1. IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 5 Table 2 Specifications continued Communications and management USB port Yes RS 232 serial port Yes Ethernet port Optional using Network Management Card 46M4110 Environmental Monitoring Probe Optional Environmental Monitoring Probe 46M4113 Surge protection and filtering Surge energy rating 1300 Joules Battery run times and recharge times Table 3 lists the expected period during which the 11000VA UPS will operate solely on batteries Table 3 IBM 11000VA UPS runtime chart Load Run time on batteries Percentload VA Watts Run time with standard internal Run time with internal battery plus battery only External Battery Module EBM Note Battery backup times are approximate and can vary with equipment configuration battery age and temperature Physical specifications and operating environment The physical specifications of the 5U uninterruptible power supply are as follows e Height 212 mm 8 3 in e Width 483 mm 19 in e Depth 740 mm 29 1 in e Weight 99 kg 218 Ib The physical specifications of the 3U Extended Battery Module are as follows e Height 127 mm 5 0 in e Width 483 mm 19 in e Depth 740 mm 29 1 in e Weight 79 kg 174 Ib The IBM 11000VA LCD 5U Rack UPS is supported in the following operating environment e Temperature 0 40 0 C 32 104 F at 0 2 000 m 0 6 600 ft e Relative humidity 5 95 e Maxi
2. 11000VA LCD 5U Rack Uninterruptible Power Supply Rear panel Figure 3 shows the rear panel of the IBM 11000VA LCD 5U Rack UPS Optional Network USB and Remote emergency Extended battery Management Card serial ports power off REPO module EBM NMC bay port connector Four IEC 320 C19 Circuit breakers for Four IEC 320 C19 Input terminal receptacles load segments 1 and 2 receptacles block Load segment 1 Load segment 2 Figure 3 Rear panel of the IBM 11000VA LCD 5U Rack UPS IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Figure 4 shows examples of how the IBM 11000VA LCD 5U Rack UPS can be configured to power the BladeCenter chassis These examples are based on label ratings of the chassis Two IBM 11000VALCD Two IBM 11000VALCD 5U Rack UPS 53959KX 5U Rack UPS 53959KX 100A total 100A total One IBM 11000VALCD One IBM 11000VALCD 5U Rack UPS 53959KxX 5U Rack UPS 53959KX 50A 50A BladeCenter E 2320W BladeCenter H 2980W 2x BladeCenter H 2980W 3x BladeCenter E 2320W 27 6A rated load 37A rated load 74A rated load 82 8A rated load 22 4A still available 13A still available 26A still available 17 2A still available Figure 4 Examples uses of the IBM 11000VA LCD 5U Rack UPS IBM UPS 3U Extended Battery Module For applications requiring extended backup times an external battery module can also be added to the 11000VA models to deliver hours of run time to critical systems during
3. Power Monitor unloaded Diagnostic test reminder Communications port unavailable Diagnostic test performed Replace battery reminder Scheduled Manual shutdown IBM UPS Manager software installed Minor on battery event General power anomaly counter Filter List fan Alerts v Legend Email T Command Broadcast _Defaut Figure 10 Event Notification window on Oo e w N lt p f D amp D D D amp D D D D D D v IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Message text m Controller will shut down in MINUTES minutes Notification delay oc seconds E mail a Broadcast D Command IV Enable e mail alert messaging Test E mail recipients ITManager CompanyX com Server Settings Modify IBM Environmental Monitoring Probe The Environmental Monitoring Probe EMP part number 46M4113 is used to report local temperature a nd humidity values and make that information available to management tools such as IBM Systems Director Active Energy Manager AEM The EMP connects to the UPS via the Network Management Card Figure 11 shows the EMP Figure 11 IBM EMP The Environmental Monitoring Probe has the following characteristics It connects to the Network Management Card NMC settings sensor connection Its temperature and humidity thresholds are easily set to trigger alarm notifications or shut down the protect
4. a prolonged power outage The IBM 3U Extended Battery Module EBM is a 3U rack mounted device that contains additional batteries Table 3 shows the additional run times achieved with the EBM connected Figure 5 shows the front of the 3U Extended Battery Module Figure 5 IBM 11000VA UPS 3U Extended Battery Module EBM IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 10 Network Management Card The IBM 11000VA LCD 5U Rack UPS also comes equipped with a communication bay for the installation of an optional Network Management Card 46M4110 The Network Management Card provides convenient over the network UPS remote monitoring and management through a standard web browser Figure 6 shows the IBM LCD UPS Network Management Card NMC Figure 6 IBM LCD UPS Network Management Card NMC The IBM LCD UPS Network Management Card Allows simultaneous shutdown of protected servers Allows configuration of automatic email messages in response to UPS alarms and to transmit periodic reports Figure 8 Allows control of UPS on off switching with a web browser Allows adjustment and control of load segments through the HTML interface including sequential starting of the installation and optimization of backup time by shutting down non priority systems Allows protection by using an encrypted password Allows protection by using a secure SSL connection Allows log storage in the nonvolatile memory Allows card firmware updates through the
5. network Allows fast Ethernet 10 100 Mbps compatibility with auto negotiation on the RJ 45 connector Allows recording of events and measurements in the card log Has a humidity temperature dry contact sensor optional EMP Has support for IPv6 Can be installed while the UPS is online maintaining the highest system availability IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 11 Figure 7 shows the Network Management Card UPS properties window Network Management Card IBM 2200VA1920W Rack HV UPS Computer Room Logs and Notification About your UPS Settings Figure 7 IBM LCD UPS Network Management Card NMC UPS properties window IBM UPS Manager software The UPS comes with the IBM UPS Manager software The management software provides up to date graphics of UPS power and system data and power flow It also gives you a complete record of critical power events and notifies you of important UPS or power information If there is a power outage and the UPS battery power becomes low the software can automatically shut down the system to protect the data before the UPS shutdown occurs IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 12 Figure 8 shows normal operating using the IBM UPS Manager The input voltage is 122 V which is within the acceptable range and is shown in the left pane The output voltage of the UPS is 121 V and is also within the acceptable range The battery is in foating mode which is the second stag
6. rack power densities that have driven the requirement for advanced power management solutions e n combination with the optional Environmental Monitoring Probe AEM enables cross platform power and thermal trending analysis for improved power management This configuration allows IT and facility managers to manage data centers for optimal energy efficiency migrate workloads to eliminate hot spots and transfer work from underutilized systems to conserve energy IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 17 Related publications For more information see the following documents IBM US Product Announcement http ibm com common ssi cgi bin ssialias infotype dd amp subtype ca amp amp htmlfid 89 7 ENUS 111 002 IBM System x UPS product page http www ibm com systems x hardware options upsrack html IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Installation and Maintenance Guide http ibm com support entry portal docdisplay Indocid MIGR 5086831 Network Management Card User Guide http ibm com support entry portal docdisplay Indocid MIGR 5085199 IBM System x Configuration and Options Guide http ibm com support entry portal docdisplay Indocid SCOD 3ZVQ5W BM System x Uninterruptible Power Supply UPS Guide http ibm com support techdocs atsmastr nsf WebIndex WP 101655 IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Notices This information was developed for products and services offered in the U S A
7. IBM may not offer the products services or features discussed in this document in other countries Consult your local IBM representative for information on the products and services currently available in your area Any reference to an IBM product program or service is not intended to state or imply that only that IBM product program or service may be used Any functionally equivalent product program or service that does not infringe any IBM intellectual property right may be used instead However it is the user s responsibility to evaluate and verify the operation of any non IBM product program or service IBM may have patents or pending patent applications covering subject matter described in this document The furnishing of this document does not give you any license to these patents You can send license inquiries in writing to IBM Director of Licensing IBM Corporation North Castle Drive Armonk NY 10504 1785 U S A The following paragraph does not apply to the United Kingdom or any other country where such provisions are inconsistent with local law INTERNATIONAL BUSINESS MACHINES CORPORATION PROVIDES THIS PUBLICATION AS IS WITHOUT WARRANTY OF ANY KIND EITHER EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF NON INFRINGEMENT MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE Some states do not allow disclaimer of express or implied warranties in certain transactions therefore this statement may not app
8. Iln nT ae Redbooks Web Doc IBM 11000VA LCD 5U Rack Uninterruptible Power Supply IBM System x at a glance guide The IBM 11000VA LCD 5U Rack uninterruptible power supply UPS optimizes for both efficiency and performance providing the right level of power protection for the moment This online double conversion UPS delivers 10 000 watts of clean conditioned power with an efficiency rating of up to 96 to protect your IBM System x and BladeCenter investment improve availability and reduce energy consumption The power dense 5U design conserves rack space allowing for the protection of more equipment and leaving room for future IT expansion Figure 1 shows the IBM 11000VA LCD 5U Rack UPS Figure 1 IBM 11000VA LCD 5U Rack UPS for IBM System x Did You Know Unlike other competing UPS topologies the IBM 11000VA UPS features online double conversion technology to fully protect connected equipment from all nine of the most common power problems outages sags surges spikes brownouts line noise frequency variation switching transients and harmonic distortion The UPS has a bright easily customizable graphical LCD display that lets you configure the device and displays important UPS status information in one of nine languages This UPS enhances system availability with Advanced Battery Management ABM technology which significantly extends battery service life and optimizes recharge time and by providing individual con
9. Traditional Chinese Includes a real time clock that enables precise shutdown and powerup of systems in preferred sequence and time stamping on event logs to track and record specific power related occurrences Integrates with IBM Systems Director Active Energy Manager for power and thermal trending analysis and management Has load segments that allow for individual control of receptacle groups maximizing run time for critical devices Supports an optional network management card part number 46M4140 for enhanced UPS monitoring and control Allows dual channel communication through the USB port and an optional Network Management Card at the same time which is an effective redundancy feature that maximizes communications flexibility Supports an optional Extended Battery Module EBM for increased runtime requirements Includes a Remote Emergency Power Off REPO port to remotely power off the UPS unit to prevent battery operation during a power failure Requires the following input power e 200 240 V ac 50 60 Hz e Single phase circuit with a 2 pole circuit breaker e 683A Europe or 80A North America circuit Includes hot swap batteries for maximum uptime availability and ease of maintenance Supports an optional Environmental Monitoring Probe part number 46M4113 for thermal management requirements temperature and humidity which requires that the Network Management Card be installed Offers an Advanced Battery Mana
10. ck Uninterruptible Power Supply 19 This document was created or updated on January 31 2011 Send us your comments in one of the following ways e Use the online Contact us review form found at ibm com redbooks e Send your comments in an e mail to redbook us ibm com e Mail your comments to IBM Corporation International Technical Support Organization Dept HYTD Mail Station P099 2455 South Road Poughkeepsie NY 12601 5400 U S A This document is available online at http www ibm com redbooks abstracts tips0814 html Trademarks IBM the IBM logo and ibm com are trademarks or registered trademarks of International Business Machines Corporation in the United States other countries or both These and other IBM trademarked terms are US registered or common law trademarks owned by IBM at the time this information was published Such trademarks may also be registered or common law trademarks in other countries A current list of IBM trademarks is available on the Web at http www ibm com legal copytrade shtml The following terms are trademarks of the International Business Machines Corporation in the United States other countries or both BladeCenter IBM Systems Director Active Energy Manager IBM Redpaper Redbooks logo System x Other company product or service names may be trademarks or service marks of others IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 20
11. e of the Eaton Advanced Battery Management ABM three stage charging technology EJ IBM UPS Manager seis Svwos Controller RAINCWE0067515J 10 222 45 44 UPS model IBM UPS 1000VA to 3000VA i input Voltage Vf UPS Status W Output Voltage ABM Floating Event Status Normal 74212010 1 42 41 PM There are no active alarm events pending Figure 8 IBM UPS Manager normal status window IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 13 Figure 9 shows that the utility power supply has failed and that the UPS is now operating on battery The UPS Manager software indicates that there is 10 minutes of battery time available based on the current load View Configuration Shutdown Disgnostics Logs woe Sona Controller RAINCWE0067515J 10 222 45 44 UPS model IBM UPS 1000VA to 3000VA Input Voltage Er UPS Status Output Voltage AGN Discharging Event Status Q warning 7 2 2010 2 26 57 PM Q warring 7 2 2010 2 26 57 PM Q Warning 7 2 2010 2 26 57 PM Figure 9 IBM UPS Manager warning status window IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 14 Figure 10 shows the event notification window where you can configure how you and other users want to be notified when certain events occur Event Notification Pl Alert Type Controller shutdown pending Shutdown in 1 minute Shutdown cancelled Shutting down Controller communications lost Controller communications established Power Monitor loaded
12. ed system Its status can be monitored from the IBM Systems Director AEM or from the Network Management Card web interface It measures temperatures between 0 and 80 C 32 and 176 F with an accuracy of 1 C It measures relative humidity between 10 and 90 with an accuracy of 5 It can be located away from the UPS with a CAT5 network cable up to 20 m 65 6 ft Its user selectable alarm thresholds enable you to define acceptable temperature or humidity limits It allows email notification through SMTP IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Figure 12 shows information retrieved from an EMP using the NMC web interface Network Management Card Mac 25 5 recorded on 20100414 03 45 31 Max 32 2 recorded on 20100404 084011 Ema onmem Figure 12 Environmental Monitoring Probe data as viewed from the Network Management Card web interface IBM Systems Director Active Energy Manager IBM Systems Director Active Energy Manager AEM provides an array of new features that allow power and thermal trending analysis for improved power management AEM collects power information for each device attached to an IBM UPS presenting a more complete view of energy usage within the data center The IBM Systems Director AEM helps e Collect power information from each device attached to an IBM UPS thus presenting a more complete view of energy usage e With server consolidation plans because of the increased server and
13. es used by an actual business enterprise is entirely coincidental Any performance data contained herein was determined in a controlled environment Therefore the results obtained in other operating environments may vary significantly Some measurements may have been made on development level systems and there is no guarantee that these measurements will be the same on generally available systems Furthermore some measurement may have been estimated through extrapolation Actual results may vary Users of this document should verify the applicable data for their specific environment COPYRIGHT LICENSE This information contains sample application programs in source language which illustrate programming techniques on various operating platforms You may copy modify and distribute these sample programs in any form without payment to IBM for the purposes of developing using marketing or distributing application programs conforming to the application programming interface for the operating platform for which the sample programs are written These examples have not been thoroughly tested under all conditions IBM therefore cannot guarantee or imply reliability serviceability or function of these programs Copyright International Business Machines Corporation 2011 All rights reserved Note to U S Government Users Restricted Rights Use duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp IBM 11000VA LCD 5U Ra
14. gement ABM three stage charging technology which significantly extends battery service life and optimizes recharge time The three stages are 1 The battery is quickly charged to 90 to make sure the UPS is prepared for the next outage 2 ABM finishes charging the battery with a more moderate float charge 3 After the battery is charged ABM turns the charger off thereby preventing the batteries from being overcharged Specifications Table 2 lists the specifications for the 11000VA UPS model Table 2 Specifications IBM part number 5395 9KX VA Watts rating 11000 VA 1000 W Nominal output voltage Vac 208 V 230 V auto sensing at first powerup user configurable Rated power output 11000 VA normal and high efficiency modes 5500 VA double conversion mode Output power capacity in watts 10000 W normal and high efficiency modes 5000 W double conversion mode Circuit breakers Four two pole output breakers rated at 20 A two breakers for each load segment Efficiency Normal mode 93 High efficiency mode 96 Battery mode 90 Nominal input voltage 208 V 230 V auto sensing at first powerup 58 33 A battery mode Hardwired to terminal block Input voltage range mains operations 155 255 V for 208 V Battery type Valve Regulated Lead Acid VRLA maintenance free sealed leak proof Optional External Battery Pack Yes 69Y1986 Typical recharge time 3 hours to 90 charge from a UPS battery discharge of 50 rated load
15. k Uninterruptible Power Supply 2 The UPS does not include an input line cord The line cord is hardwired to a terminal block on the rear of the UPS A licensed electrician will need to connect the units to a dedicated branch circuit Circuit requirements are listed in the BM 110000 VA UPS and 11000 VA EBM Installation and Maintenance Guide Operating modes The UPS has selectable high efficiency normal double conversion and converter modes of AC operation In high efficiency mode the UPS monitors incoming power and stands ready to automatically transfer to normal double conversion mode as needed In this operation mode the UPS can operate at up to 96 efficiency under normal conditions and 93 or greater efficiency when poor power conditions require the UPS to work harder As a result the UPS uses less energy and dissipates less heat which in turn reduces power and cooling costs This mode protects against these power faults Power failure Power sag Power surge Under voltage Over voltage In normal double conversion mode the UPS supplies filtered utility power protecting the connected equipment from all nine of the most common power problems Normal double conversion mode provides extra protection against four additional line quality irregularities Harmonic distortion Line noise Switching transients e e J e Frequency variation In converter mode the UPS supplies the load from utility power while acting as a f
16. ly to you This information could include technical inaccuracies or typographical errors Changes are periodically made to the information herein these changes will be incorporated in new editions of the publication IBM may make improvements and or changes in the product s and or the program s described in this publication at any time without notice Any references in this information to non IBM Web sites are provided for convenience only and do not in any manner serve as an endorsement of those Web sites The materials at those Web sites are not part of the materials for this IBM product and use of those Web sites is at your own risk IBM may use or distribute any of the information you supply in any way it believes appropriate without incurring any obligation to you Information concerning non IBM products was obtained from the suppliers of those products their published announcements or other publicly available sources IBM has not tested those products and cannot confirm the accuracy of performance compatibility or any other claims related to non IBM products Questions on the capabilities of non IBM products should be addressed to the suppliers of those products This information contains examples of data and reports used in daily business operations To illustrate them as completely as possible the examples include the names of individuals companies brands and products All of these names are fictitious and any similarity to the names and address
17. mum altitude 3 048 m 10 000 ft IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 6 Warranty The IBM 11000VA LCD 5U Rack UPS has a 3 year limited warranty Supported rack installation The IBM 11000VA LCD 5U Rack UPS requires 5U of rack space in one of the following rack cabinets IBM 42U 1200mm Deep Static Rack IBM 42U 1200mm Deep Dynamic Rack IBM 42U 1200mm Deep Dynamic Expansion Rack IBM 47U 1200mm Deep Static Rack IBM 42U Enterprise rack IBM S2 42U Dynamic rack IBM S2 42U rack IBM S2 25 U rack IBM 11U Office Enablement kit Front panel controls With a bright and easy to navigate panel that provides configurability and displays important status information the IBM 11000VA UPS is easy to manage and an ideal solution for standardization across the global enterprise Runtime load and other vital information and troubleshooting are also displayed Figure 2 shows the front panel of the UPS Remaining time on Current load battery on the UPS 55 graphical d and numeric 6050 VA Cun 211 y 6luz2 power ix fi z UPS ON Output Overall etd status Escape Down OK button button button Figure 2 Front panel showing system status IBM 11000VA LCD 5U Rack Uninterruptible Power Supply The following functions are available on the control panel System status Displays the battery status load percentage output power output voltage and frequency mode notice or alarm status Alarm hi
18. requency converter locking the UPS into a stable output frequency and transferring to battery mode as necessary Use converter mode to lock the UPS output frequency at 50 Hz or 60 Hz to suit power sensitive equipment or to provide 50 Hz output when the available standard utility input is 60 Hz or the reverse Three additional modes are available e Battery mode where the UPS operates on battery typically when utility power has failed e Bypass mode where the battery is disabled typically for the purposes of battery maintenance e Standby mode where the UPS is turned off Features The IBM 11000VA LCD 5U Rack UPS has the following features and capabilities e Occupies 5U of vertical rack space e Upto 96 energy efficiency in high efficiency mode at 100 load or 93 or greater efficiency in normal double conversion mode e Operates in one of three modes Normal high efficiency or converter mode as described above e Offers eight IEC 320 C19 receptacles e Bundled intelligent IBM UPS Manager software enhances control and manageability IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 3 IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Supports IPv6 for future proofing IP addressing and security Includes a graphical LCD display that lets you configure the device and displays important UPS status information in one of nine languages English French German Spanish Russian Korean Japanese Simplified Chinese
19. story Displays the alarm history for the 50 most recent events Meters Displays the output watts VA current power factor voltage frequency input voltage input frequency battery voltage and percentage charged Control screens Displays the battery test reset error state configure load segments and restore settings Model information Displays the machine type model and serial number of the unit as well as the firmware level of the UPS including the optional Network Management Card s firmware level and IP address if installed Configuration Allows you to change up to 17 user settings with minimal navigation The buttons have the following functions Escape X Press this button to return to the previous menu without running a command or saving any changes Down Press this button to scroll down to the next menu option OK Press this button to select the current menu or option On off Press this button to turn on the UPS Press and hold this button for 3 seconds to turn off the UPS On some screens the OK button has an additional function if you press and hold the button longer than 1 second On the User Setting screens to save the displayed setting On the Meter and Notice Alarm screens to lock the screen prevent the screen from returning to its default after timeout A locked screen displays a small key image near the status icon To unlock the screen press any button to perform its usual function IBM
20. trol of receptacle groups that can maximize run time for critical devices in the event of a prolonged power outage It also provides a real time clock that enables precise shutdown and powerup of systems in a preferred sequence and records specific power related occurrences for more accurate trending and data analyses The IBM 11000VA UPS integrates with IBM Systems Director Active Energy Manager to help improve energy management IBM 11000VA LCD 5U Rack Uninterruptible Power Supply 1 About uninterruptible power supplies A UPS is a device that acts as a defensive barrier between electronic equipment and incoming power problems It conditions regulates and filters out power disturbances to ensure a clean power source for IT equipment A UPS also provides battery backup in the event of a power failure In today s high availability server environments unplanned power outages or line quality irregularities can have a considerable financial impact on businesses of all sizes The typical utility power is 99 9 available but that means that there can be almost nine hours of downtime a year not to mention brownouts and other power quality problems Selecting the right IBM UPS can help protect against these potentially costly incidents The IBM 11000VA UPS is designed to prevent blackouts brownouts sags and surges from reaching your servers and other valuable electronic equipment The UPS filters small utility line fluctuations and isolates yo
21. ur equipment from large disturbances by internally disconnecting from the utility line The UPS provides continuous power from its internal battery until the utility line returns to safe levels or the battery is fully discharged The UPS has selectable high efficiency and double conversion modes of operation The IBM 11000VA UPS continuously conditions and controls AC output during normal operating conditions regulating both voltage and frequency Even when presented with severe power problems UPS output remains within 2 of nominal voltage Part number information Table 1 lists the orderable part numbers and feature codes for the IBM 11000VA UPS Table 1 Ordering part numbers and feature codes IBM 11000VA LCD 5U Rack UPS 208V 230V 5395 9KX 5395 RU5 FC 6662 IBM 11000VA UPS 3U Extended Battery Module EBM 69Y 1986 5395 RU5 FC 5735 IBM LCD UPS Network Management Card optional 46M4110 6145 IBM LCD UPS Environmental Monitoring Probe optional 46M4113 6146 The UPS models include the following items e Anaccessory kit containing the following items Front bezel Rack mount kit with rails and hardware including 4 post rail kit Serial cable 3 7 m 12 ft USB cable Remote emergency power off REPO connector e A documentation kit containing the following items e Warranty flyer and Important Notices Manual e Documentation CD e Software CD which contains IBM UPS Manager power management software IBM 11000VA LCD 5U Rac