Lightolier FAEM3 User's Manual

image

Contents

1. INSTRUCTION SHEET NO READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE This fixture is intended for installation in accordance with the National Electrical Code and local IS FA F Vi 3 regulations To assure full compliance with local codes and regulations check with your local electrical E inspector before installation To prevent electrical shock turn off electricity at fuse box before proceeding B0500 Page 4 of 4 Retain these instructions for maintenance reference E CLOSE IN CONT 4 Pull down SWITCH INDICATOR LIGHT BOX and clamp onto ceiling by Fig 5 TAIL tightening SCREWS on side of BOX Fig 4 5 Connect INVERTER CONNECTORS in SWITCH INDICATOR LIGHT BOX Fig 4 lt m 6 Fasten TRIM PLATE to SWITCH INDICATOR LIGHT BOX with LOCK NUT Fig 5 F ADJUST MOUNTING FRAME LOCK NUT 1 Set MOUNTING FRAME so the bottom edge is flush with finished ceil ing Fig 6 Note Final vertical adjustment can be made with MOUNTING BRACKET SCREWS Fig 7 on inside of MOUNTING FRAME Fig 6 G OPERATION When AC power is applied the charging indicator light is illuminated indi cating that the battery is being charged When the power fails the emer gency lighting ballast automatically switches to emergency operation keeping one lamp illuminated at reduced output for 90 minutes H MAINTENANCE Although no routine maintenance is required to keep emergency lighting MOUNTING FRAME ballast func
2. cap the 277V lead orange RED LAMP LEADS INSTRUCTIONS FOR WIRING EMERGENCY BALLAST FOR 1 By BLUE LAMP INSERT LEADS QUICK OR 2 4 PIN LAMPS ELECTRONIC A C BALLAST FRAME IN KIT CONNECTOR Before converting to emergency lighting please identify no of lamps and wattage of frame in kit then select appropriate Wiring Diagram A B or C for rewiring There is a requirement to remove lamp leads from A C ballast and reconnect to emergency ballast Disconnect either BLUE LAMP LEAD from BALLAST by inserting conductor of RED JUMPER provided into open terminal of QUICK CONNECTOR of BALLAST as shown in Fig 2 Gently pull BLUE LAMP LEAD out Then remove RED JUMPER for later use Repeat step 2 above to remove other BLUE LAMP LEAD and one appropriate RED OR YELLOW LAMP LEAD from BALLAST Fig 2 and wiring diagrams E Insert appropriate RED OR YELLOW JUMPER into the terminal where the RED OR YELLOW LAMP LEAD was previously removed from QUICK CONNECTOR Fig 3 Follow WIRING DIAGRAM A or B or C to complete the wiring at FLEX A WIRING DIAGRAM A 1 LAMP FIXTURE WIRING DIAGRAM B 2 LAMP FIXTURE UP TO 2 42W 1 LAMP EMERGENCY 1 LAMP EMERGENCY NOTE FOR UNSWITCHED CIRCUIT CONNECT NOTE FOR UNSWITCHED CIRCUIT CONNECT BOTH WHITE RED AND ORANGE BLACK LEADS UNSWITCHED BOTH WHITE RED AND ORANGE BLACK LEADS _ UNSWITCHED IN JUNCTION BOX TO UNSWITHCHED 120V 1I NETURAD GROUND IN JUNCTION BOX TO UNSWITHCHED 120V TN NERMAN GND OR 2
3. 77V VOLTAGE SELECTION IS MADE IN ammutan OR 277V VOLTAGE SELECTION IS MADE IN A SWITCH BOX dimming leads to dimmer SWITCH BOX dimming leads to dimmer WALL TCH SW i j EMERGENCY za EMERGENCY BALLASI ELECTRONIC PALLASI ELECTRONIC BLK FLEX FLEX wek m A C BALLAST FLEX FLEX A C BALLAST B A INVERTE B A CONNECTOR BLUE WHT CONNECTOR E CHARGE B B CHARGE JUNCTION SWITCH BOX JUNCTION SWITCH BOX BOX BOX L STAB IN CONNECTOR 2 CONDUCTORS C STAB IN CONNECTOR 2 CONDUCTORS L stas in CONNECTOR 3 CONDUCTORS L STAB IN CONNECTOR 3 CONDUCTORS ol O WHITE AND RED JUMPERS PROVIDED WHITE AND YELLOW JUMPERS PROVIDED 2 BLUE AND 1 RED LEADS REMOVED one 2 BLUE AND 1 RED LEADS REMOVED FROM ELECTRONIC BALLAST el e FROM ELECTRONIC BALLAST LAMPHOLDER 1 EMERGENCY f i Cs j Ol i R LIGHTOLIER a GENLYTE THOMAS company gt d E 2 oo 631 Airport Road Fall River MA 02720 READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE INSTRUCTION SHEET NO This fixture is intended for installation in accordance with the National Electrical Code and local regulations To assure full compliance with local codes and regulations check with your local electrical 5 Vi 3 inspector before installation To prevent electrical shock turn off electricity at fuse box before proceeding E Retain these instructions for maintenance reference C0506 Page 3 of 4 WIRING DIAGRAM C 2
4. D IN LOCATIONS AND AT A HEIGHT WHERE IT WILL NOT READILY BE SUBJECT TO TAMPERING BY UNAUTHORIZED PERSONNEL 9 THE USE OF ACCESSORY EQUIPMENT NOT RECOMMENDED BY THE MANUFACTURER MAY CAUSE AN UNSAFE CONDITION 10 DO NOT USE THIS EQUIPMENT FOR OTHER THAN INTENDED USE 11 THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT TO REDUCE THE RISK OF ELECTRICAL SHOCK DISCONNECT BOTH NORMAL AND EMERGENCY POWER SUPPLIES BEFORE SERVICING 12 BEFORE SERVICING TO PREVENT ELECTRICAL SHOCK DISCONNECT THE INVERTER CONNECTORS OF THE EMER GENCY BATTERY PACK LOCATED IN THE SWITCH INDICATOR LIGHT BOX MAKE CERTAIN THAT THE SWITCHED IF THE FIXTURE IS SWITCHED AND THE UNSWITCHED LINE TO THE EMERGENCY BATTERY PACK ARE TURNED OFF AT THE FUSE BOX SERVICING SHOULD BE PERFORMED BY QUALIFIED SERVICE PERSONNEL ONLY 13 BEFORE ANY INSTALLATION MAKE SURE TO CHECK THE COMPATIBILITY MATRIX BELOW BEFORE INSTALLATION INCORRECT MATCHING MAY CAUSE ELECTRICAL SHOCK AND DAMAGE TO BALLASTS AND LAMPS FOR USE WITH NON DIMMING U SERIES AND DIMMING J SERIES FRAME IN KITS SS Ss a Emergency Ballast Compatible Ballast Electroninc Non Dimming Advance Mark 7 and Mark 10 Dimming Lutron compact SE Hi Lume TU Wire Dimming FA EM3E Tiple Tube 4 Pin 42W LIGHTOLIER ossemimice INSTRUCTION SHEET NO READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE This fixture is intended for installation in accordance with the National Ele
5. LAMP FIXTURE UP TO 2 26W 2 LAMP EMERGENCY UNSWITCHED 120V0R COMMON NOTE FOR UNSWITCHED CIRCUIT CONNECT 277V NETURAL GROUND BOTH WHITE RED AND ORANGE BLACK LEADS IN JUNCTION BOX TO UNSWITHCHED 120V For dimming ballast connect OR 277V VOLTAGE SELECTION IS MADE IN dimming leads to dimmer SWITCH BOX WALL Z SWITCH GREEN TEST SWITCH EMERGENCY BALLAST ELECTRONIC A C BALLAST FLEX FLEX B A INVERTER CONNECTOR CHARGE LIGHT JUNCTION SWITCH BOX BOX L STAB IN CONNECTOR 2 CONDUCTORS A STAB IN CONNECTOR 3 CONDUCTORS WHITE AND RED JUMPERS PROVIDED 2 BLUE AND 1 RED LEADS REMOVED FROM ELECTRONIC BALLAST LAMPHOLDER 1 LAMPHOLDER 2 EMERGENCY C INSTALL MOUNTING FRAME TO CEILING SUPPORT MEMBERS See separate frame in kit instruction sheet SWITCH INDICATOR D WIRE IN SCREWS LIGHT BOX Connect supply leads to emergency ballast electronic Fig 4 ballast and fixture ground wire as shown in WIRING DIAGRAM A B or C Cap unused lead Close the junction box cover after wiring is completed E CLOSE IN 1 Cut appropriate hole size in ceiling for frame 2 Cut hole in ceiling for SWITCH INDICATOR LIGHT BOX in a convenient location to the side of frame Fig 4 The recommended hole size is 2 5 8 x 3 3 4 3 Close in ceiling INVERTER CONNECTORS i i Cs j Ol i R LIGHTOLIER a GENLYTE THOMAS company c gt d i aa a 631 Airport Road Fall River MA 02720
6. LAS Follow installation instructions in Step A B D and E FRAME e EMERGENCY BALLAST INSTALLATION FROM BELOW 1 Make sure AC power power is off at fuse box 2 Remove REFLECTOR see reflector trim instruction sheet 3 Install EMERGENCY BALLAST to the center of MOUNTING FRAME BRACKET as shown in Fig 1 and 9 4 Go to step A B D and E i i Cs j TOI i R LIGHTOLIER a GENLYTE THOMAS company gt d i on f oo 631 Airport Road Fall River MA 02720
7. READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE INSTRUCTION SHEET NO This fixture is intended for installation in accordance with the National Electrical Code and local regulations To assure full compliance with local codes and regulations check with your local electrical z 3 inspector before installation To prevent electrical shock turn off electricity at fuse box before proceeding E Retain these instructions for maintenance reference C0506 Page 1 of 4 Installation of Compact Fluorescent Emergency Ballast Accessory FAEM3E to Standard Calculite Four Pin Electronic Compact Fluorescent Lamp Frame In Kit IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS WHEN USING ELECTRICAL EQUIPMENT BASIC SAFETY PRECAUTIONS SHOULD BE FOLLOWED INCLUDING THE FOLLOWING 1 TURN OFF AC POWER BEFORE PROCEEDING 2 DO NOT INSTALL INSULATION WITHIN 3 INCHES OF FIXTURE SIDES OR WIRING COMPARTMENT NOR ABOVE FIX TURE IN SUCH A MANNER AS TO ENTRAP HEAT 3 BE SURE ALL ELECTRICAL CONNECTIONS ARE COMPLETE AND THE JUNCTION BOX IS CLOSED BEFORE INVERTER CONNECTORS LOCATED IN THE SWITCH INDICATOR LIGHT BOX ARE CONNECTED DO NOT USE OUTDOORS DO NOT LET POWER SUPPLY CORDS TOUCH HOT SURFACES DO NOT MOUNT NEAR GAS OR ELECTRICAL HEATERS USE CAUTION WHEN SERVICING BATTERIES CONTAINS NICKEL CADMIUM RECHARGEABLE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY DO NOT SHORT CIRCUIT MAY CAUSE BURNS 8 EQUIPMENT SHOULD BE MOUNTE
8. ctrical Code and local m 3 regulations To assure full compliance with local codes and regulations check with your local electrical 4 inspector before installation To prevent electrical shock turn off electricity at fuse box before proceeding C0506 Page 2 of 4 Retain these instructions for maintenance reference NEW INSTALLATION Fig 1 A INSTALLING EMERGENCY BALLAST TO STANDARD FRAME IN KIT Fig 1 and 8 EMERGENCY 1 Before placing FRAME IN KIT in the ceiling install EMERGENCY BALLAST to the center aE BALLAST of MOUNTING FRAME BRACKET as shown xX C ancuaniie 2 Tighten SCREW to secure two units together CONNECTOR A FRAME 3 Remove JUNCTION BOX COVER and appropriate J Box K O then attach lt j BRACKET EMERGENCY BALLAST BX CONNECTOR ea gt WIRING Read and understand all instructions before proceeding j PRASKE Make sure AC power is off at the fuse box Era SERENV Regular ballast and emergency ballast must be fed from the same branch circuit Be sure all electrical connections are made and junction box is closed before connecting inverter connectors in switch indicator light box Fig 2 In switched fixtures emergency ballast must be connected ahead of any local switching Emergency ballast is shipped from the factory ready for 120V or 277V supply connection Prive Line Voltage selecton is made at switch box For 120V remove wire nut from 120V see lead black and connect to black lead of test switch then
9. tional it should be checked periodically to ensure that it is MOUNTING BAR MOUNTING working The following schedule is recommended Fig 7 ne FRAME 1 Visually inspect the charging indicator light monthly It should be illuminated 2 Test the emergency operation of fixture once every 3 months One lamp should operate at reduced output 3 Conduct a 90 minute discharge test once a year One lamp should Operate at reduced output for 90 minutes MOUNTING EMERGENCY BALLAST REPLACEMENT enue 1 Make sure AC power is off at fuse box 2 Remove REFLECTOR see reflector trim instruction sheet 3 Remove TRIM PLATE by removing LOCKNUT see Fig 5 disconnect ie a INVERTER CONNECTORS loosen SCREW on side of SWITCH BOX and slip SWITCH BOX onto the ceiling 4 Loosen SCREW away from EMERGENCY BALLAST ASSEMBLY Fig 8 Fig 8 5 Pull EMERGENCY BALLAST off MOUNTING BRACKET and down through the frame opening Fig 9 6 Unscrew and disassemble defective EMERGENCY BALLAST from SWITCH BOX and JUNCTION BOX 7 Replace with new EMERGENCY BALLAST Follow wiring diagram and MOUNTING instruction procedure as stated in this Instruction Sheet Z T ERAME MOUNTING EXISTING INSTALLATION T NOTE Emergency ballast kit may be installed after the frame in kits and ceilings are finished If ceiling is accessible from above it may be easier to install the emergency ballast from above Fig 9 ye EMERGENCY e EMERGENCY BALLAST INSTALLATION FROM ABOVE agua BAL