APC ACFS76080 hardware cooling accessory

image

Contents

1. CHILLED WATER DX Direct Expansion MODEL MODEL TD UCV 0700 TD UAV 0511 3342 1000 TD UWV 0511 2842 1200 TD UEV 0511 2842 1700 TD UDV 0511 2842 2500 TD UTV 0511 2842 TU TDC 3400 4000 TDCV 4300 TERMINAL BLOCK WIRING DIAGRAM TERMINAL BLOCK WIRING DIAGRAM 2000004 B 20000 699222 Ode gg ea 71 als 6 pA CONTROL CARD 8 jo gt SERVOMOTOR SERVOMOTOR 660 25 222200 1 66 mrar 22200 1 66 4822 NOTE 0 10v signal Y4 and 24 V output is available 005 and can be provided Using the standard LED display Turn power off to the unit and wait for the main screen to appear Press the Prg key Using the UP or DOWN key select SERVICE MENU and press ENTER Enter the password qm Uniflair LE Accessories Manual 25 NOTE The password is found inside the envelope attached to the manual If the password has been changed enter the new password instead 5 Press ENTER 6 Using the UP or DOWN key select HARDWARE SETTINGS and press ENTER 7 Navigate to the ON OFF MODE screen ON OFF MODE Via Input Contact N NOTE These two settings are Only Via Serial N applicable Motorized Damper Y Opening Time 120 Mot Damper Ou
2. na4829a Item Description Quantity Gravity damper 1 Uniflair LE Accessories Manual 27 Condensate Pumps Overview Uniflair condensate removal pumps collect and automatically remove water up to 100 C 212 F The pump collects water in its integral reservoir After enough water has been collected an internal float switch activates the pump and the water is pumped out Once enough water has been evacuated from the reservoir the pump automatically deactivates Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to install operate service or maintain it The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure ADANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH reduce the risk of electrical shock this pump must be grounded with a properly wired grounding connection Disconnect electrical power at the power source fuse box circuit breaker etc before servicing pump Do not handle the pump with wet hands while standing on a wet damp surface or in water Failure to follow these instructions will result in death or serious injury NOTICE FLAMMABLE FLUIDS The pump should only be used for liquids compatible with pump component materials Do not
3. 480 4807 MODEL TD UAV 0511 0611 TD UWV 0511 0611 TD UEV 0511 0611 TD UDV 0511 0611 TD UTV 0511 0611 MODEL TD UCV 0700 Uniflair LE Accessories Manual 4805 Uniflair LE Accessories Manual MODEL TD UAV 0921 1822 TD UWV 0921 1822 TD UEV 0921 1822 TD UDV 0921 1822 TD UTV 0921 1822 TUAV 2242 3342 TUWV 2242 2842 TUEV 2242 2842 TUDV 2242 2842 TUTV 2242 2842 TD UCV 1000 3400 TDCV 4000 MODEL TDAV 2242 3342 TDWV 2242 2842 TDEV 2242 2842 TDDV 2242 2842 TDTV 2242 2842 41 42 4808 2 Remove any necessary unit paneling 3 Secure the bracket to the proper location with the Phillips screws There are two mounting positions horizontal and vertical a Place rubber grommet inside bracket holes b Remove the head of the sensor by gently twisting to the left to separate the base c Secure the base of the sensor using the screws and washers provided d Screw the head of the accessory back on na4628a 4 Depending on the manufacturing date the design may be different for each sensor Locate the proper sensor design in the following wiring diagrams and connect the wires accordingly MODEL TDCV4300 and or filters to access the bracket insta
4. ses 124 36 Operations ca eer a tx ee Reo A ee a cane 36 Troubleshooting cece ccc eee n 36 Smoke and Fire 4 2 22 2 24 39 39 Installation abe eee 39 Configuration 2 1 12e 44 24 V Relay for External Smoke Fire Alarm 46 iive und RE Pei a wet wi 46 Installation eS ERE DDR ERRORI ee A EE YRSA 46 Configuration oiu pe UE VY xp er 50 Water Leak 1 1 51 IAVeNtO RES ted hah p OE NU E 51 Installation Mah RE EURO A CREARI 51 EED status lights roe PIPER EP Fou ey 58 Additional installation details 58 Configuration yes ed data des 59 Automatic Floor Pressurization System 61 25 eres wiz aed P o told fre vs tocan Deke AS d 61 OTIO V qnam nail new MA qe ae 61 ii Uniflair LE Accessories Manual tote BA oen t Cooling Unit Shutdown 62 Attaching the Controller Box 62 Installing the sensors 63 corinection eae pee Late es 65 Supply power connections 65 Configuration s sm
5. E SAS E 20 5 6 7 EOD 3 J ES 51 51 84 720 s a 4 L P l 1 02 UPC5 m JUMPER JUMPER 3 Uniflair LE Accessories Manual FLOODING DETECTOR 2103 gt 9 25 25 gt JUMPER gt 4 a a 5 a p cS 0902 UPC5 m LE Il I g RED 0 RED 720 JUMPER RED 51 CP us 5 1 720 JUMPER 730 a N 4 The sensor is normally closed and the alarm activates when the circuit is completed by either the spot or tape detectors when water is present 5 After the wiring to the unit is complete locate a proper position layout location for the tape or spot leak detector STAINLESS STEEL LEADS 15mm DESIGNATED SCREW LOCATIONS 0 60 FIBER POLYESTER MATERIAL 230 9 00 25 82 Dimensions shown in mm in Dimensions shown in m ft Uniflair LE Accessories Manual 57 6 The tape sensor provides water leak detection along the entire length of the strip and can be placed the floor or on other surfaces e g wrapped around pipes and flanges It can be fastened using screws silicon or clamps 7 The spot sensor is made up of a corrosion proof metal container with access to the two terminals for connecting the line
6. 36 51 18 33 66 54 21 36 73 ACFS76057 5 914 1710 855 1 786 932 4 36 67 32 33 66 70 35 36 73 ACFS76058 6 914 2 160 855 2221 932 6 36 85 04 33 66 88 11 36 73 ACFS76059 7 914 2572 855 2 631 932 8 36 101 26 33 66 104 25 36 73 Uniflair LE Accessories Manual 12 in 18 in 24 in 36 Seismic Frame AWARNING HEAVY EQUIPMENT Use at least two people when handling and installing this equipment Failure to follow these instructions can result in death serious injury or equipment damage ACAUTION DAMAGE TO EQUIPMENT OR PERSONNEL This equipment is heavy and can easily be tipped For safety purposes adequate personnel must be present when moving this equipment Failure to follow these instructions can result in injury or equipment damage na4683a The following tables provide frame size model and fastener details for the 12 in 18 in 24 in and 36 in seismic frames Model Frame Dimensions mm in Number of Size M8 fasteners A B 76060 3 305 12 1 000 740 1060 800 4 ACFS76065 457 18 39 37 29 13 41 73 31 50 ACFS76070 610 24 ACFS76075 914 36 ACFS76061 4 305 12 1 300 855 1360 916 4 ACFS76066 457 18 51 18 33 66 53 54 36 06 ACFS76071 610 24 ACFS76076 914 36 ACFS76062 5 305 12 1710 855 17
7. 2842 53 4824 PANEL MODEL TD UAV 0511 0611 TD UWV 0511 0611 TD UEV 0511 0611 TD UDV 0511 0611 TD UTV 0511 0611 2 Install the SAS module in the proper location on the DIN rail 3 The following provides wiring diagrams based on unit type a For T CV units STANDARD WIRING DIAGRAM T CV 25 20 20 2 1 STD RAS SUS 5 1 SoS 2 5 OPT ALTERNATIVE ALTERNATIVE 9 102 BS ni i o m2 IUPCIs UPCTm 1 3 uk EN gu E Ei 2 5 lt 56 58 Er 4 now no mn OPT H x 1 B oh 1 ci b For T AV T EV T DV T WV T TV and HDCV units Uniflair LE Accessories Manual STANDARD FACTORY INSTALLATION CONDENSATE DRAIN PUMP ALARM CONTACT 20 20 lt 5 5 51 51 m 844 Ww 8 lt 5 7 J B 9 4 CP 4 Ac L r 24 651 4 4 lt 2 gt k a 4 2 5 5 E zB Op2 OID2 UPC5 m_ UPC5 m_ am i a ee 9 JUMPER JUMPER 4814 Uniflair LE Accessories Manual 56 FLOODING DETECTOR CONDENSATE DRAIN PUMP ALARM CONTACT
8. 92 Uniflair LE Accessories Manual Installation 1 Disconnect the power 2 Using a screwdriver remove the plastic hatch from the electronic controller 3 If necessary select the type of analog inputs using the dip switch This must be done before installing the card controller only 4 Using a cutting nippers remove the precut plastic hatch 5 Insert the card in the corresponding plug in connector making sure it is fully inserted against the two plastic supports on the pCO controller 6 Close the cover ensuring the connector on the optional card lines up with the cover The modem is connected using the 9 pin socket on the card A diagram of the pins on the connector are shown in the following figure na4767a Socket Description Socket Description 9 n c GND Frame 2 RX e TX RTS DTR Uniflair LE Accessories Manual 93 Configuring using the LED display NOTE If installing multiple units on the network each unit needs a unique address to avoid conflicts Press Prg on the display interface Select SETTINGS Enter the password Select SERIAL MODEM SETTINGS Enter the following Serial Address ak wn gt Serial Speed Protocol Modem GSM 6 Navigate to the main screen Configuring using the touchscreen Path Main gt Configuration gt Unit gt Communication 1 Turn on the power to the unit and wait for the touchscreen to display NOTE Settings
9. use to pump flammable or explosive fluids Do not use in explosive atmospheres In any installation where property damage and or injury could occur as a result of an inoperable or leaking pump a backup system such as high level safety float switch and or alarm is highly recommended Failure to follow these instructions can result in equipment damage IMPORTANT For correct wiring installation refer to the enclosed wiring diagrams Make certain that line voltage corresponds to voltage specified on pump motor s nameplate IMPORTANT All wiring must conform to local electrical codes In areas without local code the National Electrical Code applies Uniflair LE Accessories Manual 29 Component Identification 304 200 152 Dimensions shown in mm in Item Description Electrical component cover Motor for voltages see Pump Models and SKUs on page 31 Check valve with 12 7 mm 1 2 in copper tubing discharge Barbed 19 mm 3 4 in inlet Tank Optional 19 05 mm 3 4 in barbed inlet cover and plug must be removed 000000 30 Uniflair LE Accessories Manual Pump Models and SKUs The following table provides the model numbers SKU installation details of pumps available for Uniflair cooling units and pump wiring information External wiring External power source The pump is shipped loose from the factory Factory installed Powered internally by the unit Th
10. 19 69 67 72 34 06 117 95 discharge ACPL75137 Gray orretum ACPL75138 Black plenum e in ACPL75113 Blue 6 500 2 170 865 62 00 ACPL75139 White 19 69 85 43 34 06 136 70 ACPL75140 Gray ACPL75141 Black ACPL75114 Blue 7 500 2582 865 70 00 ACPL75142 White 19 69 101 65 34 06 154 30 1 75143 Gray ACPL75144 Black Uniflair LE Accessories Manual 12 in Plenum Stackable Up To 48 in Up to four 12 in plenums can be stacked together NOTE Fasteners are field supplied e 1 19 1 amp M4 FASTENER 2 4 m g a e 28 11 Uniflair LE Accessories Manual 13 8 The following table provides frame size model and fastener details for 12 in plenums stackable up to 1219 2 mm 48 in na4693a Type of Model Color Frame Dimensions mm in Net Weight Number of Plenum Size kg Ib M4 fasteners A B ACPL75150 Blue 3 305 1 010 750 20 0 0 ACPL75151 White 12 00 39 76 29 53 44 10 ACPL75152 Gray ACPL75153 Black ACPL75154 Blue 4 305 1 310 865 23 2 ACPL75155 White 12 00 51 57 34 06 50 70 ACPL75156 Gray ACPL75157 Black Uniflair ACPL75158 Blue 5 305 1 720 865 27 4 1 75159 White 12 00 67 72 34 06 59 53 1 75160 Gray return or a ACPL75161 Black 305 mm 1
11. 20 in Return Plenum 11 12 in Plenum Stackable Up 48 13 20 in Front Supply Plenum w 15 IPAM SUD BAS CS 17 8 in Sub Base for Piping uso o Eo e m PR d 17 20 in Sub Base for 0 19 20 in Sub Base Front Supply w Grille 20 23 Wi vaca une ros a 23 Air duet ox du cae ote 23 Motorized 23 sae Beh inne 23 Installation 24 24 Uniflair LE Accessories Manual Gravity Damper a sr Cus soe 27 Inventory aceite hana 27 Condensate 2 000 2 1 2 1 0000000000000000000000001520 29 ard EE 29 Important Safety 29 Component 30 Pump Models and 5 5 31 Installation oL ab 31 Plumbing connections 31 Wiring connections 32 Gonfiguratlon tue ER be been NU ead 35 Pump test oil Sec
12. Installation Item Description 09000000 AFPS controller Power supply harness Above floor pressure sensor tubing Below floor pressure sensor tubing Communication wiring Installation hardware screws and washers tLAN card Mounting bracket Quantity ee ee gt Uniflair LE Accessories Manual 61 A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury Cooling Unit Shutdown 1 From the display interface put the unit in stand by and wait for the fans to stop 2 Turn the disconnect switch to the OFF position Attaching the Controller Box Determine the mounting location on the unit bracket and attach the bracket to the unit frame with the two provided screws 1 INSTALLATION LOCATION FOR AFPS CONTROLLER na4827a 62 Uniflair LE Accessories Manual 2 Align the mounting bracket with the unit bracket and install with provided screws MOUNTING BRACKET UNIT FRAME na4757a 3 Using a standard screwdriver remove the front cover and rear tabs from the AFPS controller 4 Attach th
13. Starting sequences power up and restarting 86 Additional documentation 87 Configuring pCOnet parameters 87 va TRE p RUSSE Taria PCOS004850 serial card for pCO controller Part OM 21AS108CDZ 89 Inventory ina tac eh Page aly 89 90 Configuring using the LED display 91 Configuring using the touchscreen 91 Uniflair LE Accessories Manual INVENTORY ee a 92 Installation dees RES 93 Configuring using the LED display 94 Configuring using the touchscreen 94 Uniflair LE Accessories Manual Safety Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to install operate service or maintain it The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed safety messages that follow this symbol to avoid possible injury or death This is the safety alert symbol It is used to alert you to potential personal
14. Using a screwdriver remove the plastic hatch from the electronic controller na4553a 4 Insert the optional card into the corresponding connector and ensure the card is firmly placed on both plastic supports on the pCO controller case 5 Close the cover using a screwdriver to fit the outside card terminal to the cover The connection with the RS485 network is carried out by means of the plug in terminal connector on the card Pin wiring of the connector is stamped on the card na4768a Pin Connector GND RX TX RX TX ww N 90 Uniflair LE Accessories Manual If the card is placed in the last position of the supervision serial line pins 2 and 3 you must connect a 120 01 4 W end line resistor na4769a Configuring using the LED display NOTE If installing multiple units on the network each unit needs a unique address to avoid conflicts Press Prg on the display interface Select SETTINGS Enter the password Select SERIAL MODEM SETTINGS Enter the following a Serial Address b Serial Speed c Protocol Modbus 6 Navigate to the main screen gt Configuring using the touchscreen Path Main gt Configuration gt Unit gt Communication 1 Turn on the power to the unit and wait for the touchscreen to display NOTE Settings may appear on a different screen 2 Enter your credentials and begin configuration 1 Serial Address Enter the
15. at least two people when handling and installing this equipment Failure to follow these instructions can result in death serious injury or equipment damage ACAUTION TIP HAZARD The equipment is heavy and can easily be tipped For safety purposes adequate personnel must be present when moving this equipment Failure to follow these instructions can result in injury of equipment damage 8 in Sub Base for Piping M8 FASTENERS 200 MM 8 IN SUB BASE PLENUM NOTE Fasteners and vibration pads are field supplied Uniflair LE Accessories Manual 17 na4696a The following tables provide frame size model and fastener numbers for the 8 in sub base for piping Dimensions mm in Net Weight Number of kg Ib M8 Type of Frame A B C fasteners Plenum Model Color Size ACSB76140 Blue 3 200 1 000 740 17 70 4 ACSB76150 White 7 87 39 37 29 13 39 02 5 76151 Gray ACSB76152 Black ACSB76142 Blue 4 200 1 300 855 21 80 4 ACSB76153 White 7 87 51 18 33 66 48 06 ACSB76154 Gray ACSB76155 Black Sub base plenum ACSB76142 Blue 5 200 1710 855 27 20 4 200 mm ACSB76156 White 7 87 67 32 33 66 59 97 8 in ACSB76157 Gray ACSB76158 Black ACSB76143 Blue 6 200 2 160 855 31 60 6 ACSB76159 White 7 87 85 04 33 66 69 67 ACSB76160 Gray ACSB76161 Black ACSB761
16. injury hazards Obey all DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a potentially hazardous situation which if not avoided can result in death or serious injury CAUTION CAUTION indicates a potentially hazardous situation which if not avoided can result in minor or moderate injury NOTICE NOTICE addresses practices not related to physical injury including certain environmental hazards potential damage or loss of data Uniflair LE Accessories Manual 5 General Information Overview This manual provides information on accessories available with Uniflair LE cooling units It supplies general information safety instructions installation information and setup information The descriptions and illustrations in this manual are owned by Schneider Electric Schneider Electric reserves the right to make any alterations it sees fit in order to improve the product without having to update this document The illustrations and images in this manual are examples only and may differ from your model or environment Companion Manuals For more information about Uniflair units refer to the following documentation Uniflair LE Chilled Water HDCV 4500 5000 Operation and Maintenance Manual Uniflair LE DX Operation and Maintenance Manual Uniflair LE Chilled Water HD
17. is not illuminated check to ensure the the connection on the pCO side baud rate of the serial communication on pCO is set to 4800 The LonWorks network setup must follow LonWorks instructions and specifications For further information on installation maintenance cross section and cabling refer to the LonWorks documentation RS485 pCOnet PCO1000BA0 ACAC76123 DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury Electrical damage on the electronic components usually occurs because of electrostatic discharges caused by improper handling by the operator When handling these components take the following precautions Before handling any electronic component or card ground the card Keep the components inside their original package as long as possible If necessary take the main board from a package and put it into an anti static package without touching both sides of the board with your hands Avoid plastic bags and polystyrene Avoid handing a card from one operator to another to avoid any electrostatic induction and discharges The pCOnet board interfaces to pCO and connects
18. pin short circuit the two pins using the tip of a screwdriver Activation is confirmed when the LED service light activates Configuration 82 Using the LED display NOTE If installing multiple units on the network each unit needs a unique address to avoid conflicts ak gt Press Prg on the display interface Select SETTINGS Enter the password Select SERIAL MODEM SETTINGS Enter the following Serial Address 001 Serial Speed 4800 Protocol Standard Navigate to the main screen Uniflair LE Accessories Manual Using the touchscreen Path Main gt Configuration gt Unit gt Communication 1 Turn on the power to the unit and wait for the touchscreen to display NOTE Settings may appear on a different screen 2 Enter your credentials and begin configuration 51 Serial Address 001 1 Serial Speed 4800 51 Serial Protocol Standard Remote ON OFF Only Through Serial Communication Enable 3 Press the Home button to return to the main screen LON serial card LED light functionality Condition Description Green during the normal status of Signals the status of the LonWorks node as the LonWorks LonWorks node protocol Green when activating the service Remains on during the activation of the service pin pin Green when receiving the WINK Remains on for a second when receiving a WINK command command from the network Red when signaling the failure of the red anomaly LED
19. required Serial Address 1 Serial Speed Enter the required Serial Speed BMS1 Serial Protocol Modbus Remote ON OFF Only Through Serial Communication Enable 3 Press the Home button to return to the main screen Uniflair LE Accessories Manual 91 RS232 100 0 RS232 field bus card for pCO ACAC76125 A A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury Electrical damage on the electronic components usually occurs because of electrostatic discharges caused by operator improper handling When handling these components take the following precautions Before handling any electronic component or card ground the card The components must be kept inside their original package as long as possible If necessary take the main board from a package and put it into an anti static package without touching both sides of the board with your hands Avoid non anti static plastic bags and polystyrene Avoid handing a card from one operator to another to avoid any electrostatic induction and discharges Inventory na4632a Item Description Quantity PCO100MDMO board modem for PCO 1
20. unit gives up control Token of the network to another Master unit It indirectly establishes a priority between the Master units in the network High numbers guarantee the Master a higher data exchange volume MaxMaster To speed up data exchange between the Master units MaxMaster should be set to the Station Address of the Master with the highest Station Address Each Master unit after having used the network passes over control to the next Master The MaxMaster parameter specifies to pCOnet the address of the network Master with the highest Station Address Using this parameter pCOnet will know that there is no other Master with a higher Station Address than MaxMaster pCOnet then gives control of the network to the next Master however not beyond MaxMaster If no next Master is found the cycle begins again with control being given to the Master with the lowest Station Address BaudRate The data transfer speed The BaudRate must be the same for all the devices connected otherwise the exchange of data will generate communication errors For extended networks low baud rates should be specified This guarantees less communication errors If the Baud Rate is 76800 make sure that the device supports this communication speed This baud rate is not supported by the RS232 serial port on a normal PC Uniflair LE Accessories Manual RS485 PCOS004850 serial card for pCO controller Part OM 21AS108CDZ A A DANGER HAZARD OF ELECTRIC SHOCK E
21. 2 Press Prg 3 Select SERVICE MENU then press ENTER NOTE The password is found inside the envelope attached to the manual If the password has been changed enter the new password 44 Uniflair LE Accessories Manual NO on 8 9 Press ENTER Select HARDWARE SETTINGS and press ENTER Navigate to DIGITAL INPUT 4 CONFIGURATION Check to ensure the existing setting is not used If this does not correspond to your settings whatever function is currently attributed to that digital input of the control will be lost at the end of this procedure and replaced with the one relative to the operation of the fire smoke sensor Press ENTER until the cursor stops under NOT USED Press UP or DOWN until SMOKE FIRE SENSOR appears on the display 10 Press ENTER 11 To exit press the ESC key and navigate to the main screen After completion of the above procedure an alarm signal displays on the display interface in case of fire or smoke and the unit stops operating Using the touchscreen Path gt Configuration gt Unit gt Digital Inputs 1 2 3 Turn on the power to the unit and wait for the touchscreen to display Set the following configurations NOTE Settings may appear on a different screen Digital Input 4 Configuration Smoke Fire Sensor Digital Input 4 Function Alarm Signaling Digital Input 4 Normal State Normally Open Press the Home button to return to the main screen Uniflair LE Accesso
22. 2 in Stackable ACPL75162 Blue 6 305 2170 865 32 4 ACPL75163 White 12 00 85 43 34 06 70 54 ACPL75164 Gray ACPL75165 Black ACPL75166 Blue 7 305 2 582 865 36 4 ACPL75167 White 12 00 101 65 34 06 79 36 ACPL75168 Gray ACPL75169 Black Uniflair LE Accessories Manual 20 in Front Supply Plenum w Grille M4 FASTENER na4539a The following table provides frame size and model details for the 20 in front supply plenum w grille Type of Model Color Frame Size Dimensions mm in Net Weight Plenum kg Ib A B 75105 Blue 3 500 1 000 740 38 00 ACPL75115 White 19 69 39 37 29 13 83 78 ACPL75116 Gray ACPL75117 Black ACPL75106 Blue 4 500 1 300 855 50 00 ACPL75118 Gray 19 69 51 18 33 66 110 20 ACPL75119 White ACPL75120 Black Front supply plenum 500 ACPL75107 Blue 5 500 1710 855 59 00 mm 20 in 75121 Gray 19 69 67 32 33 66 130 10 ACPL75122 White ACPL75123 Black ACPL75108 Blue 6 500 2 160 855 74 00 ACPL75124 Gray 19 69 85 04 33 66 163 10 ACPL75125 White ACPL75126 Black ACPL75109 Blue 7 500 2572 855 87 00 ACPL75127 Gray 19 69 101 26 33 66 191 80 ACPL75128 White ACPL75129 Black Uniflair LE Accessories Manual 15 Uniflair Sub Bases AWARNING HEAVY EQUIPMENT Use
23. 44 Blue 7 200 2572 855 35 60 8 ACSB76162 White 7 87 101 26 33 66 74 49 ACSB76163 Gray ACSB76164 Black Uniflair LE Accessories Manual 20 Sub Base for Piping 8 BOLTS 500 MM 20 IN SUB BASE PLENUM NOTE Vibration pads and fasteners are field supplied The following tables provide frame size and model details for the 500 mm 20 in sub base for piping Type of Frame Net Weight Sub Base Model Color Size Dimensions mm in kg Ib ACSB76180 Blue 3 500 1 000 740 41 ACSB76181 White 19 69 39 37 29 13 90 38 5 76182 Gray ACSB76183 Black ACSB76184 Blue 4 500 1 300 855 53 ACSB76185 White 19 69 51 18 33 66 116 86 5 76186 Gray ACSB76187 Black Uniflair sub base ACSB76188 Blue 5 500 1710 855 62 500 mm ACSB76189 White 19 69 67 32 33 66 136 687 20 in no ACSB76190 Gray grille ACSB76191 Black ACSB76192 Blue 6 500 2 160 855 77 ACSB76193 White 19 69 85 04 33 66 169 76 ACSB76194 Gray ACSB76195 Black ACSB76196 Blue 7 500 2572 855 90 ACSB76197 White 19 69 101 26 33 66 198 42 ACSB76198 Gray ACSB76199 Black Uniflair LE Accessories Manual 19 20 Sub Base Front Supply w Grille M8 FASTENERS 500 MM 20 IN SUB BASE ecpspeu Uniflair LE Accessories Manual 20 NOTE Vibration pads and fasteners are field suppli
24. 58 Uniflair LE Accessories Manual Power Details Description Maximum Power Input 11 5 VA Maximum length of 500 m 1640 ft with single wire cable and double wiring from sensor to insulation SAS module Length of tape sensor 25 82 ft Diameter of stainless 0 6 mm 0 24 steel wiring for tape sensor Configuration Using the LED display Turn on the power to the unit and wait for the main screen to appear on the display Press Prg Select SERVICE MENU then press ENTER Enter the password PON NOTE The password is found inside the envelope attached to the manual If the password has been changed enter the new password instead Press ENTER Select HARDWARE SETTINGS then press ENTER Navigate to DIGITAL INPUT 2 CONFIGURATION Check to ensure that the existing setting is not used If this does not correspond to your settings whatever function is currently attributed to that digital input of the control will be lost at the end of this procedure and replaced with the one relative to the operation of the flooding detector 9 Press ENTER until the flashing cursor stops under NOT USED 10 Navigate to FLOODING SENSOR appears on the display 11 Press ENTER 12 To exit press the ESC key and navigate to the main screen 13 Test the accessory to ensure proper function The alarm will trip when 24 V signal is received due to water presence Additional Settings 1 Und
25. 70 916 4 ACFS76067 457 18 67 32 33 66 69 69 36 06 ACFS76072 610 24 ACFS76077 914 36 Uniflair LE Accessories Manual 10 Model Frame Dimensions mm in Number of Size 8 fasteners A B ACFS76063 6 305 12 2 160 855 2221 916 6 ACFS76068 457 18 85 04 33 66 87 44 36 06 576073 610 24 ACFS76078 914 36 ACFS76064 7 305 12 2572 855 2 631 916 8 ACFS76069 457 18 101 26 33 66 103 58 36 06 ACFS76074 610 24 ACFS76079 914 36 Seismic analysis of Uniflair floor stands A structural analysis model was created for each of the frames for the Uniflair seismic floor stands to verify that the frames are adequate for the highest seismic forces Sps 2 5g The reactions from the analyses were used to calculate the maximum Sps of the frame base assemblies For each frame type the baseplate welded bolt and nut welds and anchorage to the structure were evaluated to determine the maximum 505 of the base assembly The anchorage of the baseplate to the structure was assumed to be 2 5 HILTI Kwikbolt TZ expansion anchors with 2 embedment into a 4 in thick normal weight concrete slab with the strength of fc 4000 psi using the attached base plate The results of the analysis are provided in the following table Model 508 of Frame Sos of Base Assembly ACFS76060 ACFS76065 2 5 9 2 59 76070 760
26. 75 ACFS76061 ACFS76066 2 59 2 59 76071 76076 ACFS76062 ACFS76067 2 5g 2 5g ACFS76072 ACFS76077 ACFS76063 ACFS76068 2 5g 2 5g ACFS76073 ACFS76078 ACFS76064 ACFS76069 2 5g 2 5g ACFS76074 ACFS76079 Uniflair LE Accessories Manual Uniflair Plenums AWARNING HEAVY EQUIPMENT Use at least two people when handling and installing this equipment Failure to follow these instructions can result in death serious injury or equipment damage CAUTION TIP HAZARD The equipment is heavy and can easily be tipped For safety purposes adequate personnel must be present when moving this equipment Failure to follow these instructions can result in injury or equipment damage 20 in Return Plenum Non Stackable 4537 Uniflair LE Accessories Manual 11 NOTE Fasteners are field supplied na4693a The following table provides frame size and model details for the Uniflair plenums Type of Model Color Frame Dimensions mm in Net Weight Plenum Size A B kg Ib ACPL75110 Blue 3 500 1 010 750 37 00 ACPL75130 White 19 69 39 76 29 53 81 57 ACPL75131 Gray ACPL75132 Black ACPL75111 Blue 4 500 1 310 865 45 00 ACPL75133 White 19 69 51 57 34 06 99 21 ACPL75134 Gray ACPL75135 Black ACPL75112 Blue 5 500 1 720 865 53 50 Top ACPL75136 White
27. 8 The following diagram displays typical connection layouts Terminate the line with the provided 10 resistor see the graphic below at the end of the tape spot sensor chain NOTE The resistor is located on the back of the detector 10 kOhm RESISTOR 2 Module CAREL CAREL CAREL CAREL _CAREL CAREL 25 CAREL CAREL O NOTE There is no limit to the number of spot sensors that can be installed The maximum wiring distance is 487 m 1600 ft 9 After layout is complete and the 10 kOhm resistor is attached wire the sensor s back to terminals 3 and 4 of the SAS module inside the unit Q ee na4684a TIPS 10kOhm resistor is taped on back of SAS module The alarm is activated by the presence of water or the condensate pump alarm contact The alarm will only cause the unit to switch off if it has been chosen as a second level alarm The alarm can be configured to activate the standby unit in a group This is set under Rotational Standby Alarms LED status lights Condition Description Green Power supply present Yellow Sensor s not connected to the SAS module or line not terminated with the 10 kOhm resistor Red Water present alarm Additional installation details Power Details Description Power Supply 24 V 10 50 60Hz
28. CV 4500 5000 Installation Manual Uniflair LE DX Installation Manual 6 Uniflair LE Accessories Manual Uniflair Floorstands AWARNING HAZARD FROM MOVING PARTS Keep hands clothing and jewelry away from moving parts Check the equipment for foreign objects before closing the doors and starting the equipment Failure to follow these instructions can result in death serious injury or equipment damage CAUTION DAMAGE TO EQUIPMENT OR PERSONNEL The equipment is heavy and can easily be tipped For safety purposes adequate personnel must be present when moving this equipment Failure to follow these instructions can result in injury or equipment damage 36 in Welded Frame 8 mE FASTENER SEAL na4723a Uniflair LE Accessories Manual NOTE For installation a raised floor install a flexible seal field supplied at least 5 59 0 2 in thick between the raised floor and frame NOTE Rubber vibration isolation pads are field supplied na4682a The following table provides frame size model and fastener details for the 36 in welded frame Model Frame Dimensions mm in Number of Size M8 fasteners A B ACFS76055 3 914 1 000 740 1077 817 4 36 39 37 29 13 42 40 32 17 ACFS76056 4 914 1 300 855 1377 932 4
29. FORMATION OR BUSINESS INTERRUPTION RESULTING FROM ARISING OUT OR IN CONNECTION WITH THE USE OF OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT EVEN IF SCHNEIDER ELECTRIC IT CORPORATION HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES SCHNEIDER ELECTRIC IT CORPORATION RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE Copyright intellectual and all other proprietary rights in the content including but not limited to software audio video text and photographs rests with Schneider Electric IT Corporation or its licensors All rights in the content not expressly granted herein are reserved No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information This Publication shall not be for resale in whole or in part Table of Contents raTa LE eee 5 Important Safety 5 General esit 6 o tius ter es e 6 Companion 5 6 Uniflair FIOOESUIICIS p tcp cre eicit 7 Frames ss eq eus sana shia dda 7 12 18 24 36 in Seismic Frame 9 11
30. Installation Manual Uniflair LE Accessories 990 5565 001 Publication Date May 2014 chneider Electric Schneider Electric IT Corporation Legal Disclaimer The information presented in this manual is not warranted by the Schneider Electric IT Corporation to be authoritative error free or complete This publication is not meant to be a substitute for a detailed operational and site specific development plan Therefore Schneider Electric IT Corporation assumes no liability for damages violations of codes improper installation system failures or any other problems that could arise based on the use of this Publication The information contained in this Publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction This Publication has been compiled in good faith by Schneider Electric IT Corporation However no representation is made or warranty given either express or implied as to the completeness or accuracy of the information this Publication contains IN NO EVENT SHALL SCHNEIDER ELECTRIC IT CORPORATION OR ANY PARENT AFFILIATE OR SUBSIDIARY COMPANY OF SCHNEIDER ELECTRIC IT CORPORATION OR THEIR RESPECTIVE OFFICERS DIRECTORS OR EMPLOYEES BE LIABLE FOR ANY DIRECT INDIRECT CONSEQUENTIAL PUNITIVE SPECIAL OR INCIDENTAL DAMAGES INCLUDING WITHOUT LIMITATION DAMAGES FOR LOSS OF BUSINESS CONTRACT REVENUE DATA IN
31. Manual MODEL TD UCV 1000 4300 o PANEL MODEL TD UCV 1000 0700 47 48 na4823a PANEL na4818a PANEL eeseleese CNV1 SAS eseejesee RFF MODEL TD UAV 0921 1822 TD UWV 0921 1822 TD UEV 0921 1822 TD UDV 0921 1822 TD UTV 0921 1822 MODEL TD UAV 2242 3342 TD UWV 2242 2842 TD UEV 2242 2842 TD UDV 2242 2842 TD UTV 2242 2842 Uniflair LE Accessories Manual 4824 2 Attach the relay socked and terminal blocks to the DIN 4651 Uniflair LE Accessories Manual PANEL MODEL TD UAV 0511 0611 TD UWV 0511 0611 TD UEV 0511 0611 TD UDV 0511 0611 TD UTV 0511 0611 49 3 Connect wire 20 and 52 on the labeled terminal blocks inside 000000 the electrical box Wire routing be needed some units 4 Connect the customer external wiring to terminal blocks 026 and 006 NOTE This requires an external 24 V signal DC or AC 20 52 Configuration Using the standard LED display 1 Turn on the power to the un
32. Manual Select Configuration from the menu the left of the screen Select the Network tab Enter the IP Address example 10 0 8 56 If using DHCP leave blank or enter DHCP Enter the NetMask example 255 255 0 0 If using DHCP leave blank or enter DHCP 8 Click Submit Assigning a system location To assign a name to the machine where the pCOWeb is installed select the SNMP tab Enter the System name gx NL Enter the System location 4 Click Submit Accessing the user memory The pCOWeb features an FTP server used to access the user memory and load or retrieve files for example custom HTML pages To use this function the PC needs an FTP client installed FileZilla http filezilla project org is used as an example in the following procedure the procedure is similar for other FTP software 1 Use the following parameters to connect to the pCOWeb a Host 172 16 0 1 b Username httpadmin c Password fhttpadmin 2 Click Quickconnect 3 Under Local site locate the appropriate directory on either the CD or local hard drive Supervisory_Systems pCOWeb pCOWeb_HTML_Pages CCU Select the appropriate sub directory depending on the unit size and cooling type a Leonardo Max Cabinet Size 7 CW_Imperial Meas Chilled Water DX Imperial Meas Air or Glycol Cooled DX ES TC Imperial Meas Energy Saving or Twin Cool b Leonardo Evolution C
33. NG SCREW XLI 4 Attach the electrical wires to the 24 V AC power terminals provided in the terminal block of the Uniflair CW unit WIRES FROM THE UNIT TYPICAL 24 V CONNECTION IN UNIT 5 TERMINAL BLOCK 25 TERMINAL BLOCK 05 Configuration From the display interface put the unit in stand by mode and wait for the fans to stop From the main screen press the Prg key select SERVICE MENU and press Enter to confirm Type in the Service Password see the envelope attached to the manual and press Enter to confirm Select Hardware Settings and press Enter to confirm Navigate to the parameter settings screen and begin configuration Evaporating fan Fan Supply Fan power supply Monophase Triphase 3ph Modulation with air pressure enabled Fan modulation activated by the air pressure transducer Modulation with Air Air pressure transducer Y transducer and AFPS kit is installed in the unit N units in LAN network transducer is not installed but modulation is activated EVAPORATING FAN Fan Supply 3ph Modulation with air pressure enabled Y Y Air press transducer Y N 66 Uniflair LE Accessories Manual Transducer Range Begin The starting value of the transducer Range End Ending value of the transducer Read Value The reading taken by the sensor Delta Maximum variation without activating the filt
34. Recalling the factory configuration factory boot switch mode The pCOnet card comes with user parameters set to factory configuration values See Using the pCOnet parameters on page 87 for factory values In the factory boot switch mode pCOnet does not save the recalled values When restarted without pressing the button the pCOnet card again loads the user settings The following procedure sets the default pCOnet parameters 1 Switch the pCOnet controller on with the pCOnet board inserted by pressing and holding the button for at least 20 seconds The red status LED flashes slowly three times 2 After three red flashes on the LED release the button The LED turns green The LED then confirms recognition of the button by flashing three times red off and then returns to green Complete start up of the pCOnet controller takes another 40 seconds and the RS485 LED starts flashing At this point pCOnet controller be accessed via a remote connection Additional documentation Additional documentation relating to the pCOnet BACnetZE protocol PICS Protocol Implementation Conformance Statement and the BACset configuration tool are available at http ksa carel com Configuring pCOnet parameters This section provides procedures to configure the pCOnet parameters for correct communication over an MS TP network 1 Connect to pCOnet via a RS485 connection to a computer During configuration the Carel product code CVSTDUMORO for USB por
35. Values Mean Values Fan speed modulation is controlled by the average pressure reading taken by the sensors on the units connected on a local network LAN SETTINGS Temp Hum Control Mode Local Values Air Pressure Control Mode Mean Values After setting the parameters navigate to the main screen To save the data that has been entered restart the unit Repeat steps 1 7 for each unit go m 20900 To exit press the ESC key and navigate to the main screen NOTE Fan speed modulation settings can be determined through sensor reading of the unit or by calculating the average reading of all units on the LAN Configuring the LAN settings using the touchscreen Path gt Configuration gt Unit gt Airflow gt Group 1 Turn on the power to the unit and wait for the touchscreen to display NOTE Settings may appear on a different screen 2 Press Number of LAN Units 3 Press Yes to enter your credentials 4 Enter your credentials and begin configuration Number of LAN Units Enter the number of units on the LAN Number of Standby Units Enter the number of units in standby Sensor Values Used Enter the number of sensor values used Delta Temperature for Automatic Changeover Enter the temperature Delta Temperature to Switch to Local Control Enter the temperature Unit Rotation Time Enter the required number of hours Automatically Switchover to Standby Unit Set as required Rotate to Standby Unit Only on Alarm S
36. XPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury Electrical damage on the electronic components usually occurs because of electrostatic discharges caused by operator improper handling When handling these components take the following precautions Before handling any electronic component or card ground the card The components must be kept inside their original package as long as possible If necessary take the main board from a package and put it into an anti static package without touching both sides of the board with your hands Avoid non anti static plastic bags and polystyrene Avoid handing a card from one operator to another to avoid any electrostatic induction and discharges Inventory Item Description Quantity PCOS004850 serial card 1 Uniflair LE Accessories Manual 89 The 5004850 is an optional communication card for the pCO series controls which allows you to directly interface the pCO to a RS485 supervisory network The card ensures the controller communicates with the RS485 serial network The maximum baud rate is of 19200 baud This is set using the software Installing 1 Disconnect the power 2
37. abinet Size 3 6 CW Imperial Meas Chilled Water DX Imperial Meas Air or Glycol Cooled DX ES TC Imperial Meas Energy Saving or Twin Cool 4 Highlight all of the files and folders in the appropriate directory and drag and drop them into the usr local root flash http directory of the pCOWeb card Uniflair LE Accessories Manual 77 NOTE Some FTP clients do not use the request from pCOWeb to open the user memory for httpadmin usr local root flash http instead they show the contents of the root position The user needs to manually go to usr local root flash http Filesize Filetype Lastmodified File Folder 1 1 2011 12 00 File Folder 1 1 2011 12 44 File Folder 1 1 2011 12 00 File Folder 1 1 2011 12 01 File Folder 1 1 2011 12 00 File Folder 1 1 2011 12 01 13 989 Firefox Doc 1 1 2011 12 20 645 FirefoxDoc 1 1 2011 12 20 5 286 Firefox Doc 1 1 2011 12 20 4 617 FirefoxDoc 1 1 2011 12 20 862 FirefoxDoc 1 1 2011 12 20 1 059 Firefox 1 1 2011 17 20 5 If there are existing files on the pCOWeb card you will be prompted to overwrite the existing files Select OK to overwrite 6 Close FileZilla after the file transfer is complete Accessing custom HTML pages Open Internet Explorer and go to address 172 16 0 1 A personalized page appears on the screen depending on the type of selected unit AB 10 0 8 56 hen PCOWEB Schnei
38. anced The Proxy Settings window displays In the Exceptions field enter the address chosen for communication with pCOWeb for example http 10 0 8 56 5 Click OK to apply the changes and close the window Click OK to close the remaining open windows Uniflair LE Accessories Manual 79 LON NETWORK 10000 0 LonWorks pCO system serial card 76124 NOTE All LON cards are programed at the factory Electrical damage on the electronic components usually occurs because of electrostatic discharges caused by operator improper handling When handling these components take the following precautions Before handling any electronic component or card ground the card Keep the components inside their original package as long as possible If necessary take the main board from a package and put it into an anti static package without touching both sides of the board with your hands Avoid plastic bags and polystyrene Avoid handing a card from one operator to another to minimize electrostatic induction and discharges 10000 0 and 10001 0 cards are used with the pCO electronic controller interface and the LonWorks TP FT 10 network Inventory Item Description Quantity 10000 0 1 Installation DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be perfor
39. ata between Internet Intranet is only enabled for some devices and types of communication These decisions are defined by the network administrator pCOWEB BUILDING PERSONAL COMPUTER PERSONAL COMPUTER SS INTERNET CONNECTION N SERVER NJ SWITCH LAN LOCAL AREA NETWORK OR INTRANET DATA NETWORK ETHERNET TYPE Uniflair LE Accessories Manual 71 Inventory na4563a Item Description Quantity Network controller card 1 Cover 1 Label that includes the required Media Access Control MAC address Remove 1 one of these labels before installing to access the required MAC address Installing the pCOWeb card A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury Each pCOWeb is uniquely distinguished by its own Media Access Control MAC address The network administrator may need to check the MAC address of each pCOWeb installed The MAC address is shown on the label applied to the connector and on the two labels included the packaging Once installed the pCOWeb label may no longer be accessible During installation use scissors to separate the two labels
40. der Simutat L Ufficio tecnico STATUS PARAMETERS System On Fan g Cool Set Point C 230 Compressor 1 g R Cool Diff 15 Compressor 2 Heat Set Point C 230 Compressor 3 i e Heat 2 15 Dehumid SetP rH 55 Clear Heating 1 fo fo e e e HIHIHIHIHIE Heating 2 Deh Prop Band rH 5 e o Compressor4 Dehumidification Hum Setpoint rH 45 Chenge Web Administrator reserved area Humidification Hum Prop Band rH9o 5 Change Geer General Alarm e Room 26 7 Room R Humid rH 46 8 Cold water Valve 100 0 ALARMS 1 Reset Clogged Filter Alarm 6 To reset press the button The page features a photo on the left hand side of the selected unit A Status column indicates the operation mode on a Web page Green indicates operational status Gray indicates the item is not being used In the event of an alarm state a red indicator illuminates if unit has a cold water valve the opening value of the valve itself is also shown An Alarms column indicates the description of any alarms that may be present It should be noted that in order to reset the alarms it is necessary to click RESET A Parameters column indicates the setpoints and the relative differentials of the various parameters and the possibility of modifying them Resetting the system after cu
41. detector SAS module N A 1 Water leak detecting strip 25 82 ft ACAC76118 1 Spot water detector ACAC76119 1 10kOhm resistor N A 1 Note Taped to the back of the spot water detector Installation A A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury 1 Locate the correct unit type from the diagrams below to find the installation location of the SAS module in the electrical panel The following diagrams provide models and SAS module location Uniflair LE Accessories Manual 51 52 4825 4824 PANEL MODEL TD UCV1000 TD UCV1200 TD UCV1700 TD UCV2500 TD UCV3400 TD UCV4000 TDCV 4300 MODEL TD UCV0700 Uniflair LE Accessories Manual 4825 na4823a eese eese CNV1 SAS RFF Uniflair LE Accessories Manual MODEL TD UAV 0921 1822 TD UWV 0921 1822 TD UEV 0921 1822 TD UDV 0921 1822 TD UTV 0921 1822 MODEL TD UAV 2242 3342 TD UWV 2242 2842 TD UEV 2242 2842 TD UDV 2242 2842 TD UTV 2242
42. directly Alway connect to a terminal block in the main electrical box or in the condensate pump electrical box Electrical connections to Chilled Water units 1 Disconnect power to the unit 2 The following electrical diagrams provides connection details to connect the condensate pump to the Uniflair unit for CW TD UCV models Use terminal blocks 20 and 51 Uniflair LE Accessories Manual 33 34 1 19 gt 20 e Y 20 9 TERMINAL BLOCKS 20 S Nn gt AND 51 PFS 60 5 230 9 9 8 e O ID2 0104 0105 0101 0103 aan a A 3 Connect the pump high float switch that leads to Digital Input 2 on the Uniflair unit in series with leak detection if applicable A high water level condition in the pump reservoir causes a Flood Alarm on the Uniflair unit This alarm can be manually set to shutdown the unit if selected as a second level alarm The following provides details on configuring the condensate pump to CW TD UCV models for Digital Input 2 Use the following settings 4821 T User Remote ON OFF Flooding sensor 4 If removed replace the electrical component cover 5 Apply power to the unit The pump activates when the reservoir fills to the switch activation level Electrical connections to Direct Expansion and HDCV units 1 Disconnect power to the unit 2 The following electrical diagram pro
43. e AFPS controller to the mounting bracket using the four screws provided AFPS CONTROLLER na4759a 5 Replace the AFPS controller cover Installing the sensors Locate the mounting point for the sensor head on the wall and route the tubing through the bottom of 1 the unit and underneath the floor tiles to this location Uniflair LE Accessories Manual 63 64 NOTE Do not place the positive pressure sensor head under the raised floor where the airflow velocity is high For example directly beneath the unit The recommended position for the pressure sensor head is 3 4 m 10 13 ft away from the unit 2 Fasten the mounting clamp to a raised floor post 3 Ensure that excess tubing is carefully secured Avoid sharp bends or kinks in the tubing SENSOR HEAD CLAMPS ON RAISED POST The above floor pressure sensor can be installed in the port located at the bottom right corner of the Uniflair unit 1 Using a standard screwdriver pry off the cover on the sensor port 2 Route the tubing through the cooling unit neatly coiling any excess tubing 3 From inside the unit attach the sensor head to the port then fasten the fitting into the port from outside the unit If the unit is not in the air conditioned room the tubing can be installed using the wall mounting bracket provided with the kit WARNING HAZARD TO EQUIPMENT OR PERSONNEL Verify that the area behind the wall is free of
44. e ied ab e e s 66 Configuring the LAN settings using the LED display 68 Configuring the LAN settings using the touchscreen 69 Communications Cards ip ee pCOWeb Network 76122 71 Configuration 3 4 22d 73 User interface buttons and LEDs 74 LED indicator lights 74 75 Setting the IP address subnet mask 75 C PIOXY 76 Activating factory network settings 76 Opening 76 Accessing the user memory 77 Accessing custom HTML pages 78 nucon Em 80 Installation uo nre eet xm De x pana 80 Connecting to the LonWorks network 81 Activating the service 82 Configuration 82 LON serial card LED light functionality 83 eee ERES pCOnet PCO1000BA0 ACAC76123 83 VEMO Ex 84 84 Configuration using the LED display 85 Configuration using the lt 85 Status ie esata ek aha dae RE EAT ERES 86
45. e pump is factory installed Internal wiring Powered internally by the unit The pump is shipped loose from the factory Pump Model SKU Voltage Wiring CW TD UCV DX HDCV A5X 3AP 230 76129 230 External Wiring 230 V Internal Wiring Installed A5X 3AP 460 ACAC76136 460 575 External Wiring 460 V Internal Wiring Installed Installation A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury 1 Unpack and inspect the pump If damage is observed call Schneider Electric Technical Support They will assist with repair or replacement 2 Disconnect the electrical power at the power source fuse box circuit breaker etc before wiring the pump or connecting the electrical cord Plumbing connections 1 Position the pump so the inlet is close to and below the drain line NOTE The pump must be level Uniflair LE Accessories Manual 31 2 Install flexible tubing or pipe from the pump to the drain inlet hole Make sure the pipe does not interfere with the float IMPORTANT Ens
46. ed The following table provides frame size model and na4697a fastener details for the 20 in sub base for piping front supply w grille Type of Model Color Frame Dimensions mm Net Weight Number of Sub Base Size kg Ib M8 fasteners ACSB76165 White 3 500 1000 740 38 00 4 ACSB76166 Gray 19 69 39 37 29 13 183 78 ACSB76167 Black ACSB 108 wmo 4 S00 1300 as sooo 4 ACSB76169 Gray 19 69 51 18 33 66 110 20 ACSB76170 Black Sub base ACSB76147 Blue 5 500 aan m 1 plenum ACSB76171 White 500 mm ACSB76172 Gray 19 69 67 32 33 66 130 10 20 in ACSB76173 Black front supply 05876174 whe S00 2160 ss 7400 ACSB76175 Gray 19 69 85 04 33 66 163 10 ACSB76176 Black 08876149 Blue 7 soo 2572 855 8700 ACSB76178 Gray 19 69 101 26 33 66 191 80 ACSB76179 Black Uniflair LE Accessories Manual 21 Damper Utilization AWARNING HEAVY EQUIPMENT Use at least two people when handling and installing this equipment Failure to follow these instructions can result in death serious injury or equipment damage ACAUTION TIP HAZARD The equipment is heavy and can easily be tipped For safety purposes adequate personnel must be present when moving this equipment Failure to follow these instructions can result in injury or eq
47. eider Electric All Rights Reserved Uniflair and the Schneider Electric logo are trademarks owned by Schneider Electric Industries SAS S A S or its affiliated companies All other trademarks are the property of their respective owners 990 5565 001 5 2014
48. electrical wires or piping before drilling holes into the wall Failure to follow these instructions can result in death serious injury or equipment damage 1 After determining an appropriate location for the sensor drill a hole through the wall and mount the sensor bracket 2 Tubing can be installed behind the wall and through the hole then attached to the sensor Uniflair LE Accessories Manual NOTE Ensure that the wall mounted sensor is installed away from direct airflow to ensure proper pressurization detection tLAN connection 1 Using a screwdriver remove the analog selection cover on the controller inside the unit 3 Aligning the connector pins insert the card into the slot and push into place making sure the card is pushed against the two plastic supports on the case NOTICE UNPROTECTED OUTPUTS Be sure all pins on the circuit board are properly seated and not bent or touching other pins Failure to follow these instructions can result in equipment damage 4 Put the cover back on the controller and snap into place Supply power connections 1 Route the cables and supply power harness to the electrical panel 2 Connect J3 from the AFPS to the green connector on the tLAN card Uniflair LE Accessories Manual 65 3 Attach the grounding wire from the harness to the grounding screw the unit na4639a GROUNDI
49. er Time Duration of the filter Value Reading taken by the sensor AIR PRESS TRANSDUCER Range Begin Pa 000 0 Range End Pa 100 0 Read Value Pa 020 0 INPUT FILTER Delta Pa 4 0 Time 5 01 Value Pa 020 0 Evaporating fan speed Minimum speed Minimum evaporating fan speed during modulation Maximum speed Maximum evaporating fan speed during modulation EVAPORATING FAN REGULAT Minimum Speed 40 Maximum Speed 100 Evaporating fan regulation Setpoint The reference pressure value that needs to be maintained by the modulation of the fans Dead Band Dead band regulation Regul Band Proportional regulation band Integral Time integral time Derivat Time derivative time Air pressure the reading taken by the sensor Evaporating Fan evaporating fan regulation percentage EVAPORATING FAN REGUL Setpoint Pa 020 0 Dead Band Pa 000 0 Regul Band Pa 160 0 Integral Time s 040 Derivat Time s 000 Air Pressure Pa 020 0 Evaporating Fan 000 Alarm parameters Alarm Level Low air pressure alarm activation level Alarm Delay Low air pressure alarm activation delay time Uniflair LE Accessories Manual 67 EVAPORATING FAN REGUL Alarm Level Pa 015 0 Alarm Delay 5 060 6 To exit press the ESC key and navigate to the main screen Using the touchscreen Path Main gt Configuration gt Unit gt Airflow gt Group 1 Turn on the power to the unit and wait for the touchscreen to display NOTE Settings ma
50. er Hardware Settings select Flooding Alarm The Off setting on the alarm defaults to This indicates that the unit will not shutdown when the alarm activates 2 Change this setting to Y to enable an active leak flooding condensate alarm to shutdown the unit 3 By default Valve Closed on Al is set to N Selecting Y enables the water valve if applicable to close if the leak flooding condensate pump alarm is active Using the touchscreen Path gt Configuration gt Unit gt Digital Inputs 1 Turn on the power to the unit and wait for the touchscreen to display 2 Setthe following configurations Digital Input 4 Configuration Water Detection Sensors Digital Input 4 Function Alarm Signaling Digital Input 4 Normal State Normally Open 3 Press the Home button to return to the main screen Uniflair LE Accessories Manual 59 Automatic Floor Pressurization System Overview The Automatic Floor Pressurization System AFPS ACAC76128 maintains air pressure underneath a raised floor to a desired setpoint By modulating fan speed an AFPS kit for Uniflair Chilled Water CW units compensates for air pressure changes in an active and growing data center NOTE The AFPS is not recommended for Direct Expansion units The AFPS kit is supported by the following Uniflair CW models Inventory TDCV0700 TDCV3400 TDCV1000 TDCV4000 TDCV1200 TDCV4300 TDCV1700 HDCV4500 TDCV2500 HDCV5000
51. et as required Exclude from Rotation Set as required Switchover Mode Set as required Switchover On Power Loss Enable Number of Days Between Rotation Enter the number of required days between each rotation Hour of Rotation Enter the hour for the rotation to take place Minute of Rotation Enter the minute for the rotation to take place Uniflair LE Accessories Manual 69 70 Rotation Weekday Enter the required day 5 Press the Home button to return to the main screen Uniflair LE Accessories Manual Communications Cards The Carel pCOWeb controller provides slots for the following communications cards Slot Type SKU Part Protocol BMS2 SE N A N A Via TCP IP Modbus IP StruxureWare SNMP Touchscreen Web BMS1 Available N A N A N A TCP IP ACAC76122 N A Modbus IP StruxureWare SNMP pCOWeb BacNet IP LON 76124 0M 21AS104CDZ LONworks RS485 ACAC76123 0M 21AS102CDZ Modbus RS485 N A OM 21AS108CDZ Bacnet MS TP RS232 ACAC76125 0M 21AS106CDZ Modem NOTE Only one communications card can be installed on each pCO controller This does not apply to touchscreen communication card configurations TCP IP pCOWeb Network Card ACAC76122 The pCOWeb controller is connected to an internal network If suitably configured the PCs in the internal network communicate with pCOWeb using network language protocols included with pCOWeb In a network the exchange of d
52. h No Discharge Inspect the discharge tubing for its full length to make sure it is clear Check to ensure the tubing end is not clogged sure the check valve is not clogged If clogged unplug the pump remove the fitting and clean with mild soap or detergent The discharge port of the impeller chamber be clogged due to an accumulation of debris Uniflair LE Accessories Manual 37 Smoke and Fire Sensors Inventory na4633c Item Description Quantity Smoke sensor ACAC76115 1 Rubber grommet 2 Phillips screws 4 Washers 4 1 1 Fire sensor ACAC76116 Metal installation bracket 000000 NOTE Inspect for missing components If parts are missing contact Schneider Electric Technical Support Installation A A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury 1 Locate the installation location for the sensor based on the unit type and model The following graphics provide installation locations based on model number Uniflair LE Accessories Manual 39 40
53. he status of communication with the controller and the status of the pCOnet controller Starting sequences power up and restarting The starting sequence on power up or after restarting pCOnet controller provides the following sequence 1 Off for two seconds 2 Two seconds after restarting quick flash gt red gt green gt red gt green 3 Five seconds after restarting steady green Approximately 50 seconds after restarting communication begins The following table provides active alarm conditions and descriptions on the status LED Condition Description Quick green OFF green Indicates communication with the pCO controller is normal Slow red gt OFF gt r ed Indicates communication has not been established with the pCO controller Green gt red gt green Indicates that the pCOnet has detected an error or that there is a temporary lack of response from the pCO controller Once the starting sequence has been completed the Status LED flashes to indicate the quality of communication with the pCO controller RS485 LED The RS485 LED is located on the right side of the card and indicates the status of communication with the BACnet MS TP network RS485 and displays the following information For starting sequence on power up or after rebooting the pCOnet the RS485 LED switches in the following sequence 1 Off for approximately 50 seconds 2 Approximately 50 seconds after restarting the pCOnet controller a
54. isplays If using a proxy server click the Use a proxy server for your LAN check box Enter the Proxy Server Address and Port to be used To disable the proxy if required 1 2 3 Activating RON 3 Clear the Use a proxy server for your LAN check box Select OK to apply the changes and close the window Select OK to close the remaining open windows factory network settings Disconnect power to the pCOWeb controller Press and hold the button on the pCOWeb card and reconnect the power to the controller Continue to hold for 20 seconds until the Status LED flashes red Release the button before the Status LED flashes red three times After a total of three red flashes the LED will turn solid green After approximately one minute the Status LED blinks green At this point the pCOWeb card has rebooted to the factory settings Opening pCOWeb 1 2 3 NOTE card to On the PC open Internet Explorer Enter the address field including the dots 172 16 0 1 Press Enter The pCOWeb main page displays If the address is not found check the Status LED If solid green allow more time for the pCOWeb boot If blinking green repeat the Activating factory network settings on page 76 instructions Entering the IP Address NetMask 1 2 3 Select the Go to Administrator area link Enter the Default Username admin Enter the Default Password fadmin the Administrator Area displays Uniflair LE Accessories
55. it 2 Navigate to the Digital Input 4 Selection Screen 3 Change the setting to Smoke Fire Sensor 4 Test the smoke and fire alarms to ensure proper function 24 V CONNECTION Alarm will activate when the 24 V signal is received or lost FOR EXTERNAL depending on customer setup SYSTEM 20 32 Tips TY The relay is physically configurable between NC Normally Closed or NO Normally Open The relay is Normally Open by default The relay be installed in series with the internal smoke fire detection system Input 104 is the default Type alarm It also requires a MANUAL reset by default It is recommended to isolate ID4 as a B alarm for Smoke Fire Type B not available on models T EV0511 0611 The relay coil must be powered by an outside source customer supplied 24 V Fs RFF 26 06 na4819a Qo Using the touchscreen Path Main Configuration Unit Digital Inputs 1 Turn on the power to the unit and wait for the touchscreen to display 2 Setthe following configurations Digital Input 4 Configuration Smoke Fire Sensor Digital Input 4 Function Alarm Signaling Digital Input 4 Normal State Normally Open 3 Press the Home button to return to the main screen 50 Uniflair LE Accessories Manual Water Leak Detectors Inventory na4510a Item Description SKU Quantity Flooding sensor
56. llation location MOUNTING BRACKET RUBBER GROMMETS ACCESSORY BASE P d WASHERS SCREWS ACCESSORY HEADS Uniflair LE Accessories Manual UPC1s UPC1m VDC GND 104 FIRE SFFS000000 New Model SMOKE SFFS000000 New Model na4790a UPC1s UPC1m VDC GND 104 L xe 52 20 N iO N J FIRE OR SMOKE SFFS000000 or SFFS000000 NEW MODEL na4791a Uniflair LE Accessories Manual 43 The following graphic provides details to wire the smoke and fire detectors in 24 V series e 2226 i SFF amp RFF RFF 20 006 TAT X FIRE 412 gt 4 4 SFFF000000 412 SMOKE SFFS000000 WITH SMOKE AND FIRE ALARM 24VAX NO SMOKE AND FIRE ALARM OPTIONAL SMOKE FIRE DETECTOR CUSTOMER INTERFACE 26 06 26 06 na4803a 5 Locate the terminal connection harness near or close to the recommended installation location 6 Follow the wiring direction given in wiring diagrams above to match labeled connections wires not supplied 7 Once one or both sensors are wired to the terminal reattach the head of the sensor to the base by turning to the right Configuration Using the LED display 1 Turn on the power to the unit and wait for the main screen to appear on the display
57. may appear on a different screen 2 Enter your credentials and begin configuration 1 Serial Address Enter the required serial address BMS1 Serial Speed Enter the required serial speed 1 Serial Protocol Modem GSM Remote ON OFF Only Through Serial Communication Enable 3 Press the Home button to return to the main screen 94 Uniflair LE Accessories Manual Worldwide Customer Support Customer support for this or any other product is available at no charge in any of the following ways Visit the Schneider Electric Web site to access documents in the Schneider Electric Knowledge Base and to submit customer support requests www schneiderelectric com Corporate Headquarters Connect to localized Schneider Electric Web sites for specific countries each of which provides customer support information www schneiderelectric com support Global support searching Schneider Electric Knowledge Base and using e support Contact the Schneider Electric Customer Support Center by telephone or e mail Local country specific centers go to www schneiderelectric com Support Operations around the world for contact information For information on how to obtain local customer support contact the representative or other distributors from whom you purchased your product As standards specifications and designs change from time to time please ask for confirmation of the information given in this publication 2014 Schn
58. med by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury 80 Uniflair LE Accessories Manual 1 Disconnect the power 2 Using a screwdriver remove the plastic hatch from the electronic controller 4 Insert the pCOWeb card into the pCO controller and ensure it is fully seated Ensure that the board is properly fitted and rests against the two plastic supports on the pCO controller case 5 NOTE The insertion of the card and the fitting of the connectors may be difficult due to the space available and the location of the two plastic supports Insert the board obliquely and rotate until the connectors are fitted 6 Replace the hatch and line up the connector on the serial board with the hole made in the hatch 7 Connect the communication cable Connecting to the LonWorks network The connection to the LonWorks network is performed using the removable terminal connector present on the board Uniflair LE Accessories Manual 81 4778 20 0 78 Dimensions shown in mm in Item Description pCO connector Terminal block for LonWorks network GND A B Service pin to the board Red anomaly LED Green service that displays normal LED operation Activating the service pin To activate the service
59. nder most circumstances the pump requires little maintenance for efficient operation If a problem occurs check the following items or call Schneider Electrical Technical Support The following guidelines can help to return the pump to service Check inlet and outlet piping for blockage or kinks that inhibits flow Make sure the floats move freely Make sure the pump impeller casing is not clogged Make sure the check valve is not clogged Pump Does Not Run Check to see that the power to the system Uniflair unit is on to allow production of condensate Check that the pump is plugged in and the circuit is active fuse or breaker not blown Check the level of water in the reservoir The level must be within 50 8 mm 2 in of the reservoir top to activate the switch The inlet tube may be blocked and require cleaning if no water is entering the reservoir If there is a proper amount of water in the reservoir the float may be stuck due to dirt or algae formation Flush the reservoir with warm water and a mild soap or detergent Uniflair LE Accessories Manual NOTE In case of extreme algae formation unplug the pump and fill the reservoir with commercially available algaecide Follow the directions for destroying the algae After the proper waiting period dump the algaecide out of the reservoir Rinse with water repeat if necessary Be careful not to clog the check valve when starting the pump after cleaning Pump Motor Runs Wit
60. onnection signals regardless of whether the network parameters are correct This LED flashes green when transmitting data Condition Description Green steady Correct Ethernet data connection signals Green flashing Correct Ethernet data exchange Red No Ethernet signal detected Connecting to a PC To connect the pCOWeb cable to a PC connect the cable to the appropriate port Required equipment Computer with a Web browser for example Internet Explorer fitted with an Ethernet network interface pCOWeb card installed on the pCO controller Network cable Other requirements Turn off the power to the pCO controller PC Configuration NOTE It is necessary to have administrator status for your PC to deactivate the Windows firewall The PC communicates with pCOWeb if settings on both devices are configured correctly The pCOWeb default settings can only be changed once the connection has been established with the PC When first accessing the device the PC needs to be configured for adaption to the pCOWeb default settings Disable the firewall The firewall must be disabled to access pCOWeb mo Qm 5 On the Windows based PC select Start at the bottom left corner of the screen Select Control Panel The Control Panel window displays Select Windows Firewall The Windows Firewall window displays Select Off Select OK to apply the changes and close the window Setting the IP address and subne
61. rent screen 2 Enter your credentials and begin configuration 1 Serial Address 001 1 Serial Speed 19200 BMS1 Serial Protocol Standard Remote ON OFF Only Through Serial Communication Enable 3 Press the Home button to return to the main screen Uniflair LE Accessories Manual 73 User interface buttons and LEDs The pCOWeb features a push button and two indicator lights Status LED and Ethernet LED SELECTION PUSH BUTTON Item STATUS LED na4500a Description MAC ADDRESS ETHERNET LED Selection Push Button Used to select factory parameters or user parameters for network communication when starting the NOTE In normal operation pCOWeb reboots without disconnecting the power supply MAC Address Ethernet LED Status LED LED indicator lights 74 MAC addresses required for setup Ethernet LED light Status LED light Status LED This light displays the communication status of the pCOWeb card During normal operation the LED flashes green approximately three times a second In special circumstances it displays the operation of service activities This includes the restart of the internal program on the pCOWeb and remote updating of the program Condition Description Notes Green flashing 3 times sec Red flashing slowly once every two seconds Regular pCO pCOWeb communication pCO pCOWeb communication not established When running demanding
62. ries Manual 45 24 V Relay for External Smoke Fire Alarm Inventory Item Description Quantity Relay socket 1 24Vrelay coil 1 Terminal blocks 2 Installation A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury 1 Locate the mounting location based on the unit model The following graphics provide mounting locations 46 Uniflair LE Accessories Manual PANEL na4809a 5 5 RFF PANEL TAH PANEL S 5 E eesolocesooeso CNV2 SAS RFF 8 Uniflair LE Accessories
63. slow green red green red light displays and the BACnet MS TP network activates Status of communication with the BACnet MS TP network Once the starting sequence completes the RS485 LED flashes to indicate the quality of communication with the BACnet MS TP network The following table provides active alarms conditions and descriptions on the status LED Condition Description Green with occasional red flashes Communication is OK BACnet MS TP meaning green ON pCOnet keeps the Token control of the MS TP network green OFF pCOnet DOES NOT keep the Token red on Poll For Master search for a Master to pass the Token to 86 Uniflair LE Accessories Manual Green and red on together BACnet MS TP meaning continuous Poll For Master communication not established connection problems or no network device found this may depend on electrical connection difficulties or communication settings that are not compatible with the other network devices connected Using the push button The push button restarts the pCOnet controller and recalls the factory configuration Restarting the pCOnet controller With the board on and operating normally status LED flashing continuously hold the button between five and 10 seconds Approximately ten seconds after releasing the button the Status LED stops flashing Fifteen seconds later the pCOnet restarts and the Status LED quickly flashes red green red green
64. stomizing the HTML pages Go to the Web Administrator reserved area Enter the Default Username admin Enter the Default Password fadmin Select REBOOT on the left side of the screen moo mo 78 Uniflair LE Accessories Manual 5 Wait two minutes to allow the system to reboot Verifying setup 1 2 To check that the procedure has been carried out correctly enter the address 172 16 0 1 in the Internet Explorer browser Internet Explorer should not allow entry into the page Enter the new pCOWeb controller address The main start screen appears Returning to the initial configuration 1 2 3 4 Repeat steps one through seven of Setting the IP address and subnet mask on page 75 On the Internet Protocol TCP IP Properties window select Obtain an IP address automatically Click OK to apply the changes and close the window Click OK to close the remaining open windows The PC needs to be reset so that the network proxy device can be re used and it can answer to the IP address that was already set as well as the second IP address that is compatible for direct communication with the pCOWeb example http 10 0 8 56 Resetting the system after returning to the initial configuration 1 2 Repeat steps one through five of Setting the IP address and subnet mask page 75 On the Local Area Network LAN Settings window select Use a proxy server for your LAN check box Select Adv
65. supplied and apply one in an easily accessible position near the pCO controller on the electrical panel If more than one pCOWeb device is installed a map of the installation should be created applying the second label provided in the packaging onto the map for each pCOWeb corresponding to its physical position This provides the network administrator with the required documents on where the pCOWeb devices and corresponding MAC addresses are located 1 Disconnect the power supply to the pCOWeb controller 2 Using a screwdriver remove and recycle the plastic hatch from the electronic controller 72 Uniflair LE Accessories Manual 3 Insert the pCOWeb into the pCO controller and ensure it is fully seated na4787a 4 Secure pCOWeb card to the pCO controller with the supplied cover 5 Insert the Ethernet cable Configuration Using the LED display NOTE If installing multiple units on the network each unit needs a unique address to avoid conflicts Press the Prg on the display interface Select SETTINGS Enter the password Select SERIAL MODEM SETTINGS Enter the following Serial Address 001 Serial Speed 19200 Protocol Standard 6 To exit press the ESC key and navigate to the main screen Using the touchscreen Path Main gt Configuration gt Unit gt Communication 1 Turn on the power to the unit and wait for the touchscreen to display NOTE Settings may appear on a diffe
66. t mask The PC does not use DHCP and uses the IP address of 172 16 0 100 The Subnet mask field must also be set the Gateway is not required ov m Oo qe B On the Windows based PC select Start at the bottom left corner of the screen Select Control Panel The Control Panel window displays Select Network Connections The Network Connections window displays Select Local Area Connection The Local Area Connection Status window displays Select Properties The Local Area Connection Properties window displays Uniflair LE Accessories Manual 75 76 9 10 11 12 C Proxy If not already selected select the Internet Protocol TCP IP check box Select Properties The Internet Protocol TCP IP Properties window displays Select Use the following IP address Enter the IP address including the dots 172 16 0 100 Enter the Subnet mask including the dots 255 255 0 0 Select OK to apply the changes and close the window Select OK to close the remaining open windows The following procedure provides details on enabling and disabling the network device called the proxy for communication oar oN gt 7 On the Windows based PC select Start at the bottom left corner of the screen Select Control Panel The Control Panel window displays Select Internet Options The Internet Properties window displays Select the Connections tab Select LAN Settings The Local Area Network LAN Settings window d
67. tasks sending a large number of notifications this may be steady green for a few seconds Single red flash and then flashing green Steady red Single pCO pCOWeb communication error one failed response from the pCO or it is attempting to write a variable with an index higher than 207 Rescue mode After five failed responses the Status LED starts flashing red until communication resumes Off then green red repeated in rapid succession then green steady for 1 2 minutes Green steady for 1 2 minutes pCOWeb reboot phase pCOWeb reboot phase Wait for the conclusion of the reboot Red Off slow 1 second 1 second repeated 3 times Red Off fast 3 times a second repeated 3 times The recognition of a button pressed during reboot for selecting the factory parameters During reboot this confirms the selection of the factory parameters by pressing the button Release the button to confirm Green red repeated alternating once a second During a firmware update this shows the writing of block B to non volatile memory Do not interrupt the power supply Uniflair LE Accessories Manual Condition Description Notes Red steady followed by During a firmware update this shows Do not interrupt the power supply repeated green red the writing of block B to non volatile memory Ethernet LED Displays the status of the physical network connection Ethernet c
68. to the BACnet MS TP network Master Slave Token Pass Uniflair LE Accessories Manual 83 NOTE pCOnet is not compatible with the pCO series pCOnet that features Master Slave operation Inventory Item Description Quantity PCO1000BA0 interface board 1 Jumpers 3 Connector 1 Cover 1 Installation 1 Disconnect the power 2 Using a screwdriver remove the plastic hatch from the electronic controller 3 Insert the pCO net card in the plug in connector Ensure that the connector is inserted and in contact with the two supports on the pCO net card Due to limited space insert the pCO net card at an angle then tilt it back until the connectors line up 84 Uniflair LE Accessories Manual 4 Insert the required jumpers The following graphic provides jumper connection details e n EZ PS P2 P3 Le 9 ole lt lt lt lt 0 120 510 5Volt Jumpers P1 P2 P3 are located inside the front opening of the cover Jumper P1 adds a 510 ohm polarization resistance between the negative data line and GND Jumper P2 adds a 120 ohm terminal resistance between the two data lines and Jumper P3 adds a 510 ohm polarization resistance between the positive data line and the 5 internal voltage Insert all three jumpers on the unit at the start of the network and the unit at the end of the network Do not insert the jumpers on the intermediate
69. tput DO5 Output Contact N O 8 Press ENTER until the cursor is positioned on MOTORIZED DAMPER 9 Select Yes and press ENTER 10 damper default opening time 120 seconds Adjust if required 11 Press ENTER to move the cursor to the top left portion of the display 12 To exit press the ESC key and navigate to the main screen Using the touchscreen display Path Main gt Configuration gt Unit gt Digital Inputs 1 Turn on the power to the unit and wait for the touchscreen to display 2 Set the following configurations NOTE Settings may appear on a different screen Motorized Damper Enabled Motorized Damper Opening Time 120 seconds suggested setting Motorized Damper Output Contract Normal State Normally Open 3 Press the Home button to return to the main screen Use the direction reversal selector located on the servomotor if the rotation is incorrect DIRECTION REVERSAL SELECTOR na4652a 26 Uniflair LE Accessories Manual Gravity Damper AWARNING HEAVY EQUIPMENT Use at least two people when handling and installing this equipment Failure to follow these instructions can result in death serious injury or equipment damage ACAUTION TIP HAZARD The equipment is heavy and can easily be tipped For safety purposes adequate personnel must be present when moving this equipment Failure to follow these instructions can result in injury or equipment damage Inventory
70. ts can be used USB converters should not be used in the installation due to the large volume of data transmitted across a complex BACnet network 2 Install the Carel BACset configuration tool available at http ksa carel com NOTE If the values of the pCOnet parameters are not suitable communication with BACset may not be possible To connect to pCOnet restart the pCOnet controller using the factory boot switch mode Using the pCOnet parameters The following table and definitions provides details on parameter usage Parameter Min Max Factory Device instance 0 4194303 77000 Station Address 0 127 0 MaxMaster 0 127 127 Max Info Frames 0 255 20 BaudRate 9600 19200 38400 76800 38400 Uniflair LE Accessories Manual 87 88 Device Instance The number that uniquely identifies a device inside the network the BACnetAEE network can also include non MS TP BACnet E devices If two units have the same Device Instance identification errors will be generated Station Address The number that differentiates the units the BACnet4EE MS TP network If two units have the same Station Address identification errors will be generated To speed up the data exchange between the Master units the Station Address of the Master units should start from 0 and continue without skipping any numbers Max Info Frames This establishes the maximum number of information packages exchanged When this number is exceeded the Master
71. uipment damage Overview Schneider Electric offers the following types of dampers Motorized Damper Gravity Damper Dampers are factory installed on top of the unit NOTE Dampers can be field installed by special order Contact a Schneider Electric representative for details Air Flow Directions Air Flow Damper Type Downflow Motorized Upflow Gravity motorized Motorized Damper Inventory Item Description Quantity damper plenum 1 Uniflair LE Accessories Manual 23 Item Description Damper motor Damper Installation M4 FASTENER na4811a Configuration 24 Quantity 1 A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Do not wear jewelry when working with electrical equipment Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Failure to follow these instructions will result in death or serious injury Uniflair LE Accessories Manual 1 Turn power to the unit 2 The following electrical diagrams provide SKU and wiring details to wire the damper to Uniflair Chilled Water and Direct Expansion units
72. units NOTE If the device used to read the data from the 485 network is grounded and the RS232 RS485 converter or the RS485 serial port on the device have functional insulation of less than 2kV the connector GO on the pCO board must be grounded The board cannot be installed in direct contact with the metal panel on the electrical panel 5 Connect the communication cable Wind the cord around a ferrite core field supplied 6 Replace the cover supplied with the pCOnet controller Configuration using the LED display NOTE If installing multiple units on the network each unit requires a unique address to avoid conflicts Press Prg on the display interface Select SETTINGS Enter the password Select SERIAL MODEM SETTINGS Enter the following Serial Address ak WN gt Serial Speed Protocol STANDARD 6 Navigate to the main screen Configuration using the touchscreen Path Main gt Configuration gt Unit gt Communication 1 Turn on the power to the unit and wait for the touchscreen to display Uniflair LE Accessories Manual 85 NOTE Settings may appear a different screen 2 Enter your credentials and begin configuration BMS1 Serial Address Enter the required address BMS1 Serial Speed Enter the required serial speed BMS1 Serial Protocol Modbus Remote ON OFF Only Through Serial Communication Enable 3 Press the Home button to return to the main screen Status LED The Status LED left indicates t
73. until FLOODING SENSOR appears on the display 10 Press ENTER 11 To exit press the ESC key and navigate to the main screen Uniflair LE Accessories Manual 35 Using the touchscreen display Path Main gt Configuration gt Unit gt Digital Inputs 1 Turn power on to the unit on and wait for the touchscreen to display 2 Set the following configurations NOTE Settings may appear on a different screen Digital Input Two Configuration Water Detection Sensors Digital Input 2 Function Alarm Signaling Digital Input 2 Normal State Normally Open 3 Press the Home button to return to the main screen Pump test 1 Remove the inlet tubing from the pump 2 Pour water into the inlet until the pump turns on 4 The pump will evacuate water then turn off It will leave about 19 mm 3 4 in of water in the tank after pump out is complete Reconnect the inlet tubing to the pump Operation After proper installation the operation of the Uniflair condensate pump is automatic Troubleshooting 36 A A DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury U
74. ure a downward slope of the line in order to provide proper gravity drainage into the pump Wiring connections DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying this equipment before working on the equipment All electrical work must be performed by licensed electricians Practice Lockout Tagout procedures Do not wear jewelry when working with electrical equipment Failure to follow these instructions will result in death or serious injury IMPORTANT Connection to an intermittent power source will not allow for proper pump operation NOTE The routing of wires inside the pump is critical Keep all wires inside the pumps electrical enclosure clear of floats and switch actuation arms 32 Uniflair LE Accessories Manual The following diagram provides a general diagram of wiring to the pump motor to the unit This diagram is also located inside the cover of the pump For the DX units a junction box is provided to wire the cooling unit to the motor PURPLE PURPLE CAPACITOR BLACK AUX SWITCH GREEN GND GRN YEL 5 GREEN GND 2 GRN YEL 2 BROWN ek BROWN L1 BROWN L2 BLUE na4681a MAIN FLOAT SWITCH NOTE Make certain that the line voltage corresponds to the voltage specified on the pump motor nameplate For proper installation connect the pump to a constant source of power NOTE Never connect to Digital Input 2
75. vides details of connecting the condensate pump to the Uniflair unit Use terminal blocks 720 and 730 Uniflair LE Accessories Manual CONDENSATE DRAIN FLOODING DETECTORS STANDARD FACTORY PUMP ALARM CONTACT CONDENSATE DRAIN PUMP INSTALLATION TERMINAL TERMINAL BLOCKS BLOCKS 720 AND 720 AND 730 730 SAS RED 20 RED 20 RED 0 RED 0 RED 720 RED 720 RED 720 JUMPER RED 51 JUMPER RED 51 JUMPER RED 51 3 Connect the pump high float switch that leads to Digital Input 2 on the Uniflair unit in series with leak detection if applicable A high water level condition in the pump reservoir causes a Flood Alarm on the Uniflair unit This alarm can be manually set to shutdown the unit if selected as a second level alarm 4 If removed replace the electrical component cover 5 Apply power to the unit The pump activates when the reservoir fills to the switch activation level Configuration Using the LED display 1 Turn on power to the unit and wait for the main screen to appear on the display 2 Press Prg 3 Select SERVICE MENU then press ENTER NOTE The password is found inside the envelope attached to the manual If the password has been changed enter the new password Press ENTER Select HARDWARE SETTINGS and press ENTER Navigate to DIGITAL INPUT 2 CONFIGURATION Check to ensure the existing setting is not used Press ENTER until the cursor stops under NOT USED 9 Press UP or DOWN
76. y appear on a different screen 2 Press Fan Controlled by AFPS 3 Press Yes to enter your credentials 4 Enter your credentials and begin configuration Fan Controlled by AFPS Present Fan AFPS on Unit Present AFPS Setpoint 20 AFPS Low Air Pressure Threshold 15 AFPS Max Fan Speed 100 AFPS Min Fan Speed CW 40 Fan AFPS Control Type Advanced AFPS Deadband 100 AFPS Regulation Band 160 Air Pressure Transducer Input Filter Time 1 AFPS Sensor Min 0 AFPS Sensor Max 100 AFPS Sensor Input Filter Value 0 AFPS Sensor Input Filter Delta Threshold 4 AFPS Integral Time 40 AFPS Derivative Time 0 Fan Speed Derivative Time using AFPS 0 Fan Speed Integral Time using AFPS 40 5 Press the Home button to return to the main screen Configuring the LAN settings using the LED display 1 From the main screen press the Prg key select Settings Menu and press Enter to confirm NOTE The password is found inside the envelope attached to the manual If the password has been changed enter the new password instead 2 Enter the password 3 Select LAN Settings and press Enter to confirm 4 Navigate to the Parameters Setting screen The following provides settings for air pressure control 68 Uniflair LE Accessories Manual Local Values Fan speed modulation is controlled the pressure reading taken the sensor on each unit LAN SETTINGS Temp Hum Control Mode Local Values Air Pressure Control Mode Local

Download Pdf Manuals

image

Related Search

Related Contents

Samsung Galaxy Trend 2 Manual de Usuario  Toshiba 36HF72 36" TV  Advantage BT4 User Manual  KG3002 (Kontakt Grill) - Service Checkpoint Germany  user and maintenance manual - cipriani scambiatori españa    Sharkoon QuickStore Portable Pro  001-006 STRADA LUM I 1ed  ASX TradeAccept User Manual - Australian Securities Exchange  -1- S1CH50F LED LAMP DRIVE UNIT 取扱説明書  