1. Probe Tank Length Height aes st ee te ats Ci ee eee 5 URV 1 ur OL E Nominal Reference M m Vee TRV Point NOTE This output option requires an extra configuration of the Holding Register Sip Tank Presentation to enable negative output values RRM gt Service gt Enter Service Mode password admin Service gt View Holding Registers gt Sip click Read gt TankPresentation gt double click on bit field Bit 8 Show negative level as zero uncheck box and click Store Service gt Exit Service Mode Commissioning Reference Manual 00809 0700 4530 Rev AA Commissioning Section 3 Commissioning September 2013 Option 2 Setting LRV to 0 in 0 mm at the lower tap The tank height should be set to the distance to the zero level point In this example it is the lower side pipe located 19 in 483 mm below the reference point Output range values will equal the pipe connection heights relative to the zero level point LRV should be set at 0 in 0 mm the URV should be set at 14 in 356 mm and the probe should be set to the correct probe length Table 3 6 Option 2 example Gauge height distance to LRV 19 483 mm Probe length probe length 23 in 584mm URV distance between connections 14 in 356 mm LRV center of bottom connection 0 mm Figure 3 8 Range values f
2. In a typical measurement situation the following peaks appear in the echo curve Reference peak This reference pulse is caused by the transition between the transmitter head and the probe antenna For the Rosemount 3300 and 5300 Series the pulse is negative while for the Rosemount 5400 and 5600 Series the pulse is positive see Figure 5 6 on page 68 For Rosemount 5301 with DVC the seal pulse is used as reference See Table 5 2 on page 67 for the typical reference pulse amplitudes for the Rosemount 5300 Series Reference reflector peak Rosemount 5300 with DVC only This reference reflector pulse is caused by the transition between reference reflector and continuing part of the probe The pulse is negative but not as strong as the reference pulse In RRM it should be labelled as P2 other or P3 other if surface echo centering disk is present after vapor compensation is calibrated see Commissioning on page 35 The amplitude of the reference reflector peak is dependent on the installation chamber diameter and the process conditions of the application See also Figure 4 5 on page 55 Surface peak This pulse is caused by a reflection of the product surface See Table 5 1 for typical surface peak amplitudes for the Rosemount 5300 Series Note that the amplitude is dependent on the dielectric constant of the media transmitter type probe antenna type process conditions vapor turbulence foam etc distance to echo etc Probe
3. After calibration do the following Verify that the reference reflector echo is registered in RRM at correct length and that no error messages are present in the device diagnostics The echo from the reference reflector end can be viewed in the echo curve in RRM RRM gt Echo Curve RRM gt Tools gt Diagnostics Refer to the Rosemount 5300 Series Reference Manual Document No 00809 0100 4530 and the Using Guided Wave Radar for Level in High Pressure Steam Applications Technical Note Document No 00840 0100 4530 for details Commissioning Reference Manual Section 3 Commissioning 00809 0700 4530 Rev AA September 2013 323 3 3 3 0 Commissioning Remote housing GWR transmitters If a remote housing is added to a unit after the DVC calculation is done the unit needs to be recalibrated When using remote housing the remote connection length should be configured If the remote housing is ordered with a transmitter it is configured in the factory For more details refer to the Rosemount 5300 Series Reference Manual Appendix D Remote Mounting Document No 00809 0100 4530 RRM gt Setup gt Tank gt Probe tab select applicable Remote Housing length Setting range values for chambers options There are different options to set the range values in chamber installations to get the desired output The options are described below For displacers the output span corresponds to the displacer length w
4. 8 in Cone antenna with flushing adapter ideal for dusty applications m suitable for short distances of less than 50 ft 15 stronger surface reflection than in the case of smaller cones Installation considerations 31 Section 2 Installation Considerations Reference Manual September 2013 00809 0700 4530 Rev AA Step 2 tank connection Figure 2 28 Rosemount 5600 Series with cone parabolic antenna Rosemount 5600 Series Rosemount 5600 Series with cone antenna with parabolic antenna 6 3 in 14 6 in 370 mm 160 mm or less or less 0 7 6 in 0 19 7 0 194 mm 0 500 mm min min HINT If the signal is dampened by heavy condensation at the antenna it often helps to insulate the nozzle This minimizes the temperature disparity between the internal and ambient temperature Installing the antenna so that it is inside the vessel helps to eliminate the chance of condensation Step 3 radar location a Theradar signal must never be shaded by the inlet nor the injected product The radar should not be mounted in the center of the silo It should always be mounted as close to the silo center as possible A general practice is to mount the radar at 2 3 tank radius from tank wall a Adeflection plate might need to be installed at the inlet point in order to deflect the product stream away from the antenna 32 Installation considerations Reference Manual Section 2 Insta
5. Reference Manual Section 4 Measurement validation 00809 0700 4530 Rev AA September 2013 Figure 4 4 GWR transmitter peak amplitudes and threshold settings Surface Surface UNZ peak threshold Amplitude Distance Figure 4 5 Rosemount 5300 Series with DVC reference reflector peak and threshold settings Surface Surface UNZ peak threshold 3 2 0 a lt Reference Reference peak reflector peak Distance Step 4 transmitter diagnostics review The transmitter contains valuable diagnostics that monitor the health of the device to make sure that it does not report any errors or warnings For details on diagnostic messages refer to the transmitter reference manual In RRM RRM gt Tools gt Diagnostics Measurement validation 55 Section 4 Measurement validation September 2013 56 Reference Manual 00809 0700 4530 Rev AA Figure 4 6 Diagnostics 5 Diagnostics LT 01 Diagnostics Summary Y Device Status Device Errors Device Status Device Error Device Warnings Device Warning Measurement Status Measurement Status Interface Status Interface Status f Volume Calc Status Hed tatus Analog Out 1 Status D indication s D error s 0 warning s 2 indication s 0 indication s D indication s 0 indication s Click corresponding icon for detailed information Cose
6. See the Rosemount 5300 Series Reference Manual for details Document No 00809 0100 4530 37 Section 3 Commissioning Reference Manual September 2013 3 2 4 38 00809 0700 4530 Rev AA Figure 3 1 Echo curve before and after TNZ m gt fioe SESE evene P2 Reterence P2 Reference NOTE The effect of TNZ is only visible when an echo is present in the near zone Changing the Upper Null Zone UNZ Measurements are not performed within the Upper Null Zone UNZ By setting the UNZ parameter to zero measurements can be performed in the region close to the flange near zone Figure 3 2 Upper Null Zone UNZ Upper reference point Upper Null Zone UNZ Reference gauge height Product level If there are measurements desired in the upper part of the tank use the Trim Near Zone function to optimize the echo curve in that region see Trim Near Zone GWR transmitters on page 37 If the desired measurement range is below the near zone or if disturbing objects are located within the near zone the UNZ parameter can be used to avoid false measurements contained within the UNZ area Rosemount 5300 5400 and 5600 Series RRM gt Tank gt Probe gt Upper Null Zone enter desired value in field RRM gt Echo Curve gt Configuration Mode Drag amp Drop UNZ line Commissioning Reference Manual Section 3 Commiss
7. 1 022 0 2 in 4 mm 0 3 in 8 mm Oin 0 mm 1 180 1 3 in 33 mm 2 6 in 65 mm Oin 0 mm NOTE When performing verification at ambient pressure and temperature conditions always set vapor dielectric to 1 Otherwise level reading will be incorrect To set the Vapor Dielectric constant in RRM RRM Tank Environment Troubleshooting procedures Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013 5 5 6 Reconciling radar with other level measurements When comparing level measurements to each other they often do not match up as expected There are numerous reasons for this with the most prominent one being related to what is actually being measured Few instruments measure the level directly as radar does Instead an indirect measurement of for example pressure weight or capacitance is done and then the level is calculated from this measurement Inaccuracies in the level measurement may occur during the calculation process or from the fact that what is thought to be the measurement is not what is actually being measured Displacer Displacers are a common method to measure level The Archimedes principle is used and by measuring the apparent weight of the immersed displacer the level can be measured indirectly Beside the possibility of the displacer getting stuck it also requires precise calibration Any change in density such as a different product in the tank or changed
8. 12 in 300 mm Level 0 Table 2 6 Minimum distance X Probe Length Reflector Minimum Distance X 35 158 in 900 4000 mm 14 in 350 mm 22 in 560 mm 43 158 in 1100 4000 mm 20 in 500 mm 28 in 710 mm Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 2 3 3 Chamber mounting Chambers should be mounted onto the tank to correspond with the desired measurement and area of control This is often a small portion of the overall height For further information on chamber mounting in the control area see DVC installation best practices on page 12 2 3 4 Existing chambers Retrofitting of existing chambers is very common especially when replacing old mechanical devices such as displacers For further information see the Replacing Displacers with Guided Wave Radar Technical Note Document No 00840 2200 4811 If an existing chamber is used a spool piece might need to be added For further information on installation with a spool piece see DVC installation best practices on page 12 2 3 5 Pressure and temperature specifications The following diagram gives the process temperature maximum product temperature at the lower part of the flange and pressure ratings for chamber tank connections of the Rosemount 3300 and 5300 Series NOTE The process seal pressure and temperature specifications
9. Hep Step 5 monitor level while emptying During Step 1 the current level and or interface reading was verified This step will verify that the transmitter correctly tracks the surface during the emptying of the tank Begin by activating log functionality for the transmitter level output Either the DCS trend or a standalone tool can be used RRM gt Tools gt Log Figure 4 7 Log Registers Level m 500 600 Time in seconds Y Axis z EZ tog registers T Update Rate File name Select Registers ENProgrem Files Rosemount RAMSRsx RegLog Emptying 19930101 Standard BBE Start Log Stop Log Start emptying the tank or chamber making sure not to stop until itis completely empty With a chamber do not forget to close the process valves before draining Measurement validation Reference Manual Section 4 Measurement validation 00809 0700 4530 Rev AA September 2013 Figure 4 8 Emptying a tank or chamber Finally review the level trend for accuracy Step 6 echo curve verification with empty tank When the tank or chamber is empty download and review the echo curve according to the following steps 1 Compare echo curve with previous plots Compare the echo curve with previous plots taken during commissioning There should be no major differences Especially make sure to review E the amplitude and position of the reference pulse if all noise is below th
10. Transition 7 2 oil 2 8 in 7 8 in 20 cm 7 5 19 5 5in 14 cm 1 Single probes are the preferred choice 2 Rigid Single Lead probe without SST centering disk or with a PTFE centering disk 3 Coaxial should only be used for very clean or low DC applications 4 The distance from the upper reference point where measurements have reduced accuracy see Ain Fi gure 2 8 5 The distance from the lower reference point where measurements have reduced accuracy see in Fig ure 2 8 Figure 2 8 Measuring zones in chambers A Sinal A A gt Upper transition zone A I Single flexible rigi for chambers gt 3ft 1m Probe B Effectice measuring chamber range determined by Probe chamber diameter must be diameter mating tank connections must be 3in 4 3in 4 7 5 10 7 Sonn C Lower transition zone 10cm including weight height Always use a for flexible probes and clearance distance centering disk Use centering disks for probes gt 3ft 1m Installation considerations 17 Section 2 Installation Considerations Reference Manual September 2013 00809 0700 4530 Rev AA An example using the guidelines for fabrication of cages see Table 2 5 on page 17 for transition zones Assuming level measurement of oil worst case
11. function to reduce the impact of possible stationary disturbances in the tank The Rosemount 5300 Series solids measurement might require activation of the Probe End Projection PEP function See pages 47 39 and 48 for details on how to activate SQM Measure and Learn and PEP Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 252 Rosemount 5600 Series The Rosemount 5600 Series can be used in tanks up to 165 ft 50 m As solids generally provide a difficult measuring environment and the signal levels are often very low installation is of utmost importance Antenna selection and its location in the tank are the keys to success Step 1 antenna selection Figure 2 24 Parabolic antenna with a PTFE bag Parabolic antenna with a PTFE bag m ideal for dusty applications m the best choice for long distances handle weak surface reflection a positionable towards surface m thePTFE bag prevents dust build up at the antenna Figure 2 25 Parabolic antenna Parabolic antenna m the best choice for long distances can handle weak surface reflection gt positionable towards surface Figure 2 26 8 Cone antenna 8 in Cone antenna a Suitable for distances of less than 50 ft 15 m Stronger surface reflection than in the case of smaller cones Figure 2 27 8 in Cone antenna with flushing adapter
12. see sss 14 Measurement validation 51 Installations 6 Measuring 2 17 ceals 22 Measuring ZONES 17 N Mounting aces 19 Probe selection 27 Nozzle considerations 25 Rettolll coc sere 19 Clearance 23 Common problems 69 Disturbance misinterpreted as level 71 On the bench test 49 Incorrect 72 Possible build up on probe 72 Strong antenna echo 73 Threshold below the surface peak 69 PIDE E antenna rd 73 Probe End Projection PEP 48 Probevend erae x RS Tere 67 76 D Rosemount 5300 67 Diagnostics 0 20 eene 63 Rosemount 5400 and 5600 5 68 12 A Tm Recommended 19 58 Echo curve analysis 64 R Echo curve constituents 65 cece eect 43
13. Remote housing 20 43 G Geormetries 75 S Signal Quality Metrics 6 47 Solids measurement 28 UE 22 Static Vapor Compensation 5 9 39 Incorrect Static Vapor Compensation 78 Storing backup and verification files 49 L Lower Range Value 1 43 44 45 Measure and learn 36 39 Index Index 1 Index September 2013 T Tank installations 22 Threshold 69 Guided Wave 69 Non contacting 69 Transition ZONES 17 Trim Near Zone 7 27 U Upper Null Zone 7 38 Upper Range Value 43 44 45 V Vapor compensation 9 39 DYNAMIC 9 40 Minimum distance 12 9 39 W Write protectiori cseossscerpseesbeY tenressa Es 49 Index 2 Reference Manual 00809 0700 4530 Rev AA Index Emerson Process Management Rosemount Division 8200 Market Boulevard Chanhassen MN 55317 USA Tel US 1 800 999 9307 Tel Intern
14. clearance to tank wall or obstruction Oin 0 cm Ain 10 cm in the case of smooth metallic walls 20 in 50 cm in the case of disturbing objects rugged metallic or concrete plastic walls Ain 10 cm in the case of smooth metallic walls 20 in 50 cm in the case of disturbing objects rugged metallic or concrete plastic walls Installation considerations 23 Section 2 Installation Considerations Reference Manual September 2013 24 00809 0700 4530 Rev AA The Rosemount 5400 Series non contacting radar transmitters should be installed in locations with a clear and unobstructed view of the level surface A for optimum performance Filling inlets creating turbulence B and stationary metallic objects with horizontal surfaces C should be kept at a distance outside the signal beam Refer to the Rosemount 5400 Series Product Data Sheet for more information Document No 00813 0100 4026 Agitators with large horizontal blades may reduce the performance of the transmitter so install the transmitter in a location where this effect is minimized Vertical or slanted blades are often invisible to radar but create turbulence D Do not install the transmitter in the center of the tank E Because of circular polarization only Rosemount 5400 Series there is no clearance distance requirement from the tank wall if it is flat and free from obstructions such as heating coils and ladders F Usu
15. 0 1 0 2 0 4 0 6 0 Distance m Commissioning Reference Manual Section 3 Commissioning 00809 0700 4530 Rev AA September 2013 3 3 10 352 12 Commissioning Store backup and verification files As the last step of the commissioning procedure it is recommended that both the transmitter settings and the echo curve be stored For example these can be used for subsequent transmitter verification or troubleshooting Note that the echo curve should also be stored once more at operating conditions In RRM configure the following RRM gt Device gt Backup Config to file RRM gt Tools gt Echo Curve gt Record In Radar Configuration Tools do the following Radar Configuration Tools gt View gt Memory gt All EE Write protect A Rosemount 5300 and a 5400 Series transmitter can be password protected from unintentional configuration changes The default password is 12345 and it is recommended that this password is not changed to facilitate service and maintenance of the transmitter In RRM Tools gt Lock Unlock Configuration Area On the bench test optional Sometimes the actual process is not available and the transmitter is pre commissioned on the bench In this case the level is often simulated using metal plates water or other targets Although these tests provide a basic verification of the transmitter they do not verify that the transmitter functions properly at the actual process conditio
16. 4 25 14 ft 4 25 saab insiallations 80 15 ft 4 5 MU 149 ft 45 5 m 1 Accuracy may be affected up to 1 2 in 30 mm 2 Required chamber pipe size is 3 or 4 in 75 100 mm Installation considerations 21 Section 2 Installation Considerations Reference Manual September 2013 PA S 2 4 2 4 1 22 00809 0700 4530 Rev AA Insulation The chamber should always be insulated in hot applications to prevent personal injuries and reduce the amount of energy needed for heating It is often an advantage and sometimes even required for the radar measurement u In hot applications insulation will reduce the amount of condensation since it prevents the upper part of the chamber from becoming a cold spot In hot applications insulation will reduce the temperature drop between the tank and chamber This is important since lower temperature fluids have higher density and less volume There is a risk that the level height could be less in the chamber since the volume of higher density fluid will be smaller See Installation and location errors on page 73 for details Heat tracing well insulated inlet pipes and a good flow through will also help to reduce the temperature change Insulation prevents the product from solidifying inside the chamber and clogging the inlet pipes When the Rosemount 5300 Series is installed in high or low temperature applications it is important that the maximum minimum
17. Piodi ctieDdil Gr s me vete nre mpl EPA 59 Section 5 Troubleshooting procedures 5 1 Safetyimessages ixcssessnenexce te re tet Ne e ram re e HEN ERRARE 61 52 62 OS COS As eei 63 5 4 Echoc rvearnalysis 64 54 1 Echo culve S RENE ER 65 5 4 2 Rosemount GWR transmitter threshold settings 69 5 4 3 Rosemount non contacting radar transmitter threshold settings 69 544 Common problems rrr rr here erase 69 5 5 Sources 73 5 5 1 Installation and location errors 73 5 9 2 75 5 5 3 Probe End Pulse offset only relevant 76 55 4 Analog OlltplibseLttiligs sesevescerosert 6 eevererega fece rens 76 5 5 5 Imcornrectstatic vapor compensation 78 ii Table of Contents Reference Manual Table of Contents 00809 0700 4530 Rev AA September 2013 5 5 6 Reconciling radar with other level measurements 79 Appendix A Checklists Safety messages 81 A2 SGNECKISES t bekei 82 A 2 COMMISSIONING procedure ened 82 2 2 Measurement validation procedure 83 A 2 3 Troubleshooting procedure 84 Table of Contents iii Table of Content
18. Protocol Compensation HART 282 2 2 Device Address 0 Min Intemal Temp 381 Diagnostics Suite Option Enabled Internal Temp Safety Device 05 Option taa OC Device Operation Time Start Code Status Error Waming 192 h 2 5 7 Save as NOTE Vapor compensation is supported for product level measurement mode only NOTE For the 3 in 75 mm and 4 in 100 mm flange DVC probes coaxial HTHP equipped with a reference reflector is the only probe that supports vapor compensation The probe is marked VC2 as shown in Figure 3 5 Figure 3 5 HTHP with VC2 marking on the probe VC2 marking on nap VC2 marking on tank seal L tank seal 2 in Lm 4 DVC 2224 DVC probe probes Li T NOTE 2 in 50 mm flange DVC i probes use a single rigid style probe Probes up to 13 1 ft 4 m length are supported Pipe chamber is the only supported mounting type Supported pipe inner diameters are 2 3 and 4 in 5 7 5 and 10 cm a PEP is disabled when vapor compensation is enabled a TNZ shall not be used when DVC is used 1 A3or4 in 75 or 100 mm diameter chamber is recommended as best practice but the GWR can also be mounted in a 2 in 50 mm chamber Commissioning 41 Section 3 Commissioning Reference Manual September 2013 42 00809 07
19. Rosemount 5300 Series 1 See the Rosemount 5300 Series Reference Manual Document No 00809 0100 4530 Table 3 2 Tank installations Function Rosemount Series Trim Near Zone TNZ Rosemount 3300 Series Rosemount 5300 Series Upper Null Zone UNZ All Measure and learn Rosemount 5400 Series Configuration for process conditions All Signal Quality Metrics SQM Rosemount 5300 Series Rosemount 5400 Series Safety Instrumented Systems SIS Rosemount 5300 Series Store backup All 1 Seethe Rosemount 5300 Series Reference Manual Document No 00809 0100 4530 Commissioning Reference Manual Section 3 Commissioning 00809 0700 4530 Rev AA September 2013 33 1 Commissioning Table 3 3 Solids measurement Function Rosemount Series Trim Near Zone TNZ Rosemount 5300 Series Upper Null Zone UNZ Rosemount 5300 Series Rosemount 5600 Series Probe End Projection PEP Rosemount 5300 Series Configuration for process conditions Rosemount 5300 Series Rosemount 5600 Series Safety Instrumented Systems SIS Rosemount 5300 Series Store backup All 1 See the Rosemount 5300 Series Reference Manual Document 00809 0100 4530 Trim Near Zone GWR transmitters The Rosemount 3300 and 5300 Series are equipped with a firmware functionality that minimizes the Upper Transition Zone based on actual mounting conditions Trimming means that th
20. Tea Lia ee TOT TUR DEO Oar saa Distance m gt Distance m gt Antenna recessed up in nozzle manway Antenna reaches into tank Level is at 52 in 16 m Level is still at 52 in 16 m but now visible Geometries Review the tank geometry and check if any assumptions have been made that caused the inaccuracies For example the location of a sight glass or secondary chamber may have been assumed to be at the same location as the radar measurement but in reality they are not Figure 5 18 The sight glass and chamber are not on the same level where they are supposed to be Incorrectly assumed to be on RH T the same level Rh 0 l Troubleshooting procedures 75 Section 5 Troubleshooting Procedures Reference Manual September 2013 5 5 3 5 5 4 76 00809 0700 4530 Rev AA Probe End Pulse offset only relevant for PEP An offset of the probe end pulse is normal if there is product in the vessel However it can also be caused by mis configured probe length Ensure that correct probe length is configured by emptying the tank and reading the probe end pulse or measuring the probe Also ensure that PEP in Probe End Projection Rosemount 5300 Series solids measurement on page 48 has been followed Figure 5 19 Probe end pulse offset Reference pulse No pulse from the surface Probe end pulse Ana
21. Technical Note Document No 00840 0300 4024 u Build up on antennas can often be avoided or reduced by using heat tracing or cleaning arrangements such as purging adapter For more information refer to the Rosemount Level Instrumentation Brochure Document No 00803 0100 4161 1 Valid for coaxial and single rigid probes 2 Valid for rigid and flexible single probes 3 Valid for cone antennas Installation considerations 27 Section 2 Installation Considerations Reference Manual September 2013 2 5 25 1 28 00809 0700 4530 Rev AA Solids measurement Solids generally provide a difficult measuring environment with low dielectric products in tall tanks where pull forces may act on the probe and dust steam or risk of coating are often present In addition the surface is not flat and the angle of repose tends to change As a result the signal levels are often very low and installation is of utmost importance Rosemount 5303 Adding to the installation considerations described in Tank installations on page 22 when measuring solids it is also important to consider the following Mount the probe as far away as possible from filling and emptying ports This will minimize load and wear and will help to avoid disturbances from the incoming product Figure 2 20 Rosemount 5303 solids recommended mounting position For flexible single lead probes the minimum clearance to the tank wall L or obstruction
22. arise in the side connections In hot applications it is recommended to keep the length of the inlet pipes as short as possible to minimize temperature drop between tank and chamber To simplify the verification process of the Rosemount GWR transmitters venting is recommended to manipulate the level in the cage and to drain the cage A standard integral cage vent located on the top part of the chamber typical position is right below the flange and a drain at the bottom of the chamber are suitable Refer to the Rosemount 9901 Series Product Data Sheet Document No 00813 0100 4601 for information The vent and drain make it possible to isolate the whole chamber during fill drain procedures For the Rosemount 5300 Series with DVC special considerations to chamber dimensioning apply A 3 or 4 in 75 or 100 mm inner diameter bypass chamber with flanges appropriately sized for the pressure and temperature of the application is required Materials used for the chamber should meet ASME boiler code requirement and the chamber should be isolated from the boiler or HP heater by valves With the Rosemount GWR transmitters it is recommended that single probes in chambers be used The single lead probe can tolerate any magnetite layer that may occur The probe must not touch the chamber wall and should extend the full height of the chamber but should not touch the bottom of the chamber Allow for transition zones varies with probe type and dielectr
23. can freeze or stick from magnetite coating or cause noisy signal due to vibration Therefore GWR offers additional advantages of lower maintenance and greater stability Vapor compensation functionality In the Rosemount 5300 Series Superior Performance GWR there are two functions to compensate for the vapor dielectric Static Vapor Compensation SVC Dynamic Vapor Compensation DVC With either option the compensation occurs in the transmitter electronics and a corrected level measurement is provided to the control system No additional compensation is required As it can be seen in Table 2 1 at 247 psia 17 bar there is an error in distance of 3 4 At 1543 psia 106 bar there is an error of 20 9 when there is no compensation for the vapor dielectric The error in distance increases with the pressure and at some point this deviation is not negligible and must be taken into account in order to get high accuracy Static vapor compensation SVC Forthe static compensation function the dielectric of the vapor at expected operating pressure and temperature is manually entered as part of the configuration of the transmitter This allows the unit to compensate for the dielectric at operating conditions The static compensation works well under stable conditions and in these applications the standard High Temperature High Pressure HTHP probe is used Dynamic vapor compensation DVC DVC becomes more important for the h
24. curve presentation in RRM Amplitude Reference peak ee Surface peak Distance UNZ Surface Surface peak threshold Amplitude 0 Reference Distance peak As presented in RRM Configuration Mode View Record Mode 1 LT 01 5300 242 2040070 8 6 2013 2 26 18 Amplitude mv Surface 4000 Vy VW 10000 12000 P2 Reference 14000 T 1 r L 70 4 i 10 0 10 20 30 40 50 80 90 100 110 120 Distance gt Troubleshooting procedures 65 Section 5 Troubleshooting Procedures Reference Manual September 2013 66 00809 0700 4530 Rev AA Figure 5 3 Rosemount 5300 Series with DVC Echo curve presentation in RRM Rosemount Plot Viewer LT 1063 5300 2F2 41735 LT 1063 5300 2F2 41735 6 21 2013 8 06 03 AM M Amgitude mV 3000 2 1 Surface 1000 2000 3000 4000 5000 6000 7000 P3 Reference n an Sa 05 00 05 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 Distance Level Distance Amplitude Surface Measurer ment 0 002 ft 4065 ft P1 Surface 0 000 ft 4 066 ft 8451 P2 Reference Reflector 2828 ft 1139 ft ATI7 P3 Reference 4 290 tt 0224 ft 6438 mV
25. end as a reference to calculate the actual level When the surface echo 15 lost use the probe end echo as reference to calculate the surface echo position See the Rosemount 5300 Series Reference Manual Appendix C Advanced Configuration for configuration instructions Document No 00809 0100 4530 This probe end echo must be in a consistent position It must either be free hanging at all times to create a negative pulse or it must be attached such that a positive pulse is created NOTE This function is not compatible with SQM or DVC Surface threshold A true surface echo calibrates the Dielectric Constant DC used PEP and a false surface echo miscalibrates the DC used by PEP Therefore set the surface threshold as low as possible without ever allowing false echoes to break it For the probe end threshold automatic setting is mostly OK but must be low enough to ensure probe end pulse detection It is recommended to perform the procedure once with an empty tank and once with product in the tank NOTE Assure that the tank settings Mounting Type Probe Type and Probe Length have been assigned correct values before continuing In RRM PEP is set using RRM gt Setup gt Advanced gt Probe End Projection Figure 3 10 Probe end projection 2000 Probe end 2000 Product surface o Probe end pulse Amplitude mV Probe end offset
26. end peak This probe end pulse is caused by the transition between the probe end and the surrounding media The pulse can be positive or negative depending on if or what type of centering disk is used see Figure 5 4 and Figure 5 5 Note that the probe end pulse is not visible when measuring on a high dielectric media such as water Troubleshooting procedures Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013 Table 5 1 Typical peak amplitudes for the Rosemount 5300 Series with a single lead probe in 4in 100 mm chambers Reference peak 10 000 mV Surface peak Rosemount 5301 with oil DC 2 2 000 mV Surface peak Rosemount 5301 with water 10 000 mV DC 80 at 3 ft 1 m distance 1 This value does not apply and may be considerably lower when the probe is completely submerged in product or in applications with saturated steam or heavy condensation Table 5 2 Typical reference pulse amplitudes for the Rosemount 5300 Series with different probe types Standard Seal 12000 16000 5 6000 Seal 9000 11000 5000 7000 mV 1 This value does not apply and may be considerably lower when the probe is completely submerged in product or in applications with saturated steam or heavy condensation Rosemount 5300 Series probe end pulse Figure 5 4 A PTFE centering disk or a free hanging probe end give a negative probe end pu
27. if a different transmitter head is mounted on the DVC probe If a calibration procedure is needed this should be performed with an empty chamber at ambient conditions For best performance it is recommended that the chamber is cleared of any steam and or condensate prior to the calibration See the Reference Manual supplied with the transmitter for details on the calibration procedure Note that Probe End Projection and Signal Quality Metrics are disabled when DVC is enabled To minimize errors due to installation it is recommended that the distance between the chamber and the vessel kept as short as possible a connections to the chambers should be large enough to allow good fluid flow through u the chamber and the piping to it should be well insulated so the fluid temperature is as close as possible to the vessel temperature For further information on chamber insulation see Insulation on page 22 Chamber fabrication and probe selection Dimensioning the chamber correctly and selecting the appropriate probe is key to success in guided wave radar applications Either follow the recommendations below and have the chamber manufactured accordingly or purchase the Rosemount 3300 or 5300 Series transmitter bundled with the Rosemount 9901 Chamber where Emerson has already incorporated these best practices See the Rosemount 9901 Chamber for Process Level Instru mentation Product Data Sheet Document No 00813 0100 4601 for a 9901
28. include during commissioning process 36 3 3 1 Trim Near Zone 1 lt lt 37 Table of Contents i Table of Contents Reference Manual September 2013 00809 0700 4530 Rev AA 3 3 2 Changing the Upper Null Zone 2 38 3 3 3 Measure andlearmlunction 4 n nk E ERST 39 33 4 Vapor colnpehsalloll ves exe bird EE UC OO NE 39 3 3 5 Remote housing 1 lt lt 43 3 3 6 Setting range values for chambers 43 3 3 7 Signal Quality Metrics Rosemount 5300 and 5400 Series 47 3 3 8 Configuration for process conditions 47 3 3 9 Probe End Projection Rosemount 5300 Series solids measurement 48 3 3 10 Store backup and verification files 49 3 9 10 Vite bah pde Ra PH A 49 3 3 12 On the bench test optional 49 Section 4 Measurement validation Safetymessages dasa ENESE EU EE REE 51 42 52 4 3 Measurement validation at operating conditions 52 4 4 Operation and maintenance proof testing for SIS 58 AAA 58 AAD amp 59 AAS Specialtools sais cteasiasdcsisigtarieessassoasseaeatandawas 59 444
29. is 4 in 10 cm in the case of smooth metallic walls and 20 in 50 cm in the case of disturbing objects rugged metallic or concrete plastic walls u Installing the probe at about 3 to 2 of the silo radius is recommended to compensate for measurement errors caused by centered filling of the material cone The minimum recommended probe distance to tank wall or disturbing object is 20 in 50 cm unless the wall is comprised of smooth metal Then the distance is 4 in 10 cm In any case the probe should not be able to touch the wall of the tank during operation The maximum recommended nozzle height is nozzle diameter 4 in 100 mm a When nozzles are more than 4 in 100 mm in height a Long Stud LS option is recommended to prevent the probe from contacting the nozzle Long stud Nozzle 9 8 250 mm height Nozzle diameter Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 Probe installation should occur when the silo is empty and the probe should be regularly inspected for damage u Avoid 10 in 250 mm DN250 or larger diameter nozzles especially in applications with low dielectric constant n For environments where electrostatic discharges are likely to occur e g plastics it is recommended that the probe end is grounded with a proper grounding connection R 10 In case o
30. model code example The recommended chamber diameter is 3 in 75 mm or 4 in 100 mm Chambers with diameter less than 3 in 75 mm may cause problems with build up and it may also be difficult Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 to center the probe Chambers larger than 6 in 150 mm can be used but provide no advantages for the radar measurement When specifying a chamber it is also important to consider the physical weight of the instrument and chamber the properties of the liquid and the chance of plugging due to the build up of deposits The location of the side pipes and the effective measurement range is determined by the mating tank connections There are no diameter requirements for the side pipes but build up and clogging should be taken into consideration The recommended inlet pipe diameter is not less than 1 in 25 mm for water filtered minimal quality lube oil or liquids with similar viscosity For fuel oil bunker oil that is liquids with higher viscosity the minimum recommended inlet pipe diameter is 2 in 50 mm Note that the diameter of the inlet pipe should always be less than the chamber diameter Ensure that the inlet pipes do not protrude into the chamber because they may interfere with the radar measurement Always use the same material of construction for the chamber and the tank or mechanical tensions can
31. must comply with the design temperature and the design pressure for the application In a chamber installation there may be temperature differences between the chamber and the tank Figure 2 10 Recommended choice of process seal type Pressure psig bar 5000 345 3524 243 2940 203 High Pressure Seal Cryogenic Seal 580 40 Temperature F C 14 1 320 196 76 60 40 40 302 150 392 200 752 400 For additional information on pressure and temperature specifications refer to White paper Selecting the correct process seal for Rosemount GWR products Rev 1 September 2009 When installing a Rosemount GWR transmitter in high temperature applications it is important to consider the ambient temperature The Rosemount 5300 Series transmitter electronics have requirements for maximum ambient temperature of 140 F 60 158 70 or 176 F 80 C limits depend on Ex approval and Hart vs FF protocol refer to the product related Installation considerations 19 Section 2 Installation Considerations Reference Manual September 2013 2 3 5 20 00809 0700 4530 Rev AA Product Data Sheet for more information The ambient temperature is affected by the process temperature Figure 2 11 shows the ambient temperature vs process temperature Figure 2 11 Ambient temperature vs process temperature Ambient temperature F C Pro
32. temperature will result in inaccuracies Figure 5 22 Displacer used for measurement Example 50in 1270 mm displacer calibrated to SG 0 9 will only show 45 in 1143 mm level reading at full range with a product that has a SG 0 8 This results in a systematic error of 45 40 5 127 mm Differential pressure Another common method for measuring level is using pressure or Differential Pressure DP transmitters These are examples of indirect level measurement methods where incorrect conversion or installation can result in inaccuracies Troubleshooting procedures 79 Section 5 Troubleshooting Procedures Reference Manual September 2013 00809 0700 4530 Rev AA Potential problems include E Fluid density changes source grade product and temperature affect the density of the fluid and thereby the level output a In case of a wet leg is it completely filled Or if a dry leg is used is it really dry Loss of fluid and condensed fluid respectively create an offset in the level reading Consider using either an electronic or a capillary remote seal If a fill fluid is used is its density known Has the transmitter been scaled correctly single pressure transmitter is used process pressure will create an offset in the level reading A differential pressure transmitter should be used Figure 5 23 Differential pressure transmitter Wet Leg Level offset is creat
33. 00 4530 Rev AA Installation setup It is important that the vapor compensation function is calibrated after installation and after the basic configuration is complete The basic configuration includes setup of the unit chamber installation and the use of a remote housing connection Before calibration do the following The surface level must be at least 19 7 in 0 5 m below the end of the reflector 36 in 0 9 m or 39 7 in 1 0 m below the flange depending on reflector probe length Note that it is recommended to empty the pipe chamber and to ensure that it is cleared from any steam and or condensation remains Perform the calibration at ambient pressure and temperature conditions when the vapor dielectric constant is close to 1 0 To calibrate DVC choose one of the following RRM gt Guided Setup gt Device Specific Configuration if the configuration is recommended RRM gt Setup gt Advanced gt Vapor Compensation tab gt Click the Calibrate Vapor Compensation button Make sure Use Vapor Compensation is selected Figure 3 6 Calibrate DVC Thresholds Near Zone Probe End Projection Yapor Compensation Echo Tracking This device is capable of compensating for dynamic changes of the vapor dielectric constant Calibration of the function is required in order to use it Used Max Vapor DC Advanced Vapor Compensation Options Reference Reflector Type Vapor DC Filter Factor 0 100
34. 126 EHBLSBDDIV 3 1 7 Buelcombustion Clean Up xe rper rr RE RARE ions 3 1 8 JEN UB cca 3 KO me ubt S eed is 3 1 10 Miscellangolis rrr Rx 4 Section 2 Installation considerations 2i Saletyimessades TUN PPP EPIS 5 2 2 Introduction cssc ee cosi ERR peer op UEM Rd PES 6 2 3 COha nmiberdstallatlOFs s EV She 6 2 3 1 High pressure steam applications 7 2 3 2 Chamber fabrication and probe selection 14 2 3 3 Chamber Mounting directo er ee die ers ehem bs 19 2 41 JEXISUMOCHAMDENS 2 snaps 19 2 3 5 Pressure and temperature specifications 19 2 3 6 Remote housing Jis rrr 20 23 75 22 23 22 2 4 1 Recommended mounting position 22 24 2 Nozzle considerations sene corr ected ed rep ve ema 25 2 4 3 Probeandantennaselection 27 25 SolidsmieasHreDentisscebp ciens UPODCHO PERSE EU HDI DIO xPPEUDE EE 28 2 5 1 ROSEMOUNES3SOS 28 25 2 JRosemount5b500 Sells oen bee EORR ER PER 31 Section 3 Commissioning 3 1 Safety messies ires eaedem e dup mercem pi de 35 3 2 IntrodHtblOll secs ori LR PUER 36 3 3 Functions of procedures to
35. 16 7 1 55 24 5 649 343 2176 150 14 34 1 8 34 2 676 358 2611 180 11 86 2 19 48 691 366 2900 200 9 92 2 67 63 4 699 370 3046 210 8 9 3 12 76 6 702 372 3120 215 Above critical point distinct liquid and gas phases do not exist Extreme high pressures and temperatures In these applications temperatures above 300 F 150 C and pressures above 580 psi 40 bar are common Therefore having robustly designed equipment which prevents leakage and performs reliably is vital for safety Magnetite coating While these applications are generally considered to be composed of clean water and steam it is normal to have a layer of magnetite on metallic surfaces In some cases the deposits can be heavy enough to cause some mechanical linkages to freeze and stick resulting in a need for maintenance With no moving parts in the GWR probe assembly magnetite poses no issues for sticking 1 Maximum limit for GWR is 180 bar For applications over this pressure limit other solutions are used 8 Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 Heavy vibrations Heavy vibrations from pumps can cause a noisy signal from mechanical based techniques Advantages of GWR over other techniques Since GWR measurement devices are completely independent of density these associated errors are not present thus eliminating the need for this compensation GWR has no moving parts that
36. 5 3 Diagnostics Basic rules and philosophy about the diagnostic messages is that the transmitter will generate an alarm current if the diagnostic message indicated is a device error or a lost measurement alarm If the transmitter is not generating an alarm current but there are one or more diagnostic messages the transmitter is working properly and the messages are more measurement information device warnings status type of messages For a FOUNDATION fieldbus device the above information is the same but for a FOUNDATION fieldbus device there is no alarm current instead it is reflected through Bad status of the measurement value Some diagnostic messages are sequential diagnostic messages generated because another diagnostics is active In the device itself the diagnostics is split into different categories Device status Device errors Device warnings Measurement status Specific status messages related to specific topics such as Volume calculation status Analog output status HART only These categories are displayed in different ways across the different configuration tools Refer to the product related reference manuals for details In Rosemount Radar Master RRM the main diagnostics is presented in the Tools menu but diagnostics is also presented in other places such as the Device Display window Figure 5 1 Diagnostics in the Device Display window vice Display Untit
37. 5400 Series Signal Quality Metrics SQM indicates the surface signal integrity compared to the noise It can be used to schedule maintenance to clean the probe or detect and monitor turbulence boiling and foam The Rosemount 5300 Series with Diagnostics Suite option and the Rosemount 5400 Series have the SQM function See the Rosemount 5300 Series and Rosemount 5400 Series Reference Manuals for set up details Document No 00809 0100 4530 and 00809 0100 4026 To view SOM in RRM RRM gt Tools gt Device Display gt Signal Quality Metrics NOTE If SQM is not supported or disabled the signal quality and surface noise margin will always be set to 0 SQM can be shown on the LCD panel see Operation in the Rosemount 5300 Series and Rosemount 5400 Series Reference Manuals Document No 00809 0100 4530 and 00809 0100 4026 SQM can be assigned to transmitter variables SV TV or QV In RRM this can be done by selecting RRM gt Setup gt Output Variables can be sent to the Distributed Control System DCS to trigger an alarm Suitable trigger levels vary from application to application Guidelines for appropriate values can be determined by logging SQM over time and viewing minimum maximum values The signal quality alarm trigger value should be at least 1 but a better guideline is 2 3 Configuration for process conditions The Rosemount 5400 and 5600 Series have advanced configuration options for different process con
38. Failure to follow safe installation and servicing guidelines could result in death or serious injury Make sure only qualified personnel perform the installation Use the equipment only as specified in this manual Failure to do so may impair the protection provided by the equipment Do not perform any service other than those contained in this manual unless you are qualified Process leaks could result in death or serious injury Make sure that the transmitter is handled carefully If the process seal is damaged gas might escape from the tank if the transmitter head is removed from the probe High voltage that may be present on leads could cause electrical shock Avoid contact with leads and terminals Make sure the main power to the transmitter is off andthe lines to any other external power source are disconnected or not powered while wiring the gauge Probes covered with plastic and or with plastic discs may generate an ignition capable level of electrostatic charge under certain extreme conditions Therefore when the probe is used in a potentially explosive atmosphere appropriate measures must be taken to prevent electrostatic discharge 35 Section 3 Commissioning September 2013 3 2 3 3 36 Introduction Reference Manual 00809 0700 4530 Rev AA The transmitter installation should be carried out as described in the Quick Installation Guide that is enclosed with every transmitter Even though the transmitter ma
39. Reference Manual 00809 0700 4530 Rev AA September 2013 Rosemount Process Radar in Power Applications Best Practices User Guide w D F COMMUNICATION PROTOCOL EN FOUNDATION WirelessHART amp ROSEMOUNT EMERSON Process Management Reference Manual 00809 0700 4530 Rev AA September 2013 Rosemount Process Radar in Power Applications Best Practices User Guide The products described in this document are NOT rated for use in nuclear qualified applications Using non nuclear qualified products in applications that require nuclear qualified hardware or products may cause failure of the device For information on Rosemount nuclear qualified products contact your local Emerson Process Management Sales Representative The Guided Wave Radar GWR products Rosemount 5300 and 3300 Series are designed to meet FCC and R amp TTE requirements for a non intentional radiator It does not require any licensing whatsoever and has no tank restrictions associated with telecommunications issues For Non intentional radiators Rosemount 3300 and 5300 Series the Rosemount products are compliant with EMC Directive 2004 108 EC The Non contacting radar devices comply with part 15 of the FCC rules There are no restrictions for use of the Rosemount 5401 low frequency device The high frequency Rosemount 5402 may be used in any type of vessel The mid frequency Rosemount 5600 Series must be used in metallic vessels If
40. Using Loop Test enter the mA value representing a low alarm current output and verify that the analog current reaches that value using the reference meter This step tests for possible quiescent current related failures 1 The FMEDA report is accessible at www emersonprocess com rosemount safety PriorUse htm 58 Measurement validation Reference Manual Section 4 Measurement validation 00809 0700 4530 Rev AA September 2013 4 4 2 4 4 3 4 4 4 5 Perform a two point calibration check of the transmitter by applying the level to two points on the probe within the measuring range Verify that the current output corresponds to the level input values using a known reference measurement This step verifies that the analog output is correct in the operating range and that the primary variable is properly configured 6 Enable write protection 7 Restore the loop to full operation 8 Remove the bypass from the safety logic solver or otherwise restore normal operation 9 Document the test result for future reference For troubleshooting the transmitter see Section 5 Troubleshooting procedures or the Rosemount 5300 Series Reference Manual Document No 00809 0100 4530 For best performance use the 4 20 mA range points as calibration points Visual inspection It is recommended to inspect the probe for possible build up or clogging Special tools Not required Product repair The Rosemount 5300 Series is repaira
41. ain pit for waste oil condensate Water wash tanks a Fire water tanks u Lake or pond level 4 Power applications Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 Section 2 Installation considerations Safety messages ssns 5 Introduction 5225s ar rrr ES EE E E PEE 6 Chamber installations 15452535225 Pa UE ET V EE 6 Tankinstallations os rer tha mtn tI ER CUP FERT C PETS 22 Solids Measurement TQUE PEL NINE PE 28 2 1 Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Please refer to the following safety messages before performing an operation preceded by this symbol Explosions could result in death or serious injury Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations certifications Before connecting a HART based communicator in an explosive atmosphere make sure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices Do not remove the gauge cover in explosive atmospheres when the circuit is alive Failure to follow safe installation and servicing guid
42. ally the optimal location is 1 3 of the radius from the tank wall Figure 2 15 Proper and improper locations for the Rosemount 5400 Series transmitter A E B F C CN m GENE Le Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 2 4 2 Nozzle considerations Depending on the selection of transmitter model and probe antenna special considerations may have to be taken because of the nozzle Rosemount GWR transmitters The coaxial probe signal is unaffected by the nozzle The single probe has some nozzle restrictions e g avoid using nozzles with reducers and nozzles that are too tall or too narrow Figure 2 16 Rosemount 5300 Series mounting in nozzles UNZ H WNNIIZ S Avoid nozzles with reducer unless using a coaxial probe Table 2 9 Rosemount 3300 and 5300 Series nozzle considerations Single Rigid Flexible Coaxial Recommended Nozzle Diameter Stn 75 100 mm gt probe diameter Minimum Nozzle Diameter D 2 in 50 mm gt probe diameter Recommended Nozzle Height H 9 4 in nozzle diameter N A 1 The Trim Near Zone function may be necessary or an Upper Null Zone setup may be required to mask the nozzle 2 Longer nozzles may be used in certain applications Consult your local Emerson Process Management repre
43. ambient temperature is considered Nozzle cham ber tank insulation for the HTHP process seal version should not exceed 4 in 10 cm at the flange Figure 2 13 Chamber insulation HTHP version Chamber insulation Tank installations Recommended mounting position When finding an appropriate mounting position for the transmitter the conditions of the tank must be carefully considered Installation considerations Reference Manual 00809 0700 4530 Rev AA Section 2 Installation Considerations September 2013 For the Rosemount GWR transmitters Do not mount close to inlet pipes and ensure that the probe does not come in contact with the nozzle X If there is a chance that the probe may come in contact with the tank wall nozzle or other tank obstructions the coaxial probe is the only recommended choice However it should only be used with clean liquids Recommended clearance is given in Table 2 8 below If the probe sways due to turbulent conditions the probe should be anchored to the tank bottom Y Refer to the Rosemount 3300 or 5300 Series Reference Manual Document No 00809 0100 4811 or 00809 0100 4530 for anchoring options Also note that violent fluid movements that cause high sideway forces may break rigid probes Figure 2 14 Mounting considerations Table 2 8 Recommended clearance for probes Coaxial Rigid Single Lead Flexible Single Lead Min
44. ances such as other pipes agitation fluid flow foam and other objects The pipes can be located anywhere in the vessel that allows access For GWR the microwave signals are guided by the probe making it resistant to disturbing objects Bypass chambers may be located on a small portion of a tank or column and allow access to the measurement instrument Bypass chambers often include valves to allow instrumentation calibration verification or removal for service Bypass chambers and stilling wells are not without limitations Generally pipes should be used with cleaner fluids that are less likely to leave deposits and that are not viscous or adhesive Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 Apart from the additional cost of installation there are some sizing and selection criteria for the radar gauges that must be considered This document outlines those considerations GWR is the preferred technology for shorter installations where rigid probes may be used This makes it a suitable replacement for caged displacers which are often less than 10 ft 3 m The probes are available in a variety of materials to handle corrosive fluids For further information on how to replace displacers with GWR in existing chambers see the Replacing Displacers with Guided Wave Radar Technical Note Document No 00840 2200 4811 For taller applications or those with
45. ation of your Rosemount radar transmitter or you cannot find the suitable best practice for your application contact your local Emerson Process Management representative for support For more information on how to choose the correct technology and transmitter for an application see the Engineer s Guide to Level Measurement for Power and Steam Generation document available to order on www rosemount com Power applications 1 Section 1 Power Applications Reference Manual September 2013 1 2 1 3 1 4 1 5 00809 0700 4530 Rev Boiler systems For boiler systems radar transmitters are commonly used for the following applications Boiler drum level control High pressure feedwater heater Low pressure feedwater heater u Steam separators once through systems Boiler blowdown tanks Flash surge tanks a Condenser hotwell Condensate storage a Deaerator Turbines For turbines radar transmitters are commonly used for the following applications Gland steam condenser Lubrication oil tanks Hydraulic oil tanks Water supply and pre treatment For water supply and pre treatment activities radar transmitters are commonly used for the following applications Demineralization system chemical storage a Intake water screens Rock salt u Brine tank a Boric acid heavy water and makeup water Cooling system For cooling systems radar transmitters are commonly used for the follo
46. ational 952 906 8888 Fax 952 906 8889 www rosemount com Emerson Process Management Blegistrasse 23 P O Box 1046 CH 6341 Baar Switzerland Tel 41 0 41 768 6111 Fax 41 0 41 768 6300 Emerson FZE P O Box 17033 Jebel Ali Free Zone Dubai UAE Tel 971 4 811 8100 Fax 971 4 886 5465 Emerson Process Management Asia Pacific Private Limited 1 Pandan Crescent Singapore 128461 Tel 65 6777 8211 Fax 65 6777 0947 Enquiries AP EmersonProcess com Emerson Process Management Latin America 1300 Concord Terrace Suite 400 Sunrise Florida 33323 USA Tel 1 954 846 5030 Emerson Beijing Instrument Co No 6 North Street Hepingli Dongcheng District Beijing 100013 China Tel 8610 642 82233 Fax 8610 642 87640 ROSEMOUNT Reference Manual 00809 0700 4530 Rev AA September 2013 Standard Terms and Conditions of Sale can be found at www rosemount com terms_of_sale The Emerson logo is a trademark and service mark of Emerson Electric Co Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc HART is a registered trademark of the HART Communication Foundation All other marks are the property of their respective owners September 2013 Rosemount Inc All rights reserved gt EMERSON Process Management
47. ble by major component replacement All failures detected by the transmitter diagnostics or by the proof test must be reported Feedback can be submitted electronically at www emersonprocess com rosemount safety Contact Emerson Process Management For further information on proof testing see the Rosemount 5300 Series Reference Manual Document No 00809 0100 4530 or contact your local Emerson Process Management repre sentative 1 For best performance use the 4 20 mA range points as calibration points Measurement validation 59 Section 4 Measurement validation Reference Manual September 2013 00809 0700 4530 Rev AA 60 Measurement validation Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013 Section 5 Troubleshooting procedures Safety messages ss ie cccsccssiseresociersecssaveeseconwerseaeseee ae 61 Introduction ES 62 Diagnostics 63 Echo curve ANALYSIS 64 Sources of measurement error 73 5 1 Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Please refer to the following safety messages before performing an operation preceded by this symbol Explosions could result in death or ser
48. bly alter performance and jeopardize safety Unauthorized changes that interfere with the integrity of the welds or flanges such as making additional perforations compromise product integrity and safety Equipment ratings and certifications are no longer valid on any products that have been damaged or modified without the prior written permission of Emerson Process Management Any continued use of product that has been damaged or modified without prior written authorization is at the customer s sole risk and expense Introduction In this section the steps of measurement validation at operating conditions are described The measurement validation should be performed under operating conditions and the actual liquid must be used to ensure the accuracy of the measurement data The validation procedure outlined in this section can also be used as a suggestion of a proof test Measurement validation at operating conditions Once a Rosemount radar level transmitter has been installed and configured it will continuously deliver measurements with a minimum of maintenance The electronics are self adjusting so no re calibration is needed The outlined procedure is intended to be a part of the startup process or used as are occurring functional check to validate the integrity of the transmitter during actual operating conditions If the verification fails refer to Section 5 Troubleshooting procedures All ofthe steps in this sample verification pr
49. cations Technical Note Document No 00840 0100 4530 for details Installation considerations 13 Section 2 Installation Considerations Reference Manual September 2013 PAG WP 00809 0700 4530 Rev AA How to choose reflector length The long reflector 20 in 500 mm has the best accuracy and is recommended for all chambers where the dimensions of the chamber allow for it If the distance from the flange to the upper inlet is less than 28 in 710 mm the short reflector should be chosen This distance is a minimum when dynamic compensation is required within the whole measuring range from the lower to the upper inlet If this is not required the long reflector can be used and dynamic compensation is possible up to 28 in 710 mm from the flange However always ensure that there are no disturbances from inlets etc close to the reference reflector end when using the 2 in DVC solution DVC calibration When a transmitter is ordered with the optional DVC the function is activated from factory and the special probe is supplied For the 2 in solution a calibration procedure is needed on site during the commissioning phase For the 3 and 4 in solution the transmitter is calibrated from factory and no calibration on site is normally needed There are however two cases where a calibration procedure is needed for the 3 and 4 in solution if the transmitter is reset to factory settings which will delete the DVC calibration or
50. cess temperature F C 392 200 320 196 856 417 27 200 93 400 204 600 316 800 427 NOTE The final maximum ambient temperature rating depends on the type of approval In high temperature applications the ambient temperature limit of the electronics may be exceeded when mounted close to the vessel To prevent this the remote connection described in the next section should be considered Remote housing A remote housing connection can be used with Rosemount 5300 Series Superior Performance GWR transmitters to enable reliable measurement in environments where very high ambient temperatures or excessive vibrations exist at the mounting location of the vessel It enables the transmitter electronics to be mounted away from the probe such as to lower the ambient temperature or to place the housing in a better location for example to be able to read the display or enable installation in tight spaces The remote housing connection is specified to handle 302 F 150 The cable used is an SST flexible armored coaxial cable which is delivered with a mounting bracket for wall or pipe mounting The remote housing connection is available in lengths of 3 2 ft 1 6 5 ft 2 m or 9 8 ft 3 m Installation considerations Reference Manual 00809 0700 4530 Rev AA Section 2 Installation Considerations September 2013 Figure 2 12 Rosemount 5300 Series with remote housing When the remot
51. ctivated b Process valves are closed before draining for chambers only c The tank or chamber is emptied completely d Level trend is reviewed for accuracy 7 Echo curve is verified with empty tank Echo curve is compared with previous plots b Echo curve is stored 8 Level is monitored while filling the tank a Log functionality for the transmitter level output is activated b Process valves are closed before filling for chambers only c The tank or chamber is filled completely d Level trend is reviewed for accuracy Checklists 83 Appendix A Checklists September 2013 P523 Troubleshooting procedure Reference Manual 00809 0700 4530 Rev AA Step Task Completed 1 Voltage at transmitter terminals are checked C 2 DCS trends are checked 3 Tank survey is done to identify the application C 4 Basic errors cables transmitter diagnostics etc are checked a Cables are connected properly b Diagnostic messages are checked in RRM 5 Verification procedure is executed if necessary as described in the measurement validation procedure 6 Echo curve analysis is performed and analyzed C 7 Threshold settings are checked Rosemount 3300 and 5300 Series a Automatic threshold settings are used b Dielectric constants are entered correctly c Measure amp Learn function is applied if necessary d Custom threshold adjustments are applied 8 Threshold settings are checked Ro
52. d be set at 800 1000 mV a Itshould never be closer than 300 mV to any disturbing objects Example If there is a 1100 mV peak from inlet pipe the threshold around it should be 1400 mV a The threshold should never be below 800 mV in the range 0 1 ft 0 3 m and never below 500 mV from 1 ft 0 3 m upwards For products with very low dielectric constants such as solids it may be required to lower the threshold additionally and or to activate the PEP function See Probe End Projection Rosemount 5300 Series solids measurement on page 48 for the activation of PEP Rosemount non contacting radar transmitter threshold settings Recommendations for the Rosemount 5400 and 5600 Series T Apply the Measure amp Learn function Rosemount 5400 Series only 2 If needed use the following best practices to apply custom threshold adjustments m Generally the threshold should be at 20 of the surface peak Example if the surface is 2000 mV the threshold should be set at 400 mV m It should never be closer than 200 mV to any disturbing objects Example if there is a 500 mV peak from an obstacle the threshold around it should be 700 mV wm The threshold should never be below 300 mV For products with very low dielectric constants such as solids it may be required to lower the threshold additionally For the Rosemount 5600 Series manual adjustments are always recommended Common problems Threshold below the surface peak In this
53. dia measured see Table 2 5 The weight on the flexible probes reduces the measurement range Therefore it is recommended to size the cage A C so it does not interfere with the effective measurement range B The transition zones also limit the minimum probe length 1 Fora Rosemount 5300 Series with DVC only rigid probes are available in lengths up to 13 ft 4 m 16 Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 Table 2 4 Transition zones for the Rosemount 3300 Series installed in metallic pipes Upper Transition Zone Lower Transition Zone Probe Size High Dielectric Low Dielectric High Dielectric Low Dielectric Single Rigid Ain 10 cm Ain 10 cm 2 in 5 cm Ain 10 cm Single Flexible 5 9in 15cm 8in 20 7 5in 19cm 10 2 in 26 cm Coaxial Ain 10 cm Ain 10 cm 1 2 in 3 cm 2in 5 cm Table 2 5 Transition zones in chambers for the Rosemount 5300 Series installed in metallic pipes Dielectric Rigid Single Rigid Single Flexible Single Coaxial Constant Lead 2 Lead Lead with metallic centering disk Upper 80 water 4 3in 11cm 4 3in 11cm 4 3in 11cm 4 31 11 Transition E Zone 2 oil 6 3in 16cm 6 3in 16cm 7 1in 18cm 4 3 in 11 Lower 80 water 2 in 5 cm 2 in 5 cm 5 5 in 14 cm Ain 10 cm
54. ditions such as Foam Turbulent Surface Rapid Level Changes or Solid Product only Rosemount 5600 Series This means that the transmitter database configuration is optimized for the process condition selected e g solids measurements Additional adjustments of the database might in some cases become necessary for solids measurement In such cases contact a Rosemount representative for further details on how to proceed By selecting the suitable option for the process condition the measurement parameters are optimized for the selected condition RRM gt Advanced gt Process condition NOTE Select only one maximum two process conditions otherwise the effect may cancel out each other For the Rosemount 5300 Series in applications with rapid level changes such as a flash tank measurement parameters can be adjusted to enable a faster response time Select Rapid Level Changes under Process Condition and set Damping Value to 0 s default value is 2 s RRM gt Tank gt Rapid Level Changes Under Process Condition RRM gt Advanced gt Echo Tracking gt Damping Value 47 Section 3 Commissioning Reference Manual September 2013 3 3 9 48 00809 0700 4530 Rev AA Probe End Projection Rosemount 5300 Series solids measurement Probe End Projection PEP handles long measuring ranges on media with low dielectrics such as solids If the signal is not reflected at the surface the Rosemount 5300 Series uses the probe
55. e housing is used together with the Rosemount 5300 Series there may be a limit on measuring range and a decrease in accuracy This is because the remote housing introduces a double bounce in the tank signal at 1 5 times the remote housing cable length Because the double bounce occurs at approximately 1 5 times the remote housing cable length a longer remote housing cable can increase the maximum measuring range for distances up to 10 ft 3 m Table 2 7 shows the maximum recommended measuring range with remote housing for different remote housing lengths installation types dielectric constants and probe types Table 2 7 Rosemount 5300 Series remote housing measuring range Dielectric Rigid Single Rigid Single Flexible Single Constant 8mm 13mm Chamber pipe 2 10 ft 3 15f 45m 338 10m A 1m installations lt 4 in 80 10 ft 3 m 15 4 5m 33 ft 10 mf 2 Remote 100 mm Housing 2 4ft 1 25m 48 1 25 m 4 ft 1 25 m Tank installations 80 10 ft 3 MU 10 ft 3 MU 159 ft 48 5 my Chamber pipe 2 10 ft 3 m 15 ft 4 5m 338 10m 2 2m installations lt 4 in 80 10 ft 3 m 15 ft 4 5 m 33 10 m Remote 100 Housing 2 9 ft 2 75 9 ft 2 75 9 ft 2 75 Tank installations 80 10 ft 3 MU 10 ft 3 MU 154 ft 47 m Chamber pipe 2 15 ft 4 5 m 33 ft 10 my 9 3m installations lt 4 in 80 15 ft 4 5 m 33 ft 10 m 2 Remote 100 mm 10 ft 3 m Housing 2 14 ft
56. e measurement performance in the near zone is maintained even under these conditions and prevents false echo indication This may be the case for example when a single lead probe is installed in a chamber or if there are disturbing obstacles in the near zone As best practice in power applications where short chambers are often used the Trim Near Zone TNZ function is advised This function is especially recommended together with remote housing For the Rosemount 3300 Series TNZ instructions refer to the Rosemount 3300 Series Reference Manual Section 6 Service and Troubleshooting Document No 00809 0100 481 1 NOTE The TNZ function should only be used for reducing impact from stationary disturbances It is not suitable for occasional disturbances For firmware version 2 A2 released April 2009 the TNZ is not possible in combination with narrow nozzles as defined below 2in 50 mm Nozzle height 12 in 300 mm Nozzle diameter lt 2 in 50 mm for all single probes except 13 mm single rigid Nozzle diameter 3 in 75mm for 13 mm single rigid NOTE The TNZ function cannot be used with the Rosemount 5300 Series DVC option The TNZ function is automatically blocked in RRM when DVC is activated To activate the TNZ function ensure that the tank or chamber is empty or that the upper product is not closer than 43 in 1 1 m Then execute the TNZ command RRM gt Advanced gt Near Zone gt Trim Near Zone
57. e threshold the amplitude and position of the bottom or probe end pulse 2 Store the echo curve Permanently store the echo curve for future use with re occurring verification procedures Step 7 monitor level while filling Repeat Step 5 but fill the tank or chamber instead of emptying it Measurement validation 57 Section 4 Measurement validation Reference Manual September 2013 4 4 4 4 1 00809 0700 4530 Rev AA Operation and maintenance proof testing for SIS The Rosemount 5300 Series Prior Use option must be tested at regular intervals to confirm that the overfill and empty tank protection function result in the desired system response The required proof test intervals are dependent on the configuration of the transmitter and the process environment The Rosemount 5300 Series is designed to have a 5 year proof test interval assuming it represents the typical 35 of the SIF PFDAyc However it is the responsibility of the operator owner of the system to determine the sufficient time interval and verify that it is followed See the FMEDA report for additional details or references If the overfill and empty tank protection function cannot be tested by a controlled filling to the response height a suitable simulation of the level or of the physical measuring effect must be used to make the level sensor respond The simulation can be done in three different ways by short circuiting the probe by simulati
58. ed the transmitter automatically compensates for changes in vapor dielectrics Table 3 4 Level reading errors during shutdown with fixed saturated water steam correction activated Entered Error in reading when actual Vapor DC is 1 Offset in reading if Vapor DC Vapor DC is configured correctly Surface at 15 in 380 mm Surface at 30 in 760 mm from flange from flange 1 001 0 in 0 mm 0 mm 0 in 0 mm 1 022 0 2 in 4mm 0 3 in 8 mm in 0 mm 1 180 1 3 in 33 mm 2 6 in 65 mm 0 mm When performing a verification at ambient pressure and temperature conditions always set vapor dielectric to 1 applies to static vapor compensation Otherwise the level reading will be incorrect Also see Static Vapor Compensation Rosemount 5300 Series Static Vapor Compensation Rosemount 5300 Series For high pressure saturated steam applications the specific properties of water and saturated steam must be taken into account when commissioning the transmitter The standard version 39 Section 3 Commissioning Reference Manual September 2013 40 00809 0700 4530 Rev AA of a Rosemount 5300 Series level transmitter can be configured for static compensation of vapor by manually entering the dielectric constant of vapor to compensate for the error induced by the saturated steam For applications with a varying pressure and or temperature certain models of t
59. ed by incomplete fill Density of fill fluid must be ace known Level offset is created by condensed fluid 80 Troubleshooting procedures Reference Manual Appendix A Checklists 00809 0700 4530 Rev AA September 2013 AppendixA Checklists Safety MESSAGES 81 Checklists SEDE Cede 82 1 Checklists Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Please refer to the following safety messages before performing an operation preceded by this symbol Explosions could result in death or serious injury Verify that the operating environment of the gauge is consistent with the appropriate hazardous locations certifications Before connecting a HART based communicator in an explosive atmosphere make sure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices Do not remove the gauge cover in explosive atmospheres when the circuit is alive Failure to follow safe installation and servicing guidelines could result in death or serious injury Make sure only qualified personnel perform the installation Use the equip
60. elines could result in death or serious injury Make sure only qualified personnel perform the installation Use the equipment only as specified in this manual Failure to do so may impair the protection provided by the equipment Do not perform any services other than those contained in this manual unless you are qualified Process leaks could result in death or serious injury Make sure that the transmitter is handled carefully If the process seal is damaged gas might escape from the tank if the transmitter head is removed from the probe High voltage that may be present on leads could cause electrical shock Probes covered with plastic and or with plastic discs may generate an ignition capable level of electrostatic charge under certain extreme conditions Therefore when the probe is used in a potentially explosive atmosphere appropriate measures must be taken to prevent electrostatic discharge Installation considerations 5 Section 2 Installation Considerations Reference Manual September 2013 2 2 2 3 00809 0700 4530 Rev Introduction In addition to selecting the appropriate radar level transmitter mechanical installation is one of the most critical steps of the commissioning procedure When done correctly the subsequent transmitter configuration will be considerably simplified Because of the wide usage and application in the power industry this section provides a framework for chamber installations tank i
61. er is used which does not meet these space requirements a spool piece can be added For an installation with a spool piece with the 2 solution it is important to make sure that the reference reflector and the spool piece do not have the same length The spool piece needs to be at least 2 in 50 mm longer or shorter For a spool piece with the 3 and 4 in DVC solution this is not a requirement Figure 2 5 Installation with a spool piece NOTE If a spool piece is used with the single lead probe T designed for 2 in chambers it is important that the reference reflector and the spool piece do Not OK not have the same length Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 For high pressure steam applications above 400 psi 28 bar it is also important to limit the overall distance from the flange to where the level is controlled indicated by A in Figure 2 6 since the high pressure affects the dielectric properties of the vapor causing an error in distance measured see Table 2 1 on page 80 The overall error increases with the pressure and is percentage of distance measured Even if DVC is used and corrects the error of 8 6 at 681 psi 47 bar to 2 the 2 error may be larger than desired Figure 2 6 Limiting the overall distance A helps to minimize accuracy
62. errors caused by the vapor Table 2 3 The error in distance with and without DVC at a pressure of 600 psi 41 bar Distance A Error with no correction Error corrected to 2 with DVC 100 in 2540 mm 7 6 in 193 mm 2 in 50 8 mm 50 in 1270 mm 3 8 in 96 5 mm 1 in 25 4 mm NOTE DVC has a minimum distance requirement from the flange to the upper inlet to dynamically compensate up to level 100 See Figure 2 9 on page 18 for details For example if a GWR is installed in a chamber that covers the full height of a 10 ft 3 m tank the distance to the surface level may be as much as 9 ft 2 75 m A 2 error over 9 ft 2 75 m is 2 16 in 54 9 mm If a shorter system is used such as the minimum size needed to replace the 14 in 355 6 mm displacer approximately 35 in 889 mm total then the overall distance to the surface would be about 24 in 609 6 mm With this distance the 2 error shrinks to 0 48 in 12 3 mm For further guidelines for choosing and installing radar in chambers or stilling wells see the Guidelines for Choosing and Installing Radar in Stilling Wells and Bypass Pipes Document No 00840 0300 4024 and Replacing Displacers with Guided Wave Radar Document No 00840 2200 4811 Technical Notes 1 Seethe Using Guided Wave Radar for Level in High Pressure Steam Appli
63. example the threshold has incorrectly been set above the surface peak see Figure 5 7 The problem can be corrected by lowering the threshold see Figure 5 8 Troubleshooting procedures 69 Section 5 Troubleshooting Procedures Reference Manual 00809 0700 4530 Rev AA September 2013 Figure 5 7 Surface peak is below the surface threshold The surface peak is undetected because it is below the surface threshold Rosemount 5301 Surface threshold ATC Amplitude 0 Distance Figure 5 8 Surface peak is above the surface threshold The surface peak is detected because it is above the surface threshold Rosemount 5301 Surface threshold ATC Amplitude 0 Distance 70 Troubleshooting procedures Section 5 Troubleshooting Procedures Reference Manual September 2013 00809 0700 4530 Rev AA Disturbance misinterpreted as level In this example the transmitter incorrectly identifies the reflection from an inlet pipe as the product surface because it is the first peak above the surface threshold see Figure 5 9 Tall narrow and or rough nozzles can also create disturbance echo in the form of double bounces The double bounce will always appear at twice the disturbance distance Ensure that the recom mendations in Section 2 Installation considerations are followed The problem can be solved by increasing the surface threshold see Figure 5 10 or in so
64. f non metallic tanks a Rosemount 5303 should be mounted with a metal plate of minimum 8 in 200 mm diameter Use metal shielding for the conduit connections Figure 2 21 Installation with metal sheet in non metallic vessels In the case of bunkers with a concrete roof a Rosemount 5303 should be installed flush with the inner roof surface or in a nozzle insert Figure 2 22 Installation in concrete silo with metal shielding AA lt D 4in 100 mm Installation considerations 29 Section 2 Installation Considerations Reference Manual September 2013 30 00809 0700 4530 Rev When probes are anchored the forces are two to ten times greater than with free hanging probes To prevent an extremely high tensile load when fixing the probe and to reduce the risk of probe breakage the probe must be slack Select a probe longer than the required measuring range so that there is a sag in the middle of the probe that is greater than or equal to 11 2 per 10 feet 1 cm per m of the probe length Figure 2 23 Fixing probe with slack For applications with a probe length longer than 115 ft 35 m please consult factory a Consider using a non contacting radar for abrasive media that can wear out the probe For solids measurement a Rosemount 5300 Series with Signal Quality Metrics SQM is recommended to help monitor possible build up on probe Use the Measure and Learn
65. fications b Aconditioned power supply and terminating resistors are available for Foundation fieldbus devices c Shielded twisted pair wiring is used d Grounding is completed according to the Hazardous Locations Certifications national and local electrical codes 4 Transmitter is connected as written in the QIG 5 Transmitter is configured as written in the QIG E 82 Checklists Reference Manual Appendix A Checklists 00809 0700 4530 Rev AA September 2013 A 2 2 Measurement validation procedure Step Task Completed 1 The transmitter is in operation 2 Level reading correctness is verified a transmitter level reading is compared with an independent measurement 3 The analog output signal is validated for 4 20 mA HART units only Loopis set to manual mode in the Distributed Control System DCS b Transmitter is in simulation mode accessed RRM c Loop test function is activated d Arbitrary level readings are created at 4 12 and 20 e The arbitrary level readings and the readings in the DCS match 4 Echo curve is verified a Reference pulse amplitude and position are checked b Peak amplitudes are checked c Thresholds are set according to the Reference Manual d Echo curve is stored 5 Transmitter diagnostics is reviewed 6 Level is monitored while emptying the tank a Log functionality for the transmitter level output is a
66. gt 6 3 in 16 cm and gt 9 8 in 25 cm fora rigid single probe with a metallic centering disk and gt 7 1 18 cm and gt 9 4 in 24 cm for a single flexible probe with a standard weight There is a 2 in 5 cm clearance between the cage bottom and the end of the probe included in the C dimensions For the Rosemount 5300 Series with DVC a minimum distance from the flange to the surface level is required to measure the change in the vapor dielectric constant This minimum distance X in Figure 2 9 is 22 in 560 mm for the short reflector and 28 in 710 mm for the long reflector to dynamically compensate up to level 100 The minimum measuring range for this functionality is 12 in 300 mm If a Rosemount 5300 Series transmitter is ordered from Rosemount together with a 9901 Chamber these space requirements are met When the distance between the mounting flange and the surface is less than X see Figure 2 9 the function switches from dynamic to static vapor compensation using the last known vapor dielectric constant NOTE The distance requirements X in Figure 2 9 stated above only apply if dynamic compensation is required within the whole measuring range from lower to upper inlet However always ensure that there are no disturbances from inlets etc close to the reference reflector end Figure 2 9 DVC minimum distance Level 100 Minimum measuring range
67. h results in erroneous reading There will also be dielectric property changes both in the liquid and steam phases Steam under high pressure will slow down the propagation speed of a radar signal which can cause over a 20 error over temperature if not compensated Even though the dielectric of water decreases with temperature increase the level can be measured as long as the water dielectric remains sufficiently high which results in a reflection back from the surface However as the temperature increases the dielectric difference between the liquid and the steam becomes smaller and at a certain point it will be too small for reliable measurement with radar transmitters Between 2610 psi 180 bar and 2900 psi 200 bar the dielectric difference between steam and water becomes too small to offer reliable level measurement In this case GWR is no longer suitable Below 2610 psi 180 is a suitable means of measurement if compensation for the dielectric of the steam dielectric is completed Table 2 1 The error in distance with changing temperature and pressure without vapor compensation Temp F C Pressure psia bar DK of liquid DK ofvapor Error in distance 100 38 1 0 1 73 95 1 001 0 0 200 93 14 1 57 26 1 005 0 2 300 149 72 5 44 26 1 022 1 1 400 204 247 17 34 00 1 069 3 4 500 260 681 47 25 58 1 180 8 6 600 316 1543 106 18 04 1 461 20 9 618 325 1740 120
68. hamber should meet local boiler code requirements and the chamber should be isolated directly from the boiler or high pressure heater by valves A specially designed HTHP probe with reference reflector for vapor compensation should be used For 2 in 50 mm chambers this probe is a single rigid probe and for 3 and 4 in 50 and 100 mm chambers this is a single rigid probe with an outer pipe Probes up to 13 1 ft 4 m length are supported for DVC DVC requires a minimum distance from the flange to the surface level to measure the change in the vapor dielectric constant If the level rises within this area the unit switches over to static compensation using the last known vapor dielectric constant This minimum distance indicated by X in Figure 2 9 on page 18 is 22 in 560 mm forthe short reflector and 28 in 710 mm for the long reflector to dynamically compensate up to 100 The minimum measuring range for this functionality is 12 in 300 mm Table 2 2 Minimum distance X Probe length Reflector Minimum distance X 35 158 in 900 4000 mm 14 in 350 mm 22 in 560 mm 43 158 in 1100 4000 mm 20 in 500 mm 28 in 710 mm If a 5300 Series GWR transmitter is ordered from Rosemount together with a 9901 Chamber these space requirements are met by using the option code G1 or G2 for the chamber G1 is used with the short reflector and G2 is used with the long reflector If an existing chamb
69. he Rosemount 5300 Series have a built in function DVC used along with a special probe that automatically compensates for varying vapor dielectric constants See section below for details RRM gt Setup gt Tank gt Environment gt Advanced Mode gt Vapor Dielectric Constant Calculator Figure 3 3 RRM Vapor Dielectric Constant Calculator Vapor Dielectric Constant Calculator 19 LT 6 x Enter EITHER temperature OR pressure Vapor Gas Saturated Steam Vapor Temperature 2524 C Vapor Pressure 600 psi Calculated Vapor DC 1 158 lt lt Previous Finish Cancel Help NOTE The saturated steam compensation is fixed and will only adjust the level reading at specified conditions This means that the transmitter shows a correct level reading during operation but not during startup and shutdown when these conditions are not fulfilled See Table 3 4 on page 39 Dynamic Vapor Compensation Rosemount 5300 Series While factory calibration of the 3 in 75 mm and 4 in 100 mm DVC probe and transmitter is possible it may be necessary to perform this calibration in the field if new electronics are required or other options such as remote head connection are added at a later date 2 in 50 mm DVC probes must be field calibrated at ambient conditions For the Rosemount 5301 with DVC option it is important that the vapor compensation function is calibrated after installation The calibration mus
70. ic of the media see Table 2 5 on page 17 Also consider type of flushing connection to simplify calibration verification and cleaning Probe type selection depends on the probe length Probe length is less than 3 ft 1 m Use a single rigid probe and no centering disk is needed 1 The single probe creates a virtual coaxial probe with the chamber as the outer tube which helps to amplify the signal returned from the media 2 It is possible to use a chamber with a 2 in 50 mm inner diameter but not recommended as best practice 3 The single probe creates a virtual coaxial probe with the chamber as the outer tube The extra gain provided by the twin and coaxial probes is not necessary the electronics in the Rosemount 5300 Series is very sensitive and is not a limiting factor 4 The transition zones and the height of the weight limit the usage of single flexible probes shorter than 3 ft 1 m Installation considerations 15 Section 2 Installation Considerations Reference Manual September 2013 00809 0700 4530 Rev AA Probe length is between 3 ft 1 and 10 ft 3 m Use either a rigid single or a flexible single probe with weight and a centering disk The rigid single is easier to clean and has smaller transition zones while the flexible single requires less head space during installation and is less likely to be damaged Probe length is more than 10 ft 3 m Use a flexible single probe with weight and a centering disk Mi
71. igher pressure applications which may have more variations in the operating conditions or where the users want to be able to verify the unit under near ambient conditions such as during startup and shutdown without having to modify the vapor dielectric settings Vapor dielectric does not affect the measurement accuracy until the pressure is higher than 145 psia 10 bar DVC should be considered when the pressure is above 247 psia 17 bar when the error is more than 225 see Table 2 3 on page 13 In these cases DVC can bring the error back to 2 or in some conditions even down to 1 Application and installation conditions such as lower temperature in the bypass chamber can cause changes within the measured media Therefore the error readings can vary depending on the application conditions and may cause an increase of the measuring error by a factor of 2 to 3 Installation considerations 9 Section 2 Installation Considerations Reference Manual September 2013 00809 0700 4530 Rev AA DVC requires a special probe with a built in reflector for measurement of the dielectric of the steam DVC works by using a target at a fixed distance With this target the vapor dielectric is measured continuously The transmitter knows where the reflector pulse should have been if there were no vapor present However since there is vapor in the tank the reflector pulse appears beyond the actual reflector point The distance between the actua
72. ioning 00809 0700 4530 Rev AA September 2013 335 3 3 4 Commissioning Rosemount 3300 Series Radar Configuration Tool gt Setup gt Tank Config tab click Receive Page gt Upper Null Zone enter desired value in field and click Send Page Measure and learn function The Rosemount 5300 and 5400 Series have a firmware functionality to automatically adjust threshold settings to make the measurement more robust The Measure and Learn function in RRM automatically creates an Amplitude Threshold Curve ATC used by the Rosemount 5300 and 5400 Series transmitter to find the surface pulse For best practice use the Measure and Learn function in the empty tank RRM gt Echo Curve gt Configuration Mode gt Learn Always review the threshold settings at operating conditions See Echo curve constituents on page 65 and the Rosemount 5300 or 5400 Series Reference Manuals for details Document No 00809 0100 4530 or Document No 00809 0100 4026 Vapor compensation For high pressure steam applications the DC of the vapor increases DC of air is 1 Therefore vapor compensation is required for accurate level measurement The table below provides examples of error in level measurement reading with incorrect static vapor compensation The Rosemount 5300 Series is available with both static and dynamic compensation If the static compensation is used is important that the correct DC value is entered If dynamic compensation is us
73. ious injury Verify that the operating environment of the gauge is consistent with the appropriate hazardous locations certifications Before connecting a HART based communicator in an explosive atmosphere make sure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices Do not remove the gauge cover in explosive atmospheres when the circuit is alive Failure to follow safe installation and servicing guidelines could result in death or serious injury Make sure only qualified personnel perform the installation Use the equipment only as specified in this manual Failure to do so may impair the protection provided by the equipment Do not perform any service other than those contained in this manual unless you are qualified High voltage that may be present on leads could cause electrical shock Avoid contact with leads and terminals Make sure the main power to the transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the gauge Probes covered with plastic and or with plastic discs may generate an ignition capable level of electrostatic charge under certain extreme conditions Therefore when the probe is used in a potentially explosive atmosphere appropriate measures must be taken to prevent electrostatic discharge Process leaks could result in death or serious injury Make sure that the transmitter is hand
74. ith Lower Range Values LRV and Upper Range Values URV representing the bottom and top of the displacer In side to side chambers this corresponds to center of the pipe connections to the vessel For the level measurement to correspond to a designated nominal zero value such that it reads positively and negatively from that point some modifications are required the tank height reference gauge height should be set as the distance from the flange to the nominal level point u the URV is the positive distance from the nominal reference point to the desired upper range limit the LRV is the negative distance from the nominal reference point to the lower range limit the probe length is the actual probe length 43 Section 3 Commissioning Reference Manual September 2013 44 00809 0700 4530 Rev AA Option 1 Matching the output of deviation from the nominal reference point Choose level as primary variable to show on the local display For example if a GWR is replacing 14 in 356 mm displacer the span would be 7 178 mm to 7 in 178 mm Table 3 5 Option 1 example Gauge height distance to nominal reference point 57 in 1448 mm Probe length probe length 87 in 2210 mm URV nominal reference point 7 7 in 178 mm LRV nominal reference point 7 7 in 178 mm Special tank presentation uncheck negative value Figure 3 7 Range values for chambers option 1
75. l reflector point and the apparent reflector point is used to calculate the vapor dielectric The calculated dielectric is then dynamically used to compensate for vapor dielectric changes and eliminates the need to do any compensation in the control system When the distance between the mounting flange and the surface is less than 22 in 560 mm for the short reflector and 28 in 710 mm for the long reflector the function switches from dynamic to static vapor compensation using the last known vapor dielectric constant Figure 2 2 Radar signal curve before and after vapor compensation Signal curve after DVC Signal curve before DVC 1 The figure illustrates the radar signal curve before and after vapor compensation Without compensation the surface pulse 10 appears to be beyond the actual level After compensation the surface appears at the correct surface level point Installation considerations Reference Manual 00809 0700 4530 Rev AA Section 2 Installation Considerations Rosemount design advantages September 2013 Rosemount 5300 GWR extreme temperature and pressure probes are designed to prevent leakage and perform reliably when exposed to extreme process conditions for extended periods of time Materials are selected to avoid stress fractures commonly induced by changes in temperature and pressure conditions The robustness of the probes and materials means high safety for these extreme
76. ld have a flat or raised face but other tank flanges may be possible Consult your local Emerson Process Management representative for assistance Figure 2 18 Rosemount 5402 with process seal antenna K Bad welding Rosemount 5401 with cone antenna This antenna can be used in tanks with nozzles equal to or larger than 4 in 100 mm and should extend 0 4 in 10 mm or more below the nozzle L If required use the extended cone solution The Rosemount 5401 is low frequency 6 GHz the Rosemount 5402 is high frequency 26 GHZ which generates a wider beam width and thus it should not be recessed up in the nozzle as this will disrupt the radar beam Installation considerations Reference Manual Section 2 Installation Considerations 00809 0700 4530 Rev AA September 2013 Figure 2 19 Rosemount 5401 with cone antenna L 0 4 in 10 mm or more If the signal is dampened by heavy condensation at the antenna it often helps to insulate the nozzle This is to minimize the temperature disparity between the internal and the ambient temperature 243 Probe and antenna selection In addition to the mounting position nozzle considerations and process insulation there are other factors that need to be taken into consideration when selecting the probe or antenna Probe selection u Single probes are recommended in most applications The coaxial probe
77. lds in the bend to impede the flow The inlet pipes are sealed by closing the valves and filling the chamber with water using the upper vent hole water can also be introduced through the bottom drain connection The level is varied between the 4 20 mA set points to verify that the basic transmitter settings have been configured correctly Once the chamber is mounted on the actual tank and the process is started a complete verification is carried out see Measurement validation on page 51 Figure 3 12 Verification of transmitter measurement in bridle application using tubing Closed Valves Measure Commissioning Reference Manual Section 4 Measurement validation 00809 0700 4530 Rev AA September 2013 Section 4 Measurement validation Safety messages 51 Introduction 52 Measurement validation at operating lt 52 Operation and maintenance proof testing for SIS 58 4 1 Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Refer to the following safety messages before performing an operation preceded by this symbol Failure to follow these installation guidelines could result in death or serious injury Make s
78. led carefully If the process seal is damaged gas might escape from the tank if the transmitter head is removed from the probe Troubleshooting procedures 61 Section 5 Troubleshooting Procedures Reference Manual September 2013 5 2 62 00809 0700 4530 Any substitution of non authorized parts repair other than exchanging the complete transmitter head or probe assembly may jeopardize safety and is prohibited Unauthorized changes to the product are strictly prohibited as they may unintentionally and unpredictably alter performance and jeopardize safety Unauthorized changes that interfere with the integrity of the welds or flanges such as making additional perforations compromise product integrity and safety Equipment ratings and certifications are no longer valid on any products that have been damaged or modified without the prior written permission of Emerson Process Management Any continued use of product that has been damaged or modified without prior written authorization is at the customer s sole risk and expense Introduction This section provides information on identifying the most common problems found with radar level transmitters A typical workflow may look like this local restrictions and variations may apply 1 Check voltage at transmitter terminals Verify that the input voltage requirement is fulfilled and wiring is correct 2 View Distributed Control System DCS trends and questio
79. led1 000 Analog Out Measurement Interface Distance status 0591 Internal Temperature Upper Product Thickness Volume 236 C 0437 m status Total Volume Upper Product Volume 0 000 m3 0000 m3 Lower Product Volume Device 0000 m3 status Level Rate Interface Level Rate 0 002 0 001 m h Interface Signal Strength 5837 mV Interface Level 0 409 m RRM gt Tools gt Device Display RRM gt Tools gt Diagnostics Troubleshooting procedures 63 Section 5 Troubleshooting Procedures Reference Manual September 2013 5 4 64 00809 0700 4530 Rev AA Echo curve analysis The echo curve represents the tank as seen by the radar transmitter Each peak corresponds to a reflection of the radar signal the surface of the level an obstacle or something else By viewing single instances or movies of the echo curve how and why the transmitter behaves as it does can be understood and it can be configured accordingly to achieve a reliable level measurement Usually an echo curve analysis is not needed the transmitter automatically sets the appropriate parameters based on the start up information such as tank height and tank media etc However it is a very valuable tool for troubleshooting difficult applications Troubleshooting procedures Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013 5 4 1 Echo curve constituents Figure 5 2 Echo
80. limited head space for installing rigid probes non contacting radar may be advantageous Non contacting radar is also the preferred technology for applications with heavy deposition or very sticky and viscous fluids Figure 2 1 Possible error sources in chamber installations Error Error Sy ES Error Error 300 F 150 150 F 65 C SG 0 80 SG 0 85 I Inlet pipe clogged For application guidelines see Section 1 Power applications 231 High pressure steam applications Phase changes It is especially common during startup to experience varying temperature and pressure Both the liquid and steam phases of the system will have density changes as the system reaches the operating temperature and pressure which can cause up to a 30 error over temperature up to 600 F 315 C as seen in Table 2 1 Installation considerations 7 Section 2 Installation Considerations Reference Manual September 2013 00809 0700 4530 Rev AA Any density based level measurement device will need compensation to discern the actual level from the density associated errors Algorithms have been developed to make this compensation as seamless as possible in the control systems but require input of operating pressure as well as level Compensation can be slow whic
81. llation Considerations 00809 0700 4530 Rev AA September 2013 Step 4 inclination of antenna wm Ifthe surface echo is weak the parabolic antenna can be inclined 0 5 to 2 towards the surface slope in order to increase the reflected signal NOTE Too great of an angle can create problems in detecting surface echo at the bottom region The angle of the slope differs during filling and emptying Therefore monitor the entire cycle in order to verify and determine an optimum antenna inclination Table 2 10 Sample solid applications where non contacting radar is preferred over GWR Common Characteristics Particle Size Vapor Space PTFE Bag Dust or Small Larger Steam or Recommended Applications Powder lt 1 gt 1in Dust Condensation 2 Wood chip bins Yes Yes Yes Yes Possible Yes Grain silo small kernel Yes Yes No Yes No Yes grains Grain silo large kernel No Yes No No No No grains Lime stone silo No Yes Yes Possible No No Cement raw mill silo Yes Yes No Yes No Yes Cement finished product Yes Yes No Yes No Yes silo Coal Yes Yes Yes Yes Yes No Saw dust Yes Yes No Yes No Yes High consistency pulp stock No No No No Yes No Alumina Yes Yes No Yes No Yes Salt No Yes Yes No No No 1 These applications except salt typically involve tall vessels and therefore require the parabolic antenna option The 8 in cone antenna option can be u
82. log output settings Review the analog output settings The primary variable determines the output and is often set to level The definition is Level tank height reference gauge height measured distance Consequently the zero level point is at tank height reference gauge height below the transmitter s flange The LRV 4 mA setpoint and URV 20 mA setpoint should be set with this zero point as reference Probe length and tank height reference gauge height do not need to match Troubleshooting procedures Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013 Figure 5 20 Analog output settings range values and reference points Upper Reference Point 20 mA Upper Range Value URV 100 gt i Range 0 100 Tank Height Reference Gauge Height 4 mA Lower Range Value LRV 0 Lower Reference Point Level 0 The analog output depends on how the range values are set see Figure 5 21 for examples Figure 5 21 Analog output settings e Real level at 60 Troubleshooting procedures 77 Section 5 Troubleshooting Procedures September 2013 9 9 9 78 Incorrect static vapor compensation Reference Manual 00809 0700 4530 Rev AA Specific high temperature and high pressure applications like those with saturated steam vapors require that a compensated
83. lse Reference peak Probe end pulse Figure 5 5 A stainless steel centering disk gives a positive probe end pulse Reference peak Probe end pulse Troubleshooting procedures 67 Section 5 Troubleshooting Procedures Reference Manual September 2013 68 00809 0700 4530 Rev AA Rosemount 5400 and 5600 Series Various amplitude thresholds are used to filter out unwanted signals and pick up the different peaks The transmitter uses certain criteria to select which peaks correspond to the actual level surface For GWR transmitters counting from the top of the tank the first echo above the surface threshold is considered the product surface Pulses further away from the top although above the surface threshold are ignored Non contacting radar transmitters use other certain criteria to decide which type of pulse that is detected Echoes found above the surface threshold might be considered the product surface Surface threshold This is the amplitude threshold for detection of the product level peak The surface threshold is designed as anumber of individually adjustable amplitude threshold points the ATC Upper Null Zone Hold Off distance Measurements are not performed within the UNZ Hold Off distance consequently the UNZ Hold Off can be used to avoid measurements above a certain level for example because of disturbances in the nozzle For GWR TNZ is the prefe
84. me cases where the disturbance is close to the transmitter flange by increasing the UNZ or performing the Near Zone Trim command Figure 5 9 The surface is the reflection from the inlet pipe The reflection from the inlet pipe is selected as the surface because it is the first peak above the surface threshold Actual Rosemount 5301 level Surface threshold ATC Amplitude 0 Distance Figure 5 10 Surface peak identified correctly The peak from the actual level is now correctly identified it is the first peak above the surface Rosemount 5301 threshold Surface threshold ATC Amplitude 9 Distance Troubleshooting procedures 71 Section 5 Troubleshooting Procedures Reference Manual September 2013 72 00809 0700 4530 Rev AA Incorrect reading due to bent probe or probe contacting the nozzle wall A bent twisted probe in the case of flexible probes in contact with metal creates a strong echo that the measurement will lock onto see Figure 5 11 If this is the case the mechanical installation will need to be redone ensuring that the recommendations in Section 2 Installation considerations are followed The probe length should match the tank chamber length or be slightly shorter The problem can often be resolved by adding a centering disk at the bottom of the probe but it may also require a replacement of the complete probe assembly Fig
85. ment only as specified in this manual Failure to do so may impair the protection provided by the equipment Do not perform any service other than those contained in this manual unless you are qualified High voltage that may be present on leads could cause electrical shock Avoid contact with leads and terminals Make sure the main power to the transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the gauge Probes covered with plastic and or with plastic discs may generate an ignition capable level of electrostatic charge under certain extreme conditions Therefore when the probe is used in a potentially explosive atmosphere appropriate measures must be taken to prevent electrostatic discharge 81 Appendix A Checklists Reference Manual September 2013 00809 0700 4530 Rev AA A 2 Checklists A 2 1 Commissioning procedure Step Task Completed 1 System readiness is confirmed Rosemount 5300 and 5400 Series only a HART revision capability is checked b The latest Device Driver is downloaded c HARTrevision mode is switched if the HART configuration tool is not capable of communicating with the HART Revision 7 protocol 2 The transmitter head and probe antenna are mounted as written in the respective Quick Installation Guide QIG 3 Wiring is connected as written in the QIG a Wiring and power supply requirements are according to the approval certi
86. n the relevant people to understand when the problem occurs and the effect of the problem Could it be related to any other activities 3 Do a tank survey to identify the application Ensure that the transmitter has been selected according to Section 1 Power applications and Chamber installations on page 6 4 Check for basic errors such as cables and transmitter diagnostics then complete relevant parts of Commissioning on page 35 again 5 If necessary execute the verification procedure described in Section 4 Measurement validation or other procedure that recreates the problem 6 A If the measurement is reliable but there is an offset or the accuracy is poor refer to Echo curve analysis on page 64 B Do an echo curve analysis as described in Echo curve analysis on page 64 to try to identify the problem When the problem has been resolved the validation procedure described in Section 4 Measurement validation should be completed or any other procedure that verifies the integrity of the transmitter If the problem cannot be resolved contact your local Rosemount representative for assistance with a description of the problem and application also be able to submit the echo curve dat and the transmitter backup file bak taken at present conditions and during commissioning Troubleshooting procedures Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013
87. nd it expands and contracts with increased and decreased temperatures With certain fluids the effect on level is noticeable in hot applications with large differences in temperature between the chamber and the tank Insulating the chamber minimizes the temperature changes This is especially important for applications with saturated steam since the radar measurement is dependent on the dielectric properties of the steam See Incorrect static vapor compensation on page 78 for details Figure 5 16 Temperature drop in the chamber without insulation Error 300 F 150 C 150 F 65 C SG 0 80 SG 0 85 CE 74 Troubleshooting procedures Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013 5 5 2 Rosemount 5600 Series solids measurement In a nozzle installation review the installation considerations For solids measurement with weak surface echo mechanical installation is especially important since nozzle disturbances will disrupt the surface measurement For best practice ensure that the antenna reaches into the tank at least 2 in 50 mm If necessary review threshold settings and adjust hold off UNZ Figure 5 17 Mechanical installation What difference does it make att me Amplitude 29 5500 5000 25 4500 200 4000 1750 1500 300 1250 2500 1000 2000 m 1500 En 1000 500
88. ng the distance using the built in simulation mode by performing loop test The following proof test is recommended If an error is found in the safety functionality the measuring system must be switched out of service and the process held in a safe state by means of other measures Proof test results and corrective actions taken must be documented at www emersonprocess com rosemount safety Proof test This test detects approximately 95 of the possible Dangerous Undetected DU failures of the transmitter including the sensor element not detected by the transmitter s automatic diagnostics Instructions for performing the proof test with the Field Communicator RRM or AMS are available in the Appendix E Performing Proof Test of the Rosemount 5300 Series Reference Manual Document No 00809 0100 4530 Note that prior to this test the echo curve should be inspected to ensure that no disturbing echoes affecting the measurement performance are present in the tank Required Tools HART host communicator and mA meter 1 Bypass the logic solver or take other appropriate actions to avoid false trip 2 Disable write protection if the function is enabled 3 Using Loop Test enter the mA value representing a high alarm current output and verify that the analog current reaches that value using the reference meter This step tests for compliance voltage problems such as low loop power supply voltage or increased wiring resistance 4
89. nimum chamber diameter is 3 in 75 mm For very narrow chambers with a diameter less than 2 in 50 mm a coaxial probe can be used to help reduce the impact of possible disturbances such as splashing from upper inlet pipes However since the coaxial probe is more sensitive to build up it is only recommended for very clean liquids For a chamber with a diameter equal to or larger than 3 in 75 mm the single lead probe is therefore the preferred choice NOTE For the coaxial probe the minimum chamber diameter is 1 5 in 837 5 mm Figure 2 7 Improper and proper probe positions Make sure that the probe does not come into contact with the chamber wall e g by using a centering disk A clearance distance of 1 in 25 mm between the probe end and the cage bottom is recommended To avoid bending the probe rigid probes ortwisting flexible probes and coming into contact with the chamber wall a small clearance distance between the centering disk and the chamber bottom is recommended A clearance distance of 1 in 25 mm is suggested assuming a dome shaped chamber bottom which may prevent the centering disk from reaching the bottom Transition zones located at the very top and bottom of the probes are regions where measurement performance is reduced Different factors affect the size of the transition zones probe type centering disk or no centering disk and the material and me
90. ns Bench tests complement verification tests but do not replace them The instructions in Measurement validation on page 51 should be followed and the bench test is considered optional One of the largest differences between the simulated level and the actual level during operating conditions is the amplitude of the surface peak For example in a4 in 100 mm chamber using the Rosemount 5300 Series transmitter and a single probe the peak of water can be 10000 mV while oil would 2000 mV under the same conditions NOTE Never set the thresholds according to simulated level values since there is a major risk that the thresholds may be set too high Generally it is advised to accept the automatic settings If it is necessary to adjust the thresholds do the adjustments the first time the process is started at actual operating conditions Normally the thresholds do not require any adjustments on the custom settings 49 Section 3 Commissioning Reference Manual September 2013 50 00809 0700 4530 Rev AA Figure 3 11 The difference between the amplitude of surface peaks in the case of simulated and actual liquid levels Water How it would look with actual product oil in tank Amplitude eo 0 Distance Example A Rosemount 5300 Series transmitter mounted in a chamber can be verified by connecting flexible transparent tubing to the bottom drain ensuring that there are no crimps or fo
91. nstallations and solids measurements Chamber installations Chambers also known as bridles side pipes bypass pipes and cages are typically used because a External mounting with valves allows for servicing of the level device even in pressurized tanks that are in continuous operation for many years u They allow for radar measurement in tanks or regions with side connections only such as boiler drum condenser and feedwater tanks a They provide a calmer surface in case of turbulence boiling or other conditions that upset the product NOTE For chamber installations use metallic pipes exclusively However chambers also have some disadvantages Inlet pipes may clog generate discrepancy between the level inside the chamber and the actual level in the tank The effective measuring range is limited to the region between the upper and lower inlet pipes Different process conditions temperature pressure in the chamber than in the tank may generate discrepancy between the level inside the chamber and the actual level in the tank A pipe can increase the reliability and robustness of the level measurement especially for non contacting radar It should be noted that the coaxial probe of a Guided Wave Radar GWR is essentially a probe within a small stilling well It should be considered as an alternative to stilling wells for clean fluid applications Pipes completely isolate the transmitter from disturb
92. ocedure are independent and although it is not recommended single steps may be omitted Before you start the verification procedure ensure that proper actions have been taken not to affect the safety or performance of the process A checklist for the measurement validation process is provided on page 83 Step 1 verify the correctness of level reading At normal operating conditions compare the transmitter level reading with an independent measurement Unfortunately it often happens that two independent measurements will not match up perfectly but check the sanity and the acceptable deviation See Reconciling radar with other level measurements on page 79 for more information The independent measurement can be done using a number of different complementary devices ranging from sight glasses and hand dipping to redundant differential pressure and displacer See Sources of measurement error on page 73 if deviation is unacceptable Measurement validation Reference Manual Section 4 Measurement validation 00809 0700 4530 Rev AA September 2013 Figure 4 1 The verification of measurement data using a sight glass Step 2 analog output signal validation Note that this section refers to 4 20 mA HART units only Ensure that the loop has been set to manual mode in the Distributed Control System DCS for the applicable transmitter Use the transmitter s built in simulation mode to verify the analog output settings Outp
93. or chambers option 2 Probe length 23 in 584 mm Displacer length 14 in 356 URV 14 in 356 mm Tank Height reference gauge height 19 in 483 mm V LRV Oin 0 mm 45 Section 3 Commissioning Reference Manual September 2013 46 00809 0700 4530 Rev AA Option 3 Matching displacer output The tank height reference gauge height and the probe length should be set to the same value The LRV is the distance from the bottom of the probe to the lower tap The URV is the LRV plus the distance to the upper tap In this example tank height reference gauge height equals the probe length of 23 in 584 mm the LRV is 4 in 102 mm and the URV is 18 in 457 mm Table 3 7 Option 3 example Gauge height same as probe length 23 in 584 mm Probe length probe length 23 in 584 mm URV LRV distance between connections 18 in 457 mm LRV end of probe to center of lower connection Ain 102 mm Figure 3 9 Range values for chambers option 3 URV 18 in 457 T lt E Ay 7 DE I 5 ge m e 3E N 9 m ind Sot a SY Uo a o ciu E rv v E xd 2 am 2 Fan a LRV 4in 102 mm Commissioning Reference Manual Section 3 Commissioning 00809 0700 4530 Rev AA September 2013 3 3 7 3 948 Commissioning Signal Quality Metrics Rosemount 5300 and
94. parity between the internal and the ambient temperature Figure 5 13 Strong antenna echo and weak surface echo Sources of measurement error This section applies to radar level transmitters that track the surface but have poor accuracy or a fixed offset There are many possible error sources for this such as incorrect settings or incorrect interpretation of the analog output signal These errors almost exclusively depend on the external environment since radar is extremely accurate and does not drift Installation and location errors Review the installation to determine what the transmitter is measuring and what the expected output is In a chamber installation check that the level corresponds to the value inside the tank Ensure that the chamber has been installed where the level range can be adequately covered Troubleshooting procedures 73 Section 5 Troubleshooting Procedures Reference Manual September 2013 00809 0700 4530 Rev AA Figure 5 14 Installation error level interface range is not covered adequately SS The connections between the vessel and the chamber must allow for flow of the product Clogging should be avoided Figure 5 15 Inlet pipe clogged Inlet pipe clogged The radar transmitter is not temperature dependent However the fluid is a
95. pproved for use in hazardous area For more information on measuring solids refer to the Guided Wave Radar in Solid Level Applications Document No 00840 2300 4811 and Measuring Solids with a Rosemount 5600 Series Non Contacting Radar Document No 00840 0100 4024 Technical Notes Installation considerations Reference Manual Section 3 Commissioning 00809 0700 4530 Rev AA September 2013 Section 3 Commissioning Safety messages t rhet he her ees riaden tns 35 Introduction e 36 Functions of procedures to include during commissioning process 36 3 1 Safety messages Commissioning Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Please refer to the following safety messages before performing an operation preceded by this symbol Explosions could result in death or serious injury Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations certifications Before connecting a HART based communicator in an explosive atmosphere make sure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices Do not remove the gauge cover in explosive atmospheres when the circuit is alive
96. rom the device will not be controlled by the device measurement Make sure systems and people Status Live values No fixed current relying on data from the device are made aware of the changed conditions when entering exiting fixed current mode Failure to do so could result in death serious injury and or property damage Close Step 3 echo curve verification at operating conditions At normal operating conditions download and review the echo curve according to the following steps 1 Check reference pulse amplitude and position Compare the result against the previous plots taken during commissioning and previous verification rounds Note that deviation of pulse amplitude and position may occur between plots taken at ambient conditions and operating conditions For a Rosemount 5301 with DVC also verify that the reference reflector echo is visible NOTE The non contacting radar has a positive reference pulse 2 Review peak amplitudes and threshold settings Verify that the surface peak is visible and that the thresholds have been set according to the best practices in Section 5 Troubleshooting procedures If possible compare the current echo curve with previously stored echo curves taken during operating conditions There should be no major differences 3 Store the echo curve Permanently store the echo curve for future use with re occurring verification procedures 54 Measurement validation
97. rred choice for handling disturbances in the near zone since measurement is still possible in near zone see Trim Near Zone GWR transmitters on page 37 for activation False echo area Rosemount 5400 Series only False echo areas are set during the Measure and Learn function when the disturbing object is larger than the surface echo see Figure 5 6 Thefalse echo area can be adjusted manually See the Rosemount 5400 Series Reference Manual Document No 00809 0100 4026 for details Figure 5 6 Rosemount 5400 and 5600 Series echo curve presenting all visible echoes 2000 1800 1600 1400 1200 1000 Refere peak False echo Product surface nce Tank Hold Off bottom distance Unknown Surface threshold ATC Troubleshooting procedures Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013 5 4 2 5 4 3 5 4 4 Rosemount GWR transmitter threshold settings Recommendations for the Rosemount 3300 and 5300 Series 1 Use the automatic threshold settings and ensure that the dielectric constants of the vapor and products have been entered correctly 2 If needed apply the Measure amp Learn function 3 If needed use the following best practices to apply custom threshold adjustments a Generally the threshold should be at 40 50 of the surface peak Example If the surface is 2000 mV the threshold shoul
98. s Reference Manual September 2013 00809 0700 4530 Rev AA iv Table of Contents Reference Manual Section 1 Power Applications 00809 0700 4530 Rev AA September 2013 Section 1 Power applications Introduction ee ce sass eens 1 Boiler systems E ER RICE ANE 2 a e ELI 2 Water supply and pre treatment 2 Cooling system nur rh hr rho prre EIE E 2 Fuel DE 3 Fuel combustion clean up eee cece cece cece cee cece eee nnn 3 Ellluent POSUER IP REM PR METER INI CU nEGSS 3 Hydro poWer eorr et hh hr h rrr ETUR EE ears 3 Miscellaneous eer hp ra a err err 4 1 1 Introduction This document describes some of the best practices learned during the installation of thousands of Rosemount process radar level transmitters in power applications In a power plant the radar applications can be divided into the following subcategories Boiler systems a Turbines a Water supply and pre treatment Cooling system Fuel supply Fuel combustion clean up Effluent Hydro power Miscellaneous Each application differs in how the transmitters are to be installed to achieve optimized result It is important to follow the best practice for the specific application If unsure about the install
99. s have longer measuring ranges than the single probes but are more sensitive to build up and coating Always ensure that the wetted materials are compatible with the process and that the probe will withstand the application s temperature and pressure range In case of corrosive tank media consider using a probe in exotic materials Alloy C 275 or 400 with protective plate design or alternatively PTFE coated probes PTFE coated probes can also be used for applications with build up or condensation Build up on probes be monitored by the Signal Quality Metrics Rosemount 5300 Series Refer to the Rosemount 5300 Series Product Data Sheet Document No 00813 0100 4530 for details Antenna selection a Cone antennas are recommended in most applications Always use the largest possible antenna Always ensure that the wetted materials are compatible with the process and that the antenna will withstand the application s temperature and pressure range a In case of corrosive tank media consider using an antenna in exotic materials Alloy C 275 or 400 with protective plate design or alternatively a process seal antenna Process seal antennas can also be used for applications with build up or condensation u In case of turbulent surface conditions or foam consider using a stilling well For stilling well installation refer to the Guidelines for Choosing and Installing Radar in Stilling Wells and Bypass Pipes
100. sed in the salt application where the vessel height is less than 50 ft 15 m 2 The PTFE bag is only available for the parabolic antenna If a cone antenna is used consider the flushing connection option 3 For interstice silos the antenna can be inclined 0 5 in to 2 in towards the surface slope 4 For interstice silos the radar must be installed so that the radar signal clearly passes internal support structures without interferences 5 Clean the antenna regularly Installation considerations 33 Section 2 Installation Considerations Reference Manual September 2013 34 00809 0700 4530 Rev AA Step 5 software settings Note that solids applications in general are difficult therefore Emerson Process Management has developed a special solids mode in the radar database This means that the radar database configuration is optimized for solids measurements when the solids check box is selected in the Rosemount Radar Master RRM setup window Additional adjustments of the database might in some cases become necessary In such cases contact the factory for further details on how to proceed Some solids build up electrostatic discharges which might result in explosion risks Therefore the Rosemount 5600 Series has been approved for use in such environments See the Rosemount 5600 Series Radar Transmitter Product Data Sheet 00813 0100 4024 for detailed information about approvals Also note that the PTFE bag is NOT a
101. semount 5400 and 5600 Series a Measure amp Learn function is applied b Custom threshold adjustments are applied 9 Echo curve is checked for common problems a Threshold is below the surface peak b Disturbance is misinterpreted as level c Incorrect reading due to bent probe d Incorrect reading due to probe contacting the nozzle wall e Possible build up on probe f Strong antenna echo 9 Weak antenna echo 10 Sources of measurement errors are checked a Installation and location errors b Tank geometry c Probe End Pulse offset only for Probe End Projection d Analog output settings e Incorrect static vapor compensation f Reconciling radar with other level measurements g Chamber measurement 11 Measurement validation procedure is completed to verify the transmitter s integrity L 84 Checklists Reference Manual Index 00809 0700 4530 Rev AA September 2013 Index A Measurement error 73 Amplitude Threshold Curve ATC 39 Analog output settings 76 Analog output settings 76 Geometries esses nn 75 Antenna selection 27 31 Incorrect static vapor compensation 78 Installation and location 73 Probe end pulse 5 76 Reconciling radar with other measurements 79 Chamber 73 Fabrication
102. sentative for details 3 When using single flexible probes in tall nozzles it is recommended to use the Long Stud LS Installation considerations 25 Section 2 Installation Considerations Reference Manual September 2013 26 00809 0700 4530 Rev AA Rosemount 5400 Series non contacting radar transmitter Rosemount 5402 with cone antenna The antenna can be used in nozzles equal to or larger than 2 2 in 55 mm It can be recessed in smooth nozzles up to 6 ft 2 m However if the inside of the nozzle contains disturbing objects use the extended cone see Figure 2 17 Make sure the antenna is never the same height as the nozzle Because Rosemount 5402 has a high frequency 26 GHz this generates a narrower beam width which can allow for the antenna to recess up in the nozzle Although for best performance it is recommended that the antenna extend 0 4 in 10 mm or more below the nozzle Refer to the Rosemount 5400 Series Reference Manual Document No 00809 0100 4026 for details Figure 2 17 Rosemount 5402 with cone antenna Bad welding Bad welding Rosemount 5402 with process seal antenna The antenna can be used in 2 3 and 4 in 50 75 and 100 mm nozzles up to 6 ft 2 m tall J but disturbing objects inside the nozzle K may impact the measurement and should be avoided For best performance the recommended maximum nozzle height is 19 7 in 500 mm The flange on the tank shou
103. t be performed with an empty chamber at ambient conditions The Rosemount 5300 Series with DVC uses a reference reflector mounted on the probe at a certain distance to estimate the dielectric constant of the vapor The transmitter knows where the reference reflector pulse should have been if there were no vapor present However since there is vapor in the tank the reference reflector pulse will appear beyond the actual reflector point The distance between the actual reflector point and the apparent reflector point will be used to calculate the vapor dielectric constant The calculated dielectric constant is then Commissioning Reference Manual Section 3 Commissioning 00809 0700 4530 Rev AA September 2013 dynamically used to compensate for changes in vapor dielectric constant and eliminates the need to do any compensation in the control system To check if the DVC function is supported RRM gt Device gt Properties If Vapor Compensation is mentioned in the Device Software Configuration 2 list the device supports vapor compensation Figure 3 4 Check if DVC is supported amp Device Properties Device Model lt lt Basic 5302 Device Hardware Configuration Serial No HART 16777215 LED Primary Analog Output PV Probe Type Device Software Configuration 2 Rigid Single HTHP Meas Mode Interface Level with submerged probe evel and Interface Level Probe Length 0400 m m Vapor Boot SW Version Application SW Version
104. temperature and pressure applications Figure 2 3 Probe with reference reflector marked VC2 for recognition The GWR probe design provides multiple layers of protection Figure 2 4 HTHP seal Brazed hermetic gas tight ceramic seal is isolated from the process and is unaffected by temperature shocks vibrations and outside forces on the probe Flexible probe load and locking system with active springs and PTFE frame compensates for stress and protects the ceramics Drip off sleeve for condensation and dirt protection Spacer one used near the top of the probe and one further down if the probe is longer than 79 in 2 m Ceramic insulators and graphite gaskets provide a robust thermal and mechanical barrier and offer chemical resistance lt q Reference reflector The solution for 3 and 4 inch chambers has an outer pipe around the rod Reference reflector Illustration of the solution for 2 inch chambers Installation considerations 11 Section 2 Installation Considerations Reference Manual September 2013 00809 0700 4530 Rev AA DVC installation best practices The GWR should be mounted in a bypass chamber with flanges appropriately sized for the pressure and temperature of the application A 3 or 4 inch 75 or 100 mm diameter chamber is recommended as best practice but the GWR can also be mounted in a 2 inch 50 mm chamber Materials used for the c
105. the device is to be used in an open air application then a site license may be required For radiating products the Rosemount products are compliant with R amp TTE Directive 1999 5 EC FCC license numbers for the Rosemount 5400 and 5600 Series Rosemount 5401 K8C5401 a Rosemount 5402 K8C5402 must be mounted in a tank a Rosemount 5600 Series for applications in sealed metal tanks K8CPRO FCC rule part 15C K8CPROX FCC rule part 90 The license numbers are included on the device labels In Canada the following license numbers are valid for closed metal tanks Rosemount 5401 2827A 5401 Rosemount 5402 2827A 5402 Rosemount 5600 Series 2827A 5600PRO No certificate is applicable for Non intentional radiators The EC Declaration of Conformity for all applicable European directives for the Rosemount products can be found on the Rosemount website at www rosemount com A hard copy may be obtained by contacting our local sales representative iii Reference Manual September 2013 00809 0700 4530 Rev AA Reference Manual Table of Contents 00809 0700 4530 Rev AA September 2013 Contents Section 1 Power applications Tals 1 12 w BolersvstelliSuses entub e pP 2 THEDINeS deur dd eR Re xd eae EN x bd ds 2 1 4 Water supply and pre treatment 2 8 2 WS GOoliiGSYSteM escscse re RIGG M ERES 2
106. ure 5 11 Measurement data using a bent probe Possible build up on probe If it is anormal but strong echo noise from process or tank environment i e inlets nozzle etc perform the Trim Near Zone function If necessary adjust the surface threshold manually or by Measure amp Learn and also consider using a coaxial probe If the echo is due to contamination the probe should be cleaned If SQM is used the values of measurement margin and signal quality can be used to monitor build up If SQM is not available the secondary variable can be set to signal strength to foresee the need of cleaning The threshold can also be raised if the surface peak is strong enough Finally consider insulating the chamber to minimize risk of build up Figure 5 12 Build up on probe 2000 1800 1600 1400 1200 1000 800 600 P2 Unknown 400 200 P1 Surface Troubleshooting procedures Reference Manual Section 5 Troubleshooting Procedures 00809 0700 4530 Rev AA September 2013 3 9 3 5 Strong antenna echo and weak surface echo Water condensation in a cone antenna or build up on a process seal window will create a strong echo from the antenna and a weak surface echo Examine installation and adjust Hold Off and surface threshold if the surface echo is still strong enough Insulating the nozzle generally reduces the condensation or build up This is because it minimizes the temperature dis
107. ure only qualified personnel perform the installation Use the equipment only as specified in this manual Failure to do so may impair the protection provided by the equipment Explosions could result in death or serious injury Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations certifications Before connecting a HART based communicator in an explosive atmosphere make sure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices Electrical shock could cause death or serious injury Use extreme caution when making contact with the leads and terminals High voltage that may be present on leads could cause electrical shock Probes covered with plastic and or with plastic discs may generate an ignition capable level of electrostatic charge under certain extreme conditions Therefore when the probe is used in a potentially explosive atmosphere appropriate measures must be taken to prevent electrostatic discharge Measurement validation 51 Section 4 Measurement validation Reference Manual September 2013 4 2 4 3 52 00809 0700 4530 Rev AA Any substitution of non authorized parts or repair other than exchanging the complete transmitter head or probe assembly may jeopardize safety and is prohibited Unauthorized changes to the product are strictly prohibited as they may unintentionally and unpredicta
108. ut at least one arbitrary level and verify that the reading in the DCS match To access the simulation mode in Rosemount Radar Master RRM RRM gt Tools gt Simulation Mode Figure 4 2 Simulation Mode Simulation Mode LT 01 Simulation Values Device Communication Hazard Distance simulated Start 0 700 m During simulation the output from 2 Stop the device will not be controlled by Enable Measurement Alarm simulated L3 the device measurement Make sure systems and people Enable Device Failure Alarm simulated telying on data from the device are made aware of the changed Status Live Values No Simulation conditions when entering exiting simulation mode View live simulated values Failure to do so could result in death serious injury and or property damage Press button to open Device Display Close Help Also or alternatively activate the transmitter s loop test function Output 4 12 and 20 mA and verify that the readings in the DCS match up In RRM RRM gt Output gt Analog Out gt Loop Test Measurement validation 53 Section 4 Measurement validation Reference Manual September 2013 00809 0700 4530 Rev AA Figure 4 3 Loop test for Analog Out 1 Loop Test for Analog Out 1 LT 01 Set fixed analog out current Device Communication Hazard Current 1 Start During fixed current mode the output f
109. value be entered for the vapor dielectric constant This compensation is fixed and will only adjust the level reading at a specific condition Normally this means that the transmitter will show a correct level reading during operation but not during startup and shutdown Alternatively if no correction is entered the level reading will be correct during shutdown but not during startup and operation see Table 5 3 and Table 5 4 Table 5 3 Properties of water and saturated steam Temp Pressure DK of DK of Errorin F C psia bar liquid vapor distance 100 38 1 0 1 73 95 1 001 0 0 200 93 14 1 57 26 1 005 0 2 300 149 72 5 44 26 1 022 1 1 400 204 247 17 34 00 1 069 3 4 500 260 681 47 25 58 1 180 8 6 600 316 1543 106 18 04 1 461 20 9 618 325 1740 120 16 7 1 55 24 5 649 343 2176 150 14 34 1 8 34 2 676 358 2611 180 11 86 2 19 48 691 366 2900 200 9 92 2 67 63 4 699 370 3046 210 8 9 3 12 76 6 702 372 3118 215 Above critical point distinct liquid and gas phases do not exist Table 5 4 Level reading errors during shutdown with fixed saturated water steam correction activated Entered Error in reading when actual Vapor DC is 1 Offset reading Vapor DC corresponding to water at room if Vapor DC is temperature configured correctly Surface at 15 in 380 Surface at 30 in 760 mm from flange mm from flange 1 001 0 in 0 mm Oin 0 mm Oin 0 mm
110. wing applications Cooling tower basin Refrigerants Power applications Reference Manual Section 1 Power Applications 00809 0700 4530 Rev AA September 2013 1 6 1 7 1 8 1 9 Power applications Fuel supply For fuel supply radar transmitters are commonly used for the following applications Fuel oil storage a Natural gas separators Coal crusher hopper Coal mill supply silo bunker Coal stack pile other fuel sources bark garbage Fuel combustion clean up For fuel combustion clean up radar transmitters are commonly used for the following applications a Ammonia anhydrous Ammonia aqueous Ashslurry lime slurry or liquid gypsum Sulfur solution tanks Scrubbers Ash hopper bottom ash or fly ash Lime silo a Powder Activated Carbon PAC combustion salt bone meal dried sludge Effluent For effluent radar transmitters are commonly used for the following applications Effluent flow Open atmosphere sumps Clarifiers Hydro power For hydro power radar transmitters are commonly used for the following applications Head and tail race u Leaky weir at bottom of dam a Water catchment water supply level and silt detection Section 1 Power Applications Reference Manual September 2013 00809 0700 4530 Rev 1 10 Miscellaneous For miscellaneous radar transmitters are commonly used for the following applications Sumps dr
111. y be installed on the bench it must be configured to the actual process conditions For the Rosemount GWR transmitters it is important not to bend the probe during any part of the installation It may be necessary to shorten the probe mount a centering disk or anchor the probe during the mechanical installation For more information see the Rosemount 3300 and 5300 Reference Manuals Document No 00809 0100 4811 and 00809 0100 4530 For the Rosemount 5300 Series with QS Prior Use option in Safety Instrumented Systems SIS refer to the Quick Installation Guide Document No 00825 0100 4530 and the Reference Manual Document No 00809 0100 4530 for instructions Beside these required steps the procedures below are recommended as best practices Recommendations for grounding are available in the Grounding Best Practices and Transient Protection for Rosemount Radar Transmitters Technical Note Document No 00840 2700 4811 Functions of procedures to include during commissioning process Table 3 1 Chamber installations Function Rosemount Series Trim Near Zone TNZ Rosemount 3300 Series Rosemount 5300 Series Upper Null Zone UNZ All Setting range values All Remote housing Rosemount 5300 Series Static Vapor Compensation SVC Rosemount 5300 Series Dynamic Vapor Compensation DVC Rosemount 5300 Series Signal Quality Metrics SQM Rosemount 5300 Series Safety Instrumented Systems SIS

Download Pdf Manuals

image

Related Search

Related Contents

MODE D`EMPLOI  Valueline VLTB90205B50 telephony cable  GB. DRC4=0 + M à J.pm6  ACCESSOIRES VEDETTES  8142PRO+ Industrial Terminal Service Manual  Hubbell Canada LP, Lighting Division 870 Brock Road South  RKM MK802 IV User Manual  PDF  IDROBUILD GIUNTOFLEX 120_fr  Rodilon® user guide and record book  