Liebert UPStation GX User's Manual
Contents
1. 2 software SNMP Communications An optional internal SNMP card and SiteNet SNMP software allows communication through several network management systems Call your Liebert supplier ALARMS Alarms indicate faults power outages and UPS battery operation The tone pattern varies according to the alarm On Battery Utility Failure Alarm one beep every 4 seconds greater than 2 minutes battery time remaining Silence this alarm by depressing the Alarm Reset switch for a half second After silencing it the low battery alarm still sounds at the appropriate time Low Battery Alarm 4 beeps per second less than 2 minutes battery time remaining Silence this alarm by depressing the Alarm Reset switch for a half second UPS Shutdown A long continuous tone occurs for a few seconds after the UPS is off Then the controls and display shut off High Temperature Alarm This alarm along with a flashing FAULT indicator indicates excessive internal UPS temperature This alarm is two long beeps per second Though the UPS continues to support its critical load correct the condition immediately Poor ventilation prolonged overloads or high temperature environments may cause overheating Immediately save work in process and correct the problem TROUBLESHOOTING If the UPS shuts down due to a fault condition the FAULT indicator lights The FAULT indicator also lights if the UPS exhausts its battery or receives a shut
2. 35 to 50 without Batter Relative Humidity 0 to 95 Non Condensing Operating Attitude Full Rating Up to 3 000 M 10 Derating per 1 000 M above 3 000 M Meets FCC Part 15 Subpart J Class A 52 dBA at 1 Meter UL 1778 CSA No 107 10 Minutes 25 Minutes 50 Minutes 6 per Cabinet 1 to 3 cabinets may be connected 72 VDC 12V 15 AH Uninterrupted 4 Hours to 90 10 Minute Discharge Rate 1 Cabinet Sealed Maintenance Free 10 to 35 C Electromagnetic Noise Audible Noise Agency Approvals PHYSICAL Dimensions HxW xD UPS Weight External Cabinet Weight Rear amp Front Clearance 7 x17 x 21 177 mm x 432 mm x 534 mm 49 Ibs 22 2 kg 111 Ibs 50 3 kg 4 102 mm 14 LIMITED WARRANTY We are pleased that you have purchased our UPStation GX product to enhance the reliability of the available AC power to your sensitive electronic equipment Liebert Corp warrants to the original user that the UPStation GX product is and will remain free of defects in materials and workmanship for a period of two years from date of purchase proof of purchase will be required During the warranty period Liebert will repair or replace at Liebert s option products purchased which fail to meet above warranty Extended warranty contracts are available NOTE Warranty is void if the battery is allowed to discharge below the minimum battery voltage cutoff point TO PREVENT SUCH DISCHARGE DO NOT leave the unit POWER
3. If unable to fully insert the plug into the outlet contact an electrician All utility receptacles must be grounded as well 18 Route power supply cords so they are not walked on or pinched 19 Never block or insert any object into ventilation holes or other openings Maintain a minimum clearance of 4 all around UPS for proper air flow and cooling 20 CAUTION Do not open or mutilate battery Released electrolyte is harmful to skin and eyes and may be toxic 21 CAUTION This UPS complies with the limits for a Class A digital device pursuant to Subpart J of Part 15 of FCC rules These limits provide reasonable protection against harmful interference in a commercial environment This UPS generates uses and radiates radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this UPS in a residential area is likely to cause harmful interference which the user must correct at his own expense INTRODUCTION amp SYSTEM DESCRIPTION Congratulations on choosing the Liebert UPStation GX UPS It provides continuous conditioned power to microcomputers and other data processing equipment Upon generation AC power is clean and stable However during transmission it may be subject to load variations or accidents that cause power problems like low voltage voltage spikes or complete power failure These problems may interrupt computer
4. down command via its communication interface port In addition to the FAULT light one of several different LED segments in the LOAD or CAPACITY bar indicators light briefly also These LED segments will indicate the name of the fault condition and the reason for the shutdown Load A Over temperature condition A eE Onn ED B Output overload condition C Internal fault Capacity D UPS output is short circuited E LF ILG E Internal fault F UPS shutdown due to battery exhaustion G UPS shutdown on command from Normal Fault Battery communication interface port LED Indicators during a Fault Condition If only the Fault LED lights it indicates the UPS is in Bypass mode Refer to the Troubleshooting Guide on the next page to determine what to do if your UPS shuts down and indicates one of the shutdown codes 10 UPStation GX Troubleshooting Guide PROBLEM UPS fails to start up when turned ON REASON SOLUTION Switch UPS off verify installation per Low utility voltage no utility Call your maintenance department qualified voltage or reversed input electrician or utility company to correct line and neutral conductor voltage or wait until utility voltage returns to normal Switch UPS off and disconnect all loads Verify that nothing is lodged in output receptacles Check loads for defects or short circuits Excessively
5. programming of UPS operation and numerous internal operating parameters MAJOR INTERNAL UPS COMPONENTS Surge Suppression and EMI RFI Filters These components provide surge protection and filter electromagnetic and radio frequency interference present in the utility line These components enable the UPS to supply pure sinewave power to sensitive equipment Power Factor Correction Circuit This circuit changes the utility AC input to DC for use by the inverter and ensures sinewave input current to the UPS Sinewave input achieves two things increased power efficiency and reduced power distortion Inverter The inverter converts the DC output of the power factor correction circuit to regulated AC sinewave power During either normal utility power operation or battery operation the inverter continuously generates and regulates output power Charger The charger regulates energy from the power factor correction circuit to continuously charge the batteries The charger operates whenever the UPS is ON For maximum battery charge life and power protection leave the UPS ON Battery The sealed maintenance free spill proof batteries in the UPStation GX last for 5 years at typical room temperatures and with normal charging They maintain UPS output at full rated power for 10 minutes Reducing the load increases battery back up time Bypass This standard UPStation GX feature provides an alternate power source to the output automatically i
6. switch ON for more than 2 days without AC power being supplied to the UPS The battery must be recharged every 6 months if not in use Circuit breaker resetting is not covered by this warranty and may indicate use beyond capability of the product No warranty applies to products which have been abused mishandled modified damaged by act of God or source external to the product repaired by others or which have product serial numbers removed or altered There are no warranties other than that described herein In no event will Liebert be responsible beyond the purchase price of the product SELLER DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS OR THE FITNESS OF THE GOODS FOR ANY INTENDED PURPOSES LIEBERT ASSUMES NO RESPONSIBILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES INCLUDING WITHOUT LIMITATION LOSS OF USE PROFIT OR INCOME This product is not recommended and Liebert will not knowingly sell this product for use with life support and other U S FDA designated critical devices ANY SUCH USE BY A USER AUTOMATICALLY VOIDS AND DISCLAIMS ANY AND ALL WARRANTIES INCLUDING ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE FOR THIS PRODUCT AND THE USER EXPRESSLY AGREES THAT IN NO EVENT SHALL LIEBERT BE LIABLE FOR CONSEQUENTIAL OR INDIRECT DAMAGES To make a warranty claim for replacement first call your Liebert supplier with th
7. 50 Full Load Amps for 10 Cycles Max 120 Full Load Amps for 1 Sec Load Power Factor Range 0 6 Lagging pf to Unity Rated at 0 7 pf Transient Response Time 100 load step to within 90 nominal output voltage within 30 milliseconds Bypass Transfer 4 6 Milliseconds Efficiency AC to AC 82 at 100 Load g 4 NEMA 5 15R 2 Duplex Receptacles 4 NEMA 5 15R 2 Duplex 2 NEMA 5 20R 1 Duplex BATTERY Backup w Int Battery Only 10 Minutes Backup w 1 Ext Cabinet 90 Minutes 40 Minutes Backup w 2 Ext Cabinets 160 Minutes 90 Minutes i 4 per Cabinet Int i i Battery Quantity s oe seni ie 6 per Cabinet 8 per Cabinet 96 VDC Nominal Voltage 48 VDC 72 VDC Battery Rating 12 V 7 AH Internal Battery 12 V 15 AH External Battery Transfer Time Uninterrupted Battery Recharge Time 4 Hours to 90 10 Minute Discharge Rate Internal Battery Battery Type Sealed Maintenance Free ENVIRONMENTAL Operating Temperature Storage Temperature Relative Humidity Operating Altitude Electromagnetic Noise Audible Noise Agency Approvals PHYSICAL Dimensions HxW xD 7 x17 x 21 177 mm x 432 mm x 534 mm UPS Weight w Int Battery 71 Ibs 32 0 kg 83 Ibs 37 4 kg 97 Ibs 43 7 kg External Cabinet Weight 139 Ibs 62 6 kg 111 Ibs 50 0 kg 139 Ibs 62 6 kg Rear amp Front Clearance 4 102 mm 10 to 35 C 20 to 40 C with Internal Batter 0 to 95 Non Condensing Full Rating Up to 3 000 M 10 Derating per 1 000 M above 3 000
8. E D INCENDLE OU DE CHOC ELECTRIQUE INSTALLE DANS UN SECTEUR AVEC TEMPERATURE CONTROLE ET HUMIDITE CONTROLEE EXAMPT DE POLLUANTS CONDUCTEURS Read all safety and operating instructions before operating UPS Operate indoors only Protect UPS from moisture and install it in a clean environment free from flammable liquids gases or corrosive substances WARNING Do not modify cable Consult dealer if connector does not match equipment UPS must be grounded at all times while in use Turn UPS OFF before unplugging or the safety ground from UPS to equipment will be removed CAUTION Output receptacles on the UPS are electrically live if the UPS is ON even if the UPS is not plugged in The on off switch on the UPS does not electrically isolate the internal parts To isolate the UPS turn it OFF and unplug it CAUTION Ground leakage current must not exceed 2 75 milli amperes Most data processing equipment meets this requirement if you use no more than 4 pieces of equipment Note These instructions may be modified by local wiring regulations Unplug the UPS and turn the power switch OFF before cleaning Use only water dampened cloth never liquid or aerosol cleaners 15 Do not plug appliances such as hair dryers or heaters into UPS receptacles 16 Operate UPS only from a grounded outlet 2 wire plus ground 120 VAC 60 50 Hz 17 The UPS is equipped with a grounded NEMA 5 15 input power plug Do not defeat the safety purpose of this plug
9. M Meets FCC Part 15 Subpart J Class A 45 dBA at 1 Meter 50 dBA at 1 Meter UL 1778 CSA No 107 13 3000 VA GX SPECIFICATIONS Model Rating VA Watts 3000 VA 2100 W at 240 VAC 2600 VA 1820 W at 208 VAC INPUT Voltage Voltage Range Frequency Current Power Factor Voltage Transients Power Cord OUTPUT Voltage and Current Voltage Regulation Frequency Locked to Utility 240 VAC or 208 VAC 3 Wire plus Ground 10 20 transfer to battery at 21 47 to 63 Hz 15 Amps 12 Amps RMS per phase Minimum 94 at Full Load Meets Requirements of IEEE 587 Category A amp B 6 1 88 m w NEMA L14 20 Plug 20 A 120 VAC at 25 A 208 VAC at 12 5 240 VAC at12 5A 3 Selected nominal 50 or 60 Hz 1Hz Output Distortion Maximum 5 THD with non linear load Waveform Sinewave Overload 150 Full Load Amps for 10 Cycles Max 120 Full Load Amps for 1 Sec Load Power Factor Range 0 6 Lagging pf to Unity Rated at 0 7 pf Transient Response Time 100 Full Load Amps for 10 Cycles Max 120 Full Load Amps for 1 Sec Bypass Transfer 4 6 Milliseconds Efficiency AC to AC 85 at 100 Load Receptacles 4 NEMA 5 15R 2 Duplex 1 NEMA L6 30 1 NEMA L12 20 BATTERY Backup w 1 Ext Cabinet Backup w 2 Ext Cabinets Backup w 3 Ext Cabinets Battery Quantity Nominal Voltage Battery Rating Transfer Time Battery Recharge Time Battery Type ENVIRONMENTAL Operating Temperature Storing Temperature 20 to 40 C with Battery
10. UPStatione GX 1000 VA to 3000 VA IMPORTANT SAFETY INSTRUCTIONS WARNING Do not attempt to service this product or replace the batteries yourself Opening or removing the cover may expose you to dangerous voltages even if the UPS is unplugged There are no user serviceable parts inside the unit Refer all servicing to qualified service personnel 10 14 SAVE THESE INSTRUCTIONS ADHERE TO ALL OPERATING INSTRUC TIONS AND WARNINGS ON THE UNIT AND IN THIS MANUAL CONSERVER CES INSTRUCTIONS CETTE NOTICE CONTIENT DES INSTRUCTIONS IMPORTANTES CONCERNANT LA SECURITE Liebert Corporation neither recommends nor knowingly sells this product for use with life support or other U S FDA designated critical devices CAUTION A BATTERY PRESENTS A RISK OF ELECTRICAL SHOCK OR BURN FROM HIGH SHORT CIRCUIT CURRENT OBSERVE PROPER PRECAUTIONS ATTENTION UNE BATTERIE PEUT PRESENTER UN RISQUE DE CHOC ELECTRIQUE DE BRULURE PAR TRANSFERT D ENERGIE SUIVRE LES PRECATIONS QUI S IMPOSENT WHEN REPLACING BATTERIES USE THE SAME NUMBER AND TYPE OF BATTERIES PROPER BATTERY DISPOSAL REQUIRED REFER TO LOCAL CODES POUR LE REMPLACEMENT UTILISER LE MEME NOMBRE ET MODELE DE BATTERIES L ELIMINATION DES BATTERIES EST REGLEMENTEE CONSULTER LES CODES LOCAUX WARNING TO REDUCE RISK OF FIRE OR ELECTRIC SHOCK INSTALL IN A TEMPERATURE AND HUMIDITY CONTROLLED AREA FREE FROM CONDUCTIVE CONTAMINANTS AVERTISSEMENT POUR REDUIRE LE RISQU
11. e unit model number and serial number He will obtain the required warranty return authorization from Liebert Corporation Customer is to package and ship the defective unit to Liebert as outlined on the Warranty Return Tag The Warranty Return Tag needs to be completed with description of defect installers name and telephone number and must accompany the defective unit back to Liebert The Warranty Return Tag is included with the packing of the new or reconditioned part from Liebert UPStation GX is a trademark of Liebert Corporation 15 0 Liebert 1050 Dearborn Drive Columbus OH 43229 614 888 0246 UPStation GX 1000 3000 VA Technical Support USA as est ca ses set sceneunss sbecsth EEEE 1 800 222 5877 Outside the U S A cicceccscseceescesereeesesenens 614 841 6755 U Ceeeeen rarer ere 44 0 1793 553355 33 1 487 51 52 49 89 99 19 220 39 2 98250 1 France Netherlands vsiisccciscccccriaecatinrrariiers 00 31 475 503333 Mermet annn a a a neta ade upstech liebert com Web Site inann aaas http www liebert com Worldwide FAX tech suppott 0 cee 614 841 5471 The Company Behind The ProductsWith more than 500 000 installations around the globe Liebert is the world leader in computer protection systems Since its founding in 1965 Liebert has developed a complete range of support and protection systems for sensitive electronics While every precaution has been taken to ensure Corp
12. e UPS sounds a 1 second tone every 4 seconds but increases to 4 tones every second when there is approximately 2 minutes of battery time remaining The UPS supplies internal battery power to a full load for 10 minutes before shutdown Increase this time by turning OFF non critical equipment Do not turn OFF UPS in battery mode while supporting a critical load Battery Recharge Upon return of utility power the UPS automatically reverts to normal operation and recharges the battery Significant battery discharge causes the CAPACITY bar to flash 1 2 or 3 left most segments As the battery charges the segments stop flashing one by one until all light steadily indicating full charge 6 FRONT PANEL CONTROLS amp INDICATORS 1 UPS Power Switch The UPS ON OFF switch controls both UPS input 1 2 3 power as well as output power to the loads The position signifies ON and the 0 position signifies OFF CAUTION Resetting power switch causes loss of power to output receptacles Shutdown critical loads before resetting power switch 2 Load Bar Indicator This 5 segment LED indicates relative electrical load placed on the UPS The left most 4 segments are green and the fifth segment is red Each green segment lights at 25 load increments no LEDs light until load on the UPS reaches 11 Loads beyond 100 causes the red fifth segment to light I L U I U L U I U L Test Reset Capacity 3 Capacity Ba
13. flashes all the LED indicators and sounds an alarm on start up High input voltage 132 volts and above on start up causes the UPS to flash the NORMAL indicator and sound an audible alarm Low or unavailable input voltage 105 volts and below terminates start up and causes the UPS to illuminate the FAULT indicator and the first two segments of the LOAD bar indicator If you encounter any of these conditions call a qualified electrician Place UPS in a location of unrestricted airflow Maintain a minimum of 4 inches 10 cm clearance at the front and rear of the UPS Maintain an ambient temperature range of 50 to 95 F 10 to 35 C NOTE UPS operation in ambient temperatures above 77 F 25 C reduces battery life Locate UPS where it cannot be accidentally turned off in an area free of moisture flammable liquids gases or corrosives i RACKMOUNT INSTALLATION i 1 Turn the ON OFF switch at the front of the LiftHereto Tower Oriented Remove Inlay Template Inlay UPS OFF Remove tower oriented template inlay from the front display area The rackmount oriented designations are printed on the UPS beneath the template inlay 2 Remove the three top cover screws on the rear of the UPS Push the top cover towards the rear of the UPS and lift off Top Cover Top Cover Screws Support Bracket 3 Remove the metal top cover support bracket Retain the two flange screws near
14. gments in the CAPACITY bar light to determine battery capacity If the left three LEDs flash replacement batteries may be necessary Contact Liebert Technical Support at 1 800 222 5877 NOTE As long as the Battery Test switch is depressed the batteries discharge and shorten back up time Do not depress the switch longer than necessary especially if the UPS supports a heavy load Battery Mode Press this switch for a half second to silence on battery alarms Once silenced the UPS still sounds the low battery alarm at the appropriate time This switch cannot reset over temperature fault high AC input or bypass alarms REAR PORTS amp SWITCHES 1 Serial Communications Port This port allows remote monitoring of 1000 2100 VA 3000 VA alarm conditions See next page 2 Optional SNMP Ports The SNMP Simple Network Management Protocol option provides intelligent Ethernet or Token Ring network communications With SNMP software it provides comprehensive remote UPS control and monitoring 3 Battery Charger Switch 3000 VA ONLY This recessed switch supplies battery charger power even when the front power switch is OFF Turn OFF for initial start up turn ON for normal operation after initial start up 4 Output Voltage Selector 83000VAONLY This switch on the rear of the unit allows choice of 208 or 240 VAC NOTE The output must match the input if bypass
15. high UPS Allow a few minutes for the UPS to cool temperature down Check for adequate ventilation Restart the UPS Improper utility outlet wiring or ground fault All front Call maintenance department or a qualified panel indicators flash with electrician to correct the problem no power supplied to loads UPS output short circuited or overloaded Shutdown load equipment disconnect UPS AC LED flashes Utility voltage too high and call your maintenance department or a qualified electrician to correct outlet wiring or ground fault Bam soune Uti poweriae Limited time before UPS shutdown amp alarm sounds Utility power failure Terminate critical applications and save data Shutdown all loads and the UPS Plug UPS in and turn ON for a minimum of Reduced battery time 4 hours to recharge batteries charge due to age Check for UPS overload blocked ventilation Alarm sounds twice openings and excessively high room UPS overheated temperature high speed UPS shutdown LED amp diagnos A light UPS shutdown LED amp diagnosti light UPS shutdown LED amp diagnos F light UPS shutdown LED amp diagnos Q light ault ic LE ault ic LE ault ic LE UPS critically overheated Check for UPS overload blocked ventilation openings and excessively high room temperature Allow UPS to cool for 30 minutes the restart UPS overload Reduce loads to UPS Consult Liebert D Tec
16. hnical Support UPS shutdown fault Internal fault Requires service Contact Liebert Technical LED amp diagnostic LED Support C light UPS shutdown fault UPS short circuit Remove cause of short circuit if obvious Bagari teo Check loads connected to UPS for defects D light or shorts UPS shutdown fault Internal fault Requires service Contact Liebert Technical LED amp diagnostic LED Support E light Plug UPS in and turn ON for a minimum of Battery charge exhausted 4 hours to recharge batteries We advise you not to run critical application during this period Shut down command sent If inadvertent check system for correct D to communication port cabling 11 MAINTENANCE The UPStation GX UPS normally requires very little maintenance Keep the sealed maintenance free batteries fully charged to obtain designed life of 5 years During normal operation the UPS continuously charges the batteries To store or deactivate the UPS for any length of time charge it no less frequently than once every 6 months Switch UPS OFF when not connected to the utility AC To charge the batteries connect the UPS to the utility and turn it ON for a minimum of 4 hours Replace batteries after 5 years or sooner if exposed to adverse conditions Refer battery replacement to qualified service personnel only Heed cautions at the front of this manual at all times Call Liebert Technical Support at 1 800 222 5877 fo
17. is enabled 5 Optional Remote Emergency Power Off REPO Port 3000VAONLY The REPO option allows remote UPS shutdown in the event of emergencies 6 Control DIP Switches 3000VAONLY The DIP switches control output frequency bypass and number of battery cabinets Slide switches to the right to turn them ON to the left to turn them OFF Switch ON OFF 1 50 Hz 60 Hz 2 Enable Bypass Disable Bypass 3 2 battery cabinets 4 3 battery cabinets patel cabinet 5 Keep ON 6 8 Keep OFF MONITORING amp COMMUNICATIONS The UPStation GX UPS is capable of communicating with a stand alone computer system LAN server UNIX host or terminal via an EIA standard DB 25 female connector located on the rear of the unit The UPS typically uses this capability to provide status and power monitoring information to the computer system For instance during a power outage the operating system uses UPS information to automatically save information in buffers close files and shutdown operations in an orderly fashion prior to exhausting the UPS battery Depending on your system configuration the operating system may monitor power via the UPS and control UPS operations using a variety of interface hardware The UPS communication interface port provides the signals and control pins required by monitoring and control applications Connect the UPS and your computer system with the appropriate cable and SiteNet 1 shutdo
18. n the event of over temperature or fault within the UPS Audible and visual alarms indicate Bypass operation The UPS remains on Bypass until the user resets the power switch by turning it OFF then ON CAUTION Resetting the power switch causes loss of power to the outlet receptacles Perform all necessary shutdown procedures on critical loads before resetting the power switch BEFORE INSTALLATION Unpack UPS carefully noting the packing method Retain packaging To return the UPS re pack as originally shipped CAUTION The units are heavy The UGX1000RT 60 weighs 71 lbs the UGX1500RT 60 weighs 83 Ibs the UGX2100RT 60 weighs 97 lbs Take proper precautions when lifting or moving them Inspect UPS for freight damage Contact the carrier and or your distributor concerning freight damage or missing parts UPS Configuration Turn UPS On Off switch OFF The manufacturer ships the UPStation GX from the factory in tower configuration If this suits your application follow the tower installation instructions If your application requires rackmount configuration follow the rack mount installation instructions GENERAL INSTALLATION GUIDELINES NOTE Use a utility receptacle with bonded neutral and ground to prevent UPS damage Damage due to faulty utility wiring is not covered by product warranty The UPS will not start with an incorrectly wired input AC supply for example if the line and neutral wires are reversed In this situation the UPS
19. nderneath rackmount Unpack cabinet s carefully noting packing method Retain packaging To return cabinet s i re pack as originally shipped Inspect them for l freight damage Contact carrier and or distributor ren about freight damage or missing parts CAUTION Battery cabinets are heavy The 7 UGX48VBATT and UGX96VBATT weigh 139 Ibs the UGX72VBATT weighs 111 lbs Take je proper precautions when lifting or moving them ane Power Banery Connector Cable Connector 2 Follow UPS installation procedures for your application tower or rackmount Each battery cabinet has a power cable in the rear Once the cabinet s are in place plug the battery cabinet power cable into the UPS battery connector For two battery cabinets plug the power cable of the second battery cabinet into the battery connector of the first battery cabinet UPS OPERATION Normal Mode Normally the utility supplies UPS power The UPS filters and processes this power to provide computer grade power to the loads The UPS also float charges the batteries and displays the UPS output load on the LOAD bar Battery Mode If the UPS senses low voltage or a power outage the battery instantly supplies UPS power In battery mode the UPS sounds an alarm turns OFF the AC indicator and lights the BATTERY indicator In this mode the CAPACITY bar displays battery power remaining before depletion Initially th
20. operations cause data loss or even damage equipment The UPS protects against many of these disturbances It smoothes out voltage variations and during complete power failure supports equipment long enough for an orderly shutdown These compact units are available in three ratings 1000 1500 and 2100 VA This manual includes specifications for each model The UPStation GX is a compact on line UPS that supplies critical equipment with continuous premium computer grade power An On line UPS continuously generates and regulates output power whether utility power is present or not In contrast a standby UPS only generates output power when utility power fails The UPStation GX supplies critical equipment with clean sinewave power to simulate utility generated power Equipment like computers monitors printers phone systems and laboratory instruments operate best on sinewave power The LED bar displays indicate percentage load and battery capaci two levels of alarms during battery operation self diagnostics and a combination battery test alarm silence switch To allow communications between the UPS and a LAN server or other computer system the UPStation GX UPS is equipped with an RS 232 interface port This port provides detailed operating information including voltages currents temperature and alarm status to the host system when used with Liebert SiteNet soft ware In addition this port allows remote
21. oration assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions Environmental systems close control air s conditioning jan 15 to 60 tons 1996 Liebert Corporation All rights Power conditioning and UPS with power ranges reserved x throughout the world from 250 VA to more than 1000 kVA Specifications subject to change Integrated systems that provide both without notice environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service and support through more than 100 service centers around the world and a 24 hour Customer Response Center Liebert and the Liebert logo are registered trademarks of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners Printed in U S A SL 23130 5 96 Rev 1 0 16
22. r Indicator This 5 segment LED indicates the approximate battery capacity during battery mode or a battery test All segments light at full battery capacity and extinguish one by one in 20 increments until complete battery depletion Normally all segments should light after 4 hours recharge See battery run time curves During normal operation battery capacity below 60 causes the CAPACITY bar to flash its three left most LED segments To determine actual battery capacity depress the Battery Test switch Typically the CAPACITY bar flashes following a power outage when batteries have not fully recharged If after 4 hours of recharge or in the test mode the 3 left most LEDs still flash contact Liebert Technical Support at 1 800 222 5877 and ask about replacement batteries 4 Battery Indicator amber The UPS lights this indicator and sounds and alarm when in battery mode or during a battery test 5 Fault Indicator red The UPS lights this indicator when it detects a fault The UPS flashes this indicator and sounds an alarm during over temperature conditions 6 AC Indicator green When lit this LED indicates input utility power is available and the UPS power switch is ON UPS flashes this LED and sounds an alarm with high input voltage 7 Battery Test and Alarm Reset Switch Normal Operation Depress this switch to test battery capacity The UPS operates in battery mode as long as the switch is depressed Observe how many se
23. r battery replacement instructions Battery Safety Precautions WARNING Battery maintenance procedures expose hazardous live parts Refer servicing to qualified personnel only CAUTION Call a qualified battery supplier to dispose of batteries according to local environmental laws Do not open or mutilate batteries Released electrolyte is harmful to skin and eyes and may be toxic BATTERY RUN TIMES 1000 VA RUN TIME Mins 1500 2100 VA RUN TIME Mins Internal Internal Cabinet Internal 2 Cabinets LJ 20 30 40 50 60 70 80 90 100 20 30 40 50 60 70 80 90 100 PERCENT LOAD PERCENT LOAD 3000 VA RUN TIME Mins One External Cabinet Two External Cabinets umeme Three External Cabinets 20 30 40 50 60 70 80 90 100 PERCENT LOAD La 1000 2100 VA GX SPECIFICATIONS Model Rating VA Watts 2100 VA 1500 W INPUT Voltage 120 VAC 2 Wire Plus Ground Voltage Range 10 20 transfer to battery at 21 Frequency 60 Hz 5 Current 16 Amps Power Factor Minimum 94 at Full Load Voltage Transients Meets Requirements of IEEE 587 Category A Power Cord 6 1 88m w NEMA 5 15 Plug 15 A 6 1 88m w NEMA 5 20 Plug 20 A OUTPUT Voltage and Current 120 VAC at 17 5 A Voltage Regulation 3 Frequency Locked to Utility 60 Hz 1Hz Output Distortion Maximum 5 THD with Non Linear Load Waveform Sinewave Overload 1
24. the front of the UPS 4 Gently lay the unit on its right side when viewing the unit from the front and remove the six rubber feet Retain the screws from the two front feet to fasten securing flanges Flange Screws 5 Liebert offers kits for UPS rail or slide H installation Install the UPS on rackmount omg rails slides or shelves Use the installation 6 De instructions which came with your rackmount Top View kit Rear View with top cover off 6 Switch OFF load equipment and plug it into the UPS output receptacles Plug UPS into a dedicated and grounded wall receptacle properly protected by a circuit breaker or Retain Screws fuse Use a 15 amp device for the 1000 VA fonyironttwotest or 1500 VA units and a 20 amp device for 2100 VA units Turn ON the UPS Bottom View TOWER INSTALLATION Turn the On Off switch on the front of the unit OFF With load equipment switched OFF plug it into the UPS output receptacles N Plug UPS into a dedicated and grounded wall receptacle properly protected by a circuit breaker or fuse Use a 15 amp rated device for 1000 or 1500 VA units and a 20 amp device for 2100 VA units Turn ON the UPS OPTIONAL BATTERY CABINETS Connect up to two 2 optional battery cabinets to the UPS for additional run time DO NOT connect more than two 2 battery cabinets to UPS Cabinets fit beside UPS towers and u
25. wn software sold separately Consult your local Liebert representative to determine the correct software kit for your application Intelligent Communications Serial Communications Port Connection not to exceed NEC Class 2 limits The DB 25 port provides several signals listed below by pin number FUNCTION Reserved RxD TxD Not Used On Inverter active low On UPS active closed On battery active closed Common for pins 15 16 18 24 On battery active open UPS shutdown active high Not Used Not Used Signal ground Not Used Low battery relay contact common Low battery relay contact active opened Low battery relay contact active closed Shutdown active low Not Used active low Not Used Not Used On Bypass active closed Altos specification tri voltage signal OO NN ny op fo e k N 13 Power failure active high In addition to power monitoring information signals the UPS communicates intelligently with LAN servers UNIX hosts or other connected computer systems Optional SiteNet 2 software allows these additional capabilities Quantitative monitoring of utility and UPS power Quantitative monitoring of internal UPS parameters Periodic tests of battery quality and replacement notification Timed and delayed shutdown of the UPS Logging of power disturbances and anomalies Consult your Liebert sales agent for more information about SiteNet