Emerson 630 Regulator Installation Guide
Contents
1. A f 2 8 N 4 5 6 7 DO G 0X00119 F Figure 1 Spring Loaded Type 630 Regulator Low Pressure Construction Table 3 Outlet Pressure Ranges 630 Series MAXIMUM ALLOWABLE MAXIMUM EMERGENCY REGULATOR RELIEF INLET PRESSURE CONSTRUCTION SETTINGS PSIG Ear PART NUMBER RELIEF INLET PRESSURE INLET CASING PRESSURE PSIG bar PSIG bar 3to8 0 21 to 0 55 0W019227022 6to17 0 41 to 1 1 0W019127022 Relief Pressure Setting Plus Low Pressure 15 to 22 1 0 to 1 5 0019027022 Maximum Allowable Build up of 75 5 2 20t035 1 4to 2 4 0066427022 25 psig 1 7 bar 27050 1 9 to 3 5 13146927142 30 to 70 2 0 to 4 8 0019127022 High Pressure 30 to 39 91910 69 OWO 19027022 ea nd 550 38 0 75t0175 5 2 to 12 1 0Y066427022 E E 150t0250 10 4 to 17 3 1J146927142 1 Leakage or bursting of pressure containing parts may occur if inlet pressure exceeds these values Regular operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line The regulator should be inspected for damage after any overpressure condition Startup The regulator is factory set at approximately Adjustment To change the outlet pressure remove the closing cap or loosen the locknut and turn the adjusting screw clockwise to increase outlet pressure or
2. The recommended pressure limitations are stamped on the regulator nameplate Some type of overpressure protection is needed if the actual inlet pressure exceeds the maximum operating outlet pressure rating Overpressure protection should also be provided if the regulator inlet pressure is greater than the safe working pressure of the downstream equipment Ss EMERSON D100300XUS2 630 Series Specifications Available Configurations Type 630 Spring loaded reducing regulators Type 630R Spring loaded relief valves Body Size and End Connection Style 1 or 2 NPT Maximum Allowable Inlet Pressures Type 630 Regulators See Table 1 Type 630R Relief Valves See Table 3 Outlet Pressure Ranges 3 to 500 psig 0 21 to 34 5 bar with intermediate values shown in Table 2 Maximum Allowable Outlet Pressures See Table 2 Maximum Allowable Pressure Drops See Table 1 Temperature Capabilities Standard 20 to 150 F 29 to 66 C Optional 20 to 300 F 29 to 149 C Orifice Sizes 1 8 inch 3 2 mm 3 16 inch 4 8 mm 1 4 inch 6 4 mm 3 8 inch 9 5 mm or 1 2 inch 13 mm 1 The pressure temperature limits in this installation guide or any applicable standard limitati ion should not be exceeded Table 1 Maximum Allowable Inlet Pressures and Pressure Drops Maximum inlet pressure not to exceed 1500 psig 103 bar ORIFICE SIZE INCHES mm drops Some erosion of valve disks o
3. in personal injury and property damage due to escaping fluid To avoid such injury and damage install the regulator in a safe location www emersonprocess com regulators 630 Series Clean out all pipelines before installation of the regulator and check to be sure the regulator has not been damaged or has collected foreign material during shipping For NPT bodies apply pipe compound to the external pipe threads Install the regulator in any position desired unless otherwise specified but be sure flow through the body is in the direction indicated by the arrow on the body Vents When the unit is installed in an enclosed area or indoors escaping gas may accumulate and be an explosion hazard Under these conditions the vent should be piped away from the unit to a freely ventilated outdoor location away from air intakes windows etc Protect all vent openings against weather or the entrance of any foreign material that may plug the vent or affect operation of the regulator or relief valve Inspect all vent openings periodically to be sure they are not plugged If the vent is in an environment where freezing rain ice or snow could clog the vent it is recommended that a weatherproof vent be used Spring loaded constructions have a screened vent assembly key 27 installed in the 1 4 NPT spring case vent opening If a remote vent is required remove the vent assembly and install a remote vent line Overpressure Protection
4. Installation Guide English September 2009 Introduction This installation guide provides instructions for installation startup and adjustment To receive a copy of the instruction manual contact your local Sales Office or view a copy at www emersonprocess com regulators For further information refer to 630 Series Instruction Manual form 1243 D100300X012 Installation Only qualified personnel should install or service a regulator Regulators should be installed operated and maintained in accordance with international and applicable codes and regulations and Emerson Process Management Regulator Technologies Inc instructions If the regulator vents fluid or a leak develops in the system it indicates that service is required Failure to take the regulator out of service immediately may create a hazardous condition Personal injury equipment damage or leakage due to escaping fluid or bursting of pressure containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given in the Specifications section or where conditions exceed any ratings of the adjacent piping or piping connections To avoid such injury or damage provide pressure relieving or pressure limiting devices as required by the appropriate code regulation or standard to prevent service conditions from exceeding limits Additionally physical damage to the regulator could result
5. RE PRESSURE OVER OUTLET CASING PSIG bar SETPOINT PSIG bar PRESSURE PSIG bar 3 to 10 0 21 to 0 69 0W019227022 10 0 69 20 1 4 8 to 20 0 55 to 1 4 0W019127022 20 1 4 f Low Pressure 17 to 30 1 2 to 2 1 0W019027022 30 2 1 20 1 4 45 3 1 27 to 40 1 9 to 2 8 OY0664000A2 40 2 8 Limitediby Maximum Emergency Outlet Pressure 27 to 50 1 9 to 3 5 0W019227022 50 3 5 46 to 95 3 2 to 6 6 0W019127022 95 6 6 g 90 to 150 6 2 to 10 3 0W019027022 150 10 3 200 13 8 High Pressure 150 to 200 10 3 to 13 8 OY0664000A2 200 13 8 550 37 9 200 to 275 13 8 to 19 0 13146927142 275 19 0 275 to 500 19 0 to 34 5 1K370927082 500 34 5 200 13 8 1 Damage to internal parts of the regulator may occur if outlet pressure exceeds the actual pressure setting by amounts greater than those shown in this column 2 For outlet pressure settings to 25 psig 1 7 bar only For pressure settings over 25 psig 1 7 bar outlet pressure is limited by maximum emergency outlet pressure of 45 psig 3 1 bar 3 For outlet pressure settings to 350 psig 24 2 bar only For pressure settings over 350 psig 24 2 bar outlet pressure is limited by maximum emergency outlet pressure of 550 psig 37 9 bar 4 Leakage or bursting of pressure containing parts may occur if outlet pressure exceeds these values
6. ccurs at all pressure drops due to solid particles in the flow si DISK MATERIAL 1 8 and 3 16 3 2 and 4 8 1 4 6 4 3 8 9 5 1 2 13 Nylon PA and Polytetrafluoroethylene PTFE 1500 103 1000 69 500 34 5 250 17 2 Nitrile NBR 600 41 4 600 41 4 500 34 5 250 17 2 Fluorocarbon FKM 200 13 8 200 13 8 200 13 8 200 13 8 MAXIMUM BECO ARTE INEEy PRESSURE 1500 103 1500 103 1000 68 9 750 51 8 Psig bar 1 Inlet pressure must not exceed the sum of the actual outlet pressure setting and the maximum allowable pressure drop For example with an outlet pressure setting of 200 psig 13 8 bar and a 3 8 inch 9 5 mm orifice with a maximum allowable pressure drop of 500 psi 34 5 bar differential the maximum allowable inlet pressure is 700 psig 48 3 bar 2 Nitrile NBR valve disks are normally furnished for pressure drops to 200 psi 13 8 bar differential For better erosion resistance Nylon PA valve disks are normally furnished for higher pressure high pressure drops Valve disks and other regulator parts must be inspected periodically for erosion and damage and must be replaced as necessary ream The rate of erosion is higher with large amounts of impurities in the flow stream and with Table 2 Maximum Outlet Pressures REGULATOR OUTLET PRESSURE SPRING MAXIMUM OPERATING MAXIMUM OUTLET MAXIMUM EMERGENCY CONSTRUCTION RANGE PSIG bar PART NUMBER OUTLET PRESSU
7. counterclockwise to decrease pressure Monitor the outlet pressure with a test gauge during the adjustment Replace the closing cap or tighten the the midpoint of the spring range or the pressure requested so an initial adjustment may be required to give the desired results With proper installation completed and relief valves properly adjusted slowly open the upstream and downstream shutoff valves locknut to maintain the desired setting Taking Out of Service Shutdown To avoid personal injury resulting from sudden release of pressure isolate the regulator from all pressure before attempting disassembly 630 Series Parts List Key Description Adjusting Screw Hex Nut Spring Case Upper Spring Seat Spring Cap Screw Lower Spring Seat Diaphragm Plate Cap Screw 10 Cap Screw 11 Diaphragm 12 Connector Head Assembly 13 Diaphragm Adaptor 14 Lever Assembly 15 Pin 16 Gasket 17 Cap Screw 18 Inlet Adaptor 19 Inlet Body Gasket 2 required 20 Orifice 21 Valve Disk Assembly Type 630 only 21 O Ring Holder Type 630R only 22 Valve Carrier 23 Body 27 Vent Assembly Type Y602 12 31 Cap Screw 2 required not shown 32 O Ring Washer Type 630R only 33 Plug not shown 34 Nameplate 35 Drive Screw 4 required 36 Machine Screw Type 630R only 37 O Ring Type 630R only 52 NACE Tag not shown 53 Tag Wire not shown OANDARWN Industrial Regulators Emerson Process Management Regula
8. mational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Process Management does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Process Management product remains solely with the purchaser Emerson Process Management Regulator Technologies Inc 2005 2009 All Rights Reserved S EMERSON Process Management
9. tor Technologies Inc USA Headquarters McKinney Texas 75069 1872 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Shanghai China 201206 Tel 86 21 2892 9000 Europe Bologna Italy 40013 Tel 39 051 4190611 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75069 1872 USA Tel 1 800 558 5853 os fan Sk ZAA S WW CB2197 E Figure 2 Spring Loaded Type 630 Regulator High Pressure Construction UEOROZOROZORG CD3355 E Figure 3 Spring Loaded Type 630R Relief Valve High Pressure Construction TESCOM Emerson Process Management Tescom Corporation USA Headquarters Elk River Minnesota 55330 2445 USA Tel 1 763 241 3238 Outside U S 1 972 548 3574 Asia Pacific Singapore Singapore 128461 Tel 65 6777 8211 Europe Bologna Italy 40013 Tel 39 051 4190611 Europe Selmsdorf Germany 23923 Tel 49 0 38823 31 0 Gallardon France 28320 Tel 33 0 2 37 33 47 00 For further information visit www emersonprocess com regulators The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls Inc a business of Emerson Process Management The contents of this publication are presented for infor