Home

Sanyo CH0951 User's Manual

image

Contents

1. Press the operation button and start cooling opera tion When the low pressure gauge reading falls to 1 to 0 5 kg cm 14 2 to 7 1 PSI fully close the wide tube valve stem with a standard screwdriver Then quickly stop the unit Disconnect all gauges and hoses and replace the bonnets and the valve caps as they were before 7 Remote Control Unit Installation Position The remote control unit can be operated from either a non fixed position or a wall mounted position To ensure that the air conditioner operates correctly do not install the remote control unit in the following places In direct sunlight Behind a curtain or other place where it is covered More than 26 ft 8 m away from the air conditioner In the path of the air conditioner s airstream Where it may become extremely hot or cold Where it may be subject to electrical or magnetic interference 7 1 Mounting on a Wall 1 Confirm the indoor unit beeps when the ON OFF button is pressed at the wall location where the remote control unit is to be attached then attach the holder to the wall Fig 56 2 When taking out the remote control unit pull it from the holder When using the remote control unit e Point the transmission portion of the remote control unit at the receiver area of the indoor unit when operating the remote control unit and during operation of the air conditioner e Do not place objects that may block the trans mitted signals betw
2. SANYO INSTALLATION INSTRUCTIONS Split System Air Conditioner COOL DRY HEAT Model_ Contents Model Combinations Page IMPORTANT Combine indoor and outdoor units only as listed Please Read Before Starting ccccccceee 2 below Indoor Units Outdoor Units Te GENERAL 4 22 ees nee eae 3 1 1 Tools Required for Installation not supplied KHS0951 CH0951 1 2 Accessories Supplied with Unit 1 3 Optional Copper Tubing Kit KHSTZST CH1251 1 4 Type of Copper Tube and Insulation Material Power sores 1 5 Field Wiring l l 60 Hz single phase 115 V 1 6 Additional Materials Required for Installation 2 INSTALLATION SITE SELECTION 4 KHS1852 CH1852 2 1 Indoor Unit 2 2 Outdoor Unit Power Source 60 Hz single phase 230 208 V 3 HOW TO INSTALL THE INDOOR UNIT 6 3 1 Remove the Rear Panel from the Unit 3 2 Make a Hole 3 3 Install the Rear Panel on the Wall 3 4 Remove the Grille to Install the Indoor Unit 5 7 Finishing the Installation 3 5 Shape the Indoor Side Tubing 6 AIR PURGING 0 00 18 3 6 Wiring Instructions E Air Purging with a Vacuum Pump for Test Run 3 7 Recommended Wire Length and Diameter E Basic Function of the Service Valves 3 8 Wiring Instructions for Inter unit Connections E Pump Down 3 9 Mounting 3 10 Drain Hose 7 REMOTE CONTROL UNIT INSTALLATION POSITION aa aee sessile esd castles 22 4 HOW TO INSTALL THE OUTDOOR UNI
3. In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support Ina Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation for the outdoor unit This prevents water damage and abnormal vibration In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow Provide snow vents When Connecting Refrigerant Tubing e Use the flare method for connecting tubing e Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection e Check carefully for leaks before starting the test run When Servicing e Turn the power OFF at the main power box mains before opening the unit to check or repair electrical parts and wiring e Keep your fingers and clothing away from any moving parts e Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the un
4. tion and the possibility of fire do oF 5 cm min a not place obstacles enclosures 2 5 cm min 6 15 cm min 2 cm min and grilles in front of or surround 68 15 cm min 6 15 cm min ing the air conditioner in a way that may block air flow Yy KHS1852 only Front View AVOID Fig 2 direct sunlight nearby heat sources that may affect performance of the INDOOR Tubing length L unit UNIT areas where leakage of flammable gas may be expected ree Elevation places where large amount of oil mist exist difference H ee DO select an appropriate position from which every corner of Fig 3a the room can be uniformly cooled High on a wall is best select a location that will hold the weight of the unit fiskur select a location where tubing and drain hose have the shortest run to the outside Fig 1 S Wall For stable operation of allow room for operation and maintenance as well as unre the alr conditioner do Minimum height stricted air flow around the unit Fig 2 not install wall mounted from floor level Fy ee type indoor units under Sato install the unit within the maximum elevation difference H 5 ft 1 5 m from floor above the outdoor unit and within a total tubing length L al i from the outdoor unit as detailed in Table 3 and Fig 3a 3 Floor ieye Fig 3b Table 3 Max Allowable Tubing Limit of Tubing Limit of Elevation Required Amou
5. 2 to 2 1 2 CHO9 12 2 1 2 to 3 CH18 in x Drain holes o 16 in 5 to 6 5 6 5 to 7 5 x 40 cm beams or equal a minimum of 4 in 10 cm above ground level to reduce humidity and protect the unit against possible ED ED water damage and decreased service life Figs 5b Fig 5b and 5c Anchor bolts 4 pcs CAUTION A solid base must not cover the hole of the bottom plate use lug bolts or equal to bolt down unit reducing amp vibration and noise Air intake Concrete eer or equal to 2 1 2 5 to 6 5 cm CH18 1 2 to 3 6 5 to 7 5 cm Fig 5c 3 How to Install the Indoor Unit 3 1 Remove the Rear Panel from the Unit 1 Remove and discard the set screw on the rear panel Fig 6 2 Press the 2 A marks on the frame cover and disengage the sta tionary tabs from the frame Fig 7 3 Remove the rear panel NOTE Set screw only for transportation Fig 6 Tubing can be extended in 5 directions KHS0951 KHS1251 and g KHS1852 as shown in Fig 8a or 8b Select the direction you need Rear panel providing the shortest run to the outside unit 3 2 Make a Hole 1 Place the rear panel from the indoor unit on the wall at the loca tion selected Make sure the panel is horizontal using a carpen ter s level or tape measure to measure down from the ceiling Wait until after cutting the hole before attaching the rear panel to the wall 2 Determine which side of the unit you should make the
6. from the wall with the outdoor side tubing Fig 47 Torque wrench Spanner Indoor unit b To fasten the flare nuts apply specified torque as Table 5 Outdoor unit Tube Dia Tightening Torque Fig 47 1 4 6 35 mm Approx 130 170 lbs in 150 200 kg cm 3 8 9 52 mm Approx 300 340 Ibs in 350 400 kg cm in in 1 2 12 7 mm Approx 430 470 Ibs in 500 550 kg cm 5 8 15 88 mm Approx 520 560 lIbs in 600 650 kg cm an r r Insulation 5 5 Insulation of Refrigerant Tubing Fig 48 IMPORTANT To prevent heat loss and wet floors due to dripping of con densation both tubes must be well insulated with a prop eo er insulation material Fig 48 The thickness of the insula Pee i Min Thickness tion should be a minimum 5 16 8 mm Fig 49 5 16 8 mm min 5 16 8 mm Ne After a tube has been insulated never try to bend it into a narrow curve as this may cause the tube to Fig 49 break or crack 5 6 Taping the Tubes a Atthis time the 2 refrigerant tubes and electrical wire if local codes permit should be taped together with armor ing tape The drain hose may also be included and taped together as 1 bundle with the tubing Insulated tubes b Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall As you wrap the tubing overlap ha
7. hole for tubing and wiring Fig 9 KHS0951 KHS1251 Right rear tubing recommended 3 Before making the hole check carefully that no studs or pipes are directly run behind the spot to be cut tubing CAUTION Left rear i tubing Right tubing Also avoid areas where electrical wiring or conduits are Fig 8a located Downward tubing Switching drain hose and drain cap KHS1852 a Locate the drain hose and the drain cap Fig 8c Left tubing Right rear tubing b Remove the drain hose on the right side by pushing and recommended turning the hose connector counter clockwise to release it Fig 8c c Apply moderate force to pull off the drain cap on the left side If you cannot pull it off by hand use a long nose pli Right tubing ers Fig 8b J F D d i d Reattach the drain hose to the left side and the drain cap ownward tuging to the right side Fig 8c The above precautions are also applicable if tubing goes through the wall in any other location In case of right rear Fig 9 4 Using a sabre saw key hole saw or hole cutting drill attachment cut a hole in the wall See Table 4 and Fig 10 Table 4 Hole Dia 2 9 16 65 mm 3 5 32 80 mm 5 Measure the thickness of the wall from the inside edge to the outside edge and cut PVC pipe at a slight angle 0 25 in 6 mm shorte
8. hose to manifold valve Fig 53 How to Test Run the Air Conditioner 1 Switch on the power source 2 Press the ON OFF button on the remote control unit once 3 Set the operation selector switch of the indoor unit to the TEST position This starts the fan producing uncooled forced air Figs 54a and 54b 4 After 3 minutes the system shifts into cooling operation and cool air will start to be felt Cooling operation during with the switch at the TEST posi tion is unaffected by the room temperature 5 After stopping the test run turn the operation selector switch of indoor unit to the OFF position once then move to ON position 6 Press the ON OFF button on the remote control unit to stop the air conditioner If the unit does not operate and the OPERATION lamp on the unit is blinking after going through the proce dure check the wiring between the units 20 KHS0951 KHS1251 ON OFF TEST OPERATION TIMER STANDBY Fig 54a KHS1852 7 r Operation OFF 4 selector switch Fig 54b m Basic Function of the Service Valves The basic function of the service valves are given in Table 7 below Table 7 Action Narrow Tube Service Wide T
9. T 15 7 1 Mounting on a Wall 4 1 Wiring Instructions for the Outdoor Unit 5 REFRIGERANT TUBING cceee 16 5 1 Use of the Flaring Method IMPORTANT 5 2 Flaring Procedure with a Flare Tool A N 5 3 Caution before Connecting Tubes Tightly P f H0951 H1251 is 60 H 5 4 Connecting Tubing between Indoor and ower souros foro HOgSTrand C 3 Outdoor Units single phase 115 V 5 5 Insulation of Refrigerant Tubing 5 6 Taping the Tubes In Canada SANYO FISHER COMPANY SANYO Canada Inc A DIVISION OF SANYO NORTH AMERICA CORPORATION 300 Applewood Crescent Concord 21605 Plummer Street Ontario L4K 5C7 Canada 85264189615003 SANYO 2002 Chatsworth CA 91311 U S A W IMPORTANT Please Read Before Starting This air conditioning system meets strict safety and operating standards As the installer or service person it is an important part of your job to install or service the system so it operates safely and efficiently For safe installation and trouble free operation you must Carefully read this instruction booklet before beginning Follow each installation or repair step exactly as shown Observe all local state and national electrical codes Pay close attention to all warning and caution notices given in this manual This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death This symbol refers to a hazard or CAUTION unsare practice which
10. TDOOR UNIT Swie Power lines Terminal Field supply Terminal pn 0T D 070 gt er gt a O na L 52x Inter unit N 3 ao Control lines Boe O neces se eee l Grounding line CH1852 Model INDOOR UNIT Diseonnect Inter unit OUTDOOR UNIT SwE Power lines Terminal Field supply Terminal poe 0T 9 3 OO S la a a A 2 S gt S ea nQ 2 DEER Inter unit 8 L2 OF Z Control lines x O a be Sosss es Grounding line Fig 23 Wall 10 c Remove the screws to open the cover plate secur ing the electrical component box Figs 25a 25b 25c and 25d d Insert the wrapped tubing into the hole in the wall e Hang the indoor unit on the rear panel f Using a Phillips screwdriver take out the screws on the earth plate Fig 26a KHSO9 12 models only Remove the earth plate g Remove the lock nut from the conduit connector Insert the conduit connector through the opening from the underside of the electrical component box After insertion Fit the screw at the top of the con duit connector into the cut out Fig 26b Position the earth plate over the conduit connector allowing the connector and wires to extend through the hole in the plate Next attach the conduit connector to the earth plate by replacing and tightening the lock nut Figs 26c and 26d Then re attach the earth plate to the electrical component box with the 2 screws h Give s
11. ach power wire to the corresponding termi nal follow the instructions How to connect wiring to the termi nal and fasten the wire securely tight with the fixing screw of the terminal plate How to connect wiring to the terminal a For Indoor Unit 1 Cut the wire end with a cutting pliers then strip the insu lation to expose the wire about 9 32 in 7 mm See the label Fig 28 near the terminal plate 2 Using a screwdriver loosen the terminal screw on the ter minal plate 3 Insert the wire and tighten the terminal screw completely using a screwdriver b For Outdoor Unit E For solid core wiring or F cable 1 Cut the wire end with a cutting pliers then strip the insu lation to expose the solid wire about 15 16 in 25 mm Fig 29 2 Using a screwdriver remove the terminal screw s on the terminal plate 3 Using the pliers bend the solid wire to form a loop suit able for the terminal screw 4 Shape the loop wire properly place it on the terminal plate and fix it securely with the removed terminal screw using a screwdriver E For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insu lation to expose the stranded wiring about 3 8 in 10 mm and tightly twist the wire ends Figs 30 and 31 2 Using a screwdriver remove the terminal screw s on the terminal plate 3 Using a ring connector fastener or pliers securely clamp each stripped wire end with a rin
12. can result in personal injury or product or property damage If Necessary Get Help These instructions are all you need for most installation sites and maintenance conditions If you require help for a special problem contact our sales service outlet or your certified dealer for additional instructions In Case of Improper Installation The manufacturer shall in no way be responsible for improp er installation or maintenance service including failure to follow the instructions in this document SPECIAL PRECAUTIONS When Wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH ONLY A QUALIFIED EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked e Highly dangerous electrical voltages are used in this system Carefully refer to the wiring diagram and these instructions when wiring Improper connections and inadequate grounding can cause accidental injury or death Ground the unit following local electrical codes e Connect all wiring tightly Loose wiring may cause over heating at connection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and out door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu minum fins on the air conditioner can cut your fingers When Installing
13. e tubing if necessary to run A along the wall in the direction of the outdoor unit Refrigerant and then tape as far as the fittings See Caution tuong on page 17 The drain hose should come straight ADADARRARN A down the wall to a point where water runoff won t I tntertihit stain the wall wiring 4 I Drain hose 4 Connect the refrigerant tubing to the outdoor unit After performing a leak test on the connecting part insulate it with the tubing insulation Fig 37a Also refer to Section 5 4 Connecting Tubing between Indoor and Outdoor Units 5 Assemble the refrigerant tubing drain hose and conduit including inter unit wiring as shown in Fig 37b Esa Refrigerant tubing n E 2 a Insulation Fig 37a O V O Oxo Conduit Drain hose Inter unit wiring Fig 37b To unmount indoor unit Press the 2 A marks on the lower part of the indoor unit and unlatch the tabs Then lift the indoor unit and unmount Fig 38 3 10 Drain Hose a The drain hose should be slanted downward to the outdoors Fig 39 b Never form a trap in the course of the hose c Ifthe drain hose will run in the room insulate the hose with insulation so that chilled condensation will not damage furniture or floors Fig 40 Foamed polyethylene or its equivalent is recom mended Do not supply power to the unit or operate it until all tubing and wiring to the o
14. een the receiver and the remote control unit When mounting the remote control unit to prevent theft 1 Mount the holder to the wall with one of the screws using only the hole in the top of the holder Fig 57 2 Remove the cover of the remote control unit and take out the batteries Next place the remote control unit in the holder 3 Fasten both the remote control unit and holder to the wall with the remaining screw using the hole in the bottom of the holder 4 Install the batteries in the remote control unit and close the cover 22 Truss head tapping screw 5 32 x 5 8 4 x 16mm supplied Remote control unit holder Truss head tapping screw 5 32 x 5 8 4 x 16mm supplied Holder Holder
15. g connector Fig 30 4 Place the ring connector wire and replace and tighten the removed terminal screw using a screwdriver Fig 32 12 9 32 7mm ACTUAL STRIP SIZE SIZE ZZZZ Fig 28 E Solid wire Ke aL Loop 3 oO 3 E 2 5 Insulation Fig 29 pS Stranded wire 3 I Ring A N Connector ee m 2 ao Fig 30 Twist wire ends amp Special washer Pa Screw a Ring connector x Terminal plate Fig 31 ail D Screw and special washer Ring a connector ZZ 3 9 Mounting 1 To install the indoor unit mount the indoor unit onto the 2 tabs on the upper part of the rear plate 2 Hold down the air discharge outlet and press the lower part of the indoor unit until it clicks to secure ly fasten to the 2 tabs on the lower part of the rear plate Fig 33 For tubing choose either the right or left tubing direc tion and follow the steps below Also extend the sup port on the back of the indoor unit as a stand to make your work easier Fig 34 Push Fig 33 E Right side tubing 1 Shape the refrigerant tubing so that it can easily go Stand into the wall hole Fig 35 2 Push the wiring refrigerant tubing and drain hose Fig 34 through the hole in the wall Adjust the indoor unit oe Rear panel so it is securely seated on the rear panel Fig 36 Cover 3 Carefully bend th
16. ht rear or left rear tubing In this case the corner of the frame need not be cut 2 To mount the indoor unit on the rear panel Hang the 2 mounting slots of the unit on the upper tabs of the rear panel Fig 22 3 6 Wiring Instructions General precautions on wiring 1 Before wiring confirm the rated voltage of the unit as shown on its nameplate then carry out the wiring closely following the wiring diagram Provide a power outlet to be used exclusively for each unit with a power supply disconnect and cir cuit breaker for overcurrent protection provided in the exclusive line To prevent possible hazard due to insulation failure the unit must be grounded Each wiring connection must be done tightly and in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate or become damaged Do not allow wiring to touch the refrigerant tubing compressor or any moving parts of the fan Unauthorized changes in the internal wiring can be very dangerous The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes ts ee Frame Left tubing outlet li Frame Right tubing outlet 3 7 Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality For field wiring requirements please refer to your local electrical codes Carefully observe these reg
17. ig 14 3 16 4 8 mm TA dia hole gt Rawlplug Fig 15 3 4 Remove the Grille to Install the Indoor Unit Basically these models can be installed and wired with out removing the grille If access to any internal part is needed follow the steps as given below How to remove the grille 1 Set the flap in the horizontal position 2 Unscrew the screws Fig 16a or 16b 3 Remove the grille Fig 17 a Hold both corners of the air intake grille then pull out and up to open b Pull the lower part of the grille toward you to remove c Use a standard screwdriver to push up the 3 tabs to remove the grille How to replace the grille 1 Close the flaps 2 Reinstall the grille into the lower part while aligning its tabs on the upper part Fig 18 Insert the tabs in the slots and push the lower part of the grille back into position 3 Press at each of the 4 tabs to completely close the grille Make sure that the grille and frame are firmly fitted together Fig 19 KHS0951 KHS1251 Ow N ANY w 7 Na Screw cover Flap Up and down air direction louvre Fig 16a KHS1852 Fig 18 3 5 Shape the Indoor Side Tubing 1 Arrangement of tubing by directions a Right or left tubing Cut out the corner of the right left frame with a hacksaw or the like Figs 20 and 21 b Rig
18. it being serviced 1 General This booklet briefly outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning 1 1 Tools Required for Installation not supplied 1 Standard screwdriver 2 Phillips head screwdriver 3 Knife or wire stripper 4 Tape measure 1 2 Accessories Supplied with Unit 5 Carpenter s level 6 Sabre saw or key hole saw 7 Hacksaw 8 Core bits 9 Hammer 10 Drill 11 Tube cutter 12 Tube flaring tool 13 Torque wrench 14 Adjustable wrench 15 Reamer for deburring Table 1 Parts Figure Q ty Parts Figure Q ty Parts Q ty Truss head Rawl plug 42 Tapping Phillips Y 12 Pemolg l screw 5 32 x 5 8 4 x 16 mm control unit Remote Drain hose AAA alkaline control 1 2 adapter qaq O 1 holder battery Hex f 1 wrencn L Packed in the outdoor unit 1 3 Optional Copper Tubing Kit Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing fittings and insulation Consult your nearest sales outlet or A C workshop 1 4 Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrigeran
19. kwise to close it again Fig 53 CAUTION Be sure to completely insert the hex wrench before attempting to turn the valve 7 Leak test all joints at the tubing both indoor and outdoors with liquid soap Bubbles indicate a leak Be sure to wipe off the soap with a clean cloth 8 With the hex wrench turn the wide tube service valve stem counter clockwise to fully open the valve 9 Turn the narrow tube service valve stem counter clockwise to fully open the valve 10 Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure Then remove the hose 11 lt Replace the bonnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench Next mount the valve cap and tighten it with a torque wrench the cap needs to be tightened with the torque of 170 Ibs in 200 kg cm This process is very important to prevent gas from leaking from the system 12 Test run the air conditioner See next page 13 While the air conditioner is running apply liquid soap to check for any gas leaks around the ser vice valves or caps 14 If there is no leakage stop the air conditioner 15 Wipe off the soap on the tubing This completes air purging with a vacuum pump and the air conditioner is ready for actual operation 19 SOP letun Narrow tube A jL pee s Hex wrench A Valve cap Vacuum
20. lf of each previous tape turn Fig 50 c Clamp tubing bundle to wall using 1 clamp approx every 47 in 120 cm Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also be sure the conden sation drain hose splits away from the bundle and drips clear of the unit and the tubing Fig 50 Apply putty here Tubing Fig 51 5 7 Finishing the Installation After finishing insulating and taping over the tubing use seal ing putty to seal off the hole in the wall to prevent rain and draft from entering Fig 51 17 6 Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below Therefore they must be purged completely pressure in the system rises operating current rises cooling or heating efficiency drops moisture in the air may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant sys tem E Air Purging with a Vacuum Pump for Test Run 1 Check that each tube both narrow and wide tubes between the indoor and outdoor units have been properly connected and all wiring for the test run has been com pleted Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage Using an adjustable wrench or box wrench remove the valve caps from the service valve on both narrow and wide tubes 3 Connect a vacuum pump and a manif
21. nt of Length at Shipment Length L Difference H Additional Refrigerant Model ft ft ft oz ft 25 50 23 a 0 16 9 000 BTU 25 65 23 b 0 27 12 000 18 000 BTU If total tubing length becomes a 25 to 50 ft max b 25 to 65 ft max charge additional refrigerant R22 by a 0 16 oz ft b 0 27 oz ft No additional compressor oil is necessary 2 2 Outdoor Unit NO 7 AVOID heat sources exhaust fans etc Fig 4 Exhaust fan _ Heat source Hot air NY damp humid or uneven locations Do Outdoor unit choose a place as cool as possible choose a place that is well ventilated allow enough room around the unit for air intake Fig 4 exhaust and possible maintenance Fig 5a Obstacle above Min Min 14 2 7f 7 ft amp 2m 2m Install the outdoor unit above snowfall line 3 Air intake f Min 6 15 cm 2 a Ee e Do not place objects on or sit on the out Ed 2 door unit Also never block the air ae s Q intake outlet or exhaust Distortion of the i Min 6 Air discharge Min 12 _ outdoor unit or incomplete combustion 15 cm i 30 cm may result Gro nd Do not introduce foreign matter into the air ice au intake outlet or exhaust Do not poke them Air intake with such objects as a stick Fig 5a provide a solid base level concrete pad concrete fata m block
22. old valve with pres sure gauges to the service port on the wide tube service valve Fig 52 CAUTION Be sure to use a manifold valve for air purging If it is not available use a stop valve for this purpose The Hi knob of the manifold valve must always be kept closed S With the Lo knob of the manifold valve open run the vacuum pump The operation time for the vacuum pump varies with tubing length and the capacity of the pump The following table shows the amount of time for evacua tion Table 6 Required time for evacuation when capacity of 100 liter h vacuum pump is used If tubing length is If tubing length is less than 33 ft 10 m more than 33 ft 10 m 10 min or more 15 min or more The required time in the above table is calculated based on the assumption that the ideal or target vacuum condition is around 10 mmHg abs 18 Indoor unit 4 Outdoor unit 4 Dy Manifold valve Pressure K Oui gauge 2 3 ji es x aco Vacuum pump Fig 52 5 With the vacuum pump still running close the Lo knob of the manifold valve Then stop the vacuum pump 6 With the accessory hex wrench turn the valve stem on the narrow tube service valve counter clockwise by 90 degrees 1 4 turn for 10 seconds and then turn the stem cloc
23. ome play to the inter unit wiring from the out door unit to the corresponding terminals on the termi nal base See Wiring System Diagram on page 10 ANu e Be sure to refer to the Wiring System Diagram label inside the electrical component box and carry out the correct field wiring Wrong wiring can cause the unit to misoperate or result in a fire hazard Check local electrical codes and any specified wiring instructions or limitations i Fix cover plate and cover plate and back into posi tion with their screws When closing the air intake grille press on both corners and the center Fig 27 KHS0951 KHS1251 Electrical component box Fig 25a KHS1852 Electrical component box Fig 25c KHS0951 KHS1251 KHS0951 KHS1251 KHS0951 KHS1251 plate Earth plate Electrical component box Fig 25b Terminal plate Earth plate Electrical Component box Fig 25d KHS1852 TOP of conduit connector Inter unit Inter unit Power line Control line wiring iri Fig 26c 11 KHS1852 Inter unit Control line Wiring 2 Power line maa Earth Lock plate nut Top of conduit Fig 26d MWV i ii em Loose wiring may cause the termi nal to overheat or result in unit mal function A fire hazard may also exist Therefore be sure all wiring is tightly connected When connecting e
24. r than the thick ness of the wall Fig 11 6 Place the plastic cover locally purchased over the end of the pipe for indoor side only and insert the pipe in the wall Fig 12 3 3 Install the Rear Panel on the Wall Be sure to confirm that the wall is strong enough to sus pend the unit See either Item a or b below depending on the wall type a If Wooden Wall 1 Attach the rear panel to the wall with the 10 screws provided Fig 13 If you are not able to line up the holes in the rear panel with the beam locations marked on the wall use rawl plugs or toggle bolts to go through the holes on the panel or drill 3 16 in 5 mm dia holes in the panel over the stud locations and then mount the rear panel S Double check with a ruler or carpenter s level that the panel is level This is important to install the unit properly Fig 14 Make sure the panel is flush against the wall Any space between the wall and unit will cause noise and vibration b If Block Brick Concrete or Similar Type Wall Make 3 16 in 4 8 mm dia holes in the wall Insert rawl plugs for appropriate mounting screws Fig 15 Hole should be made at a slight downward slant to the outdoor side INSIDE Plastic cover Indoor Outdoor side Cut at slight angle Fig 11 OUTSIDE Wall PVC pipe LA Sight EnS A angle F
25. t tubing as detailed in Table 2 When cutting tubing add approximately 12 to 16 30 cm to 40 cm to each tube length to reduce Foamed polyethylene insulation for the specified O D copper tubes as required to precise length of tubing Wall thickness of the insulation should be not less than 0 3 in 8 mm 1 5 Field Wiring Use insulated copper wire for field wiring Wire size varies with the total length of wiring Refer to 3 6 Wiring Instructions for details CAUTION Check local electrical codes and regulations before obtaining wire Also check any specified instructions or vibration between the air conditioning units limitations Table 2 Narrow Tube Wide Tube Model Outer Dia Thickness Outer Dia Thickness 6 35 mm 1 4 0 8 mm 0 0314 9 52 mm 3 8 0 8 mm 0 0314 CH0951 6 35 mm 1 4 0 8 mm 0 0314 12 7 mm 1 2 0 8 mm 0 0314 CH1251 6 35 mm 1 4 0 8 mm 0 0314 15 88 mm 5 8 1 0 mm 0 0394 CH1852 1 6 Additional Materials Required for Installation Indoor unit 1 Refrigeration armored tape 2 Insulated staples or clamps for connecting wire See local codes 3 Putty 4 Refrigeration lubricant 5 Clamps or saddles to secure refrigerant tubing Z Go Drain hose 2 Installation Site Selection l Outside drainage 2 1 Indoor Unit Fig 1 To prevent abnormal heat genera a
26. te to prevent water from entering The following are examples of improper wiring that result in system misoperation You should confirm that you have wired the units correctly before beginning the test run Problem 1 e Short circuit will occur after approx 3 minutes and the power circuit fuse blows Disconnect Outdoor unit Indoor unit Problem 3 O oJ 7 Indoor unit Problem 2 Grounding line e Compressor will not start only indoor unit will operate Disconnect switch Indoor unit Outdoor unit E Disconnect switch Outdoor unit e Air conditioner will not operate Disconnect switch C ay Oto NE C ordie Indoor unit Outdoor unit Indoor unit Grounding line 15 Outdoor unit 5 Refrigerant Tubing 5 1 Use of the Flaring Method Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units In this method the copper tubes are flared at each end and connected with flare nuts 5 2 Flaring Procedure with a Flare Tool a Cut the copper tube to the required length with a tube cutter It is recommended to cut approx 12 to 20 in 30 to 50 cm longer than the tubing length you estimate b Remove burrs at the end of the copper tube with a
27. tube reamer or file This process is important and should be done carefully to make a good flare Fig 42 When reaming hold the tube end downward and be sure that no copper scraps fall into the tube Fig 43 c Remove the flare nut from the unit and be sure to mount it on the copper tube d Make a flare at the end of copper tube with a flare tool Fig 44 Use RIGID or equivalent A good flare should have the following characteristics inside surface is glossy and smooth edge is smooth tapered sides are of uniform length 5 3 Caution before Connecting Tubes Tightly a Be sure to apply a sealing cap or water proof tape to prevent dust or water from getting into the tubes before they are used b Be sure to apply refrigerant lubricant to the match ing surfaces of the flare and union before connect ing them together This is effective for reducing gas leaks Fig 45 c For proper connection align the union tube and flare tube straight with each other then screw in the flare nut lightly at first to obtain a smooth match Fig 46 16 Before Deburring After tubing Vo Flare tool Fig 44 Apply refrigerant lubricant here and here Copper vga Flare nut 9 a tubing T Union Flare nut Fig 46 Copper 5 4 Connecting Tubing between Indoor and Outdoor Units a Tightly connect the indoor side refrigerant tubing extend ed
28. ube Service Valve 2 Way Valve 3 Way CLOSED y O ring Valve cap Shipping aie A a CLZLLA Fully OPEN ip 4 Z Operating and test running 224 KZZ j sa the air conditioner Fully OPEN lt Measuring pressure and gas charging Af Aj call Mz m I Air purging with F a vacuum pump 3 Aj The service port on the wide tube service valve uses a Schrader core valve to access the refrigerant system Therefore be sure to use a hose connector which has a push pin inside Fig 55 Pump Down Pump down means collecting all refrigerant gas in the system back into the outdoor unit without losing any of the gas Pump down is used when the unit is to be moved or before servicing the refrigerant circuit Pump Down Procedure Be sure to carry out pump down with the unit in cooling mode 1 Connect the Lo side charging hose of the manifold valve to the service port on the wide tube service valve 2 Using a hex wrench turn the narrow tube service 21 Service valve SS mn I TIT 5 LJ Fig 55 valve clockwise all the way to close the service valve Be sure to confirm that the wide tube ser vice valve is fully open
29. ulations when carrying out the installation Refer to the wiring system diagram Fig 23 Refer to your local codes or in the absence of local codes with the National Electric Code ANSI NFPA70 WARNING e Be sure to comply with local codes on running the wire from the outdoor unit to the indoor unit size of wire and wiring method etc e Each wire must be firmly connected No wire should be allowed to touch refrigerant tubing the compressor or any moving part WARNING e To avoid the risk of electric shock each air conditioner unit must be grounded J N ane e Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram The indoor unit draws its power from the outdoor unit 3 8 Wiring Instructions for Inter unit Connections a Remove the grille See 3 4 Remove the Grille to Install the Indoor Unit on page 8 b Insert the inter unit wiring according to local codes into the through the wall PVC pipe Run the wiring toward the indoor side allowing approx 10 in 25 cm to extend from the wall face Fig 24 Never fix the wiring by any means before the indoor unit is fully seated on the rear panel WIRING SYSTEM DIAGRAM CH0951 CH1251 Models INDOOR UNIT Diseonnect Inter unit OU
30. utside unit are completed Risk of Electric Shock 14 Push Fig 38 Slant Indoor unit Drain hose Fig 39 Condensation ze og 0 t Insulation material SSD locally purchased must be used Fig 40 4 How to Install the Outdoor Unit First refer to Section 2 Installation Site Selection 4 1 Wiring Instructions for the Outdoor Unit Regulations on wire size differ from locality to locality For field wiring requirements please refer to your local electrical codes Make sure that the installation fully complies with all local and national regulations Remove access panel Fig 41 panel side Connect the power line according to the drawing on the Be sure to size each wire allowing approx 4 in 10 cm longer than the required length for wiring Store excess wiring inside the cabinet When connections are completed check that all connec tions are correct as shown in the wiring system diagram on panel side m Examples of Incorrect Wiring Be sure to ground the unit according to your local codes Terminal Lock nut block Access panel Conduit plate 6 K ea Power supply Plug Power line Control line Conduit Conduit Sheath cable Fig 41 Apply sealer putty etc to the gap between the sheath cable and the hole of the conduit pla

Download Pdf Manuals

image

Related Search

Related Contents

Toshiba PCX1000 Network Card User Manual  Black Box ServSwitch Wizard IP Plus  Refrigeradores y congeladores compactos  Cables Direct Cat5e UTP 5m    

Copyright © All rights reserved.
Failed to retrieve file