1. function testing of the detector In the control panel all types of fires are detected by continuously comparing fire patterns Intelligent evaluation algorithms use the current condi tion of the sensing chamber to predict the likely time of the next maintenance Thus the alarm threshold is automatically adjusted within the permissible range depending on the contamination With that the con stant response sensitivity of the detector is ensured for the duration of its usage The two LEDs with 360 visibility indicate the activated condition of the detector The detector address is se lected with two decadic rotary switches thus allowing to change the detector without additional tools A detector function test can be conveniently conducted using a magnet or test gas The detector is attached to the base B524FTXE R LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH A 1231 WIEN WIEGELESTRASSE 36 TEL 43 1 52114 0 FAX 43 1 52114 27 OFFICE LST AT WWW LST AT ALL RIGHTS RESERVED FTX P1_DBL_LST_EN_0804 PDF PAGE 1 Smoke Sensor Exhaust Specifications Operating voltage Air and Smoke Filters Air Smoke Dust or Water Mist Supply through loop voltage Current consumption sensor max 230uA quiescent Operating voltage fan 15 30VDC Cyclic current consumption fan 6mA in quiescent state 30s 60mA in operation 5s Ambient temperatu
2. Optical Filtrex Detector FTX P1 ADM loop technology with System Sensor 200 protocol areas Replaceable filter For use in heavily contaminated Constant response sensitivity e Function testable with magnet The addressable Optical Filtrex Smoke Detector FTX P1 uses the scattered light principle and was developed for the detection of smoke particles in heavily conta minated areas The detector is used for example in industrial plants where dust Is released by production or cleaning By means of an integrated fan air samples are drawn into the sensing chamber through two separate filters The fan is powered by a separate 24VDC supply and operates in a 15 duty cycle 5 seconds on 30 se conds off thus allowing low power consumption as well as precise evaluation of the air samples The filters are monitored for contamination They are designed to let smoke reach the sensing chamber whereas causes of deceptive alarms dust particles and tiny drops of water are kept away from it The ou ter filter is removeable and can be cleaned or replaced by the operator The modern design of the sensing chamber allows to reliably evaluate the characteristics of fire Building Safety Building Security The proven ADM loop technology with System Sen sor 200 protocol establishes a permanent communi cation between the fire detection control panel and the detector That ensures a periodical
3. re 10 C to 55 C Relative humidity 10 93 no condensation Dimensions x H 102 x 89 mm Colour cream Weight 207g Approval DIFT 0845 CPD 232 1427 Denmark Order number 241019 Order name Optical Filtrex Smoke Detector Anal 500 SS FTX P1 Detector Base Filtrex Dimensions x H 102 x 35 mm Colour cream Weight 91g Order number 246012 Order name Replacement Filter Filtrex Detector Base Filtrex Anal 500 SS B524FTXE Dimensions x H 80 x 19 mm Colour cream Weight 10g Order number 249047 Order name Replacement Filter for Filtrex RF FTX Building Safety Building Security LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH e A 1231 WIEN WIEGELESTRASSE 36 TEL 43 1 52114 0 FAX 43 1 52114 27 OFFICE LST AT WWW LST AT ALL RIGHTS RESERVED FTX P1_DBL_LST_EN_0804 PDF PAGE 2

Download Pdf Manuals

image

Related Search

Related Contents

VC-3020 MANUAL DE INSTRUÇÕES  "取扱説明書"  Samsung CX913P User Manual  Getac F110 Basic    10 - Argon  SDL TRADOS 2007 – WinAlign Manual de Utilização  MANUAL - AquaGlide  istruzioni d'uso instruction manual mode d'emploi  ADVERTIMENT. La consulta d`aquesta tesi queda condicionada a l  

Copyright © All rights reserved.
Failed to retrieve file