Operating Instructions Pressure Controller Type „ROBOTER“
Contents
1. IRSA Operating Instructions REGLEA Pressure Controller Type ROBOTER 1 Function 1 1 By the connection Z the controller is provided with air supply free of dust oil and water of a constant pressure of 1 4 bar max 2 0 bar The connection Y is for the actuator diaphragm control valve or the like The supply air blows on a nozzle flapper system which is mounted to a lever The constant restrictor in the air supply line measures the air quantity out so that with open nozzle the adjustable pressure at connection Y goes towards zero bar and with closed nozzle towards 1 0 bar max 2 0 bar 1 2 At the other end of the lever an adjustable reset spring is fastened It increases or decreases the feedback force in accordance with the lift position of the valve with increasing force the control circuit becomes lazier A setpoint spring secures the lever in its bearing The bellows assembly consists of the bellows and a pressure bolt which are connected If the pressure on the bellows increases the lever rises if the pressure on the bellows decreases the lever inclines 1 3 With the design increasing increasing on increasing pressure the lever is pushed upwards by the bellows so that air is stowed between nozzle and flapper As a result the pressure Y n creases 1 4 With the design increasing decreasing the lever 5 pushed upwards by the bellows on h creasing pressure so that air escapes between nozzle and flapper and the output
2. Pressure Controller Type ROBOTER 2 3 On the start up the required air supply Z of minimum 1 4 bar max 2 bar is adjusted at the air pressure reducer The air supply should be by approx 0 2 bar higher than the max operating pressure of the connected actuator see name plate control range 2 4 After the adjustment of the controller it has to be checked if the control equipment runs through the whole range e g lift of a control valve If the required output pressure is not achieved the following has to be examined a the air connections as regards leakage points b the constant throttle with regard to soiling After start up or longer standstill the impulse chamber part 37 has to be air vented by screw part 39 3 Service instructions 3 1 As a complete control station the pressure controller in connection with a control valve is inde pendent of an outside service only on air failure or breakage of the actuating diaphragm the valve must be operated by the hand adjustment device 3 2 If set value and actual value of the pressure in balanced condition of a control circuit do not co incide by means of the setpoint spring the pressure can be increased by turning clockwise and decreased by turning counter clockwise A change of the proportionality of the controller is achieved by adjustment of the reset spring A diminution of the active turns results in a greater P range and vice versa 3 3 In case that still then the controller is
3. pressure Y drops 1 5 A change of the setpoint value is effected by more or less biasing the setpoint spring In the output Y of the pressure controller is a damping throttle which has to be adjusted once at the service place and by which the control speed of the actuator can be influenced in case of a slight tendency to vibration of the control circuit 2 Start up 2 1 The pressure controller is mounted to the actuator at the works Regarded in flow direction the connection for the impulse line has to be arranged with the over flow plant before the control valve with the reducing plant after the control valve The impulse line has to be laid in such way that condensate with medium steam can develop before the bellows e g by U shaped or trumpet shaped arrangement A shut off device valve or slide has to be provided so that an exchange of defective bellows is possible without stopping the whole plant 2 2 With the basic adjustment of the controller especially after exchange of bellows it has to be observed that the pressure screw part 29 always engages accurately in the counter bearing of the measuring bellows part 35 For this purpose the pressure screw has to be screwed into an extent that the bellows are bi ased by approx 1 5 mm and then it has to be countered with the nut part 31 Code 902BVE DOC 902 BVe Date of issue 23 January 2001 ARCA Regler GmbH D 47918 T nisvorst Page 1 of 2 IRSA Operating Instructions REGLEA
4. restless by turning in the damping throttle part 16 the control pressure Y to diaphragm chamber can be damped approx 2 5 revolutions max 4 Maintenance At bigger intervals depending on the air quality the constant restrictor should be taken off and cleaned by experienced personnel e g precision mechanics Code 902BVE DOC 902 BVe Date of issue 23 January 2001 ARCA Regler GmbH D 47918 T nisvorst Page 2 of 2
Download Pdf Manuals
Related Search
Related Contents
Applicateur et film de protection Mode d`emploi Denver MC-5000 home audio set QEP 22900Q Instructions / Assembly 謹告 重ねてのお願い - 古河電気工業株式会社 ー 製品サノ 、一 ト AV Receiver User Manual Copyright © All rights reserved.
Failed to retrieve file