the ventilation system with the binary input BE13 When the mode switch is switched to the following opplies BE13 OFF Ventilation system operation according to the times of use BE13 ON Ventilation system opera tion however the system cannot be switched off during a time of use period by BE13 OFF If the binary output BE10 is not used for any other purposes you can switch off the system even during a time of use over BE10 ON When the mode switch is switched to or to the following applies BE13 OFF Ventilation system not in op eration BE13 ON Ventilation system operation however only during a time of use set for automatic operation The system starts up if necessary taking into account
58. code numbers Anl 6 8 and 9 The sensor input F is the control variable input by default Alternatively you can also change to the analog input AE2 by selecting F in function block Co5 Fb19 The supply air humidity is controlled by a PID control algorithm with an adjustable Supply air humidity day set point or Supply air humidity day night point PAS The humidity control circuit can be used for just humidifying or for humidifying and dehu midifying depending on the control method In humidifying and dehumidifying mode the Function descriptions cooling coil is controlled in sequence to the humidifier The requirements of the humidity control circuit for dehumidifying and the tem perature control circuit for cooling are con verted internally into a common control sig nal Y3 for the cooling coil Each output can be adapted to the dynamics of the corre sponding system components by means of the Kp TN and Ty control parameters PA3 PAA that are adjustable A manual set point correction has an unre stricted effect on the control by the shifting the set point 5 1 7 Exhaust air room humidity control The exhaust air or room humidity control is only selectable for system code numbers 6 8 and 9 The sensor input F7 is the control variable input by default Alternatively you can also change to the analog input AEA by selecting F7 in function block Co5 Fb21 The exhaust air or room humidity control is implemented as
59. cription of systems RENE Gf ama Sgi A Ext ON Ext speed 2 r7 77H r PEIRE mai S o o t T m ig q D 0X I BE11 BE12 BEI3 BETO BE7 BA4 BA3 BA4 BA5 Speed Speed 2 F3 FA FI F8 NES F2 AE2 AE1 AEA AE3 AE3 Y1 Y4 Specifications in parentheses can be selected as an alternative Fig 3 System code number 0 System code number 0 Heating coil control Outdoor temperature controlled supply Fan operation 2 speed or 0 to 10 V see air control see section 5 5 3 section 5 3 3 EB 5177 EN 35 Description of systems Control levels 2 VA Hxt ON Ext speed 2 mm 35 Inv NZ c EE TIMERE Lt FL i re Ox X I I BE11 BE12 BEI3 BEIO BE7 BA4 BA3 BAS BA4 BA5 Speed 1 Speed 2 F3 FA FI F8 F5 F2 AE2 AE1 AEA AE3 AE3 Specifications in parentheses can YI YS YA be selected as an alternative Fig 4 System code number 1 System code number 1 Heating coil and cooling coil control Summer compensation see section 5 5 2 Fan operation 2 speed or 0 to 10 V see Sequence operation of heating cooling section 5 3 3 or overlapping operation see section 9 9 0 36 EB5177 EN Control levels Fig 5 System code number 2 Description of systems BE11 BE12 BE13 BE1O BE7 BA3 BA4 BA5 Speed 1 Speed 2 ES F7 FA Fl F8 F F5 p AE2 AE1 AEA AE3 AE3 Specifications in parentheses can Y2 YI YA be sele
60. cted as an alternative System code number 2 Mixed air chamber and heating coil control Summer time operation see section 5 4 2 Sequence operation of heating dampers or mixed air temperature control see sec Hon 5 3 12 Automatic reversal of operating action for mixed air chamber see section 5 3 12 Fan operation 2 speed or 0 to 10 V see section 5 3 3 EB 5177 EN 37 Description of systems Control levels Cis Antifreeze required HJ Q p Ext ON Ext speed 2 in HRU De m _ Q Y a4 D OX I BE11 BE12 BE13 BELO BE7 BAA BA7 BA3 BAA BA5 Speed 1 Speed 2 FS F F4 Fl F8 F5 Ir AE2 AE1 AEA AE3 AE3 Specifications in parentheses can Y2 Y YA be selected as an alternative Fig 6 System code number 3 System code number 3 Heat recovery unit HRU and heating coil control Frost protection for HRU see section Fan operation 2 speed or 0 to 10 V see 541 section 5 3 3 JO EB5177EN Control levels Description of systems LN JF iet E s H xt ON Ext speed 2 PV VA LLL dui Wi f OX I BE11 BE12 BEI BETO BE7 BAA BA3 BAA BA5 Speed 1 Speed 2 F3 F FA F1 F8 F5 F2 AE2 AE1 AE4 AE3 AE3 Specifications in parentheses can Y2 y Y4 be selected as an alternative Fig 7 System code number 3 with cross flow heat exchanger System code number 3 Heat recovery unit HRU and heating coil control He
61. d This display also contains two other pieces of 5 4 2 Summer time operation PA The summer time operation function runs in all systems that have a mixed air chamber and outdoor temperature feedforward Anl 2 Anl 4 Anl 8 The system is operated at outdoor temperatures that exceed a set limit value with a minimum outdoor air rate to avoid operation with 100 outdoor air Set the following parameter in PA2 for this function 68 EB5177 EN Time functions information the bar graph beneath the num ber O to 24 at the top of the LCD indicates the number of outdoor temperatures which have already been measured and used to result in the daily mean outdoor temperature currently shown The figure 0 or 1 in front of the daily mean outdoor temperature on the display indicated whether the summer deactivation function is currently active 1 or inactive 2 If the summer deactivation is active the heat ing coil is switched off at 22 00 h for the next 24 hours i e control signal Y1 0 and pump output BA3 OFF If the outdoor temperature falls below the set limit value the heating coil control is enabled from 22 00 h for the next 24 hours provid ing this is required according to the times of use or by the mode switch Summer time operation when the outdoor temperature is greater outdoor tempera ture limit for summer time operation Summer time operation can also be used in systems with cooling coil in which it is b
62. d line bus operation 7 4 Operation with a dedicated line bus operation 7 4 1 Bus connection to RS 485 interface A converter cable SAMSON 1400 7308 is required to integrate the ventilation converter in a four wire bus It converts the RS 232 sig nal from the controller into a RS 485 signal for the bus as well as vice versa Fig 27 shows the bus topology The bus line connects all the control devices through an open ring The four wire bus is connected to the control station at the end of bus line using 7 4 2 Configuring the interface The following settings must be made before the controller is ready for bus operation 1 Activate the function block FbOO in Co9 06 EB5177 EN a RS 485 RS 232 converter e g TROVIS 5484 The maximum cable length is 1 200 m In this segment up to 32 devices may be con nected If you wish to use more devices or bridge greater distances make sure repeat ers e g TROVIS 5482 are installed to repli cate the signal On the whole max 246 par ticipants can be connected in line 2 Deactivate all other function blocks 3 Set the parameters for station number and baud rate in PAY Data transfer between controller and memory module Memory module 8 Memory module The memory module allows configuration data and parameter settings to be trans ferred from the controller to the PC and vice versa Like wise all the settings of one controller can be copied and transferred to a
63. display as shown here appears vacations You have now exited the menu for times of use time schedules Press the changeover key to exit the configuration level and return to the operating level EBSI77EN 29 Operation Control levels 3 3 5 Key code N Caution The key code may only be used by trained personnel Several functions are protected against unin page 143 Tear out this page or blank out tentional and unauthorized access These the key code to prevent its unauthorized use functions can only be altered when the key If you are prompted to enter the key code code is known The key code is written on proceed as follows Press Display shows Comments O 12 3 4576782 011213 415 6 lZ 18 19 2021222324 If the same display as shown here appears you are being prompted to enter the key code VA V2 NS N Or VL OILS 3040526 712809 TOI 29S 141516 15 08 19 20 21 22 23 244 Use the arrow keys to enter the key code see page 143 Note The longer you press an arrow key the quicker the numbers change on the display Ya V2 NS gt Press the enter key to confirm the key code When the correct key code has been entered the function block you want to change starts then to blink on the display Note The key code remains active three minutes after the last key has been pressed 30 EB5177 EN Control levels Operation 3 3 6 Configuration levels Co and function blocks Fb J 23 2 22 Z 2 01 12
64. e air quality Activate the function block Co4 Fb02 for the operation of the two speed fans You can then choose between two relay switching options for demanding speed 2 A combina tion of one or two squares appears at the top of the display below the right side of the num EB5177 EN 57 Function descriptions bers 4 or 5 for BAA BAS BA4 BA5 ON or BA4 OFF BA5 ON If the outdoor air outgoing air damper is additionally to be controlled over BA4 it will be necessary that BA4 also remains activated when fan speed 2 is in operation Following this you are prompted to set a Delay time up to 60 seconds After fan speed Outputs 2 has been demanded when the system is on stand by first fan speed 1 is enabled speed 2 is only enabled after the Delay time has elapsed When the speed 2 is switched back to speed 1 the fans are switched off speed 1 is only enabled after the Delay time has elapsed The Delay time is still taken into account even if the fans are switched on in the manual mode Fan speed dependent on the air quality Co5 Fb18 21 PA4 Configure an analog input for processing the air quality L in function block Co5 Fb18 19 20 or 21as well as set the following parame ter in PAA Air quality set point Differential gap of speed 2 1 IF the air quality falls below the Air quality set point the operation of fan speed 2 is demanded The fans are switched back to fan speed 1 when the air quality ha
65. e broad range of modems available on the market and the different terms used for commands refer to the operating manual of the modem used for further settings When operating with a dial up modem data cannot be written to the controller at first after connection has been established It is first possible after the correct key number has been sent to holding register 70 The following settings are often used in QO Result codes on numerous modems CO Data compression off EO Echo off ANT Buffer switched off X3 Do not wait for dial tone B9600 Baud rate 9600 V Result code in text format WO Standard connect messages The following parameters are set in PA level Refer to Appendix B for a list of value ranges and default settings Station number The stations number is the controller s system network and can be set in PA9 address It can only be allocated once in a Baud rate BAUD The baud rate indicates the transmission rate the same as the transfer rate between the con and can be set in the parameter level PAQ trol station and the controller The baud rate Within a bus system the transmission rate is within the system must always be the same Cyclic initialization 1 This parameter defines the period of time for The command is not issued during dial up or a cyclical issue of the initialization command when connected ATZ When the ATZ command is issued An example of initialization of a modem wi
66. e is controlled by a PID control algo rithm with adjustable Temperature set point of the slave loop set point of supply air temperature control Depending on the system code number the temperature control circuit has between 1 and 3 sequence outputs that are adapted to the dynamics of the corresponding system components by means of the Kp TN and Ty 50 EB5177 EN control parameters which you can change in the parameter level PA1 PA2 PA3 The parameters Supply air temperature minimum limit and Supply air temperature maximum limit restrict the set point shift which arises when the room temperature control circuit takes influence on the supply air temperature control circuit each deviation in room tem perature by the amount x causes a shift of the supply air temperature set point by the amount x multiplied by the parameter Kp Temperature master loop Example Room temperature set point B2 C Current room temperature 20 C Supply air temperature set point 30 C Kp Temperature master loop 2 5 Supply air temperature minimum limit zd Supply air temperature set point calculated 35 C Shifts in the set point which are caused by manudl set point correction return air tem Control method perature limit summer compensation or by condensation detection have unrestricted effects on the room temperature set point 5 1 6 Supply air humidity control The supply air humidity control is only selectable for system
67. e p 85 BE11 in status register FSR see p 85 BE12 in status register FSR see p 85 BE13 in status register FSR see p 85 Appendix A 9 Configuration level Co9 for Modbus communication Fb Function WE Anl Comments Modbus Modem dialing procedure Block dialing Modbus addressing SMS error message to a mo bile phone SMS dialing procedure Error message to a fax Fax dialing procedure l SMS short message service 102 EB 5177 EN Parameters set in PAT level Appendix B Parameters Parameters These parameters are set in levels PA1 to PAY Appendix B 1 Parameters set in PAT level Symbols with default settings Parameter name After pressing range of values the enter key 0123456 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 START m F e f START J 1 System start up mode when the outdoor temperature is lower O to10 C Only for Anl 0 to 6 8 9 with outdoor temperature feedforwarding See outdoor temperature dependent system start up mode p Z0 Pump advance running time for start up O t015 min Anl 0 to 6 8 9 See system start up mode on p 70 Control signal limit for Y1 O to 100 Anl 0 to 6 8 9 See system start up mode on p 70 EB5I77EN 103 Parameters Symbols with default settings Par
68. e pressed to confirm the setting 32 EB 5177 EN Control levels number gt Press the enter key to access the Co level you want to change The first function block Fb00 appears on the display pears underneath the function block number at the top of the display Fb is deactivated Besides this either the next function block or a function block parameter appears on the display Function block parameters are immediately active Proceeds as follows or Usethe arrow keys to set a new value Press the enter key to confirm the new value Following this either the next function block parameter the next func tion block or End appears on the display If necessary change further function blocks and their parameters Alternatively exit the Co level or configuration level as described below or gt If you have reached End on the dis play press the enter key The next Co level or the next function block appears on the display Control levels Operation Exiting the configuration level 9 Press the changeover key to return to the operating level Note The controller automatically returns to the operating level two minutes after the last key has been pressed EB 5177 EN 33 Description of systems 4 Description of systems The ventilation controller can be used to con trol ten different types of systems which are assigned system code numbers in the control ler The system code number Anl is fixed in the config
69. e the function block FbOO in Co7 to switch on LON communication 2 Allocate a node address in PAZ A subnet is automatically assigned to each type of controller e g 5174 see table below Assign each controller a node address 1 to 20 in the parameter level PA7 making sure a node address is only assigned once within a subnet But for example it would be permissible to assign the node address 9 for a TROVIS 5174 Controller as well as for a TROVIS 5179 Controller since they belong to dif ferent subnets Configuring the LON interface Controller type Subnet Node address 5174 4 to 20 5177 7 to 20 21 9 9 to 20 Primary controller value to the LON bus It is possible to define that a controller send all values or each differ ent value is sent from a separate controller Data are transmitted every 4 minutes over the LON bus except when the temperature values changes significantly Ata gt 0 5 K Atv gt 2 K which are sent immediately The values from the LON bus remain valid in the controllers for a maximum of 10 minutes before error routines become active If the controller issuing the time fails the time runs on locally in all the other controllers You can optionally determine the following functions in Co7 You can define a controller to function as the primary controller in a control system this is however not absolutely necessary The primary controller receives the re quest for t
70. ect F2 in the function block Co5 Fb20 for AE3 Control method The exhaust air temperature is controlled by a PID algorithm with an adjustable Exhaust air temperature set point PAS Depending on the system code number the temperature control circuit has between 1 and 3 sequence outputs that are adapted to the dynamics of the corresponding system Function descriptions components by means of the Kp TN and Ty control parameters which can be set in the parameter level PA1 PA2 PA3 Functions such as return air temperature limit summer compensation manual set point correction or condensation detection can shift the set point 5 1 3 Exhaust air temperature cascade control The sensor input F2 is the control variable input for the exhaust air temperature and the sensor input F1 is the control variable input for the supply air temperature by default Alternatively you can also change to the ana log input AE1 for the supply air temperature by selecting F1 in function block Co5 Fb18 as well as change to the analog input AE3 for the exhaust air temperature by selecting F2 in the function block Co5 Fb20 The exhaust air temperature control circuit is implemented as a P control circuit with adjust able Exhaust air temperature day set point Exhaust air temperature night set point and Kp Temperature master loop PA5 The sup ply air temperature is controlled by a PID con trol algorithm with adjustable Supply air tem peratu
71. emperature deviation Fig 18 Different output signals e g in Anl 4 sponds to a control signal of 0 to 10 V Acti vate function block Co2 Fb21 to reverse the operating action the outdoor air rate O to 100 then corresponds to 10 to 0 V On feedforwarding the outdoor temperature the summer time operation function is taken into account see section 5 4 2 By additionally feedforwarding the exhaust air temperature the automatic reversal of the operating action takes effect I there is a con siderable difference in temperature between exhaust air and extract air due to the heat C variable With feedforwarding of outdoor temperature or exhaust air temperature tA lt t Ab tA gt Tt Ab System C variable Outdoor temperature deviation given off by the fan the extract air tempera ture can also be selected as the measured variable in place of the exhaust air tempera ture Activate for this Co5 Fb07 and then select SEQ If the operating action of the control output Y2 is automatically reversed due to changing temperatures while the control is in the sequence range Y1 or Y3 the mixed air chamber is then reversed with a constant changing rate of 15 per minute Independent mixed air temperature control Fig 18 You can achieve the independent mixed air temperature control by activating Co5 FbO7 and then selecting mixed air sensor The inde 62 EB5177 EN pendent mixed air temperature control is
72. entification 84 Status register 85 Summer compensation 7 Summer deactivation 68 Summer time operation 68 Supply air humidity control 5 Supply air humidity limit 3 Supply air temperature control 48 Supply air temperature limit 74 Surge protection measures Sustained room temperature 72 Symbols on the display 147 System code number CHONGING 2 ato sa cay pa a pachas SA 1 System frost protection 77 System start up mode 70 Dependent on outdoor temperature 70 Return air temperature controlled 70 T Technical data 93 94 Telephone number Alternative recipient 84 Three step output for heating coil 60 Time overlON 79 setting 22 V NGCHHORS RM 69 Variable return air temperature maximum limit EB 5177 EN 14 Key code 1732 EB 5177 EN 143 144 EB 5177 EN EB 5177 EN 145 146 EB 5177 EN Important symbols on the display Important symbols on the display 2 2 S A 10111213 14 15 16 17 18 192 21 22 29 2A i VT IL LILI 16 4 15 14 9 13 7 8 9 10 11 12 l Time d
73. ess the changeover key with a pointed object to access the config 3 Change the function block as described in the section on Changing function blocks 4 Exit the configuration level as described in section on Exiting the configuration level uration level PAT appears on the display EB 5177EN 3 Operation ay Press an arrow key until the or required Co level Col to Co9 appears on the display Note You can see at the top of the display which function blocks Fb are activated squares located under the right hand side of the Changing function blocks Access the Co level as described Y Use the arrow key to find the func tion block you want to change gt Press the enter key to access the function block Fbxx now appears on the display and can be changed Note If 0000 is shown on the display this is a prompt for entering the key code see page 30 Press the upward arrow key to acti I vate the function block Press the downward arrow key to Y deactivate the function block gt Press the enter key to confirm the setting Depending on the function block setting a square appears underneath the function block number at the top of the display Fb is activated or a square disap Exiting a Co level N Press both arrow keys simulta both neously The next Co level or PA level appears on the display Note Display should not start blinking A blinking display requires first the enter key to b
74. eters set in PA2 level Symbols with default settings Parameter name After pressing range of values the enter key 012345678 9 11112191415 161718192021 222324 OO outdoor air when the outdoor temperature is greater 10 to 50 C Anl 2 4 8 with outdoor temperature controlled mixed air chamber only See outdoor temperature controlled mixed air chamber on p 63 Summer time operation when the outdoor temperature is greater O to 40 C Anl 2 4 8 with feedforwarding of outdoor temperature only See summer time operation on p 68 Kp Mixed air chamber 0 1 to 99 9 Ty Mixed air chamber 60 1 to 999 sec Ty Mixed air chamber to 999 sec Anl 2 4 8 only however not with outdoor tempera ture controlled mixed air chamber See mixed air chamber on p 61 01234567 8 9 101112131415 16 17 18192021 222324 Heat recovery minimum temperature Cc 1 to 10 C MIN L1 um PA Anl 3 5 with F only See frost protection HRU on p 77 108 EB 5177 EN Parameters set in PA3 level Parameters Symbols with default settings Parameter name After pressing range of values the enter key 01234 56 7 8 9 101112 1314 15 16 17 18 19 20 21 22 23 24 Kp Heat recovery unil 0 1 to 99 9 TN Heat recovery unit 60 1 to 999 sec Ty Heat recovery unit to 999 sec Kp Tn Ty Anl
75. etter to prevent operation with just outdoor air at high outdoor temperatures for reasons of energy efficiency Time functions Function descriptions 5 4 3 Automatic summer time winter time changeover Co5Fb16 If you activate the function block Co5Fb16 the ventilation controller automatically changes between summer time and winter time The clock is set one hour forward on the last Sunday in March from 2 00 h to 3 00 h and set back one hour on the last Sunday in October from 3 00 h to 2 00 h 5 4 4 Public holidays and vacations PA5 The ventilation controller allows you to define 20 public holidays and 10 vacation periods There are no preprogrammed vacation peri ods Default settings for public holidays include 01 01 01 05 25 12 and 26 12 Enter the day and month to configure a pub lic holiday For vacation periods enter the date day and month when the vacation is to start as well as the date when it should end To enter a public holiday set the display to and enter a new date To delete a public holiday or vacation period set the date shown to on the dis play This display appears between the dates 31 12 and 01 01 To delete a vacation period change the start ing date to The ventilation controller uses the same times of use on public holidays as for Sunday The ventilation system is switched off during a vacation period 5 4 5 Time schedules times of use PA4 PA5 You can set
76. fax machine See p 84 Info level Inf Operating level Appendix C Operating level Appendix C 1 Info level InF1 Display shows Parameter After pressing the enter key 01234567 8 9 101112131415 1617 18 19 2021 222324 Return air temperature of heating coil 01234 5 67 8 9 10111213 14 15 16 17 18 19 20 21 22 23 24 Pump of heating coil m ON OFF 0123 4 5 6 7 8 9 1011121314 15 16 17 18 19 20 21 22 23 24 Control signal output of heating coil X were Y We WS EB 5177 EN 123 Operating level Info level InF2 Appendix C 2 Info level InF2 Display shows Parameter After pressing the enter key 0123 4 5 6 7 8 9 101112 13 14 15 16 17 18 19 20 21 22 23 24 Mixed air temperature 012234 5 6 7 8 9 101112 13 14 15 16 17 18 19 20 21 22 23 24 Temperature HRU Pump of heat recovery ON OFF 124 EB 5177 EN Info level InF3 Operating level Display shows Parameter After pressing the enter key 012345678 9101112191415 1617 1819202122284 Control signal output of heat recovery or mixed air chamber Appendix C 3 Info level InF3 Display shows Parameter After pressing the enter key 01234 56 7 8 9 1011121314 15 16 17 18 19 20 21 22 23 24 Binary output BA6 ON OFF 0123 45 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 Control signal output of cooling coil EB5177
77. for Anl 0 to 6 8 9 with feedforwarding of return air and outdoor temperature See variable return air temperature maximum limit on p 75 return air temperature controlled system start up mode on p 70 Return air temperature limit factor O to 10 Only for Anl 0 to 6 8 9 with return air sensor See variable return air temperature maximum limit on p 75 return air temperature controlled system start up mode on p Z0 Kp Heating coil 0 1 to 99 9 Ty Heating coil 60 Anl O to 6 and 8 9 1 to 999 sec Ty Heating coil to 999 sec See p 0 Parameters set in PA2 level Parameters Appendix B 2 Parameters set in PA2 level Symbols with default settings Parameter name After pressing range of values the enter key 0123456 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 Mixed air temperature set point 10 to 30 C Anl 2 4 only with mixed air temperature sensor See independent mixed air temperature control on p 2 Minimum outdoor air rate O to 100 25 Anl 2 4 8 only See mixed air chamber on p 61 summer time operation on p 68 and air quality control on p 73 Minimum outdoor air rate at an outdoor temperature is lower 10 to 50 C Anl 2 4 8 only with outdoor temperature controlled mixed air chamber See outdoor temperature controlled mixed air chamber on p 53 EB 5177 EN 107 Parameters Param
78. hamber heating coil cooling coil and humidifier Two control circuits temperature and hu Summer time operation see section midity control 5 4 2 Humidifying or humidifying and dehu Automatic reversal of operating action for midifying operation configurable see mixed air chamber see section 5 3 12 section 3 3 3 Fan operation 2 speed see section 5 3 3 Summer compensation see section 5 5 2 EB 5177 EN 45 Description of systems Control levels Antifreeze required E in HRUI Ext ON Ext speed 2 gt v s F R D T A M D XH X X i BE1 1 BE12 BE13 BE10 BE7 BAA BA7 BA3 BAS BAA BAS Speed 1 Speed 2 F3 FA Fl F FB F Wrs F F2 AE2 AE1 AE2 AEA AE3JAEAJ AE3 J Specifications in parentheses can be p p Y2 Y Y3 Y4 selected as an alternative Fig 14 System code number 9 System code number 9 Control of heat recovery unit HRU heating coil cooling coil and humidifier only humidification Two control circuits temperature and hu section 3 3 3 midity control Summer compensation see section 5 5 2 Humidifying or humidifying and dehu Fan operation 2 speed see section 5 3 3 midifying operation configurable see 46 EB5177 EN Control levels T E THAM Q i On MK OX i l BE11 BE12 BAA BAS BA7 je F3 FA AE2 y YE Y1 Y4 Fig 15 System code number 9 Description of systems Ex ON Ext speed 2 w v
79. he circuit blinks e Any changes to an output are kept if you push the selection switch for manual operation B Exiting manual mode Slide Display shows Comments D om2 A 5 o 78 9 012 134 151617 18 1920222 2324 ihe mode switch A to EBSI77EN 1 Operation 3 3 Control levels N Note Control levels Any changes in the configuration level PA and CO levels may cause errors in the sys tem Therefore they must be only performed by the specialist Fig 1 shows the level structure in the TROVIS 5177 Ventilation Controller It also shows the operating steps that need to be taken to access each individual level The con troller contains two main levels the operat ing level and the configuration level Use the changeover key C to switch between the lev els The operating level contains the info lev els in addition to this when switched to the manual mode a manual level is also accessi ble The configuration level contains the parameter levels the system code number level and the configuration levels The info parameter and configuration levels are assigned to an index from 1 to 9 which is the same in all three levels In this way specifica tions concerning the heating coil are always termed InF1 PAT und Col index 1 accord ing to the level All other indices are summa rized in the table opposite Usually the ventilation controller is in the operating level and the time appears on the d
80. he externally required signal from all the other controllers and controls the primary flow temperature correspond ingly Activate Co7 Fb01 in a controller to turn it into the primary controller Activate Co7 Fb02 to send the time This function block however may only be set in one controller to ensure all the control lers function with the same time If the time is sent over LON all the other de vices in a system automatically function with this time Activate Co7 Fb03 to send the outdoor temperature Lon and activate Co7 Fb04 for outdoor temperature Lon2 After acti vating these function blocks the number of the terminal to which the outdoor sen EBSI77EN 79 Configuring the LON interface 80 sor is connected must be entered This does not necessarily have to be the out door sensor AF it can also be a sensor connection of any other free terminal In each controller in the system you must set which outdoor temperature Lon 1 Lon 2 or local is to be used in the con troller for the control The function block EB 5177 EN Co5 Fb02 determines which outdoor tem perature in the controller is to be used When Fb02 ON the local outdoor tem perature at sensor F3 or measured at an analog input is used Deactivate FbO2 to choose between no outdoor tempera ture Lon or Lon2 Interface versions 7 Serial interface Co9 7 1 Interface versions The ventilation controller is equipped with a RS 232 C serial
81. hone number may have 23 characters at the maximum indicates the end of the string Enter numbers with arrow keys and confirm the number with the enter key Enter short pauses of 1 second e g between dialing code and the teleohone number using P which appears on the display when scrolling with arrow key after 9 Example Telephone number 069 654321 gt Enter 069 P654321 Telephone number of the alternative recipient rESno Enter the telephone number of an alternative recipient which is to be dialed when the line of the control station is busy Enter in the Station identification The station identification can be any number 04 EB5177 EN same manner as the control station number Status register 7 3 Status register Serial interface Co9 The 16 bit holding register HR 60 is an error dialed over the dial up modem as soon as status register which contains controller the status of this holding register changes errors The control station is automatically HR 60 is transferred in text format Bit value 22 25 24009 Qu e v 2 D Do 2 2 2 2 2 Sensor failure Default values read Mode switch defective Selection sw for manual operation defective Set point correction switch defective Unauthorized access Error message from a binary input D5 D D7 D8 D9 D10 D11 D12 D13 D14 D15 EB 5177EN 85 Serial interface Co9 Operation with a dedicate
82. ildings Sensor for heating coil return air temperature and HRU circuit temperature Type 5207 21 immersion sensor with brass sensor shaft Type 5277 duct sensor thermowell required Type 5267 contact sensor Sensor for room temperature Type 5257 1 Sensor for room temperature and potentiometer 1000 to 2000 Q Type 5257 2 Sensor for room temperature potentiometer 1000 to 2000 Q and external request for opera tion speed 2 Type 5257 6 Sensor for outdoor supply air exhaust air and mixed air temperature Type 5217 duct sensor Resistance thermometers with Pt 100 measuring element Sensor for outdoor temperature Type 5225 for outside walls of buildings Sensor for heating coil return air temperature and HRU circuit temperature Type 5204 21 immersion sensor with brass sensor shaft Type 5205 47 immersion sensor with CrNiMo sensor shaft Sensor for room temperature Type 5255 Sensor for outdoor supply air exhaust air and mixed air temperature Type 5215 duct sensor 128 EB 5177 EN Info level InF5 Resistance values of temperature sensors Resistance thermometers with PTC measuring element Sensor for outdoor temperature Type 5224 for outside walls of buildings Sensor for heating coil return air temperature and HRU circuit temperature Type 5264 duct sensor thermowell required and Type 5265 strap on sensor 10 20 25 30 40 50 60
83. int O to 40 C With exhaust air temperature control or exhaust air tempera ture cascade control See p 48 49 Room temperature night set point O to 40 C With room temperature control or room temperature cascade control See p 50 p 75 Supply air temperature minimum limit O to 50 C Only with feedforwarding of supply air temperature See supply air temperature limit on p 74 Parameters set in PA5 level Symbols with default settings Parameters Parameter name range of values After pressing the enter key 0123 45 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 START PA 7 e Supply air temperature maximum limit O to 50 C Only with feedforwarding of supply air temperature See supply air temperature limit on p 74 Sustained room temperature O to 20 C Only with Anl 0 to 6 8 9 with feedforwarding of room tem perature See sustained room temperature on p 72 Summer compensation when the outdoor temperature is greater 50 to 40 C Only with Anl 0 1 and 4 to 9 with outdoor temperature See summer compensation on p 71 Set point at an outdoor temperature of 32 C Supply air temperature O to 40 C Only with Anl 0 1 and 4 to 9 with outdoor temperature See summer compensation on p 71 EBSI77EN 115 Parameters
84. isplay In Fig 1 for example 10 24 is indicated on the display Apart from the time symbols to represent the operating mode and operating status as well as the sys tem represented symbolically appear on the display Refer to page 147 for a summary of the major symbols A bar graph appears on bottom right hand B5177 EN corner of the display showing roughly the control signals Y1 Y2 and Y3 This bar graph is shown in the operating level Note Two minutes after the last entry the controller returns automatically from the configuration level back to the operating level Information parameters functions Designation of levels InF1 PAI Col Heating coil InF2 PA2 Co2 Heat recovery unit mixed air chamber InF3 PA3 Co3 Cooling coil InF4 PA4 CoA Fans humidifier InF5 PA5 Co5 Functions affecting all systems Co Sensor initialization PAZ Co7 LON communication Co8 Error initialization PA9 Co9 Modbus communication Anl System code number and control method Control levels Information on Manual operation Functions affecting all the systems Fans humidifiers Function block setting for Modbus communication Error initialization LON communication Sensor initialization Functions affecting all the systems Fans humidifiers Cooling coil Heat recovery mixed air chamber Heating coil Fig 1 Control levels Co
85. lay shows ANY Any display both or OMIM 55456 7 S o 0 IJN2 9 3 151617 Ji8 19 20 2122 2324 Vl V2 Ne Operation Comments Every time you press the key another piece of information appears on the display See page 123 ff for further displays On reaching the end of an info level End appears on the display Comments Press both arrow keys simulta neously The next info level appears on the display depending on the sys tem code number When End appears on the display press the enter key In this way you can also access the next info level EB5177 EN 15 Operation Control levels 3 3 2 Changing the system code number The ventilation controller contains different Every change in system code number or con types of systems which are assigned to sys trol method supply air control exhaust air tem code numbers 0 to 9 They are deter control causes the assignment of sensors to mined in the configuration level under Anl be reprogrammed the sensor inputs required system code number By entering the system for the function blocks are activated and the code number you determine both the inputs sensor inputs not used are deactivated These and outputs of the controller as well as the settings can be changed manually selectable function blocks and parameters Proceed as follows to change the system You can find a list of the different systems in code number section 4 Press Display shows Comments e OMI
86. m operation the control output Y2 Independent mixed air temperature con Mixed air chamber in sequential operation Fig 17 For this mixed air chamber mode select ters Kp Mixed air chamber TN Mixed air Co5 FbO7 OFF and then select SEQ chamber and T Mixed air chamber The sequential operation or Co5 Fb07 2 ON parameter Minimum outdoor air rate PA2 and then select SEQ sequential operation guarantees an minimum proportion of out with outgoing air temperature The mixed door air air chamber is controlled from the Y2 output The operating action of the control output Y2 which can be adapted to the dynamics of the con be reversed The default setting is an out mixed air chamber by means of the parame door air rate of O to 100 which corre Without feedforwarding outdoor temp or exhaust air and outgoing air temperature Y2 Y3 System deviation Cont variable With feedforwarding outdoor temp or exhaust air or outgoing air temperature With outdoor temperature feedforwarding Control signal Y2 Y3 g Yl Y2 tA gt t Ab tA t Ab System deviation Cont variable Contr variable gt Outdoor temperature Outdoor temperature Fig 17 Different output signals e g in Anl 4 EB 5177EN 6 Function descriptions Outputs Without feedforwarding of outdoor temperature or exhaust air temperature Contr variable System deviation With outdoor temperature feedforward System Outdoor t
87. m elements operat ing in sequence Activate for this Co3 Fb12 and then select PAr Following this three function block parameters require setting Minimum activated time Minimum run ning fime that the chiller runs after demand Minimum deactivated time Interval be tween operation after the chiller has been switched off Deactivate cooling Heating coil control signal Y1 at which the chiller is switched off after Minimum activated time As soon as a low temperature is requested the chiller is activated at least for the period determined under Minimum activated time The other system elements can be requested in parallel to the chiller An excess amount of cold air is at first compensated for by the HRU and heating coil IF the heating coil con trol signal Y1 exceeds the value Deactivate cooling the chiller is switched off at least for the time period determined under Minimum deactivated time When the outdoor tempera ture is fedforward the chiller basically is only enabled when the outdoor temperature is 3 C higher than the current set point with a cascade control higher than the current sup ply air set point A chiller that is running is deactivated when Y1 gt 0 observing the Minimum activation time if the outdoor tem perature is lower than the set point with out door temperatures higher than the set point depending on the parameter Deactivate cooling The control signal Y3 is not available 5 3 7 Circulation pu
88. m limit O to 100 C Only for Anl 0 to 6 8 9 with return air sensor without feedforwarding of outdoor temperature See return air temperature limit on p 74 and return air temperature controlled system start up mode on p 70 Return air temperature maximum limit coordinate 1 O to 100 C Only for Anl 0 to 6 8 9 with feedforwarding of return air and outdoor temperature See variable return air temperature maximum limit on p 75 return air temperature controlled system start up mode on p 70 Outdoor temperature coordinate 1 50 to 20 C Only for Anl 0 to 6 8 9 with feedforwarding of return air and outdoor temperature See variable return air temperature maximum limit on p 75 return air temperature controlled system start up mode on p 70 EB5177EN 105 Parameters Symbols with default settings Parameters set in PA level Parameter name After pressing range of values the enter key 0123 4 5 6 7 8 9 10111213 14 15 16 17 18 19 20 21 22 23 24 STOP 106 EB 5177 EN Return air temperature maximum limit coordinate 2 O to 100 C Only for Anl 0 to 6 8 9 with feedforwarding of return air and outdoor temperature See variable return air temperature maximum limit on p 75 return air temperature controlled system start up mode on p 70 Outdoor temperature coordinate 2 50 to 40 C Only
89. matically You can try to start the ventilation system manually by Setting the mode switch A briefly to 2 and then back to System frost protection Co5 Fb15 Refer to section 5 7 1 Condensation detection Co3 FbO1 BE10 BE7 In all systems with cooling coil without a Function descriptions BE10 7 ON Note that the function is only available when CoA Fb02 is activated It is possible to switch the system off even dur ing a time of use of fan speed 2 with BE10 ON under the following conditions Co5 Fb13 ON Automatic operation External demand for fan speed 2 over Co4 Fb03 ON BEZ selected Triggering an external demand for oper ation or Switching on the BE12 for at least one second using an external key If you use the binary input BE1 2 for another purpose other than external demand for oper ation it is still possible to switch off the sys tem within the times of use by deactivating BE12 However STOP blinks on the display to indicate an error in the operating level If you then activate the binary input BE12 again the system starts without the system start up mode The binary input BE12 is a floating make contact soon as condensation is detected in standard dehumidifying function a condensation moni operation the set point of the control is tor can be activated for chilled ceilings As raised by 3 C IF the condensation monitor EB5177 EN 55 Function descriptions indicates a norm
90. mp control for the HRU BA7 In systems with connected heat recovery unit Anl 3 Anl 5 and Anl 9 the binary output BA7 controls the HRU pump This pump is only activated when the control signal is Y2 gt 0 IF Y2 is O for longer than three minutes when the system is in operation the circulation pump is switched off First when Y2 gt 0 it is switched on again IF the time of use finishes the HRU pump is switched off after three minutes The HRU pump is activated at least once for approxi mately one minute every 24 hours to prevent it from becoming jammed up 5 3 8 On off output for heating coil Co1 Fb12 BA7 The binary output BA7 can also be used to control an electric air heater in on off opera tion instead of the HRU pump BA7 is then controlled depending on the control signal Y1 Activate Col Fb12 and determine the following function block parameters Activating value START of Y1 value at which BA7 is activated Deactivating value STOP of Y1 value at which BA7 is deactivated EB5177EN 59 Function descriptions Outputs The control signal Y1 is available in parallel for this function 5 3 9 Three step output for heating coil Co1 Fb13 BA6 BA7 In system Anl O the heating coil can alterna BA6 the operating action CLOSING If you tively be controlled with a three step output want to use this function activate The binary output BA7 then controls the oper Col Fb13 and determine the functi
91. natively the room tem perature can also be guided over the analog input AE3 to the controller For this select F5 for AE3 in function block Co5 Fb20 The room temperature is controlled by a PID algorithm with an adjustable Room tempera ture day set point or Room temperature night set point PAS Depending on the system code number the Control method temperature control circuit has between 1 and 3 sequence outputs that are adapted to the dynamics of the corresponding system components by means of the Kp TN and Ty control parameters which you can change in the parameter level PA1 PA2 PA3 Func tions such as return air temperature limit summer compensation manual set point cor rection or condensation detection can shift the set point 5 1 5 Room temperature cascade control The sensor input F5 is the control variable input for the room temperature and the sen sor input F1 is the control variable input for the supply air temperature by default Alternatively you can also change to the ana log input AE3 for the room temperature by selecting F5 in function block Co5 Fb20 as well as change to the analog input AE1 for the supply air temperature by selecting F1 in the function block Co5 Fb18 The room temperature control circuit is imple mented as a P control circuit with adjustable Room temperature day set point Room tem perature day night point and Kp Tempera ture master loop PA5 The supply air tem peratur
92. nction descriptions is switched on a 100 signal is issued at the control output of the heating coil Y1 When the frost protection function is active STOP and the symbol gt blink on the dis play The standard mode is only restarted when the binary input BE11 is reactivated The frost protection function is also active in man ual operation sequential operation The limit value pro grammed in PA2 under Heat recovery mini mum temperature is used as the set point for an independent temperature control of this unit to make sure that further cooling off of the outgoing air return air does not occur The frost protection HRU remains active until the control signal Y2 for heat recovery has risen to a value of 95 directly after that the sequential operation is reactivated When the frost protection mode for HRU is active the symbol blinks on the display the outdoor temperature is lower PA 1 If the stand by monitoring is active the symbol appears on the display of the controller in the operating level EB5177 EN 77 Function descriptions Protective functions Stand by control If the outdoor temperature sensor and a monitoring function An active stand by con return air temperature sensor F4 exist the trol is indicated in the operating level of the value Return air temperature minimum limit controller by the m symbol appearing on PA1 is controlled in the heating coil for the he display frost
93. ne The ventilation controller can send an error message over text messaging SMS to a mobile phone The device uses for this the TAP protocol which is supported in Germany by the mobile telephone network D1 and EPlus To do this enter the access number and the complete mobile telephone number in the PA9 level The D1 access number is 01712092522 and following this the mobile phone number starting with 49171 Error message to a fax Define the following function blocks in CO9 1 F500 Fb01 Fb06 OFF 2 Fb10 ON 02 EB5177 EN modem to a control station or to a mobile phone or a fax according to your own requirements 4 Set the parameters in PA9 described in section 7 2 2 For E Plus the access number is 01770610000 and following this the mobile phone number starting with 49177 Define the following function blocks in CO9 1 FbOO Fb01 Fb10 OFF 2 Fb06 ON 3 FbO7 according to your own requirements 4 Enter the access number ZUGno and mobile phone number HAndY in PAY Enter the telephone number of the fax machine teLno in PAY Optionally set a sta tion identification St Id Operation with a dial up modem Serial interface Co9 7 2 2 Parameters for operation with dial up modem PA9 Note The specified initialization settings must be set when the controller is used with a dial up modem It cannot be guaranteed that data are transferred after the initialization settings have been adjusted Due to th
94. nfiguration and parameter level System code number and control method Operation Information on Heating coil Heat recovery mixed air chamber Cooling coil Parameters for Heating coil Heat recovery mixed air chamber Cooling coil Fans humidifiers Function affecting all the systems LON communication Modbus communication EB5177 EN 13 Operation 3 3 1 Info levels Information is displayed in the info levels InF1 to InF5 about for example the operat ing states of the pumps and fans or control signals and values of the temperature sen sors The system code number and configura tion determine what sort of information is Control levels shown on the display Refer to Appendix C for a summary of symbols that appear on the display and their meanings It is not possible to make any changes to parameters when the controller is in an info level Activating the info level from the operating level Press t or V Display shows 14 EB 5177 EN OP 253A S67 89 2 TO 11213 14151617 8 92021 222324 Comments Use arrow keys to find the required InF level InF1 to InF5 Press enter key to activate the info level The first piece of information appears on the display This exam ple shows the supply air temperature Vl YE2 Ve Control levels Press or V Display shows OMIM E3456 7 9 o 02 1451617 8 1920222 2324 VAL YEA Ve Exiting an info level Press Disp
95. ng from Fb00 Sensor input F deviating from FbOO Sensor input F7 deviating from FbOO Sensor input F8 deviating from FbOO Sensor input F9 deviating from FbOO Sensor input F10 deviating from FbOO Sensor input F1 1 deviating from FbOO Sensor input F12 deviating from FbOO Sensor input 13 deviating from FbOO Sensor calibration see p 53 100 EB 5177 EN Anl Comments LESE np p s m E ET ars fa CLE TAN LES n s ge Lists or Tuncilon blocks LO Co tor LON communication Appendix A 7 Configuration level Co7 for LON communication Fb Function WE Anl Comments LON s S 79 Primary controller see p 79 System time see p 79 Outdoor temp 1 see p 79 Outdoor temp 2 see p 79 Appendix A 8 Configuration level Co8 for error initialization Fb Function WE Anl Comments BEOI in status register FSR see p 85 BEO2 in status register FSR see p 85 BEO3 in status register FSR see p 85 BEOA in status register FSR see p 85 BEOS in status register FSR see p 85 BEO in status register FSR see p 85 BEO7 in status register FSR see p 85 O8 BEOB in status register FSR see p 85 10 EB 5177 EN Lists of function blocks Configuration level Co9 for Modbus communication Fb Function WE Anl Comments BEO in status register FSR see p 85 BE10 in status register FSR se
96. nother controller The memory module has a sub D 25 pin female connec tor to connect it to a PC and a modular jack to connect the memory module to the connector Fig 28 Connecting the memory module at the controller A Connect the memory module at the front panel of the controller only The rear connection is only suitable for communication with the control station Never connect the memory module to a controller and a PC simultaneously 8 1 Data transfer between controller and memory module Proceed as follows to transfer data between i e from the controller to the memory the ventilation controller and the memory module press the arrow key until 77 SP module appears on the display 1 Insert the RJ12 jack of the memory mod 3 Press the enter key The bars run across ule into the controller the top section of the display to indicate SP 77 appears on the display This com that data transmission from the controller bination allows data to be transferred to the memory module is in progress from the memory module SP to the con 4 When the bars stop running across the troller 77 display carefully remove the RJ12 jack 2 For data transfer in the other direction EBSI77EN 87 Installation 9 Installation The controller consists of the controller hous ing with the electronics and the rear panel of the controller with the terminals It is suitable Panel mounting 1 Remove both screws 1 2 P
97. ntrol station fax Phone number of alternative recipient Access number D1 or E Plus network Mobile phone number Station identification 138 EB 5177 EN O to 9 P pause end Customer data Parameter Info level InF5 Range of values Public holidays max 20 days Vacations Starting date Finishing date Parameters in PA7 level Parameter max 10 vacation periods Range of values Station address Parameters in PAQ level Parameter 1 20 Range of values Station number to 247 Baud rate 150 to 9600 Cyclic initialization O 10255 Modem dialing interval 1 to 255 Modem timeout 1 to 255 Number of dialing attempts to control station 0 to 99 Phone number of control station fax Phone number of alternative recipient Access number D1 or E Plus network Mobile phone number Station identification 138 EB 5177 EN O to 9 P pause end Index A Air qualilfy 58 66 Air quality control via mixed air chamber 73 Air volume control 66 Analog input Air quality 58 66 73 Exhaust air humidity S192 Operating action 66 Room humidity 51 52 Supply air humidity 51 52 Analog output Air volume control Humidifier 64
98. of change Kp 5 Current supply air temperature 18 C Supply air temperature min 18 C For YA 50 YAnew Y XD KP 50 24 C 22 C 40 C 100 5 75 XD is the percentage error in relation to the measuring range lts maximum limit is 10 The air quality control is implemented by a PI control algorithm with the parameters Kp Air quality control and TN Air quality control PA4 The operating action of the air quality input can be reversed The default setting is an air quality of O to 100 which corresponds to an input signal of 0 to 10 V LO means an insufficient air quality By activating the func tion block Co4Fb20 the operating action is reversed air quality O to 100 then corre sponds to 10 to O V As a result LO means a very good air quality 5 3 17 Request for externally required signal over LON Co1Fb01 This function allows you to request the required flow temperature from a primary controller in complex systems The required flow temperature is superimposed on the LON bus Activate the request for externally required signal function over the function block Co1Fb01 ON Following this set the function block parameters listed below 66 EB5177 EN Flow requirement MIN Flow requirement MAX Change when Y1 MIN Change when Y1 MAX The required flow temperature is calculated from the heating coil control signal If this exceeds in standard operation the limit value Change when Y1 MAX
99. on block ating action OPENING and the binary output parameter Valve running time 5 3 10 Fault alarm output BAT The binary output BAT is an open collector applied to this output the electric current output It is activated when the status register should not exceed 100 mA when connected FSR is gt 0 A maximum of 24 V DC may be 5 3 11 Heating coil Y1 Col Fb21 TN Heating coil and Ty Heating coil PA 1 The operating action of the control output Y1 can be reversed The default setting of the operating action heating capacity O to 100 0 to 10 V Activate Col Fb21 to reverse it to heating capacity 0 to 100 10 to OV An electric air heater can be controlled via the binary output BA5 subject to Y1 see sec System Control tion 5 3 8 deviation variable Control signal The heating coil can alternatively be con trolled over a three step output in system Anl O see section 5 3 9 Fig 16 Output signal in Anl O The heating coil is controlled from the control output Y1 The heating coil control is imple mented by a PID control algorithm with the adjustable parameters Kp Heating coil 60 EB5177 EN Outputs Function descriptions 5 3 12 Mixed air chamber Y2 Co5 Fb07 Co2 Fb21 PA2 You can choose between three operating trol or modes for operation of the mixed air Outdoor temperature controlled mixed chamber air chamber Mixed air chamber in sequential The mixed air chamber is controlled fro
100. onfiguration level Co for sensor initialization 101 Configuration level Co7 for LON communication 102 Configuration level Co8 for error initialization 102 Configuration level Co for Modbus communication 103 EB5177 EN 3 AppendixB Parameters 000 e eee eee ee eee eas 104 Appendix B Parameters set in PAl level 2 2 2 ee 104 Appendix B 2 Parameters set in PA2 level 2 2 2 a 108 Appendix B 3 Parameters set in PA3 level 2 2 2 ee 110 Appendix B 4 Parameters set in PA4 level 2 2 a 111 Appendix B 5 Parameters set in PAS level 2 ee 112 Appendix B 6 Parameters set in PA7 level LON communication 120 Appendix B 7 Parameter der Ebene PA Modbus ee 121 Appendix C Operating level eee eee ene 124 Appendix C 1 InfolevelInFl 2 a 124 Appendix C 2 Info level InF2 0 0 0 00000000 eee 125 Appendix C 3 Info level InF3 0 2 0 0 0 00000 126 Appendix C 4 Info level InF4 0 00 0 00000000 eee ee 127 Appendix C 5 Info level InF5 2 ln 128 Appendix D Resistance values of temperature sensors 129 Appendix E Customerdofa 0 e eee eee eee eas 131 GER wa hee eee oe eee Be PPP 142 Key code ee te tt et ee 145 Important symbols on the display 149 ig PTT ee SQ Q S eS ee ee 150 4 EB5177 EN Scope of the ventilation controller
101. onfiguration level Co2 for heat recovery Fb Function WE Anl Comments 21 Operating action of OFF 2 5 BB Coss s heat recovery 8 9 Appendix A 3 Configuration level Co3 for cooling coil Fb Function WE Anl Comments 01 Condensation OFF 1 4 ON activated select BETO BEZ StEIG FALL detection 5 6 StEIG make contact FALL break contact see p 55 7 8 Note Can only be changed after entering key code eu See p 30 humidifying only EB 5177 EN 95 loa fF rar Toss A s ens ee DEC an AE scr Fey Lists of function blocks Configuration level Co4 Fb Function WE Anl Comments Enabling the cold storage see p 58 BA6 dependent onY3 see p 58 Chiller in parallel operation see p 61 Operating action of cooling coil Appendix A 4 Configuration level Co4 Fb Function WE Anl Comments Fan operation feed back at BE12 see p 53 2 speed fans over BA4 BA5 see p External demand for fan speed 2 see p 54 Air volume control over Y4 see p 66 96 EB 5177 EN Fb Function WE Anl Comments Operating action L Operating action of humidifier Operating action of fans Appendix A 5 Configuration level Co5 of functions affecting all systems Fb Function WE Anl Comments F1 supply air temperature F2 exhaust air temperature F3 outdoor temperature FA return air tempera ture of heating coil F5 room
102. ontrol The difference between temperature and humidity control circuits is shown on the dis play by blinking symbols For the tempera ture control circuit heating and cooling coil blink on the display For the humidity control circuit the cooling coil and humidifier blink on the display Additionally for the humidity control circuit a difference is made between humidifying and dehumidifying operation and just humidifier operation You can set the control method in the configu ration level under the system code number Anl Refer to Changing the system code number in section 3 3 2 on page 16 ters are recognizable by a combination of symbols that appear on the display You will find a summary in Appendix B If you want to change parameters proceed as follows Press Display shows Comments Refer to Appendix B for the parameter levels and the symbols assigned to the parameter s gt 0815203254560 72 S 9101112115 1415 61738 19 20 22223 22 Press the changeover key to change to parameter level PAT REN Yl 12 VS EBSI77EN 19 Operation Press or V until t or V until 20 EB5177 EN Display shows om 4555657 8 230 02 13 14 15 T 1Z318 19 20 2122 23 24 Control levels Comments Use the arrow keys to select the parameter level needed This exam ple requires PA5 Press the enter key to access the parameter level PAS The first parameter appears In the example it is the time
103. ontrol via mixed air chamber on p 73 and air volume dependent on the air quality on p Parameters set in PA5 level 01234 506 7 8 9 101112 1314 15 1617 18 19 20 21 22 23 24 o 123 45 6 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 START STOP PA Parameters Kp Humidifier 0 5 0 1 to Note For Anl 8 9 the 99 9 humidifier is assigned to Tx Humidifier 60 1 to 999 analog output Y4 not con sec display not shown trol output Y2 as shown on Ty Humidifier to 999 the display sec display not shown Anl 6 8 9 only See humidifier on p 64 Times of use for fan speed 2 two time schedules with adjustable start and stop Default setting 10 00 12 00 and 12 00 15 00 Appendix B 5 Parameters set in PAS level Symbols with default settings Parameter name After pressing range of values the enter key Time o 123 45 6 7 8 9 10111213 14 15 16 17 18 19 20 21 22 23 24 PA EB 5177 EN 111 Parameters Parameters set in PA5 level Symbols with default settings Parameter name After pressing range of values the enter key o 123456 7 8 9 1011 12 13 14 15 16 17 18 19 20 21 22 23 24 Date PA o 123 45 6 7 8 9 10111213 14 15 16 17 18 19 20 21 22 23 24 Year 01234 596 7 8 9 1011121314 15 16 17 18 19 20 21 22 23 24 Supply air temperature day sel point FI 010 5
104. oor temperature of 32 C PA determines also the gradient of the characteristic curve see also Fig 25 Example A heating coil is to warm up the supply air to Outdoor temperature C EBSI77EN 71 Function descriptions Control functions Set point C a Outdoor temperature C Fig 25 Outdoor temperature controlled supply air control 35 C at an outdoor temperature of 15 C Supply air temperature The foot of the perpendicular is to be at maximum limit 40 C 15 C outdoor temperature 20 C supply The calculation of the temperature required air temperature for the parameter Set point at an outdoor Supply air temperature temperature of 32 C results in set point 35 c a 79 32s Cb Summer compensation when the outdoor le b temperature is greater b 15 C zu 35 C 20 C s s Bc Q taon sil ao 15 C 15 C X92 C19 6 temperature of 32 C E Supply air temperature 1159 minimum limit de205 SS Foot for outdoor temperature e 15 C 5 5 4 Sustained room temperature Co5Fb05 If a room temperature sensor is connected ture maximum limit PA5 minus 1 K When the Sustained room temperature PAS is the room temperature has reached the Sus monitored when the system is switched off If tained room temperature plus 2 K the sus the room temperature falls below this limit tained room temperature function and usu value at first the system start up mode is initi ally the operation of
105. ppendix A 4 Appendix A 5 Appendix A Appendix A 7 Appendix A 8 Appendix A 9 Setting default values aaa 76 Protective functions sow 9 orc k x dee a 77 Frost protection ooa L 77 Locking settings Co5Fb23 aoaaa ee 78 Forced operation of the pumps a 78 LON communication Co7 PA7 Co5 Fb03 79 Configuring the LON interface 2 2 79 Serial interface Co9 2 T T T leeren 81 Interface versions e 8 Operation with a dial up modem 92 Configuring the controller interface 2 2 ee 82 Parameters for operation with dial up modem PA9 83 Status register 2 2 2 2 ll ll ll sss 85 Operation with a dedicated line bus operation 86 Bus connection to RS 485 interface 2l 86 Configuring the interface ooa aa 86 Memory module cler 87 Data transfer between controller and memory module 87 Installation s ssy eee eee See Ge ROR s 9 R 2 S eee ee v 88 Electrical connection s s s sss sss sos e 90 Technical data _ oe cp m em aeo o 93 Lists of function blocks len 95 Configuration level Col for heating coil ls 95 Configuration level Co2 for heat recovery 95 Configuration level Co3 for cooling coil 2 2 ee 95 Configuration level Co4 a oaa 96 Configuration level Co5 of functions affecting all systems 97 C
106. protection in addition to the stand by 5 7 2 Locking settings Co5Fb23 Activate this function block to mask all Co lev CoS level Fb23 appears on the display els and all the parameters in the PA levels Only after Co5Fb23 has been deactivated except for time and date settings the night which also requires entry of the key code all and day set points for supply air exhaust air functions and parameters are accessible and room temperatures as well as the set again points of the slave loop times of use vaca tions and public holidays After accessing the 5 7 3 Forced operation of the pumps The circulation pump of the heating coilas once every day to prevent them from jam well as the heat recovery unit s pump are au ming tomatically started by the controller at least 78 EB5177 EN Configuring the LON interface LON communication Co7 PA7 Co5 Fb03 LON communication Co7 PA7 Co5 Fb03 The TROVIS 5177 Ventilation Controller can be linked together with other controllers from the TROVIS 5100 series in a specific SAMSON LON network In this way two out door temperatures the flow temperature for externally required signal and the time can be exchanged among the connected control lers A special communication tool is not nec essary Just the LON communication must be activated an address allocated to each con troller in the LON network as well as a defini tion about which controller sends which 6 1 1 Activat
107. r Select F1 in the function block Co5 Fb18 for AE The supply air temperature is controlled by a PID algorithm with an adjustable Supply air temperature day set point or Supply air tem perature night set point PAS Depending on the system code number the temperature control circuit has between 1 5 1 2 Exhaust air temperature control The sensor input F2 is the control variable input by default Alternatively the exhaust air temperature can also be guided over the 48 EB5177 EN Control method parameters All the parameters that you can set in the parameter level or in the function blocks are written in italics For system code numbers Anl 6 8 and 9 the control method for humidity control circuit is set in the same manner as the temperature control circuit In the humidity control circuit humidifying and dehumidifying mode or just humidifying mode are differentiated between Read section 3 3 3 to find out how to set this control method and 3 sequence outputs that are adapted to the dynamics of the corresponding system components by means of the Kp TN and Ty control parameters which can be set in the parameter level PA1 PA2 PA3 Functions such as return air temperature limit summer compensation manual set point correction or condensation detection can shift the set point The supply air can be controlled dependent on the outdoor tempera ture see section 5 5 3 analog input AE3 to the controller Sel
108. r GOMMOl 2 tng auch ogee a qoi ETHER 7 Outgoing air damper 57 P Parallel operation Chiller uud sonet pra ees aE q 59 Parameters GHEMGING a0 aia bathe od ba ean 68 Potentiometer Correction of humidity set point 56 Correction of temperature set point 56 Primary conrroller 79 PI1O00sensor 100 Pt 1000 sensor 100 PTC en or 2 e dove q wa vae aes 100 Public holidoys 69 R Reduced operotion 7 Request for externally required signal 66 Resistance values of temperature sensors 128 129 Return air flow temperature sensor 70 Return air temperature limit 74 vorioble qs Return air temperature sensor 70 78 Room humidity cascade control 52 Room humidity control 51 Room humidity limit 29 Room temperature cascade control 50 EB5177EN 140 Room temperature control 50 RS 232 Ciinterlace 8 RS 485bus 8 S Sensor selecingiype 53 Sensor calibration 53 Sensor failure _ 76 Sensor version 100 Sequential operation 6 Serial interface 81 86 Stand by control _ 78 Stand by monitoring 77 Stand by operation 7 Station id
109. re set point slave loop set point of the supply air temperature control PA5 Depending on the system code number the supply air temperature control circuit has between 1 and 3 sequence outputs that are adapted to the dynamics of the correspond ing system components by means of the Kp TN and Ty control parameters which can be changed in the parameter level PA1 PA2 PA3 The parameters Supply air tempera ture minimum limit and Supply air tempera ture maximum limit PAS restrict the set point shift which arises when the exhaust air tem perature control circuit takes influence on the supply air temperature control circuit each deviation in exhaust air temperature by the amount x causes a shift of the supply air tem perature set point by the amount x multiplied by the parameter Kp Temperature master loop Example Exhaust air temperature set point 22 C Current exhaust air temperature 20 C Temperature set point slave loop 30 C Kp Temperature master loop 2 5 Supply air temp minimum limit 40 C Temperature set point slave loop calculated 35 C Shifts in the set point which are caused by manual set point correction return air tem perature limit summer compensation or by condensation detection have unrestricted ef fects on the exhaust air temperature set point EB5177 EN 49 Function descriptions 5 1 4 Room temperature control The sensor input F5 is the control variable input by default Alter
110. revious mode reduced operation Rated operation The ventilation sys tem is constantly in operation It is controlled acc to the set point s for day e g Supply air day set point J Reduced operation The ventilation system is constantly in operation It is controlled acc to the set point s for night e g Supply air night set point Stand by operation The ventilation system is switched off The frost protec tion is active provided it has been enabled see section 5 7 1 Manual operation In combination with the selection switch for manual operation B the ventilation controller can be operated in the manual mode see section 3 2 EV E5177 EN 7 Operation Operating controls on front panel 3 1 2 Selection switch for manual operation B Y Y2 If the mode switch A is set to manual mode Q and the manual level is activated you can O use this switch to operate the output which 3 1 3 Changeover key and reset key C D NIA lt g 1 0 are avail gt 8 B5177 EN you have selected over the selection switch for manual operation B see section 3 2 Control output Y1 heating coil Control output Y2 humidifier mixed air chamber heat recovery unit Control output Y3 cooling coil Control output YA humidifier Anl 8 and Anl 9 Pump s Fans former symbol Theses keys must be operated with a pointed object e g pencil The
111. rifting of the supply air humidity The main purpose of the supply air humidity maximum limit is to prevent condensation forming in the supply air duct EB5177 EN 75 Function descriptions Controller reaction when faults occur 5 6 Controller reaction when faults occur 5 6 1 Sensor failure and malfunctions Interruptions or short circuits in the sensor wir active the fans are switched off by this ing as well as other malfunctions are indi cated by the symbol that blinks on the dis play In the InF levels appears on the dis play instead of a measured value when a sen sor has failed After a sensor for a controlled variable has failed all the control outputs of the controller runa 0 control signal The binary outputs for pumps and fans maintain their operating states IF the frost protection function becomes 5 6 2 Setting default values Deactivate the function block Co5Fb23 to reset in the parameter level all parameters to their default values by pressing the gt reset key Refer to Appendix B to find a list of 6 tEB5177 EN function When the sensor for exhaust air temperature or humidity or for room temperature or umidity required for the master loop fails the Supply air temperature maximum limit or Supply air humidity maximum limit is used by the controller When any of the other sensors fail the con troller continues to function as if this sensor is not configured the defaul
112. s risen to a value greater than Air quality set point Differential gap of speed 2 1 provided that the Times of use for fan speed 2 PA4 or the external demand for fan speed 2 do not require the opposite 5 3 4 Enabling the cold storage Co3 Fb12 BA6 In all systems with cooling coil the binary out put BA can be used to enable the charging of a cold storage Deactivate Co3 Fb12 and set the function block parameter Enabling the cold storage at outdoor temperature If the outdoor temperature measured over an hour exceeds the value Enabling the cold storage at outdoor temperature BAG is switched on If the value falls below the limit for an hour BAG is switched off 5 3 5 Binary output dependent on Y3 Co3 Fb12 BA6 In all systems with cooling coil the binary out put BAS can be activated dependent on the control signal Y3 It can for example control a direct expansion evaporator For this activate Co3 Fb12 and select SEQ Following this both function block parame lers require setting 58 EB5177 EN Activating value START of Y3 value at which BAG is activated Deactivating value STOP of Y3 value at which BAG is deactivated The control signal Y3 is available in parallel for this function Outputs Function descriptions 5 3 6 Controlling the chiller Co3 Fb12 BA6 In all systems with cooling coil except for Anl 7 a chiller can be run to overlap i e in parallel to the other syste
113. ss the enter key to confirm the new year A new parameter appears on the dis play In this example it is the supply air temperature day set point Press the changeover key to change to the operating level The time is shown on the display Note If this is not the case a param eter is still activated You must press the enter key first Vl YR NS EB 5177EN 25 Operation Programming the time schedules times of use You can enter the time schedules separately for the system PA5 and if required for the fan speed 2 PA4 Refer to pages 118 and 111 for the relevant symbols You can also set the time schedule as described as follows You can enter two time periods for each day Display shows gt O23 WAS Ce FS 9810121512 51617 18 I 2021022 23 24 VL until 26 EB5177 EN Control levels Example The time schedules for every week day are to be changed The time of use was previously set between 07 00 h and 22 00 h default setting The new times of use are to be between 06 00h and 14 00 h as well as between 19 00 h and 23 00 h The following settings must be entered at the controller Comments Press the changeover key to access the parameter level PA1 Press the arrow key until PA5 appears on the display Press the enter key The time appears on the display Control levels Press until h or v Display shows 9 ONIS SE ROO IONS 15 A TSS 17 185190 21 222324 START STOP
114. systems with an outdoor temperature sensor the circulation pump s operation depends on the parameter Start up when the outdoor temperature is lower If the outdoor temperature is above 5 3 2 Enabling fan speed 1 BA4 Usually the fan speed 1 is enabled over the binary output BA4 at the programmed start of the time of use Times of use of the system PA5 The system start up mode has already been completed if necessary at the time period set under Pump advance running time for start up PA1 before the time of use starts When a request for an externally required signal is issued the fan speed 1 may be enabled with a delay due to the sys or stand by control During the summer deactivation the circulation pump of the heat ing coil is basically switched off It is acti vated daily for approximately one minute to prevent it from becoming jammed up tem start up mode If the outdoor air outgoing air damper is additionally to be controlled over BA4 it will be necessary to determine in function block CoA Fb02 that BA4 also remains activated when fan speed 2 is in operation In case of the malfunctions system frost pro tection or missing fan feedback the fans are immediately switched off 5 3 3 Enabling fan speed 2 Co4 Fb02 BA5 The fan speed 2 is controlled via the binary output BAS It is enabled either by Times of use for fan speed 2 by an external demand for fan speed 2 see section 5 2 4 dependent on th
115. t and end Default setting 1 2 7 Mon Tue 7 00 12 00 and Sun 12 00 22 00 See p 6 Public holidays Standard public holidays 01 01 01 05 25 12 26 12 maximum 20 public holidays adjustable The times of use for Sunday are valid on public holidays See p 69 Parameters set in PA7 level LON communication Parameters Symbols with default settings Parameter name After pressing range of values the enter key 01234 56 7 8 9 101112 13 14 15 16 17 18 19 20 21 22 23 24 Vacations Starting and finishing dates START STOP Standard vacation none maximum 10 vacation periods adjustable In vacation periods the ventila tion system is switched off See p 69 Appendix B 6 Parameters set in PA7 level LON communication Symbols with default settings Parameter name After pressing range of values the enter key 01234 5 67 8 9 10111213 14 15 16 17 18 19 20 21 22 23 24 Station address 1 20 EBSI77EN 119 Parameters Parameter der Ebene PA9 Modbus Appendix B 7 Parameter der Ebene PA9 Modbus Symbols with default settings Parameter name range of values After pressing the enter key 012 34 56 7 8 9 101112 13 14 15 16 17 18 19202122 23 24 120 EB 5177 EN Station number 1 to 247 See p 83 Baud rate 150 300 600 1200 2400 4800 9600 See p 84
116. t settings The controller is ready for operation using its default values Just the current date and time need to be set Protective functions 5 7 Protective functions 5 7 1 Frost protection System frost protection Co5Fb15 BE11 This function is used to protect the heating coil from being damaged by frost Activate the function with Co5Fb15 Depending on the binary input BE11 the system runs in standard mode or the frost protection func tion is run BE11 must be ON for standard mode IF BE11 input makes contact the frost protec tion function starts the fans are switched off and the circulation pump of the heating coil Frost protection HRU Co5Fb06 PA2 The function Frost protection HRU is set when the sensor F is activated e g Co5Fb06 ON It makes sure when the sys tem is running that the heat recovery equip ment e g circuit connected heat exchanger or rotating heat moisture recovery does not freeze on the outside If the HRU return air temperature falls below or alternatively the outgoing air temperature measured directly at the heat recovery unit falls below the parameter Heat recovery minimum tempera ture the frost protection function is started the heat recovery unit is released from the Stand by monitoring The outdoor temperature is required for this function The circulation pump of the heating coil is activated whenever the outdoor temper ature falls below the value Pump ON when Fu
117. t up mode Usually all ventilation systems go over to standard operation first after a start up phase when a request for operation exists from deactivated state or from manual opera tion The duration of the start up is deter mined by the parameter Pump advance run ning time for start up PA 1 Two options exist to suppress the start up mode partially or totally Set the Pump advance running time for start up to zero to deactivate it totally When the outdoor temperature is fedforward the mode is only used when the outdoor temperature is lower than the parameter Start up mode when the out door temperature is lower PA1 If the ventilation system goes into operation according to the programmed times of use then the start up mode already starts to run before the time of use commences by the time period set in Pump advance running time for start up The fans are enabled exactly when the time of use starts If however the ventilation system is required to run by an external request for operation or by the mode switch the fans are first enabled after a time delay set in Pump advance running time for start up By enabling the heating coil circulation pump the control signal Y1 for the heating coil is enabled at the same time Without the temperature sensor F4 in the heating coil return air duct the control JO EB5177 EN Control functions output Y1 runs either 100 control sig nal or is set to the fixed value under Con trol
118. th the profile O is copied to the active profile in a terminal program the modem provided the modem parameters AT amp F terminal input set modem have been set and saved in profile O using a to default settings terminal program that came with the modem OK modem feedback EB 5177 EN 83 Serial interface Co9 AT EO SO 1 terminal input data echo off answer after first ring and establish communication Modem dialing interval P This parameter indicates the time interval that must be kept between two calls to avoid over Modem timeout t Modem timeout is the time period after which a connection to the control station GLT is ter Operation with a dial up modem loading the telephone network It is usually between 3 to 5 minutes minated after there is no response to the sta tion address Number of dialing attempts to control station C The parameter C indicates how many attempts are to be made to dial the control station when the control station line is busy without resetting the function to trigger a call by the control system After the specified number of redialing attempts have failed the controller uses the alternative phone number The function to trigger a call is reset by the control system by polling the status register FSR Telephone number of the control station tELno Enter here the telephone number of the con trol station s modem or fax if necessary with dialing code The telep
119. the entire system is ated for the time set under Pump advance ended running time for start up After this if neces sary the supply air temperature is controlled constantly to the set point Supply air tempera J EB5177 EN Control functions 5 5 5 Night purge Co5Fb17 During the times of non use the night air can be used to cool the rooms under certain conditions the fan operation is enabled and if necessary the mixed air chamber is reversed to 100 outdoor air rate The night purge requires the room tempera ture and outdoor temperature Additionally activate the function block Co5Fb17 and set its following parameters Enable night purge which indicates which room temperature must be exceeded be fore the night purge function can be re quested Finish night purge which indicates which room temperature must be reached be fore the night purge function is canceled Temperature difference to outdoor tem perature is the minimum temperature dif ference between room temperature and the outdoor temperature that needs to be reached before the night purge function can be requested The night purge is only enabled when the summer deactivation function is active see section 5 4 1 and additionally the following Function descriptions conditions are met Room temperature is greater than the room temperature limit Enable night purge and Temperature difference between room temperature and the outdoor temperature is
120. the request for exter Outputs Function descriptions nally required signal is increased gradually last phase finished with When the system until Flow requirement MAX is reached starts with system start up mode the temper When the flow temperature falls below ature set under Flow requirement MAX is Change when Y1 MIN it is gradually always requested see example shown in increased until it is reduced to Flow require Fig 23 ment MIN A new operating phase starts with the same request for externally required signal that the Example Flow requirement MIN 60 C Change when YI MIN 10 Flow requirement MAX 90 C Change when Y MAX 90 Control signal Y1 10 Request for externally required signal C mu Fig 23 Request for externally required signal EB 5177 EN 67 Function descriptions 5 4 Time functions 5 4 1 Summer deactivation In summer the heating coil is switched off when the date in a defined time period and the daily mean outdoor temperature exceed a set limit The function is inactive outside of this time period Set the following parameters in PAT for this function Date when summer deactivation is en abled Date when summer deactivation is dis abled Outdoor mean temperature The daily mean outdoor temperature is mea sured every hour between 6 00 h and 22 00 h You can view this temperature in the InF5 level the current outdoor tempera ture by holding the gt K key presse
121. ting controls on front panel 3 Operation To understand the operation of this control ler use the fold out page at the end of these mounting and operating instructions The controller is operated over switches and keys They are accessible after the clear front door is opened The mode switch A switches between the various operating modes You can view parameters such as temperatures and set points using switch C and the keys H and I as well as determine the selectable functions and controller param 3 1 3 1 1 Mode switch A OW 2 3524 5 Z 8 9 JO Use this switch to select the operating mode Automatic operation Rated opera Xt tion stand by operation The control ler works according to set times of use and switches between rated and stand by operation Automatic operation Rated opera tion reduced operation The control ler works according to set times of use and switches between rated and in WO Operation eters During which you can access the vari ous levels described in section 3 3 All set tings made and the information required appear on the display G It is also possible to transfer configuration and parameterization data with a memory module in the controller refer to section 8 The following sections contain a description of the individual switches and keys as well as concerning the operation of the individual levels Operating controls on front panel contrast to p
122. ull apart the controller housing and the rear panel 3 Make a cut out of 138 x 92 08 mm w x h in the control panel 4 Insert the controller housing through the panel cut out 5 Insert a mounting clamp 2 each ot the Wall mounting Remove both screws 1 2 Pull apart the controller housing and the rear panel 3 If necessary bore holes with the specified dimensions in the appropriate places Fasten the rear of the housing with four screws Top hat rail mounting 1 Fit the spring loaded hook 4 at the bot tom of the top hat rail 3 2 Slightly push the controller upwards and 00 EB5177 EN Data transfer between controller and memory module for panel wall and top hat rail mounting Fig 29 top and the bottom Screw the threaded rod towards the panel so that the housing is clamped against the control panel 6 Install the electrical connections at the rear of the housing as described in section 9 7 Fit on the controller housing 8 Fasten both screws 1 4 Install the electrical connections at the back of the housing as described in sec tion 1O 5 Fit on the controller housing 6 Fasten both screws 1 pull the upper hooks 5 over the top hat rail Data transfer between controller and memory module Installation Panel mounting Top hat rail mounting Screws Mounting clamp Top hat rail Spring loaded hook Fixed hook Fig 29 Mounting the controller
123. ummer compensation see section 5 5 2 Frost protection for HRU see section 2 ui Fan operation 2 speed or 0 to 10 V see section 5 3 3 EB 5177 EN 4 Description of systems Control levels Antifreeze required in HRU Ex ON Ext speed 2 AAH th M NN D OX OX OX i ivy i BEI 1 BE12 BE13 BE10 BE7 BAA BA3 BAS BAA BAS Speed 1 Speed2 F3 FA FI F FB FO WFF5 F7 F2 AE2 AE1 AE2 AEA AE3 AE4 AE3 Specifications in parentheses can be Y Y3 Y2 YA selected as an alternative Fig 10 System code number 6 System code number 6 Control of heating coil cooling coil and humidifier just humidity Two control circuits temperature and hu section 3 3 3 midity control Summer compensation see section 5 5 2 Humidifying or humidifying and dehu Fan operation 2 speed or O to 10 V see midifying operation configurable see section 5 3 3 42 EB5177 EN Control levels Description of systems Antifreeze required in HRU Ext ON Ext speed 2 QD M BEI 1 BENZ BEI3 BELO BE7 BA4 BA6 BA3 BAA BA5 Speed Speed F3 FA Fl F F8 F9 WNFzr5 F7 F2 AE2 AE1 AE2 AEA AE3 AE4 AE3 Note The position of the cooling coil does not appear on the controller s display as in the above schematics Y3 Y Y2 YA Specifications in parentheses can be selected as an alternative Fig 11 System code number 6 System code number 6
124. uration level Co Default setting is Anl 1 If you want to change the system code Control levels number refer to section 3 3 2 for more details The table below contains the main dif ferences between the system types Each system type is described on the following pages System code number Description of the system System 0 Ventilation system with a heating coil System Anl 1 Ventilation system with a heating coil and a cooling coil also chilled ceiling or direct expansion coil 1 speed System Anl 2 Ventilation system with a heating coil and a mixed air chamber System Anl 3 Ventilation system with a heating coil and a heat recovery unit System Anl 4 Ventilation system with a heating coil and cooling coil also chilled ceiling or direct expansion coil 1 speed and a mixed air chamber System Anl 5 Ventilation system with a heating coil and a cooling coil also chilled ceiling or direct expansion coil 1 speed and a heat recovery unit System Anl 6 Air conditioning system with a heating coil and a cooling coil and a humidifier System Anl 7 Ventilation system with a cooling coil also chilled ceiling or direct expansion coil 1 speed System Anl 8 Air conditioning system with a heating coil and a cooling coil a mixed air chamber and a humidifier System Anl 9 Air conditioning system with a heating coil and a cooling coil a heat recovery unit and a humidifier 34 B5177 EN Control levels Des
125. utdoor air rate can be gradually reduced by the PI con trol algorithm until it reaches Minimum out door air rate provided the temperature con EB5177 EN 73 Function descriptions trol loop does not demand the opposite Control functions 5 5 7 Supply air temperature limit Co5Fb01 Co5Fb18 PA5 The intention of the supply air temperature limit is to reduce the draft when supply air that is fairly cold is blown in A supply air temperature sensor must be configured for this function Co5F12 ON or in Co5F18 for the analog input AE1 F1 In addition set the following parameters in the parameter level PAS Supply air temperature minimum limit Supply air temperature maximum limit Both these parameters limit the temperature range within which the supply air tempera ture may vary If the supply air temperature is the control variable i e for supply air temperature con trol or exhaust air or room temperature cas cade control the controller only permits set point shifts within this range If F1 or AET is just used as a limit input i e for exhaust air or room temperature control this deviation is included in the control when the supply air temperature exceeds or fall below the limit values to counter any further drifting of the supply air temperature 5 5 8 Return air temperature limit Co5Fb04 PA1 Activate the function block Co5Fb04 for the return air temperature limit and set the follow ing parameters in the
126. ystem code numbers a control signal of 0 to 10 V By activating Anl 8 and 9 the function block Co4Fb21 the operating The humidifier control is implemented bya action is reversed a humidifier capacity O to PID control algorithm with the parameters 100 then corresponds to 10 to 0 V 5 3 15 Cooling coil Y3 The cooling coil is controlled from the control algorithm with the parameters Kp Cooling output Y3 It is implemented by a PID control coil TN Cooling coil and Ty Cooling coil 64 EB5177 EN Outputs Control signal Y2 Function descriptions Control variable Fig 22 Output signals for example in Anl 6 humidifier only In the system code numbers Anl 6 8 and 9 the demands made by the humidity control circuit for humidifying or the temperature control circuit for cooling are converted inter nally into one common control signal Y3 for the cooling coil The operating action of the control output Y3 can be reversed The default setting is a cooling capacity of 0 to 100 which corre sponds to a control signal from 0 to 10 V By activating the function block Co3Fb21 Control signal Humidilying Dehumidilyin i Lo System deviation the operating action is reversed the cooling capacity O to 100 then corresponds to 10 to 0 V Cooling can also be controlled using an on off signal which is issued at the binary output BA see section 5 3 5 Control of a chiller is likewise possible see section 5 3 6

Download Pdf Manuals

image

Related Search

Related Contents

Lieber Kunde und neuer Markisen-Besitzer,  accès au téléchargement  (H-377) Manual  Configuration Manager - Bosch Security Systems  IBM eServer x3650 M3  210_XXXX_Acripur_Colores_Carta_1_es    IO Module - Operating Instructions - GMC  Avaya Business Communications Manager 5.0 - Configuration - System Configuration manual  

Copyright © All rights reserved.
Failed to retrieve file