CyberPower 3000 VA User's Manual

image

Contents

1. Network Protection RJ45 One In One Out Physical Total of UPS Receptacles Maximum Dimensions Weight Kg Battery 5 3 IEC 2 Schuko 2U Rack 2 Sealed Maintenance Free Lead Acid Battery Typical Recharge Time 12V 7AHx8 8 Hours Warning Diagnostics Indicators Audible Alarms Environmental Power On Using Battery AVR Load Level Battery Level On Battery Low Battery Overload Operating Temperature 32 F to 95 F 0 C to 35 C 0 to 95 NON CONDENSING Operating Relative Humidity Communication PowerPanel Business Edition Windows 98 ME NT 2000 XP Server 2003 Software Management Self Test Manual Self Test Auto Charger Yes Auto Restart Yes C ep us Yes SNMP HTTP Network Optional DEFINITIONS FOR ILLUMINATED LED INDICATORS Condition Normal AVR Max boost 13 of input voltage for output regulation while input voltage is from 8 to 15 under nominal Off Bi Slow flash AVR Max boost 26 of input voltage for output regulation while input voltage is from 15 to 26 under nominal Rapid flash AVR Max buck 11 of input voltage for output regulation while input voltage is from 8 to 26 over nominal Tio Beane Utility Failure The UPS is providing battery power to PS the Battery Power Supplied outlets Rapid Utility Failure The UPS is providing battery power B ae Rapid beeps indicate the battery will run out of charge Q Q within a few mi
2. total load that you will be placing on the battery powered outlets should not exceed 80 of the unit s capacity DIRECTIONS TO MOUNT THE UPS IN THE RACK 1 Assemble the handlebars to the rack mount brackets ears as shown in the figures using the flat head screws M4 0 8mm provided 2 Assemble the two ears to the both sides of the UPS enclosure as shown in the figures using the flat head screws M5 0 8mm provided 3 Install the UPS at or near the bottom of the rack CAUTION At least two people are required when mounting the UPS in the rack due to its weight The battery pack may be removed while mounting it in the rack HARDWARE INSTALLATION GUIDE 1 To connect auxiliary battery pack a Remove the protection cover on the UPS rear panel b Connect the black wire and the red wire of the Battery Pack to the negative black terminal and the positive red terminal of the PR3000E respectively See below figure Note Due to the large current make sure to connect the positive to positive and the negative to negative Otherwise it may cause a short circuit and the unit may be irreversibly damaged t 4 2 Recharging the battery for at least four hours is recommended to insure that the battery s maximum charge capacity is achieved Charge loss may occur during shipping and storage To English version 1 0 recharge the battery simply leave the unit plugged into an AC outlet 3 Connect the equipmen
3. Cy berPower eu cyberpowersystems com Professional Rackmount UPS 3000 VA User Manual K0O1 3000E0A 02 SAFETY WARNINGS SAVE THESE INSTRUCTIONS This manual contains important safety instructions Please read and follow all instructions carefully during installation and operation of the unit Read this manual thoroughly before attempting to unpack install or operate your UPS This equipment can be operated by any individuals with no previous training The AC power outlet must be installed near the UPS and must be easily accessible During the installation of the UPS it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3 5mA Attention hazardous through electric shock Also with disconnection of this unit from the mains hazardous voltage still may be accessible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the battery when maintenance or service work inside the UPS is necessary Do not dispose of batteries or battery pack in a fire the battery may explode Do not open or mutilate the batteries Electrolyte is harmful to the skin and eyes To reduce the risk of fire connect only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electrical Code ANSI NFPA 70 INSTALLING YOUR UPS SYSTEM UNPACKING Inspect the UPS upon r
4. eceipt The box should contain the following UPS Unit Rack Mount Bracket x 2 Stand x 2 PowerPanel Business Edition Software Disk x 1 PowerPanel Software Disk x 1 Serial Interface Cable DB 9 x 2 Serial Interface to USB Adapter X 1 Telephone Cablex1 IEC to IEC Power Cord X 2 IEC to Schuko Power Cord X 2 UPS User Manual PowerPanel Business Edition Software User Manual PowerPanel Software User Manual HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 1 Insure that the equipment plugged into the battery power supplied outlets does not exceed the UPS unit s rated capacity 3000VA 2200W for PR3000E If rated unit capacities are exceeded an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip 2 If the power requirements of your equipment are listed in units other than Volt Amps VA convert Watts W or Amps A into VA by doing the calculations below Note The below equation only calculates the maximum amount of VA that the equipment can use not what is typically used by the equipment at any one time Users should expect usage requirements to be approximately 60 of below value TO ESTIMATE POWER REQUIREMENTS 1 ss Watts W x 2 0 VA or Amps A x 230 ___ VA 2 Add the totals up for all pieces of equipment and multiply this total by 0 6 to calculate actual requirements There are many factors that can affect the amount of power that your computer system will require The
5. ies Release electrolyte is harmful to the skin and eyes and may be toxic BATTERY PACK REPLACEMENT PROCEDURE 1 Turn off and unplug all connected equipments 2 Turn the UPS off and unplug it from the AC power source 3 Unplug the black and red wire of the Battery Pack from the UPS 4 Follow the_Hard Installation Guide to connect a new Battery Pack to the UPS STORAGE First turn off your UPS and disconnect its power cord from the wall outlet Disconnect all cables connected to the UPS to avoid battery drain To store your UPS for an extended period cover it and store with the battery fully charged Recharge the battery every three months to insure battery life If the battery remains uncharged for an extended period of time it may suffer permanent loss of Capacity TROUBLE SHOOTING Possible Cause The UPS does not Batteries are not fully charged Recharge the battery by leaving the UPS plugged f perform expected Contact CyberPower Systems at time is sli runt Battery is slightly worn out service cyberpower eu com prevent damage by rapidly Att ae seit off Wait 10 seconds and then turn turning it off and on The unit is not connected to an The unit must be connected to a 220 240V AC outlet 50 60Hz outlet Contact CyberPower Systems at The battery is worn out service cyberpower eu com The on off switch is designed to The UPS will not turn on hschanical orableni Contact CyberPower Systems at i service cyberpo
6. nutes On Off On Off Flash Overload Turn the UPS off and unplug at least one On Off Set Long Beep piece of equipment from the UPS Wait 5 seconds reset the circuit breaker and restart the UPS Overload Turn the UPS off and unplug at least one Off On Up Long Beep piece of equipment from the UPS Wait 5 seconds reset the circuit breaker and restart the UPS Surge Protection Malfunction Power surge has Off Off Set Off damaged the unit Please contact CyberPower Systems For more information visit eu cyberpowersystems com or contact CyberPower Systems B V Netherlands Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 73 649 1209 Fax 31 0 40 2340314 E MAIL sales cyberpower eu com CyberPower Systems Inc USA 4241 12th Avenue East Suite 400 Shakopee MN 55379 U S A Tel 1 952 4039500 Fax 1 952 4030009 E MAIL sales cyberpowersystems com Entire contents copyright 2004 CyberPower Systems B V All rights reserved Reproduction in whole or in part without permission is prohibited PowerPanel and PowerPanel Plus are trademarks of CyberPower Systems USA Inc CyberPower warrants to you the original purchaser that CyberPower UPS will be free from defects in design assembly materials and workmanship for two years battery is only one year from the date of original purchase Any warranty services please contact your local dealers or distributors
7. re temporary uninterrupted operation during a power failure and against surges and spikes Individual Backup Power for Critical Load The UPS provides one battery powered and surge protected outlet for the most critical connected equipment and insures temporary uninterrupted operation of connected equipment during a power failure NOTE When the UPS is overloaded the UPS will interrupt power supply to the 4 battery outlets and leave the one outlet for critical loads uninterrupted Ethernet RJ 45 Network Protection Ports These ports are the protection for your computer network cable IN OUT Serial Port to PC Professional Rack Mount Series UPS provides two serial ports to allow connection and communication between the UPS and two computers The two serial ports allow connection and communication from the DB 9 serial or USB port on the computer to the UPS unit These interfaces are also compatible with the UPS service provided by Windows 98 Windows ME Windows 2000 Windows NT Windows XP Windows Server 2003 Secondary PC wih Primary PU with PowerPanel Piua iahaied Power Panal onaiaised The Primary computer with PowerPanel Business Edition installed is the computer that you will use to control the UPS and make any change to the operation of the UPS The Secondary computer with PowerPanel installed is unable to exhibit any control over the UPS When power failure occurs one of the following shutdown seq
8. ss this button to silence an audible alarm Power On Indicator E This LED is illuminated when the utility condition is normal and the UPS outlets are providing clean power free of surges and spikes AVR Indicator This LED indicates that the UPS is operating in automatic voltage regulation mode When the led is illuminated continuously it indicates input over voltage and the UPS unit bucks the voltage When the led is flashed in rotation it indicates that the UPS unit boosts input voltage Using Battery Indicator a This LED illuminates during utility failure indicating that the battery is supplying power to the battery power supplied outlets Battery Level Indicator wes his indicator shows a visual indication of the battery charge When battery capacity s under 20 no indicator LED will illuminate If the battery capacity is under 20 even after 8 hour charge the batteries may be worn out part Load Level Indicators This indicator shows a visual indication of the UPS load The load indicator LED will em turn orange if the load is between 80 and 100 If the load is under 20 no indicator LED will illuminate T Circuit Breaker Reset for Overload Protection e Resettable circuit breakers provide optimal overload protection Battery Backup and Surge Protection Outlets The UPS provides 4 battery powered and surge protected outlets for connected equipment to insu
9. t to your UPS outlets The IEC IEC and the IEC to Schuko power cords coming with the unit are used to connect your computer and monitor to the UPS Items such as copiers laser printers vacuums space heaters or other large electrical devices should not be connected to the UPS Please make sure that the total loads of your equipments are less than the maximum total power load of your UPS 4 Plug UPS power cord to a wall outlet Please avoid using extension cords and adapter plugs To maintain optimal battery charge leave the UPS plugged in at all times 5 Press the UPS power button to turn it on The Power On indicator will be illuminated in Green 6 Install your software and accessories To use the software simply connect the enclosed serial interface cable to the serial port on the UPS and an open serial port on the computer BASIC OPERATION FRONT PANEL AND REAR PANEL DESCRIPTION 7 MI WUUUU UU Power Switch ee Epa ff a Press the power button to turn the UPS ON or OFF Test Switch pr Press this button to perform a self test of your UPS This UPS also performs a self C test automatically when powered on After the UPS passes the test it returns to n on line operation If the UPS fails the self test please recharge the battery for at least 4 hours and perform another self test If it fails after recharging the battery please replace the battery In battery mode you can pre
10. uences will be executed 1 If the Primary and Secondary serial ports are both in use the Primary computer will start to count down user controlled delay for shutdown User Control delay can be set in the PowerPanel Business Edition software Recommended time is 5 minutes Once the Primary computer is shutdown the UPS will signal the Secondary computer and initiate the Secondary to shutdown The UPS default shutdown time is 2 minutes Therefore it is recommended that Secondary computer is set to shutdown within 1 minute in PowerPanel Software 2 If only the Secondary serial port is in use the Secondary computer will shutdown following the user settings in PowerPanel Software However the Secondary computer will not able to signal the UPS to shut down Therefore the UPS will only power off when it is in low battery BATTERY PACK REPLACEMENT AND STORAGE CAUTION Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery pack Do not open the battery pack and service the batteries inside If you have questions contact your dealer or call the number in this manual for information on battery replacement CAUTION Use only CyberPower Battery Pack for replacement See your dealer for this model CAUTION The battery may present the risk of electrical shock Do not dispose of batteries in a fire as it may explode Follow all local ordinances regarding proper disposal of batteries CAUTION Do not open or mutilate the batter
11. wer eu com EIE Turn the UPS off and unplug at least one piece of a is tripped due to equipment Wait 10 seconds reset the circuit i breaker and then turn the UPS on Batteries are discharged Allow the unit to recharge for at least 4 hours Outlets do not provide power to equipment Unit has been damaged by a Contact CyberPower Systems at surge or spike service cyberpower eu com PowerPanel ai The serial USB cable is Seen ol OF vannectedtothe wrong port Try another serial USB port of your computer sect a TOP IS MOL PLO CIN ately T a cael A DFA an aiti should reset the unit are gray The serial cable is not the cable You must use the cable included with the unit for that was provided with the unit the software l Connect the serial USB cable to the UPS unit and a es a caie IS NOL an open serial port on the back of the computer You must use the cable that came with the unit Block Diagram AVR Switch Transformer Inverter DC AC Battery Charger TECHNICAL SPECIFICATIONS PR3000E 3000VA 2200W Capacity VA Capacity Watts Input 220 240Vac 50 60 Hz Voltage Range Frequency Range Output Pure Sine Wave at 230Vac 7 50 60 Hz On Battery Output Voltage On Battery Output Frequency Transfer Time Typical A n Overload Protection On Utility Circuit Breaker On Battery Internal Current Limiting Surge Protection and Filtering Lightning Surge Protection PY n