Home
Remeha Avanta Plus HMI Gas 310/610 Eco Pro Installation User and Service Manual
Contents
1. 53 State 61 Sub status Flow temperature Return temperature Outside temperature C Only with an outside temperature sensor Accessory 6 Exchanger temperature S Internal set point F L 7 lonization current pA al Fan speed rpm Water pressure bar MPa Only with the hydraulic pressure sensor connected Accessory P a Supplied relative heat output 5 Pressure switch minimum Gps Not connected i Gas pressure 2 Gas pressure incorrect Only with connected minimum gas pressure switch Accessory 5 Gas valve leak proving system Vps Not connected i No gas leak 2 Gas leak present Only with connected gas leakage control Accessory Analogue input V Llg Analogue output V The current values can be read as follows 6 Press the key The readout cycle starts again with 5 Press the two Y keys simultaneously The symbol flashes nfirm using key 5 is displayed alternating with the current status 3 for example Press the key 5 is displayed alternating with the current sub status 3 5 for example Lu
2. 2 Select the installers menu using the key 171712121 appears on the display Use keys or to input the installer code PT 3 4 Confirm using key P is displayed with y flashing 5 Press the key to go to parameter 5 1 7 6 Confirm using key 7 Press the button to reduce the speed from 514 to 5 for example 8 Confirm the value with the lt key 9 Press the key 2 times to return to the current operating mode lt 3 2x T004356 A 19 160514 125482 04 HMI Gas 310 610 PRO 5 Commissioning 5 3 5 Return to the factory settings A CAUTION By restoring the factory settings customized settings can also be erased So first write down all the customized parameters eg settings for attached accessories such as a flue gas valve or gas leak control Adjust these specific settings again after the factory settings have been restored 1 Press the two keys Y simultaneously and then key until the E symbol f flashes on t
3. pla Display screen 2 minutes 3 Automatic switching to simple after 3 minutes Key blocking is active v 0 Dimmed PIS Brightness of display lighting 1 Bright 1 7 Maximum fan speed 620 Gas H 52 55 35 38 43 41 100 x G20 Gas H PI 18 Minimum fan speed x100 rpm 14 15 9 10 11 10 PLAS offset Minimum fan speed PO not modify 50 50 50 50 x1 rpm Do not modify Pell Start speed x100 rpm 25 25 13 14 14 14 Pa Maximum flow temperature of 0 to 90 90 system Heat curve set point Maximum outside temperature Piele Only with an outside temperature sensor Accessory Heat curve set point Flow temperature Plel3 Only with an outside 0 to 90 20 temperature sensor Accessory 0 to 30 20 Heat curve set point Minimum outside temperature Plel4 Only with an outside temperature sensor Accessory Antifreeze temperature Alels xi with an outside emperature sensor Accessory 30 to 0 C 15 from 30 to 0 10 relay function 4 0 Operation signal If connected 1 Alarm signal Fault relay function X5 0 Operation signal If connected 1 Alarm signal Minimum water pressure Wps Only with the hydraulic 0 7 bar MPa x 0 1bar MPa press
4. 13 5 3 1 Parameter descriptions 13 5 3 2 Modification of the user level parameters 18 5 3 3 Modification of the installer level parameters 18 5 3 4 Setting the maximum heat input for central heating 19 5 3 5 Return to the factory settings 20 5 3 6 Carrying out an auto detect 20 5 3 7 Setting the manual mode 21 LR remeha 160514 125482 04 Contents 6 Troubleshooting 6 2 A 22 Shutdowns and lock outs 22 6 1 1 22 6 1 2 BIOCKING 22 6 1 3 Lock OU ladies 24 Error MEMORY iii 27 6 2 1 Error readout memorised 28 6 2 2 Deletion of the error display 29 160514 125482 04 LR remeha 160514 125482 04 HMI Gas 310 610 ECO PRO 1 Introduction 1 1 Symbols used 1 2 Abbreviations 1 3 Liabilities 160514 125482 04 1 Introduction In these instructions various danger levels are employed to draw the user s attention to particular information In so doing we wish to safeguard the user s safety obviate hazards and guarantee correct operation of the appliance DANGER Risk of a dangerous situation causing serious phy
5. I flashing appears and c3 flashes for example Change the value by pressing the or key In this example using key to B C Lu I flashing 18 5 Commissioning 700 539 500 400 200 1091 0 Ea M F 3000 4300 5000 R R000279 TEITE 16 101916 AA ri u 1 i K P id a P jdn HMI Gas 310 610 ECO PRO 8 If necessary set other parameters by selecting them using the or keys 9 Press the key 2 times to return to the current operating mode The boiler also returns to operating status if no keys are pressed for 3 minutes 5 3 4 Setting the maximum heat input for central heating operation Type Gas 310 ECO PRO 575 M Maximum heat input natural gas F Factory setting Q Power input kW R Fan rotation speed rpm The speed can be changed using parameter P 1 A linear relationship exists between the speed and the input See graph A graph for the other boilers can be produced in the same way 1 Press the two keys Y simultaneously and then key until the symbol f flashes on the menu bar
6. lt 2 160514 125482 04 lx r A 2 L XD 3 or c p r tie T001530 B 6 Troubleshooting 6 2 1 Error readout memorised 1 Press the two keys Y simultaneously and then key until the symbol N flashes on the menu bar 2 Select the installers menu using the key 171712121 appears on the display Use keys or to input the installer code 7171 2 4 Press the key appears on the display Ele XIX 5 The fault list or shutdown list can be displayed by pressing the or key Confirm using key El W Y is displayed with flashing Last error which occured For example XIX Use or key to scroll through the faults or shutdowns 8 Press the key to display the details of the faults or shutdowns Press the or key to view the following information nl Number of times that the error occured The number of operating hours Se State Sub status ell Flow
7. Press the key y is displayed alternating with the current flow temperature 5 for example Lu Press the key successively to scroll down the various parameters 7 Press the key 2 times to return to the current operating mode CR remeha 160514 125482 04 HMI Gas 310 610 ECO PRO A LLL Y ky O ww 4 Alle 1 gt y m Y 9150 v Alle 1312121 y 1 t 11518 lo v Slelx 4 5 2 T000816 G State 5 t 0 Rest Boiler start Heat demana Burner start 160514 125482 04 5 Commissioning 5 2 2 Readout from the hour counter and percentage of successful starts 1 Press the two keys Y simultaneously and then key until the symbol flashes on the menu bar 2 Press the key y and the number of hours of boiler operation 351515 for example are displayed alternately 3 Press the key The display shows JJ is displayed alternating with the number of operating hours in central heating operation 51570 for example 4 Press the key The display shows 4 5 1 is displayed alternating with the
8. Chimney sweeping keys press the 2 and 3 keys simultaneously Y Menu keys press the 4 and 5 keys simultaneously 8 On Off switch 9 PC connection 9 LH The display has several positions and symbols and provides 10034790 Information on the operating condition of the boiler and any possible failures A service message may also appear the display Numbers dots and or letters may be displayed The symbols located above the function keys indicate their current function gt The display content can be changed using parameter 7 4 The brightness of the display lighting can be changed using parameter P 5 Key lock out is activated by setting parameter 4 to 3 If no key is pressed for 3 minutes the display lighting switches off and only the current water pressure the key and the s symbol are displayed Water pressure Only with the hydraulic pressure sensor connected Press the key for about 2 seconds to reactivate the display and other keys The 0 symbol disappears from the display 7 LR remeha 160514 125482 04 Gas 310 610 PRO 3 Technical description 3 1 2 Meaning of the symbols on the display Information menu On Off switch 0 1 Reading the various current values After 5 lock outs the boiler must be switched off on again User menu Central heating function Para
9. current Check the operation and setting of the gas valve unit 5 Flame loss Check that the air inlet and flue gas discharge flues are not blocked Check that there is no recirculation of flue gases Communication error Check whether the SU PCB has been correctly fitted with the SU PCB in the connector on PCU PCB Communication error Bad connection Check the wiring with the SCU PCB Defective SCU PCB Replace SCU PCB Bad connection Check the wiring Shutdown input in locked out mode External cause Suppress the external cause Parameter incorrectly set Check the parameters 6 2 Error memory The boiler control is equipped with an error memory The last 16 errors encountered are recorded in this memory In addition to the error codes the following data are also saved Number of times that the error occured in gt Boiler operating mode selected 5 The flow temperature E and the return temperature te XX when the error occured To view the error memory you first have to enter access code e LL 27 LR remeha 160514 125482 04 HMI Gas 310 610 ECO PRO 9 lt
10. 610 PRO 5 Commissioning 5 Commissioning 5 1 Switch on the instrument panel e For operation of the boiler Gas 610 ECO PRO A The features and instructions described are for each boiler module The instrument panel HMI GAS 310 610 PRO is for use as soon as the power to the boiler is switched on 1 Open the gas valve on the boiler 2 Turn on the boiler using the on off switch 3 Setthe controls thermostats control system so that they request heat 4 The start up cycle begins and cannot be interrupted During the start up cycle the display shows the following information A short test where all segments of the display are visible FI Software version P Parameter version The version numbers are displayed alternately By pressing the key for a short time the current operating status is shown on the display Heat demand Heat demand stopped S Bumer sop g Boiler is igniting 5 Post circulation of the pump 1 UB 3 Heating System 2 Standby In STAND BY the display normally shows the water pressure next to 0 only when the hydraulic pressure sensor is connected and the symbols and 4 Error during the start up procedure gt No information is shown on the display Check the mains supply voltage Check the main fuses Check the connection
11. flame during operation No ionization current ERU canna ion Check the wiring Gas valve unit defect Gas leakage control fault Replace the gas valve unit Gas leakage control VPS fault Internal error on the SU PCB Pe Replace the SU PCB Replace gas leakage control VPS 6 1 3 Lock out If the blocking conditions still exist after several start up attempts the boiler will switch into locking mode fault The display shows In a red flashing display The symbol A gt The symbol RESET The fault code for example 5 17 Press the RESET key for 2 seconds If the error code continues to display search for the cause in the error table and apply the solution The error code is important for rapid and correct tracking ofthe type of problem and for any technical assistance from Remeha Error Description Probable causes Checking solution code Storage unit PSU T n El The safety parameters gt connection gt Check the wiring 1 are incorrect PSU defective Replace PSU Bad connection Check the wiring Flow temperature sensor Sensor not or badly Check that the sensors are operating correctly short cieuited connected Check that the sensor has been correctly fitted Sensor fault Replace the sensor if necessary Bad connection Check the wiring Flow temperature sensor Sensor not or badly Check that the sensors are operating corre
12. manufacturer s dealer or another suitably skilled person to prevent hazardous situations LR remeha 160514 125482 04 HMI Gas 310 610 ECO PRO 2 Safety instructions and recommendations 2 Safety instructions and recommendations 2 1 Safety instructions 2 2 Recommendations 160514 125482 04 Strictly follow the safety instructions given gt gt RNING This equipment operates using electricity Disconnect the equipment from the power supply before making electrical connections Only qualified professionals are authorised to work on the appliance and the installation Only the manufacturer is authorised to carry out repairs Only qualified professionals are authorised to work on the appliance and the installation e gt A Store this document in the document wallet on the inside of the boiler casing Keep the appliance accessible at all times Never remove or cover labels and rating plates affixed to the appliance 6 3 Technical description HMI Gas 310 610 ECO PRO 3 Technical description 3 1 Control panel For operation of the boiler Gas 610 ECO PRO Each module has its own instrument panel jul o 3 1 1 Functions of the keys Display 4 Escape or reset key Heating temperature key or se key A SERVICE um Bic ul Um n gt lt Enter or cancel 0 Key lock out o a A WO N
13. temperature Eg Return temperature ely Outside temperature Only with an outside temperature sensor ells Exchanger temperature 5 5 Internal set point F L lonization current pA n E Fan speed in rpm D Water pressure bar MPa Only with the hydraulic pressure sensor connected Ala Supplied relative heat output 76 10 Press the key to interrupt the display cycle ET 1 I is displayed with flashing Last error which occured XIX 11 Use the or key to scroll through the faults or shutdowns 12 Press the 4 key to show the fault list or shutdown list 13 Press 2 times on the key 42 to exit the error memory 28 6 Troubleshooting HMI Gas 310 610 ECO PRO 6 2 2 Deletion of the error display 1 Press the two keys Y simultaneously and then key until the lt symbol N flashes on the menu bar WW 2 Select the installers menu using the key 171712121 appears 4x CN v on the display 3 U
14. Great Britain HMI Gas 310 610 ECO PRO Installation User and Service Manual LR remeha Contents 1 o AAA A 4 1 1 Symbols Used irure eoi co iniit 4 1 2 Abbreviations cc ecce nonne 4 ES Liabilities CE 4 1 3 1 Manufacturer s liability 4 1 3 2 Installer s liability 5 1 3 3 Users liability csseee 5 2 Safety instructions and recommendations 6 2 1 Safety instructions 6 2 2 Recommendations eene 6 3 Technical description A 7 3 1 Control panel 7 3 1 1 Functions of the keys 7 3 1 2 Meaning of the symbols on the display 8 4 Installation M S 9 4 1 Control panel assembly 9 5 COMMISSIONINAO 10 5 1 Switch on the instrument panel 10 5 2 Reading out measured values 11 5 2 1 Reading the various current values 11 5 2 2 Readout from the hour counter and percentage of successful starts 12 5 2 3 Status and sub status 12 5 3 Changing the settings
15. ctly open circuit connected Check that the sensor has been correctly fitted Sensor fault Replace the sensor if necessary 160514 125482 04 CR remeha 24 6 Troubleshooting HMI Gas 310 610 ECO PRO Probable causes Checking solution code Temperature of heat exchanger too low Exchanger temperature too high Return temperature sensor short circuited Return temperature sensor open circuit Return temperature too low Return temperature too high Difference between the flow and return temperatures too great Air differential pressure switch has been triggered Temperature of heat exchanger above normal range high limit thermostat STB 25 Bad connection No circulation Sensor not or badly connected Sensor fault Bad connection Sensor not or badly connected Sensor fault Bad connection Sensor not or badly connected Sensor fault Bad connection No circulation Sensor not or badly connected Sensor fault No circulation Sensor not or badly connected Sensor fault Air inlet or flue gas discharge blocked Bad connection No circulation Sensor not or badly connected Sensor fault Viv v wv wv v v wv viv v v v v v viv v v viv v v viv v v v
16. d Close hydraulic valve Start anti hunting On eJ 3 e ep oe cp cp cp ts ee nur eur eer a eur ee Las gt lt E bu cf ieu Paul j Oy o On un oc Lo Ina ico Wait for burner start 8 Control stop Anti hunting Shutdown code X X 9 Blocking X 5 3 Changing the settings The boiler control panel is set for the most common heating systems With these settings practically all heating systems operate correctly The user or installer can optimise the parameters according to own preferences For the settings of the Gas 610 PRO boiler A The parameters and settings described are for each boiler module Each parameter changing must therefore be done identical on each module 5 3 1 Parameter descriptions Boiler type Gas 310 PRO Factory setting Parameter Description Adjustment range Gas 310 ECO PRO mm Flow temperature 20 to 90 C 1 to 98 minutes Post circulation of the pump 95 minutes continuous Boiler rea lati n 0 Heating deactivated 4 9 1 Heating activated 13 LR remeha 160514 125482 04 HMI Gas 310 610 PRO 5 Commissioning Factory setting Parameter Description Adjustment range Gas 310 ECO PRO 285 355 430 500 575 650 0 Simple 1 Comprehensive 2 Automatic switching to simple after 3
17. d follow the instructions given in the manuals provided with the appliance Carry out installation in compliance with the prevailing legislation and standards Perform the initial start up and carry out any checks necessary Explain the installation to the user gt maintenance is necessary warn the user of the obligation to check the appliance and maintain it in good working order Give all the instruction manuals to the user 1 3 3 User s liability To guarantee optimum operation of the appliance the user must respect the following instructions Read and follow the instructions given in the manuals provided with the appliance Call on qualified professionals to carry out installation and initial start up Get your installer to explain your installation to you Have the required checks and services done by a qualified professional Keep the instruction manuals in good condition close to the appliance This appliance is not intended to be used by persons including children whose physcial sensory or mental capacity is impaired or persons with no experience or knowledge unless they have the benefit through the intermediary of a person responsible for their safety of supervision or prior instructions regarding use of the appliance Care should be taken to ensure that children do not play with the appliance Ifthe mains lead is damaged it must be replaced by the original manufacturer the
18. e heat exchanger Check that the sensor has been correctly fitted Check that the sensors are operating correctly Replace the sensor if necessary 160514 125482 04 HMI Gas 310 610 PRO 6 Troubleshooting Probable causes Checking solution code Check cabling of ignition transformer Check the onization ignition electrode No ignition Check breakdown to earth Check the earthing Defective control SU PCB Check that the air inlet and flue gas discharge flues are not blocked Check that the gas valve is fully opened Check the supply pressure Ignition arc but no flame Purge the gas supply to remove air f ti 5 burner start up failures Check the operation and setting the gas valve unit Check the condition of the burner set Check the wiring on the gas valve unit Defective control SU PCB Check that the gas valve is fully opened Check the supply pressure Check the wiring on the ionization ignition electrode Presence of the flame but insufficient ionization 3 Check the earthing Check the ionization ignition electrode Check the operation and setting of the gas valve unit Check the condition of the burner set Gas pressure non existen Check that the gas valve is fully opened or too low Check the supply pressure Wiring fault Check the wiring l Incorrect adjustment of thej p Check whether the VPS gas pressure control 5 failed gas leakage VPS switch system has been correctly
19. fitted controls Pressure switch VPSisnotl Check that the VPS switch has been adjusted or badly fitted correctly Defective VPS pressure Replace the VPS gas pressure control system if switch need be Gas valve defect Check the gas valve and replace if necessary lonization current present even though there is no flame Check the ionization ignition electrode The burner remains very Set the 2 False flame signal hot CO too high Ignition transformer defective Replace the ignition transformer if necessary Check the gas valve and replace if necessary Gas valve defect Problem on the gas gt connection gt Checkthe wiring Check the wiring Bad connection Check for adequate draw on the chimney Fan defective connection Replace the fan if need be Fan fault Water circulation direction reversed Check the circulation direction pump valves Bad connection Check that the sensor has been correctly fitted Flow and return reversed Sensor not or badly Check that the sensors are operating correctly connected Sensor fault Replace the sensor if necessary 160514 125482 04 LR remeha 26 6 Troubleshooting HMI Gas 310 610 ECO PRO Probable causes Checking solution code Purge the gas supply to remove air Check that the gas valve is fully opened Check the supply pressure No or insufficient ionization
20. he menu bar T 2 Select the installers menu using the key 1972 appears v on the display c OIE 3 Use keys or to input the installer code Fmi 2 7 ME 4 Confirm using key 5 1 is displayed with y flashing GG 5 Press the key several times 2 is displayed with Jc P flashing mmm 0 6 Press the key 2 is displayed with y flashing This is Ya TTEN the current value of X for dF Check this against the value of X on P jglFi the type plate bd uU 7 Enter the value of X shown on the type plate using the or igit Xi key E e 8 Confirm the value with the key j Y is displayed with y flashing This is the current value of Y for dU Check this against the value of Y on the type plate 9 Enter the value of Y shown on the type plate using the or key 10 Confirm the value with the key The factory settings are reset 11 The display returns to the current operating mode v lt E T000820 H 5 3 6 Carrying out an auto detect After removing a control PCB an auto detect must be carried out To E do this proceed as follows J 1 Press the
21. meter 28 Check that the gas valve is fully opened Non existent or insufficient circulation Incorrect setting of the Gps gas pressure switch on the SCU PCB Check the supply pressure Check whether the Gps gas pressure control system has been correctly fitted Replace the Gps gas pressure control system if need be Configuration fault or SU Wrong SU PCB for this Configuration fault or default Parameter error on the parameter table incorrect PCU PCB to eps denen Configuration fault or PSU Wrong PCU PCB for this Configuration fault or parameters d Fl a h unknown Configuration procedure gt Active for a short time afte 1 switching on the boiler ld Check whether the SU PCB has been correctly fitted in the connector on PCU PCB Parameter error Communication error with the SU PCB Bad connection These lock outs are not stored in the fault memo as 160514 125482 04 HMI Gas 310 610 PRO 6 Troubleshooting Shutdown Probable causes Checking solution code Purge the gas supply to remove air Check that the gas valve is fully opened Check the supply pressure Check the operation and setting of the gas valve unit Check that the air inlet and flue gas discharge flues are not blocked Check that there is no recirculation of flue No
22. meters at user level can be changed Access to central heating temperature parameter pz Heating programme deactivated Locking the keys The heating function is deactivated Key lock out is activated Manual mode Yellow display with the symbols Boiler is set to manual operation f SERVICE 8 Maintenance message a Service menu Water pressure f Chimney sweeping position Circulation pump Forced full or part load for CO2 measurement The pump operates ER Parameters at installer level can be changed The water pressure is too low Only with the hydraulic pressure sensor connected Dereci Antifreeze protection Boiler indicates a fault This can be seen from the OMA prieta Boiler is running in frost protection mode code and red display Burner level Hour counter menu Readout of the operating hours number of successful Output level starts and hours on mains supply Outside sensor Signal strength symbol i Only if an outside temperature sensor is connected Signal strength of the wireless controller if connected Accessory Battery symbol Status of battery of wireless controller if connected 160514 125482 04 LR remeha 8 4 Installation HMI Gas 310 610 ECO PRO 4 Installation 4 1 Control panel assembly The instrument panel HMI GAS 310 610 ECO PRO is standard fitted in the Gas 310 610 ECO PRO boiler 9 LR remeha 160514 125482 04 HMI Gas 310
23. n automatically when the reason E XIX A for the blocking has been removed T001632 B Shutdown Description Probable causes Checking solution code mE Parametererror gt Parameter error onthe Reset d F and PSU PCB gt Restore parameters with Recom 5 5 Check the circulation direction pump valves Reasons for the heat demand Check the circulation direction pump valves Check the water pressure Maximum heat exchanger Non existent or insufficient y Check the cleanliness of the heat temperature increase has circulation exchanger been exceeded Sensor error Maximum flow temperature Non existent or insufficient exceeded circulation Check that the sensors are operating correctly Check that the sensor has been correctly fitted 1 These lock outs are not stored in the fault memo 160514 125482 04 CR remeha 22 6 Troubleshooting HMI Gas 310 610 ECO PRO Shutdown Probable causes Checking solution code The maximum temperature increase speed tolerated in the exchanger has been exceeded Maximum difference between the flow and return temperature exceeded No release signal Phase and neutral of mains supply mixed up Shutdown input is open Shutdown input active or fros
24. o increase the flow temperture manually Confirm the value with the key The boiler is now set to manual operation Press the key 2 times to return to the current operating mode 160514 125482 04 HMI Gas 310 610 PRO 6 Troubleshooting 6 Troubleshooting 6 1 Shutdowns and lock outs e For operation of the boiler Gas 610 ECO PRO A The features and instructions described are for each boiler module 6 1 1 General The boiler is fitted with an electronic regulation and control unit The heart of the control system is a microprocessor the Comfort Master which controls the boiler and also protects the boiler When a failure is signalled the boiler stops or becomes locked 6 1 2 Blocking A temporary blocking mode is a boiler operating function caused by an unusual situation In this case the display gives a code of blocking code 5 E 1 19 The boiler control will try to re start several times The boiler will start up again after the blocking conditions have been eliminated The shutdown codes can be read out as follows 1 Press the two J keys simultaneously gt v 2 Confirm by pressing key 5 is displayed alternating with e Sle the shutdown code g 18 3 Press the key 5 appears on the display y i 510 o The boiler starts up agai
25. of the mains lead to the connector in the instrument box Check the fuse F2 10 AT Check the fuses on the control panel F122AT gt A fault is indicated on the display by the fault symbol A and a flashing fault code The meaning of the error codes is given in the error table Press for 2 seconds on key reser to restart the boiler 160514 125482 04 LR remeha 10 5 Commissioning HMI Gas 310 610 ECO PRO 5 2 Reading out measured values Ss i Y Y AE 3 v 1910 I 1316 ww ee E d v 4 gla gt Y m 7m E 1 13101010 1 Ple 3 bar Y 7 NS gt WGI 11511 r D Ale n n Ul i 7 Ule Y 11516 n 95 4 0 2x T004355 A e A 5 2 1 For operation of the boiler Gas 610 ECO PRO The features and instructions described are for each boiler module Reading the various current values The following current values can be read off the information menu v v v v v v v v v wv
26. percentage of successful starts 9 3 for example 5 Press the key 2 times to return to the current operating mode 5 2 3 Status and sub status The information menu i gives the following status and sub status numbers Sub status 5 co cy c aa Inu at SA a Cal Pu Pu a ea Rest Anti hunting Open hydraulic valve Start pump Wait for the correct temperatures for burner start Open external gas valve Fan ON Open flue gas damper Pre ventilation Wait for release signal Burner on Gas valve leak proving system VPS Pre ignition Main ignition Flame detection Intermediate ventilation 5 Commissioning HMI Gas 310 610 ECO PRO State Sub status 5 ul Temperature control Limited temperature control AT safety Output control Increase protection level 1 Modulate down Increase protection level 2 Part load J Burner for central heating operation Increase protection level 3 Blockage Modulate up for flame control Temperature stabilisation time Cold start Burner off Post ventilation Fan OFF Close flue gas damper 5 Burner stop Stop fan Close external gas valve Pump post circulation Pump off Boiler stop End of heat deman
27. se keys or to input the installer code 77121 Y E 4 Press the key appears on the display 0181 tle 5 The fault list or shutdown list can be displayed by pressing the w EFC or key 6 Confirm using key 2 is displayed with flashing LO den 7 Press the key several times until 727 171 is displayed on the E 2 E screen E q 107 8 Press the key P is displayed with 77 flashing ES 9 Press key to modify the value to y Yy cla LACE 10 Press the lt key to delete the errors from the error memory v 11 Press 3 times on the key to exit the error memory fu E v mye jl VW P y 29 E 3x T000831 D 29 LR remeha 160514 125482 04 Remeha Commercial UK Part of the THERMEA Remeha House Molly Millars Lane Wokingham Berks RQ41 2QP After Sales Tel 01189743076 Technical Enquires 01189743067 Internet www remeha co uk O Copyright All technical and technological information contained in these technical instructions as well as any drawings and technical descriptions supplied remain our property and shall not be multiplied without our prior consent in writing ane remeha AU A 20482
28. sical injury WARNING Risk of a dangerous situation causing slight physical injury CAUTION Risk of material damage Signals important information gt gt 37 Signals a referral to other instructions or other pages in the instructions PCU Primary Control Unit PCB for managing burner operation PSU Parameter Storage Unit Parameter storage for PCBs PCU and SU SCU Secondary Control Unit Extended control PCB SU Safety Unit Safety PCB Central heating Central heating 1 3 1 Manufacturer s liability Our products are manufactured in compliance with the requirements of the various applicable European Directives They are therefore delivered with marking and all relevant documentation 4 1 Introduction HMI Gas 310 610 ECO PRO In the interest of customers we are continuously endeavouring to make improvements in product quality All the specifications stated in this document are therefore subject to change without notice Our liability as the manufacturer may not be invoked in the following cases Failure to abide by the instructions on using the appliance Faulty or insufficient maintenance of the appliance Failure to abide by the instructions on installing the appliance 1 3 2 Installer s liability The installer is responsible for the installation and inital start up of the appliance The installer must respect the following instructions Read an
29. t protection active Communication error with the SCU PCB The water pressure is too low Gas pressure too low Check the circulation direction pump valves Reasons for the heat demand Non existent or circulation Check the circulation direction pump valves Check the water pressure Non existent or insufficient circulation Sensor error Check the cleanliness of the heat exchanger Check that the sensors are operating correctly Check that the sensor has been correctly fitted External cause Suppress the external cause Parameter error Check the parameters Bad connection Mains supply incorrectly wired Invert phase and neutral Check the wiring Floating or 2 phase Set parameter P 3 4 to network External cause Suppress the external cause Parameter error Check the parameters Bad connection External cause Check the wiring Suppress the external cause Parameter error Check the parameters Bad connection Bad connection with BUS SCU PCB not installed in the boiler The water pressure is too low Check Water pressure in the installation Check the wiring Check the wiring Carry out automatic detection Incorrect adjustment of water pressure parameter 218 Water leakage Setting of hydraulic pressure sensor Setting para
30. the factory settings or when X m replacing the main PCB enter the values and Factory setting dF and dU from the type plate in parameters Y 17 and dl 160514 125482 04 HMI Gas 310 610 ECO PRO i q 1 T v POM 9 tt w AA ee iem jBl5 c w n A BD v 4 Y 11 D Y 2x T001906 B Ly gt Y 1 3x 1 Vv A TEO LE L 3 D odile v Pld ft v aa ee 8 Ole v n 5 D P 7 IR wr 1 PP ie y E 1 2x T000819 E 160514 125482 04 Confirm the value with the key 9 y is displayed with Select the fitter menu using the key Use keys or to input the installer code 7171 2 4 Confirm using key 6 7 is displayed with 5 Press the key a second time The value g Confirm the value with the key 5 1 is displayed with 5 Commissioning 5 3 2 Modification of the user level parameters Parameters P to P 5 can be changed by the user A CAUTION Modification of the factor
31. two keys Y simultaneously and then key until the v symbol f flashes on the menu bar vu 111092 2 Select the installers menu using the key 297 121 appears a on the display A 0 0 40 3 Use keys or to input the installer code pjg i2 4 p r3 4 Confirm using key 5 1 is displayed with y flashing e 5 Press the key several times 21 12121 is displayed with 121 us B flashing w PERS 6 Confirm using key Auto detect is carried out aa 7 The display returns to the current operating mode T000445 B 160514 125482 04 LR remeha 20 5 Commissioning Pu 3 n E 3 2x 21 T005266 B HMI Gas 310 610 ECO PRO 5 3 7 Setting the manual mode In some cases it may be necessary to switch the boiler to manual operation For example if the controller has not yet been connected The boiler can be switched to automatic or manual operation under the symbol To do this proceed as follows 1 Press the two keys Y simultaneously and then key until the symbol y flashes on the menu bar Press the key or The value of the minimum flow temperature or The value the minimum flow temperature and The current water pressure Only with the hydraulic pressure sensor connected Press the key t
32. unning P1318 time HdV 0 to 255 seconds 0 If connected Flue gas damper running PLL time FgV 0 to 255 seconds 0 connected Pale Release waiting time 0 to 255 seconds 0 Gas valve leak proving _ IEE system VPS 0 Not connected 0 Accessory 1 Connected Mains detection phase B qu 1 1 1 Shutdown without frost protection p Shutd input functi 2 Shutdown with frost protection 4 25 MR DLE 3 7 Lock out with frost protection Pump only 0 0 10 V Wilo control PCB From Analogue output 0 1 0 10 V Grundfos control PCB 35 10V 2 PWM pump 0 SCU S05 control PCB 3 Heat output feedback 4 Temperature feedback 0 OpenTherm regulator From Analogue input 1 Analogue temperature based control PJG 0 10V C 1 SOS gon PCB 2 Analogue heat output based control 96 Average flow temperature Do not modify Pale factor a 0 bar 315 Display units 4 F PSI 0 0 Service messages off 21910 Maintenance message 1 Service messages on 0 2 Customized service message 100 Service operating hours Dr 175 Do not modify 100 b h x 30 c ervice burning hours Do not modiy Setting the pump speed PHJ Minimum pump speed for 2 10 x 10 2 central heating operation Setting the pump speed 21419 Maximum pump speed for 6 10 x 10 10 central heating operation PHIS AT Modulate down 10 to 30 C 25 Ald Detection of connected 0 No detection 0 SCUs 1 Detection To restore
33. ure sensor connected 0 Not connected Accessory Minimum gas pressure check _ EE Gps 0 Not connected 1 Connected Accessory Hydraulic valve running time Psa HdV 0 to 255 seconds 0 If connected Flue gas damper running PLL time FgV 0 to 255 seconds 0 connected Pale Release waiting time 0 to 255 seconds 0 160514 125482 04 LR remeha 14 5 Commissioning HMI Gas 310 610 ECO PRO Factory setting Parameter Description Adjustment range Gas 310 ECO PRO 285 355 430 500 575 650 Gas valve leak proving 0 Not connected system VPS 0 Accessory PSY Mains detection phase a a on 1 1 1 Shutdown without frost protection Plas Shutdown input function 2 Shutdown with frost protection 1 3 Lock out with frost protection Pump only 0 0 10 V Wilo control PCB From Analogue output 0 1 0 10 V Grundfos control PCB 35 10V 2 PWM pump 0 SCU S05 control PCB 3 Heat output feedback 4 Temperature feedback 0 OpenTherm regulator PLG eg Hs T Rc 1 Analogue temperature based control 1 2 Analogue heat output based control 96 PI3IB Average flow temperature Do not modify 6 factor 0 bar PL319 Displa
34. ve Boiler regulation Display screen m G20 Gas H Minimum fan speed x100 rpm 19 offset Minimum fan speed x1 rpm Do not modify Start speed x100 rpm 25 Maximum flow temperature 0 to 90 C of system Heat curve set point Maximum outside temperature 5 Only with an outside Mate temperature sensor Accessory Heat curve set point Flow temperature Only with an outside to 90 20 temperature sensor Accessory Heat curve set point Minimum outside temperature 5 Only with an outside temperature sensor Accessory Antifreeze temperature Only with an outside from 30 to 0 temperature sensor Accessory Fault relay function X4 0 Operation signal If connected 1 Alarm signal Fault relay function X5 0 Operation signal 4 If connected 1 Alarm signal Minimum water pressure Wps Only with the hydraulic pressure sensor connected Accessory 0 7 bar MPa x 0 1bar MPa 0 Not connected 160514 125482 04 CR remeha 16 5 Commissioning HMI Gas 310 610 ECO PRO Factory setting Gas 610 ECO PRO 570 710 860 1000 1150 1300 Parameter Description Adjustment range Minimum gas pressure 0 Not connected 3 1 Connected 9 Hydraulic valve r
35. vv vw v v v v v v v v Check the wiring Vent the air in the heating system Check the circulation direction pump valves Check the water pressure Check the cleanliness of the heat exchanger Check that the sensor has been correctly fitted Check that the sensors are operating correctly Replace the sensor if necessary Check the wiring Check that the sensor has been correctly fitted Check that the sensors are operating correctly Replace the sensor if necessary Check the wiring Check that the sensor has been correctly fitted Check that the sensors are operating correctly Replace the sensor if necessary Check the wiring Check the cleanliness of the heat exchanger Vent the air in the heating system Check the circulation direction pump valves Check the water pressure Check that the sensors are operating correctly Check that the sensor has been correctly fitted Vent the air in the heating system Check the water pressure Check that the heating pump is operating correctly Check the circulation direction pump valves Check the cleanliness of the heat exchanger Check that the sensor has been correctly fitted Check that the sensors are operating correctly Replace the sensor if necessary Check that the air inlet and flue gas discharge flues are not blocked Check the wiring Check the water pressure Check that the heating pump is operating correctly Check the circulation direction pump valves Check the cleanliness of th
36. y settings may be detrimental to the functioning of the appliance Press the two keys Y simultaneously and then key until the symbol flashes on the menu bar Select the users menu using the key 5 15 displayed with 1 flashing Press the lt key a second time The value B 2 C appears and flashes for example Change the value by pressing the or key In this example using key to 5 5 C flashing Press the key 2 times to return to the current operating mode The parameters a 2 to p 5 are changed in the same way e A as pl 1 After step 2 use the key to move to the I required parameter 5 3 3 Modification of the installer level parameters Parameters 7 1 to must only be modified by a qualified professional To prevent unwanted settings some parameter settings can only be changed after the special access code 12 10 is entered A CAUTION Modification of the factory settings may be detrimental to the functioning of the appliance Press the two keys Y simultaneously and then key until the symbol f flashes on the menu bar AdE appears on the PA display
37. y units 1 F PSI 0 0 Service messages off Pus Maintenance message 1 Service messages on 0 2 Customized service message 100 Service operating hours Ox 175 Do not modify x 100 Pla S b h 30 g ervice burning hours Be not nodi Setting the pump speed PIG 3 Minimum pump speed for 2 10 x 10 2 central heating operation Setting the pump speed 21914 Maximum pump speed for 6 10 x 10 10 central heating operation PHIS AT Modulate down 10 to 30 C 25 Ald Detection of connected SCUs d Ho 0 1 Detection To restore the factory settings when X 77 replacing the main PCB enter the values dF diF and Idli Factory setting and dU from the type plate in parameters Y and diu 15 CR remeha 160514 125482 04 Gas 310 61 Parameter PRO 5 Commissioning m Boiler type Gas 610 PRO Description Adjustment range Gas 610 ECO PRO 1 to 98 minutes Post circulation of the pump 59 minutes continuous 0 Heating deactivated 1 Heating activated 0 Simple 1 Comprehensive 2 Automatic switching to simple after 3 minutes 3 Automatic switching to simple after 3 minutes Key blocking is acti
Download Pdf Manuals
Related Search
Related Contents
SPRAY WATER DEVICE - T Philips VR447 User's Manual Mode d`emploi - FR Bedienungsanleitung User Guide - Ipvision A/S UltraCure DOT Samsung SP-M200 Projector User Manual User`s Manual balanza de precisión precision balance balance de précision Copyright © All rights reserved.
Failed to retrieve file