Eaton 5P1150iR
Contents
1. Output on battery power e Voltage 200 208 220 230 240 V 10 6 e Frequency 50 60 Hz 0 1 Hz Battery sealed lead acid maintenance free e Standard Tower 1x12V 2x12V 2x12V 3x12V 9 Ah 7 Ah 9 Ah 9 Ah Rack 2x6V 4x6V 4x6V 6x6V 9 Ah 7 Ah 9 Ah 9 Ah Environment e Operating 0 to 35 C 0 to 40 C temperature range e Storage 15 to 50 C temperature range e Relative humidity e Noise level 0 to 90 without condensation lt 40 dBA 1 The high and low thresholds can be adjusted using UPS settings up to 150 294 V 2 Up to 40 Hz in low sensitivity mode programmable using UPS settings 3 Adjustable to 200 208 220 230 240 V must be set to the identical AC power source value When the appliance is used in EU area use an external circuit breaker in front of line with rating 16 A 250 V which is IEC EN 60898 1 standard compliant When the appliance is used in America area use an external circuit breaker in front of line with rating 20 A 250 V This product is designed for IT power distribution system 620 00082 02 i en Page 21 Page 22 620 00082 02 i en
2. E T N Installation and user manual Tower models 5P 650i 5P 850i 5P 1150i 5P 1550i 1U Rack models 5P 650i R 5P 850i R 5P 1150i R 5P 1550i R Copyright 2013 EATON All rights reserved Service and support Call your local service representative 620 00082 02 i en Certification Standards UPS directives e Safety IEC 62040 1 2008 C2 e EMC IEC 62040 2 2005 VCCI e Performance IEC 62040 3 2010 CE mark EN 62040 1 2008 and EN 62040 2 2006 C1 Class B emission level CISPR 22 2005 A2 2006 EN 55022 Harmonics emission IEC 61000 3 2 edition 3 2 2009 Flickers emission IEC 61000 3 3 edition 2 2008 VCCI Notice OMB PAAR KRES RRS AEM BRS VCCI OHMIC ESS TIFAAPHRARE CH ORE RER CHATS LEBER GHBENXBITFLEBSVIESF TORA AS HEDBRENSZILEBSVETF The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Eaton Power Quality or check Eaton website www powerquality eaton com Special Symbols De pg e e Page 2 The following are examples of symbols used on the UPS or accessories to alert you to important information RISK OF ELECTRIC SHOCK Observe the warning associated with the risk of electric shock symbol Important instructions that must always be followed Do not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed a
3. 3 4 5 2 Presentation USB communication port RS232 communication port Slot for optional communication card Connector for ROO remote ON OFF or RPO Remote Power Off control Outlets for connection equipment Primary group 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for 7 8 connection of equipment Socket for connection to AC power source Ground screw Page 7 2 Presentation 2 4 Control panel The UPS has a five button graphical LCD It provides useful information about the UPS itself load status events measurements and settings Tower models Power On On battery Alarm Indicator Indicator Indicator red green yellow Escape Up Down Enter On Off button Rack models Alarm Up On Off Indicator red button On battery Indicator E e Escape yellow Power On Down Indicator green The following table shows the indicator status and description Indicator Status Description NJ On The UPS is operating normally Green El On The UPS is on battery mode Yellow A On The UPS has an active alarm or fault See trouble Red shooting on page 18 for additional information Page 8 620 00082 02 i en 2 5 LCD description 620 00082 02 i en Operation status Load equipment status Efficiency and load group information 2 Presentation m Battery status As default or aft
4. Press the Enter 1 button to activate the menu options Use the two middle buttons A and W to scroll Menu map for Display Functions through the menu structure Press the Enter 1 button to select an option Press the Esc button to cancel or return to the previous menu Main menu Submenu Display information or Menu function Measurements Load W VA Load A pf Output V Hz Input V Hz Battery V min Efficiency Power usage Control Load Segments Group 1 ON OFF Group 2 ON OFF These commands overrule user settings for load segments Start battery test Starts a manual battery test Reset fault state Clears active faults Restore factory settings Returns all settings to original values UPS restart required Reset power usage Clears power usage measurements Settings Local settings Sets product general parameters Input output settings Sets Input and output parameters ON OFF settings Sets ON OFF conditions Battery settings Sets battery configuration Fault log Displays event log or alarms Identification Com card address UPS Type Part Number Serial Number Firmware release 2 7 User settings Page 10 The following table displays the options that can be changed by the user Description Available settings Default settings Local settings Language English Frangais Deutsch Italiano Portugu s Espanol Pyccku Menu
5. see diagram Contact open UPS shutdown Contact closed UPS start up UPS connected to AC power and AC power is available Note The local ON OFF control using button overrides the remote control function Contact open UPS shutdown LED A goes ON To return to normal operation deactivate the remote external contact and restart the UPS by pressing button b 4 Plug connector 4 into the back of the UPS 5 Connect and restart the UPS following the previously described procedures 6 Activate the external remote shutdown contact to test the function Warning This connector must only be connected to SELV Safety Extra Low Voltage circuits 620 00082 02 i en Page 17 5 Maintenance 5 1 Troubleshooting Operation status Possible cause Action Batteries disconnected The UPS does not recognise the internal batteries If the condition persists contact your service representative The batteries are disconnected Verify that all batteries are properly connected If the condition persists contact your service representative Overload Power requirements exceeds the UPS capacity greater than 105 of nominal Remove some of the equipment from the UPS The UPS continues to operate but may shutdown if the load increases The alarm resets when the condition becomes inactive End of battery life The end of the battery life is reached Contact your service repr
6. to keep some equipment running while turning off other equipment This feature allows to save battery power Group 1 Disable Group 2 Disable Overload prealarm 10 15 20 100 105 Gives a warning when a predefined critical percentage of load is reached 105 ON OFF settings Cold start Disable Enable Enables the product to be started on battery power First cold start always disabled Enable Forced reboot Disable Enable If mains recover during a shutdown sequence if enabled shutdown sequence will complete and wait 10 seconds prior to restart if disabled shutdown sequence will not complete and restart will occur immediately Enable Auto restart Disable Enable Enables the product to restart automatically when mains recovers after a complete battery discharge Enable Energy saving Disable Enable If enabled UPS will shutdown after 5min of back up time if no load is detected on the output Disable Sleep mode Disable Enable If disabled LCD and communication will turn OFF immediately after UPS is OFF If enabled LCD and communication stays ON 1h30 min after UPS is OFF Disable Remote command Disable Enable If enabled shutdown or restart commands from software are authorised Enable RPO delay 0 s 1s 2 s 180 s Delays remote power off command 0 s Battery se
7. 5P 650i 7 52 16 60 345 x 150 x 233 13 6 x 5 9 x 9 2 5P 850i 9 93 21 90 345 x 150 x 233 13 6 x 5 9 x 9 2 5P 1150i 10 91 24 10 345 x 150 x 233 13 6 x 5 9 x 9 2 5P 1550i 15 95 35 20 445 x 150 x 233 17 5 x 5 9 x 9 2 Rack models Description Weights kg lb Dimensions mm inch DxWxH 5P 650i R 8 6 19 00 363 5 x 438 x 43 2 14 3 x 17 2 x 1 7 5P 850i R 13 8 30 40 509 x 438 x 43 2 20 0 x 17 2 x 1 7 5P 1150i R 14 64 32 70 509 x 438 x 43 2 20 0 x 17 2 x 1 7 5P 15501 R 19 36 42 70 554 x 438 x 43 2 21 8 x 17 2 x 1 7 620 00082 02 i en Page 5 2 Presentation 2 2 Tower rear panels Page 6 5P 650i 1 2 3 4 5 USB communication port RS232 communication port Slot for optional communication card Connector for ROO remote ON OFF or RPO Remote Power Off control Outlets for connection of critical equipment Primary group 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for 7 8 connection of equipment Socket for connection to AC power source Ground screw 620 00082 02 i en 2 3 Rack rear panels 620 00082 02 i en 5P 650i R 5P 850i R Q oe A 5P 1150i R Eaei 5P 1550i R 1 2
8. cover with D the 2 screws G Characteristics of the optocouplers communication port optional e Pins 1 3 4 5 6 10 not used e Pin 2 common user ni e Pin 7 low battery JE lt YE e Pin 8 operation on battery 2 lt lt Je power L H e Pin 9 UPS ON equipment supplied n o normally open contact When a signal is activated the contact is closed between the common pin 2 and the pin for the corresponding signal Contact characteristics optocoupler e Voltage 48V DC max e Current 25 mA max e Power 1 2 W 620 00082 02 i en Page 15 4 Operation 4 1 Start up and Normal operation To start the UPS Verify that the UPS power cord is plugged in The UPS front panel display illuminates and shows EATON logo Verify that the UPS status screen shows bh Press the button on the UPS front panel for at least 2 seconds The UPS front panel display changes status to UPS starting 5 Check the UPS front panel display for active alarms or notices Resolve any active alarms before continuing See Troubleshooting on page 18 If the A indicator is on do not proceed until all alarms are clear Check the UPS status from the front panel to view the active alarms Correct the alarms and restart if necessary 6 Verify that the indicator illuminates solid indicating that the UPS is operating normally and any loads are powered and protected The UPS should be in Normal mode po na 4 2 Starting
9. S on Battery AAA ee an 16 AS UPS SU ties scaisnds eagroskesvine a a E AE a N 16 4 4 Operation on Battery POW s i neyi i inea a adi 16 4 5 Retro AC IMPUt POr asas 17 AiG UPS remote control functions ss ea EEE A E EANA ASE E 17 5 Maintenance cocino linia as aisien svaconaeiedocaccuseaeeeeeeese 18 5 1 MOUDIESMOOTIN Geienean ieoa ra Poda duet arde prada 18 5 2 Battery MoOdule TEC diaria caca 19 A siririna rer aek e edda daie E eani 21 6 1 lechnical Sp cification S s renser E E E E EEEE EERE EEREN 21 620 00082 02 i en Page 3 1 Introduction Thank you for selecting an EATON product to protect your electrical equipment The 5P range has been designed with the utmost care We recommend that you take the time to read this manual to take full advantage of the many features of your UPS Uninterruptible Power System Before installing 5P please read the booklet presenting the safety instructions Then follow the instructions in this manual To discover the entire range of EATON products and the options available for the 5P range we invite you to visit our web site at www eaton com powerquality or contact your EATON representative 1 1 Environmental protection Page 4 EATON has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFCs HCFCs or asbestos Packing To improve waste treatment and facilitate recycling separate the var
10. er 5 minutes of inactivity the LCD displays the screen saver The backlight LCD automatically dims after 10 minutes of inactivity Press any button to restore the screen The following table describes the status information provided by the UPS Note If other indicator appears see troubleshooting on page 18 for additional information Operation status Possible cause Action Standby mode The UPS is OFF waiting for start up command from user Equipment is not powered until 4 button is not pressed Normal mode The UPS is operating normally The UPS is powering and protecting the equipment Battery LED is on 1 beep every 10 seconds the UPS is in Battery mode In AVR mode The UPS is operating normally but The UPS is powering the the utility voltage is outside normal equipment through a Automatic mode thresholds Voltage Regulation device The equipment is still normally protected No beep On Battery A utility failure has occurred and The UPS is powering the equipment with the battery power Prepare your equipment for shutdown End of backup time 1 beep every 3 seconds The UPS is in battery mode and the battery is running low This warning is approximate and the actual time to shutdown may vary significantly Depending on the UPS Load the Battery Low warning may occur before the battery reaches 20 capacity Page 9 2 Presentation 2 6 Display functions
11. ery Page 16 620 00082 02 i en 4 Operation Low battery warning e The wv and E indicator illuminates solid e The audio alarm beeps every three seconds The remaining battery power is low Shut down all applications on the connected equipment because automatic UPS shutdown is imminent End of battery backup time e LCD displays End of backup time e All the LEDs go OFF e The audio alarms stops 4 5 Return of AC Input Power Following an outage the UPS restarts automatically when AC input power returns unless the restart function has been disabled and the load is supplied again 4 6 UPS remote control functions The 5P offers a choice between two remote control functions e RPO Remote Power Off allow a remote contact to be used to disconnect all the equipment connected to the UPS Restarting the UPS requires manual intervention e ROO Remote ON OFF allows remote action of button to shut down the UPS These functions are obtained by opening a contact connected between the appropriate pins of connector 4 on the rear panel of the UPS see figures below m Remote control connection and test 1 Check that the UPS is OFF and disconnected from the AC input source 2 Remove connector 4 after unscrewing the screws 3 Connect a normally closed volt free contact 60 V DC 30 V AC max 20 mA max 0 75 mm cable cross section between the two pins of connector 4
12. esentative for battery replacement Event An UPS event occurs Example Set the contact back to its normal Remote Power OFF the RPO position and press l button contact has been activated to to restart shutdown the UPS and now prevents restart UPS fault The UPS has an internal fault The UPS does not protect the equipment anymore Note the alarm message and the UPS Serial Number then contact your service representative Page 18 620 00082 02 i en 5 2 Battery module replacement Safety recommendations e use tools with an insulated handle Battery tray removal on tower models Mounting the new battery module Carry out the above instructions in reverse order 5 Maintenance The battery can cause electrocution and high short circuit currents The following safety precautions are required before servicing the battery components remove watches rings bracelets and all other metal objects from the hands and arms A Remove the front panel B Disconnect the battery block by separating the two connectors never pull on the wires C Remove the plastic protection cover in front of the battery one screw D Pull the plastic tab to remove the battery block and replace it e To ensure safety and high performance use only batteries supplied by EATON e Take care to firmly press together the two parts of the connec
13. ious packing components e The cardboard we use comprises over 50 of recycled cardboard e Sacks and bags are made of polyethylene e Packing materials are recyclable and bear the appropriate identification symbol oy PET Materials Abbreviations Number in cy the symbols Polyethylene terephthalat PET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local regulations for the disposal of packing materials End of life EATON will process products at the end of their service life in compliance with local regulations EATON works with companies in charge of collecting and eliminating our products at the end of their service life Product The product is made up of recyclable materials Dismantling and destruction must take place in compliance with all local regulations concerning waste At the end of its service life the product must be transported to a processing centre for electrical and electronic waste Battery The product contains lead acid batteries that must be processed according to applicable local regulations concerning batteries The battery may be removed to comply with regulations and in view of correct disposal 620 00082 02 i en 2 Presentation 2 1 Standard installations Tower models Description Weights kg lb Dimensions mm inch DxWxH
14. itate sorting 620 00082 02 i en 3 Installation 3 2 Installation of tower models 3 3 Wall installation of rack models 650i R 850i R 1150i R 620 00082 02 i en Page 13 3 Installation 3 4 Installation of rack models 650i R only Follow steps 1 to 3 for rack mounting 3 5 Installation of rack models 850i R 11501 R 15501 R Follow steps 1 to 4 for module mounting on the rails i The rails and necessary hardware are supplied by EATON Page 14 620 00082 02 i en 3 Installation 3 6 Communication ports Connection of RS232 or USB communication port The RS232 and USB communication ports cannot operate simultaneously 1 Connect the RS232 5 or USB 6 communication cable to the serial or USB port on the computer equipment 6 2 Connect the other end of the communication cable 5 or 6 to the USB 1 or RS232 2 communication port on the UPS O gt e UPS gt The UPS can now communicate AN with EATON power management software NN N e Qo odd e LANE Installation of the communication cards optional nn It is not necessary to shutdown the UPS before installing a communication card secured by screws 2 Insert the communication card in the slot 1 Remove the slot cover 3 s 3 Secure the card
15. s status notices and alarms UPS fault Event Log data and settings are in all supported languages English User selectable when UPS is powered for the first time LCD settings Modify LCD screen brightness and contrast to adapt to room light conditions Audible alarm Enabled Disabled on battery Always disabled Enable or disable the buzzer if an alarm occurs Enabled In Out settings Output voltage 200 V 208 V 220 V 230 V 240 V User selectable when UPS is powered for the first time Input thresholds Normal mode Extended mode Extended mode reduces lower input voltage to 150 V before UPS transfers to battery This can be used if the load can withstand low voltage supply Normal mode Sensitivity High Low High for sensitive equipment UPS will easily transfer to battery when utility conditions are becoming bad Low for equipment that can withstand bad utility conditions in that case the UPS will not transfer to battery High Load segments Auto start delay No Delay 1 s 2 s 65354 s The connected load is powered after the specified delay Group 1 3s Group 2 6s 620 00082 02 i en 620 00082 02 i en 2 Presentation Description Available settings Default settings In Out settings Load segments Auto shutdown delay Disable Os 1 s 2 s 65354 s During a power outage authorises
16. s it s explain in this manual For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Information advice help 620 00082 02 i en Contents 1 Introductio cintia 4 1 1 Environmental protection oooooooccccncconcooccccccononnncnncnnnnnnnnnnnnnnnnnnnnc cane nn nro EEE SE EEEE EEEn EEEE Enne e erenn 4 2 Presentation PP 5 2 Standard installations y sia laca 5 2 2 TOWEL rear Panels imita en A EOS acid rain a dianas 6 2 3 MACK TEA PS ii tds 7 2 AC ntrol panel eaire R E a a E O E 8 O A E a E EEEE taken E EEO RE 9 2 6 Display UNCION S iia e a e ive a a raaa ited ent a 10 27 USE SMN ct 10 3 Installation A aa ete ea eee 12 3 1 Unpacking and Contents Cheka 12 3 2 Installation of tower models 3 3 Wall installation of rack models 650i R 850i R 11501 R o oooooiocccnnccccnncccccooccnoncncconncnos 13 3 4 Installation of rack models 650i R only oooooooconccocnoocccconocccoonnnooooncnnonnncnonno canon o ncnonnncionnnnos 14 3 5 Installation of rack models 850i R 11501 R 15501 R ocooooonoccnnnncccnoncccconocccconncononcncnonncoos 14 3G Communication POTS anta 15 A iiaiai nadaa atu aceeevncieteaddancensneucvccaecneeaed 16 4 1 Start upsand Normal operati N ro dia ol eea i a aat 16 4 2 Staiting the UP
17. the UPS on Battery Before using this feature the UPS must have been powered by utility power with output enabled at i least once Battery start can be disabled See the Cold start setting in ON OFF Settings on page 11 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting The UPS cycles through Standby mode to Battery mode The E indicator illuminates solid The UPS supplies power to your equipment 2 Check the UPS front panel display for active alarms or notices besides the Battery mode notice and notices that indicate missing utility power Resolve any active alarms before continuing See Troubleshooting on page 18 Check the UPS status from the front panel to view the active alarms Correct the alarms and restart if necessary 4 3 UPS Shutdown To shut down the UPS 1 Press the button on the front panel for three seconds The UPS starts to beep and shows a status of UPS shutting OFF The UPS then transfers to Standby mode and the indicator turns off 4 4 Operation on Battery Power Transfer to battery power e The connected devices continue to be supplied by the UPS when AC input power is no longer available The necessary energy is provided by the battery e The and 7 indicator illuminates solid e The audio alarm beeps every ten seconds i The connected devices are supplied by the batt
18. tor during remounting 620 00082 02 i en Page 19 5 Maintenance Battery tray removal on rack models A Remove the front panel B Remove the left hand side of the front panel by pushing the button and then by sliding the part C Disconnect the battery block by separating the two connectors never pull on the wires D Remove the metal protection cover in front of the battery two screws E Pull the plastic tab to remove the battery block and replace it Mounting the new battery module Carry out the above instructions in reverse order i e To ensure safety and high performance use only batteries supplied by EATON e Take care to firmly press together the two parts of the connector during remounting Page 20 620 00082 02 i en 6 Appendices 6 1 Technical specifications Transformer Filter AVR Charger Inverter alien Ea Nm O Battery Tower 5P 650i 5P 850i 5P 1150i 5P 15501 Rack 5P 650i R 5P 850i R 5P 1150i R 5P 1550i R Output Power 650 VA 850 VA 1150 VA 1550 VA 230 V 420 W 600 W 770 W 1100 W Output Power 585 VA 765 VA 1035 VA 1395 VA 208 V 378 W 540 W 693 W 990 W Output Power 585 VA 765 VA 1035 VA 1395 VA 200 V 378 W 540 W 693 W 990 W AC Input power e Rated input voltage Single phase 200 240 V e Input voltage range 160 to 294 V 1 e Input frequency range 47 to 70 Hz 50 Hz system 56 5 to 70 Hz 60 Hz system
19. ttings Automatic battery test No test Every day Every week Every month Available only if battery charge mode is set to constant charge Every week in constant charge otherwise following ABM battery test method Low battery 1 2 100 20 warning The alarm triggers when the set percentage of battery capacity is reached during a back up time Restart battery 1 2 100 0 level If set automatic restart will occur only when percentage of battery charge is reached Battery charge ABM cycling Constant charge ABM cycling mode Deep discharge Yes No Yes protection If set to Yes the UPS automatically prevents battery from deep discharge by adapting end of back up time voltage threshold Page 11 3 Installation 3 1 Unpacking and contents check Page 12 Tower models Rack models 1 5P UPS 2 Quick start and safety instructions 3 User manual and IPSS Intelligent Power Software Suite CDROM 4 2 connection cables for the protected equipment 5 RS232 communication cable 6 USB communication cable 7 Cable locking systems 1 x 4 outlets 650i R and 850i R models 1 x 6 outlets 1150i R and 1550i R models 8 1U Rack kit ears only for 650i R model Packing materials must be disposed of in compliance with all local regulations concerning waste Recycling symbols are printed on the packing materials to facil
Download Pdf Manuals
Related Search
Related Contents
MS-BACEOL-0 MS/TP FC バス用終端末器 Fuzzy GM965/GME965 MANUEL D`INSTALLATION ET DE MAINTENANCE PhotoniQ Multi-Channel Data Acquisition Systems AMD 7ZX-1 Computer Hardware User Manual Player/Menu - pipeorgancontrol.com Revo SR-1500 Shoulder Support User Manual manual ARTICULADOS Mod:SDE/6-CL Intronics VGA Matrix SwitchVGA Matrix Switch Copyright © All rights reserved.