Liebert II User's Manual

image

Contents

1. Monitoring Features S Package C Package D Package LED Status Indicators Vv Vv Vv Built In Component Integrity Test BICIT Vv Vv v Sonic Alarm va Vv Vv Form C Dry Contacts Vv Vv Vv Surge Counter Vv Vv Swell Counter Vv Remote Monitor Panel Optional Optional Optional Figure 4 Operation controls and indicators ENA PHASE C L O NEUT GND O DISABLE URG Lo sua SWELL COUNTE RESET Status LED Indicators Green and red LEDs for each protected phase provide a visual status summary of all surge modules within device Full Protection LEDs Green LEDs are illuminated only when all surge components are at 100 percent efficiency Reduced Protection Red LED illuminated only when protection has been reduced by off line surge components such as open fuse links Built In Component Integrity Test BICIT While the monitoring circuitry provides visual status during operation the built in test circuitry will verify that every fuse link and associated MOV is operational The built in test may be operated easily by simply pressing one push button during normal operation The BICIT cycles through each phase bank including neutral ground sending out a test request signal to all modules If all fuse links are in intact the red reduced pro tection LED for the particular bank in test will illuminate for a two to four seconds Should this light stay lit for more than 5 seconds one m
2. When replacing surge modules other components should be inspected for damage and replaced if necessary Standard electrical troubleshooting procedures should be used to isolate problems other than failed surge current diverter modules When replacing components for continued proper operation and safety replace only with identi cally rated components Please contact factory for information on replacement parts Preventive Maintenance Inspection and Cleaning Periodic system inspections cleaning and connection checks are recommended to ensure reliable system performance and continued surge transient protection It is difficult to establish a schedule for preventive maintenance since conditions vary from site to site Inspections for failed surge current diverter modules using available diagnostics should be done routinely weekly or monthly Troubleshooting Service amp Maintenance 6 0 LIMITED WARRANTY This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordi nary course of each purchaser s business General Liebert s products are in our opinion the finest available We take pride in our products and are pleased that you have chosen them Under certain circumstances we offer with our products the following Five Year Warranty Against Defects in Material and Workmanship Please read your Warranty carefully This Warranty sets forth our responsibilities in the unlikely event of d
3. 0 Liebert POWER PROTECTION Interceptor Il Transient Voltage Surge Suppressor Installation Operation 8 Maintenance Manual 1 0 2 0 2 1 2 2 2 3 2 4 2 5 3 0 3 1 3 2 4 0 5 0 5 1 5 2 5 3 5 4 6 0 TABLE OF CONTENTS INTRODUCTION o aaa 1 UNPACKING AND INSTALLATION 00 0c cece eee eee eee eee eee 2 Unpacking and Preliminary Inspection 0 0 00 cece eee eee eens 2 Handling Considerations LL 2 Storage a weet OR eats ee ace tie Boh ate hee Dees te DS Sc is 2 Location Considerations nuns sca Bik ew Me AR ee ett abate ee 2 2 4 1 Equipment Performance 0 aia nieh cee een teen eens 2 Door Closing Adjustments LL 2 ELECTRICAL CONNECTIONS 000 cece cocoa 4 Voltage Ratings and Power Source Configurations 00 cece eee eee eee 4 Parallel Connection see Figures 2 and 3 4 3 2 1 System Grounding and Bonding LL 7 OPERATION ati a di nta 8 TROUBLESHOOTING SERVICE amp MAINTENANCE 0 cece eee eeeeeeeeeueee 10 Troubleshooting iii geiko E ae ys Os Bo Swab See OE OMG Soe 10 EC oy o lidi est dele pe dire calli pe o e ale oo 10 Corrective Mamtenanee ss 21 0 0 lau elia LS AAA EAN ia 10 Preventive Maintenance Inspection and Cleaning o oooooooooooooo 10 LIMITED WARRANTY 505 dii acs al cd a iw eee ae i Ele 11 Figure 1 Figure 2 Figure 3 Figure 4 Table 1 Table 2 Table 3 Table 4 FIGURES Typical cabinet data Form
4. C contact and Wiring 0 0 tenes Typical parallel connections without internal rotary disconnect o o ooooooooo Typical parallel connections with internal rotary disconnect LL Operation controls and indicators TABLES Units with or without internal service disconnect switch o oooooooooooooooooo Suggested wire and breaker size eee enn nee ee ene Voltage ratings and power source configurations 0 0 0 60 c cee eee nes Monitoring features 1 0 INTRODUCTION The Liebert Interceptor II Series Transient Voltage Surge Suppressor TVSS is a high quality high energy surge current diversion system designed to protect sensitive equipment from damag ing transient voltage surges Proper installation is required for maximum system performance The installer should perform the following steps to ensure a high quality installation The entire installation manual should be read before starting installation These instructions do not replace national or local electrical codes Check applicable electrical codes to ensure compliance Installa tion of the Liebert TVSS system should be performed only by qualified personnel Introduction 1 2 0 UNPACKING AND INSTALLATION 2 1 2 2 2 3 2 4 2 4 1 2 5 Unpacking and Preliminary Inspection 1 Inspect the shipping crate s for damage or signs of mishandling before unpacking the unit 2 Remove any securing bands and cardboa
5. Switch TVSS units must be connected to the load side of the main service discon nect or load side of a protected circuit s disconnecting means Interceptor II SI Models with an R designator in the part number are equipped with an inter nal disconnect switch that can be used to de energize the unit s transient surge suppressing com ponents for servicing Table 3 Voltage ratings and power source configurations Nominal Operating Voltage Model Voltage Source Configurations L N L L L G Code e a 120 N A 120 120N 230 N A 230 230N 78 G Single Phase L N 2W G ere NA 277 277N Si N A 208 208 208L aid N A 240 240 240L Single Phase L L 2W G N A 480 480 480L f 120 208 240 120 120S e A e 230 400 460 230 230S Split Phase 3W G 277 480 554 277 277S gt A N A 208 208 208D ai N A 240 240 240D Three Phase Delta 3W G N A 480 480 480D ras 120 240 120 240H E 240 480 240 480H Three Phase Delta Hi Leg 4 W G A 120 208 120 120Y Ta 230 400 230 230Y E E 277 480 277 277Y Three Phase Wye 4W G For other voltages or source configurations consult factory Electrical Connections 5 Figure 2 Typical parallel connections without internal rotary disconnect punog s seyd e1nan Neutral Protected Panel and straight as Transient Ground Wire should be less than 5
6. feet possible Figure 3 Typical parallel connections with internal rotary disconnect punolJe seseud ennen Protected Panel Wire should be less than 5 feet and straight as li possible To gt Protected Loads Liebert Surge Protective Device To Protected Loads Liebert Surge Protective Device 6 Electrical Connections 3 2 1 System Grounding and Bonding The performance and safety of any TVSS system is dependent on proper grounding and bonding Grounding is required primarily for safety Correct implementation also enhances equipment per formance Incorrect grounding can reduce or impede the TVSS s operation All electrical circuits to the TVSS must include an equipment grounding conductor as required by the NEC and local codes An insulated grounding conductor is required in addition to any metallic raceway that may be used as a grounding conductor For parallel connected TVSSs the grounding conductor should be the same wire size as the associated power conductors Grounding conductors must be routed with the associated power conductors in the same raceway conduit When metallic raceways are used adequate electrical continuity must be maintained at all race way connections particularly raceway terminations to the electrical enclosures The use of isolating bushings or other means to interrupt a metallic conduit ru
7. TRICT LIABILITY TORT OR OTHERWISE Miscellaneous NO SALESPERSON EMPLOYEE OR AGENT OF LIEBERT IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY Warranty terms may be modified if at all only ina writing signed by a Liebert officer This Warranty is effective as of the date of Liebert receipt of payment and supersedes all previous warranties Liebert reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others In the event that any provision of this Warranty should be or becomes invalid and or unenforce able during the warranty period the remaining terms and provisions shall continue in full force and effect This Warranty is given in and is intended to be construed under the laws of the State of Ohio This Warranty represents the entire agreement between Liebert and User with respect to the subject matter herein and supersedes all prior or contemporaneous oral or written communica tions representations understandings or agreements relating to this subject Limited Warranty O Liebert Interceptor Transient Voltage Surge Suppressor The Company Behind the Products With more than 1 000 000 installations around the globe Liebert is the world leader in computer protection systems Since its founding in 1965 Liebert has developed a complete range of support and protection systems for sensitive electronics Environmental systems close control air condi
8. der this warranty to such components Descriptions Liebert warrants for the period and on the terms of the Warranty set forth herein that the Liebert product will conform to the descriptions contained in Liebert final invoices orders and Liebert product brochures Liebert does not control the installation and use of any Liebert product Accordingly it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE Obtaining Performance Under This Warranty Within a reasonable time but in no case to exceed thirty 30 days after User s discovery of a defect User shall contact Liebert and request a return authorization number User shall ship the product with proof of purchase to Liebert freight prepaid Liebert products shipped to Liebert without a return authorization number will be refused and returned freight collect to User at User s expense Liebert products shipped by User to Liebert which have incurred freight damage due to User s improper packaging of the product will not be covered by this Warranty and any repairs or replacement parts components or products needed will be invoiced in the full current price amount and returned freight collect to User Subject to the limitations specified herein Liebert will repair or replace at its option without charge for Liebert labor or materials subsequent to its inspection and F O B Liebert facility the Liebert product ship
9. e wall or mounting surface Be sure all mounting screws are tightened securely 2 Unpacking and Installation Figure 1 Typical cabinet data Form C contact and wiring a ice i Uy rad i E Table 1 Units with or without internal service disconnect switch Model Dimensions Inches Weight Series Application Connection A B Cc D E F Ibs Wire Lugs 16 12 9 16 75 10 0 31 35 S1016 All voltage 1025 configurations Disconnect 4g 46 9 16 75 14 0 31 45 optional S1032 Wire Lugs 16 16 9 16 75 14 0 31 45 S1040 ar db Disconnect configurations S1050 g optional 20 16 9 21 25 10 0 44 55 Wire Lugs 20 16 9 21 25 10 0 44 55 S1060 All voltage SI075 configurations Disconnect 29 29 9 21 25 14 0 44 85 optional Wire Lugs 20 20 9 21 25 14 0 44 85 S1100 All voltage configurations Disconnect 20 24 9 21 25 18 0 44 95 optional i Single Phase L N Single Phase L L Split Phase Three Phase Wye Three Phase Delta Three Phase Delta Hi Leg First five digits of model number Unpacking and Installation 3 3 0 ELECTRICAL CONNECTIONS 3 1 3 2 All electrical connections should be installed only by a qualified licensed electrician All wiring must comply with the National Electrical Code NEC and applicable local codes N CAUTION Verify that all power circuits are de ener
10. efect and tells you how to obtain performance under this Warranty Five Year Limited Warranty Against Defects In Material And Workmanship Liebert products covered Interceptor II and Interceptor Hybrid Advantage SAD Series TVSS Terms of Warranty As provided herein the Liebert product is warranted to be free of defects in material and work manship for a period of five 5 years from the date of delivery of the product to User The delivery date will be determined only from the Liebert bill of lading If any of the Liebert products fail to conform to the warranty within the warranty period Liebert at its option will furnish new or fac tory remanufactured parts for repair or replacement of that part Warranty Extends to First Purchaser for Use Non transferable This Warranty is extended to the first person firm association or corporation for whom the Lie bert product specified herein is originally installed for use in the United States the User This Warranty is not transferable or assignable without the prior written permission of Liebert Assignment of Warranties Liebert assigns to User any warranties which are made by manufacturers and suppliers of compo nents of the Liebert product and which are assignable but Liebert makes NO REPRESENTA TIONS as to the effectiveness or extent of such warranties assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no cover age un
11. gized and locked out before making electrical connections Voltage Ratings and Power Source Configurations Before making connections to the unit verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source See Table 3 for voltage rating applications with typical power source configurations Surge Voltage Ratings To obtain the suppression voltage ratings SVRs as obtained by Underwriters Laboratory Incorporated in accordance with the Standard for Safety Transient Voltage Surge Suppressors TVSS Standard 1449 Second Edition dated August 15 1996 marked on this product 2 AWG wire must be utilized to connect the unit to your facilities power grid Connections made with conductors other that 2 AWG may result in different SVRs Circuit Ampacity Limitations Representative samples of this product have been investigated by Underwriters Laboratories Incorporated to withstand without exposing live circuits or compo nents at system voltages and fault currents of up to 200 000 AIC as described in the Standard for Safety Transient Voltage Surge Suppressor TVSS Standard 1449 Second Edition dated August 15 1996 Parallel Connection see Figures 2 and 3 With parallel connection the length of the wiring to the Transient Voltage Surge Suppressor TVSS unit must be minimized for best performance Wires should be as short and straight as possible To reduce the wir
12. ing impedance to surge currents the phase neutral if required and ground conductors are recommended to be twisted together and routed in the same raceway conduit Avoid any sharp bends in the conductors Wire Sizing With parallel connection the size of the wiring to the TVSS unit is independent of the protected circuit s ampacity Suggested wire size based on the unit s transient surge current capabilities are show in the table below Table 2 Suggested wire and breaker size Model Series Outline Drawing Wire Size Breaker Size SI016 SI025 Wire Lugs 82010 81 0 4a 1016 SI025 Disconnect 82011 8 1 0 40A 0320 S1050 Wire Lugs 82012 4 1 0 80A 0320 S1050 Disconnect 82013 4 1 0 80A S1060 SI075 Wire Lugs 82014 4 1 0 80A S1060 SI075 Disconnect 82015 4 1 0 80A S1100 Wire Lugs 82016 4 1 0 80A 1100 Disconnect 82017 4 1 0 80A NEC Articles 280 21 and 22 require surge arrestor connecting conductors to be at least 14 copper or 12 aluminum Overcurrent Protection The TVSS unit conducts practically no current under normal opera tion and conducts only very short duration transient surge currents External overcurrent protection is not specifically required by NEC Article 280 nor is it desired since it impedes the performance of the transient voltage surge suppressor If fusing is required please consult factory for recommendations 4 Electrical Connections Disconnect
13. m and its connections are normal the unit should be repaired At this point consult the factory having available the following information Unit identification number the model and serial numbers detailed on the data label on the upper left hinge side of the enclosure Nature of problem including status of all status indicators and alarms Service N WARNING ONLY QUALIFIED PERSONNEL SHOULD PERFORM MAINTENANCE ON THE SYSTEM HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT DURING NORMAL OPERATIONS ELECTRICAL SAFETY PRE CAUTIONS MUST BE FOLLOWED WHEN SERVICING THIS UNIT TO PREVENT RISK OF ELECTRICAL SHOCK TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE SERVICING UNIT FOR SERVICING ASSISTANCE CONTACT YOUR LOCAL LIEBERT SALES REPRESENTATIVE OR LIEBERT AT 800 288 6169 OR 607 724 2484 Corrective Maintenance The Liebert Interceptor II TVSS is designed for years of trouble free operation However even the most reliable equipment may fail under abnormal conditions Diagnostic indicators are provided to indicate when the unit needs replacement see 4 0 Opera tion for details To ensure continuity of surge protection failed units should be replaced at the earliest convenient service opportunity On systems rated greater than 100 KAmp surge capacity and larger parallel modules provide redundant transient surge protection such that any single module failure does not completely eliminate the TVSS protection
14. n is a potential safety hazard and is not recommended Grounding Electrode Transient voltage surge suppressors do not discharge all surges to ground earth Transient voltage surge suppressors divert the surge current back to its source to complete the electrical circuit In the case of lightning whose potential is developed with respect to the earth the TVSS diverts the surge current to the grounding electrode earth connection However for most transient surges which are developed by switching loads the TVSS diverts the surge current back to its source without involving the grounding electrode For proper TVSS performance the service entrance grounding electrode system must comply with the NEC by having all available electrodes building steel metal water pipe driven rods concrete encased electrodes etc properly bonded together and connected to the power system grounding N CAUTION The use of a separate grounding electrode to ground the TVSS defeats the effectiveness of the TVSS is a potential safety hazard and may cause equipment damage The arrestor grounding conductor must be connected per NEC 280 21 N CAUTION a For proper and safe operation the neutral if provided must be reliably connected to the neutral of the source Failure to provide a reliable neutral connection may result in module failure Electrical Connections 7 4 0 OPERATION Table 4 Monitoring features
15. nces Service clearance is needed only at the front of the unit Thirty six inches 36 in or 914 mm minimum is recommended Equipment Performance For maximum system performance the unit must be located as close to the protected circuit as practical to minimize interconnecting wiring length For optimum transient surge protection coordinated surge suppression should be applied at the service entrance and all other electrical connections to the building telephone CATV etc at known surge generating loads within the building large motors arc welders switched capacitors etc as well as at sensitive electronic loads such as computers electronic appliances solid state motor drives etc For interconnected electronic loads such as by way of data cabling transient surge suppression should also be applied to the interconnecting wiring data cables Mounting Unit is intended to be wall mounted Refer to Figure 1 or unit submittal drawings for typical mounting dimensions and weight Door Closing Adjustments If the surface on which the enclosure is mounted is not flat the door may not open and close prop erly Also if heavy equipment is mounted on a large door the door may sag slightly If the top of the door strikes the lip that extends around the body opening place metal shims behind the mounting foot that is located at the bottom of the enclosure and closest to the door hinge Place the shims between the mounting foot and th
16. nter is AC coupled and rejects transient voltages longer than 100us Swell Counter The Swell Counter monitors all line to line and line to neutral voltages It is fac tory set to record whenever the peak voltage on any normal mode exceeds the MCOV of the TVSS for more than 100us This allows the counter to record temporary line over voltages that many result from utility switching line regulation problems etc Remote Monitor Panel A remote monitor panel is available to provide unit status and alarm information at a location up to 500 feet away from the Liebert TVSS System See Table 4 Oper ation of the Remote Monitor Panel is similar to the unit system monitor panel The Enable posi tion of the switch is the normal position which allows audible alarm operation The Disable switch position silences the audible alarm The Test position tests the audible alarm and indica tor lights The remote monitor panel requires an external source of power Standard units are fur nished with a six foot line cord with a 5 15P NEMA plug Operation 9 5 0 TROUBLESHOOTING SERVICE amp MAINTENANCE 5 1 5 2 5 3 5 4 Troubleshooting If status failure indication occurs or Form C relay has changed states a qualified electrician should first determine if the systems voltage and proper phasing exists If the Interceptor II TVSS remains in an alarm condition once the technician is satisfied that the electrical syste
17. odule in that bank has at least one open fuse link While testing the Test LED will illuminate Also during the built in test sequence the alarm should sound for each bank Pressing the alarm disable switch before or during the test will silence the alarm Sonic Alarm TIf one or more of the surge modules require replacement an audible alarm is acti vated to draw attention to the fact that repair service is required to restore the system to normal operation An audible alarm disable button is provided to silence the alarm The system will auto matically reset itself after repair 8 Operation Form C Dry Contacts Dual summary alarm Form C 1 N O and 1 N C relay contacts are provided for remote indication of each failed surge current modules The summary alarm contacts terminals are located on the PC board inside the unit Contacts are rated for 5 amps at 240 VAC with a power factor of 1 0 The states of the Form C Dry Contacts are determined with power applied Connection to the Form C Dry Contacts are provided by 18 AWG wires attached to the status module The yellow wire is for connection to the NO contact The blue wire is for connection to the NC contact The orange wire is for connection to the common point of the Form C Dry Con tacts Surge Counter The Surge Counter monitors line to ground transient voltages This circuit totalizes all surges that deviate from the line sine wave envelope by more than 125 volts The cou
18. ped to Liebert with a return authorization number and warranted hereunder which does not conform to the Warranty Replacement parts components or products shipped to User prior to Liebert receipt and inspection of the product claimed to be defective shall be invoiced in the full current price amount and shipped freight collect F 0 B Liebert facility War ranty coverage will be extended only after Liebert receipt of the claimed defective product within thirty 30 days of shipment of any replacement parts components or products if applicable Lie bert inspection discloses the claimed defect and the returned product shows no signs of treatment or use which would void the coverage of this Warranty Limited Warranty 11 Items Not Covered By Warranty THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse improper application wrong or inadequate electrical current or connection inadequate water or drain ser vices negligence inappropriate on site operating conditions corrosive atmosphere repair by non Liebert designated personnel accident in transit tampering alterations a change in location or operating use exposure to the elements Acts of God theft or installation contrary to Liebert rec ommendations or specifications or in any event if the Liebert serial number has been altered defaced or removed THIS WARRANTY DOES NOT COVER shipping costs installation costs circuit breaker reset ting or maintenance or ser
19. rd packing and inspect the unit for any obvious shipping damages 3 If any damage as a result of shipping is observed immediately file a claim with the shipping agency and forward a copy to your local Liebert sales representative Handling Considerations Larger units are bolted to a shipping pallet to facilitate handling by forklift or pallet jack Check the size and weight Refer to the cabinet data furnished with the unit Typical size and weights are referred to in Table 1 Storage The unit should be stored in a clean dry environment Storage temperature range is 55 C to 85 C 67 F to 185 F Care should be taken to avoid condensation All packing and shipping materials should be left intact until the unit is ready for final installation If the unit has been stored for an extended period of time the unit should be cleaned and carefully inspected before placing into service Location Considerations Environment The unit is designed for operation indoors in ambient temperatures of 40 C to 60 C 40 F to 140 F with a relative humidity of 0 to 95 non condensing The unit is provided in an industrial use enclosure that is dust tight and drip tight The unit should not be installed in areas with excessive dust corrosive vapors flammable materials or explosive atmospheres Audible Noise The audible noise of the unit is less than 40 dBA at five feet which allows its placement in almost any room Service Cleara
20. tioning from 1 5 to 60 tons Power conditioning and UPS with power ranges from 250 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service and support through more than 100 service centers around the world and a 24 hour Customer Response Center Liebert Corporation Liebert Europe 1050 Dearborn Drive Via Leonardo Da Vinci 8 P O Box 29186 Zona Industriale Tognana Columbus OH 43229 35028 Piove Di Sacco 800 877 9222 Phone Italy 614 841 6022 Fax 39 049 9719 111 Phone 39 049 5841 257 Fax Liebert Asia Liebert Web Site 23 F Allied Kajima Bldg http www liebert com 138 Gloucester Road Wanchai Hong Kong 852 2 572 2201 Phone 852 2 831 0114 Fax While every precaution has been taken to ensure the accuracy and completeness of this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions O 2001 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert and the Liebert logo are registered trademarks of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners Printed in U S A SL 22010 Revised April 2001
21. vice items and further except as provided herein does NOT include labor costs or transportation charges arising from the replacement of the Liebert product or any part thereof or charges to remove same from any premises of the User THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY use of the Liebert product in combination with any electrical or electronic components circuits systems assem blies or other materials not furnished by Liebert Liebert does NOT warrant the suitability for use or the results of the Liebert product in combination with the products of others REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD Limitations THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PUR POSE USER S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE LIE BERT PRODUCT AS SET FORTH HEREIN IF USER S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION LIEBERT RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED ONE TIMES THE NET PRODUCT PURCHASE PRICE IN NO EVENT SHALL LIEBERT ASSUME ANY LIABILITY FOR INDIRECT SPECIAL INCI DENTAL OR ECONOMIC CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER INCLUDING WITHOUT LIMITATION LOST PROFITS BUSINESS INTERRUPTION OR LOSS OF DATA WHETHER ANY CLAIM IS BASED UPON THEORIES OF CONTRACT NEG LIGENCE S