1. page 2 4 Operating Instructions Altenburger Electronic GmbH e The optics of the motion sensor are designed for a ceiling height of 2 5 m to 3 0 m In higher rooms the density detection of the sensor dimin ishes e During the setting of the light level to be kept constant no person should be pre sent directly under the sensor in order to avoid a falsification of the measured brightness value e The mounting into a draught e g close to a ventilator or air conditioner should be avoided e The regulations for the handling with SELV safety extra low voltage have to be observed Communication objects and parame ters For the exact projection and parametrizing of the control please refer to the enclosed description of the application and the technical handbook Safety and installation requirements MSD module and terminals Control elements The IBMSD may be installed and put into operation only by skilled designated electricians Wiring mounting and other work may be performed only in a voltage free state Applicable safety instructions and regulations for the prevention of accidents have to be observed For operation of the IBMSD in the lamp an UV resistant cable has to be used When clipsing the IBMSD to lamp tubes an undue load must be avoided Altenbu
2. brightness of colours inside the room reflections of floor and ceiling furniture etc Thus the constant light level at a high daylight portion can differ a little from that at a low daylight portion A direct exposure of the sensor to the daylight source window or glass roof has to be avoided Setting of light levels to be kept constant The adjustment of the required light level can be performed as follows e Directly as a parameter in the ETS software Via the object set light level room brightness or storage of the object set light level e Directly via the pushbutton for the storage and the IBMSD In this case at the pushbutton for the light level to be set at the control directly the required light level is set by the dimming function pressing the button 10 secs after the release of the pushbutton the set light level automatical ly is measured and stored Altenburger Electronic GmbH Operating Instructions page 1 4 Mounting of the IBMSD The Multi Sensor Dimmer EIB is available for the surface mounting on ceilings or for the mounting to lamp tubes by clamps Before mounting to the ceiling the base plate is drawn from the control and is screwed to the ceiling It is then wired according to the wiring diagram The control part then is plugged onto the baseplate Please observe after the wiring of master controls phase and 1 10V connected the enclosed cable insulation must be plugged onto the wire Action after bus vo
3. 6A oV 1 410V slave unit Master module electronic ballasts or tranformers only 1 10V 08 06 2011 V 1 1 Subject to error and technical modifications Altenburger Electronic GmbH Operating Instructions page 5 4
4. also could be wired to all ALTENBURGER dimmers with their interface of 0 10 V such being able to dim also incandescent lamps high voltage halogen lamps low voltage halogen lamps with wire wound transform ers or with electronic transformers 230V and neon lamps The integrated switch contact can be used for the direct switching of a load of up to 5 A For higher loads relays or contactors can be used Motiondetection The motion sensor within the Multi Sensor dimmer has an angle of detection of approx 100 The acquisi tion range is 7 m in diameter at a room height of 3 m If larger rooms or areas have to be controlled several IBMSD controls can be coupled In this case each IBMSD would care for the constant light control in its individual range of detection while the motion control applies for all connected circuits even if just one IBMSD recognizes a presence The IBMSD s also can be used just as motion detectors without the function constant light control Consiant Light control The integrated light sensor part within the Multi Sensor continuously measures the brightness at the IBMSD and compares this with the set light level Artificial lighting is added or reduced according to the set light level The light level measured at the sensor of course is not identical with the one at the workplace Presettable are light values between 25 750 lux at the control appr 50 1500 lux at the workplace depending on the room conditions
5. ALTENBURGER ELECTRONIC GMBH 77960 Seelbach SchloBweg 5 Phone 49 7823 509 0 Fax 49 7823 27 61 email info altenburger de Internet http www altenburger de Operating instructions Multi Sensor Dimmer EIB KNX Type IBMSD order no 80 14 800 Range of application The EIB Multi Sensor Dimmers are suitable for the daylight dependent constant light control and the pres ence detection in one unit It operates within the EIB system If motion is detected the control adjusts the artificial light to the daylight portion in a room It adds only so much artificial light to the daylight as necessary for the achievement of the preset light level to be kept constant If no motion is detected any longer the control reduces the daylight level after a set delay time to a low level and finally switches it off after a second delay time Additionally switch operations in dependence of motion detection can be performed within the EIB of venti lators air conditioners automatic doors heaters etc are within the range of application Lamps to be controlled With the Multi Sensor Dimmer EIB KNX electronic ballasts with 1 10V interface for fluorescent lamps electronic transformers with 1 10 V interface for low voltage halogen lamps can be operated directly without any additional component The IBMSD will be wired to the supply phase for the switch contact the low voltage interface 1 10V and to the EIB bus Instead of to interfaces of 1 10V the IBMSD
6. ltage return The behaviour of the system after a bus voltage return can be set as a parameter within the ETS software Generally the lighting is switched ON after a bus voltage return independent of the set light level After the control is in normal action again after the delay time and the switch OFF time the lighting switches OFF If the motion detection however is deactivated the lighting remains ON unless it is switched OFF manually Sensitivity and interference protection The sensitivity of the motion detection can be pre adjusted as parameter setting within the ETS software sensitivity motion detection in 3 steps reduced medium and very high sensitivity Additionally for the suppression of fault releases the minimum pulse range of the measured motion pulses can be fixed If fault releases are observed the required length of pulses have to be increased As the increase of the required length of pulses makes the evaluation a bit less sensitive separate values for the switch ON and switch OFF states are to be set Wiring instructions e The Multi Sensor Dimmer EIB KNX should be mounted directly above the place where the constant light level is required e g a working place The brightness inside the room however should always be picked up by the sensor indirectly at the point of reference A direct light on the sensor from the in terior illumination or the illumination of the place of work is to be avoided
7. ontact input T switch contact output 4 please refer to wiring diagrams in case of miswiring malfunction or damage possible function switch ON OFF no safe release of contacts y contact slot 5A resistive loads gt 30p elec bal 1lamp 18W 20 p elec bal 2lamps 18W 30p elec bal 1lamp 36W 20 p elec bal 2 lamps 36W 20p elec bal 1lamp 58W 10 p elec bal 2 lamps 58W external through 6A Il protective insulation IP 20 100 m control wires 0 5 mm load and supply wires 1 5 mm screw type terminals for single wires or litz wires 0 3mm 1 5 mm or with 1 5 m cable bus 24 V DC 6V 4 V ElB power supply SELV Plastic housing for mounting on ceilings or lamp fixture louvres 2 dry non conducting according to IEC664 10 92 W x Hx D 58 5 x 70 5 x 42 mm approx 100 g CE EIB KNX see wiring diagrams Number of connectable electronic ballasts with 15 m cable of 1 5 mm from the distribution rack to the IBMSD and further 20 m to the midst of the load circuit impedance approx 800 mQ With greater cable diameters or shorter wires the permissible load would be reduced e g at an impedance of 400 mQ by 20 Wiring diagram 1 EIB MSD for the dimming and switching of a large area with additional controls for motion detection page 4 4 Operating Instructions Altenburger Electronic GmbH L Power supply 230V 50 60Hz I ey aa gh eer yea re ae PEL i Fi
8. rger Electronic GmbH Operating Instructions page 3 4 awn Potentiometer for the setting of the lagging time adjustable between 1 and 30 min Set pushbutton for the setting of the required brightness to be kept constant Light value exposure Learn pushbutton for programming of the physical address Programming LED Terminals also see wiring diagrams 6 Chassis OV 7 Bus 8 Bus 9 1 10V passive for electronic ballasts 10 Switch contact output 11 Switch contact input Technical Data Description and order number Operating temperature Selectable light values Angle of detection Height of assembly Control terminals Base insulation Load capacity control output Load terminals Wiring Load contact Load capacity of the control output Protection Protective class protective system Max cable length Wire connections EIB connections EIB supply Construction Contamination level Dimensions Weight Designation Wiring of terminals Multi sensor dimmer EIB KNX Type IBMSD Order No 80 14 800 approx 25 750 lux directly at the module equivalent to approx 50 1500 lux at the workplace approx 100 light and motion sensor 2 5m 3 0m 1 10V interface of ballasts or transformers according to IEC 664 10 92 not protective low voltage 50 mA approx 50 electronic ballasts or transformers see manufacturer s specifications switch c
Download Pdf Manuals
Related Search
Related Contents
Présentation NFPA 1500 Anexo F Información sobre EPP para Materiales Manuel d`instructions Lyophilisateur GAMMA 1 Tripp Lite DNET1 User's Manual STR-485 スター分配器 仕様書 Serie MG279 Monitor LCD Guida dell`utente Steam Mop User manual Model number: LSM4001 DOC TECHNIQUE ( 1204 Ko) Copyright © All rights reserved.