SPX Cooling Technologies Cooling Tower Marley MD User's Manual

image

Contents

1. 2578 i z s available at spxcooling com provides MD model recommendations based on customer s specific design requirements PLAN t 3651 _ 35 569 140 7 8 INLET Pm MOTOR z H A rai y SIDE ELEVATION END ELEVATION Marley MD Cooling Tower Engineering Data Schematic 11 MD5010 SINGLE CELL i hipping Weight dBA Dimensions Design shipping Wald Model Nominal Tons Motor P Operating kg 1 5m from air 3 note 2 note 3 kW A Weight Heaviest inlet face H A k Weight Cell i g Section MD5010PAC1L 248 11 81 MD5010PLC1L 249 11 80 MD5010QAC1L 269 15 81 3412 2299 3883 2079 1052 MD50100LC1L 270 15 80 MD5010RAC1L 286 18 5 81 MD5010RLC1L 289 18 5 80 MD5010PAD1L 279 11 81 MD5010PLD1L 280 11 80 MD50100AD1L 304 15 81 3717 2604 4046 2242 1190 MD50100LD1L 305 15 80 MD5010RAD1L 325 18 5 81 MD5010RLD1L 329 18 5 80 MD5010PAF1L 293 11 81 MD5010PLF1L 294 11 80 MD50100AF1L 317 15 81 MD5010QLF1L 318 15 80 4021 2909 4234 2430 1353 MD5010RAF1L 341 18 5 81 MD5010RLF1L 346 18 5 80 MD5010SAF1L 360 22 81 MD5010SLF1L 362 22 81 NOTE 1 Use this bulletin for preliminary layouts only Obtain current drawings from your Marley sales representative All table data is per cell 2 Last two characters of the model number indicate number of cells and cell configuration 3 Nominal tons are based up
2. The thermal performance rating shall be Certified by the Cooling Technology Institute Tower shall comply with all ASHRAE 90 1 standards Performance Warranty CTI Certification notwithstanding the cooling tower manufacturer shall guar antee that the cooling tower supplied will meet the specified performance conditions when the tower is installed as shown on the plans If because of a suspected thermal performance defi ciency the owner chooses to conduct an on site thermal performance test under the supervision of a qualified disinterested third party in accordance with CTI ASME or other applicable standards during the first year of oper ation and if the tower fails to perform within the limits of test tolerance then the cooling tower manufacturer will pay for the cost of the test and will make such corrections as are appro priate and agreeable to the owner to compensate for the performance defi ciency E Your specification base establishes the type configuration base materi al and physical limitations of the cooling tower to be quoted During the planning and layout stages of your project you will have focused your attention on a cooling tower selection that fits your space allotment and whose power usage is acceptable Limitations on physical size and total operating horsepower avoid the introduction of unforeseen operational and site related influences Specifying the number of cells and the max imum fan hp
3. 35 152 SIDE ELEVATION END ELEVATION Marley MD Cooling Tower Engineering Data Schematic 15 MD5016 SINGLE CELL i Shipping Weight dBA Dimensions Design oe E Model Nominal Tons Motor Lom fomar Operating note 2 note 3 kW on Weight Heaviest inlet face H A k Weight Cell s g Section MD5016PAC1L SAWA 11 79 MD5016PLC1L 320 11 78 MD50160AC1L 345 19 80 MD5016QLC1L 348 15 79 4239 2529 5805 3225 1710 MD5016RAC1L 369 18 5 80 MD5016RLC1L 372 18 5 79 MD5016SAC1L 390 22 81 MD5016SLC1L 394 22 80 MD5016PAD1L 350 11 79 MD5016PLD1L 353 11 78 MD5016QAD1L 383 15 80 MD5016QLD1L 384 15 7h MD5016RAD1L 410 18 5 80 4544 2834 6089 3508 1763 MD5016RLD1L 412 18 5 79 MD5016SAD1L 436 22 81 MD5016SLD1L 437 22 80 MD5016TAD1L 475 30 82 MD5016TLD1L 471 30 80 MD5016PAF1L 368 11 79 MD5016PLF1L 370 11 78 MD50160AF1L 403 15 80 MD5016QLF1L 401 15 79 MD5016RAF1L 431 18 5 80 4848 3139 6320 3739 1977 MD5016RLF1L 431 18 5 79 MD5016SAF1L 460 22 81 MD5016SLF1L 459 22 80 MD5016TAF1L 500 30 82 MD5016TLF1L 493 30 80 NOTE 1 Use this bulletin for preliminary layouts only Obtain current drawings from your Marley sales representative All table data is per cell 2 Last two characters of the model number indicate number of cells an
4. Engineering Data Schematic 21 MD5O016 FOUR CELL QUAD i Shipping Weight dBA Dimensions Design ALE z Model Nominal Tons Motor tem fomair Operating kg note 2 note 3 kW a Weight Heaviest inlet face H A k Weight Cell g Section MD5016PAC4B SN 11 79 MD5016PLC4B 320 11 78 MD50160AC4B 345 15 80 MD5016QLC4B 348 15 79 4801 3091 5933 3353 1710 MD5016RAC4B 369 18 5 80 MD5016RLC4B 372 18 5 79 MD5016SAC4B 390 22 81 MD5016SLC4B 394 22 80 MD5016PAD4B 350 11 79 MD5016PLD4B 353 11 78 MD50160AD4B 383 15 80 MD50160LD4B 384 16 19 MD5016RAD4B 410 18 5 80 5106 3396 6217 3636 1874 MD5016RLD4B 412 18 5 19 MD5016SAD4B 436 22 81 MD5016SLD4B 437 22 80 MD5016TAD4B 475 30 82 MD5016TLD4B 471 30 80 MD5016PAF4B 368 11 79 MD5016PLF4B 370 11 78 MD5016QAF4B 403 15 80 MD5016Q0LF4B 401 16 79 MD5016RAF4B 431 18 5 80 5410 3701 6448 3868 2105 MD5016RLF4B 431 18 5 79 MD5016SAF4B 460 22 81 MD5016SLF4B 459 22 80 MD5016TAF4B 500 30 82 MD5016TLF4B 493 30 80 NOTE 1 Use this bulletin for preliminary layouts only Obtain current drawings from your Marley sales representative All table data is per cell 2 Nominal tons are based upon 35 C HW 29 5 C CW 25 5 C WB and 68 m3 hr per ton The Marley UPDATE web based selection software provides MD model recommendations based on specific design requirements 3 Standard overflow is a
5. Marley MD Cooling Tower Engineering Data 8 Specifications IM Wy iy Giy SP COOLING TECHNOLOGIES Marley MD Cooling Tower Table of Contents Engineering Data Schematic 6 Support 22 Outlet Connection 24 Hoisting Info 25 Freeze Prevention 26 Water Quality 27 Specifications Base Base 28 Thermal Performance 28 Performance Warranty 28 Design Loading 29 Construction 29 Mechanical Equipment 29 Fill Louvers and Drift Eliminators 31 Hot Water Distribution System 31 Casing and Fan Guard 31 Access 31 Collection Basin 32 Warranty 32 Specifications Options Stainless Steel Options Stainless Steel Collection Basin 33 All Stainless Steel Cooling Tower 33 Convenience and Safety Options Mechanical Access Platform 34 Ladder Extension 34 Ladder Safety Cage 34 Control Options Fan Motor Starter Control Panel 35 Vibration Limit Switch 36 Basin Heater 36 Fan Motor Variable Speed Drive 36 Miscellaneous Options Equalizer Flume Weir Gates 38 Premium Efficiency Motor 38 Sound Control 39 Marley MD Cooling Tower E Air Movement Package High efficiency fan wide chord design for maximum efficiency at low fan tip speeds Eased inlet fan cylinder ensures full area low turbulent airflow through the cylinder Spherical roller bearings are rated at an L4 life of 100 000 hours TEFC Fan Motor 1 15 service factor variable torque and specially insulated for cooling tower duty The MD Series air movement package includ
6. 2837 5860 3279 1710 MD5016RAC2L 369 18 5 80 MD5016RLC2L 372 18 5 19 MD5016SAC2L 390 22 81 MD5016SLC2L 394 22 80 MD5016PAD2L 350 11 79 MD5016PLD2L 353 11 78 MD5016Q0AD2L 383 15 80 MD5016Q0LD2L 384 15 1 MD5016RAD2L 410 18 5 80 4852 3142 6143 3563 1800 MD5016RLD2L 412 18 5 79 MD5016SAD2L 436 22 81 MD5016SLD2L 437 22 80 MD5016TAD2L 475 30 82 MD5016TLD2L 471 30 80 MD5016PAF2L 368 11 79 MD5016PLF2L 370 11 78 MD50160AF2L 403 15 80 MD5016QLF2L 401 15 79 MD5016RAF2L 431 18 5 80 5156 3447 6375 3794 2032 MD5016RLF2L 431 18 5 T9 MD5016SAF2L 460 22 81 MD5016SLF2L 459 22 80 MD5016TAF2L 500 30 82 MD5016TLF2L 493 30 80 NOTE 1 Use this bulletin for preliminary layouts only Obtain current drawings from your Marley sales representative All table data is per cell 2 Last two characters of the model number indicate number of cells and cell configuration Change as appropriate for your selection 3 Nominal tons are based upon 35 C HW 29 5 C CW 25 5 C WB and 68 m hr per ton The Marley UPDATE web based selection software provides MD model recommendations based on specific design requirements 4 Standard overflow is a 3 dia M connection located on the side of the collection basin Makeup water connection is 2 dia M connection located on the side of the tower A 3 M drain connection is located on the side of the collection basin Marley MD Cooling Tower Engineering Data Schematic MD5O16 FOUR OR MORE CELLS Use thi
7. E Propeller type fans require only half the operating hp of blower type fans However they should be readily adjustable to permit compen sation for jobsite conditions The fans of one manufacturer require the purchase of special positioners for each increment of fan blade pitch The Marley Power Belt drive system features all aluminum ML Marley MD Cooling Tower Specifications Base 30 Specification Value shall be driven through a one piece multi groove solid back V type belt sheaves pulleys and tapered roller bearings Bearings shall be rated at an L4 life of 100 000 hours or greater Both motor and fan sheaves pulleys shall be all cast aluminum to prevent premature corrosion Motor s shall be ____ kW maximum TEFC variable torque inverter duty and specially insulated for cooling tower duty Speed and electrical char acteristics shall be RPM single winding __ phase ___ hertz ___ volts Motor nameplate power shall not be exceeded at design operation TEAO motors are not acceptable The complete mechanical equipment assembly for each cell shall be support ed by a rigid hot dip galvanized steel structural support that resists misalign ment between the motor and sheaves pulleys For belt drive towers with motors inside the airstream motors shall be mounted on an adjustable base that swivels outside the access door for maintenance For belt drive tow ers with motors mounted outside the airstre
8. WIDTH OF BASIN Il Il Il TOWER COLLECTION i BASIN Il ANCHOR ai SUPPORTING STEEL MULTICELL NOTE 1 Use this bulletin for preliminary layouts only Obtain current 3 Design operating weight occurs with collection basin full to drawings from your Marley sales representative for final design overflow level Actual operating weight varies with m hr and 2 Purchaser to provide tower support complete with holes and piping scheme anchor bolts Do not use studs Anchor points must be framed 4 Tower may be placed on a flat concrete slab Side outlet and flush and level at top optional side drain and overflow must be specified Marley MD Cooling Tower Engineering Data Outlet Connection 24 MAKEUP MAKEUP 2 NPTM ALTERNATE LOCATION MECHANICAL N COUPLING GROOVE o III WELDING SUCTION HOOD et BEVEL c REMOVABLE TRASH SCREEN D E TOWER PUMP 89 Br OVERFLOW SUCTION 28 5 NPTE DRAIN ALEJE SUCTION SECTION SIDE OUTLET SUCTION CONNECTION Dimensions MAKEUP Model 3 2 NPTM gos Suction A B c D Diameter SLOPING i BASIN FLOOR b SE Bae 305 MD5008 8 191 493 588 305 t 10 493 588 305 D Kool fn eae a 6 477 588 305 HBA f MD5010 8 191 477 588 305 OVERFLOW 10 477 588 305 PU
9. adjust frequency output of the drive in response to the tower cold water temperature The temperature of the cold water and set point shall be displayed on the door of the control panel The bypass shall include a complete magnetic bypass circuit with capability to isolate the VFD when in the bypass mode Transfer to the bypass mode shall be automatic in the event of VFD failure or for specific trip conditions allowing safe transfer E Unless specified otherwise a 3171 switch will be provided A double pole double throw model is also available If purchased in con junction with the Control System it is also factory wired The requirement for manual reset assures that the tower will be visited to determine the cause of excess vibration E The Marley basin heater components described at left represent our rec ommendation for a reliable automatic system for the prevention of basin freezing They are normally shipped separately for installation at the job site by the installing contractor When purchased in conjunction with the enhanced Control System option however they are customarily factory mounted and tested Submerged in basin water in which zinc ions are present copper immersion heaters must not be used Insist upon stainless steel The ambient air temperature that you insert in the specifications should be the lowest 1 level of winter temperature prevalent at site E Marley VFD drive systems are designed to combine
10. in the plenum on the motor side of the tower Cold Water Collection Basin The collection basin shall be heavy gauge galvanized steel and shall include the number and type of suction connections required to accommodate the out flow piping system shown on the plans Suction connections shall be equipped with debris screens A fac tory installed float operated mechani cal make up valve shall be included An overflow and drain connection shall be provided in each cell of the tower The basin floor shall slope toward the drain to allow complete flush out of debris and silt which may accumu late Towers of more than one cell shall include steel flumes for flow and equalization between cells Warranty The MD cooling tower shall be free from defects in materials and work manship for a period of eighteen 18 months from the date of shipment E The MD tower design offers side suction as standard Bottom outlets may be supplied to accommodate a variety of piping schemes Unless so specified the tower you may be asked to approve may only be avail able with one type of suction connection requiring you to redesign your piping layout The sloping floor and low level drain is valuable because it provides a way to achieve flush out cleanability Marley MD Cooling Tower Specifications Options Specifications Stainless Steel Options Stainless Steel Collection Basin Replace paragraph 11 1 with the foll
11. solids resulting from water evaporation as well as airborne impurities and biological contaminants including Legionella an effective consistent water treatment program is required Simple blowdown may be adequate to control corrosion and scale but biological contamination can only be controlled with biocides An acceptable water treatment program must be compatible with the variety of materials incorporated in a cooling tower ideally the pH of the recirculating water should fall between 6 5 and 9 0 Batch feeding of the chemicals directly into the cooling tower is not a good practice since localized damage to the cooling tower is possible Specific startup instructions and additional water quality recommendations can be found in the MD Cooling Tower User Manual which accompanies the cooling tower and also is available at spxcooling com Marley MD Cooling Tower Specifications Base 28 Specification Value Base Furnish and install an induced draft counterflow type factory assembled film fill industrial duty cooling tower Unit shall consist of cell s as shown on plans The limiting overall dimensions of the tower shall be wide long and high Total operating power of all fans shall not exceed kW consisting of kW motor s Tower shall be Marley Model Thermal Performance The tower shall be capable of cool ing m hr of water from C to C at a design entering air wet bulb temperature of C
12. 3 dia M connection located on the side of the collection basin Makeup water connection is 2 dia M connection located on the side of the tower A 3 M drain connection is located on the side of the collection basin Marley MD Cooling Tower Engineering Data Support 21 OVERALL OF BASIN ANCHOR BOLT D ANCHOR BOLT w I I o l l U I Z lt i TOWER Z HOLES FOR COLLECTION T MIG ANCHOR BASIN 3 BOLTS 4REQD I H z u i O SUPPORT E i l BY OTHERS Q C I I 3 I 2 NORMAL i NO I GAUGE I I O TOWER COLLECTION I I 3 BASIN VIEW A w O T I U I Z I I lt a SUPPORTING STEEL SINGLE CELL Dimensions Design Design Model eee Operating Load w L c D E F zap Gall at wata kg MD5008__C 2578 2731 2537 2629 51 165 3072 563 MD5008__D 2578 2131 2537 2629 51 165 3197 586 MD5008__F 2578 2731 2537 2629 51 165 3323 609 MD5010_C 2578 3651 2537 3550 51 165 3906 549 MD5010__D 2578 3651 2537 3550 51 165 4069 568 MD5010__F 2578 3651 2537 3550 51 165 4256 592 MD5016_C 3607 3651 3566 3397 127 318 5860 908 MD5016_D 3607 3651 3566 3397 127 318 6143 951 MD5016_F 3607 3651 3566 3397 127 318 6375 982 22 Marley MD Cooling Tower Engineering Data Support OVERALL LENGTH OF BASIN E D F E ANCHOR ANCHOR ANCHOR ANCHOR J BOLT BOLT BOLT BOLT HOLES FOR MI6 ANCHOR i BOLTS 4 CELL i W OVERALL
13. 50 motor speed The cooling tower manufacturer shall supply VFD start up assistance Tower vibration testing throughout the speed range is required to identify and lockout any natural frequency vibration levels which may exceed CTI guidelines Add the following paragraph in the Mechanical Equipment section when VFD is used with customers Building Management System A complete UL listed Variable Speed Drive system in a IP10 indoor IP52 indoor or IP14 outdoor enclosure shall be provided The VFD shall use PWM technology with IGBT switching and integrated bypass design VFD out put switching shall not cause mechanical issues with gearbox teeth or drive shafts The VFD shall catch a fan spinning in the reverse direction without tripping The panel shall include a main disconnect with short circuit protection and external operating handle lockable in the off position for safety The VFD system shall receive a speed refer ence signal from the Building Management System monitoring the tower cold water temperature The bypass shall include a complete magnetic bypass circuit and with capability to isolate the VFD when in the bypass mode Transfer to the bypass mode shall be manual in the event of VFD failure Operator controls shall be mounted on the front of the enclosure and shall consist of gt N IB ko Marley MD Cooling Tower Specifications Options 38 Specification Value start and stop control bypass
14. 5008PLC2L 202 11 80 MD50080AC2L 217 15 81 MD50080LC2L ZW 15 80 MD5008MAD2L 180 5 5 80 MD5008MLD2L 180 5 5 79 MD5008NAD2L 196 75 81 MD5008NLD2L 196 75 79 MD5008PAD2L 222 11 81 a MD5008PLD2L 222 11 80 MD50080AD2L 239 15 81 MD50080LD2L 239 15 80 MD5008MAF2L 188 5 5 80 MD5008MLF2L 188 5 5 79 MD5008NAF2L 205 7 5 81 1083 MD5008PAF2L 234 11 81 MD5008PLF2L 234 11 80 MD50080AF2L 251 15 81 MD50080LF2L 251 15 80 NOTE 1 Use this bulletin for preliminary layouts only Obtain current drawings from your Marley sales representative All table data is per cell 2 Last two characters of the model number indicate number of cells and cell configuration Change as appropriate for your selection 3 Nominal tons are based upon 35 C HW 29 5 C CW 25 5 C WB and 68 m hr per ton The Marley UPDATE web based selection software provides MD model recommendations based on specific design requirements 4 Standard overflow is a 3 dia M connection located on the side of the collection basin Makeup water connection is 2 dia M connection located on the side of the tower A 3 M drain connection is located on the side of the collection basin Marley MD Cooling Tower Engineering Data Schematic MD5010 SINGLE CELL Use this data for preliminary layouts only Obtain current drawing from your Marley sales representative The UPDATE web based selection software
15. 5010PLD2L 280 11 80 MD50100AD2L 304 15 81 3932 2820 4069 2265 1213 MD50100LD2L 305 15 80 MD5010RAD2L 325 18 5 81 MD5010RLD2L 329 18 5 80 MD5010PAF2L 293 11 81 MD5010PLF2L 294 11 80 MD50100AF2L 317 15 81 MD50100LF2L 318 15 80 4237 3124 4256 2453 1376 MD5010RAF2L 341 18 5 81 MD5010RLF2L 346 18 5 80 MD5010SAF2L 360 22 81 MD5010SLF2L 362 22 81 NOTE 1 Use this bulletin for preliminary layouts only Obtain current drawings from your Marley sales representative All table data is per cell 2 Last two characters of the model number indicate number of cells and cell configuration Change as appropriate for your selection 3 Nominal tons are based upon 35 C HW 29 5 C CW 25 5 C WB and 68 m hr per ton The Marley UPDATE web based selection software provides MD model recommendations based on specific design requirements 4 Standard overflow is a 3 dia M connection located on the side of the collection basin Makeup water connection is 2 dia M connection located on the side of the tower A 3 M drain connection is located on the side of the collection basin Marley MD Cooling Tower Engineering Data Schematic MD5016 SINGLE CELL Use this data for preliminary layouts only Obtain current drawing from your Marley sales representative The UPDATE web based selection software available at spxcooling com provides MD model recommendations based on customer s specific design requirements 8651
16. ER Base Module Top Module MD5008 2 6m 3m 1100 2 8m 3m 900 MD5010 2 6m 4m 1350 2 6m 3m 1050 MD5016 3 7m 4m 1650 3 7m 3m 1750 NOTE 3 Ensure that slings are of sufficient length so not to impose 1 Hoisting operations can be dangerous and suitable safety precautions should be taken to protect personnel and the bending loads onto the casing use of spreader bars is equipment being hoisted i essential 2 All hoisting equipment should be certified and comply with 4 For overhead lifts or where additional safety is required add local and national safety regulations slings beneath the tower unit Marley MD Cooling Tower Engineering Data Freeze Prevention When the ambient air temperature falls below 0 C the water in a cooling tower can freeze Marley Technical Report H 003 Operating Cooling Towers in Freezing Weather describes how to prevent freezing during operation Available at spxcooling com or ask your Marley sales representative for a copy During shutdown water collects in the cold water basin and may freeze solid You can prevent freezing by adding heat to the water left in the tower or you can drain the tower and all exposed pipework at shutdown Electric Basin Heaters An automatic basin water heater system is available consisting of the following components e Standard weatherproof IP55 enclosure rating depending on model and minimum expected winter temperature
17. Extension Add the following to the end of para graph 10 2 Provide a ladder extension for connection to the foot of the ladder This extension shall be long enough to rise from the roof grade level to the base of the cooling tower The install ing contractor shall be responsible for cutting the ladder to length attaching it to the foot of the cooling tower ladder and anchoring it at its base Ladder Safety Cage Add the following paragraph in the Access section A welded aluminum safety cage shall surround the ladder extending from a point approximately 2m above the foot of the ladder to the top of the handrail E Periodic inspection and maintenance of a cooling tower distribution sys tem is fundamental to preserving maximum cooling system efficiency All cooling towers crossflow or counterflow are subject to clogging to varying degrees by waterborne contaminants such as pipe scale and sediment Therefore safe and easy access to these components is of significant value to the operator Access can be provided in a number of ways including portable lad ders or scaffolding but for maximum safety and convenience a field installed Marley access platform with guardrails is available to make this task as safe and user friendly as possible Further its location on the side of the tower does not add to the height of the unit preserving architectural integrity It also saves the owner time and money in that maintenance pe
18. F4L 459 22 80 MD5016TAF4L 500 30 82 MD5016TLF4L 493 30 80 NOTE 1 Use this bulletin for preliminary layouts only Obtain current drawings from your Marley sales representative All table data is per cell 2 Last two characters of the model number indicate number of cells and cell configuration Change as appropriate for your selection 3 Nominal tons are based upon 35 C HW 29 5 C CW 25 5 C WB and 68 m hr per ton The Marley UPDATE web based selection software provides MD model recommendations based on specific design requirements 4 Standard overflow is a 3 dia M connection located on the side of the collection basin Makeup water connection is 2 dia M connection located on the side of the tower A 3 M drain connection is located on the side of the collection basin Marley MD Cooling Tower Engineering Data Schematic m MD5016 FOUR CELL QUAD WON TE Use this data for preliminary layouts only Obtain current drawing from your Marley sales representative BR 4 EL 2 The UPDATE web based selection software available at spxcooling com provides MD model recommendations based on customer s specific design requirements Safty i i Ni A lt A Q his 0 a X DX 0 a RASH ing STN SIDE ELEVATION END ELEVATION Marley MD Cooling Tower
19. MP 7 ag Sere k 496 Aya 6 477 639 331 DRAIN 8 191 477 639 331 MD5016 3 NPTF 878 10 216 477 639 331 12 477 639 331 END OUTLET SUCTION CONNECTION MAKEUP MAKEUP 2 NPTM ALTERNATE LOCATION ANTI VOTEX PLATE Cc WITH SCREEN OR ma REMOVABLE ovERFLOW TOWER D Q 3 NPTF DRAIN 69 B 3 NPTF TRASH SCREEN SUMP FACE MAY DRAIN BE ROTATED 90 OR 180 1 2 NPTF BY OTHERS es BOTTOM OUTLET CONNECTION SIDE OUTLET SUMP CONNECTION SUMP SECTION Maximum m hr per Outlet Sump Bottom Outlet Sump pump flow Bottom Outlet plump flow Side or End Suction pump flow with anti vortex plate or pump flow with anti vortex plate or Outlet pump flow without gravity flow without gravity flow Diameter anti vortex plate with or without anti vortex plate with or without anti vortex plate anti vortex plate MD5008 MD5010 MD5016 MD5008 MD5010 MD5016 MD5008 MD5010 MD5016 MD5008 MD5010 MD5016 MD5008 MD5010 MD5016 6 144 144 144 205 205 205 76 8 259 338 S55 248 248 248 259 338 355 136 136 136 10 493 259 338 891 259 338 493 96 101 215 215 215 123 493 493 142 143 143 259 304 304 14 173 73 173 259 338 368 16 226 226 226 259 338 480 18 259 286 286 259 338 493 20 338 255 338 493 24 493 493 Marley MD Cooling Tower Engineering Data Hoisting ss OFFSET MAY BE REQUIRED OFFSET MAY BE REQUIRED FOR BALANCED LIFT FOR BALANCED LIFT CENTER OF CENTER OF TOW
20. VFD selec tion Auto Manual selections manual speed control To prevent heating prob lems in the cooling tower fan motor and to assure proper gear reducer lubrication the VFD system shall de energize the motor once 25 motor speed is reached and cooling is no longer required The cooling tower manufacturer shall supply VFD start up assistance Tower vibration testing throughout the speed range is required to identify and lockout any natu ral frequency vibration levels which may exceed CTI guidelines Miscellaneous Options Equalizer Flume Weir Gates Add the following paragraph under Cold Water Collection Basin The interconnecting flume between cells shall be equipped with a removable cover plate to permit the shutdown of one cell for maintenance purposes or to permit independent cell operation Premium Efficiency Motor Replace paragraph 6 3 with the fol lowing The complete mechanical equipment assembly for each cell shall be supported by a rigid hot dip galvanized steel structural support that resists misalignment between the motor and sheaves pulleys For belt drive towers with motors inside the airstream motors shall be mounted on an adjustable base that swivels outside the access door for maintenance For belt drive towers with motors mounted outside the airstream a protective cover shall be mounted over the motor and sheave to protect it from the weather and prevent inadvertent con tact The mechanical e
21. above water quality and load carrying capabili ties into account in the selection of their materials of manufacture Mechanical Equipment Fan s shall be propellertype incorpo rating heavy aluminum alloy blades and electrogalvanized hubs Blades shall be individually adjustable and both stati cally and dynamically balanced Fan s mi E The indicated design values are the minimum allowables under accepted design standards They give you assurance that the cool ing tower can be shipped handled hoisted and ultimately oper ated in a normal cooling tower environment Most MD models will withstand significantly higher wind and seismic loads If your geo graphic location dictates higher wind load or seismic load values please make the appropriate changes after discussion with your Marley sales representative E In the history of cooling towers no other coating for carbon steel has exhibited the success and longevity of galvanization in expo sure to the normal cooling tower water quality defined at left No paints or electrostatically applied coatings however exotic they may be can approach galvanization s history of success If extended longevity of the cooling tower is required or unusually harsh operating conditions are expected consider specifying stain less steel as either the base construction material or the material utilized for specific components of your choice See Stainless Steel Options on page 16
22. absolute tempera ture control with ideal energy management The cooling tower user selects a cold water temperature and the drive system will vary the fan speed to maintain that temperature Precise temperature control is accomplished with far less stress to the mechanical equipment compo nents The improved energy management provides fast payback Marley MD Cooling Tower Specifications Options Specification Value of utility voltage to the motor Automatic bypass with an earth ground condition is not allowed The bypass contactor shall be cycled on and off while operating in bypass to maintain the set point temperature of the cold water The drive design shall be oper ated as a stand alone system without the need for a BMS system Operator controls shall be mounted on the front of the enclo sure and shall consist of start and stop control bypass VFD selector switch Auto Manual selector switch manual speed con trol and solid state temperature controller An emergency bypass selector switch inter nal to the panel allowing the cooling tower fan motor to be run at full speed shall be furnished To prevent heating problems in the cooling tower fan motor and to assure proper gear box lubrication the VFD system shall de energize the motor once 25 motor speed is reached and cooling is no longer required The VFD shall include de icing logic with auto canceling and adjust able time Speed in De lce mode shall not exceed
23. am a protective cover shall be mounted over the motor and sheave to protect It from the weather and prevent inadvertent contact The mechanical equipment assembly shall be warranted against any failure caused by defects in materials and workmanship for no less than five 5 years following the date of tower shipment This warranty shall cover the fan speed reducer drive shaft and couplings and the mechanical equipment support The electric motor shall carry a manufacturer s warranty of at least one year The bearing assem blies and V belts shall be warranted for 18 months sheaves power band belts and long life bearings for dependable ser vice TEFC motors offer additional benefits over TEAO motors whose only source of cooling is the flow of air produced by the cooling tower fan This air rate is not always ideal due to motor position blockage etc TEFC ensures the motor will always be cooled properly Unless otherwise specified motor speed will be 1500 RPM in on stan dard models Low noise models will use motor speeds appropriate for the specific model If you prefer the operating flexibility of two speed operation please specify two speed single winding motors which offer full and half speeds for maximum energy savings Incidentally two speed motors are a far better choice than separate pony motors which simply double the problems indicated above and induce parasitic loads during operation for lower than nameplate
24. ature control devices The temperature controller shall be adjustable for the required cold water temperature If a thermostatic control ler is used it shall be mounted on the side of the tower with the temperature sensing bulb installed in the cold water basin using a Suspension mounting bracket If a solid state temperature controller is used the controller will be door mounted on the control panel The temperature controller will display two temperatures one for outgoing water and the other for set point Water temperature input shall be obtained using a three wire RTD with dry well in the outlet water piping and wired back to the solid state tempera ture controller in the control panel E If it is your opinion that the control system for the cooling tower be part of the cooling tower manufacturer s responsibility we are in wholehearted agreement with you Who better to determine the most efficient mode and manner of a cooling tower s operation and to apply a system most compatible with it than the designer and manufacturer of the cooling tower Marley variable speed drives are also available for the ultimate in temperature control energy management and mechanical equip ment longevity ELECTRICAL HAZARD N Marley MD Cooling Tower Specifications Options m Specification Value Vibration Limit Switch Add the following paragraph in the Mechanical Equipment section A single pole double throw
25. cation not only relates the language to use in describing an appropriate MD cooling tower but also defines why certain items and features are important enough to specify with the intention of insisting upon compliance by all bidders The left hand column of pages 28 through 39 provides appropriate text for the various specification paragraphs whereas the right hand column comments on the meaning of the subject matter and explains its value Pages 33 through 39 indicate those paragraphs which will result in the purchase of a basic cooling tower one that accomplishes the specified thermal performance but which will lack many operation and maintenance enhancing accessories and features that are usually desired by those persons who are responsible for the continuing operation of the system of which the cooling tower is part It will also incorporate those standard materials which testing and experience has proven to provide acceptable longevity in normal operating conditions Pages 33 through 39 provide paragraphs intended to add those features components and materials that will customize the cooling tower to meet the user s requirements Marley MD Cooling Tower Engineering Data Schematic MD5OOS SINGLE CELL Use this data for preliminary layouts only Obtain current drawing from your Marley sales representative ZR Migs SK a i SED Mi The UPDATE web based selection software A available at spxcooling com pr
26. cell will work to your advantage You are specifying a counterflow tower which is a type noted and usu ally specified for its economical use of plan area on projects where the required thermal performance is very difficult It effectively replaces most makes of older towers both forced draft and induced draft with out major redesign of the existing site E CTI Certification means that the cooling tower has been tested under operat ing conditions and found to perform as rated by the manufacturer under those circumstances It assures the buyer that the tower is not intentionally or inadver CERAIEI D tently undersized by the manufacturer E However CTI certification alone is not sufficient to assure you that the cooling tower will perform satisfactorily in your situation Certification is established under relatively controlled conditions and cooling towers seldom operate under such ideal circumstances They are affected by nearby structures machinery enclosures effluent from other sources etc Responsible and knowledgeable bidders will take such site specific effects into consideration in selecting the cooling tower but the speci fier must insist by the written specification that the designer manufac turer guarantee this real world performance Any reluctance on the part of the bidder should cause you some concern Marley MD Cooling Tower Specifications Base 29 Specification Value Design Loadin
27. d cell configuration 3 Nominal tons are based upon 35 C HW 29 5 C CW 25 5 C WB and 68 m hr per ton The Marley UPDATE web based selection software provides MD model recommendations based on specific design requirements 4 Standard overflow is a 3 dia M connection located on the side of the collection basin Makeup water connection is 2 dia M connection located on the side of the tower A 3 M drain connection is located on the side of the collection basin Marley MD Cooling Tower Engineering Data Schematic MD5016 TWO OR THREE CELL Use this data for preliminary layouts only Obtain current drawing from your Marley sales representative The UPDATE web based selection software available at spxcooling com provides MD model recommendations based on customer s specific design requirements 35 153 SIDE ELEVATION END ELEVATION Marley MD Cooling Tower Engineering Data Schematic 17 MD5016 TWO OR THREE CELL i Shipping Weight dBA Dimensions Design Ppa 3 Model Nominal Tons Motor Lom fomar Operating kg note 2 note 3 kW za Weight Heaviest inlet face H A k Weight Cell A g Section MD5016PAC2L 317 11 79 MD5016PLC2L 320 11 78 MD50160AC2L 345 15 80 MD5016QLC2L 348 15 79 4547
28. declines with distance by about 5 or 6 dB A each time the dis tance doubles Where noise at a critical point is likely to exceed an acceptable limit you have several options listed below in ascend ing order of cost impact e In many cases noise concerns are limited to night time when ambient noise levels are lower and neighbors are trying to sleep You can usually resolve these situations by using two speed motors in either full half speed or full 2 3 speed configuration and operating the fans at reduced speed without cycling after hours The natural night time reduction in wet bulb temperature makes this a very feasible solution in most areas of the world but the need to avoid cycling may cause the cold water temperature to vary significantly e Variable speed drives automatically minimize the tower s noise level during periods of reduced load and or reduced ambient without sacrificing the system s ability to maintain a constant cold water temperature This is a relatively inexpensive solution and can pay for itself quickly in reduced energy costs e Where noise is a concern at all times for example near a hos pital the best solution is to oversize the tower so it can operate continuously at reduced 2 3 or 2 motor speed even at the highest design wet bulb temperature Typical sound reductions are 7 dB A at 2 3 fan speed or 10 dB A at 12 fan speed but larger reductions are often possible eThe most extreme case
29. e Ratings are in kW for specified ambient temperature For lower ambient temperatures refer to SPX engineering for advice e Standard electircal supply is 380 415 V 3ph 220 240V 1 ph available as extra cost option e Heater has an integral thermostat set point nominally 3 C but adjustable to suit operating requirements Heater components are normally shipped separately for installation by others Note any exposed piping that is still filled with water at shutdown including the makeup water line should be electrically traced and insulated by others 26 Indoor Storage Tank With this type of system water flows from an indoor tank through the load system and back to the tower where it is cooled The cooled water flows by gravity from the tower to the tank located in a heated space At shutdown all exposed water drains into the tank where it is safe from freezing The amount of water needed to successfully operate the system depends on the tower size and GPM and on the volume of water contained in the piping system to and from the tower You must select a tank large enough to contain those combined volumes plus a level sufficient to maintain a flooded suction on your pump Control makeup water according to the level where the tank stabilizes during operation Marley MD Cooling Tower Engineering Data Water Quality The MD cooling tower can be a very effective air washer Atmospheric dust able to pass through t
30. efficiency The value of a 5 year mechanical equipment warranty speaks for itself Except for the motor virtually all of the mechanical equipment on a Marley tower is designed and manufactured by SPX Cooling Technologies Cooling tower vendors who purchase commercial fans gear reducers driveshafts etc may require that you deal directly with those commercial suppliers for warranty satisfaction Marley MD Cooling Tower Specifications Base 31 Specification Value Fill Louvers and Drift Eliminators Fill shall be cross corrugated counterflow film type thermoformed from 0 40mm thick PVC Fill shall be assembled into packs for ease of removal and cleaning Fill shall be sup ported on channel sections supported from the tower structure and have a flame spread rating less than 25 Drift eliminators shall be PVC with a mini mum of three changes in air direction and shall limit drift losses to no more than 0 001 of the design water flow rate Air inlet louvers shall be a minimum of 127mm air travel triple pass PVC to prevent water splashout and eliminate sunlight from entering the collection basin For ease of service and long life of louvers PVC louvers shall be enclosed in a removable frame that attaches to the air inlet without tools Louvers with less than three changes in air direction are unacceptable Hot Water Distribution System A pressured spray system shall dis tribute water evenly over the fil
31. g The tower and its components shall be designed to withstand a wind load of 1 44kPa The cooling tower shall be de signed to withstand shipping and hoist ing loads of 2g horizontal or 3g vertical Guardrails where specified shall be capable of withstanding a 890N con centrated live load in any direction and shall be designed in accordance with OSHA guidelines Construction Except where otherwise specified all components of the cooling tower shall be fabricated of heavy gauge steel protected against corrosion by EN10142 2000 grade Z600 galvaniz ing After passivation of the galvanized steel 8 weeks at pH 7 8 and calcium hardness and alkalinity at 100 300 mg L each the cooling tower shall be capable of withstanding water having a pH of 6 5 to 9 0 a chloride content up to 500 mg L as NaCl 300 mg L as CI a sulfate content as SO4 up to 250 mg L a calcium content as CaCO3 up to 500 mg L silica as SiO2 up to 150 mg L and design operating ranges up to 10 C The circulating water shall contain no oil grease fatty acids or organic solvents The specifications as written are intended to indicate those materials that will be capable of withstanding the above water quality in continuing service as well as the loads described in paragraph 4 1 They are to be regard ed as minimum requirements Where component materials unique to indi vidual tower designs are not specified the manufacturers shall take the
32. he relatively small louver openings will enter the recirculating water system Increased concentrations can intensify systems maintenance by clogging screens and strainers and smaller particulates can coat system heat transfer surfaces In areas of low flow velocity such as the collection basin sedimentary deposits can provide a breeding ground for bacteria In areas prone to dust and sedimentation you should consider installing some means for keeping the collection basin clean Typical devices include side stream filters and a variety of filtration media Blowdown Blowdown or Bleedoff is the continuous removal of a small portion of the water from the open recirculating system Blowdown is used to prevent the dissolved solids from concentrating to the point where they will form scale The amount of blowdown required depends on the cooling range the difference between the hot and cold water temperatures of the closed circuit and the composition of the makeup water 27 A CAUTION The MD cooling tower must be located at such distance and direction to avoid the possibility of contaminated discharge air being drawn into building fresh air intake ducts The purchaser should obtain the services of a Licensed professional Engineer or Registered Architect to certify that the location of the cooling tower is in compliance with applicable air pollution fire and clean air codes Water Treatment To control the buildup of dissolved
33. ing the structural support guaranteed against failure for a period of five full years The motor is warranted separately by the motor manufacturer E Water Distribution System Pressurized spray system distributes water evenly over the fill Low clog polypropylene nozzles delivers precise distribution of water over the fill area Marley MC thermoformed PVC film fill assembled into packs for ease of removal and cleaning Marley XCEL drift eliminators limit drift losses to no more than 001 of the design GPM flow rate E Structure Induced draft counterflow design may require less plan area than crossflow towers typically use Series 300 stainless steel 316 stainless steel or heavy mill galvanized steel construction Factory assembled ensures final field installation will be hassle free Triple pass PVC inlet louvers limits splash out and eliminate sunlight from entering the collection basin Marley MD Cooling Tower Mi towers are galvanized steel factory assembled counterflow cooling towers designed to serve air conditioning and refrigeration systems as well as light to medium industrial process loads on clean water The Marley MD evolved from a factory assembled concept of towers pioneered by Marley some 75 years ago and incorporate all of the design advancements that our customers have found valuable MD towers represent the current state of the art in this cooling tower category The specifications portion of this publi
34. l The branch arms shall be corrosion resis tant PVC with polypropylene spray noz zles attached to the branch arms with a rubber socket connection for ease of removal and cleaning To ensure proper spray system operation nozzles shall seat in branch arms without regard for direction or alignment Casing and Fan Guard The casing shall be heavy gauge EN10142 2000 grade Z600 galvanized steel and shall be capable of with standing the loads described in para graph 4 1 Casing panels shall encase the fill on all four sides of the tower The top of the fan cylinder shall be equipped with a conical non sagging removable fan guard fabricated of welded 5 16 and 7 gauge rods and hot dip galvanized after fabrication E Fill modules can be removed for inspection and cleaning in accor dance with local anti legioinella guidelines Drift rate varies with design water loading and air rate as well as drift eliminator depth and number of directional changes The indi cated rate of 0 001 is easily achievable without premium cost If a lower rate is required please discuss with your Marley sales repre sentative E The combination of PVC piping and polypropylene nozzles is very resistant to the build up of scale and slime o es 0 2 Marley MD Cooling Tower Specifications Base 32 Specification Value Access A large rectangular access door shall be located
35. ley UPDATE web based table data is per cell selection software provides MD model recommendations 2 Last two characters of the model number indicate number of based on specific design requirements cells and cell configuration 4 Standard overflow is a 3 dia M connection located on the side of the collection basin Makeup water connection is 2 dia M connection located on the side of the tower A 3 M drain connection is located on the side of the collection basin Marley MD Cooling Tower Engineering Data Schematic MD5008 MULTICELL Use this data for preliminary layouts only Obtain current drawing from your Marley sales representative The UPDATE web based selection software available at spxcooling com provides MD model recommendations based on customer s specific design requirements PLAN 2371 H 35 569 2794 nd 2 INLET A INSTALLED HEIGHT A 7 SIDE ELEVATION END ELEVATION Marley MD Cooling Tower Engineering Data Schematic MD5008 MULTICELL dBA Dimensions Design Shipping Weight Model Nominal Tons Operating kg note 2 note 3 on tromait Weight Heaviest inlet face kg Weight Cell EiT MD5008MAC2L 165 5 5 80 MD5008MLC2L 165 5 5 79 MD5008NAC2L 179 75 81 MD5008NLC2L 179 75 79 MD5008PAC2L 202 11 81 az MD
36. on 35 C HW 29 5 C CW 25 5 C WB and 68 m hr per ton The Marley UPDATE web based selection software provides MD model recommendations based on specific design requirements 4 Standard overflow is a 3 dia M connection located on the side of the collection basin Makeup water connection is 2 dia M connection located on the side of the tower A 3 M drain connection is located on the side of the collection basin Marley MD Cooling Tower Engineering Data Schematic MD5O10 MULTICELL Use this data for preliminary layouts only Obtain current drawing from your Marley sales representative 2578 The UPDATE web based selection software available at spxcooling com provides MD model recommendations based on customer s specific design requirements 35 569 INLET 4 A SIDE ELEVATION END ELEVATION Marley MD Cooling Tower Engineering Data Schematic 13 MD5O1O MULTICELL i hipping Weight dBA Dimensions Design sipping Wald Model Nominal Tons Motor f Operating kg 1 5m from air note 2 note 3 kw Weight Heaviest inlet face H A k Weight Cell s g Section MD5010PAC2L 248 11 81 MD5010PLC2L 249 11 80 MD5010QAC2L 269 15 81 3628 2515 3906 2102 1052 MD50100LC2L 270 15 80 MD5010RAC2L 286 18 5 81 MD5010RLC2L 289 18 5 80 MD5010PAD2L 279 11 81 MD
37. ovides MD model recommendations based on customer s specific design requirements f 2731 35 569 140 7 2 ee i ana P H A A E a SIDE ELEVATION END ELEVATION Marley MD Cooling Tower Engineering Data Schematic MD5OOS SINGLE CELL i Shipping Weight dBA Dimensions Design Z g Model Nominal Tons Motor domow ait Operating kg note 2 note 3 kW i Weight Heaviest inlet face H A k Weight Cell i g Section MD5008MAC1L 165 5 5 80 MD5008MLC1L 163 5 5 79 MD5008NAC1L 179 75 81 MD5008NLC1L 179 75 79 3294 2181 3051 1702 891 MD5008PAC1L 202 1 81 MD5008PLC1L 202 1 80 MD50080AC1L 216 15 81 MDS50080LC1L 216 15 80 MD5008MAD1L 180 5 5 80 MD5008MLD1L 177 5 5 79 MD5008NAD1L 197 75 81 MD5008NLD1L 196 75 79 3599 2486 3176 1828 936 MD5008PAD1L 223 11 81 MD5008PLD1L 223 11 80 MD50080AD1L 239 15 81 MD5008Q0LD1L 238 15 80 MD5008MAF1L 189 5 5 80 MD5008MLF1L 185 5 5 79 MD5008NAF1L 207 75 81 MD5008NLF1L 206 75 79 3904 2791 3302 1953 1062 MD5008PAF1L 234 m 81 MD5008PLF1L 234 n 80 MD50080AF1L 255 15 81 MD5008QLF1L 257 15 80 NOTE 1 Use this bulletin for preliminary layouts only Obtain 3 Nominal tons are based upon 35 C HW 29 5 C CW 25 5 C current drawings from your Marley sales representative All WB and 68 m3 hr per ton The Mar
38. owing The collection basin shall be heavy gauge Series 300 stainless steel Only low carbon stainless steel alloys will be accepted in order to minimize the risk of intergranular cor rosion in the weld zones Basin shall include the number and type of suction connections required to accommodate the out flow piping system shown on the plans Basin suction connections shall be equipped with debris screens A factory installed float operated mechanical make up valve shall be included An overflow and drain con nection shall be provided in each cell of the tower The basin floor shall slope toward the drain to allow complete flush out of debris and silt which may accumulate All Stainless Cooling Tower Replace paragraph 5 1 with the following Except where otherwise specified all components of the cool ing tower shall be fabricated of heavy gauge series 300 stainless steel Only low carbon stainless steel alloys will be accepted in order to minimize the risk of intergranular corrosion in the weld zones The tower shall be capable of withstanding water having a chloride content NaCl up to 750 mg L a sul fate content S04 up to 1200 mg L a calcium content CaCO3 up to 800 mg L silica SiO2 up to 150 mg L and design operating ranges up to 278 C The circulating water shall contain no oil grease fatty acids or organic sol vents 33 Specification Value E The cold water basin is the only part of the tower
39. quipment assem bly shall be warranted against any fail ure caused by defects in materials and workmanship for no less than five 5 years following the date of tower ship ment This warranty shall cover the fan speed reducer motor drive shaft and couplings and the mechanical equip ment support The bearing assemblies and V belts shall be warranted for 18 months E Where it is your intention to be able to operate both cells of the tower while the flume cover plate is installed separate outlet connections float valves and overflows must be provided for each cell Likewise this would require separate sensors and controls for basin heater systems if installed E IEC premium efficiency motor with a five year warranty enhances the standard five year mechanical equipment warranty of the MD cooling tower Marley MD Cooling Tower Specifications Options 39 Specification Value Sound Control Add the following paragraph under Base The cooling tower shall be quiet operating and shall produce an overall level of sound no higher than ____ dBA measured at the critical location indicated on the plans E Sound produced by a standard MD tower operating in an unob structed environment will meet all but the most restrictive noise limitations and will react favorably to natural attenuation Where the tower has been sized to operate within an enclosure the enclosure itself will have a damping effect on sound Sound also
40. rsonnel may devote their time to inspection rather than searching for ladders or erection of portable scaffolding E Many cooling towers are installed such that the base of the unit is 60cm or more above the roof or grade level This makes it difficult to get up to the foot of the attached ladder The ladder extension alleviates this problem Marley ladder extensions are available in standard 1 5m and 3 5 lengths Marley MD Cooling Tower Specifications Options 35 Specification Value Control Options Fan Motor Starter Control Panel Add the following paragraph in the Mechanical Equipment sec tion Each cell of the cooling tower shall be equipped with a UL listed control system in a IP52 or IP56 out door enclosure capable of controlling single speed or two speed motors as required and designed specifically for cooling tower applications The panel shall include a main fused discon nect or main circuit breaker with an external operating handle lockable in the off position for safety Across the line magnetic starters or solid state soft start starters as required shall be controlled with a thermostatic or solid state temperature controller Door mounted selector switches shall be provided to enable automatic or manual control and wired to meet local control voltage If required control cir cuit to be wired out to terminal blocks for field connection to a remote vibra tion switch overload trip alarms and remote temper
41. s data for preliminary layouts only Obtain current drawing from your Marley sales representative The UPDATE web based selection software available at spxcooling com provides MD model recommendations based on customer s specific design requirements 35 153 SIDE ELEVATION END ELEVATION Marley MD Cooling Tower Engineering Data Schematic 19 MD5016 FOUR OR MORE CELLS i Shipping Weight dBA Dimensions Design PE E Model Nominal Tons Motor Lom fomar Operating kg note 2 note 3 kW za Weight Heaviest inlet face H A k Weight Cell s 9 Section MD5016PAC4L 317 11 79 MD5016PLC4L 320 11 78 MD50160AC4L 345 15 80 MD5016QLC4L 348 15 79 4801 3091 5933 3353 1710 MD5016RAC4L 369 18 5 80 MD5016RLC4L 372 18 5 19 MD5016SAC4L 390 22 81 MD5016SLC4L 394 22 80 MD5016PAD4L 350 11 79 MD5016PLD4L 353 11 78 MD5016Q0AD4L 383 15 80 MD5016QLD4L 384 15 Je MD5016RAD4L 410 18 5 80 5106 3396 6217 3636 1874 MD5016RLD4L 412 18 5 79 MD5016SAD4L 436 22 81 MD5016SLD4L 437 22 80 MD5016TAD4L 475 30 82 MD5016TLD4L 471 30 80 MD5016PAF4L 368 11 79 MD5016PLF4L 370 11 78 MD50160AF4L 403 15 80 MD5016QLF4L 401 15 Je MD5016RAF4L 431 18 5 80 5410 3701 6448 3868 2105 MD5016RLF4L 431 18 5 z9 MD5016SAF4L 460 22 81 MD5016SL
42. s may require discharge sound attenuator sections however the static pressure loss imposed by discharge attenuators may necessitate an increase in tower size Your Marley sales representative will be able to help you meet you sound requirements SP COOLING TECHNOLOGIES GREGORY S BANK WORCESTER WR3 8AB UNITED KINGDOM 44 0 1905 720 200 info uk spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling Technologies Inc uk_MD TS 08A
43. that is subject to periods of stagnant water concentrated with treatment chemicals and customary contaminants It is also the most expensive and dif ficult part of any tower to repair or replace For these reasons many customers particularly those who are replacing older towers choose to specify stainless steel cold water basins M E For pure resistance to corrosion coupled with the capability to meet stringent fire and building codes there is no substitute for stainless steel No paints or electostatically applied coatings how ever exotic they may be can match stainless steel s ability to with stand adverse operating conditions N N IGO Marley MD Cooling Tower Specifications Options 34 Specification Value Convenience and Safety Options Mechanical Access Platform Add the following paragraph in the Access section here shall be a mechanical access platform at the mechanical access door allowing access to the mechanical system drift eliminators distribution system and fill The platform shall be galvanized steel bar grating supported by galvanized steel framework attached to the tower The platform shall be surrounded by a guardrail kneerail and toeboard designed according to meet local safety requirements A ladder shall be permanently attached to the platform and to the casing of the tower rising from the base of the tower to the top of the handrail Ladder
44. vibration limit switch in a NEMA 4 housing shall be installed on the mechanical equipment support for wiring into the fan motor shutdown circuit The purpose of this switch will be to interrupt power to the motor in the event of excessive vibra tion It shall be adjustable for sensitiv ity and shall require manual reset Basin Heater Add the following paragraph in the Cold Water Provide an electric immer sion heater for each cell of the tower to prevent freezing of water in the collection basin during periods of shut down The rod type heater is installed in the side of the cold water basin Each heater will include an integral thermostat set point nominally 4 C but adjustable to suit local operating requirements Fan Motor Variable Speed Drive Add the following paragraph in the Mechanical Equipment section when VFD is used as a stand alone system A complete UL listed Variable Speed Drive system in a IP52 indoor or IP56 3R outdoor enclosure shall be pro vided The VFD shall use PWM technol ogy with IGBT switching and integrated bypass design VFD output switching shall not cause mechanical issues with gearbox teeth or drive shafts The VFD shall catch a fan spinning in the reverse direction without tripping The panel shall include a main disconnect with short circuit protection and external operating handle lockable in the off position for safety The system shall include a solid state PI temperature controller to