Home
Vinotemp VINO4500HZD User's Manual
Contents
1. WINE MATE Cooling Unit Use amp Care Manual VINO1500HZD VINO2500HZD VINO3500HZD VINO4500HZD VINO6500HZD VINO8500HZD V inotemp International Corp www winemate com READ AND SAVE THESE INSTRUCTIONS Important Safetv Information A WARNING To avoid the risk of electrical shock propertv damage personal injurv or death The power cord must be plugged into a 3 prong grounding type wall receptacle grounded in accordance with the National Electrical Code ANSI NFPA 70 latest edition and local codes and ordinances ltisthe personal responsibility of the consumer to have a proper 3 prong wall receptacle installed by a qualified electrician 795 GROUNDING TYPE WALL RECEPTACLE DONOT UNDER ANY CIRCUMSTANCES REMOVE THE POWER CORD GROUNDING PRONG Aseparate adequately fused and grounded circuit should be available for this appliance Donotremove any grounding wires from individual components while servicing unless the component is to be removed and replaced t is extremely important to replace all grounding wires when components replaced GROUNDING PLUG A WARNING ELECTRIC SHOCK HAZARD Disconnect electric supplv from appliance before servicing Replace all panels before operating Failure to do so could result in death or electrical shock e DO NOT PLUG IN UNTIL 24 HOURS AFTER
2. Complaint Possible Causes Response 1 Unit not a Power cord unplugged a Check for power cord plug running b No power to unit b Check power at receptacle amp fuses c Setting higher than ambient c Lower temperature setting temperature d Differential too high d Decrease the value as to 4 F e Incorrect or loose wirings e Check all wirings and connections f Low voltage f Contact an authorized electrician g Defrost light blinking g Unitis under defrost mode h Compressor light blinking h Unit waits for anti short cycle delay 2 Fan running a Post compressor fan running a See 4 to set FON 0 continually mode for humidity modulation 3 Temperature Air sensor a When using an air sensor the wine fluctuating bottle temperature is X mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature and turns off at 55 F of air temperature The average air temperature is 577F and then the wine temperature is around 57 0 5 The air is light enough to change so quickly that it maintains relatively constant average temperature that would prevent wine bottle temperature from varying 4 Temperature ja Displaying 55 F air sensor 8 Move the air sensor away from the high unit contacting the evaporator or in evaporator and supply air i the supply air stopping and b Lower setting short running time 5 Temperature a
3. Check compressor windings start relay and overload protector 7 Unit running mproper room insulation amp seal a Check for insulation gasket and too long door opening b Exhaust restricted b Leave minimum 3 feet clearance for the exhaust side and leave minimum 1 foot clearance for the fresh air intake side c Room too large c Check for excessive size or increase setting d Ambient temperature higher gt d Check for installation location or 90 F increase setting e Dirty Condenser e Clean condenser 8 Fan motor a Postcompressor fan running a Check for fan running time FON i mode running put b Incorrect power supply b Check for proper voltage c Incorrect or loose wirings c Check all wirings and connections not running d Failed components d Check start relay start capacitor overload protector compressor e Liquid refrigerant the Call service for OEM information compressor 9 Compressor ja Fan blade stuck a Check for proper clearance running but b Incorrect or loose wirings b Check all wirings fan not c Failed motors C Call service for checking open or shorted windings running 10 Evaporator a Evaporator air flow restriction a Check for fans lcing b Not stopping due to air leak high b Check for seal door opening ambient temperature or low ambient temperature and setting setting c Low ambient temperature c Defrost unit d Bad thermostat or sensor d Check for th
4. Incorrect voltage Check for voltage high b Failed thermistor b i i by placing it in ice water and measuring resistance compressor c Failed components c Check 1 start stopping and relav and overload protector starting but d Improper condenser airflow d Check for condenser fan short e Dirty condenser e Clean condenser running time f Overcharge of refrigerant f Call service for removing refrigerant g Discharge or suction pressure g Call service for OEM information too high 6 HA alarm a Improper room insulation amp seal a Check for insulation gasket and inki door opening ANN and b Room too large b Check for excessive size Ambient temperature too high c Gheck for installation location temperature jg Exhaust restricted d Leave minimum 3 feet clearance for high or not the exhaust side and leave cooling and minimum 1 foot clearance for the running fresh air intake side ti Il e Malfunctioning fans e Check for both evaporator and condenser fans f Improper evaporator or f Check for air restrictions condenser airflow g Dirty Condenser 9 Clean condenser h Iced evaporator h Defrost and reset temperature i Refrigeration system restriction i Call service for checking restrictions j Refrigerant leak j Call service for checking loss of refrigerant k Undercharge or overcharge k Call service to add or remove refrigerant l Failed components l
5. follows COOLING MODEL CAPACITY E IN ELECTRICAL ocn 55 F 75 F 55 F 75 F 1 8 D 14 25X13 25X 16 115V 60HZ 4A 50 1 00 14 25X13 25X 16 115V 60HZ 5A 55 La pos Ai 2 ind 14 25x19 75x21 25 115V 60Hz 6A 75 A DEED n d b 1 14 25x19 75x21 25 115V 60Hz 9A 75 Sen E ae rd 17x22x28 115V 60Hz 14A 110 erd pe 4 2 liri 17x22x28 115V 60Hz 16A 110 Fig 1 2 DIMENSIONS Installation Instruction WARNING Always check wiring harness connections before initiating any test proce dures Disconnect electric power from the appliance before performing any main tenance or repairs Voltage checks should be made by inserting meter probes beside the wires in the connector blocks with the electric power source on and the connec tor block plugged in Resistance checks should be made on components with the electric power off and the connector block disconnected Select a place to mount the unit where the exhaust airflow is unobstructed for a minimum of 6 inch The area into which the unit exhausts must be well ventilated If it is not heat exhausted by the unit will build up and the unit will not operate properly The ambient temperatures shall not be higher than 90 F or lower than 50 F Additionally cold supply air from the front grille must remain unobstructed The unit shall be mounted near the ceiling with e
6. shall have a vapor barrier and a minimum of R11 insulation All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation The vapor barrier shall be installed on the warm side of the insulation All joints door frames electrical outlets or switches and any pipes or vents that go through the enclosure shall be sealed to prevent air and moisture leakage into the room Concrete rock and brick are not insulation or vapor barriers Doors shall be of a minimum size insulated to at least R11 and tightly sealed with high qualitv weather stripping Be sure to seal the bottom of the door and fill gap between the door s frame and wall before installing the cap molding In order to maintain 55 F in the wine cellar the ambient temperature surrounding the enclosure shall not exceed the temperature of the enclosure bv more than 25 F No enclosure wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer to insure lights are not left on when the enclosure is not occupied The cooling system will not be able to maintain the proper temperature if fresh moisture laden air is constantly being introduced to the enclosure Symptoms of this condition are unit runs all the time with only a slight reduction in temperature and or water overflows from the unit Because of the temperature difference between the inside and outside very small cracks can allow large amounts of outside air to enter into the en
7. DELIVERY e DO NOT USE A GROUND FAULT INTERRUPTER GFI e A DEDICATED 15 OR 20 AMPCIRCUIT IS HIGHLY RECOMMENDED TABLE OF 5 Feature 3 Installation Instruction eee een nnne 5 Temperature Control amp Humidity Adjustment 12 G re 16 Troubleshootingi eic 17 Wiring Diagram i jj nei 20 Customer SUP POM ii i erect ero eee nenne lt lt oe Enn 22 Ao tm 23 Feature Description e HZD cooling unit is designed and used to provide a stable temperature between 50 65 F for suitable space at a normal environment e The refrigerated space will maintain humidity of 50 70 RH even when the environment becomes drv and humid e These temperatures and humilities are optimized for long term storage of wine fur and tobacco e Horizontal cold air supply is optimized for use in the wide cabinets or wine rooms e Self contained ready for use and easy for installation 1 COLD AIR SUPPLY 2 RETURN AIR INTAKE 3 AMBIENT AIR INTAKE 4 HOT AIR REAR EXHAUST 5 HOT AIR TOP EXHAUST OPTION 6 DIGITAL CONTROLLER 7 POWER CORD m ig 1 1 FEATURE DESCRIPTIONS e See the voltage frequency and current from the label on the back side of the cooling unit The dimension and capacity are specified as
8. II outputs OFF i1F bAL 2 2 Alarm Recovery Probe alarms P1 start a few seconds after the fault in the related probe they automatically stop a few seconds after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA automatically stops as soon as the temperature returns to normal value Alarm CA with i1 FZPAL recovers only by switching off and on the instrument 3 Temperature Set Point 3 1 How to see the set point 1 Push and immediately release the SET key the display will show the Set point value 2 Push and immediately release the SET key or wait for 5 seconds to display the probe value again 3 2 How to change the set point 1 Push the SET key for more than 3 seconds to change the Set point value 13 2 The value of the set point will be displaved and the LED starts blinking To change the Set value push the keys 4 or arrows within 10s 4 To memorize the new set point value push the SET kev again or wait 10s 4 Humiditv Adjustment The parameter Fon is used to adjust the humiditv in the wine cabinet The higher value of Fon the higher relative humiditv will be 1 Press the Set keys for sec until the C or F LED starts blinking 2 Release the keys then push again the Set keys for more than 7sec the Pr2 label will be displaved 3 Release the keys select the required parameter F
9. OWER LINE N CAPACITOR DIGITAL CONTROLLER TEMP PROBE FANS COND FANS e THERMAL PROTECTOR ORANGE Z GROUND GROUND lt lt lt L POWER LINE N CAPACITOR FANS DIGITAL CONTROLLER TEMP PROBE COND FANS e Fig 6 4 VINO3500 8500HZD Call Feature Wiring Diagram Customer Support If vou still have problems please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com 22 Warrantv Thank vou for choosing a Vinotemp cooling unit Please enter the complete model and serial numbers in the space provided Model Serial No Attach your purchase receipt to this owner s manual 1 Limited Warrantv VINOTEMP warrants its products to be free from defects due to workmanship or materials under normal use and service for twelve months after the initial sale If the product is defective due to workmanship or materials is removed within twelve months of the initial sale and is returned to VINOTEMP in the original shipping carton shipping prepaid VINOTEMP will at its option repair or replace the product free of charge Additionally VINOTEMP warrants all parts to be free from defects for a period of sixtv months after initial sale This warrantv constitutes the entire warrantv of the VINOTEMP with respect to its pro
10. Warrantv VINOTEMP S SOLE LIABILITV FOR ANY DEFECTIVE PRODUCT IS LIMITED TO AT OUR OPTION REPAIRING OR REPLACING OF UNIT VINOTEMP SHALL NOT BE LIABLE FOR DAMAGE TO OTHER PROPERTY CAUSED BY ANY DEFECTS IN THE UNIT DAMAGES BASED UPON INCONVENIENCE LOSS OF USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to properly cool particular enclosure Customers are cautioned that enclosure construction unit location and many other factors can affect the operation and performance of the unit There for suitability of the unit for specific enclosure or application must be determined by the customer and cannot be warranted by VINOTEMP 24
11. closure Please be aware that moisture can pass through solid concrete paint and wood Often a newly constructed room contains fresh wood paint concrete and other building materials These materials contain large amounts of moisture When placed into operation in this type of environment the system will work harder to remove this extra moisture resulting in increased run time 4 Electrical Cord Because of potential safety hazards under a certain condition we strongly recommend against the use of an extension cord However if you still select to use an extension cord it is absolutely necessary that it is a UL LISTED 3 wire grounding type appliance extension cord having a 3 blade grounding plug and a 3 slot receptacle that will plug into the appliance The marked rating of the extension cord shall be 115 V 15 A or equivalent for VINO1500 2500HZD 115 V 20 A or equivalent for VINO3500 8500HZD and not greater than 15ft in length NOTES 1 DO NOT INSTALL ANY DUCTS ONTO THE SUPPLY INTAKE ANY EXHAUST 2 MOUNTING BRACKETS SCREWS GASKETS AND OTHER SEAL MATERIALS ARE NOT INCLUDED 11 Temperature Control amp Humidity Adjustment 1 Temperature Setting e Set the temperature at 55 F for the optimum aging of wine e On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature e Allow 24 hours to stabilize the temp
12. ducts and is in lieu of all other warranties express or implied including anv of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification or unauthorized repair of VINOTEMP products shall void this warranty Service under Warranty This service is provided to customers within the continental UNITED STATES only VINOTEMP cooling units are warranted to produce the stated number of BTU H While every effort has been made to provide accurate guidelines VINOTEMP can not warranty its units to cool particular enclosure In case of failure VINOTEMP cooling units must be repaired by the factory or its authorized agent Repairs or modifications made by anyone else will void the warranty Shall VINOTEMP cooling unit fail contact the dealer for instructions do not return the unit to the factory without authorization from VINOTEMP If the unit requires repair re pack it in the original shipping carton and return it to the factory shipping prepaid VINOTEMP will not accept COD shipments If the unit 23 is determined to be faultv and is within the twelve month warrantv period VINOTEMP mill at its discretion repair or replace the unit and return it free of charge to the original retail customer If the unit is found to be in good working order or bevond the initial twelve month period it will be returned freight collect 2 Limitation of Implied
13. erature for each new temperature setting operation 2 Use of the controller Fig 3 1 DIGITAL CONTROLLER 1 Display During normal operating conditions the display shows the value measured by the air regulation probe In case of active alarm the temperature flashes alternately to the code alarm 1 1 LED Functions MODE FUNCTION Compressor enabled Flashing Anti short cvcle delav enabled Defrost enabled COS CLI ON JMeasurementunit C F Flashing Programming phase za gt 464 m c o 1 2 Front Panel Commands 12 SET display target set point in programming mode it selects parameter or confirm an operation DEF start manual defrost A UP To see the max stored temperature in programming mode it browses the parameter codes or increases the displayed value DOWN To see the min stored temperature in programming mode it browses the parameter codes or decreases the displayed value To turn OFF the controller if enabled KEV COMBINATIONS A To lock amp unlock the keyboard SET I To enter in programming mode SET A To retum to the room temperature display 2 Alarm Signals 2 1 Code Description Mee ca om _ Room probe failure Compressor output to par and COF HA Maximum temperature alarm Outputs unchanged LA Minimum temperature alarm Outputs unchanged CA E Serious external alarm A
14. ermostat and sensor e Moisture in the system e Working initially then stopping f Refrigerant low or leaking f Check for current and sealed system leakage 9 Capillary tube blockage g Check for low side pressure 11 Water leak a High humidity a Use drain line b Air leak in wine cellar b Check for any air leak c Evaporator air flow restriction c Check air flow or air TD crossing evaporator d Water passages restricted d Clean the drip tray e Drip tray leak e No water overflow but leak 12 Circuit a Incorrect fuse or breaker a Check for proper fuse or breaker tripping b Incorrect wirings b Check for wirings and connections c Failed components c Call service 13 Noisy a Mounting area not firm a Add support to improve installation operation b Loose parts b Check fan blades bearings cabinet washers tubing contact and loose Screws c Compressor overloaded due to c Check for airflow blockage high ambient temperatures or airflow restriction d Malfunctioning components d Call service for checking internal loose inadequate lubrication and incorrect wirings Wiring Diagram THERMAL PROTECTOR GROUND GROUND L POWER LINE N DIGITAL CUNTROLLER ORANGE Z GROUND GROUND SL L POWER LINE N Fig 6 2 VINO1500 2500HZD CALLING FEATURE WIRING DIAGRAM 20 THERMAL PROTECTOR GROUND GROUND zr L P
15. ig 2 5 COOLING UNIT MOUNT BRACKET MOUNT SCREW Fig 2 6 FASTENING BRACKET amp SCREW Fig 2 7 CABINET GRILLE VINO3500 8500HZD THROUGH WALL INSTALLATION Cut a rectangular opening at the wine room wall as illustrated The dimensions of the opening shall be 1 4 larger than the width and height of the unit If top exhaust cut another rectangular opening at the top of the cabinet to the length and width of the top exhaust Construct a shelf as shown The shelf must be capable of supporting the weight of the unit Place the unit on the shelf with the back of unit flush with the outside of the wall Attach the grille to the outside wall with screws Seal the area between the cooling unit and opening with a high qualitv weather stripping or polvurethane sprav foam and cover with molding If top exhaust place another gaskets along the top exhaust at the top of the cooling unit see Fig 2 9 Attach the molding to the wall not the unit Plug the unit into a properly grounded and dedicated outlet of adequate capacitv AIR GEILING EXHAUST COLD AIR GRILLE SUPPLY 36 CLEARANCE FRESH AIR IRN INTAKE SUPPORT SHELF Wa FRONT VIEW SIDE VIEW Fig 2 8 THROUGH WALL INSTALLATION GASKET Fig 2 9 TOP EXHAUST GASKET 3 Cellar Construction This is only guide and shall be considered as minimum requirements All interior walls and floors
16. on by up or down keys A 7 4 Press the SET to displav its value 5 Use up or down keys 4 to change its value 6 The default value is 0 change high or low value to maintain high or low humidity 7 Press SET to store the new value 8 To exit Press SET amp or wait 15sec without pressing a key 5 Regulation Differential The parameter Hy is used as intervention differential for set point Compressor cut in is the set point 4 Hy and compressor cut out is the set point 1 Press the Set keys for sec until the C or F LED starts blinking 2 Release the keys then push again the Set keys for more than 7sec the Pr2 label will be displayed 3 Release the keys HY will display immediately 4 Press the SET key to display its value 5 Use up or down keys 4 to change its value 6 The default value is 4 change high or low value to result in long high or short running cycle 7 Press SET to store the new value 8 To exit Press SET 4 or wait 15sec without pressing a key 6 Defrost Cycle The parameter IdF is used as interval between defrost cycles 1 Press the Set keys for sec until the C or F LED starts blinking 2 Release the keys then push again the Set keys for more than 7sec the Pr2 label will be displayed Release the keys select the required parameter IdF by up or down keys A 4 Press the SET key to display its value 5 U
17. qual distance from each side of the cabinet or room The cooling unit produces cooling supplied into the cabinet and it also generates heat that must be exhausted outside the cabinet So the supply side and exhaust side must be separated and sealed 1 VINO1500 2500HZD CABINET INSTALLATION Cut a rectangular inside opening with the 1 4 clearance inwards to the width and height of the cooling unit By not going through leave 1 2 lip inside at the wall to place the gaskets see Fig 2 1 amp 2 2 If top exhaust cut another rectangular opening at the top of the cabinet to the length and width of the top exhaust Make 2 holes at the ceiling to install the 1 4 inside diameter wood thread inserts see Fig 2 1 amp 2 4 Place the gaskets 1 2 foam tape on the mounting lip sides see Fig 2 2 If top exhaust place another gaskets along the top exhaust at the top of the cooling unit see Fig 2 3 Move the cooling unit towards the mounting sides and push to press the gaskets see Fig 2 5 Fasten the 2 brackets and use 7 16 wrench to tighten the two 14 screws see Fig 2 6 Attach the exhaust and fresh air grille from the rear side of the cellar see Fig 2 7 Plug the cooling unit in receptacle Plug the wine cellar HOLES FOR THREAD INSERT 16 75 REAR WALL QUTSIDE Fig 2 2 GASKET GASKET Fig 2 3 TOP EXHAUST GASKET 0 25 THREAD INSERT Fig 2 4 THREAD INSERT COOLING UNIT F
18. se up or down keys fa to change its value 6 The default value is 24 change high or low value to result in less or more defrost cycle 7 Press SET to store the new value 8 To exit Press SET amp or wait 15sec without pressing a key 7 Manual Defrost Push the DEF key for more than 2 seconds and a manual defrost will start 15 Care Guide 1 Coil Cleaning e Clean the condenser coil regularly may need to be cleaned at least everv 6 months Coil is on the ambient air intake side of the cooling unit e Unplug the unit or disconnect power e Use a condenser brush or a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty Plug the cooling unit or reconnect power 2 Moisture Removing Remove the extra condensate if it is accumulated in the wine cellar at high humidity condition 3 Drain Line VINO3500 8500HZD units are equipped with a drain line fitting In case there is a drain line needed remove the drain plug on the bottom left at the rear then remove the fitting plug add a drain tube onto the drain fitting 0 25 ID tube for VINO3500 4500HZD and 0 5 ID tube for VINO6500 8500HZD DRAN FITTING FITTING PLUG DRAN PLUG 16 Troubleshooting This Troubleshooting Chart is not prepared to replace the training required for a professional refrigeration service person not is it comprehensive Troubleshooting Chart
Download Pdf Manuals
Related Search
Related Contents
Edbak PWB2 Life Fitness 39735 Home Gym User Manual User Guide Guide De L'Utilisateur Guia Para El Usuario Sony Qualia 006 User's Manual Husqvarna 324LX-Series Chainsaw User Manual D-Link DI-824VUP User's Manual The Sybari Enterprise Manager - Center IC-Emc User's Manual - Insa Copyright © All rights reserved.
Failed to retrieve file