Home
Kidde Pro line User's Manual
Contents
1. 240108 C moa J rosiema Prova PovRWS Po orma o 56 a 2005740 21005740 Ps o 340081 340173 340173 340173 KIDDE RESIDENTIAL amp COMMERCIAL KIDDE PRO LINE STORED PRESSURE DRY CHEMICAL PORTABLE EXTINGUISHER DIAGRAM ALUMINUM VALVE The following spares parts are available for the Kidde Pro Line 1 Hose nozzle assembly 2 Syphon tube assembly excludes o ring 3 Valve assembly includes handle amp lever attached amp valve body excludes o ring 4 O ring kit includes valve o ring syphon tube o ring stem assembly stem assembly spring 5 Wall hanger 6 Retention bracket 7 Pull pin 8 Pressure gauge 9 Hanger loop and screw 10 Hose strap P a 21005720 21005720 __ om 6 e 254082 o Mode Pro 20 4 Pro 20 5 Part Number 466206 466206 440126 440330 2 21005553 21005553 14260 14260 292474 292474 ie aoe aie sae EO 14 KIDDE RESIDENTIAL amp COMMERCIAL KIDDE PRO SERIES ST
2. Operation Instructions 1 Remove the extinguisher from its hanger or bracket 2 Pull and remove the ring pin breaking the visual tamper seal 3 Using the extinguisher carrying handle transport the unit to a safe position upwind of the fire 4 Remove the hose nozzle from the retention clip if equipped and while keeping the extinguisher in a vertical position aim the nozzle at the base of the fire 5 Approach fire from upwind to within approximately 8 to 12 feet of the front edge of the fire WARNING Failure to start back at a sufficient distance from the front edge of the fire or to use an adequate sweeping tempo of the agent discharge stream could cause splashing and or scattering of the burning material 6 Starting back from this distance squeeze the operating lever fully to initiate the agent discharge 7 Apply the dry chemical agent discharge in a side to side sweeping manner being careful not to splash or scatter the fuel Operators may advance closer as control of the fire is gained however they should avoid stepping into the fuel or fire area 8 After fire extinguishment stand by and be prepared to address any re flash 9 Once the fire is out and has cooled ensure the fuel is properly removed and disposed of in accordance with any local handling requirements KIDDE RESIDENTIAL amp COMMERCIAL After Use Instructions Note Fire extinguishers should always be recharged immediately after any use 1 I
3. WARNING To prevent injury or death always ensure all pressure is properly relieved from an extinguisher prior to attempting any service repair or recharge 1 Ensure extinguisher is installed in its proper location and that it is readily accessible Most Kidde dry chemical extinguisher models are approved for temperature ranges between 40 F to 120 2 Remove extinguisher from its hanger or bracket and ensure that all mounting hardware is properly installed secure and in good operating condition 3 Externally examine unit for any signs of damage that might prohibit service or dictate the need for any special maintenance repair procedures 4 The periodic re hydrostatic test date of the extinguisher should be checked The maximum periodic interval for Kidde dry chemical stored pressure hand portable fire extinguishers is 12 years Note NFPA 10 requires stored pressure dry chemical fire extinguishers having a 12 year periodic hydrostatic test interval to be emptied and internally examined every 6 years Should this 6 year tear down requirement be due refer to the recharge section of this manual for recommended procedures 5 Unthread and remove the discharge nozzle and or hose assembly from the cylinder valve assembly and visually ensure it is not plugged or obstructed Closely examine the discharge nozzle and or hose assembly including hose crimp couplings for any damage wear or conditions which might effect their proper
4. are written and intended to be used by those personnel already familiar with standard industry fire extinguisher safety procedures and practices All fire extinguishers should be installed inspected and maintained in accordance with the National Fire Protection Association Standard titled Portable Fire Extinguishers NFPA 10 and all the requirements of the local authority having jurisdiction The instructions appearing in the National Fire Protection Association standard for portable fire extinguishers NFPA 10 the Code of Federal Regulations and in the Compressed Gas Association CGA pamphlets are not generally repeated in this manual except where they may emphasize or clarify a point Hydrostatic testing of fire extinguisher cylinders for example is amply covered in NFPA 10 and CFR 49 part 180 209 which reference procedures in CGA pamphlets C 1 C 2 and C 6 NFPA Government Printing Office Compressed Gas Association 1 Batterymarch Park P O Box 371954 1235 Jefferson Davis HWY Quincy MA 02269 Pittsburgh PA 15250 7954 Arlington VA 22202 617 770 3000 202 512 1802 703 412 0900 www nfpa org www bookstore gpo gov www cganet com General Information These Kidde extinguisher models are stored pressure hardware designs which utilize steel and Aluminum agent cylinders These models are charged with various types of Kidde dry chemical agents that include Regular Sodium Bicarbonate Purple K Potassium Bicarbonate and Multipurpo
5. function Verify that the A KIDDE RESIDENTIAL amp COMMERCIAL discharge nozzle and or hose assembly is correct for the model Newer Kidde models indicate this information on their nameplates 6 Visually examine the cylinder valve discharge port for any signs of thread wear corrosion obstructions or accumulations of any foreign material 7 Examine the pressure gauge for the following properly depressurize and replace if necessary For corrective action refer to the trouble shooting section in this manual a Ensure the gauge pressure needle indicates within the green operable area b Visually ensure there is no external gauge damage deformation dents or cracks c Verify gauge charge pressure properly correlates with charge pressure on nameplate d Ensure gauge indicates proper compatibility for dry chemical extinguishing agent e Ensure gauge indicates proper compatibility for use with either aluminum or plated brass valve material Note Recent Kidde Pro extinguisher models feature plated brass valve body assemblies 8 Closely examine the carrying handle and operating lever for any damage or deformation and ensure the rivets are secure 9 Being careful not to accidentally discharge the extinguisher pull and remove the ring pin breaking the visual inspection seal to ensure the ring pin functions freely and is not bent damaged or corroded Re install proper ring pin through the proper lever and valve port
6. ORED PRESSURE DRY CHEMICAL PORTABLE EXTINGUISHER DIAGRAM BRASS VALVE The following spares parts are available for the Kidde Pro Line 1 Hose nozzle assembly 2 Syphon tube assembly excludes o ring 3 Valve assembly includes handle amp lever attached amp valve body excludes o ring 4 O ring kit includes valve o ring syphon tube o ring stem assembly stem assembly spring 5 Wall hanger 6 Retention bracket 7 Pull pin 8 Pressure gauge 9 Hanger loop and screw 10 Hose strap 21005776 21005779 21005782 21005785 21005789 21005789 21005789 21005789 21005790 21005789 21005789 21005789 320213 320213 320213 320213 21005805 340104 294063 294063 340081 340081 340173 5 340357 340358 340358 340791 7 BA Kidde Kidde Residential and Commercial 1394 South Third Street Mebane NC 27302 9711 Phone 1 800 880 6788 Manual P N 300290 Copyright Kidde 2005
7. Pro Line Stored Pressure Dry Chemical Hand Portable Fire Extinguishers 27 Ib 2016 Agent Capacity KIDDE RESIDENTIAL amp COMMERCIAL Table of Contents Page 2 Contents Page 3 Introduction General Information Descriptions Page 4 Operation Instructions Page 5 After Use Instructions Monthly Inspection Procedures Page 6 Annual Maintenance and Service Examination Procedures Page 8 Recharge Instructions Page 10 Hydrostatic Test Requirements Page 12 Trouble Shooting Suggestions Page 13 Spare Parts Offering Part Numbers and Descriptions Warning Failure to follow the instructions contained herein may result in property damage and or personal injury Important Notice Any time an unusual extinguisher discrepancy is noticed or the specific corrective action or procedure required to resolve this condition is not fully understood personnel should stop and seek proper qualified assistance prior to continuing For assistance you may contact the nearest authorized Kidde fire extinguisher distributor Your local distributor can be located in the phone book yellow pages by contacting Kidde directly at 1 800 880 6788 or by logging on to www kiddeus com KIDDE RESIDENTIAL amp COMMERCIAL Introduction This manual is designed as a guide to service personnel in the performance of operation after use inspection maintenance service and recharge of Kidde dry chemical hand portable fire extinguishers These instructions
8. e Agent cylinder damaged or corroded KIDDE RESIDENTIAL amp COMMERCIAL Corrective Suggestion Secure repair or replace Clear clean or replace Replace Replace and lightly lubricate Replace Clean or empty and replace Replace De pressurize and replace Check ambient temperature correlation De pressurize and recharge or replace De pressurize and replace De pressurize and replace De pressurize and replace De pressurize and replace De pressurize and recharge Replace Inspect and hydrostatic re test or dispose of in accordance with NFPA 10 For gauge replacement Kidde recommends the use of Loctite 242 thread sealant be utilized and allowed to properly cure 12 A KIDDE RESIDENTIAL amp COMMERCIAL KIDDE PRO LINE STORED PRESSURE DRY CHEMICAL PORTABLE EXTINGUISHER DIAGRAM ALUMINUM VALVE The following spares parts are available for the Kidde Pro Line 1 Hose nozzle assembly 2 Syphon tube assembly excludes o ring 3 Valve assembly includes handle amp lever attached amp valve body excludes o ring 4 O ring kit includes valve o ring syphon tube o ring stem assembly stem assembly spring 5 Wall hanger 6 Retention bracket 7 Pull pin 8 Pressure gauge 9 Hanger loop and screw 10 Hose strap C moai Pozez rems poa7saws moata Ps S a 21005740 21005720
9. ing agent and expellant All rechargeable fire extinguishers shall be recharged after any use or as indicated by an inspection or when performing maintenance When performing extinguisher recharge the recommendations of the manufacturer shall be followed Because of potential performance or detrimental material compatibility problems which may occur with the use of other agents Kidde requires that only the dry chemical extinguishing agent specified on the extinguisher nameplate be utilized for recharge WARNING Prior to recharging an extinguisher personnel should be thoroughly familiar with the contents of this manual to recognize any equipment conditions or discrepancies that might prohibit the recharge of the extinguisher or direct further equipment maintenance or repair 1 Invert the extinguisher then while securing and pointing the nozzle safe direction squeeze the operating valve lever to remove all remaining pressure from the extinguisher Check the extinguisher gauge pressure reading to verify all pressure is removed WARNING To avoid personal injury or death always ensure all pressure is properly relieved from an extinguisher prior to attempting any service repair or recharge 2 Visually examine overall extinguisher for any signs of damage wear corrosion or other conditions which might prohibit the unit from being recharged 3 Unscrew and remove the discharge nozzle and or hose assembly from the valve asse
10. isher pressurization obtained too quickly may indicate a plugged siphon tube 13 Upon reaching proper pressurization release the operating lever shut off and remove the pressure source then install the ring pin into the valve assembly Verify that the extinguisher gauge operating pressure is also properly reading within the green operable area and then install a visual inspection tamper seal through the ring pin pull loop and around the top operating lever Remove the pressurization charge adapter from the extinguisher valve assembly 14 Using a soapy solution or leak detecting fluid properly perform a leak check of the valve assembly gauge and cylinder collar to ensure no pressure leakage is occurring Upon successful completion of the leak check properly clean and dry all extinguisher surfaces Note Prior to placing recharged dry chemical extinguishers back into fire protection service Kidde recommends the extinguisher pressure gauge reading be re verified a minimum of 24 hours after pressurization 15 Examine the discharge nozzle and or hose assembly to be sure it is not loose damaged worn or obstructed Reinstall and secure the nozzle and or hose assembly into the discharge valves outlet port Adjust and secure the hose nozzle into the retention band clip if equipped 16 Weigh the extinguisher to verify the total charged extinguisher weight falls within the tolerance 17 Wipe the extinguisher clean with a damp cloth to remove a
11. mbly 4 Slowly unscrew the discharge valve assembly from the agent cylinder WARNING To avoid personal injury or death should any audible pressure leakage be observed during extinguisher disassembly technicians should stop any further service action and wait until all residual pressure is relieved A KIDDE RESIDENTIAL amp COMMERCIAL 5 Remove the discharge valve assembly from the agent cylinder Disassemble the siphon tube and remove the spring and discharge valve stem Note Fire extinguisher valve assemblies are not typically indexed for orientation with other cylinders so any time extinguisher valve assemblies are removed they should always be tagged or referenced so they remain matched to the specific cylinder that they were removed from 6 Closely examine all components to ensure they are not damaged cracked or worn Remove the O ring and replace Re lubricate o ring with a light coat of silicone grease such as Vislox V711 or equivalent 7 Examine the valve stem to ensure it is not bent or corroded Replace O ring and re lubricate with a light coat of silicone grease such as Vislox V711 or equivalent 8 Properly reassemble the discharge valve assembly Ensure the valve stem spring and siphon tube are correctly installed and securely tightened 9 Empty the agent cylinder and visually examine it internally and externally for any damage thread wear dents repairs corrosion discoloration or contaminants If neces
12. nvert extinguisher then while securing and pointing the nozzle in a safe direction squeeze the operating lever valve to clear hose and vent all remaining pressure from the extinguisher 2 Notify proper person that extinguisher was used so that the extinguisher can be immediately recharged or a replacement obtained Monthly Inspection Procedures According to NFPA 10 inspection is a quick check that an extinguisher is available and will operate It is intended to give reasonable assurance that the extinguisher is fully charged and operable This is done by verifying that it is in its designated place that it has not been actuated or subjected to tampering and that there is no obvious physical damage or condition to prevent its operation Inspections should be conducted whenever extinguishers are initially placed into service and there after at approximately 30 day intervals When circumstances require more frequent intervals may be necessary Any time an inspection reveals a discrepancy maintenance and service procedures should be performed 1 Ensure the extinguisher is properly located in plain view and its access is unobstructed 2 Examine unit for any signs of corrosion leakage or physical damage 3 Ensure the nameplate is secure and legible and that the operating instructions face outward 4 Ensure ring pin and visual inspection tamper seal are in place and intact 5 Ensure pressure gauge pointer needle indicates
13. ny surface dirt or contaminates that may have accumulated 18 Properly tag label and record the extinguisher recharge procedure in accordance with NFPA 10 and all local requirements Hydrostatic Test Requirements Hydrostatic testing is the integrity pressure testing method of a vessel utilizing a liquid compression medium Kidde dry chemical fire extinguisher cylinders require hydrostatic testing at periodic intervals or any time the integrity of the vessel is questioned from any visually observed condition Hydrostatic testing should be performed in accordance with NFPA 10 recommendations A KIDDE RESIDENTIAL amp COMMERCIAL Evidence of conditions such as exposure to fire or heat thread damage thread wear corrosion cylinder repairs or physical damage as detailed within NFPA 10 require the extinguisher cylinder to be removed from service and proper disposal at the owner s direction Hydrostatic testing should only be performed by those persons trained in the appropriate testing procedures safeguards and having the proper testing equipment facilities and information Some Kidde hydrostatic test recommendations e Extinguisher cylinders should be replaced any time the pressure vessel has been weakened due to corrosion cuts dents digs etc e That only water be used as the test medium and that the extinguisher then be flushed clean dried and visually re examined after testing e The discharge valve assembly should be remo
14. s then install a new visual inspection tamper seal through the pull pin loop and around the carrying handle 10 Looking under the operating lever ensure the visual portion of the valve stem shaft is not bent damaged or corroded The top of the stem should extend from the valve body approximately 1 4 of an inch 11 Ensure the extinguisher nameplate is legible and secure The nameplate operating instructions should face outward and be orientated within 30 degrees of the pressure gauge face Check to ensure HMIS information is present and legible 12 Reinstall and secure the discharge nozzle and or hose assembly into the discharge valves outlet port Adjust and secure the hose nozzle into the retention band clip if equipped 13 Examine the cylinder hose retention band assembly if equipped for any damage and ensure it is properly adjusted to accommodate the hose assembly nozzle 14 Weigh the extinguisher and verify that the total charged extinguisher weight falls within the tolerance limitations specified on the nameplate instructions KIDDE RESIDENTIAL amp COMMERCIAL 15 Wipe the extinguisher clean with a damp cloth to remove any surface dirt or contaminants that may have accumulated 16 Upon satisfactory completion of the maintenance examination properly tag label and record the procedure in accordance with NFPA 10 and any local requirements Recharge Instructions According to NFPA 10 recharge is the replacement of extinguish
15. sary remove extinguisher from service and replace 10 Add the proper type and quantity of Kidde dry chemical agent specified on the extinguisher nameplate recharge instructions 11 Reinstall the discharge valve assembly onto the agent cylinder Ensure the valve is properly snugged down and the pressure gauge is properly orientated perpendicular to the front of the extinguisher WARNING Regulated extinguisher pressurization sources should never be set any higher than 25 PSI 172 kpa over the intended extinguisher charge pressure or be left connected to an extinguisher for extended periods of time Never stand directly in front of an extinguisher gauge or stand over the valve assembly during pressurization 12 Install the proper Kidde pressurization charge adapter into the discharge valve outlet port Using a regulated source of dry nitrogen containing a calibrated pressure gauge depress operating lever and slowly pressurize the extinguisher to pressure indicated on the nameplate Reference the calibrated pressurization gauge for proper charge Note To avoid damaging non metal siphon tube assemblies charge pressure should be applied slowly KIDDE RESIDENTIAL amp COMMERCIAL Note During recharge dry chemical agent can accumulate and pack within the siphon tube when installing the valve assembly into the cylinder Recharge personnel should ensure the time required for total pressurization is appropriate for the model size Extingu
16. se Mono Ammonium Phosphate The extinguishers should only be pressurized with nitrogen Never attempt to recharge a Kidde dry chemical fire extinguisher with any other dry chemical agent other than that specified on the original nameplate Descriptions The Kidde dry chemical extinguishers are stored pressure hardware designs that contain both the agent and expellant charge within the same cylinder The extinguishers are engineered to effectively discharge the contents of the dry chemical charge These extinguishers consist of the following basic parts 1 Agent cylinder contains the dry chemical agent and expellant charge 4 KIDDE RESIDENTIAL amp COMMERCIAL 2 Discharge valve assembly consists of the operating lever carrying handle valve stem pressure gauge and discharge outlet that permits the actuation and discharge of the dry chemical extinguishing agent 3 Siphon tube assembly houses the spring assembly and provides the means for the extinguishing agent to be drawn up from the bottom of the cylinder to the discharge valve 4 Ring pin and tamper seals provide a means of visual assurance that the extinguisher has not been activated charged or subjected to tampering 5 Discharge hose assembly provides a flexible means of agent delivery from the discharge valve to the nozzle 6 Nozzle assembly provides the agent discharge stream shaping characteristics necessary for optimum fire fighting performance
17. ved prior to hydrostatic testing of the cylinder Refer to Note in Step 5 of Recharge instructions e The agent cylinder hydrostatic test marking method should only utilize the proper type of record labels per NFPA 10 requirements e Never stamp or etch any markings onto the cylinder e Any time a fire extinguisher is known to have contained agents additives or mediums other than that specified on the nameplate it should be removed from service and properly disposed at the owner s direction No repairs to the cylinder are permitted If such cylinder repairs are observed the extinguisher should be removed from service and properly disposed at the owner s direction Hydrostatic Re Test Data Component Description Periodic Test Interval Test Pressure Agent cylinders 12 year 585 PSI Trouble Shooting Suggestions Problem Wall hook bracket loose or damaged Nozzle obstructed Discharge hose assembly worn cracked or damaged Hose o ring missing cracked or damaged Hose retainer band missing or damaged Valve discharge port obstructed dirty Pull pin bent corroded missing or damaged Lever handle loose bent or damaged Pressure gauge reads outside green area Pressure gauge damaged Gauge operating pressure differs from label Gauge does not indicate for use with dry chemical Gauge does not indicate compatible with valve material Total charge weight of unit outside tolerance Nameplate instructions missing or illegibl
18. within the green operable pressure range 6 Heft or weigh extinguisher to determine its fullness Note Kidde recommends stored pressure dry chemical fire extinguishers be weighed at least semi annually to verify the proper agent charge weight in accordance with nameplate instructions 7 Visually examine the discharge nozzle and or hose assembly to ensure it is clear and unobstructed 8 Date and initial the inspection tag or record in accordance with NFPA 10 and local requirements 44 KIDDE RESIDENTIAL amp COMMERCIAL Annual Maintenance amp Service Procedures Per NFPA 10 maintenance is a thorough examination of a fire extinguisher and is intended to provide maximum assurance that it will operate effectively and safely It includes a thorough examination of all components and the repair or replacement of such items if necessary Maintenance should be performed at intervals not to exceed one year apart or any time an inspection discrepancy dictates Kidde recommends that only authorized Kidde distributors or personnel having been properly trained to recognize and correct discrepancies as well as understand all the proper industry safety procedures conduct the maintenance or service of Kidde fire extinguishers Refer to the trouble shooting section of this manual for additional information on specific equipment observations or discrepancies Only Kidde factory replacement parts are recommended for use in Kidde extinguishers
Download Pdf Manuals