1. Air Conditioning Clinic Refrigeration Compressors One of the Fundamental Series TRG TRC004 EN BUSINESS REPLY MAIL FIRST CLASS MAIL PERMIT NO 11 LA CROSSE WI POSTAGE WILL BE PAID BY THE TRANE COMPANY Attn Applications Engineering 3600 Pammel Creek Road La Crosse WI 94601 9985 BUSINESS REPLY MAIL FIRST CLASS MAIL PERMIT NO 11 LA CROSSE WI POSTAGE WILL BE PAID BY THE TRANE COMPANY Attn Applications Engineering 3600 Pammel Creek Road La Crosse WI 94601 9985 NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES Crop to width of 7 75 abpea wo SZ 0 UONeIOLed doi wio 10q WO G G UOI eJOH d Comment Card We want to ensure that our educational materials meet your ever changing resource development needs Please take a moment to comment on the effectiveness of this Air Conditioning Clinic Refrigeration Compressors Level of detail circle one Too basic Just right Too difficult One of the Fundamental Series Rate this clinic from 1 Needs Improvement to 10 Excellent TRG TRC004 EN Content 1 2 3 4 5 6 7 8 9 10 Booklet usefulness 1 2 3 4 5 6 Z 8 9 10 Slides illustrations 1 Za 3 4 5 6 7 8 9 10 Presenter s ability 1 2 3 4 5 6 7 8 9 10 Training environment 1 2 3 4 5 6 74 8 9 10 Other comments About me Type of business Job function Optional name phone address Give the completed card to the
2. 0 kW 20 F 30 F 40 F 50 F 6 7 C 1 1 C 4 4 C 10 C suction temperature In the case of comfort cooling applications however the load generally changes slowly in small intervals For example assume that the load decreases from 28 tons 98 5 kW B to 25 tons 88 kW In response to the decreasing load the compressor unloads to C on the four cylinder capacity curve where it has a pumping capacity equivalent to 19 tons 66 8 kW The 25 ton 88 kW evaporator load causes the suction temperature to rise and the capacity of the compressor increases toward D When the load reaches D the compressor reloads the first set of two cylinders and the compressor capacity jumps to 31 tons 109 kW Because at this point the available compressor capacity exceeds the evaporator load the suction temperature decreases toward B where the compressor is again unloaded to C From this example it becomes obvious that the compressor and evaporator cannot reach a balance point while the evaporator load remains between these stages of compressor loading This example compressor can produce a pumping capacity of 28 tons 98 5 kW B with six cylinders loaded or 22 tons 77 4 kW D with four cylinders loaded It cannot exactly match the 25 ton 88 kW evaporator load As long as the evaporator load remains between the Capacities produced by four and six cylinders the compressor will alternate between the two stages of loading in an effort to produ
3. A similar 40 ton 140 6 kW unit using scroll compressors would include four separate 10 ton 35 2 kW scroll compressors Just as the reciprocating compressor unloads in equal intervals by unloading a pair of cylinders the scroll compressor unit unloads in the same 10 ton 35 2 kW intervals by shutting off individual compressors TRG TRC004 EN TRG TRC004 EN S TRANE period two Compressor Capacity Control Cycling Scroll Compressors A S SSO 40 tons B A corner 140 7 kW i vy egsot D 9 core IC resso Si 20 tons F z come G 70 3 kW 7 E P ese H v x cone G 0 tons 0 kW 20 F 30 F 40 F 50 F 6 7 C 1 1 C 4 4 C 10 C suction temperature At design conditions the capacities of the evaporator and this four compressor unit balance at a suction temperature of 43 F 6 1 C and a capacity of 44 tons 154 7 kW A As the cooling load decreases below this balance point assuming a constant condensing pressure the capacity of the unit decreases with the falling suction temperature along the four compressor curve until it reaches B Here the first scroll compressor is shut off and the capacity of the unit decreases immediately to 30 tons 105 5 kW C along the three compressor curve As the load continues to decrease the individual compressors shut off in a similar manner until the suction temperature reaches a minimum set point and the final compressor is shut off The minimum capacity of the four co
4. liquid refrigerant absorbs heat from air water or some other fluid causing the refrigerant to boil expansion device A component of the refrigeration system used to reduce the pressure and temperature of the refrigerant to the evaporator conditions flash The process of liquid refrigerant being vaporized by a sudden reduction of pressure heat of compression The amount of heat added to the refrigerant vapor by the compressor during the process of raising the pressure of the refrigerant to condenser conditions helical rotary compressor A type of compressor that uses two mated rotors to trap the refrigerant vapor and compress it by gradually shrinking the volume of the refrigerant hermetic compressor A type of compressor that has the motor sealed within the compressor housing The motor is cooled by refrigerant hot gas bypass A method used to prevent evaporator freeze up by diverting hot high pressure refrigerant vapor from the discharge line to the low pressure side of the refrigeration system impeller The rotating component of a centrifugal compressor that draws refrigerant vapor into its internal passages and accelerates the refrigerant as it rotates increasing its velocity and kinetic energy inlet vanes A device used to vary the capacity of a centrifugal compressor by oreswirling the refrigerant in the direction of rotation before it enters the impeller lessening its ability to take in the refrigerant vapor liqui
5. S TRANE period two Compressor Capacity Control variable speed drive Variable Speed Alternatively the capacity of a compressor can be controlled by varying the rotational speed of the compressor motor This is accomplished using a device called an adjustable frequency drive AFD or variable speed drive On a reciprocating compressor this would vary the speed at which the crankshaft rotates thus controlling the rate at which the piston travels back and forth inside the cylinder On a scroll compressor this would vary the speed at which the driven scroll rotates If applied to a helical rotary compressor this would vary the speed at which the rotors rotate Applied to a centrifugal compressor this would vary the speed at which the impeller rotates Although variable speed capacity control could be applied to all four types of compressors discussed in this clinic it is most often applied to centrifugal compressors Because speed variation reduces both the flow rate of refrigerant through the compressor and the pressure differential created by the compressor it is used in conjunction with inlet vanes This requires fairly complex control strategies to balance refrigerant flow rate pressure differential and load 29 30 period three The Compressor in a System Refrigeration Compressors period three The Compressor in a System Period Two presented several methods used to control the capacity of a compressor T
6. Types Helical Rotary Compressor meshing point discharge port Viewing the compressor from the opposite side shows that continued rotation of the meshed rotor lobes drives the trapped refrigerant vapor to the right toward the discharge end of the compressor ahead of the meshing point This action progressively reduces the volume of the pockets compressing the refrigerant Finally when the pockets of refrigerant reach the discharge port the compressed vapor is released and the rotors force the remaining refrigerant from the pockets Helical Rotary Compressor Tac opening f b slide valve motor rotors discharge opening In this example helical rotary compressor refrigerant vapor is drawn into the compressor through the suction opening and passes through the motor cooling it The refrigerant vapor is drawn into the compressor rotors where itis compressed and discharged out of the compressor TRG TRC004 EN TRG TRC004 EN S TRANE period one Compressor Types In the air conditioning industry helical rotary compressors are most commonly used in water chillers ranging from 70 to 450 tons 200 to 1 500 kW Centrifugal Compressor impeller Centrifugal Compressor The centrifugal compressor uses the principle of dynamic compression which involves converting energy from one form to another to increase the pressure and temperature of the refrigerant It converts kinetic energy velo
7. a 43 Answers ages cage tases 44 Glossary ereere 45 TRG TRC004 EN lil TRG TRC004 EN Introduction Vapor Compression Refrigeration expansion device 4 compressor evaporator The purpose of the compressor in a refrigeration system is to raise the pressure of the refrigerant vapor from evaporator pressure to condensing pressure It delivers the refrigerant vapor to the condenser at a pressure and temperature at which the condensing process can be readily accomplished at the temperature of the air or other fluid used for condensing A review of the refrigeration cycle using the pressure enthalpy chart will help to illustrate this point TRG TRC004 EN Introduction Refrigeration Cycle J condenser D F D i 3 expansion a device compressor So a A evaporator enthalpy The pressure enthalpy P h chart plots the properties of a refrigerant refrigerant pressure vertical axis versus enthalpy or heat content horizontal axis A diagram of the basic vapor compression refrigeration cycle can be superimposed on a pressure enthalpy chart to demonstrate the function of each component in the system Refrigerant enters the evaporator in the form of a cool low pressure mixture of liquid and vapor A Heat is transferred from the relatively warm air or water to be cooled to the refrigerant causing the liquid refrigerant to boil and in some cases superheat B Th
8. presenter or drop it in the mail Thank you r E The Trane Company Worldwide Applied Systems Group 3600 Pammel Creek Road La Crosse WI 54601 7599 www trane com An American Standard Company Response Card We offer a variety of HVAC related educational materials and technical references as well as software tools that simplify system design analysis and equipment selection To receive information about any of these items just complete this postage paid card and drop it in the mail Education materials J Air Conditioning Clinic series About me LJ Engineered Systems Clinic series Name L Trane Air Conditioning Manual Tite 0 J Trane Systems Manual Business type o o s o non o o Software tools L Equipment Selection Phone fax 2 LI System design amp analysis E mail address SS Periodicals L Engineers Newsletter Company 2 Other Ld Address S TRANE The Trane Company Worldwide Applied Systems Group 3600 Pammel Creek Road La Crosse WI 54601 7599 www trane com Thank you for your interest An American Standard Company Refrigeration Compressors One of the Fundamental Series A publication of The Trane Company Worldwide Applied Systems Group Preface Refrigeration Compressors A Trane Air Conditioning Clinic The Trane Company believes that it is incumbent on manufacturers to serve the industry by regularly disseminating information gathered through laboratory re
9. refer to the following references Trane Air Conditioning Manual Trane Reciprocating Refrigeration Manual Helical Rotary Water Chillers Air Conditioning Clinic Trane literature order number TRG TRC0O12 EN Centrifugal Water Chillers Air Conditioning Clinic Trane literature order number TRG TRCO10 EN Hot Gas Bypass Control Applications Engineering Manual Trane literature order number AM CON10 ASHRAE Handbook Refrigeration ASHRAE Handbook Systems and Equipment Visit the ASHRAE Bookstore at www ashrae org For more information on additional educational materials available from Trane contact your local Trane office request a copy of the Educational Materials catalog Trane order number EM ADV1 or visit our online bookstore at www trane com bookstore TRG TRC004 EN 41 42 TRG TRC004 EN S TRANE Quiz Questions for Period 1 1 What is the purpose of the compressor in a refrigeration system 2 List the four primary types of compressors used in air conditioning applications 3 What causes the suction valve to open on a reciprocating compressor 4 True or False The intake of refrigerant vapor in a scroll compressor occurs at the outer edge of the scroll assembly and discharge occurs through the port at the center of the scroll 5 What is the term for the type of compressor that has the motor sealed within the compressor housing Questions for Period 2 6 Assuming a constant condensing temperatu
10. 19 20 period two Compressor Capacity Control Cylinder Unloaders 0o controller unloader solenoid valve unloader valve refrigerant discharge vapor In response to an increasing load the controller sends a signal to close the solenoid valve This closes the port that allows the pressurized refrigerant vapor to travel to the top of the unloader valve A controlled leakage rate around the unloader valve relieves the pressure allowing the valve to open and refrigerant vapor to once again flow to the cylinder to be compressed Another type of cylinder unloader uses either pressure or electrically actuated valving mechanisms to hold open the suction valve of the piston cylinder pair Since the suction valve is prevented from closing no compression occurs in that cylinder and the discharge valve does not open Still other types of cylinder unloaders divert the compressed refrigerant vapor back to the suction side of the compressor In contrast to the cylinder unloaders shown these other methods expend energy in moving refrigerant vapor during both the upward and downward piston strokes within the unloaded cylinders TRG TRC004 EN S TRANE period two Compressor Capacity Control Capacity Versus Suction Temperature 40 tons Aer 140 7 kW 6 RN ade NAS Lat N o O 20tons ETAG Q ros N 0 tons 0 kW 20 F 30 F 40 F 50 F 6 7 C 1 1 C 4 4 C 10 C suction temperature A plot of
11. Compressor refrigerant enters diffuser 5 ab gt T erant EE ieni sag enters volute 5 _ enters impeller P L ox Oo T Dn path through compressor This chart plots the conversion of energy that takes place as the refrigerant passes through the centrifugal compressor In the radial passages of the rotating impeller the refrigerant vapor accelerates increasing its velocity and kinetic energy As the area increases in the diffuser passages the velocity and therefore the kinetic energy of the refrigerant decreases This reduction in kinetic energy velocity is offset by an increase in the refrigerant s static energy or static pressure Finally the high pressure refrigerant collects in the volute around the perimeter of the compressor where further energy conversion takes place Centrifugal Compressor inlet vanes suction impeller In this example centrifugal compressor refrigerant vapor is drawn into the compressor and enters the center of impeller This particular centrifugal compressor uses multiple impellers to perform the compression process in stages The impellers rotate on a common shaft that is connected to the motor 15 16 period one Compressor Types In the air conditioning industry centrifugal compressors are most commonly used in prefabricated water chillers ranging from 100 to 3 000 tons 350 to 10 500 kW They are also used in field assembled water chillers up to 8 500 to
12. RG TRC004 EN S TRANE period two Compressor Capacity Control Slide Valve discharge port slide valve open slide valve closed to suction valve opening full load part load At full load the slide valve is closed The compressor pumps its maximum volume of refrigerant discharging it through the discharge port As the load on the compressor decreases the slide valve modulates toward the open position The opening created by the valve movement allows refrigerant vapor to bypass from the rotor pockets back to the suction side of the compressor This reduces the volume of vapor available for the compression process It also reduces the amount of rotor length available for compression In this manner the volume of refrigerant that is pumped by the compressor is varied unloading it to balance the existing load Inlet Vanes inlet vanes impeller Inlet Vanes A common method of modulating the capacity of a centrifugal compressor is to use a set of vanes installed at the inlet of the compressor impeller While a survey of other centrifugal compressor designs shows that there are other 27 period two Compressor Capacity Control methods of capacity control many of them function in a manner similar to the inlet vanes presented in this section of the clinic Inlet vanes preswirl the refrigerant before it enters the impeller By changing the refrigerant s angle of entry th
13. a constant volume of air supplied to meet the changing load conditions of the space cycling The practice of turning a compressor on and off to match the system load cylinder unloader A device used to unload the capacity of a reciprocating compressor by either closing the suction passage to the cylinder holding open the suction valve of a piston cylinder pair or diverting the compressed refrigerant vapor back to the suction side of the compressor diffuser passages Passages inside the centrifugal compressor that start out small and become larger as the refrigerant travels through them As the size of the diffuser passages increases the velocity and therefore the kinetic energy of the refrigerant decreases This kinetic energy is converted to static energy or static pressure direct expansion DX system Uses the refrigerant directly as the cooling media The refrigerant inside the evaporator absorbs heat directly from the air used for space conditioning discharge line A pipe that transports refrigerant vapor from the compressor to the condenser in a mechanical refrigeration system dynamic compression A method of compression that involves converting energy from one form to another to increase the pressure and temperature of the refrigerant vapor enthalpy A measure of heat quantity both sensible and latent per pound kg of refrigerant 45 46 Glossary evaporator A component of the refrigeration system where cool
14. ally shrinking the volume of the refrigerant semihermetic compressor A type of compressor that has the motor sealed within the compressor housing The sealed housing may be opened to repair or overhaul the compressor or motor slide valve The part of the helical rotary compressor used to vary the flow rate of refrigerant vapor through it suction line A pipe that transports refrigerant vapor from the evaporator to the compressor in a mechanical refrigeration system variable air volume VAV system A type of air conditioning system that varies the volume of constant temperature air supplied to meet the changing load conditions of the space variable speed drive See adjustable frequency drive volute A large space around the perimeter of a centrifugal compressor that collects refrigerant vapor after compression 47 Literature Order Number TRG TRC004 EN S TRANE P File Number E AV FND TRG TRC004 0200 EN The Trane Company Worldwide Applied Systems Group Supersedes 2803 2 385 and 2803 13 587 3600 Pammel Creek Road i La Crosse WI 54601 7599 Stocking Location Inland La Crosse www trane com An American Standard Company Since The Trane Company has a policy of continuous product improvement it reserves the right to change design and specifications without notice
15. ce an average capacity of 25 tons 88 kW Alternating between these stages of loading does not harm the reciprocating compressor The only time it should be avoided is when the compressor must cycle between off and on to balance a load that is less than the minimum stage of compressor loading Excessive starting and stopping of large reciprocating compressor motors is generally discouraged due to the mechanical wear on a motor of that size TRG TRCO004 EN 23 S TRANE 24 period two Compressor Capacity Control Cycling On and Off Cycling On and Off Scroll compressors do not have valves or unloaders A piece of equipment that uses scroll compressors generally unloads by using multiple compressors and turning them on and off as needed to satisfy the evaporator load Cycling Scroll Compressors reciprocating scroll of of cylinders nominal compressors nominal step active capacity active capacity 1 2 10 tons 1 10 tons 35 kW 35 kW 2 4 20 tons 2 20 tons 70 kW 70 kW 3 6 30 tons 3 30 tons 105 kW 105 kW 4 8 40 tons 4 40 tons 140 kW 140 kW Cycling multiple scroll compressors is very similar to the use of cylinder unloaders on a single reciprocating compressor As an example a large 40 ton 140 6 kW reciprocating compressor may have eight cylinders with unloaders on six of them allowing it to unload in equal steps of 10 tons 35 2 kW each with a minimum nominal capacity of 10 tons 35 2 kW
16. city to static energy pressure The core component of a centrifugal compressor is the rotating impeller 13 S TRANE 14 period one Compressor Types Centrifugal Compressor volute diffuser passages radial impeller passages blades impeller The center or eye of the impeller is fitted with blades that draw refrigerant vapor into radial passages that are internal to the impeller body The rotation of the impeller causes the refrigerant vapor to accelerate within these passages increasing its velocity and kinetic energy The accelerated refrigerant vapor leaves the impeller and enters the diffuser passages These passages start out small and become larger as the refrigerant travels through them As the size of the diffuser passage increases the velocity and therefore the kinetic energy of the refrigerant decreases The first law of thermodynamics states that energy is not destroyed only converted from one form to another Thus the refrigerant s kinetic energy velocity is converted to static energy or static pressure Refrigerant now at a higher pressure collects in a larger space around the perimeter of the compressor called the volute The volute also becomes larger as the refrigerant travels through it Again as the size of the volute increases the kinetic energy is converted to static pressure TRG TRC004 EN TRG TRC004 EN S TRANE period one Compressor Types Centrifugal
17. compressor capacity versus suction temperature assuming a constant condensing temperature reveals that the capacity of the compressor increases as the suction temperature increases As the suction temperature and therefore the suction pressure increases the refrigerant vapor becomes denser A greater quantity of refrigerant can be compressed in a given compression cycle and the capacity of the compressor is higher For an example nominal 30 ton 105 kW reciprocating compressor that has six cylinders Figure 31 shows the capacity produced by the various stages of unloading Four of the six cylinders are equipped with unloaders and two cylinders are unloaded as a pair The compressor therefore can operate with all six cylinders loaded with four cylinders loaded with only two cylinders loaded or it can shut off Again these capacity curves assume the compressor is operating at a constant condensing discharge pressure TRG TRC004 EN 21 S TRANE period two Compressor Capacity Control Compressor Unloading 40 tons EA 140 7 kW 6 oh here NS Ko oO 20tons XS nde S 70 3 kW A E F 0 tons 0 kW 20 F 30 F 40 F 50 F 6 7 C 1 1 C 4 4 C 10 C suction temperature At design conditions the capacities of the evaporator coil and compressor balance A at a suction temperature of 45 F 7 2 C and a capacity of 31 tons 109 kW As the cooling load decreases below this balance point assumi
18. compressors eliminate the need for the shaft couplings and external shaft seals that are associated with open motors The coupling needs precise alignment and these seals are a prime source of oil and refrigerant leaks On the other hand if a motor burns out a system with a hermetic compressor will require thorough cleaning while a system with an open compressor will not Semihermetic Compressor compressor crankshaft motor housing Similarly the motor for a semihermetic compressor is also contained within the compressor housing and is cooled by the refrigerant The term semihermetic means that the sealed housing is designed to be opened to repair or overhaul the compressor or motor 17 S TRANE period two Compressor Capacity Control Refrigeration Compressors period two Compressor Capacity Control The capacity of a compressor is defined by the volume of evaporated refrigerant that can be compressed within a given time period The compressor needs a method of capacity control in order to match the ever changing load on the system Methods of Compressor Unloading 4 Reciprocating Cylinder Unloaders a Scroll Cycle On and Off a Helical Rotary Slide Valve a Centrifugal Inlet Vanes Variable Speed Capacity control is commonly accomplished by unloading the compressor The method used for unloading generally depends on the type of compressor Many reciprocating compressors use cylinder unloaders Scroll com
19. cycling This control scheme referred to by Trane as FROSTAT is especially well suited for equipment using scroll compressors which are designed to start and stop much more often than large reciprocating compressors TRG TRC004 EN TRG TRC004 EN TRANE period three The Compressor in a System Hot Gas Bypass to Evaporator Inlet q LE expansion valve enh liquid line hot gas bypass valve e E sn compressor oil return line Hot gas bypass may be another solution for preventing evaporator frosting in DX applications Hot gas bypass diverts hot high pressure refrigerant vapor from the discharge line to the low pressure side of the refrigeration system This added false load helps to maintain an acceptable suction pressure and temperature Hot gas bypass however fails to reduce energy consumption because it does not allow the compressor to shut off at these low load conditions In a DX application there are two bypass methods used The first method bypasses refrigerant vapor from the compressor discharge line to the inlet of the evaporator coil Sensing a decrease in suction pressure a pressure actuated valve opens to bypass hot refrigerant vapor from the compressor discharge line to the inlet of the evaporator coil between the expansion valve and the liquid distributor This increases the rate at which liquid refrigerant is boiled off within the evaporator coil and causes the temperature of th
20. d line A pipe that transports refrigerant vapor from the condenser to the evaporator in a mechanical refrigeration system open compressor A type of compressor that is driven by an external power source such as an electric motor or a turbine The motor is coupled to the compressor crankshaft by a flexible coupling and a seal is used to prevent refrigerant from leaking out of the compressor housing ported compressor A type of compressor where the refrigerant vapor enters and exits through ports no valves are used positive displacement compressor A class of compressors that works on the principle of trapping the refrigerant vapor and compressing it by gradually shrinking the volume of the refrigerant pressure enthalpy chart A graphical representation of the properties of a refrigerant plotting refrigerant pressure versus enthalpy TRG TRC004 EN TRG TRC004 EN S TRANE Glossary reciprocating compressor A type of compressor that uses a piston that travels up and down inside a cylinder to compress the refrigerant vapor refrigerant A substance used to absorb and transport heat for the purpose of cooling rotor The part ofthe helical rotary compressor used to trap and compress the refrigerant vapor The male and female rotors mesh together forming pockets of refrigerant to move through the compressor scroll compressor A type of compressor that uses two opposing scrolls to trap the refrigerant vapor and compress it by gradu
21. discharge valve suction valve refrigerant piston vapor cylinder Reciprocating Compressor The first type of compressor to be discussed is the reciprocating compressor The principles of operation for all reciprocating compressors are fundamentally the same The refrigerant vapor is compressed by a piston that is located inside a cylinder similar to the engine in an automobile A fine layer of oil prevents the refrigerant vapor from escaping through the mating surfaces The piston is connected to the crankshaft by a rod As the crankshaft rotates it causes the piston to travel back and forth inside the cylinder This motion is used to draw refrigerant vapor into the cylinder compress it and discharge it from the cylinder A pair of valves the suction valve and the discharge valve are used to trap the refrigerant vapor within the cylinder during this process In the example reciprocating compressor shown the spring actuated valves are O shaped allowing them to cover the valve openings around the outside of the cylinder while the piston travels through the middle During the intake stroke of the compressor the piston travels away from the discharge valve and creates a vacuum effect reducing the pressure within the cylinder to below suction pressure Since the pressure within the cylinder is less than the pressure of the refrigerant at the suction side of the compressor the suction valve is forced open and the refrigeran
22. e refrigerant leaving the coil to rise Sensing this increased temperature the expansion valve feeds additional refrigerant to the coil increasing the suction pressure and temperature The principal advantage of hot gas bypass to the evaporator inlet is that the refrigerant velocity in the evaporator and suction line is higher at low loads This promotes a uniform movement of oil through the evaporator coil and suction piping When the evaporator is located above the compressor as shown the holdup of oil within the vertical hot gas bypass riser must be considered Since the flow rate within the hot gas bypass line modulates over a wide range no size of pipe can ensure adequate velocity to carry oil up the riser Oil will collect at the base of the vertical riser when the bypass valve throttles to lower flow rates This problem is commonly addressed by adding a small oil return line between the base of the riser and the suction line 35 S TRANE 36 period three The Compressor in a System Hot Gas Bypass to Suction Line liquid line solenoid valve L Th d ip JX a liquid injection valve suction line compressor The second method bypasses refrigerant vapor from the compressor discharge line to the suction line This method requires the service of an additional expansion valve called a liquid injection valve The remote bulb of this valve is attached to the suction line near the compressor When reduced suction pressur
23. e causes the bypass valve to open the expansion valve senses the resulting rise in suction temperature superheat at its remote bulb A rising suction temperature causes this expansion valve to open mixing liquid refrigerant with the hot bypassed refrigerant vapor The heat content of this refrigerant vapor causes the liquid refrigerant to evaporate thus cooling the mixture This increase in the refrigerant flow rate stabilizes the compressor suction pressure temperature The principal advantage of hot gas bypass to the suction line is that the amount of refrigerant piping is generally less than the other method A key disadvantage is that the refrigerant velocity in the evaporator and suction line drops very low when the bypass valve is open This creates a problem of oil hanging up in the evaporator coil and suction piping For this reason this method is not acceptable in applications where the evaporator is located below the compressor When hot gas bypass is applied to a water chiller containing a direct expansion evaporator hot gas bypass to the evaporator inlet is always used In a direct expansion evaporator liquid refriegerant flows through the tubes and water fills the surrounding shell Oil holdup within the tubes can be a problem at part load when refrigerant velocity is reduced The increased velocity brought about by bypassing to the evaporator inlet solves this problem for water chillers Finally when hot gas bypass is appli
24. e resulting vapor B is then pumped from the evaporator by the compressor which increases the pressure and temperature of the refrigerant vapor Notice that during the compression process B to C the heat content enthalpy of the vapor is increased The mechanical energy used by the compressor to increase the pressure of the refrigerant vapor is converted to heat energy called the heat of compression This causes the temperature of the refrigerant to also rise as the pressure is increased The resulting hot high pressure refrigerant vapor C enters the condenser where heat is transferred to ambient air or water at a lower temperature Inside the condenser the refrigerant desuperheats C to D condenses into a liquid D to E and in some cases subcools E to F The refrigerant pressure inside the condenser is determined by the temperature of the air or water that is available as the condensing media This liquid refrigerant F then flows from the condenser to the expansion device The expansion device creates a pressure drop that reduces the pressure of the refrigerant to that of the evaporator At this low pressure a small portion of the refrigerant boils or flashes cooling the remaining liquid refrigerant to the desired evaporator temperature A The cool mixture of liquid and vapor refrigerant travels to the evaporator to repeat the cycle TRG TRC004 EN TRG TRC004 EN S TRANE period one Compressor Types Refrigerati
25. earing assembly The refrigerant vapor enters through the outer edge of the scroll assembly and discharges through the port at the center of the stationary scroll period one Compressor Types Scroll Compressor journal bearing direction of rotation driven scroll The center of the scroll journal bearing and the center of the motor shaft are offset This offset imparts an orbiting motion to the driven scroll Rotation of the motor shaft causes the scroll to orbit not rotate about the shaft center Scroll Compressor intake discharge port intake This orbiting motion causes the mated scrolls to form pockets of refrigerant vapor As the orbiting motion continues the relative movement between the orbiting scroll and the stationary scroll causes the pockets to move toward the discharge port at the center of the assembly gradually decreasing the refrigerant volume and increasing the pressure Three revolutions of the motor shaft are required to complete the compression process TRG TRC004 EN S TRANE period one Compressor Types Scroll Compressor intake phase compression phase discharge phase During the first full revolution of the shaft or the intake phase the edges of the scrolls separate allowing the refrigerant vapor to enter the space between the two scrolls By the completion of first revolution the edges of the scrolls meet again forming two closed pockets of refrige
26. ed to a system the need for condensing pressure control must be considered Sufficient condensing pressure must be available to ensure adequate refrigerant flow to produce a bypass load when the hot gas bypass valve is to be opened If a decreasing load is accompanied by a corresponding reduction in condensing pressure the hot gas bypass valve may not be capable of bypassing refrigerant vapor at the rate required to stabilize the suction temperature within reasonable limits The result is that the TRG TRC004 EN S TRANE period three The Compressor in a System suction temperature falls and coil frosting or chiller freezing may occur Since the hot gas bypass valve is sized to pass a given quantity of refrigerant vapor at a particular condensing suction pressure difference some means of maintaining the condensing pressure within limits must be provided Various methods of controlling condensing pressure are discussed in the Refrigeration System Components clinic TRG TRC004 EN 37 S TRANE period four Review Refrigeration Compressors period four Review We will now review the main concepts that were covered in this clinic on refrigeration compressors Review Period One centrifugal Period One introduced the four types of compressors commonly used in air conditioning applications reciprocating scroll helical rotary or screw and centrifugal The first three types are called positive displacement compress
27. ese vanes lessen the ability of the impeller to take in the refrigerant As a result the compressor s refrigerant pumping capacity decreases to balance with the evaporator load Inlet Vanes vane position degrees pressure difference unloading line capacity These curves represent the performance of a typical centrifugal compressor over a range of inlet vane positions The pressure difference between the compressor inlet evaporator and outlet condenser is on the vertical axis and compressor capacity is on the horizontal axis The surge region represents the conditions that cause unstable compressor operation As the load on the compressor decreases from the full load operating point A the inlet vanes partially close reducing the flow rate of refrigerant vapor and balancing the compressor capacity with the new load B Less refrigerant and therefore less heat are transferred to the condenser Since the available heat rejection capacity of the condenser is now greater than required the refrigerant condenses at a lower temperature and pressure This reduces the pressure difference between the evaporator and the condenser Continuing along the unloading line the compressor remains within its stable operating range until it reaches C Inlet vanes on a centrifugal compressor allow it to unload over a broad capacity range while preventing the compressor from operating in the surge region TRG TRC004 EN TRG TRC004 EN
28. gerant pumping Capacity decreases to balance with the evaporator load Alternatively the capacity of any of these types of compressors can be controlled by varying the rotational speed of the compressor motor It is most often applied however to centrifugal compressors TRG TRCO004 EN 39 40 period four Review Review Period Three a System level control Constant volume DX system e Control by sensing space temperature VAV DX system e Control by sensing supply air temperature Chilled water system e Control by sensing temperature of water leaving evaporator a Preventing evaporator freeze up Sensing suction temperature Hot gas bypass Period Three considered the entire system and discussed how the capacity of the compressor is controlled to maintain desired space conditions In a constant volume DX system in order to respond to changing loads the capacity of the compressor is controlled by directly sensing space temperature In a VAV DX system the capacity of the compressor is controlled by sensing the supply air temperature In a chilled water system the capacity of the compressor is typically controlled by sensing the temperature of the water leaving the evaporator Period Three also discussed sensing suction temperature and hot gas bypass as methods for preventing evaporator freeze up TRG TRC004 EN period four Review TRANE An American Standard S ici ten hace a For more information
29. his next section considers the entire system in order to determine how the capacity of the compressor is controlled to maintain desired space conditions System Level Control direct expansion DX PI chilled water System Level Control The method of controlling compressor capacity to maintain desired space conditions depends on 1 whether the system is a chilled water or a direct expansion system and 2 how the airside system responds to changes In space loads Generally in air conditioning applications compressors will be applied in either a chilled water or a direct expansion DX system A chilled water system uses water as the cooling media The refrigerant inside the evaporator absorbs heat from the water and this water is pumped to coils in order to absorb heat TRG TRC004 EN TRG TRC004 EN S TRANE period three The Compressor in a System from the air used for space conditioning In contrast the refrigerant inside the evaporator of a direct expansion DX system absorbs heat directly from the air used for space conditioning The airside system responds to changing space loads by varying either the temperature or the quantity of air delivered to the conditioned space A constant volume system provides a constant quantity of variable temperature air to maintain the desired conditions in a space A variable air volume VAV system however maintains the desired space conditions by varying the quantity of co
30. mpressor unit in this example is 8 tons 28 1 kW Excessive starting and stopping of scroll compressors is not a concern The reciprocating compressor system on Figure 35 includes a single large compressor with a single large motor In contrast the scroll compressor system has four small compressors each with its own small motor These small motors are designed to cycle just like those used with small reciprocating compressors 25 26 period two Compressor Capacity Control Slide Valve discharge housing port rotors slide valve Slide Valve The helical rotary compressor used as the example in this clinic is unloaded using a slide valve that is an integral part of the compressor housing Other helical rotary compressor designs may use a variety of methods to vary capacity Some of these methods are similar in function to the slide valve presented in this clinic One major determining factor is whether the compressor is designed to unload in steps like a reciprocating compressor or if it has variable unloading The position of the slide valve along the rotors controls the volume of refrigerant vapor delivered by the compressor by varying the amount of rotor length actually used for compression By changing the position of the slide valve the compressor is able to unload to exactly match the evaporator load instead of unloading in steps like the reciprocating compressor discussed earlier TRG TRC004 EN T
31. ng a constant condensing pressure the compressor pumping capacity decreases with the falling suction temperature along the six cylinder curve until it reaches B Here the compressor unloads the first set of two cylinders When the first set of two cylinders is unloaded the compressor operates with only four active cylinders and the compressor capacity falls immediately to 19 tons 66 8 kW along the four cylinder curve C As the load continues to decrease the capacity and suction temperature follow the four cylinder curve until it reaches D Here the second set of two cylinders is unloaded decreasing the compressor capacity to 9 5 tons 33 4 kW along the two cylinder curve E As the load continues to decrease the suction temperature reaches the minimum set point 28 F 2 2 C in this example F and the two remaining cylinders are deactivated by shutting off the compressor The minimum capacity of the compressor in this example is 7 tons 24 6 kW This illustrates how cylinder unloading extends the stable part load range of a reciprocating compressor The example compressor is able to perform over 77 of its capacity range 31 tons to 7 tons 109 kW to 24 6 kW An increasing load reverses the sequence 22 TRG TRC004 EN S TRANE period two Compressor Capacity Control Alternating Cylinders On and Off 40 tons der 140 7 kW 6 oh B S capacity I 20 tons i 25 tons I D S 88 kW nas ae fs oii 0 tons
32. ns 30 000 kW Open Compressor d K rs tt i K A he SES le pi iink k o a housing Sas Wee i y wi 1 ee ai z m compressor a crankshaft a phe In addition to the different methods of compression compressors can be classified as open hermetic and semihermetic A reciprocating compressor will be used to explain these terms An open compressor is driven by an external power source such as an electric motor an engine or a turbine The motor is coupled to the compressor crankshaft by a flexible coupling Since the shaft protrudes through the compressor housing a seal is used to prevent refrigerant from leaking out of the compressor housing This motor is cooled by air that is drawn in from the surrounding space The heat removed from the motor must still be rejected from the space either by mechanical ventilation or if the space is conditioned by the building s cooling system TRG TRC004 EN TRG TRC004 EN S TRANE period one Compressor Types Hermetic Compressor housing motor compressor piston A hermetic compressor on the other hand seals the motor within the compressor housing This motor is cooled by the refrigerant either by refrigerant vapor that is being drawn into the compressor from the suction line or by liquid refrigerant that is being drawn from the liquid line The heat from the motor is then rejected by the condenser Hermetic
33. nstant temperature air Constant Volume DX System DX cooling coll compressor capacity controller Again a constant volume system supplies the same quantity of air to the space and varies the temperature of this air to respond to changing loads In this example single zone constant volume DX system in order to respond to changing space loads the capacity of the compressor is controlled by directly sensing space temperature The compressor is loaded or unloaded based on how close the actual space temperature is to the set point temperature Loading and unloading the compressor results in a temperature change of the air leaving the evaporator coil 31 S TRANE period three The Compressor in a System Variable Air Volume DX System compressor capacity thermostat controller As mentioned previously a VAV system varies the quantity of air supplied to the space in order to satisfy the load The supply temperature is held constant in this system In a VAV DX system the capacity of the compressor is controlled by sensing the temperature of the air being supplied to the system The compressor is loaded or unloaded based on how close the actual supply air temperature is to the set point Chilled Water System modulating amp water valve pump Fi compressor capacity controller In contrast to the DX system examples shown previously a chilled water system responds to changing space loads by cont
34. on Compressors period one Compressor Types This period is devoted to the discussion of the different types of compressors helical rotary pehinhiall There are primarily four types of compressors used in the air conditioning industry reciprocating scroll helical rotary or screw and centrifugal The traditional reciprocating compressor has been used in the industry for decades It contains cylinders pistons rods a crankshaft and valves similar to an automobile engine Refrigerant is drawn into the cylinders on the downstroke of the piston and compressed on the upstroke Scroll and helical rotary or screw compressors have become more common replacing the reciprocating compressor in most applications due to their improved reliability and efficiency These three types of compressors reciprocating scroll and helical rotary all work on the principle of trapping the refrigerant vapor and compressing it by period one Compressor Types gradually shrinking the volume of the refrigerant Thus they are called positive displacement compressors In contrast centrifugal compressors use the principle of dynamic compression which involves converting energy from one form to another in order to increase the pressure and temperature of the refrigerant The centrifugal compressor uses centrifugal force generated by a rotating impeller to compress the refrigerant vapor Reciprocating Compressor intake stroke
35. op units split systems self contained units and even small water chillers Helical Rotary Screw Compressor Helical Rotary Screw Compressor Similar to the scroll compressor the helical rotary compressor traps the refrigerant vapor and compresses it by gradually shrinking the volume of the refrigerant This particular helical rotary compressor design uses two mating screw like rotors to perform the compression process TRG TRC004 EN S TRANE period one Compressor Types Helical Rotary Compressor female rotor male rotor housing The rotors are meshed and fit with very close tolerances within the compressor housing The gap between the two rotors is sealed with oil preventing the compressed refrigerant vapor from escaping through the mating surfaces Only the male rotor is driven by the compressor motor The lobes of the male rotor engage and drive the female rotor causing the two parts to counter rotate Helical Rotary Compressor pocket of refrigerant vapor Refrigerant vapor enters the compressor housing through the intake port and fills the pockets formed by the lobes of the rotors As the rotors turn they push these pockets of refrigerant toward the discharge end of the compressor After the pockets of refrigerant travel past the intake port area the vapor still at suction pressure is confined within the pockets by the compressor housing TRG TRC004 EN 11 12 period one Compressor
36. orator design Evaporator freeze protection in a chilled water application is accomplished by sensing the temperature of the water in the evaporator If the water approaches 32 F 0 C the compressor is shut off to protect the evaporator from freezing Most chilled water equipment includes this protection as part of the controls for the equipment Sensing Suction Temperature condenser valve line evaporator In a direct expansion DX application where the refrigerant in the evaporator is cooling air frost protection can be accomplished in a number of ways As mentioned if the surface temperature of the coil gets too cold the moisture that condenses out of the air can form frost on the surface of the coil This coil frosting is detrimental to system performance and compressor reliability compressor Historically in DX air conditioning applications hot gas bypass coil pressure regulators and defrost cycles initiated by a timer pressure sensor or temperature sensor are a few of the methods that have been used to prevent evaporator frosting This clinic will focus on two of these a defrost cycle initiated by a temperature sensor and hot gas bypass A temperature sensor on the suction line leaving the evaporator is used to determine if the coil reaches a frosting condition Compressors are turned off and the supply fan continues to run to de ice the coil Timers prevent the compressors from rapid
37. ors They work on the principle of trapping the refrigerant vapor and compressing it by gradually shrinking the volume of the refrigerant Centrifugal compressors use the principle of dynamic compression which involves converting energy from one form to another to increase the pressure and temperature of the refrigerant 38 TRG TRC004 EN period four Review Review Period Two 4 Reciprocating Cylinder Unloaders 4 Scroll Cycle On and Off a Helical Rotary Slide Valve a Centrifugal Inlet Vanes Variable Speed Period Two reviewed various methods of varying compressor capacity Reciprocating compressors typically use cylinder unloaders that match the compressor capacity to the evaporator load by deactivating piston cylinder pairs Refrigeration systems using scroll compressors generally unload by using multiple compressors cycling them on and off as needed to satisfy the evaporator load A common method of unloading a helical rotary compressor is to use a slide valve that is an integral part of the compressor housing By changing the position of the slide valve along the compressor rotors the volume of refrigerant vapor being delivered by the compressor can be controlled to match the evaporator load Finally centrifugal compressors generally use inlet vanes to preswirl the refrigerant before it enters the impeller lessening the ability of the impeller to take in the refrigerant As a result the compressor s refri
38. pressors generally cycle on and off Helical rotary compressors use a slide valve or a similar unloading device Centrifugal compressors typically use inlet vanes or a variable speed drive in combination with inlet vanes In addition all four types of compressors could use variable speed to control their capacity 18 TRG TRC004 EN S TRANE period two Compressor Capacity Control Cylinder Unloaders J controller unloader solenoid valve 4 piston refrigerant discharge vapor Cylinder Unloaders Most large reciprocating compressors above 10 tons 35 kW are fitted with cylinder unloaders that are used to match the compressor s refrigerant pumping capacity with the falling evaporator load by progressively deactivating piston cylinder pairs The cylinder unloader shown in this example reciprocating compressor uses an electrically actuated unloader valve to close the suction passage to the cylinder that is being unloaded In response to a decreasing load an electronic controller sends a signal to open a solenoid valve This solenoid valve diverts pressurized refrigerant vapor from the compressor discharge to the top of the unloader valve causing the unloader valve to close and shut off the flow of refrigerant vapor into the cylinder Even though the piston continues to travel back and forth inside this cylinder it is no longer performing compression since it cannot take in any refrigerant vapor TRG TRCO004 EN
39. rant During the second full revolution or the compression phase the volume of each pocket is progressively reduced increasing the pressure of the trapped refrigerant vapor Completion of the second revolution produces near maximum compression During the third full revolution or the discharge phase the interior edges of the scrolls separate releasing the compressed refrigerant through the discharge port At the completion of the revolution the volume of each pocket is reduced to zero forcing the remaining refrigerant vapor out of the scrolls Looking at the complete cycle notice that these three phases intake compression and discharge occur simultaneously in an ongoing sequence While one pair of these pockets is being formed another pair is being compressed and a third pair is being discharged TRG TRC004 EN 9 10 period one Compressor Types Scroll Compressor dome 4 a scrolls discharge opening F suction opening In this example scroll compressor refrigerant vapor enters through the suction opening The refrigerant then passes through a gap in the motor cooling the motor before entering the compressor housing The refrigerant vapor is drawn into the scroll assembly where it is compressed discharged into the dome and finally discharged out of the compressor through the discharge opening In the air conditioning industry scroll compressors are widely used in heat pumps rooft
40. re Preventing Evaporator Freeze Up In addition to unloading the compressor in order to match the ever changing system load a second system related concern involves maintaining the suction temperature above the conditions where evaporator freeze up may occur This can be illustrated by returning to an earlier example Assume that in response to a decreasing load the capacity of the 40 ton 105 5 kW scroll compressor unit is progressively reduced to a minimum of 8 tons 28 1 kW corresponding to a suction temperature of 28 F 2 2 C H If the load on the evaporator decreases no further the suction temperature is maintained within safe operating limits However if the system must be operated at loads below this minimum stage of unloading the suction temperature may fall to the point I where evaporator freeze up can occur In a direct expansion DX application where the refrigerant in the evaporator is cooling air a suction temperature of approximately 28 F 2 2 C can cause the moisture that condenses out of the air to form frost on the surface of the evaporator coil In a chilled water application where the refrigerant in the evaporator is cooling water a suction temperature of approximately 30 F 1 1 C can cause the water to freeze inside the evaporator This minimum 33 period three The Compressor in a System suction temperature for a specific application depends on the system operating conditions and the evap
41. re does the capacity of a compressor increase or decrease as the suction temperature decreases 7 What method of capacity control is commonly applied to scroll compressors 8 What method of capacity control is commonly applied to centrifugal compressors Questions for Period 3 9 In a VAV DX system the capacity of the compressor is typically controlled by sensing Space temperature supply air temperature chilled water supply temperature 10 In a constant volume chilled water system the capacity of the compressor is typically controlled by sensing space temperature Supply air temperature chilled water supply temperature 11 In aconstant volume DX system the capacity of the compressor is typically controlled by sensing Space temperature supply air temperature chilled water supply temperature 12 What are the two common methods of preventing evaporator frosting in a direct expansion DX system TRG TRC004 EN 43 44 Answers O N OF a AB To elevate the pressure and therefore the temperature of the refrigerant vapor high enough that it can reject heat to air or some other fluid at normally available temperatures Reciprocating scroll helical rotary or screw and centrifugal During the intake stroke the piston travels away from the discharge valve and creates a vacuum effect reducing the pressure within the cylinder to below suction pressure Since the pressure within the cylinder is les
42. rolling the capacity of the chilled water cooling coil Although there are various methods of controlling the capacity of this coil this discussion will assume the use of a modulating water valve 32 TRG TRC004 EN TRG TRC004 EN S TRANE period three The Compressor in a System In a VAV chilled water system shown in Figure 46 the capacity of the chilled water coil is controlled to maintain the desired supply air temperature By sensing the supply air temperature a controller varies the flow of water through the coil by modulating the valve Varying the water flow maintains the temperature of the air as the flow rate of the air changes to match the space load In a constant volume chilled water system the capacity of the chilled water coil is controlled by directly sensing space temperature and varying the flow of water through the coil by modulating the valve Varying the water flow changes the temperature of the air leaving the coil to match the space load In either case the capacity of the compressor is generally controlled by sensing the temperature of the water leaving the evaporator and comparing it to the set point Preventing Evaporator Freeze Up l A S 40tons _ freeze up B npes 140 7 kW occurs AC y gso i 1 C esso v r cs l Si 20 tons HF z come G 70 3 kW TE v asso l H cont l G 0 tons l 0 kW 20 F 30 F 40 F 50 F 6 7 C 1 1 C 4 4 C 10 C suction temperatu
43. s than the pressure of the refrigerant at the suction side of the compressor the suction valve is forced open and the refrigerant vapor is drawn into the cylinder True Hermetic or semihermetic Decreases Cycling individual scroll compressors on and off Inlet vanes or variable speed drive with inlet vanes Supply air temperature 10 Chilled water supply temperature 11 Space temperature 12 Sensing the suction temperature and hot gas bypass TRG TRC004 EN TRG TRC004 EN S TRANE Glossary adjustable frequency drive AFD A device used to vary the capacity of a compressor by varying the speed of the compressor motor ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers centrifugal compressor A type of compressor that uses centrifugal force generated by a rotating impeller to compress the refrigerant vapor chilled water system Uses water as the cooling media The refrigerant inside the evaporator absorbs heat from the water and this water is pumped to coils in order to absorb heat from the air used for space conditioning compressor A mechanical device in the refrigeration system used to increase the pressure and temperature of the refrigerant vapor condenser A component ofthe refrigeration system where refrigerant vapor is converted to liquid as it rejects heat to air water or some other fluid constant volume system A type of air conditioning system that varies the temperature of
44. search testing programs and field experience The Trane Air Conditioning Clinic series is one means of knowledge sharing It is intended to acquaint a nontechnical audience with various fundamental aspects of heating ventilating and air conditioning We have taken special care to make the clinic as uncommercial and straightforward as possible Illustrations of Trane products only appear in cases where they help convey the message contained in the accompanying text This particular clinic introduces the concept of refrigeration compressors 2000 American Standard Inc All rights reserved TRG TRC004 EN Contents Introduction n 1 period one Compressor Types 0 0 3 Reciprocating COMPIESSO accctslesssececseconstennpteletons 4 DCO COMO SSO qetsceyetecennateedaeuconssescchae maeeecateaes 7 Helical Rotary Screw CompreSSoOr cceeeeee es 10 C ntritugal COMPFESSO Aiimvissnranaacvoncoaivestnehentanmaawuns 13 period two Compressor Capacity Control 0 18 CYST OGG OTS iiccermuscssninyseiivssonaadeosionteecinsst 19 CCMA Omand UIT sentewecaidsuctecctaatuanoredccast oeeatereretae 24 Ss IVY e N 26 NALS VNC Secetatacecsatetevecee ee ca aseeuneametoresedeeserteese 27 E E a E 29 period three The Compressor in a System 30 System Level Control cvcechecxserccaleveuenseiareceninnneeedses 30 Preventing Evaporator Freeze Up ccccccccrcc 33 period four Review eerren 38 QuiZ
45. t vapor is drawn into the cylinder TRG TRC004 EN TRG TRC004 EN S TRANE period one Compressor Types Reciprocating Compressor compression stroke discharge valve suction valve During the compression stroke the piston reverses its direction and travels toward the discharge valve compressing the refrigerant vapor and increasing the pressure within the cylinder When the pressure inside the cylinder exceeds the suction pressure the suction valve is forced closed trapping the refrigerant vapor inside the cylinder As the piston continues to travel toward the discharge valve the refrigerant vapor is compressed increasing the pressure inside the cylinder Reciprocating Compressor N headspace AEn discharge m u m vave e e E suction valve discharge opening When the pressure within the cylinder exceeds the discharge or head pressure the discharge valve is forced open allowing the compressed refrigerant vapor to leave the cylinder The compressed refrigerant travels through the headspace and leaves the compressor through the discharge opening period one Compressor Types Reciprocating Compressor suction cylinder headspace _ Opening discharge opening 37 piston rod motor crankshaft In the reciprocating compressor shown the refrigerant vapor from the suction line enters the compressor through the suction opening It then passes around and thro
46. ugh the motor cooling the motor before it enters the cylinder to be compressed The compressed refrigerant leaves the cylinder travels through the headspace and leaves the compressor through the discharge opening Most reciprocating compressors have multiple piston cylinder pairs attached to a single crankshaft In the air conditioning industry reciprocating compressors were widely used in all types of refrigeration equipment As mentioned earlier however scroll and helical rotary compressors have become more common replacing the reciprocating compressor in most of these applications because of their improved reliability and efficiency TRG TRC004 EN TRG TRC004 EN S TRANE period one Compressor Types Scroll Compressor stationary scroll intake intake driven shaft scroll Scroll Compressor Similar to the reciprocating compressor the scroll compressor works on the principle of trapping the refrigerant vapor and compressing it by gradually shrinking the volume of the refrigerant The scroll compressor uses two scroll configurations mated face to face to perform this compression process The tips of the scrolls are fitted with seals that along with a fine layer of oil prevent the compressed refrigerant vapor from escaping through the mating surfaces The upper scroll called the stationary scroll contains a discharge port The lower scroll called the driven scroll is connected to a motor by a shaft and b