LST 130 User's Manual

image

Contents

1. ean aaa aaa 20 Transmitting devices 1a amak akn Haba nn hm E TANG bags oe DINDO NG UNAN an 20 Actuation sero fans Na KG conto ge eet owt NG NAGP TEE oye ales eaves eae ees 21 Information devices for the fire brigade cee cece cee ene een eens 21 Information SYSteMS GANANG KAKA KAG BARS ene one BENG PE En En T kk maa 21 Displaying and operating elements 00 c cece eee cee cence eens 22 Mfo field orre e rere orc rea ec re a Pench a eer ere REGET 23 UnfO DUtCON ss sarin iaeoe e eE cin Gatnbe mths EAE axed wed led At boned genni tlt 24 Menu buttons aakala eins saa NANA Aka Gn Un a ened weet ees 24 Numeric Keys nalan GALA LG Dam GANA AnG EEE T DALA Dn E dene mna 24 Element bUtton 10530 2 s0resestatenareetetask prin hova tee te eee INENG E tees 24 KANAN NAA Gye ede nee 25 Light emitting diodes displays cece cece cece enn AGA a 25 TRANSM DEVICE 1 field ose 0n ais kn NAY pee NG KGAD GANGBANG 25 ALARM DEVICE T field gts Sena md GN na hanna BANA nal 26 Optional LED display field ai AA Aa 27 ACOUSTIC sinal e aiai aeaa o ate Gok la dag TERA bee hahaa DU ANGKAN 27 Protocol printer crees retensie ra en eee AD NG TR ANT MPG PALDA YANG shes 27 Basic operation of the fire detection control panels Series BC216 29 Operating authorization daanan GIG NGALANG Sheds NIKA NING E E DEAN DAA 29 Operations using single buttons AA AA 31 Resetting t
2. Further devices e g remote display and operating units gateways for the connection to foreign net works etc can be embedded in the network of a network fire detection control panel as GSSnet mem ber in addition to BCnet sectional control panels Features of the fire detection control panel Series BC216 Fire detection control panel BC216 1 stand alone The fire detection control panel BC216 1 is designed as compact stand alone control panel to be used in a modern fire detection system of small and medium size as a receiving and controlling unit Due to its modular construction and its flexibility in the setting of parameters it can be very easily adapted to different demands and thus generally can be used in a large variety of circumstances The fire detection control panel BC216 1 sets new standards for user comfort variety of functions and security in the fire alarm technology which benefit the user as well as the installer of the fire detection system An over view of the most important features of the control panel is provided in the following list Depending on the built in technology the detectors of the fire detection system are connected to the control panel either by one or two loops in intelligent ADMPRO or ADM technology with up to 128 detector zones in each loop or by 8 or 16 detector zones in addressable conventional technology or by a combination of the two technologies The decision which technology should be used th
3. Is one of the yellow light emitting diodes Fault or Call fire brigade in the field TRANSM DE VICE 1 illuminated it is not certain that the fire brigade has been notified automatically In this case contact the fire brigade immediately If the red light emitting diode Activated is not illuminated the fire brigade has not been notified The omission may be caused by a defect in this case the fire brigade is to be contacted immedi ately or by the activation of the alarm delay procedure and with it of the delayed activation of the primary transmitting device In case of a two zone dependency it may be caused by the fact that the transmitting device will be activated only after an alarm from another detector zone which is also contained in this two zone dependency E If the delay procedure has been activated the light emitting diode Alarm delay in the field TRANSM DEVICE 1 is illuminated If you press the button Alarm delay Explore in the field TRANSM DE VICE 1 during the time set for reaction e g 30 seconds the light emitting diode Alarm delay will start to flash as an indication that you have started the exploration timer Now you have exactly the set exploration time e g 270 seconds this time is country specifically setable in order to decide if it is necessary to notify the fire brigade If you decide that this is not necessary you can forestall the notifi cation by disabling the alarming detector zone s In ca
4. Nr 2 ACTU DIS 0002 018 Disablement of an actuation zone e g Nr 2 automatically in authoriza 1 ACTU DIS 0002 tion level 2 or 3 Disablement of a transmitting device e g Nr 1 1 TR DEV DIS 01 Disablement of a transmitting device e g Nr 1 automatically in 1 TR DEV DIS 01 authorization level 2 or 3 Disablement of an alarming device e g Nr 1 1 AL DEV DIS 01 Table 5 Messages of the disablement condition HB216AE SAM 0130 AN9161202 ZN5002 73 62 User Manual Series BC216 Part A Chapter 5 e Operating conditions of fire detection control panels Series BC216 63 HB216AE SAM 0130 AN9161202 ZN5002 73 63 5 7 E In case of several current disablements you can tell the order of their occurrence by the number in front of the disablement message Starting with the tenth disablement a is written instead of the number E If all elements of a zone have been disabled individually the whole detector zone is rated as disabled A manually disabled part of the system can be enabled again either by using the menu or by pressing the button during the display of disablements menu point Disablements See from page 33 in Chapter 4 3 1 Menu quick operation System parts which were automatically disabled when entering authorization level 2 or 3 are automatically re enabled when exiting authorization see from page 29 in Chapter 4 1 Operating authorization Consider that an
5. Part A Additional information e g date and time of the test procedure the number of current test procedures hints for operating the menu hints for authorization can be displayed by using the Info button You can scroll through all current test procedures by using the T buttons The following test conditions are displayed on the LC display of the control panel Condition Displaying 1st line Test condition of a detector zone e g Nr 4 for fire alarm 1 TEST COND 0004 Test condition of an element e g Nr 29 of a detector zone e g Nr 4 1 TEST COND 0004 029 for fire alarm Test condition of a detector zone e g Nr 3 for technical messages 1 TECH TEST 0003 Test condition of an element e g Nr 5 of a detector zone e g Nr 3 1 TECH TEST 0003 005 for technical messages Test condition of a detector zone e g Nr 5 for faults 1 FLT TEST 0005 Test condition of an element e g Nr 14 of a detector zone e g Nr 5 1 FLT TEST 0005 014 for faults Alarm of a detector zone e g Nr 4 for fire alarm being put in test 1 TEST AL 0004 condition Alarm of an element e g Nr 29 of a detector zone e g Nr 4 for fire 1 TEST AL 0004 029 alarm being put in test condition Alarm of a detector zone e g Nr 3 for technical messages being putin 1 TECH T AL 0003 test condition Alarm of an element e g Nr 5 of a detector zone e g Nr 3 for tech 1 TECH T AL 000
6. ized company preferably the company that performs the periodic maintenance of your system to carry 10 1 3 Chapter 1 e Introduction User Manual Series BC216 Part A out the reconditioning Together with the fire prevention officer you have to determine the additional protective measures that are to be taken until the system is fully operational again Such measures might include e g special attention by your personnel or fire watches in the area where the fault has occurred Two special faults are to be emphasized e The light emitting diode POWER is not illuminated If nothing else is illuminated on the control panel e g when testing the displays by the function display test it is likely that the mains power as well as the emergency power of the correspond ing BCnet sectional control panel are shut off Therefore the part of the fire detection system which was surveilled by this BCnet sectional control panel is out of function If the fire detec tion control panel only consists of one control panel BC216 1 the whole fire detection system is out of function e The light emitting diode System fault is illuminated or flashing This is a sign that important parts of the control panel BC216 1 or with the fire detection control panel BCnet216 the corresponding BCnet sectional control panel are out of function The display ing of events on the display is affected But the reception of alarms from unaffected parts of the sy
7. BC net216 this function effects the entire control panel irrespective of the BC net sectional control panel on which the button was pressed For further information see from page 31 in Chapter 4 2 1 Resetting the fire detection control panel e Silence buzzer button The internal buzzer is silenced by pressing this button With a fire detection control panel BCnet216 the internal buzzers of all BCnet sectional control panels are silenced irre spective of the BC net sectional control panel on which the operation was made This button has the additional function of activating the display test See page 44 in Chapter 4 7 12 2 Testing the op tic and acoustic displays and the buzzer submenu point Display test Light emitting diodes displays The illumination of one of the light emitting diodes indicates a current event Detailed information is shown on the LC display or if several events occurred simultaneously can be displayed separately Notice that area filters may be parameterized for BCnet sectional control panels of a fire detection control panel BCnet216 which suppress the output of various information on the corresponding BCnet sectional control panel Actuation activated red Is illuminated if one or more actuations transmitting devices or alarming devices are activated See page 55 in Chapter 5 3 Activation condition of actuations Technical message yellow Is illuminated if one or more technical
8. Generally the actuation is activated until the cause of the activation e g the alarm of a specific detec tor Zone is terminated E Is an actuation deactivated all actuation displays remaining in the display memory are renumbered in the order of their activation You can scroll through all activated actuations by using the TL buttons The following activation messages are displayed on the LC display of the control panel Condition Displaying 1st line Activation of an actuation zone e g Nr 4 1 ACTU ACT 0004 Activation of an element e g Nr 21 of an actuation zone e g Nr 4 1 ACTU ACT 0004 021 Activation of a transmitting device e g Nr 2 1 TR DEV ACT 02 Activation of an alarming device e g Nr 6 1 AL DEV ACT 06 Table 3 Messages regarding the activation condition of actuations E The number series for defining the actuations in the example above 0004 is independent from the numbers of the fire detector zones fault detector zones and technical messages Detection zones ac tuations transmitting devices and alarming devices have their own number series Activating an actuation in a two zone dependency To increase the security against deceptive activation the parameters of every actuation e g the actua tion of an extinguishing system can be set so that it is activated only after at least two detector zones are in the condition of alarm at the same time E The fire alar
9. Nr 4 for fire 1 FAULT 0004 029 alarms The transmitting of a fire alarm from the concerning element to the control panel is no longer possible Fault in a detector zone e g Nr 3 for technical messages 1 TECH FLT 0003 60 Chapter 5 e Operating conditions of fire detection control panels Series BC216 User Manual Series BC216 Part A Condition Displaying 1st line Effect Fault in an element e g Nr 5 of a detector zone e g Nr 3 for technical 1 TECH FLT 0003 005 messages The transmitting of an alarm from the concerning element to the control panel is no longer possible Fault in a detector zone e g Nr 5 for fault messages 1 FLT FLT 0005 The transmitting of a fault message from the concerning detectors to the control panel is no longer ensured Fault in an element e g Nr 14 of a detector zone e g Nr 5 for fault 1 FLT FLT 0005 014 messages The transmitting of a fault message from the concerning element to the control panel is no longer possible Fault in an actuation zone e g Nr 2 1 ACTU FLT 0002 The activation of the elements of the concerning actuation zone is impossible Fault in an element e g Nr 18 of an actuation zone e g Nr 2 1 ACTU FLT 0002 018 The activation of the concerning elements of the actuation zone is impossible Fault in a transmitting device e g Nr 1 1 TR DEV FLT 01 The transmitting device e g for transmitting alarms to the fire brigade
10. Special technical messages The technical messages activated by detectors are described in the foregoing section Some messages can also be displayed on the LC display that have been activated directly by other peripheral devices of the fire detection system These messages are always self resetting Besides the displaying on the LC 58 5 5 Chapter 5 e Operating conditions of fire detection control panels Series BC216 User Manual Series BC216 Part A display of the panel the yellow light emitting diode Technical message and the buzzer are activated by these messages also Technical messages of that kind are e The processing of a sabotage message of a key safe Usually this message is reported to a burglar alarm control panel and indicated there as a burglar alarm or sabotage message If no burglar alarm system is installed in the building the sabotage mes sage can be reported to the fire detection control panel and can be shown on the LC display as tech nical message The activation of an extinguishing system The confirmation of the executed activation of the primary transmitting device Fault message condition The cause of the fault message condition can be either the activation of a detector zone for faults e g the surveillance of weight or pressure loss of the extinguishing agent in extinguishing systems or a fault of a function of the fire detection system itself Faults of the fire detection system can concern the
11. by Labor Strauss Sicherungsanlagenbau Ges m b H Wien Fire Detection Control Panel Series BC216 User Manual Part A Description Operating Instructions Subject to change without notice 2 User Manual Series BC216 Part A All rights reserved Under the copyright laws no part of this manual or of the software may be multiplied copied disseminated transferred by photo technical means reproduced translated or reduced to any electronic medium or machine readable form in whole or in part without the prior written con sent of Labor Strauss Sicherungsanlagenbau Ges m b H Vienna The information written in this User Manual has been worked out with the highest care Neither juridical responsibility nor any kind of liability is taken for eventually remaining incorrect information Labor Strauss Sicherungsanlagenbau Ges m b H reserves the right to change information without notice and thereby does not take any liability The pointing out of possible errors in the manual will be gratefully accepted by the authors All brand names and product names used in this manual are trade names sevice marks trademarks or registered trademarks of their respective owners HB216AE SAM 0130 AN9161202 ZN5002 73 2 User Manual Series BC216 Part A 1 1 1 1 2 1 2 1 1 2 2 1 3 1 4 1 5 2 1 2 2 2 3 2 3 1 2 3 2 2 4 2 4 1 2 4 2 2 4 3 2 4 4 2 4 5 2 4 6 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 3 10 3 11 3 12 4 4 1
12. described starting page 55 in Chapter 5 3 Activation condition of actuations The first operations on the control panel in fire alarm condition The most important thing is Keep calm and do not lose control of the situation Always assume that the fire alarm is real and not a deceptive alarm Therefore do not press the button Panel reset under any circumstances before the investigation into the cause of the alarm is finished HB216AE SAM 0130 AN9161202 ZN5002 73 52 User Manual Series BC216 Part A Chapter 5 e Operating conditions of fire detection control panels Series BC216 53 E The information on the transmission to the fire brigade and the sirens given in this chapter are only valid for the common case that the panel was configured during commissioning so that an alarm notifi cation of the fire brigade takes place by the primary transmitting device and the local sirens act as pri mary alarming device The operating and displaying devices of the fields TRANSM DEVICE 1 and ALARM DEVICE 1 are only effective in the way described then Otherwise you have to operate the transmitting device and the alarming device by the use of the menu The installer of the system informs you on the corresponding details of the configuration Reset the internal buzzer press the button Silence buzzer Check if the fire brigade has been notified The light emitting diodes in the field TRANSM DE VICE 1 indicate this as follows
13. dure and timer activation Operations using the menu The displaying and operating menus are similar in structure to the menus of modern programs for PCs By using the amp buttons you scroll ring shaped in the main menu You can display only one point of the menu at a time While scrolling in the main menu the titles of the display menu points Alarms Activated actua tions Technical messages Faults Disablements and Test conditions are displayed briefly on the LC display If you stop at a point of the main menu and use the TL buttons you are scrolling ring shaped in the submenu belonging to the priorly shown main menu point If you are confirming a submenu point by using the I button this point is executed or you are entering another submenu If further entries are necessary for the chosen submenu point you can browse these by using the Mg buttons or you can directly enter numbers and confirm your entry by using the button E The most common operations can be made without strictly observing the structure of the menu See from page 33 in Chapter 4 3 1 Menu quick operation Some points of the menu demand the additional selection of a number e g you have to enter the de sired detector zone number in the main menu point Zone After confirming the menu the lowest possible number e g the detector zone with the lowest zone number is automatically suggested This number can either be accepted over
14. lt zone textl1 gt lt element text gt 3 ALARM 0016 020 press V button 3 ALARM 0016 020 lt zone textl1 gt lt element text gt 3 ALARM 0016 020 press V button 1 ALARM 0003 029 you have arrived at the first display again lt zone text1 gt lt element text gt 3 ALARM 0016 020 Figure 17 Display sequence of a fire alarm condition of the control panel with three current fire alarms By us ing the N buttons the first three lines of the LC display show the alarm information By using the Info button additional information for the corresponding alarm is displayed E The fourth line is reserved for the alarm received last Every newly received alarm overwrites the fourth line A fire alarm is saved on the control panel even if the cause of the alarm is no longer current The reset ting of an alarm is described starting page 54 in Chapter 5 2 4 Terminating the fire alarm condition E Displaying the activation of the further transmitting devices is described starting page 42 in Chapter 4 7 9 Displaying and operating transmitting devices menu point Transmit device Displaying the activation of the further alarming devices is described starting page 43 in Chapter 4 7 10 Display ing and operating alarming devices menu point Alarming device Furthermore you can view all activated transmitting devices and all activated alarming devices in the menu point Activated actua tions
15. 1 You operate the fire detection control panel Series BC216 with the clear and sturdy keypad on the front of the case An illuminated LC display and light emitting diodes LED are integrated in the keypad as optical display elements For acoustic alarming a loud buzzer is fitted in the case of the control panel E Event messages of the whole control panel are standardizedly displayed on the displaying elements of all operable BCnet sectional control panels with the network fire detection control panel BCnet216 The operating menus are exclusively displayed on the BCnet sectional control panel where the opera tion is made Info field The Info field of the fire detection control panel BC216 1 and every operable BCnet sectional control panel of the fire detection control panel BCnet216 contains 4 display elements e Exact information is provided by the LC display measuring four lines by 20 characters All mes sages about events and menu points for operation and setting of parameters are displayed here by using text The messages that are displayed separately on the control panel by using light emitting diodes are shown in detail on the LC display as well The display lights up if an event has occurred In the normal condition that means there is no event and no operating action at the control panel the illumination is turned off 30 seconds after a button was pressed last 30 seconds after the last operating action the display returns to s
16. 32 53 Alarm verification 11 Alarming device 15 20 26 Display 43 Number 20 Operate 43 Primary 11 26 31 Reactivate 31 Silence 31 54 Two zone dependency 43 Ambient condition 9 Approvals 10 Area filter 23 27 43 44 50 Authorization Change code 47 Enter code 36 Exit 34 47 Light emitting diode 25 36 Wrong input 36 37 Authorization level 29 30 Enter 36 Exit 30 36 AUTO setup 11 18 BCnet sectional control panel 11 Buzzer 25 27 Reminder 27 Silence 27 31 Clock 18 Clock time correction 45 Clock time setting 45 Date setting 45 Summer wintertime 45 Timer 18 Competent installer 11 Componentry Display 46 Deceptive alarm 11 Dependency Two detectors 12 55 Two zones 14 Detection area 12 Detector Fault detector 20 Fire detector 19 Technical detector 20 Detector line 12 Detector zone 12 20 Alarm criteria 39 Display 39 Number 20 Operate 39 Detector zone alarm Reset 54 Detector zone elements Operate 40 Disablement Display 38 Light emitting diode 25 Disablement condition 61 Display test 31 44 Element button 24 Energy fault 25 Event counter 44 Event memory 18 43 68 Filter 18 44 Exploration time 12 26 32 51 False alarm 12 Fault What to do 9 Fault detector 12 Fault message Display 38 Fault message condition 58 Features 17 Fire ala
17. 4 2 4 2 1 4 2 2 4 2 3 4 2 4 4 3 4 3 1 4 3 2 4 4 4 5 4 6 4 7 HB216AE SAM 0130 AN9161202 ZN5002 73 3 Contents Introductions ii KNANG NGA Bs Sls GNG NPA LP DN GG NG nb aE NGAY dad weer 7 Symbols and type fonts 20 0 cece ccc eee ener eee eben GA GN tence ence tence es 8 Important hints for the user and the installer aaa 8 What to do in case of a fire alarm ma aaa 9 What todon case ofa Tault ag Nak NAL KEN agbeletion heeds eeel 9 Standards CE labeling approvals cee cece cece cece nee een ence eee aaa 10 Warranty asciuctirh ec kana leds E EAE ONE OEE des amie cbs bend ve T EMAA i 11 Special terms nka naa NS Pod In dena e gies odd kan Ly lang eel pnt KATE NN ag 11 Fire detection control panel Series BC216 06 0 ccc ccc cee cece teens 15 Typical construction of a fire detection system with control panel BC216 1 15 Typical construction of a fire detection system with network control panel BCnet216 ana a e a E AA EEK 16 Features of the fire detection control panel Series BC216 eee eee eee 17 Fire detection control panel BC216 1 stand alone aaa 17 Fire detection control panel BCnet216 network control panel 19 Peripheral devices for the fire detection control panel Series BC216 19 Detectors blerrie aret NAGA KANAN Ly Maa N NG Ma DN HUAN AUNG ANG NG GA AG 19 Acoustic and optic alarming devices
18. AN9161202 ZN5002 73 69 Chapter 7 e Event memory entries User Manual Series BC216 Part A Event Event text Text 2nd line Text 3rd line Additional text info button Test activation termination AL DEV TEST T 01 alarming device text 1 alarming device text 2 Control panel events Activation term exing sys EXTING ACT T Activation exing system EXTING ACT Automatic exit user level AUTHORIZATION EXIT timeout user level Control panel initialization INITIALIZE Count n Control panel reset on the CONTROL PANEL RESET fire brigade control unit fire brigade control unit Control panel reset on the CONTROL PANEL RESET keypad control panel FAULT EMERGENCY Emerg oper control panel Enter installer level AUTHORIZATION ON installer level Enter user level AUTHORIZATION ON user level Exit installer level AUTHORIZATION EXIT installer level Exit user level AUTHORIZATION EXIT user level Fault ABB216 FAULT ABB216 fault cause Fault earthing ENERGY FAULT short to earth Fault external consumer FAULT fuse 4 blown Fault external consumer FAULT fuse 5 blown Fault extinguishing system EXTING FLT Fault function module 2 FAULT FM2 fault cause Fault function module 1 FAULT FM1 fault cause Fault FWI2 FAULT FWI fault cause Fault FWZ2 FAULT FWZ fault cause Fault INFO bus SER IF FLT 0 01 Fault LAB48 FAULT LAB fa
19. BC216 and the connection of the peripheral components of a fire detection sys tem to the fire detection control panel are described in this chapter Typical construction of a fire detection system with control panel BC216 1 Fire brigade Siren Flashlight control unit Key safe Fire brigade E i 8 0g baa KG Wa ae ie ee 7 bei Conventional detectors Fo oR ai So o MJ Max 2 Loops in Max 16 detector lines in HY a concentional technology ARM technology Mj pa M Ck CT 7 7 7 7 7 Z7 LO NG foj Special detectors Door actuation Ventilation Smoke escape Remote Map system maintenance Figure 2 View ofa typical fire detection system constructed with the fire detection control panel BC216 1 The system consists of the fire detection control panel BC216 1 including the power supply the automatic and non automatic fire detectors that are combined into detector zones the acoustic and or optic alarming devices the transmitting device linked to a designated alarm respondent fire control systems information devices and information systems The fire detection control panel is the compact processing unit of a fire detection system all informa tion from the system is received here Automatic fire detectors that react to signs of fire such as smoke radiation heat etc as well as manual call points are combined in detector zones an
20. Series BC216 leaves authorization level 2 automatically E If you press the button T in the menu point Authorization code the display shows an information for 5 seconds This information enables the manufacturer to reset a lost installer code for further in formation see Part C of the User Manual If you have pressed the button erroneously do not pay atten tion to the information it will vanish automatically Entering and exiting authorization level 3 To enter authorization level 3 this level is reserved for the installer from authorization level 1 you have to enter the 5 digit installer code in the same way as described starting page 36 in Chapter 4 5 Entering and exiting authorization level 2 by using either the menu or the menu quick operation If the entry was correct the LC display shows Installer level and the green light emitting diode Authorization flashes on the panel E By entering authorization level 3 and depending on the parameters set by the authorized installer transmitting devices or actuations can be put out of operation automatically Earlier activated devices are not put out of operation By returning to authorization level 1 the parts are put back into operation again HB216AE SAM 0130 AN9161202 ZN5002 73 36 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 37 HB216AE SAM 0130 AN9161202 ZN5002 73 37 4 7 4 7 1 The numb
21. These actions are described in Part B of this User Manual The selection of a detector zone is similar to the description in the foregoing section but you have to use the button Element LC display shows instead of the button to confirm the zone number Now the first available element number will be suggested and displayed to the right of the zone number and the The third line of the LC display shows the element text You select the desired element similar to the selection of the detector zone and confirm it by using the button For the installer The button Element is represented by the divide button of the numeric keypad on the PC keyboard The third line of the LC display shows the current condition of the chosen element in capital letters You can either scroll to the desired condition by using the TL buttons or by menu quick operation us ing numeric buttons O disable 1 enable 2 activate for test purposes 3 test condition on 4 measured value maintenance The warning hints starting page 39 in Chapter 4 7 7 1 Operating whole detector zones are valid analogously for the operation of single elements as well dependency Does the dependency consist only of two detectors the second detector is ineffective as N A detector that is disabled and is programmed in a dependency of two detectors is removed from this well because it can only activate a pre alarm E If you have disabled a
22. alarm condition since only pre alarm can be activated 5 3 Activation condition of actuations If one or more actuations have been activated the fire control panel is in activation condition of actua tions Actuations are predominantly used for automatic activation of fire control systems e g for clos ing fire doors switching off air condition or ventilation systems opening smoke escapes activating extinguishing systems etc Actuations can be activated by one detector zone or by a two zone de pendency or if the detector technology used allows it by a single detector or by an interdependence of two detectors E The activation of transmitting devices or alarming devices generally is displayed as an actuation too by the LED display Actuation activated Which events e g fire alarm of a detector zone alarms of determined detectors of a detector zone disablements faults etc are to activate automatically which actuations is determined during the plan ning of the fire detection system Access this information in the engineering data of your fire detection system E The fire control panel transmits only an activation signal to the connected fire protection devices It does not activate the fire protection devices itself The activation condition of actuations is displayed on the control panel as follows e The red light emitting diode Actuation activated is illuminated e The menu jumps automatically to the menu point
23. alarm or fault message can be caused and that actuations transmitting devices etc can be activated by enabling a part of the system that is not in normal condition E At the enablement of a detector zone or of elements of these zones the control panel checks for 5 sec onds if a criteria for an alarm currently exists in this zone In such a case e g a non automatic fire de tector has not been reset the enablement is refused and the LC display shows Cannot be enabled or Cannot be enabled completely E Is a disabled part enabled again all displays of disablements remaining in the display memory are re numbered in the order of their occurrence Test condition The fire detection control panel is in test condition if one or more detector zones actuations or alarm ing devices are put in test condition The test condition makes it possible to test the function of fire de tectors technical detectors and fault detectors during maintenance without causing a condition of fire alarm technical messages or fault messages on the control panel Only the LC display shows the test alarm and an entry is made in the event memory The test alarm is reset automatically after 5 sec onds one man maintenance Furthermore alarming devices and actuations can be tested on their function without having to activate a fire alarm the actuations in case of fire Therefore put detector zones in test condition only for test purposes and terminate t
24. all BCnet sectional control panels can be operated via the main operating unit Maintainer The company or its representative who carries out maintenance reconditioning and repairs Simi lar requirements apply to the maintainer and to the competent installer but the maintainer addition ally has to be trained periodically at least once a year by the manufacturer of the fire detection system and the fire detection control panel in maintenance and reconditioning Maintenance The totality of preventive measures to maintain the functions of a fire detection system Network control panel The control panel consists of single BCnet sectional control panels which are arranged locally spread in the surveillance area of the fire alarm system and connected via a redundant network These BCnet sectional control panels together form a virtual overall control panel At least one of these BCnet sectional control panels is defined as main operating unit via which the network administration is executed The main operating unit is equipped with a display and operat ing unit all further BCnet sectional control panels may also be equipped with a display and operat ing unit but also can work without display and operating unit Organization in case of an alarm The total of all planned measures that are in place to warn rescue prevent the fire from spreading fight the fire and for orientation Pre alarm The information that the first detector in an inte
25. an interdependence of two detectors consisting of just two detectors one is disabled the second detector is ineffective as well because it can only activate a pre alarm ment or a fault of the corresponding detector zone or by entering authorization level 2 or 3 You find N The parameters of an actuation can be set so that the actuation is also activated in case of a disable information on the kind of actuation used in the engineering data of your fire detection system The disablement condition is displayed on the control panel as follows e The yellow light emitting diode Disablement is illuminated 62 Chapter 5 e Operating conditions of fire detection control panels Series BC216 User Manual Series BC216 Part A Atdisablement of the primary transmitting device or the primary alarming device the correspond ing yellow disablement LED displays are illuminated e The menu jumps automatically to the menu point Disablements 30 seconds after any button was pressed last if no event of higher priority is currently on the control panel The first line of the LC display shows the first disablement The second and third line display addi tional text e g a zone or an element specific text for the disablement displayed in the first line The fourth line is reserved for displaying fire alarms The disablements are numbered in order of their execution 1 DISABLEM 0001 029 lt zone textl1 gt lt element text gt Figure 2
26. are only avail able if the appropriate optional componentries are installed Which of the possible functions of the con trol panel of your fire detection system are admissible and efficient is decided by the authorized installer Relevant information can be found in the description of your fire detection system It is no de ficiency if your fire detection system does not use all features described in this User Manual This User Manual describes the variety of functions of the fire detection control panels of the Series BC216 that are valid for the operating software PL149 V4 1106 How to access the version number of the software is described from page 46 in Chapter 4 7 12 9 Displaying the installed componentries submenu point Componentries Control panels using software with a different version number can differ in certain functions from the software described in this Manual Symbols and type fonts Especially important parts of this Manual are marked by the following symbols Means DANGER Paying no attention to these hints can lead to danger to health and life property Means TIP Here the text contains hints for easier operation of the control panel N Means ATTENTION Ignoring these hints can lead to malfunctions of the system and to damage of Means that the country and or the site specific demands of the approvals have to be observed ay A di Menupoints and displays of the LC display are put in brackets in this text In c
27. be found in the engineering data of your fire detection system The alarming of a detector zone for test purposes leads to a real alarm technical message or fault alarm and to the activation of all actuations whose parameters have been set for this detector zone Note that this can lead to an unintended activation of an extinguishing system and thus to danger to life and to costly damage of property Contact the responsible person e g fire prevention officer safety officer prior to activating a test alarm so that he can make the required mechanical or electrical switch offs of extinguishing systems or similar devices before the activation of the alarm During a test alarm transmitting devices or alarming devices are not activated BB B E During maintenance of the system detector zones are set to test condition so that its detectors can be tested on their function without activating a fire alarm See from page 65 in Chapter 6 1 2 Testing of detectors By disabling and then enabling the detector zone you leave the state of test condition of this detector zone Operating single elements of detector zones Provided that the technology used in your control panel allows it you can operate individual elements of a detector zone Elements can be enabled and disabled and can be activated for test purposes The maintainer also can get a read out of the actual measured value and a maintenance prediction if intelli gent detectors are used
28. brigade in case of an alarm You can write the user code for example on a tag on the building key in the key safe or in the fire brigade control unit or else into the system engineering data fire prevention plan etc You have to coordi nate these actions with the safety personnel Note that the user code is not to be made public or else you have to expect improper use of the fire de l tection control panel Authorization level 3 Further important operation proceedings for the maintenance technician and the overall parameter settings for the site specific data are accessible in addition to all operations of authorization level 2 Authorization level 3 is reserved for the authorized installer of the fire detection system You enter authorization level 3 by entering a 5 digit numeric code installer code on the keypad of the con trol panel or the corresponding operable BCnet sectional control panel in authorization level 1 NI With the network fire detection control panel BCnet216 the setting of the parameters of the network specific data is possible exclusively via PARSOFT see User Manual Part C The processing of messages in the fire detection control panel on basis of the old parameters is still effective during the setting of new parameters The same parts of the system that can be put out of operation in authorization level 2 can be put out of operation in authorization level 3 depending on local regulations and restricti
29. by selecting events according to criteria that are needed frequently The contents of the memory are like all other parameters of the control panel preserved indefinitely in case of a total power failure for unlimited time The built in clock supplies the time information for the display of events as well as for the events saved in the memory The switch between summer and wintertime is automatic The user can define the date for the next two time switches in advance The timer with weekly program enables the timed switching of day operation of the control panel for alarm delay operation of the transmitting device for fire alarm messages The connections for a tool for setting parameters or for an external serial printer are provided by two serial interfaces Since the interface for the printer has open parameters the printer may be used as a protocol printer maintenance printer to print measured values of detectors or as a setup printer With the AUTO setup feature the fire detection control panel recognizes all connected components of the system and sets their setup to standard setup when it is put into operation Under normal circumstances elaborate measures for compensating power spikes and high frequency fields enable the control panel to operate in an unshielded network Remote maintenance is possible with an optional interface converter that connects the fire detection system to the Security System Manager SAM of LST Automatic
30. e g disable the alarming detector zone A disabled transmitting device cannot transmit an alarm Is a disabled transmitting device enabled while criteria for activation exist it will be activated immediately HB216AE SAM 0130 AN9161202 ZN5002 73 42 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 43 HB216AE SAM 0130 AN9161202 ZN5002 73 43 4 7 10 4 7 11 E If the parameters of the transmitting device have been set to take the device out of operation automati cally in authorization level 2 or 3 see from page 36 in Chapter 4 5 Entering and exiting authoriza tion level 2 and page 36 in Chapter 4 6 Entering and exiting authorization level 3 the LC display shows the condition the transmitting device will have after returning to authorization level 1 Displaying and operating alarming devices menu point Alarming device You can disable and enable an alarming device and activate it in this menu point Consider the hints given starting page 33 in Chapter 4 3 Operations using the menu Minimum requirement for this menu point is authorization level 2 E Have the parameters of an alarming device been set for a two zone dependency to increase the security against deceptive activation the activation of the alarming device will take place only after at least two detector zones of this two zone dependency are in condition of alarm After confirming the m
31. fire detectors are in steady contact with the air of the surveilled area Due to the dirt in the air e g dust every detector will get dirty as time passes Dirty detectors are one of the main reasons HB216AE SAM 0130 AN9161202 ZN5002 73 18 User Manual Series BC216 Part A Chapter 2 e Fire detection control panel Series BC216 19 HB216AE SAM 0130 AN9161202 ZN5002 73 19 2 3 2 2 4 24 1 for false fire alarms The fire detection control panel BC216 1 besides automatic adjusting of the sen sitivity of the detectors is capable of displaying a dirt message on the control panel before the detec tors activate false alarms due to dirt by using ADM ADMPRO as well as addressable conventional technology The control panel is capable of making a forecast for each detector about the time of the next cleaning by analyzing the measured values provided by the automatic detectors of ADMPRO and ADM technology Fire detection control panel BCnet216 network control panel The network fire detection control panel BCnet216 consisting of BC net sectional control panels BC216 2 and BC216 3 is designed to be used in a modern fire detection system of medium to very large size as a receiving and controlling unit Due to its compact modular construction of the single BC net sectional control panels and its flexibility in the setting of parameters it can be very easily adapted to different demands and thus generally can be used in a larg
32. in the control panel Meas value print out Measured value print out for zones prints a list of all ADM and ADMPRO detectors and their measured values as well as the maintenance prognosis after entering a domain which is determined by the upper and lower zone element limits an interval for a possible periodical output and the desired printer filter Besides the current measured value the month s average values of the last 6 months the current alarm threshold and the expected value in one year are printed out The input O for the interval means a single print out If an interval is defined area 00 00 10 48 59 59 the print out is repeated periodically Print all Maint lt 12 months and minimum value can be selected as printer filters When selecting Maint lt 12 months all detectors which should be replaced within the next 12 months are printed on basis of the maintenance prognosis When selecting minimum value input of a threshold value is required all detectors whose values are equal to or higher than the threshold will be printed e Meas print out act Meas print out al d Measured value print out for actuations and alarm ing devices on loops actuation modules prints a list of all ADM and ADMPRO actuation modules of the selected area and their measured values after entering a domain determined by the upper and lower actuation element limits and an interval for a possible periodical print out Th
33. line Additional text info button Fire detector zones elements Activation ALARM 0001 001 7one text 1 zo text 2 element text Activation termination ALARM T 0001 001 7one text 1 zo text 2 element text Disablement DISABLEM 0001 001 7one text 1 zo text 2 element text Enablement ENABLEMENT 0001 001 zone text 1 zo text 2 element text Fault FAULT 0001 001 zone text 1 zo text 2 element text fault cause Fault termination FAULT T 0001 001 zone text 1 zo text 2 element text fault cause Pre alarm PRE AL 0001 001 zone text 1 zo text 2 element text Pre alarm termination PRE AL T 0001 001 7one text 1 zo text 2 element text Test activation TEST AL 0001 001 7one text 1 zo text 2 element text Test activation termination TEST AL T 0001 001 zone text 1 zo text 2 element text Test condition off TEST COND T 0001 001 zone text 1 zo text 2 element text Test condition on TEST COND 0001 001 zone text 1 zo text 2 element text Technical detector zones elements Activation TECH MSG 0001 001 zone text 1 zo text 2 element text Activation termination TECH MSG T 0001 001 zone text 1 zo text 2 element text Disablement TECH DIS 0001 001 zone text 1 zo text 2 element text Enablement TECH ENA 0001 001 zone text 1 zo text 2 element text Fault TECH FLT 0001 001 zone text 1 zo text 2 element text fault cause Fault termination TECH FLT T 0001 001 zone text 1 zo text 2 element text fault cause Test activati
34. person e g fire prevention officer safety officer prior to making a test alarm so that he can make the required mechanical or electrical switch offs of ex tinguishing systems or similar devices before the start of the activation Testing the transmitting devices For safety reasons no operating function is provided on the control panel for activating a transmitting device for test purposes The testing of a transmitting device can take place only by intentionally acti vating a detector e g a manual call point spondent e g the fire brigade Alerting the safety personnel for no good reason has to be avoided at all costs The activation of a transmitting device by activating a detector is a real alarm message and leads to the activation of all actuations and alarming devices whose parameters have been set accordingly N The activation of a transmitting device absolutely has to be coordinated with the designated alarm re Other tests Besides testing the functions of the devices regular checks have to be made to make sure that the sys tem fulfills its intended purpose Observe all official regulations for the operation of the fire detection system The following list serves as example of checks of the most important criteria for a typical fire detection system Make sure that no changes in the use of rooms have been made that would demand a change in the fire detectors Make sure that no architectural changes have been
35. regu lations and the setting of the parameters by the authorized installer which are also dependent on the regional restrictions and regulations Devices activated earlier are not put out of operation By return ing to authorization level 1 the parts are put into operation again W Do not stay in authorization level 2 longer than needed for operation Return to authorization level 1 immediately after completing the task so that the disabled parts can be put into opera tion again If you have entered the wrong code Wrong entry will be displayed on the LC display the buzzer will send a short signal and you will have to repeat the input You can clear the entry by using the esc button and then can begin to enter the code again The number of wrong inputs is not limited If a first fire alarm occurs while entering the user code the code entry is rejected and the fire alarm is displayed You have to begin your entry again subsequently To return from authorization level 2 to authorization level 1 you have to scroll to the main menu point Exit authorization either by using the menu or by using the menu quick operation see page 33 in Chapter 4 3 1 Menu quick operation and confirm the menu point by using the I button The LC display shows the hint User level exited and the green light emitting diode Authorization on the panel is switched off E 15 minutes after any button was pressed last the fire detection control panel
36. text 1 transmit device text 2 Delay disabled DELAY DISABLE 01 transmitting device text 1 transmit device text 2 Delay enabled DELAY ENABLE 01 transmitting device text 1 transmit device text 2 Disablement TR DEV DIS 01 transmitting device text 1 transmit device text 2 Enablement TR DEV ENA 01 transmitting device text 1 transmit device text 2 Fault TR DEV FLT 01 transmitting device text 1 transmit device text2 fault cause Fault termination TR DEV FLT T 01 transmitting device text 1 transmit device text 2 fault cause Test activation TR DEV TEST 01 transmitting device text 1 transmit device text 2 Test activation termination TR DEV TEST T 01 transmitting device text 1 transmit device text 2 Alarming devices Activation AL DEV ACT 01 alarming device text 1 alarming device text 2 Activation termination AL DEV ACT T 01 alarming device text 1 alarming device text 2 Disablement AL DEV DIS 01 alarming device text 1 alarming device text 2 Enablement AL DEV ENA 01 alarming device text 1 alarming device text 2 Fault AL DEV FLT 01 alarming device text 1 alarming device text2 fault cause Fault termination AL DEV FLT T 01 alarming device text 1 alarming device text 2 fault cause Test activation AL DEV TEST 01 alarming device text 1 alarming device text 2 HB216AE SAM 0130
37. the basic control panel or just the events of the detector zones are printed depending on the setting of the parameters of the corresponding printer interface by the author ized installer After every 50 printed lines a hint is printed showing the actual filter E The parameterized area filter of the BCnet sectional control panel is effective also besides the actual printer filter with BCnet sectional control panels of a fire detection control panel BCnet216 The print out lines are numbered continuously each event is printed with date and time of occurrence respectively of termination as well as with the texts that are used for displaying in the LC display An event can activate a series of secondary events that are printed on the printer as well For example in case of an alarm from a detector zone transmitting devices actuations and alarming devices are acti vated successively as well E At the termination of an event the text of the event is printed with an appended T as an indication for termination 321 21 12 2002 08 32 ALAR 0002 014 1 Floor Store room 3 322 21 12 2002 08 32 ACTU ACT 0012 Loft Fire dampers 323 21 12 2002 08 32 AL DEV AC 01 Sirens Main building 324 21 12 2002 08 33 DELAY ACT 01 Trans dev fire Fire brigade 325 21 12 2002 08 36 AUTHORIZATION O User level 326 21 12 2002 08 36 DISABLEM 0002 1 Floor Storage area 327 21 12 2002 08 36 ALARM T 0002 1 Floor Storage area 328 21 1
38. the choice by us ing the button I The third line of the LC display shows the current condition of the chosen actuation in capital letters You can either scroll to the desired condition by using the TJ buttons or the menu quick operation using numeric buttons O disable 1 enable 2 activate E If the authorized installer has set the parameters of the actuation so that it is put out of operation auto matically in authorization level 2 or 3 see from page 36 in Chapter 4 5 Entering and exiting authori zation level 2 and page 36 in Chapter 4 6 Entering and exiting authorization level 3 the LC display shows the condition which the actuation will have after returning to authorization level 1 Whether or not you can disable an activated actuation is set by the installer while the system is put into operation A disabled actuation or a disabled element of an actuation cannot carry out its purposes in case of an alarm 42 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A The activation of an actuation for test purposes acts like a real activation Consider that this may lead to an unintended activation of an extinguishing system and thus to danger to life and to costly damage of property Contact the responsible person e g fire prevention officer safety officer prior to activating a test alarm so that he can make the required mechanical or elec
39. usable life of the stand by batteries used in the control panel or in the BCnet sectional control panels Promptly replace expired batteries during the peri odic maintenance of the system Make sure that the discarded stand by batteries are disposed of legally The stand by batteries used in fire detection systems are built on the basis of lead and sulphuric acid Such batteries never are to be disposed of in domestic waste Testing of detectors Proper testing devices are available optionally for testing the functions of automatic fire detectors The function testing is carried out as follows e Put the detector zone whose detectors you want to test in test condition See from page 63 in Chap ter 5 7 Test condition automatically activate the fire control systems including if existing extinguishing systems danger to N If you carry out a detector test without putting the corresponding detector zone into test condition you life and the alarming devices and unintentionally call the safety personnel e g the fire brigade e Activate the detectors that are in test condition one after the other by using the appropriate testing device You recognize the correct function by the light display on the detector The alarm condition of the detector is reset automatically after a few seconds you do not have to reset the alarm on the control panel one man maintenance Make sure that you are activating only detectors that are in test
40. will not be activated in case of alarm Fault in an alarming device e g Nr 1 1 AL DEV FLT 01 The alarming device e g a siren will not be activated in case of alarm Fault in a serial interface e g Nr 1 1 SER IF FLT 1 The connected device e g a printer does not work properly Fault in an Info bus interface number 0 e g device Nr 2 1 SER IF FLT 0 02 The connected device e g a fire brigade control punit does not work properly Fault in a loop e g function module Nr 1 loop position Nr 12 1 LOOP FLT 0001 012 The cabling system has a fault in the specified position An effect on the function is to be expected with a further fault only Fault in an extinguishing system activation of a FWI input especially 1 EXTING FLT parameterized for this The extinguishing system will not be activated in case of alarm Fault in the power supply mains battery earthing 1 ENERGY FAULT See following explanations Fault in an external consumer e g fuse blown with complementary info 1 FAULT displayed in the second line Thereon connected devices are not supplied with power General fault the cause is displayed in the second line 1 FAULT See following explanations D The alarm message from a detector zone whose parameters have been set for fault messages i e the activation of a fault detector in this zone as well as a fault in the detector zone itself e g a broken wire
41. 1 Display in the condition of disablement Element Nr 29 of the detector zone Nr 1 is displayed as the first executed disablement The second and third line display information on this disablement Has no element text been programmed the second zone text if available is displayed The fourth line is reserved for fire alarm messages Additional information e g date and time of the disablement the number of current disablements hints for operating the menu hints for authorization can be displayed by using the Tnfo button You can scroll through all current disablements by using the TL buttons The following disablements are displayed on the LC display of the control panel Condition Displaying 1st line Disablement of a detector zone e g Nr 4 for fire alarms 1 DISABLEM 0004 Disablement of an element e g Nr 29 of a detector zone e g Nr 4 1 DISABLEM 0004 029 for fire alarms Disablement of a detector zone e g Nr 3 for technical messages 1 TECH DIS 0003 Disablement of an element e g Nr 5 of a detector zone e g Nr 3 for 1 TECH DIS 0003 005 technical messages Disablement of a detector zone e g Nr 5 for fault messages 1 FLT DIS 0005 Disablement of an element e g Nr 14 of a detector zone e g Nr 5 1 FLT DIS 0005 014 for fault messages Disablement of an actuation zone e g Nr 2 1 ACTU DIS 0002 Disablement of an element e g Nr 18 of an actuation zone e g
42. 2 2002 08 36 AL DEV ACT T 01 Sirens Main building 329 21 12 2002 08 36 ACTU ACT 0012 Loft Fire dampers ier Ha E 28 Chapter 3 e Displaying and operating elements User Manual Series BC216 Part A 330 21 12 2002 08 45 ENABLEMEN 0002 1 Floor Storage area 331 21 12 2002 08 47 AUTHORIZATION EXIT User level Figure 6 Example of a protocol print out The continuous line number date time event with zone and element number if available event text I event text 2 are printed from left to right 08 32 The detector 2 14 activated an alarm due to this the actuation 12 and the alarming device Nr 1 were automatically activated 08 33 The alarm delay was activated by the user 08 36 The authorization code was entered and the detector zone 2 was disabled Due to this the alarm was terminated followed by the automatic silencing of the alarming device and of the actua tion 08 45 The detector zone 2 was enabled 08 47 The authorization was exited At events which also supply a complementary text e g at a fault of a detector zone the information whether wire breakage or short circuit occurred this text is printed in a second line after the event line The event print out of a network fire detection control panel BCnet216 is always printed in two lines the number of the GSSnet member is also printed besides a possible complementary text see above paragraph The events are printed in their temporal order as they w
43. 3 005 nical messages being put in test condition Alarm of a detector zone e g Nr 5 for fault messages being put in test 1 FLT T AL 0005 condition Alarm of an element e g Nr 14 of a detector zone e g Nr 5 for fault 1 FLT T AL 0005 014 messages being put in test condition Test activation of a transmitting device e g Nr 1 1 TR DEV TEST 01 Test activation of an alarming device e g Nr 1 1 AL DEV TEST 01 Test activation of an actuation e g Nr 1 1 ACTU TEST 0001 Test activation of an element e g Nr 4 of an actuation e g Nr 1 1 ACTU TEST 0001 004 Table 6 Messages of test conditions E You terminate a test procedure by disabling the corresponding detector zone The displays of test con ditions remaining in the display memory are renumbered in the order of their occurrence HB216AE SAM 0130 AN9161202 ZN5002 73 64 User Manual Series BC216 Part A Chapter 6 e Ensuring the efficacy of the system by the user 65 HB216AE SAM 0130 AN9161202 ZN5002 73 65 6 1 6 1 2 Ensuring the efficacy of the system by the user In order to ensure the efficacy of the fire detection system the user periodically should make sure that the system fulfills its determined purposes in all areas and that it functions fully and well This internal control may also be ordered by the regulatory agencies M d Periodic function tests Periodic function tests have to be performe
44. 5 in Chapter 6 Ensuring the efficacy of the system by the user Be sure to pay attention to the safety instructions starting page 8 in Chapter 1 2 Important hints for the user and the installer The second part of the User Manual Part B gives the authorized installer of fire detection sys tems the information necessary for planning the setup of the control panel as well as for installing and assembling the fire detection control panel The third part of the User Manual Part C supplies the information necessary for the trained in staller for putting the control panel into operation for setting the parameters and for maintenance of the control panel 8 1 1 1 2 Chapter 1 e Introduction User Manual Series BC216 Part A This User Manual is not designed as a description of or as an operating instruction for a fire detection system Therefore detailed instructions for how to act in case of an alarm or a fault are not given Indi vidual differences in the variety of components used and in the setup are so extensive that an efficient general description of the system or of the organization in case of an alarm would not be possible Due to national guidelines or regulations and local restrictions some of the described functions of the control panel can be used only selectively or maybe even not at all Authorization to operate the control panel is also regulated differently in different communities Furthermore many features
45. 6 Part A e Delay time The delay time consists of reaction and exploration time During the reaction period the activation of the transmitting devices for fire alarm messages can be delayed during day operation of the fire detection system Exploration time allows the user to find the cause of the alarm and to decide if the fire brigade indeed should be notified Detection area A particular part of a surveilled area where the fire detectors installed there share a display on the fire detection control panel e Detector line Branch cable wiring that connects fire detectors usually conventional detectors to the fire detec tion control panel e Detector zone The fire detectors of a surveilled area that share a display on the fire detection control panel are summed up to detector zones Detector zones can be set for fire alarm fault alarm and technical messages on the fire detection control panel Series BC216 Disablement Deliberately set condition of a fire detection system where either the whole system or parts of it are put out of operation False alarm Alarm that is released because of a technical fault in the fire detection system e Fault detector A fault detector transmits an appropriate signal to the control panel if a fault has occurred such as e g a loss of weight of the extinguishing agent in an extinguishing system e Fire brigade control unit This optional unit indicates the most important operational condit
46. Activated actuations if no event of higher prior ity is currently on the control panel The first line of the LC display shows the temporarily first activated actuation The second and third line display the zone and the element specific text for the actuation displayed in the first line The fourth line is reserved for displaying alarms The activated actuations are numbered in the order of their activation 1 ACTU ACT 0004 021 lt zone textl1 gt lt element text gt 1 ALARM 0003 029 Figure 18 Display in activation condition of actuations Actuation Nr 4 actuation element Nr 21 is displayed as the first activated actuation The second and third lines contain text information regarding the actuation Is no element text available the third HB216AE SAM 0130 AN9161202 ZN5002 73 55 56 5 3 1 5 4 Chapter 5 e Operating conditions of fire detection control panels Series BC216 User Manual Series BC216 Part A line will show the second zone text if this is available The fourth line is reserved for fire alarm messages Ifthe parameters have been set accordingly the light emitting diodes of all activated actuations are illuminated on the optional LED display field Additional information e g date and time of the activation of the actuation displayed in the first line the number of activated actuations hints for operating the menu hints for authorization etc can be displayed by using the Info button
47. Chapter 5 2 Fire alarm condition What to do in case of a fault The fire detection control panel Series BC216 as well as the connected components of your whole fire detection system are in operation for 24 hours a day over many years Although the components have been built with highest care and are checked thoroughly and regularly during maintenance faults can occur due to such factors as dirty fire detectors malfunctioning components damage etc Different faults have different effects on the functioning of the alarm system ranging from no effect to com plete shutdown of the fire detection system In order to maintain the most important functions of the control panel in case of malfunctions in single parts of the control panel the manufacturer has included elaborate security measures that were devel oped during many years of experience with fire alarm technology Nevertheless a total guarantee for the proper working of the control panel in case of a fault cannot be given especially if two or more malfunctions occur simultaneously If the display or a light emitting diode indicates a fault you have to assume that the corresponding part of the system does not work Make sure that the system is reconditioned fast In some cases such as e g a mains power fault message caused by erroneous shutdown the reconditioning may be carried out by yourself In most cases however you will have to commission a trained and authorized special
48. E 66 Testing the fire control systems aaa cece cece nee enn cnet eee kaan 66 Testing the transmitting devices cece NAAN aaa aaa 66 Other tests 2 ln ABANGAN ALA E ESDA ETRE EE EE BIT EDE EEE seb Paa EERENS 66 Reconditioning and maintenance sese KA aan 67 Specifications of control panel devices of Series BC216 aaa 67 Event memory entries 0 cece cece GAGA k aaa ws 68 INC NA I2 User Manual Series BC216 Part A HB216AE SAM 0130 AN9161202 ZN5002 73 6 HB216AE SAM 0130 AN9161202 ZN5002 73 7 User Manual Series BC216 Part A Chapter 1 e Introduction 7 Introduction Decades of research and development of LST in the field of fire detection control panel technology and the successful cooperation with renowned international test authorities led to the development of the new fire detection control panels BC216 1 and BCnet216 of LST The fire detection control panel BC216 1 was drafted as a compact control panel for application in fire detection systems of small and medium size The control panel BCnet216 is based on the successful concept of the BC216 1 and additionally offers all advantages of a modern network technology It con sists of several sectional control panels which are allocated exactly where they are needed most in the vicinity of the fire detectors This network control panel is applied in fire detection systems of me dium to very large size and
49. Their parameters can be set for displaying conditions of single detec tor zones actuations transmitting devices and alarming devices The individual lettering of this display is done with insertable labels Acoustic signal A buzzer is built into the fire detection control panel BC216 1 or in every operable BCnet sectional control panel of a fire detection control panel BCnet216 for acoustic signalling of fire alarms fault alarms faults and other exceptional conditions Inadmissible inputs with the keypad are indicated by a short beep as well The buzzer also is used as a reminder If there is a current fire alarm a fault alarm a fault or a techni cal message the silenced buzzer is activated briefly every 15 minutes The buzzer is silenced by using the button Silence buzzer with the fire detection control panel BCnet216 the buzzers of all other BCnet sectional control panels are silenced as well Protocol printer For printing a protocol of all incoming events or of all operation proceedings a commercial printer with serial interface can be connected to the fire detection control panel BC216 1 or to every BCnet sectional control panel of a fire detection control panel BCnet216 Following printers are currently sup ported by the control panel e Seiko DPU 414 Art Nr 0227003 e Epson LX 300 Art Nr 0227008 You can read further information on the printers in Part B of the User Manual Either all events just the events of
50. abled also depending on the built in function modules The operating and displaying of detector zones are described starting page 39 in Chapter 4 7 7 Dis playing and operating detector zones menu point Zone Acoustic and optic alarming devices Persons who are in danger can be warned by the fire detection control panel BC216 1 or by every BC net sectional control panel of a fire detection control panel BCnet216 by acoustic alarming devices e g sirens or optical ones e g flashlights that are combined into up to ten independent zones The activation of the alarming devices is dependent on logic combinations of the alarm activation of detec tor zones or of single detectors Thereby evacuation alarms for example can be adapted to the level of danger present in the local situation Each alarming zone can be enabled disabled and silenced individually in case of an alarm The dis playing and operating of alarming devices are described starting page 43 in Chapter 4 7 10 Displaying and operating alarming devices menu point Alarming device The overall number of all zones of alarming devices is limited to 99 in a fire detection control panel BCnet216 Transmitting devices Up to ten independently operating transmitting devices can be activated by the fire detection control panel BC216 1 or by every BCnet sectional control panel of a fire detection control panel BCnet216 to alarm the designated alarm respondent e g the fi
51. abled and disabled individually The displaying and operating of the actua tions are described starting page 41 in Chapter 4 7 8 Displaying and operating actuations menu point Actuations Information devices for the fire brigade The fire detection control panels Series BC216 support the functions of various devices used in a fire detection system for the information of and use by the fire brigade These are for example fire brigade control units key safes and key depots fire brigade map systems etc The modular construction of the fire detection control panels Series BC216 facilitates the simple adaptation to country specific designs of these devices Information systems Besides the standard devices mentioned above printers additional computer aided information systems and superior managing devices and main control panels are often used in a fire detection system Such devices are connected to and managed by the control panel via the serial interfaces contained in the fire detection control panel Series BC216 or with fire detection control panels BCnet216 also via gate ways which are connected to the network 22 Chapter 3 e Displaying and operating elements User Manual Series BC216 Part A 3 Displaying and operating elements The functions and effects of the displaying and operating elements of the fire detection control panel Series BC216 and the optional protocol printer are described in this chapter The operation of the c
52. anel by connected fault detectors are dis played in this menu point E In this case the I button has a special function The detector zone whose fault message is currently displayed is disabled by using this button Displaying disablements menu point Disablements Scroll through all current disablements by using the TL buttons details see from page 61 in Chapter 5 6 Disablement condition HB216AE SAM 0130 AN9161202 ZN5002 73 38 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 39 1 TECH DIS 0003 lt zone textl1 gt lt zone text2 gt Figure 11 Example for the display of the disablement of a technical message zone 3 In this case the button has a special function The part of the system whose disablement is cur rently displayed is enabled by using this button Menu quick operation 4 7 6 Displaying test conditions menu point Test conditions Scroll through all system parts in test condition by using the TL buttons details see from page 63 in Chapter 5 7 Test condition 1 TEST COND 0003 lt zone textl1 gt lt zone text2 gt Figure 12 Example for the display of a test condition of zone 3 E In this case the button has a special function The part of the system whose test condition is cur rently displayed is disabled by using this button Menu quick operation 4 7 7 Displaying and operating detector zon
53. are evaluated as a fault in the same way Table 4 Messages of the fault message condition By pressing the button Info detailed information on the faults are displayed E In case of several current faults you can tell the order of their occurrence by the number in front of the fault message Starting with the tenth fault a is written instead of the number The exact time of the occurrence of the fault can be displayed by pressing the button Info HB216AE SAM 0130 AN9161202 ZN5002 73 60 User Manual Series BC216 Part A Chapter 5 e Operating conditions of fire detection control panels Series BC216 61 HB216AE SAM 0130 AN9161202 ZN5002 73 61 5 6 power shut down The required bridging time is regulated by local guidelines Often a bridging time d of 72 hours is demanded Note that longer mains power shut down times mean that the fire detection system will be out of power and therefore out of function At a fault of the stand by battery the fire detection system is supplied by the mains power only With a shut down of the mains power the fire detection system runs out of power and is therefore out of func tion A single earthing of the cabling system does not impair the fire detection system multiple earthings are additionally displayed as a fault of the corresponding part of the system If the second line of the LC display shows FWT FM1 FM2 ABB216 or LAB as fault cause in case of a fault you have to
54. arm of a detector ZONE s e aaa aaa 54 Terminating the fire alarm condition see aa 54 Fire alarm condition special case alarm in an interdependence of two detectors 55 Activation condition of actuations aaa awan aan 55 Activating an actuation in a two zone dependency cece eee eee eee eee 56 Message condition for technical messages 0 cee cece eee eee eee ee teen een ed 56 Resetting a technical message 1 ce eect cee een cnet teen anakan 57 Special technical Messages 0b ieee ge baa doses e E E RA E i E E slats 57 Fault message condition 1 0 0 0 cece cece cece nen e cnet ene e enn cnet ence erences 58 Disablement condition serrr Nah NGA deeds eae ket woh eee E a ade see eh ee kang 61 Te st condition ern 20 taccetalnoiiadeebatholes DROGA LP AB EDIT ent beads RETRETE PR 63 Ensuring the efficacy of the system by the user 0 6 cece nennen 65 Periodic t nction tests 2 0 Hanap Bote Made rated PALAPAG GANG Lada ania tly gel ee 65 ESF HB216AE SAM 0130 AN9161202 ZN5002 73 4 User Manual Series BC216 Part A 6 1 1 6 1 2 6 1 3 6 1 4 6 1 5 6 2 6 3 6 4 HB216AE SAM 0130 AN9161202 ZN5002 73 5 Testing of the fire detection control panel and the power supply devices 65 Testing of detectors 2n ka BAGAN NGA DNA IL pb ede cb ESEESE EE RP GG nessa EE Ks 65 Testing the alarming devices 4 nana Da aNG LAN odes tia seedeestoaea KEAN A
55. arted The actual transmission to the fire brigade requires the connection of the control panel to the regional transmission system of the fire brigade e Fault Disabled yellow Is flashing in case of a fault in the primary transmitting device or in its transmittal and is illuminated in case of the disablement of the transmitting device Nr 1 e Alarm delay yellow Is illuminated in alarm delay operation day operation and is flashing dur ing exploration time after the activation of the alarm delay See page 32 in Chapter 4 2 4 Alarm delay procedure of the primary transmitting device Call fire brigade yellow Is illuminated in case of a fire alarm if the alarm has been transmitted to the primary transmitting device but the transmittal to the fire brigade did not take place This dis play depends on the regional transmitting device system Ask the authorized installer of your fire detection system for information Confirmation yellow Is illuminated to confirm the successful activation of the transmitting de vice to the fire brigade e g This display depends on the regional transmitting device system Ask the authorized installer of your fire detection system for information Alarm delay Explore button This button has several functions depending on the operating condi tion of the fire detection control panel If there is no current fire alarm you can alternate between operation with alarm delay day oper
56. ase of writing the dis plays in a display frame the brackets are left out Important hints for the user and the installer Get to know the functions and operation of the control panel and their effects on the whole fire detec tion system right away so that you can take appropriate measures quickly and without delay in case of fire A short summary of the most important operations of the control panel is included in the delivery documents of the control panel Operation Manual In Short Form This summary is supposed to be an instructional booklet for the user It does not replace the Manual at all Contained in the summary is a survey where the authorized installer has recorded the actual setup of the basic functions of the control panel On this setup depend the workings the handling and the displays of the different parts of the control panel that are described in general terms in this Manual Also pay attention to the overall de scription of your fire detection system Peripheral devices like fire detectors remote signalling and operating units signalling equipment etc used in addition to the control panel in a fire detection system are only mentioned as examples and are not described in detail in this User Manual Fire detection systems and devices are used to detect fire and to raise alarm rapidly Since this equip ment is designed to protect life and property from the dangers of fire it has to be planned installed and put into ope
57. assume that the public safety personnel e g the fire brigade will not be notified automatically in case of alarm FAULT FWT or e the fire detectors connected to the function modules FM1 or FM2 are no longer serviced by the con trol panel and therefore can no longer report alarms to the control panel and consequently cannot activate actuations FAULT FM1 FAULT FM2 Please retrieve information on which fire de tectors or detector zones are affected by this fault from your engineering data e the display and operating unit of the control panel FAULT ABB216 or the LED display field of the control panel FAULT LAB is out of function The fire detection system is supplied with power by the stand by battery in case of a fault with mains M If a fire detection control panel BCnet216 displays MEMB FLT xxx in case of fault you have to as sume that the GSSnet member number xxx is completely out of function If this GSSnet member is a BC net sectional control panel of the BCnet216 the area which is attended by this BC net sectional con trol panel is no longer monitored If a fire detection control panel BCnet216 displays GSS N FLT xxx in case of fault a line fault ex ists in the GSSnet wiring after the GSSnet member number xxx Since the GSSnet is built on circular wiring this does not yet impair the fire detection system If however two such faults are displayed the GSSnet members arranged between the two displayed GSSnet me
58. ast Aside from the resulting gross negligence dan ger to human life and to property a fire insurance may reject the claim for compensation in such cases 6 4 Specifications of control panel devices of Series BC216 Mains voltage 230VAC 10 15 50Hz Power requirement 60VA Supply current max 0 26A Output rated voltage typ 28VDC Peak current max 1 8A Case Colour Dimensions w Xh xd Weight without battery Ambient temperature Relative humidity of air steel sheet Imm powder coated grey white RAL9002 420 x 520 x 120 mm ca 6kg 5 C to 50 C 95 not condensed Further detailed specifications are available in Part B of the User Manual of the fire detection control panel Series BC216 HB216AE SAM 0130 AN9161202 ZN5002 73 67 Chapter 7 Event memory entries Event memory entries User Manual Series BC216 Part A You can browse in the event memory by the use of the TL buttons The first three lines of the LC display show the event text as well as the free programmable text information on the event and provide additional information on events on the control panel By pressing the Tnfo button additional texts e g the reason for a given fault appear as well as the date and time of the occurrence or of the termi nation of the event Event Event text Text 2nd line Text 3rd
59. ation and operation without alarm delay night operation by pressing this button If this button is pressed during activated alarm delay operation in case of fire the transmitting of the alarm to the fire brigade is delayed for the span of the programmed exploration time See page 32 in Chapter 4 2 4 Alarm delay procedure of the primary transmitting device During running exploration time pressing of the button leads to displaying the time remaining till the activation of the transmitting device E By using the built in timer the switch to day operation can be limited to a defined time window At all other times the button Alarm delay Explore is ineffective See from page 32 in Chapter 4 2 4 Alarm delay procedure of the primary transmitting device The alarm delay procedure may be suppressed to tally depending on local restrictions ALARM DEVICE 1 field The fire detection control panel BC216 1 or every BC net sectional control panel of a fire detection control panel BCnet216 can manage up to ten different alarming devices The device connected to the supervised siren output of the control panel or the BC net sectional control panel is presumed that the output was parameterized as alarming device named primary alarming device This primary alarming device is operated by the displaying and operating elements located in the field ALARM DEVICE 1 All further possible alarming devices are operated exclusively by the use of the menu a
60. ation code Exit authorization After confirming this menu point you can either enter the code for authorization level 2 or 3 or exit authorization level 2 or 3 depending on the current authorization level See from page 36 in Chapter 4 5 Entering and exiting authorization level 2 HB216AE SAM 0130 AN9161202 ZN5002 73 47 48 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A 4 8 Operating the control panel by using the fire brigade control unit A fire brigade control unit offers the fire brigade the possibility to operate the necessary functions of the control panel uniformly Fire brigade control units are locally designed differently and sometimes have to fulfill different functions Thus only the basic operations can be described in this User Manual Information on the actually possible operations is to be found in the User Manuals of the respective fire brigade control units E Commonly fire brigade control units are secured with a lockable door and thus can be operated only by the fire brigade In the following the most common input elements of the different fire brigade control units are juxta posed to the comparable operations on the control panel itself Operation element on the fire brigade control unit Operation on the control panel BC216 1 Reset control panel corresponds to the button Panel reset Silence acoustics on the control panel correspon
61. ault alarm fault or technical message the silenced buzzer is activated briefly every 15 minutes If the buzzer is not activated and you are pressing this button the function display test is activated This means that the buzzer all dots of the LC display and all light emitting diodes are activated you can check if all display elements are in function The function display test of the button buzzer off is locked as long as an event is current which has activated the buzzer e g alarm or fault condition You can activate the display test by the use of the menu as well See from page 44 in Chapter 4 7 12 2 Testing the optic and acoustic displays and the buzzer submenu point Display test Silencing the primary alarming device In case of an alarm you are silencing the corresponding primary alarming device by using the button On off located in the field ALARM DEVICE 1 As long as the control panel is still in the state of fire alarm the silenced alarming device can be reactivated by pressing the button again The silenced primary alarming device is activated again by receiving another alarm message and can be silenced in the same way provided that this feature of the control panel has been enabled by the in staller when parameters are set For silencing and reactivating the primary alarming device authorization level 1 or 2 is required de pending on the parameterization of the control panel 32 4 2 4 Chapter 4 e Bas
62. bmenu point by using the button Pay attention to the special functions of this button in some menu points Return to the next higher menu point by using the button esc Infor mation on the displayed event and on the operations now possible is provided by pressing the button Info For individual displays of all events of detector zones actuations transmitting devices alarming de vices etc two lines of the LC display are for use In case of an event e the second line of the LC display shows the zone transmitting device etc textl and the third line of the LC display shows the element text or if there is no element text the zone transmitting device etc text2 The authorized installer enters the texts during the setting of the parameters Displaying fire alarms menu point Alarms Scroll through all current fire alarms by using the N buttons for details see from page 50 in Chapter 5 2 Fire alarm condition 1 ALARM 0003 029 lt zone text 1 gt lt element text gt 1 ALARM 0003 029 Figure 7 Example for an alarm display of the detector zone 3 detector Nr 29 Has no element text been pro grammed the second line of the zone text if available is displayed E In this case the I button has a special function The detector zone whose alarm is currently displayed is disabled by using this button E Pre alarms are displayed in this menu point as well Pre alarms are activated by t
63. can either accept the proposal search the desired detector zone by using the N buttons or directly enter the zone number of the desired zone You confirm the choice by using the button E You can go directly to the menu point Zone by using the menu quick operation See from page 33 in Chapter 4 3 1 Menu quick operation The third line of the LC display shows the current condition of the chosen zone in capital letters If you intend to change this condition you can either scroll to the desired condition by using the N buttons or by the menu quick operation using numeric buttons 0 disable 1 enable 2 activate for test purposes 3 test condition on HB216AE SAM 0130 AN9161202 ZN5002 73 39 40 4 7 7 2 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A No alarm is transmitted by detector zones that are disabled faulted or put in test condition A detector zone that is disabled faulted or put in test condition and is programmed in a two zone dependency is removed from this dependency If the dependency consists only of two detector zones one of which is out of function the two zone dependency cannot activate the devices that are to be activated Parameters of actuations can be set so that they are activated at disablement or at a fault of the corre sponding detector zone as well Information on the kind of activation used in your system can
64. ces In this case the condition of fire alarm is attained only if at least two detectors of an interdependence of two detectors are in the state of alarm at the same time Is the first detector of an interdependence of two detectors in the state of alarm the control panel evaluates this as a pre alarm The LC display of the control panel displays a pre alarm similarly to an alarm but uses the word PRE AL Usually no further optical or acoustic displays are activated However the parameters of an actuation can be set so that the actuation is activated in case of a pre alarm A pre alarm is either deleted after a short period of time typically after 2 minutes or it changes directly to fire alarm condition if a second detector mean while attained the state of alarm during the pre alarm time as well The further processing and the dis play happen as described starting page 50 in Chapter 5 2 Fire alarm condition Also more than two detectors can be combined into an interdependence of two detectors If at least two detectors of this interdependence of two detectors are in the state of alarm the fire alarm condition is attained A detector is removed automatically from the interdependence of two detectors if it is disabled or has a A fault until the fault or the disablement is terminated Have the parameters of the interdependence of two detectors been set for just two detectors the disablement or the fault of one of these detectors pre vents fire
65. condition E In addition you can check on the executed activation of the detectors by reading the event memory subsequently 66 6 1 3 6 1 4 6 1 5 6 2 Chapter 6 Ensuring the efficacy of the system by the user User Manual Series BC216 Part A After finishing the testing of the detectors you have to terminate the test condition immediately the actuations in case of fire Therefore put detector zones in test condition only for test purposes and N Detection zones in test condition cannot transmit an alarm to the fire brigade the alarming devices and terminate this condition as soon as possible Testing the alarming devices The easiest way to test the installed alarming devices e g sirens is to activate them See from page 43 in Chapter 4 7 10 Displaying and operating alarming devices menu point Alarming device N The activation of the alarming devices for test purposes has the same effect as a real activation Before the activation make sure that everybody in the building is informed of the test alarm Testing the fire control systems You are testing the functions of the fire control systems by activating them See from page 41 in Chap ter 4 7 8 1 Operating actuations The activation of an actuation for test purposes is a real activation which may lead to an unin tended activation of an extinguishing system and thus to danger to life and to costly damage of property Contact the responsible
66. condition on easured value maintenance Actuation Disable Enable Activate eas val Maint Transmit device Disable Enable Alarming device Disable Enable Activate eas val Maint Silence Reactivate Event memory Display all Control panel Detector zones Event memory Display all Control panel Detector zones System Event counter Display test Repeat print out System Event counter Display test LCD contrast Clock time correct Clock time setting Date setting Winter summertime Summer wintertime Componentries Print out Repeat print out Stop measurement print out Change user code Change install code Authorization code Exit authorization D These submenu points are accessible only in authorization level 3 that means only to the authorized maintainer Table 1 Overview of the available main and submenus in authorization levels 1 and 2 respectively You are scrolling the main menu ring shaped by using the t buttons and the submenu by using the TL buttons The corresponding standard entry menu point in normal condition is marked by Single menu points can be suppressed depending on the context I point was called last HB216AE SAM 0130 AN9161202 ZN5002 73 35 The menus for setting the parameters which are reserved for the installer in authorization level 3 are not shown in
67. connection lines e g broken wire short circuit earthing between individual parts of the system the power supply single detectors the control panel itself etc Every current fault affects the function of the whole fire detection system Be aware that a part of a AN system that has a fault is out of function in its whole For example a faulty fire detector zone cannot detect a fire in this detector zone Have the fault repaired immediately by a company authorized and trained by the manufacturer Pay attention to the statements starting page 9 in Chapter 1 2 2 What to do in case of a fault Not all parts of a fire detection system can be checked on continuously A fault of a part of the system that is not automatically surveilled constantly can be detected only during maintenance or during the periodic testing of its functions by the user The fault message condition is displayed on the control panel as follows e The yellow summary display FAULT is flashing e The internal buzzer is sounding constantly You can reset the internal buzzer by using the button Silence buzzer The buzzer is activated again by each new fault and can be reset in the same way e The menu jumps automatically to the menu point Faults if no event of higher priority is currently on the control panel The first line of the LC display shows the first occurred fault The second and third line display de pending on the kind of fault additional text e g a zo
68. ctuation element In this case the maintenance prognosis is insignificant Displaying and operating transmitting devices menu point Transmit device You display the current switch condition of a transmitting device on the LC display and disable and en able a transmitting device in this menu point Consider the hints given starting page 33 in Chapter 4 3 Operations using the menu Minimum requirement for this menu point is authorization level 2 E Have the parameters of a transmitting device been set for a two zone dependency to increase security against deceptive activation the activation of the transmitting device will take place only after at least two detector zones of this two zone dependency are in condition of alarm After confirming the menu point Transmit device the first available transmitting device is proposed You can either accept the proposal search the desired transmitting device by using the N buttons or by directly entering the number of the transmitting device You confirm the choice by using the button paki The third line of the LC display shows the current condition of the chosen transmitting device in capi tal letters You can either scroll to the desired condition by using the N buttons or the menu quick operation using numeric buttons O disable 1 enable An activated transmitting device cannot be disabled directly Before you can disable it you have to re move the cause of the activation
69. d are wired to the control panel The data transmitted by the fire detectors are analyzed and rated in the fire detection control panel The fire detection control panel decides if the situation is to be rated as a fire alarm Does the control panel decide for fire alarm the alarming devices and the fire control systems are automatically activated by the fire detection control panel and the alarm is transmitted to the public fire report post Controls that are activated by the fire detection control panel can comprise single functions e g switching off the ventilation as well as elements combined to zones e g several door closers in a fire area 16 2 2 Chapter 2 e Fire detection control panel Series BC216 User Manual Series BC216 Part A Typical construction of a fire detection system with network control panel BCnet216 Basically the network fire detection control panel BCnet216 does not work differently than described from page 15 in Chapter 2 1 Typical construction of a fire detection system with control panel BC216 1 The most essential difference to a single control panel is that the network fire detection con trol panel does not form a physical unit but consists of single sectional control panels which are ar ranged throughout the surveilled area of the fire detection system and which are combined to a virtual control panel by a network cable interconnected in a circular pattern A maximum of failure proofness and cost ef
70. d by trained personnel e g by the fire prevention officer The function tests generally are simple tests of the operational readiness of the fire detection system as described exemplary in the following Testing of the fire detection control panel and the power supply devices e Make sure that the light emitting diode POWER is illuminated on the fire detection control panel BC216 1 or on all operable BCnet sectional control panels of the network control panel BCnet216 E In normal condition of the control panel only the green light emitting diode POWRR is solely illuminated e Make sure that no fault is currently on the control panel You recognize the fault condition see from page 58 in Chapter 5 5 Fault message condition by the flashing of the yellow display FAULT e Make sure that no disablements are in effect and that no detector zones are in test condition e Carry out a display test by pressing the button Silence buzzer on the control panel or on all oper able BC net sectional control panels Thereby you are testing the optical displays and the internal buzzer See from page 44 in Chapter 4 7 12 2 Testing the optic and acoustic displays and the buzzer submenu point Display test In spite of the complex charging control for charging the stand by batteries the lifespan of the maintenance free batteries used in security systems is limited Notice the specifications of the manufacturer of the battery regarding the
71. d test conditions are not affected by the reset Disabled parts of the system and parts that are put in test condition are not enabled either by resetting the control panel The minimum requirement for resetting the control panel is authorization level 2 E The causes of the alarms faults etc are not affected by resetting the control panel If the causes have not been removed prior to resetting the alarms faults etc will be displayed again after resetting the control panel and will be processed like new messages leading for example to the activation of the transmitting devices activation of fire protection devices etc Important information can vanish from the display and fire control systems that should be kept acti vated can be reset prematurely or not be activated at all by resetting the control panel prematurely Silencing the internal buzzer display test You can silence the internal buzzer of the fire detection control panel BC216 1 or of all operable BCnet sectional control panels of a control panel BCnet216 by using the button Silence buzzer The buzzer will be reactivated by every received fire fault or technical message For silencing the buzzer and for testing the displays authorization level 1 is sufficient At a fault message or a technical message the buzzer silences automatically after 15 minutes without the pressing of a button E The buzzer is used as a reminder as well In case of a current fire alarm f
72. dependency are in the condition of alarm See from page 39 in Chapter 4 7 7 Displaying and operating detector zones menu point Zone 52 5 2 1 Chapter 5 e Operating conditions of fire detection control panels Series BC216 User Manual Series BC216 Part A E The activation of a transmitting device and of an alarming device are classified as an actuation and therefore activate the red light emitting diode Actuation activated as well Ifthe parameters have been set accordingly the red light emitting diodes of all alarming zones ac tuations transmitting devices and alarming devices are illuminated on the optional LED display field You can scroll through all current alarms by using the TL buttons The running number in front of the word ALARM indicates which alarm is currently displayed starting with the tenth alarm a is used instead of the number The second and third line show the text for the alarm displayed in the first line By pressing the button Info additional information on the displayed alarm is provided such as e g date and time of the reception of the alarm displayed in the first line the number of current alarms hints for operating the menu hints for the authorization etc The following example of three current fire alarms shall illustrate this operation 1 ALARM 0003 029 first display lt zone textl1 gt lt element text gt 3 ALARM 0016 020 press V button 2 ALARM 0003 010
73. display in a 3 second cycle For example in a case of a fault in a de tector zone the kind of fault e g a dirty detector the date and time of the occurrence and the number of current faults are displayed successively after pressing the Info button With the fire de tection control panel BCnet216 it is also displayed which BC net sectional control panel the detector zone or the detector is connected to e This information is followed by the display of relevant help hints Basically the input possibilities that are admissible in the current situation are displayed successively E If you are pressing a button during the displaying of the additional information or the help text the displaying will be stopped and your input will be evaluated Therefore you do not need to wait for the end of the help text before you can start a new input Menu buttons By using the 5 buttons you are scrolling the main menu points ring shaped by using the ie buttons you are scrolling the submenu points of the priorly shown main menu ring shaped The sub menu point that you confirm by using the button will be executed You return to the next higher menu level by the use of the esc button E For faster operation of the control panel the most frequently used operations can be executed without having to use the structure of the menu For further information see from page 33 in Chapter 4 3 1 Menu quick operation Numeric keys Numeric inp
74. ds to the button Silence buzzer Silence sirens all alarming devices are silenced jointly Acoustic signals off all alarming devices are silenced jointly Table 2 Comparison of the common operating elements of fire brigade control units to the corresponding op erations of the fire detection control panel Series BC216 HB216AE SAM 0130 AN9161202 ZN5002 73 48 User Manual Series BC216 Part A Chapter 5 e Operating conditions of fire detection control panels Series BC216 49 HB216AE SAM 0130 AN9161202 ZN5002 73 49 Operating conditions of fire detection control panels Series BC216 This chapter describes the operating conditions of a fire detection control panel or system and the pos sibilities of operation resulting from these conditions The following operating conditions are interna tionally standardized normal condition i e no event is registered on the control panel fire alarm condition at least one alarm has been received from a fire detector e fault condition at least one function of the control panel or the connected network has a fault or a fault alarm from a fault detector has been received disablement condition at least one function of the control panel or a part of the system is disabled test condition at least one part of the system is in test condition and therefore is out of function Furthermore the fire detection control panels Series BC216 satisfy expectations of modern sec
75. ds under no circumstances may enter the interior of the case Prior to opening a case the mains voltage of the regarding case has to be shut down and secured against restart Consider that if the mains voltage is connected there are parts in the open case of the control panel that carry life endangering voltage The protective case of these parts may never be removed Further security hints for the installer are given in Part B of this User Manual What to do in case of a fire alarm Keep calm in case of a fire alarm Silence the internal buzzer of the control panel BC216 1 or of all BCnet sectional control panels of the network control panel BCnet216 by using the button Silence buzzer All further actions such as e g identifying the alarming detector zone activating the delay time exploring the fire location starting to extinguish the fire instructing the fire brigade etc depend on the local circumstances These actions summarily called organization in case of an alarm are to be determined by both the user of the system and the fire brigade at the time when the control panel is planned and put in operation If the light emitting diode Call fire brigade is illuminated on the fire de tection control panel or your fire detection system is not connected to a permanently manned desig nated alarm respondent e g the fire brigade you have to notify the fire brigade yourself immediately Further hints are given starting page 50 in
76. e detection control panel BCnet216 the operating authorization is valid only for the operable BCnet sectional control panel on which the user code was entered Fire alarm condition The control panel is in fire alarm condition when it receives an alarm from one or more fire detectors classifies it as a fire alarm and initiates the corresponding outputs HB216AE SAM 0130 AN9161202 ZN5002 73 50 User Manual Series BC216 Part A Chapter 5 e Operating conditions of fire detection control panels Series BC216 51 N No rules or instructions beyond those necessary for the operation of the control panel are given in this User Manual You have to analyze the site specific dangers and gain the corresponding measures in case of emergency yourself or you delegate this responsibility to a skilled person The fire alarm condition is indicated on the control panel as follows The red summary display ALARM in the info field is illuminated The internal buzzer is activated intermittently You can silence the internal buzzer by using the button Silence buzzer The buzzer is reactivated by every received alarm and can be reset in the same way The menu automatically jumps to the menu point Alarms immediately after the first alarm and with all other alarms 30 seconds after the last button was pressed The first line of the LC display shows the first alarm the fourth line displays the last alarm re ceived The second and third line disp
77. e event with the highest priority automatically 30 seconds af ter a button in authorization level 2 was pressed last if an event is currently on the control panel This is independent of the menu point where a button was pressed last The current authorization level is maintained No time limit is assigned in authorization levels 3 and 4 Overview of the display and operation menus In authorization level 1 only a limited operation of the fire detection control panel is possible Only in formation on current events or information on the system e g event memory can be viewed by using the menu buttons No permanent changes of conditions can be made Silencing the internal buzzer and the primary alarming device is possible in this authorization level as well Unlimited operation of the control panel is facilitated by authorization level 2 Authorization level 3 is reserved for the installer of the fire detection system HB216AE SAM 0130 AN9161202 ZN5002 73 34 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 35 Authorization level 1 Main menu points Alarms Submenu points Authorization levels 2 and 3 Main menu points Submenu points Activated actuations activated actuations Technical messages Technical messages Faults Disablements Pisablements Test conditions rest conditions Disable Enable Activate Test
78. e input 0 for the interval stands for a single print out Is an interval defined the print out will be repeated periodically The service and settings print out can be stopped with the esc button The characters already con tained in the printer s memory are still printed out after stopping the print out A measured value print out can be aborted via the menu point System Stop measurement print out see from page 47 in Chapter 4 7 12 12 Abort measured value print out submenu point Stop measurement print out This menu point is accessible in authorization level 2 and higher The menu can be changed while the print out is executed in the background HB216AE SAM 0130 AN9161202 ZN5002 73 46 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 47 E With a single measured value print out the output of current events is suppressed until the print out has been finished With the periodical measured value print out occurring events are printed instantly therefore interrupting the running measured value print out shortly E If no printer is permanently connected to the control panel you have to set the parameters of a serial interface for a printer interface and connect the printer to the control panel by using the Serial Inter face Module SIM216 1 before starting the print out Consider the baud rate the printer is set to Fur ther information on setting the paramete
79. e variety of circumstances The control panel sets new standards for the security in the fire alarm technology while reducing the costs due to the simplicity of cabling The listed features from page 17 in Chapter 2 3 1 Fire detection control panel BC216 1 stand alone of the stand alone control panel are valid also for every BC net sectional control panel of the network control panel BCnet216 The operation of the whole network control panel BCnet216 is made via the display and operating units of one or more BC net sectional control panels or via remote display and operating units in the same way as the operation of a compact control panel The user will not recognize that in reality the control panel consists of several components which are spread over a wide range of space Display and operating units of BCnet sectional control panels or remote display and operating units can also be configured as sectional display and operating units for displaying and operating area parts of the whole system depending on the requirements The network is constructed circularly and redundant In case of a line fault of the network through wire breakage or short circuit all BCnet sectional control panels and other GSSnet members keep work ing uneffectedly Even in case of multiple faults of the network cabling all GSSnet members keep working but in this case displaying and operating is probably only possible directly on the BCnet sec tional control panels a
80. een Is illuminated after entering the code for authorization level 2 operating the control panel is possible now or is flashing after entering the code for authorization level 3 setting of parameters is possible now See page 29 in Chapter 4 1 Operating authorization TRANSM DEVICE 1 field Up to ten independent transmitting devices can be managed by the fire detection control panel BC216 1 and by every BC net sectional control panel of the fire detection control panel BCnet216 They can be parameterized either as primary transmitting device or as transmitting device for fire mes sages or as transmitting device for faults I3 The function domain notification of the fire brigade in case of fire regionally is regulated differently Therefore the following list only presents the most important possibilities of this function domain of the fire detection control panel Series BC216 26 3 9 Chapter 3 e Displaying and operating elements User Manual Series BC216 Part A The displaying and operating elements of the field TRANSM DEVICE 1 are reserved for the primary transmitting device which is exclusively designed for the transmission of fire alarm messages All fur ther transmitting devices are operated exclusively by the use of the menu and displayed on the LC display e Activated red Is illuminated if the fire alarm has been transmitted to the primary transmitting de vice 1 e the notification of the fire brigade has st
81. el The parameters of the control panel are set by the authorized installer either by using the keypad of the control panel by using a standard PC keyboard or by using a PC Notebook and the comfortable parameter setup software Text for example can be entered or changed easily by using a PC keyboard The power supply from the mains power is ensured by a switched power unit with 50W rated power that also supplies enough energy for the connected peripheral devices Low current consumption low heat emission and by that high reliability is guaranteed by the high efficiency of the switched power unit A sufficiently dimensioned optional stand by battery ensures that the fire detection system will con tinue to work unaffectedly for a long time in case of mains power shut down The stand by battery is charged temperature controlled by the power unit and is secured against total discharge in case of mains power shut down The case of the fire detection control panel is built for accommodating the stand by battery An optional case with the same dimensions as the standard case is available to house a second set of batteries in case of increased power consumption as well as for housing additional componentries for expansion The event memory saves the last 500 events that have been registered by the control panel You can display the contents of the memory at any time on the LC display A filter enables you to limit displays of the saved events
82. el Series BC216 User Manual Series BC216 Part A played on the control panel In addition to the zone number the fire detection control panels Series BC216 are capable of displaying a zone specific text for every detector zone and a detector specific text for every single fire detector Thereby relevant information is provided for the safety personnel fast and without delay Besides with automatic and non automatic fire detectors the fire detection control panels Series BC216 are also equipped for the connection of fault detectors and the processing of their information e g surveillance of weight of the extinguishing agent in an extinguishing system and of technical de tectors e g the indication of the position of fire dampers These detectors too are combined to fault detector zones and to detector zones for technical messages The processing of the information of these detector zones is similar to the processing of fire alarm information The only difference is the kind of alarm activated in case of an event The fire fault and technical detectors connected to the fire detection control panel BC216 1 or to every BC net sectional control panel of a control panel BCnet216 can be combined into up to 144 detector zones Each detector zone can be disabled and enabled independently and is displayed on the LC display of the control panel with its zone number and information text On the control panel individual detectors can be enabled and dis
83. en an prozessorgesteuerte Gefahrenmeldeanlagen VdS 2489 Brandmeldesysteme Anforderungen und Pr fmethoden VdS 2540 Brandmelderzentralen Anforderungen und Pr fmethoden VdS 2541 Energieversorgungseinrichtungen Anforderungen und Priifmethoden 0 9 9 0 9 9 2 o The CE labeling results from a guideline of the board of the European Community for the coordination of the laws of its member states including the mutual approval of laws With the CE label the manu facturer of the control panel confirms the observance of all relevant EMC and security regulations The fire detection control panels BC216 1 and BCnet216 have been approved by the test authorities in the following states e Austria Pr fstelle f r Brandschutztechnik des sterreichischen Berufsfeuerwehrverbandes e Germany VdS Schadensverhiitung GmbH Zertifizierungsstelle BCnet216 pending e Hungary EMILABS GMBH HB216AE SAM 0130 AN9161202 ZN5002 73 10 HB216AE SAM 0130 AN9161202 ZN5002 73 11 User Manual Series BC216 Part A Chapter 1 e Introduction 11 1 4 1 5 Further approvals are in preparation Warranty Your fire detection control panel Series BC216 has been manufactured with greatest precision and care Nevertheless the possibility of malfunctions cannot be excluded entirely Please contact the authorized installer of your fire detection system in case of a problem As long as the warranty is in effect all parts that fail to op
84. enu point Actuations You can operate activate for test purposes and display the condition of actuations or single elements of actuations in this menu point Consider the hints given starting page 33 in Chapter 4 3 Operations using the menu Minimum requirement for this menu point is authorization level 2 An actuation can activate single fire control systems e g switching off the ventilation system in case of a fire alarm as well as several elements simultaneously e g several door closers in a fire area E Depending on the purpose different kinds of actuations are used for fire control systems The ability to operate an actuation can be restricted depending on its purpose For example the parameters of an actuation can be set so that you can only disable the activated actuation after you have removed the cause of the activation e g a fire alarm E Have the parameters of an actuation been set for a two zone dependency to increase the security against deceptive activation the activation of the actuation will take place only after at least two detec tor zones of this two zone dependency are in condition of an alarm Operating actuations After confirming the menu point Actuations the first available actuation is proposed with the corre sponding text You can either accept the proposal search for the desired actuation by using the 4 buttons or directly enter the actuation number of the desired actuation You confirm
85. enu point Alarming device the first available alarm output is proposed You can either accept the proposal search the desired alarm output by using the TL buttons or directly en ter the output number of the desired alarm output You confirm the choice by using the button The third line of the LC display shows the current condition of the chosen alarming device in capital letters You can either scroll to the desired condition by using the TL buttons or the menu quick operation using numeric buttons O disable 1 enable 2 activate 4 Measured val Maint 5 silence 6 reactivate a silenced alarming device You cannot disable an already activated alarming device only silence it The alarming devices can be parameterized so that a silenced alarming device is activated again by a new alarm or can be reacti vated by using the menu provided that the alarm situation still exists depending on local requirements N A disabled alarming device cannot alarm It is not enabled automatically by a new alarm fore starting the activation for test purposes make sure that everybody in the building is informed of the test alarm When calling up the function Measured val Maint a measured value according to the condition of the module at the time of call up will be put out depending on the type of device used The maintenance prognosis is insignificant N The activation of an alarming device by using the menu c
86. er of incorrect inputs is limited After 5 incorrect inputs the input of the installer code is locked for 15 minutes To return from authorization level 3 to authorization level 1 you have to scroll to the main menu point Exit authorization either by using the menu or by using the menu quick operation and confirm the menu point by using the I button The LC display shows the hint Installer level exited and the green light emitting diode Authorization on the panel is turned off If any parameters were changed the con trol panel will restart automatically in order to make the new parameters effective Further information can be found in Part C of the User Manual E In the same way as when pressing the button Panel reset all current alarms faults etc are reset by re starting See from page 31 in Chapter 4 2 1 Resetting the fire detection control panel E An automatic time activated exiting of authorization level 3 is not provided Description of the menu points All main and submenu points accessible to the user are described briefly in this chapter Furthermore alternative possibilities of menu quick operations are described Note that some menu points are only accessible in authorization level 2 E Scroll the menu points of the main menu by using the buttons and scroll the menu points of the corresponding submenu as well as the list of the information to be displayed by using the buttons a Confirm the displayed su
87. erate properly because of a demonstrable flaw in their manufacture or in material either will be replaced or repaired free of charge In such cases nei ther the time of the original warranty is extended nor is a new warranty period set for the replaced or repaired parts All further claims are excluded especially those regarding secondary damages Beyond these regulations the current regulations of the Allgemeinen Lieferbedingungen der Elektroindustrie are in effect Special terms Some of the special terms often used in this manual are defined in the following Actuation Actuations are used to automatically activate fire control systems e g ventilation fire doors etc in case of an alarm e Alarm Warning of an existing danger to persons and property e Alarm delay procedure Appliance to delay the automatic transmission to the public fire report post e g the fire brigade for a set amount of time Alarm verification Automatic verification of an alarm by checking if the signs of fire last longer than a set amount of time e g 1 minute Alarming device Equipment which is connected to the control panel and whose duty it is to alarm the public e g a siren The alarming device for fire messages which can also be operated additionally to the menu control via the buttons in the field ALARM DEVICE 1 of the key pad of the control panel is called primary alarming device e AUTO setup After confirming the approp
88. ere received by the fire detection control panel The print out can be repeated anytime The repetition of the print out is started in the menu point Sys tem Repeat print out as described starting page 47 in Chapter 4 7 12 11 Repeating a print out submenu point Repeat print out If the printer detects out of paper the print out is interrupted The messages received in the meantime are saved partly in the printer and partly in the control panel The printer memory of the control panel is capable of saving up to 500 printer lines The saved data is printed after the printer is in operation again E If you switch off the printer the data in the printer s memory is lost Use of the protocol printer for printing control panel configuration detector measured values and fur ther information which is required by the authorized installer or the maintenance technician are de scribed from page 46 in Chapter 4 7 12 10 Printing submenu point Print out and in the further parts of this User Manual HB216AE SAM 0130 AN9161202 ZN5002 73 28 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 29 HB216AE SAM 0130 AN9161202 ZN5002 73 29 4 1 Basic operation of the fire detection control panels Series BC216 The basic functions of the fire detection control panels Series BC216 together with their operation are described in this chapter Almost all necessary o
89. erefore can be made without compromises considering only fire protection criteria The parameters of the detector zones can be set for detector zones for fire detector zones for fault or for detector zones for technical messages A supervised siren output dry relay contacts for fire alarm and fault alarm and 16 open collector outputs with open parameters for general activation purposes are supplied to show conditions of opera tion and to activate fire protection systems The Info display with its 4 line illuminated LC display provides text to keep you informed of all cur rent events Text consisting of 20 characters each line can be used not only for detectors and detector zones but also for activation outputs transmitting devices etc This information makes it possible to locate the occurrence of the event exactly and to act fast in case of an emergency For separate displaying of events of detector zones actuations transmitting devices etc and thus to provide higher transparency the optional 48 double LED display with open parameters can be used For lettering the display insert and letter the supplied insertable labels individually Four levels of authorization guarantee high safety against unauthorized access Two of these authori zation levels are secured by the use of freely setable codes The simple operating structure enables the user to operate the control panel without stress Using easy understandable menus logically co
90. es menu point Zone In this menu point you can operate activate for test purposes and display the condition of whole de tector zones as well as single elements of detector zones Note the hints given starting page 33 in Chap ter 4 3 Operations using the menu Minimum requirement for this menu point is authorization level 2 The installer sets the parameters of detector zones to zones for fire detection for technical messages or for fault messages while the system is put into operation The differences between the different kinds of detector zones lie basically in the kind of alarm given and in how the alarm is reset At the enablement of a detector zone or of elements of these zones the control panel checks for 5 seconds if a criterion for an alarm currently exists in this zone In such a case e g a manual call point has not been reset after an alarm activation the enablement is refused and the LC display shows Cannot be enabled or Cannot be enabled completely Before enabling a detector zone or a detector you have to make sure that the local conditions cannot cause an alarm situation during enablement Not all automatic fire detectors that are on the market are able to detect an alarm situation and contact the fire detection control panel within 5 seconds 4 171 Operating whole detector zones After confirming the menu point Zone the first available detector zone is proposed with the corre sponding zone text You
91. evel allows the manufacturer of the fire detection control panel or an authorized representative in a specific country to change the logic operation of the program for example to comply with mandated country specific functions by using special tools and tools for setting pa rameters This level of authorization requires the opening of the control panel special tools and pre cise knowledge of the interactions of the software modules HB216AE SAM 0130 AN9161202 ZN5002 73 30 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 31 HB216AE SAM 0130 AN9161202 ZN5002 73 31 4 2 4 2 1 4 2 2 4 2 3 During activities that require authorization level 4 the fire detection control panel is usually completely out of service Operations using single buttons Single buttons are provided on the control panel for the following operations Resetting the fire detection control panel By using the button Panel reset fire alarms fault alarms faults activated actuations technical mes sages activated transmitting devices activated alarming devices etc all of which are displayed on the fire detection control panel BC216 1 are simultaneously reset With the network fire detection control panel BCnet216 the button Panel reset of every operable BCnet sectional control panel acts on the whole fire detection control panel Displays of faults of the system disablements an
92. ficiency is achieved with this technique of optimizing the cabling system BC216 2 A wm 2 amp r a ae a PIT PFF ci Beso 4 eo ra BC216 3 DW BC216 2 Bag wos B le o ON PEE a 7907777 o n po o7 7o F Fl Go GG a ee lif gree icy Ng bzg FP As o Hg 4 BC216 3 Ba 3 gt 9 o CI a aa mr B A o9 j CHK KE Figure 3 View of a typical fire detection system constructed with the fire detection control panel BCnet216 The system consists of one BC net sectional control panel parameterized as main operating unit A further BCnet sectional control panels BC216 2 with display and operating unit further BCnet sectional control panels BC216 3 without own display and operating unit e the automatic and non automatic fire detectors that are combined into detector zones e the acoustic and or optic alarming devices the transmitting device linked to a designated alarm respondent fire control systems information devices and information systems which are connected either d
93. for all BCnet sectional control panels when setting the parameters of the control panel on the main operating unit via PC and parameter setup software PARSOFT 2 provided that no individual user codes have been parameter ized This common user code can be changed subsequently on every BCnet sectional control panel E The control panel is delivered with a preset user code of 1111 4 7 12 14 Changing the numeric code by the installer submenu point Change installer code 4 7 13 This menu point is accessible only for the specialist installer i e only in authorization level 3 By en tering a five digit numeric code twice the installer sets a new installer code Please pay attention to the hints starting page 29 in Chapter 4 1 Operating authorization With the fire detection control panel BCnet216 the installer codes of the single BCnet sectional control panels can also be defined individually However an installer code for all BCnet sectional control pan els can be entered when setting the parameters of the control panel on the main operating unit via PC and parameter setup software PARSOFT 2 individual installer codes defined prior to this will be over written This installer code can be changed subsequently on every BCnet sectional control panel E The control panel is delivered with a preset installer code of 99999 The program demands the in staller to change this code when it is put into operation first Menu points Authoriz
94. for technical messages 1 TECH MSG 0005 011 lt zone textl1 gt lt element text gt Figure 9 Example for the display of a technical message from detector zone 5 detector Nr 11 Has no element text been programmed the second line of the zone text if available is displayed E In this case the I button has a special function The detector zone whose technical message is cur rently displayed is disabled by using this button Displaying fault messages menu point Faults Scroll through all current faults by using the TL buttons details see from page 58 in Chapter 5 5 Fault message condition 1 ACTU FLT 0003 018 2 ENERGY FAULT lt actuation text15 stand by battery lt actu element text gt Figure 10 Example for the display of faults Left figure Display of a fault of actuation Nr 3 element Nr 18 Has no element text been pro grammed the second line of the actuation text if available is displayed Right figure Energy fault fault of the stand by battery In addition to the fault cause the name and number of the concerning BCnet sectional control panel GSSnet member number are displayed if the fault of a part of a BCnet sectional control panel of the network fire detection control panel BCnet216 is reported Faults that are detected by the control panel itself e g a fault of the function of a part of the control panel as well as faults that are transmitted to the control p
95. g the chosen filter with the W button the most recent event is displayed with its running number Now you can scroll forward or backward in the event memory by using the T buttons The event with the number 001 is always the oldest event kept in the event memory An overview of all possible event texts can be found starting page 68 in Chapter 7 Event memory entries An example for the display of an alarm ALARM 0001 016 lt zone textl1 gt lt element text gt 234 Figure 14 Display of the event memory entry here Nr 234 of an alarm of the detector zone 1 detector Nr 16 Has no element text been programmed the second zone text if available is displayed To gain space for the running number the information displayed in the third line here the element text is shortened to 16 characters for displaying E By pressing the Info button date and time of occurrence of the event and depending on the kind of event extended event texts as well as the GSSnet member number are displayed on the LC display Menu point System In this menu point you can get a read out and modify settings of different system information as de scribed in the following With the fire detection control panel BCnet216 all menus related to date and time can be called on the BC net sectional control panel defined as main operating unit only All clocks of other BCnet sectional control panels are permanently synchronized with the ti
96. he fire detection control panel ccc cece cece ene een eens 31 Silencing the internal buzzer display test cece cee eee een aaa 31 Silencing the primary alarming device 0 cece cece cece cee e eee n ence anes 31 Alarm delay procedure of the primary transmitting device 0 eee eee 32 Operations using the MENU 2 4k eee cece GA GANANG 33 Menu quick operation cece ce cece cece nnn eee NG GA GANANG 33 Exiting the MENU 2 pa nk GG ANDA hand a ea a hhmm lata 34 Overview of the display and operation menus 0 cece cece cece eee eee eee 34 Entering and exiting authorization level 2 aaa aaa 36 Entering and exiting authorization level 3 aaa aaa 36 Description of the menu points aika 37 471 4 7 2 4 7 3 4 7 4 4 7 5 4 7 6 4 7 7 4 7 7 1 4 7 7 2 4 7 8 4 7 8 1 4 7 8 2 4 7 9 4 7 10 4 7 11 4 7 12 4 7 12 1 4 7 12 2 4 7 12 3 4 7 12 4 4 7 12 5 4 7 12 6 4 7 12 7 4 7 12 8 4 7 12 9 4 7 12 10 4 7 12 11 4 7 12 12 4 7 12 13 4 7 12 14 4 7 13 4 8 5 5 1 5 2 5 2 1 5 2 2 5 2 3 5 2 4 5 2 5 5 3 5 3 1 5 4 5 4 1 5 4 2 5 5 5 6 5 7 6 6 1 User Manual Series BC216 Part A Displaying fire alarms menu point Alarms 0 ce cee cece eee eee eens 37 Displaying activated actuations menu point Activated actuations 38 Displaying technical messages menu point Technical message
97. he first alarming de tector in an interdependence of two detectors A pre alarm is displayed on the LC display as PRE AL Further information can be found starting page 55 in Chapter 5 2 5 Fire alarm condition spe cial case alarm in an interdependence of two detectors 38 4 7 2 4 7 3 4 7 4 4 7 5 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A Displaying activated actuations menu point Activated actuations Scroll through all activated actuations by using the TL buttons details see from page 55 in Chapter 5 3 Activation condition of actuations Note that activations of transmitting devices and of alarming devices are displayed as activated actuations as well 1 TR DEV ACT 01 3 ACTU ACT 0001 lt transm dev text1 gt lt actuation text1 gt lt transm dev text2 gt lt actu element text gt 1 ALARM 0003 029 1 ALARM 0003 029 Figure 8 Examples for the display of an actuation activation Left figure Transmitting device Nr 1 is activated as the first actuation Right figure Actuation Nr 1 is activated as the third actuation Has no element text been pro grammed the second line of the actuation text if available is displayed Displaying technical messages menu point Technical messages Scroll through all current technical messages by using the TL buttons details see from page 56 in Chapter 5 4 Message condition
98. hin a short time e g 2 minutes after the activation of the first detector the first detector is reset automatically by the control panel The activation of the first detector is shown on the LC display as pre alarm Us ing the fire detection control panel BC216 1 or when using the fire detection control panel BCnet216 in each of BCnet sectional control panels also more than two detectors can be combined to a multiple detector dependency still called interdependence of two detectors for simplicity HB216AE SAM 0130 AN9161202 ZN5002 73 12 User Manual Series BC216 Part A Chapter 1 e Introduction 13 HB216AE SAM 0130 AN9161202 ZN5002 73 13 Loop Ring shaped wiring with bi directional data bus to connect intelligent fire detectors e g sensors detectors and actuation devices to the fire detection control panel A wire breakage in the loop leads to a fault display on the control panel but does not affect the functions of the connected de vices Isolation elements limit the effect of a short circuit in the wiring so that a short circuit will either have no effect at all or impair only one or a few devices Main operating unit The operable BCnet sectional control panel of a fire detection control panel BCnet216 which be sides supervising the fire detectors etc also realizes network administration of a GSSnet All events of the fire detection control panel BCnet216 are basically displayed on the main operating unit and
99. his condition as soon as possible Also note the warning hints starting page 61 in Chapter 5 6 Disablement condition N Detection zones in test condition cannot transmit an alarm to the fire brigade the alarming devices and The test condition is displayed on the control panel as follows e The yellow light emitting diode Test condition is illuminated e The menu jumps automatically to the menu point Test conditions 30 seconds after any button was pressed last if no event of higher priority is currently on the control panel The first line of the LC display shows the first zone that has been put in test condition The second and third line display additional text e g a zone or an element specific text for the test procedure displayed in the first line The fourth line is reserved for displaying fire alarms The test procedures are numbered in the order of their execution 1 TECH TEST 0003 005 lt zone textl1 gt lt element text gt Figure 22 Display in test condition Element Nr 5 of the detector zone for technical messages Nr 3 is displayed as the first executed test procedure The second and third line display text information on the displayed test procedure Has no element text been programmed the second line of the zone text if available is displayed The fourth line is reserved for fire alarm messages 64 Chapter 5 Operating conditions of fire detection control panels Series BC216 User Manual Series BC216
100. howing the earliest event with the highest level of priority no matter what event was displayed last e The red illuminated display ALARM indicates the condition of a fire alarm Every message from a fire detector that is evaluated by the fire detection control panel BC216 1 or BCnet216 as fire alarm activates this display and keeps it illuminated until all alarms have been reset e The yellow illuminated display FAULT indicates the condition of a fault Every message from a fault detector or fault evaluated by the fire detection control panel BC216 1 or BCnet216 as a fault activates this display and keeps it flashing until no fault is left e The green light emitting diode POWER indicates the sufficient supply of energy to the fire detec tion control panel BC216 1 or the corresponding BCnet sectional control panel of the BCnet216 E With the fire detection control panel BCnet216 area filters can be set by the installer for every BCnet sectional control panel through which only certain messages are processed and displayed on the BCnet sectional control panel Basically all messages are processed and displayed on the BCnet sectional control panel defined as main operating unit If the light emitting diode POWER is not illuminated you have to assume that the control panel or the BC net sectional control panel is not able to receive evaluate and transmit messages of detectors due to a total loss of power i e the mains power as well as
101. ic code user code on the keypad of the control panel in authorization level 1 This ensures that only persons who are authorized by the user can enter this level of authorization E Different user codes can be programmed for single operable BCnet sectional control panels of a net work fire detection control panel BCnet216 By entering authorization level 2 various important parts of the system such as e g transmitting devices actuations etc can be put out of operation automatically depending on regional regula tions and restrictions Due to this do not stay in authorization level 2 longer than needed for operation Return to authorization level 1 immediately after completing the task so that the disabled parts can be put into operation again 30 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A By confirming the menu point Exit authorization authorization level 2 is left Has no operation occurred for 15 minutes the control panel returns to authorization level 1 automatically The numeric code for authorization level 2 user code is set by the installer of the fire detection system together with the user Has the code been forgotten the installer in authorization level 3 can set a new code for authorization level 2 It is impossible to get a read out of a forgotten code on the control panel E This user code has to be accessible to the safety personnel fire
102. ic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A E With the possibility to reactivate the primary alarming device you can repeat a prematurely inter rupted evacuation alarm of a building without activating a new alarm as long as the fire alarm is still displayed on the control panel After resetting the fire alarm the repetition of the evacuation alarm is only possible by renewed activation of an alarm E All other alarming devices are operated exclusively by the use of the menu Further operating functions for the primary alarming device e g disablement are possible by the use of the menu See from page 43 in Chapter 4 7 10 Displaying and operating alarming devices menu point Alarming device E Note the difference between silencing and resetting which are valid only for the current event and disablement which is an enduring condition terminated only by the enablement of a part of the sys tem e g an alarming device Alarm delay procedure of the primary transmitting device If there is no current fire alarm you can switch the corresponding primary transmitting device between day operation light emitting diode Alarm delay is illuminated and night operation light emitting di ode Alarm delay is not illuminated by pressing the button Alarm delay Explore During night operation an incoming alarm message activates the corresponding primary transmitting device immedia
103. in test condition in the menu point Test conditions you can directly disable the displayed parts of detector zones actuations and alarming devices being in test condition by using the button e Enablement of disabled parts of the system If you are displaying the currently disabled parts of the system in the menu point Disablements you can enable the displayed part of the system by using the button e Direct entering of the desired condition After selecting a part of the system you can directly set the desired condition by entering a number without using the menu The meaning of the numbers is uniform e g O for disable 1 for en able etc but not all possible inputs are available in every menu point Exiting authorization level 2 By pressing the button esc repeatedly how often depends on the point of the menu you are cur rently in you arrive directly at the menu point Exit authorization which you confirm by press ing the I button E Note for all the above points that for any change in conditions the minimum requirement is authoriza tion level 2 Exiting the menu Basically you exit the menu by confirming the menu point Exit authorization with the button The control panel returns to authorization level 1 automatically 15 minutes after a button was pressed last in authorization level 2 independent of the menu point in which a button was pressed last The control panel returns to displaying th
104. ions in standardized form and thus enables the fire brigade to coordinate the necessary procedures efficiently e Fire control system Fire protection systems or other equipment e g ventilation fire doors automatic gas extinguishing systems elevators that will be activated automatically in case of fire e Fire detector automatic Automatic fire detectors test continually or periodically the presence of one or more signs of fire Automatic fire detectors differ by the kind of signs they are observing such as smoke heat flame etc e Fire detector non automatic Non automatic fire detectors are designed to be activated manually Usually a simple mechanical safeguard e g a pane of glass is used in the manual call point has to be removed before the fire detector can be activated GSSnet member The Global Security System GSSnet consists of the single components of the system and the failure safe redundant data line which combines the components to one unit All system components such as BCnet sectional control panels remote display and operating units gateways etc connected to this data line are named GSSnet members Each GSSnet member is assigned a GSSnet member number during putting the system into operation Interdependence of two detectors Measure to verify an alarm The state of alarm is only attained after two fire detectors of the same detector zone have detected signs of fire Is the second detector not activated wit
105. irectly to one or more of the applied BCnet sectional control panels or via gateways to the network The stated devices can basically be connected to every BCnet sectional control panel The operation of these devices is independent from which BCnet sectional control panel it is connected to and is made via one or more therefore parameterized operable BCnet sectional control panels BC216 2 HB216AE SAM 0130 AN9161202 ZN5002 73 16 User Manual Series BC216 Part A Chapter 2 e Fire detection control panel Series BC216 17 HB216AE SAM 0130 AN9161202 ZN5002 73 17 2 3 2 3 1 Basically all fire detectors and other devices that may be connected to a stand alone control panel of type BC216 1 may also be connected to every single of these BC net sectional control panels see from page 15 in Chapter 2 1 Typical construction of a fire detection system with control panel BC216 1 The operation of the network control panels by the user is made as usual like with a one case fire detection control panel Either the whole control panel can be operated via one or more display and op erating units of BCnet sectional control panels or via remote display and operating units or only parts of the whole system can be operated by the display and operating units depending on the requirements In none of the different possibilities the user will recognize that in reality the control panel consists of several components spread over a wide range of space
106. lay the programmed zone and the element specific text for the alarm displayed in the first line The alarms are numbered in the order they are received on the con trol panel 1 ALARM 0003 029 1 ALARM 0003 029 lt zone text1 gt lt zone text1 gt lt element text gt lt element text gt 1 ALARM 0003 029 6 ALARM 0015 123 Figure 16 Display of a fire alarm condition of the control panel Left figure Just one alarm Nr 1 detector zone 3 detector Nr 29 is present This alarm is displayed as the first as well as the last alarm Right figure Six alarms are present The last received alarm Nr 6 is displayed in the fourth line of the LC display The displayed texts always refer to the alarm displayed in the first line Has no element text been programmed the second zone text if available is displayed instead Provided that the parameters of the primary transmitting device have been set in a way that the cause of the current alarm is a reason for automatic transmission of the alarm to a designated alarm respondent e g the fire brigade the red light emitting diode Activated in the field TRANSM DEVICE 1 is illuminated E Is the alarm delay procedure activated the yellow light emitting diode Alarm delay in the field HB216AE SAM 0130 AN9161202 ZN5002 73 51 TRANSM DEVICE 1 flashes during exploration time the transmitting device is Activated only after the lapse of the exploration time or a
107. ll detectors of a detector zone this is displayed as a disablement of the whole de tector zone E During maintenance of the system detectors are set to test condition so that the detectors can be tested on their function without activating a fire alarm See from page 65 in Chapter 6 1 2 Testing of detec tors By disabling and then enabling the detector you end the test condition of this detector HB216AE SAM 0130 AN9161202 ZN5002 73 40 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 41 HB216AE SAM 0130 AN9161202 ZN5002 73 41 4 7 8 4 7 8 1 If the function measured value maintenance is selected the LC display shows the measured value at the time of function selection of this detector Also displayed is the time that the detector presumably will work reliably without maintenance at stable environmental conditions Zone 0001 016 Meas val maint 125 gt gt 12 Figure 13 Display when selecting the function Measured val Maint for detector Nr 16 of zone 1 The left side of the third line displays the current measured value of this detector the right side dis plays the time in months that the detector will function without maintenance The function Measured val Maint does not disable the corresponding detector An alarm criterion of the detector is processed in the control panel in normal ways Displaying and operating actuations m
108. lt message condition 58 Fire alarm condition 50 Normal condition 50 Priority 49 Technical message 56 Test condition 63 Operation menu 33 34 Optional case 18 Organization in case of an alarm 9 13 Panel reset 31 54 57 Button 25 Power supply 18 Energy fault 25 Total shut down 23 Pre alarm 13 55 Display 37 Primary alarming device 13 Primary transmitting device 13 Print out 46 Measured value 46 Repeat 47 Service 46 Settings 46 Printer 18 21 27 46 Out of paper 28 Printer filter 27 46 Protocol printer 27 47 Reaction time 32 Reconditioning 67 Remote maintenance 18 Sectional control panel 11 17 19 29 Operable 22 Self control 10 58 65 Serial interface 18 21 Setting the parameters 13 Signs of fire 13 Siren output 26 HB216AE SAM 0130 AN9161202 ZN5002 73 72 User Manual Series BC216 Part A Software version 8 46 Specifications 67 Stand by battery 18 65 Disposal 65 Standards 10 System fault 10 25 Technical message 49 56 Display 38 Light emitting diode 25 Reset 57 Self holding 57 Self resetting 57 Test condition 63 65 Display 39 Light emitting diode 25 Timer 18 26 32 Transmitting device 13 17 Day night operation 32 Display 42 For fault messages 25 For fire alarm 13 25 Number 20 Operate 42 Primary 14 25 26 Two zone dependency 42 Two zone dependenc
109. m condition of the control panel already is attained with the alarm of the first detector A detector zone is removed automatically from a two zone dependency if it is disabled or has a fault AN until the fault or the disablement is terminated Have the parameters of the two zone dependency been set for just two detector zones the disablement or the fault of one of these detector zones prevents the second detector zone from activating the actuation Message condition for technical messages Technical messages inform on the control panel about devices that do not directly belong to the fire de tection system but are important for fire protection The devices for technical messages e g about fire doors fire dampers smoke escapes etc are combined to zones and wired to the control panel similar to fire detectors But they do not cause an alarm or fault display on the control panel The message condition for technical messages is displayed on the control panel as follows e The yellow light emitting diode Technical message is illuminated HB216AE SAM 0130 AN9161202 ZN5002 73 56 User Manual Series BC216 Part A Chapter 5 e Operating conditions of fire detection control panels Series BC216 57 HB216AE SAM 0130 AN9161202 ZN5002 73 57 5 4 1 5 4 2 e The internal buzzer is sounding constantly You can silence the internal buzzer by using the button Silence buzzer The buzzer is activated again by each further received
110. made that would demand a change in the fire de tection system Make sure that the installed devices and wiring are not damaged A space of 0 5m has to be kept clear below fire detectors to ensure the proper functioning of the de tectors Manual call points have to be freely accessible at all times Make sure that all action data e g fire prevention plans are available in their latest edition for use in case of emergency E Should you find problems or have doubts during a test of your fire detection system inform your maintainer HB216AE SAM 0130 AN9161202 ZN5002 73 66 User Manual Series BC216 Part A 6 3 Reconditioning and maintenance Chapter 6 Ensuring the efficacy of the system by the user 67 Parts of the system that have a fault are not able to perform their functions efficiently or at all There fore have faults repaired as soon as possible by a qualified and authorized company preferably the one that performs the periodic maintenance of your system Fire detection systems have to be serviced and if necessary reconditioned periodically by a qualified maintainer Only specialized companies that are demonstrably periodically trained specifically for the functions of this specific fire detection system by LST or by persons being explicitly authorized by LST A fire detection system that has not been serviced at all or not competently may not be able to fulfill its purpose to detect a fire reliably and f
111. mat hhmm The seconds are set to O after confirming the settings by using the button The quartz clock has an additional power reserve of approximately 10 minutes in case of a total shut down of the power supply The set switching times of the alarm delay timer and the dates for shifting between summer and wintertime are conserved indefinitely also at a total shut down of the power supply Setting the date submenu point Date setting This menu point is only accessible to the installer i e only in authorization level 3 The installer sets the date in this menu point in the format ddmmyyyy when the control panel is put into operation first Switching to summertime submenu point Winter summertime You can enter the date for the automatic switch to summertime in this menu point When first put into operation or if no switch is desired the LC display shows after confirming this menu point Now you can enter the desired switching date in the format ddmmyyyy and confirm it by pressing I In case of an error you can erase your input by using the esc button and begin with enter ing the date again The entered date is checked for formal correctness If the date is invalid a fault mes sage is displayed The switch to summertime takes place on the set date at 02 00 o clock E If you did not set the switching date in time you can set it to yesterday for example The clock will switch to summertime immediatel
112. mbers are no longer connected to the main operating unit and therefore can no longer be attended by it E With multiple line faults of the network cable the whole circular network will be separated into iso lated segments If the fire detection control panel BCnet216 consists exclusively of operable BCnet sectional control panels even with such multiple line faults each of the separate segments stays fully operatable In this case the BCnet sectional control panel with the lowest member number in the seg ment becomes the main operating unit of this segment Please retrieve the corresponding hints from the engineering data of your fire detection system Disablement condition The disablement condition is an intentional condition of a fire detection system in which the system or parts of it are taken out of operation By disabling a part of the system or a function the corresponding part or function is put out of opera tion Therefore disable parts of the system only in exceptional cases and make sure that these parts are A not kept disabled longer than necessary A disabled detector zone that is part of a two zone dependency of an actuation a transmitting device or an alarming device is removed from the two zone dependency Have the parameters of the two zone dependency been set for just two detector zones one of which is disabled the devices that ought to be activated cannot be activated by the two zone dependency in case of fire If in
113. me an earthing can cause the fault condition and a disabled detector zone can cause the disablement condition Since not all operating conditions can be displayed at the same time priorities are set for displaying fire alarm condition highest priority activation condition of actuations message condition for technical messages fault condition disablement condition test condition lowest priority 0 9 9 9 E Of course the powerful microprocessor systems used in the fire detection control panels Series BC216 are capable of processing all information virtually at the same time The above list of priorities applies only to the displaying of information not to their processing In addition to their display on the LC display the current operating conditions are indicated by using light emitting diodes on the display and operating unit of the control panel Does an event of higher priority occur the control panel will change to the corresponding event menu automatically You can browse in the menu at any time by using the lt buttons and thereby display events of lower priority as well By using the entries of the event memory you can display events on the LC display that have been terminated in the meantime e g a temporary fault of a part of the system 50 5 1 5 2 Chapter 5 e Operating conditions of fire detection control panels Series BC216 User Manual Series BC216 Part A E By using the TL buttons y
114. me of this BCnet sectional control panel Read out of the event counter submenu point Event counter You can display the number of alarms that have triggered an activation of a primary transmitting device or a transmitting device for fire alarms since the fire detection control panel BC216 1 or all BCnet sec tional control panels of a fire detection control panel BCnet216 were first put into operation If the cor responding transmitting device is already activated no further alarms are counted BC net sectional control panels which were limited to a part of the whole fire detection system by an area filter during commissioning will only count alarms which originated from that part E The event counter alarm counter cannot be reset Testing the optic and acoustic displays and the buzzer submenu point Display test In this test the buzzer the LC display and all light emitting diodes are activated Thereby you can check easily if all displaying elements work The same functions are executed by pressing the button Silence buzzer See from page 25 in Chapter 3 6 Reset buttons Setting the contrast submenu point LCD contrast Using the buttons you can set the contrast of the LC display in 10 steps according to the position ing of the control panel viewing angle and to local light conditions Minimum requirement for this submenu point is authorization level 2 HB216AE SAM 0130 AN9161202 ZN5002 73 44 Use
115. messages of corresponding de tectors have arrived See page 56 in Chapter 5 4 Message condition for technical messages Disablement yellow Is illuminated if one or more parts of the system or functions are disabled See page 61 in Chapter 5 6 Disablement condition Test condition yellow Is illuminated if one or more detector zones or elements are in test condi tion See page 63 in Chapter 5 7 Test condition Energy fault yellow Is flashing in case of a fault in the power supply power unit stand by bat tery etc See page 58 in Chapter 5 5 Fault message condition e System fault yellow Is flashing in case of a fault in the central computer it is illuminated in case of a fault of the display and control panel computer In order to maintain the most important functions of the control panel or the BCnet sectional control AN panels in case of malfunctions of single parts of the control panel the manufacturer has included elaborate security measures that were developed during many years of experience with fire alarm tech nology Nevertheless a total guarantee for the proper workings of the control panel cannot be given especially if two or more faults occur simultaneously Observe the Hints given from page 9 in Chapter 1 2 2 What to do in case of a fault from page 58 in Chapter 5 5 Fault message condition and from page 67 in Chapter 6 3 Reconditioning and maintenance e Authorization gr
116. n ACTU ACT T 0001 001 actuation text 1 actu text2 element text Automatic disablement by ACTU DIS 0001 001 actuation text 1 actu text2 element text authorization Automatic enablement by ACTU ENA 0001 001 actuation text 1 actu text2 element text authorization Disablement ACTU DIS 0001 001 actuation text 1 actu text2 element text Enablement ACTU ENA 0001 001 actuation text 1 actu text2 element text Fault ACTU FLT 0001 001 actuation text 1 actu text2 element text fault cause Fault termination ACTU FLT T 0001 001 actuation text 1 actu text2 element text fault cause Test activation ACTU TEST 0001 001 actuation text 1 actu text2 element text Test activation termination ACTU TEST T 0001 001 actuation text 1 actu text2 element text Transmitting devices Activation TR DEV ACT 01 transmitting device text 1 transmit device text 2 Activation termination TR DEV ACT T 01 transmitting device text 1 transmit device text 2 Automatic disablement by TR DEV DIS 01 transmitting device text 1 transmit device text 2 authorization Automatic enablement by TR DEV ENA 01 transmitting device text 1 transmit device text 2 authorization Confirmation TR DEV CONF 01 transmitting device text 1 transmit device text 2 Confirmation termination TR DEV CONF T 01 transmitting device text 1 transmit device text 2 Delay activated DELAY ACT 01 transmitting device
117. n on the locality of every one of them If the displays FAULT or Disablement are illuminated you have to find out which parts of the system are affected and start alternative measures if necessary N Parts of the system e g actuations that are disabled or have a fault cannot cope with their assigned HB216AE SAM 0130 AN9161202 ZN5002 73 53 tasks 54 5 2 2 5 2 3 5 2 4 Chapter 5 e Operating conditions of fire detection control panels Series BC216 User Manual Series BC216 Part A E Starting at the display of alarms you can scroll to the main menu points Faults and Disablements by using the lt buttons In these menu points you can scroll through the events by using the TL buttons Determine either by yourself or through other qualified persons the actual potential for danger in the locations where a fire has been detected All further actions result from the above point and are not dealt with further in this User Manual E For all operations explained here authorization level 1 is sufficient which means that you do not have to enter a numeric code Resetting the alarming devices You can reset the primary alarming device by pressing the button On off located in the field ALARM DEVICE 1 See from page 26 in Chapter 3 9 ALARM DEVICE 1 field After receiving a new alarm or after pressing this button again the alarming device can be reactivated depending on local in stallation regula
118. n time In addition specific organizatorial The delay times are often regulated exactly by local or country specific directives Typical values are Zu d r measures are often mandated as well tors in interdependence of two detectors and from automatic extinguishing systems are transmitted to N Alarm messages originating from manual call points from detectors in two zone dependency detec the fire brigade without delay even if the alarm operation is activated For switching between day and night operation authorization level 2 is needed exploring can be ac tivated in authorization level 1 as well This switch can be influenced by the internal timer of the control panel The timer with weekly pro gram releases a time window in which the user can switch between day and night operation as he likes Outside this time window the timer switches directly to night operation and fixes this condition The switching times are entered on the control panel by the installer when putting the control panel into operation HB216AE SAM 0130 AN9161202 ZN5002 73 32 User Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 33 HB216AE SAM 0130 AN9161202 ZN5002 73 33 4 3 4 3 1 E By exception of the primary transmitting device all other transmitting devices are operated exclusively by the use of the menu Only the primary transmitting device is equipped with an alarm delay proce
119. nd displayed on the LC display The displaying and operating elements have following functions e Activated red Is illuminated if the primary alarming device is activated e Fault Disabled yellow Is flashing in case of a fault of the primary alarming device or its wiring it is illuminated in case of its disablement On off button The primary alarming device e g siren is silenced by pressing this button In case of a new alarm or by pressing the button again if the alarm is still current the alarming device can be reactivated and can be silenced in the same way this repeating function is dependent on local re quirements The button On off is not assigned for general disablement of the alarming devices HB216AE SAM 0130 AN9161202 ZN5002 73 26 User Manual Series BC216 Part A Chapter3 e Displaying and operating elements 27 HB216AE SAM 0130 AN9161202 ZN5002 73 27 3 10 3 11 3 12 this is only possible by the use of the menu see from page 43 in Chapter 4 7 10 Displaying and operating alarming devices menu point Alarming device The displaying and operating elements of the field ALARM DEVICE 1 are out of function if the su pervised siren output of the fire detection control panel has not been parameterized as alarming device Optional LED display field The optional LED display field LED display field LAB48 1 consists of 48 red and 48 yellow light emitting diodes working in pairs
120. nd limited to the corresponding surveillance area Optionally the activation of a transmitting device can be constructed so that even with a double fault in the network cabling no im pairing of the function occurs Connection of the BC net sectional control panels to the network is made by one of the serial interfaces built into the sectional control panels Up to 127 GSSnet members i e BCnet partial control panels remote display and operating units gateways etc can be connected to the network The line length between two neighbouring GSSnet members may be up to 1200m for larger distances repeaters can be interposed Up to 9699 detector zones 9699 actuations 99 transmitting devices and 99 alarming devices can be managed in a network fire detection control panel BCnet216 Peripheral devices for the fire detection control panel Series BC216 In a fire detection system a series of peripheral devices such as fire detectors sirens transmitting de vices displaying devices etc are used which are activated and or monitored by the fire detection con trol panel Detectors Fire detectors of a fire detection system are combined locally to fire protective efficient detector zones and connected to the fire detection control panel BC216 1 or to the BCnet sectional control panels of a fire detection control panel BCnet216 The location of fire is identified by the zone number s dis 20 24 2 2 4 3 Chapter 2 e Fire detection control pan
121. ne respectively an element specific text for the fault displayed in the first line The fourth line is reserved for displaying fire alarms The faults are numbered in the order of their occurrence 1 FAULT 0011 029 1 FLT ALARM 0012 028 lt zone text1 gt lt zone text1 gt lt element text gt lt element text gt Figure 20 Examples of displays in fault condition Left figure Element Nr 29 in detector zone Nr 11 is displayed as the first received fault message Right figure The activation of fault detector Nr 28 in detector zone Nr 12 is displayed as the last fault alarm The second and third line show text information on the displayed fault Has no element text been pro grammed the second line of the zone text if available is displayed The fourth line is reserved for fire alarm messages Have the parameters been set to transmit the current fault to a transmitting device for fault mes sages the red light emitting diode Actuation activated is illuminated to indicate that the transmit ting device has been activated HB216AE SAM 0130 AN9161202 ZN5002 73 58 User Manual Series BC216 Part A HB216AE SAM 0130 AN9161202 ZN5002 73 59 Chapter 5 e Operating conditions of fire detection control panels Series BC216 59 e Ata fault in the primary transmitting device or the primary alarming device the corresponding yel low LED displays are flashing Ata fault in the power supply the yello
122. nnected sequences are combined into simple operations The experienced user can execute the most important operations very fast without having to scroll through every single menu point by using the menu quick operation The supervised connection of two independent transmitting devices for connecting the fire detection system to a designated alarm respondent e g the fire brigade and to a country specific fire brigade control unit the optional Fire Brigade Interface is to be used 18 Chapter 2 e Fire detection control panel Series BC216 User Manual Series BC216 Part A In case of an alarm the user can explore the possible danger prior to the transmission of the fire alarm to the fire brigade by using the alarm delay procedure with deadman s handle The standard built in INFO bus makes the connection of a fire brigade control unit and of display de vices transmission devices for remote indication units and of other information devices using wire saving technology possible A 32 bit high performance microprocessor system together with additional extra auxiliary micro processors on the componentries is operated by a special real time multi tasking operating system and together with redundant logic for processing provides clarity and security Open parameters of the control panel parameters of detectors and modules as well as display texts outputs and interfaces to peripheral devices emphasize the universal flexibility of the control pan
123. ns and numbers for the menu quick operation are stated in the following sections By using the esc button you are returning to the next higher point of the menu Menu quick operation Some frequently used operations can be accessed directly by using shortcuts in the structure of the menu e Input of the numeric code for authorization level 2 As long as a numeric input is made in a main menu point of authorization level 1 it is evaluated as 34 4 3 2 4 4 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A the beginning of a code and leads you straight to the menu point Authorization code This hap pens also if you are in a display menu point such as e g the display of current fire alarms This menu quick operation can not be used while you are viewing the event memory Selection of a detector zone If you are in a main menu point of authorization level 2 or 3 that does not require a numeric input any numeric input is evaluated as an input of a detector zone and leads you to the menu point Zone Disablement of a detector zone being in alarm condition If you are displaying the current alarms in the menu points Alarms Technical messages or Faults you can directly disable the displayed detector zone by using the W button Disablement of parts of the system being in test condition If you are displaying the parts of the system that are currently
124. nter summer CLOCK TIME SHIFT Winter summer Shifting summer winter CLOCK TIME SHIFT Summer winter Fault messages for BCnet216 Network fault GSS N FLT 002 No communication Member fault MEMB FLT 001 fault cause Checksum error Configuration FEPROM FAULT Param setup fault cause FEPROM Configuration RAM FAULT Parameter setup fault cause RAM Programme memory FAULT Software fault cause Settings FEPROM FAULT Sys settings fault cause FEPROM Settings RAM FAULT System settings fault cause RAM Table 7 List of event memory entries The actual entries in the event memory depend on the country specific specifications of the control panel You can set a filter for reading the event memory See from page 43 in Chapter 4 7 11 Menu point Event memory At events which relate to a specific BCnet sectional control panel e g ENERGY FAULT the third line of the LC display shows the GSSnet member number of the corresponding BCnet sectional con trol panel when using a network fire detection control panel BCnet216 HB216AE SAM 0130 AN9161202 ZN5002 73 71 72 Chapter 8 e Index 8 Index Activation condition of actua tions 55 Actuation 21 Display 38 41 Light emitting diode 25 Operate 41 Two zone dependency 56 Alarm counter 44 Alarm delay 18 Alarm delay procedure 11 32 Button 26 Day night operation 32 Day night operation 26 Delay time 12 Exploration time 32 53 Reaction time
125. of the control panel and the connected fire detectors for service and maintenance purposes You select one of the print out possibilities below Confirmation by pressing starts the print out IN With the fire detection control panel BC216 1 the print out possibilities relate to the data of the whole control panel with the network fire detection control panel BCnet216 to the data of the BC net sec tional control panel to which the printer is connected Exceptions are print outs for which a print out range can be entered in these cases the print out range can include several BC net sectional control panels or even the entire control panel Service print out Service print out prints a list of the event memory contents The last occurred event is printed first Depending on the setting of the parameters of the printer interface either all events are printed or just the events of the detector zones or just the events of the basic control panel The print out lines are numbered by the numbers of the event memory Further information can be found in the Chapter Setting the parameters of the interfaces in Part C of this User Manual e Settings print out Settings print out clearly and concisely prints the parameters of the fire detec tion control panel BC216 1 or of the BC net sectional control panel of a fire detection control panel BC net216 to which the printer is connected The succession of the parameters on the print out is the same as
126. ommand Activate is a real activation Be Menu point Event memory The fire detection control panel Series BC216 saves every detected event of the fire detection system in an event memory with a capacity of 500 events The oldest event will be overwritten The contents of the event memory are saved in non volatile semi conductor memories and are conserved like all other parameters of the control panel in case of a total loss of the power supply for an unlimited time The events of the entire control panel filtered by the area filter set for the corresponding BC net sectional control panel are saved in the event memory of every operable BC net sectional control panel of a fire detection control panel BCnet216 E The most important entries in the event memory are begin and end of authorization occurrence and termination of alarms technical messages fault alarms faults of activations of zones elements and actuations of test conditions disablements alarm delay procedures of activations of transmitting de vices and of alarming devices 44 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A 4 7 12 4712 1 4 7 12 2 4 7 12 3 The event memory can be accessed by using the menu point Event memory You can set one of the possible filters Display all Control panel or Detector zones for the displaying of the events by the use of the TL buttons After confirmin
127. on trol panel itself is described starting page 29 in Chapter 4 Basic operation of the fire detection control panels Series BC216 and starting page 49 in Chapter 5 Operating conditions of fire detection control panels Series BC216 E For reasons of simplicity the BCnet sectional control panels of the fire detection control panel BCnet216 equipped with an display and operating unit are named operable BCnet sectional control panels in the following paragraphs of this chapter BC216 1 INFO field ALARM POWER mu INFO button Actuation activated oti O Technical message fO MENU buttons O Disablement t Jl gt LED summary displays gt rest condition PAY naka fault ua ELEMENT button O System fault 7 8 9 Authorization TRANSM DEVICE 1 4 5 6 Activated NUMERIC keys O Fault Disabled 1 2 3 TRANSMITTING DEVICE 1 field gt Mar delay Alarm delay Call fire brigade esc 0 O Confirmation Explore a ALARM DEVICE 1 T On off Silence buzzer Panel reset ALARMING DEVICE 1 field runona RESET buttons eo seo seo seo optional _ S LED display field eo seo so so eo o o Figure 4 Displaying and operating elements of the fire detection control panel Series BC216 HB216AE SAM 0130 AN9161202 ZN5002 73 22 User Manual Series BC216 Part A Chapter 3 e Displaying and operating elements 23 HB216AE SAM 0130 AN9161202 ZN5002 73 23 3
128. on TECH T AL 0001 001 zone text 1 zo text 2 element text Test activation termination TECH T AL T 0001 001 zone text 1 zo text 2 element text Test condition off TECH TEST T 0001 001 zone text 1 zo text 2 element text Test condition on TECH TEST 0001 001 zone text 1 zo text 2 element text Fault detector zones elements Activation FLT ALARM 0001 001 7one text 1 zo text 2 element text Activation termination FLT ALARM T 0001 001 zone text 1 zo text 2 element text Disablement FLT DIS 0001 001 zone text 1 zo text 2 element text Enablement FLT ENA 0001 001 zone text 1 zo text 2 element text Fault FLT FLT 0001 001 7one text 1 zo text 2 element text fault cause Fault termination FLT FLT T 0001 001 7one text 1 zo text 2 element text fault cause Test activation FLT T AL 0001 001 7one text 1 zo text 2 element text Test activation termination FLT T AL T 0001 001 zone text 1 zo text 2 element text HB216AE SAM 0130 AN9161202 ZN5002 73 68 User Manual Series BC216 Part A Chapter 7 e Event memory entries 69 Event Event text Text 2nd line Text 3rd line Additional text info button Test condition off FLT TEST T 0001 001 zone text 1 zo text 2 element text Test condition on FLT TEST 0001 001 zone text 1 zo text 2 element text Actuations Actuation elements Activation ACTU ACT 0001 001 actuation text 1 actu text2 element text Activation terminatio
129. ons Notice the statements made for authorization level 2 E In authorization level 3 the first three lines of the LC display are reserved for displaying the opera tions of setting the parameters Only the fourth line is used for displaying the latest alarm event By confirming the menu point Exit authorization authorization level 3 is left During exiting authorization level 3 the entered parameters are checked and adopted Have any parameters been changed the control panel will restart using the new parameters E Similar to when the button Panel reset is pressed all current alarms faults actuations etc are reset by restarting nd Einr ckung Different installer codes can be programmed for single operable BCnet sectional con trol panels of a network fire detection control panel BCnet216 No time limit is assigned in authorization level 3 The numeric code for authorization level 3 installer code is set by the installer himself and should be treated confidentially in his own interest Has the installer code been forgotten only the manufacturer of the fire detection control panel can reset the code to the initial value It is impossi ble even for the manufacturer to get a read out of a forgotten installer code on the control panel E Different installer codes can be programmed for single operable BCnet sectional control panels of a network fire detection control panel BCnet216 Authorization level 4 This authorization l
130. or zones or detectors are enabled the control panel checks for five seconds if crite ria for an alarm exist in this zone In such a case e g a non automatic fire detector has not been re set the enablement is rejected and the LC display shows Cannot be enabled or Cannot be enabled completely E Some special fire detectors may require special resetting procedures the authorized installer will in form you about them The fire alarm condition is terminated after you have reset all alarming detector zones and detectors By pressing the button Panel reset you reset all current fire alarms together with other displays at once By resetting all alarms and other displays at the same time you are deleting all entries in the event menus and thereby you lose the fast access to information on current events isting still Has for example the sign of fire not been reduced properly e g for smoke detectors by thoroughly ventilating a smoky room a new alarm is activated after resetting N When resetting with the button Panel reset no check is made to see if the local alarm situation is ex HB216AE SAM 0130 AN9161202 ZN5002 73 54 User Manual Series BC216 Part A Chapter 5 e Operating conditions of fire detection control panels Series BC216 55 5 2 5 Fire alarm condition special case alarm in an interdependence of two detectors Interdependencies of two detectors can be set during planning for exceptional local circumstan
131. ou can browse in an event category e g in all current alarms by using the lt buttons you can scroll to the previous or the next main menu point See from page 34 in Chapter 4 4 Overview of the display and operation menus 30 seconds after the last operation the LC display returns automatically to displaying the first event with the highest priority regardless which event you displayed last With the network fire detection control panel BCnet216 the event information is equally available on every operable BCnet sectional control panel Area filters however can be set by the installer for every BCnet sectional control panel except the main operating unit through which events of other BCnet sectional control panels are excluded from displaying and operating on the corresponding BCnet sectional control panel At least on the BCnet sectional control panel defined as main operating unit all operating conditions of the entire network control panel are visible Normal condition In accordance with its definition no event is currently on the control panel in normal condition This is the standard condition of every fire detection control panel It should be left only in exceptional cases and for a limited time Every condition other than normal condition indicates that an event is currently on the control panel or the control panel is not operating fully The normal condition is indicated by The illumination of only the g
132. ountry specific regulations during operating an operating unit e Area operating units are implemented besides the main operating unit These are designated for the operation of limited areas of the fire detection control panel e g limited on one floor of a build ing only The globally effective operating procedures e g by the button Panel reset however act on the whole fire detection control panel BCnet216 Please retrieve the information on which operating possibilities and operating restrictions are provided especially in your fire detection control panel from the engineering data of your fire detection system Operating authorization The whole operation and setting of parameters of the fire detection control panels Series BC216 is made in four hierarchically arranged levels of authorization according to international standards Authorization level 1 Admissible operations basically are restricted to displaying information and to silencing the built in buzzer No permanent modifications of conditions such as e g the disablement of a detector zone can be made in this level of authorization Anybody who has access to the keypad of the control panel has authorization level 1 Authorization level 2 The unrestricted operation of the fire detection control panel is possible The modification of site specific parameters is not possible in this level of authorization You enter authorization level 2 by entering a 4 digit numer
133. perations can be executed by the use of the menu For a few operations some special buttons are mandated by standards Also described is the operation of the fire detection control panel by using a connected fire brigade control unit No principle differences exist between operation possibilities via the key pad of the fire detection con trol panel BC216 1 and the network fire detection control panel BCnet216 At least one BCnet sec tional control panel with key pad exists in a control panel of type BCnet216 which was defined by the installer as main operating unit All operating actions on this main operating unit are the same as the operation of a compact control panel of type BC216 1 If a fire detection control panel BCnet216 consists of several operable BCnet sectional control panels the operating possibilities can be regulated differently depending on the corresponding application or country specific regulations Following combinations are provided e The main operating unit is the only operating unit which is active in normal condition All other op erating units are blocked Only after multiple line faults of the network lines have interrupted the connection of a BCnet sectional control panel to the main operating unit the operation of this sepa rated BCnet sectional control panel is automatically activated All operating units are of equal rank The operation of further units can still be partially or com pletely blocked depending on c
134. r Manual Series BC216 Part A Chapter 4 e Basic operation of the fire detection control panels Series BC216 45 HB216AE SAM 0130 AN9161202 ZN5002 73 45 4712 4 4 7 12 5 4 7 12 6 4 7 12 7 4 7 12 8 Correcting the clock time submenu point Clock time correction The built in quartz clock has an accuracy of a few seconds per year In case of higher deviations the time of the clock can be corrected by the maintainer during the periodic maintenance The user too can correct the time displayed on the LC display in normal condition for up to 10 minutes After entering the submenu the time to be corrected is displayed You can change the time by using the N buttons in steps of minutes Confirming the corrected time with the button the new time is ac cepted and the seconds are set to 0 When the time is corrected the control panel automatically calcu lates a correctional factor that optimizes the accuracy of the clock For reasons of safety the range of correction is limited to 10 minutes and can only be spent once in 7 days Minimum requirement for this submenu point is authorization level 2 Setting the clock time submenu point Clock time setting This menu point is only accessible to the authorized installer i e only in authorization level 3 To correct higher deviations of the clock time as when the control panel is put into operation first the installer sets the clock time in this menu point in the for
135. ration very carefully by competent and skilled technicians Changes in the use of rooms or HB216AE SAM 0130 AN9161202 ZN5002 73 8 HB216AE SAM 0130 AN9161202 ZN5002 73 9 User Manual Series BC216 Part A Chapter 1 e Introduction 9 1 2 1 1 2 2 in the expansion of the area surveilled require careful replanning and adaptation of the fire detection system The fire detection system has to be checked and maintained regularly at least once a year by trained and skilled personnel in order to maintain its functions and to avoid false alarms For planning installing modifying maintaining and servicing your fire detection system be o sure to commission only specialists who are demonstrably trained specifically for the functions of the fire detection control panel BC216 1 or BCnet216 by Labor Strauss Sicherungsanlagen bau Ges m b H Wien LST or by persons being explicitly authorized by LST The control panel has to be protected from moisture and damage of any kind It is to be installed in a dry and clean room easy accessible to the safety personnel The temperature has to be within the range of 5 C and 50 C For the fire detection control panel BCnet216 whose components are usually spread in the surveilled area these requirements are equally valid for all components of the control panel Do not use corrosive or abrasive cleaners for cleaning the case or the keypad use only mild household cleaners Water or other flui
136. rdependence of two detectors has detected signs of fire The pre alarm is shown on the LC display but usually no other signalling is taking place The pre alarm is either terminated automatically after a short while or turns into a fire alarm when a sec ond detector of the interdependence of two detectors is activated Primary alarming device See Alarming device Primary transmitting device See Transmitting device for fire alarm messages Reset An activated device e g an alarming device is returned to inactive condition by a reset this device will not be disabled permanently A reset device can be renewedly activated automatically by a new event e g a new alarm Setting of the parameters Setting of the site specific parameters on the fire detection control panel by the authorized installer when the system is put into operation or modified The user can not modify the parameters Signs of fire Changes in measurable conditions in the vicinity of an initial fire e g temperature Transmitting device for fire alarm messages Equipment for transmitting a fire alarm to a public fire report post e g fire brigade The fire alarm evaluated by the control panel is transmitted to the transmitting device which is usually mounted close to the control panel The transmitting device alarms the public fire report post by us 14 Chapter 1 e Introduction User Manual Series BC216 Part A ing proper equipment for transmission e g con
137. re brigade The activation of each transmitting de vice is dependent on logical combinations of the alarm activation of detector zones or of individual de tectors Thereby an alarm activated by a manual call point can be distinguished from one activated by an automatic fire detector for example at the transmission of the alarm information to the fire brigade Transmitting devices can also be set for the transmission of fault messages e g to a central fault re port post or for the transmission of technical messages Each transmitting device can be enabled and disabled individually The displaying and operating are described starting page 42 in Chapter 4 7 9 Displaying and operating transmitting devices menu point Transmit device The overall number of all transmitting devices is limited to 99 in a fire detection control panel BCnet216 HB216AE SAM 0130 AN9161202 ZN5002 73 20 User Manual Series BC216 Part A Chapter 2 e Fire detection control panel Series BC216 21 HB216AE SAM 0130 AN9161202 ZN5002 73 21 2 4 4 2 4 5 2 4 6 Actuations Practically any number of actuations can be activated by the fire detection control panels Series BC216 The activation of each actuation is dependent on logic combinations of the alarm activation of detector zones and of single detectors Actuations can be set for the case of fire fire control system as well as for faults and technical messages Fach actuation can be en
138. reen light emitting diode POWER while the control panel is in authorization level 1 e The date and time on the first line of the LC display If the control panel has been switched to authorization level 2 see from page 29 in Chapter 4 1 Oper ating authorization the second line of the LC display shows User level and the green light emitting diode Authorization is illuminated In authorization level 2 depending on regional regulations and re strictions important parts of the system e g transmitting devices actuations etc can be taken out of operation automatically In this case the control panel is no longer in normal condition but in disable ment condition See from page 61 in Chapter 5 6 Disablement condition Pay attention to the hints given starting page 36 in Chapter 4 5 Entering and exiting authorization level 2 03 05 2002 16 32 03 05 2002 16 32 User level Figure 15 Display in normal condition of the control panel Left figure authorization level 1 Right figure authorization level 2 Hints for operating the menu and for authorization are displayed by using the Info button The possi bilities for operations are explained starting page 29 in Chapter 4 Basic operation of the fire detection control panels Series BC216 E 15 minutes after a button was pressed last the fire detection control panel BC216 1 leaves authoriza tion level 2 automatically E With the network fir
139. riate menu point during putting the control panel into operation the control panel automatically recognizes the built in components as well as the external devices e g fire detectors and sets the setup for these parts to standard setup On the basis of the standard setup the authorized installer sets the parameters of the control panel using the site specific data e BCnet sectional control panel Part of a fire detection control panel BCnet216 which is installed in the surveilled area of the fire detection system and to which fire detectors among others are connected BCnet sectional control panels can either be equipped with an own display and operating unit and therefore be directly oper atable or without own display and operating unit to be operated only from another operable BCnet sectional control panel e g the main operating unit e Competent installer The company which is acquainted with local installation regulations has adequate experience in planning and building fire detection systems and whose technicians are periodically trained at least once a year by the manufacturer of the fire detection system and the fire detection control panel on the components of the fire detection system e Deceptive alarm A fire alarm activated by automatic fire detectors that react to signs that are similar to those of fire but are caused by other agents such as welding steam heat etc 12 Chapter 1 e Introduction User Manual Series BC21
140. rm Display 37 Terminate 54 What to do 9 52 Fire alarm condition 50 Fire brigade Information devices 21 key depot 21 key safe 21 Fire brigade control unit 12 17 21 Operation functions 48 Fire control system 12 15 21 55 66 Fire detector Automatic 12 Dirt message 19 Non automatic 12 Function test 65 Alarming device 66 Detector 65 Fire control system 66 Fire detection control panel 65 Other 66 Stand by battery 65 Transmitting device 66 GSSnet Line fault 61 Member 12 19 28 Member fault 61 Member number 28 Repeater 19 INFO bus 18 Info button 24 Installer 7 11 Installer code 30 36 At delivery 47 Change 47 Lost 30 Interdependence of two detec tors 12 Disabled detector 40 61 Fault of a detector 59 User Manual Series BC216 Part A Fire alarm condition 55 LC display 23 Adjusting the contrast 44 Illumination 23 LED display field 27 Loop 13 17 Main operating unit 13 29 44 Maintainer 13 Maintenance 9 13 63 67 Forecast 19 Maintenance prognosis 41 One man 63 65 Manual call point 12 15 Measured value Abort print out 46 47 Display 41 42 43 Print 46 Menu quick operation 33 Menu buttons 24 Network 19 Normal condition 23 50 Numeric keys 24 Operating authorization 29 Operating condition 49 Activation cond of actuations 55 Disablement condition 61 Fau
141. rs of the interfaces can be found in Part C of this User Manual 4 7 12 11 Repeating a print out submenu point Repeat print out Is a protocol printer connected to the fire detection control panel you can repeat the print out of the last events to reprint lost print outs e g in case of being out of paper or a printer fault with this menu point The repeated print out usually starts five events prior to the last alarm event but contains at least 20 and a maximum of 50 events After finishing the repeated print out the normal protocol print out is resumed without any loss This menu point is accessible in authorization level 1 4 7 12 12 Abort measured value print out submenu point Stop measurement print out A running measured value print out single print outs as well as periodical print outs can be aborted via this menu point the last printed line will be completed This menu point is accessible in authorization level 2 and higher 4 7 12 13 Modifying the numeric code for the user submenu point Change user code This menu point is only accessible to the installer i e only in authorization level 3 By entering a four digit numeric code twice the installer sets the code for the user See from page 29 in Chapter 4 1 Operating authorization With the fire detection control panel BCnet216 the user codes of the single BCnet sectional control panels can also be defined individually A common user code can be entered
142. s 38 Displaying fault messages menu point Faults aaa 38 Displaying disablements menu point Disablements 0 cece ee eee 38 Displaying test conditions menu point Test conditions 0 eee ee 39 Displaying and operating detector zones menu point Zone 004 39 Operating whole detector Zones 0 0 cece eee cece eee een ence awan anan 39 Operating single elements of detector zones 0 cece cece cnet eee ences 40 Displaying and operating actuations menu point Actuations 41 Operating ACUAHONS anan maana aNG LG NAG KANAN ANG BR LAN DONNA IRUN GG 41 Operating single elements of actuations aaa aan aaa eens 42 Displaying and operating transmitting devices menu point Transmit device 42 Displaying and operating alarming devices menu point Alarming device 43 Menu point Event memory 0 cece cece cece cee eee e cnet eee e ence en eenens 43 Men point System 2 2 207s0seehee se peetcanncet te NA AnG AP LJET ARA DONA Dhea Sede 44 Read out of the event counter submenu point Event counter 44 Testing the optic and acoustic displays and the buzzer submenu point Dis play testi aka isos Kaagad oe pele adda Kna HONDA Anne BAG PN ALENA Nana 44 Setting the contrast submenu point LCD contrast aaa aaa 44 Correcting the clock time s
143. s tem and their transmission to the primary transmitting device to the fire brigade usually to the primary alarming device and to the displays on the control panel will continue to work due to spe cial measures built into the system In this state of fault the control panel may not be able to distinguish between alarms of fire detector zones alarms of fault detector zones and technical alarms Every alarm message is evaluated as fire alarm message Further information on faults of the fire detection control panel are found from page 58 in Chapter 5 5 Fault message condition E Regular checks of the functions of the control panel and of the fire detection system by the person re sponsible for fire protection ensures proper functioning of the fire detection system See from page 65 in Chapter 6 1 Periodic function tests Standards CE labeling approvals The fire detection control panels Series BC216 1 correspond to the following international and national standards national regulations and guidelines EN54 1 Fire detection and fire alarm systems Introduction EN54 2 Fire detection and fire alarm systems Control and indicating equipment EN54 4 Fire detection and fire alarm systems Power supply equipment OENORM F3000 Brandmeldesysteme OENORM F3001 Brandfallsteuersysteme TRVB S 123 Brandmeldeanlagen DIN VDE 0833 2 Gefahrenmeldeanlagen f r Brand Einbruch und berfall VdS 2203 Erg nzende Anforderung
144. se of doubt you have to contact the fire brigade immediately Check if the connected sirens have been activated If you are within hearing distance of the sirens this check is very easy If not you will have to rely on the displays in the field ALARM DEVICE 1 Is the light emitting diode Activated not illuminated the sirens have not been activated Is the light emitting diode Fault Disabled illuminated or flashing it is not clear whether or not the sirens have been activated In this case you have to start alternative measures to alarm the persons in the endangered areas Reset the sirens only if you are sure that no evacuation alarm is needed Find out where the first fire alarm has occurred The first line of the LC display shows the number of the detector zone and the number of the fire detector that activated the alarm the second and third lines show hints on the locality You also can get information on the locality by looking up the numbers of the detector zones and the fire detec tors in the list of detector zones provided in the engineering data Find out how many alarms were activated The fourth line displays the last alarm Its running number e g 6 ALARM shows how many alarms were activated in the example 6 Take a survey of all current alarms Here the superiority of the operation of the control panel becomes obvious By using the tl buttons you can scroll through all current alarms and obtain informatio
145. spatially highly ramified systems Due to network technology the connec tions of the fire detectors to the control panel can be established vastly more efficient than in conventional fire detection technology Due to the modular structure of the control panels these products of high quality can be combined to highly flexible systems of fire detection technology Besides less cabling work the failure safety of the system is vastly improved by combining several intelligent sectional control panels to an overall system by means of network technology The high failure safety the modular structure using standardized components the simplicity of opera tion but also the high quality standards of LST for development and manufacture classify the fire detec tion control panels BC216 1 and BCnet216 as the most modern high performance control panels available in the world Figure l Front view of the fire detection control panel Series BC216 The User Manual for the fire detection control panels BC216 1 and BCnet216 which are collectively referred to as Series BC216 in this User Manual consists of three parts e The second chapter of the first part Part A sums up the main features for the user of the fire de tection control panel Series BC216 Chapters 3 through 5 give detailed descriptions and clear oper ating instructions of the functions of the control panel Hints to protect the working of the fire detection system are given starting page 6
146. t the reception of a further alarm or of a fault See from page 32 in Chapter 4 2 4 Alarm delay procedure of the primary transmitting device Have the parameters of the transmitting device been set for a two zone dependency the activation of the transmitting device takes place only after at least two zones of this two zone dependency are in the condition of alarm See from page 39 in Chapter 4 7 7 Displaying and operating detector zones menu point Zone Provided that the parameters of the alarming device have been set for the current cause of the alarm the red light emitting diode Activated located in the field ALARM DEVICE 1 is illuminated to in dicate that the alarming devices connected to the primary alarming device have been activated Have the parameters of the alarming device been set for a two zone dependency the activation of the alarming device takes place only after at least two zones of this two zone dependency are in the condition of alarm See from page 39 in Chapter 4 7 7 Displaying and operating detector zones menu point Zone Provided that the parameters of actuations have been set for the current cause of the alarm the red light emitting diode Actuation activated is illuminated to indicate that the actuations have been ac tivated Have the parameters of the actuation been set for a two zone dependency the activation of the ac tuation takes place only after at least two zones of this two zone
147. technical message and can be reset in the same way If no event of higher priority is currently on the control panel the menu jumps automatically to the menu point Technical messages The first line of the LC display shows the technical message that was received first The second and third line display the zone and the element specific text for the technical message displayed in the first line The fourth line is reserved for displaying fire alarms The activated actuations are num bered in the order of their arrival on the control panel 1 TECH MSG 0005 011 lt zone textl1 gt lt element text gt Figure 19 Display in message condition for technical messages Message Nr 5 element Nr 11 is displayed as the first technical message received The second and third line display text information regarding the displayed technical message Has no element text been programmed the second line of the zone text if available is displayed The fourth line is re served for fire alarm messages e Ifthe parameters have been set accordingly the light emitting diodes of all technical messages that were received are illuminated on the optional LED display field Additional information e g date and time of the arrival of the technical message displayed in the first line the number of technical messages received hints for operating the menu hints for authorization can be displayed by using the Info button You can scroll through all c
148. tely if the parameters of this alarm message have been set to activate the transmitting device During day operation an incoming alarm message activates the corresponding primary transmitting de vice delayed by the span of time for reaction if the parameters of this alarm message have been set to activate the transmitting device Is the button Alarm delay Explore pressed during the time for reaction this means before the trans mitting device has been activated the control panel switches to exploring and extends the delay time During this extended delay time the exploration time the responsible persons can locally decide if it is necessary to contact the fire brigade If this is not necessary the contacting of the fire brigade can be forestalled by disabling the alarming detector zone Is the delay time elapsed without the alarm having been reset the fire brigade is contacted During running exploration time you can display the time remaining till activation of the transmitting device on the LC display by pressing the button Alarm delay Explore Is another alarm or fault message received during this delay the delay is automatically interrupted and the fire brigade is contacted immediately The light emitting diode Activated located in the field TRANSM DEVICE 1 is illuminated during day operation only after the exploration time has elapsed or has been interrupted 30 seconds for reaction time and 270 seconds for exploratio
149. the above table They are described in detail in Part C of this Manual The control panel returns to displaying the event with the highest priority automatically 30 seconds af ter a button was pressed last if an event is currently on the control panel independent of which menu 36 4 5 4 6 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A Entering and exiting authorization level 2 To enter authorization level 2 from authorization level 1 you have to enter the 4 digit user code pro grammed by the installer You have two possibilities to start this e Scroll the main menu points to the menu point Authorization code by using the or the button or e Enter your user code directly and arrive automatically at the menu point Authorization code with out scrolling through the menus This menu quick operation is not possible while you are viewing the event memory You enter the 4 digit code and confirm the entry by using the button One is displayed on the LC display for every entered digit If the entry was correct the second line of the LC display shows User level and the green light emitting diode Authorization is illuminated on the panel By entering authorization level 2 different important parts of the system e g transmitting devices actuations etc can be put out of operation automatically depending on regional restrictions and
150. the emergency power supply are shut down Kind of message Zone number Element number Fire alarm Nr 1 lt Information text 1 lt Information text 2 Last alarm Nr 5 POWER f f Alarm display Power display Fault display Figure 5 Info field exemplary fire alarm with 5 current fire messages The first line displays the current alarm with the zone and element number The second line displays the first text information for the zone of the current alarm 24 3 2 3 3 3 4 3 5 Chapter 3 e Displaying and operating elements User Manual Series BC216 Part A The third line displays the text information for the element of the current alarm Is no element text programmed the second text information for the zone is displayed instead At installations without elements the element display is inapplicable The fourth line displays the last registered alarm here the 5th alarm with zone and element number E The fourth line of the LC display is reserved for the displaying of the last registered fire alarm In the absence of a fire alarm the fourth line of the display stays blank at all times The fourth line of the dis play is only inscribed for a short time during the testing of the display Info button The Info button basically has two functions e By pressing the Info button additional information to the current information is displayed in the second and third line of the LC
151. til the faults have been reset e g by disabling the fault detector zone Fault displays that are recorded by the control panel it self e g a mains power shut down are not kept saved When the cause of the fault is eliminated the display on the control panel disappears E You can survey the last 500 events anytime by viewing the event memory See from page 43 in Chap ter 4 7 11 Menu point Event memory E Has a fault been repaired all faults remaining in the display memory are renumbered in the order of their occurrence The following fault messages are displayed on the LC display of the control panel The transmitting of an alarm from the concerning detectors to the control panel is no longer ensured Condition Displaying 1st line Effect Alarm message from a detector zone e g Nr 5 for fault messages 1 FLT ALARM 0005 Alarm message from an element e g Nr 14 of a detector zone e g Nr 1 FLT ALARM 0005 014 5 for fault messages Alarm of a detector zone e g Nr 5 for fault messages in test condition 1 FLT T AL 0005 Alarm of an element e g Nr 14 of a detector zone e g Nr 5 for fault 1 FLT T AL 0005 014 messages in test condition Fault in a detector zone e g Nr 4 for fire alarms 1 FAULT 0004 The transmitting of a fire alarm from the concerning fire detectors to the control panel is no longer ensured Fault in an element e g Nr 29 of a detector zone e g
152. tinually monitored telephone cables The transmit ting device for fire alarm messages which can also be operated additionally to the menu control via the buttons in the field TRANSM DEVICE 1 of the key pad of the control panel is called pri mary transmitting device The possibility of alarm delay also see the terms Alarm delay proce dure Delay time is exclusively existing for the primary transmitting device e Two zone dependency Measure to guard against deceptive activation of actuations e g of an extinguishing system The activation of the corresponding parts of the system takes place only after at least one fire detector in each of the two linked detector zones have detected signs of fire Using the fire detection control panel BC216 1 or when using the fire detection control panel BCnet216 in every BCnet sectional control panel also more than two detector zones can be combined to a multiple detector zone de pendency still called two zone dependency for simplicity e User Person s who are responsible for the operation and the use of the fire detection system HB216AE SAM 0130 AN9161202 ZN5002 73 14 User Manual Series BC216 Part A Chapter 2 e Fire detection control panel Series BC216 15 HB216AE SAM 0130 AN9161202 ZN5002 73 15 21 Fire detection control panel Series BC216 The construction of a typical fire detection system the most important features of the fire detection control panels Series
153. tions The further alarming devices are reset by using the menu This operation is described starting page 43 in Chapter 4 7 10 Displaying and operating alarming devices menu point Alarming device Resetting an alarm of a detector zone You can reset the alarm of a detector zone by disabling the corresponding detector zone or the alarming detector see from page 39 in Chapter 4 7 7 Displaying and operating detector zones menu point Zone Thereby all actuations dependent on this alarm are reset as well E Alarms of detector zones remaining in the display memory are renumbered in order of their occurrence Terminating the fire alarm condition The condition of fire alarm is terminated if no detector zone is reporting a fire alarm anymore The con dition for this is that e the signs of fire e g smoke temperature etc that caused the fire alarm do not exist anymore and the fire detectors have been reset or e the affected detector zone and the affected elements have been disabled Automatic fire detectors usually are reset from the control panel by disabling followed by enabling the detector zone or a single detector The disablement and enablement of detector zones and detectors are described starting page 39 in Chapter 4 7 7 Displaying and operating detector zones menu point Zone Manual fire detectors manual call points have to be priorly reset mechanically on the detec tor itself E If individual detect
154. trical switch offs of extinguishing systems or similar devices before the start of the activation If the criterion for activation of the actuation exists at the time of the enablement of this actuation the actuation will be activated immediately 4 7 8 2 Operating single elements of actuations 4 7 9 Provided that the technology used in your control panel allows it you can operate individual elements of an actuation Such elements can be enabled and disabled and can be activated furthermore their measured values can be displayed The selection of an actuation element is similar to the selection of elements of a detector zone see from page 40 in Chapter 4 7 7 2 Operating single elements of detector zones The third line of the LC display shows the current condition of the chosen element in capital letters You can either scroll to the desired condition by using the TL buttons or the menu quick operation using numeric buttons O disable 1 enable 2 activate 4 Measured val Maint The warning hints on page 41 in Chapter 4 7 8 1 Operating actuations are valid analogously for the operation of single actuation elements as well If you have disabled all elements of an actuation this is displayed as a disablement of the whole actuation When calling up the function Measured val Maint a measured value according to the condition of the element at the time of call up will be put out depending on the type of a
155. ubmenu point Clock time correction 45 Setting the clock time submenu point Clock time setting 45 Setting the date submenu point Date setting aaa 45 Switching to summertime submenu point Winter summertime 45 Switching to standard time submenu point Summer wintertime 45 Displaying the installed componentries submenu point Componentries 46 Printing submenu point Print out aa aaa 46 Repeating a print out submenu point Repeat print out 2 eee 47 Abort measured value print out submenu point Stop measurement print out 47 Modifying the numeric code for the user submenu point Change user code 47 Changing the numeric code by the installer submenu point Change installer COME ANA 47 Menu points Authorization code Exit authorization cece eee eee 47 Operating the control panel by using the fire brigade control unit 48 Operating conditions of fire detection control panels Series BC216 49 Normal condition 88233 nh RAANG nan Sader eae ea eee GN GN pA eee 50 Fire alarm condition seierisrerresr es hotp e Eth EEE PEPEE TETEE REEE REER bares 50 The first operations on the control panel in fire alarm condition 52 Resetting the alarming devices sese a a AGANG NGA GAN nent eenens 54 Resetting an al
156. ult cause Fault loop LOOP FLT 0001 012 Fault power unit ENERGY FAULT power unit Fault serial interface SER IF FLT 1 Fault stand by battery ENERGY FAULT stand by battery Fault term stand by battery ENERGY FAULT T stand by battery Fault termin ext consumer FAULT T fuse 4 blown Fault termin ext consumer FAULT T fuse 5 blown Fault termin exting system EXTING FIT T Fault termin serial interface SER IF FLT T 1 Fault termination ABB216 FAULT T ABB216 fault cause Fault termination earthing ENERGY FAULT T short to earth Fault termination funcion module 1 FAULT T FM1 fault cause HB216AE SAM 0130 AN9161202 ZN5002 73 70 User Manual Series BC216 Part A Chapter 7 e Event memory entries 71 Event Event text Text 2nd line Text 3rd line Additional text info button Fault termination function FAULT T FM2 fault cause module 2 Fault termination INFO bus SER IF FLT T 0 01 Fault termination LAB48 FAULT T LAB fault cause Fault termination loop LOOP FLT E 0001 012 Fault termination power unit ENERGY FAULT T power unit Notification new year CLOCK TIME SHIFT Happy New Year Sabotage fire brig key safe SABOTAGE KEY SAFE Sabotage term f b key safe SABOTAGE KEY SAFE T Shifting wi
157. urity technology by offering the additional possibility to display technical messages and the condition of installed actuations on the control panel Usually the technical messages and actuations are informa tion concerning preventive fire protection such as the displaying of messages from fire protection de vices displays of weight or pressure loss of the extinguishing agent in gas extinguishing systems positions of fire doors and fire dampers etc This additional information is not directly related to the fire detection system but in many cases pro vides an essential basis for decisions of the fire prevention officer in case of fire The local approval d t authorities decide over the admissibility of the processing and displaying of technical messages on the fire detection control panel In addition to the operating conditions defined in normative standards e the message condition for technical messages at least one message of a transmitter for technical messages has been received and e the activation condition of actuations at least one actuation has been activated due to a fire alarm fault disablement or technical message have been defined as further possible operating conditions of the fire detection control panels Series BC216 Other than the normal condition all conditions can occur at the same time E g a fire detection system can display the fire alarm of a fire detector fire alarm condition and at the same ti
158. urrent technical messages by using the TL buttons NI The number series for technical messages in the example above 0005 is the same as for fire detec tor zones and fault detector zones Resetting a technical message The parameters of detector zones for technical messages can be set to self holding or self resetting The kind of resetting required in each case is set by the installer Self resetting detector zones for technical messages display the current detector condition If the de tector returns to normal condition the technical message disappears Self holding detector zones continue to display the technical messages until the detector zone or the detector is disabled on the control panel By disabling all actuations dependent on this message are re set also Whether or not the detector itself can be returned to normal condition by disabling the detector zone depends on the kind of detector used E Is a technical message reset all displays of technical messages remaining in the display memory are renumbered in the order of their occurrence E Some special detectors may require special resetting procedures the authorized installer will inform you about them By pressing the button Panel reset you reset all current technical messages in addition to other displays at the same time In this connection please pay attention to the comments starting page 31 in Chapter 4 2 1 Resetting the fire detection control panel
159. uts are performed by using the numeric buttons of the keypad Examples are the input of an authorization code selection of a detector zone or of an element of a detector zone etc In addition and depending on the relevant menu point direct operating functions are made possible by using the numeric buttons By using the button you confirm an input or are moving to the submenu shown By using the esc button you undo an input or else you return to the preceding menu point Element button Many processes of operating displaying or setting of parameters of the fire detection control panel Se ries BC216 also can have an effect on just a single element of a detector zone e g on a single fire de tector of a detector zone The selection of an element is made by entering the detector zone number pressing of the Element button the display shows and entering the number of the element E For the installer On the PC keyboard the Element button is represented by the dividing button of the numeric keypad HB216AE SAM 0130 AN9161202 ZN5002 73 24 User Manual Series BC216 Part A Chapter 3 e Displaying and operating elements 25 HB216AE SAM 0130 AN9161202 ZN5002 73 25 3 6 3 7 3 8 Reset buttons Panel reset button All actual fire alarms technical messages fault alarms faults and actuations are reset in one action on the control panel by pressing this button With a fire detection control panel
160. w light emitting diode Energy fault is flashing e Ata fault in the system the yellow light emitting diode System fault is flashing or is illuminated depending on the kind of fault see from page 9 in Chapter 1 2 2 What to do in case of a fault e Ifthe parameters have been set accordingly the light emitting diodes of all faulted zone s or other parts of the system are flashing on the optional LED display field Additional information e g date and time of the occurrence of the fault displayed in the first line the kind of fault etc can be displayed by using the Info button You can scroll through all current faults by using the TL buttons an alarming device is removed from the two zone dependency Have the parameters of the two zone N A faulted detector zone that is part of a two zone dependency of an actuation a transmitting device or dependency been set for just two detector zones and one of them is faulted the to be activated actua tions cannot be activated by the two zone dependency in case of fire Does an interdependence of two detectors consist of just two detectors and one of them is faulted the second detector is ineffective as well because it can activate only a pre alarm The number series for faults in above example 0012 is the same series as for fire detector zones and detector zones for technical messages Fault messages transmitted to the control panel by fault detectors are saved un
161. written by using the keypad or increased or decreased by using the N buttons You can only enter the submenu if you have confirmed your entries by using the button Additionally some points of the menu provide the selection of an element in addition to the selection of a zone or actuation number For this you do not confirm the entered zone or actuation number by using the button but by using the special button Flement the LC display is showing and enter ing the desired number of the element After confirming this number with the button you enter the submenu At entering a submenu the first submenu point is displayed You can scroll to the desired submenu point by using the TL buttons and confirm it by using the button After choosing a part of the system by using the button the current condition of this part is dis played in the submenu in capital letters You can either change to the desired condition by using the N buttons and confirm your choice with the button or you can by using the menu quick operation achieve the desired condition by entering one number e g 0 disable 1 enable If you do not want to change the condition you have to press the button esc In both cases the display re turns to the previously displayed submenu point If you want to operate the same part of the system again you have to confirm it again by using the button W The possible submenu points conditio
162. y You can erase the date by entering the number 99 in the day digits or by using the button del on the PC keyboard The LC display shows Date deleted as confirmation and at renewed confirmation of this menu point is displayed and the switch will not take place The switch from summer to standard time is not affected by this Minimum requirement for this submenu point is authorization level 2 Switching to standard time submenu point Summer wintertime You can enter the date for the automatic switch from summer to standard time in this menu point The action is similar to the one described on page 45 in Chapter 4 7 12 7 Switching to summertime sub menu point Winter summertime The switch to standard time takes place at the set date at the time of 03 00 o clock 46 Chapter 4 e Basic operation of the fire detection control panels Series BC216 User Manual Series BC216 Part A 4 7 12 9 Displaying the installed componentries submenu point Componentries You can display the corresponding number of the software version and an additional information such as e g the serial number of the componentries installed in the control panel by using the buttons nee Minimum requirement for this submenu point is authorization level 2 4 7 12 10 Printing submenu point Print out This menu point is only accessible to the installer i e only in authorization level 3 The installer can print the essential parameters
163. y 14 Disabled detector zone 40 61 Fault of a detector zone 59 Of a transmitting device 42 Of an actuation 41 56 Of an alarming device 43 User 7 14 User code 29 30 36 At delivery 47 Change 47 Warranty 11 HB216AE SAM 0130 AN9161202 ZN5002 73 73 Chapter 8 e Index 73