1. A dedicated Intruder Alarm connection is provided Site Layout Examples Net2 plus Net2 plus Net2 plus Net2 plus Net2 plus Net2 plus RS485 data line TCP IP TCP IP TCP IP TCP IP LAN LAN LAN LAN Here are three typical site layouts Net2 plus Net2 plus Net2 classic 1 The Net2 plus ACU s can be individually connected to the Net2 PC via the site LAN network 2 The Net2 plus ACU s can be hardwired on a daisy chain RS485 data line with ONE of them connected to the Net2 PC via the site LAN network RS485 data line 3 The Net2 plus ACU can be used as the TCP IP TCP IP converter for a line of Net2 plus and Net2 classic ACU s LAN The TCP IP interface allows an RS485 data line to be controlled by the Net2 Server running across a LAN network An RS485 data line has a 1 km maximum length This distance can be increased by using Paxton high speed repeaters or by using shorter independant data lines using multiple LAN connections controlled from the same PC Control unit installation Wire the components to the Access Control Unit ACU as shown on the first page Power up the unit and wait for the OK heartbeat Press the exit button or in the absence of an exit button short the OV and exit terminals together The lock relay LED will come on and the lock should release The reader s default indication has all the LED s on Access granted is denoted with a single flashing Green LED Access Denied is a single flashing Red L
2. and RS485 LED indication The Net2 plus performs two functions It is an access control unit and also a TCP IP RS485 converter Information can pass across the PCB between the TCP IP and RS485 data port but is not relevant to this ACU Server Connected LED Steady Green This LED shows that the TCP IP interface is active and receiving data from the Net2 PC server This includes all data for other ACU s that may be linked via the RS485 data port Rx and Tx LED s These LED s show the activity for this ACU only This is same indication as seen on a Net2 classic ACU It is not dependant on the source TCP IP or RS485 The Rx LED will flash for all data being received and the Tx LED will only flash when this unit responds to its own address Page 7 Specifications features amera YO EC ThumberofPiNs S C8000 Nev a G S o o mems OOS o o a S Mamu door operam i sess OO wers OOo S S o S osen OOOO CdS response OOO S S o o esser OOOO S T o T ews OOO S T o acu persotaine OO a mese OOo o S o a Dat retention ater soist powers ve POC Ss Tethermetneworkspeed tomos momes a a 20s O O C T Cd C a E Crear C eC Te Poe current ependng on say 4 tm SO o S o S Relay swtchabiecurent Oooo o a o momomo OO O o o a o contin rencer por owore coma ereronnent Min Topeeting temperature Beer mms eee d ese OOOO CE This product is not suitable for retail sale All warranties are invalid if this product
3. firewall virus protection software and other wireless hardware can block the IP detection process Disable these and try to detect the device again Please contact Technical Support if you require further advice If you detect the MAC address but the device now shows Not Responding you must check the IP address to make sure it is still in range with the PC or network If it is not you should either change the IP address of the PC or the IP address of the device so they are both again in the same range Our Technical team can talk you through this if you need help If the MAC address does not appear when you click Detect ensure that the following ports are open on all devices between this unit and the Net2 PC TCP IP Reset The unit can be returned to DHCP settings by powering down the unit and linking the Brown and Mauve terminals on reader port 2 Power up the unit again and the unit will beep to acknowledge the link You may now remove the link and the OK LED will flash fast for a few seconds When the OK LED returns to a steady heartbeat the IP settings will be reset to DHCP If you still cannot detect the MAC address of the device call our Technical Support Help line The device will beep when detected by the Net2 Server Configuration Utility or when new IP settings are applied The sounder will also respond to a direct Ping over the network This is a feature to assist with finding devices hidden from view Connecting to
4. 30 08 2012 v Ins 30080 Net2 plus control unit Paxton Technical Support 6 01273 811011 support paxton co uk Technical help is available Monday Friday from 07 00 19 00 GMT Saturday from 09 00 13 00 GMT Documentation on all Paxton products can be found on our website http www paxton co uk The Net2 plus can be connected to the PC via an RS485 data line or a TCP IP connection This unit requires the controlling PC to be running Net2 v4 14 or later software 12V DC Wiring Intruder alarm integration power supply YIVIVIVIG O O O O Co JES Fail closed release http paxton info 107 UTM 123456 00 01 02 03 04 05 Exit button push to make Reader keypad Q i O Q Door contact switch held closed by door OOO VIV V VIO lt lt a WADA Switchable WAY al 120 ohm gt X resistors Tamper switch optional TCP IP patch lead The Net2 plus ACU has 2 reader ports and From previous To next For a fail open lock 3 output relays but can control just one ACU ACU Maglock wire OV to the door The configuration of one control N C terminal instead of unit per door greatly simplifies installation N O and is ultimately highly cost effective LED indications 12V Green Power LED Relay 1 Orange The relay is energised N O COM contacts are closed Relay 2 Orange The relay is energised N O COM contacts are closed Alarm Re
5. CP IP interface must be listed in the Net2 Server Configuration Utility and responds when PINGed from the utility A static IP address must be used for the interface 2 If the interface is responding try a loopback test see Loopback section 3 The Net2 data line should be checked for resistance readings 6 Readers Keypads not working Software settings Confirm that the settings of the reader or keypad are correct Connections Check the wiring and integrity of the connectors If possible test this reader on the other port Cable Belden 9540 should be used to extend the reader cable 100 m maximum Twisted pair alarm cable Should not be used To confirm that a cable extension is not at fault wire the reader direct into the reader port Supply voltage Confirm that the voltage is within specification see table User token Confirm that the user token used for testing is OK by presenting it to a Known working reader Interference Confirm whether the reader works when tested in hand and not mounted on the wall Ensure that readers are not mounted back to back or there is no interference from other local RF devices Page 6 Here is the list of topics about this product that receive the most technical support enquiries We list them here to help you speed up the installation and trouble shooting process 7 Fire alarm integration Net2 Professional software must be used A voltage free normally closed conta
6. ED Remember the Net2 plus is a combined TCP IP interface and an Access Control unit If the TCP IP interface is being used you will need to detect the interface first using the procedure on the following page This is important if you are replacing an existing Net2 plus The Replace wizard in the Doors screen does NOT reconfigure the IP address so it must be done manually The wizard will then copy across the user data Each time the unit is powered on it will run an internal health check During this phase about 5 secs the OK LED will flash quickly before changing to a slower heartbeat Page 2 Connecting to the PC via the Ethernet port The IP address should be assigned a fixed value or should be given a DHCP reservation Unreserved IP addresses issued by DHCP servers are not guaranteed to be constant leading to potential failure of communication between Net2 software and the device Run the Net2 Server Configuration Utility Start Programs Net2 and Click on TCP IP nodes Net2 Server Configuration Utility x Net2 Server Configuration Utility TE General Database Wiegand Dial up nofes TCP IP nodes New Ait Bridge Paths System Features Diagnosti_ gt General Database Wiegand Dial up nodes TCP IP nodes Net2air Bridge Paths System Features Diagnosi a gt m TCP IP nodes TCP IP nodes Name MAC address Add Name MA address Add 5th unit 00 49 D6 0E 49 7E Net2 plus 0 12 0 05 De
7. P IP interface any fixed IP settings will be retained If the unit is in DHCP mode it will need to be detected at each stage using the Net2 Server Config Utility as a new address may be issued by the IP server each time the PCB resets 3 Can we use a DHCP IP address The Ethernet interface does support DHCP but for more reliable communication a static IP address must be reserved for the unit This is because some servers issue different DHCP addresses each time they are restarted and this requires the Net2 interface to be manually set up again a time consuming process 4 TCP IP Direct PC connection Connect the network interface directly to the LAN port of the PC Without the presence of a DHCP server the unit will default to an IP address in the range 169 254 X X Check the IP address of the network card of your PC by typing IPCONFIG at the command prompt Detect the TCP IP interface with the Net2 Server Configuration Utility and change the IP address to an address similar to that of your machine For example if the IP address of the PC is 192 168 10 7 change the IP address of the TCP IP interface to 192 168 10 8 Once the IP address of the interface has been changed into the range of the PC then Net2 will be able to communicate with it NOTE Do not change the IP address of your PC to 169 254 x x this will not allow the IP address of the TCP IP interface to be fixed correctly 5 Cannot detect ACU via a TCP IP interface 1 The T
8. To run the test go to Net2 Server Config Utility TCP IP Nodes Advanced and click on Loopback test If the test fails connect the unit directly to the PC with an RJ45 patch cable and test it again Should this still fail please call Technical Support for further advice Connecting to the PC or other ACU s via the RS485 data connection 90 of installation faults are caused by wiring errors on the RS485 data line Special attention to getting this right first time saves a lot of time and effort END OF LINE TERMINATION SWITCHES These should all be OFF except for those at both ends of the data line READER amp DATA CABLE SCREENS Data cable screens and spare cores MUST be connected throughout Reader and keypad screens where provided should be connected to the Black OV terminal Reader Net2 Server Control unit LAN WAN The data line must be wired in a single daisy chain The data converter may be located anywhere along the data line 120 ohm terminating resistors must be linked across each data pair at the beginning AND end of the line This can be done on many units with a switch or jumpers If not free resistors are provided with the converter RS485 data line resistance checks Power down all TCP IP USB and RS232 converters individual and Net2 plus S Check the resistance across each data pair is 60 80 ohms S Check that there are no data line to screen shorts S Check the screen of the data cable
9. a WAN or different subnet mask If you are connecting this device to a remote subnet which is different from the Net2 software PC the standard detect mechanism cannot work across the network routers between them The IP address along with the correct subnet mask and gateway for the remote subnet have to be set Either do this on the local subnet with the existing Net2 PC or use a PC on the remote subnet once the device is installed The PC that has the Net2 server installed must be able to access the IP address range on the WAN remote site Page 3 This may require the routers and gateways to be configured between the networks Again this would be done by the Network administrator of that site Make sure the ports listed above are open on all intermediate routers Once installed create a record with the Add button if none was created during initial set up and you should then be able to detect its MAC by entering the IP address in the Configuration screen Ping box TCP IP Loopback test The following test should be run if there are problems setting up the IP configuration of the interface This test sends data to the device and checks this against the data it receives back This confirms that the network is working correctly The Net2 server program must be shut down during this test Remove any wires from the RS485 data line connector and create a hardwired data loop as follows Connect the Orange to White Green and Green to White Orange
10. ct from the fire alarm system should be wired across an ACU input Contact PSU Tamper Exit The doors that are required to open from that trigger are set up in the software for that ACU under the Fire Alarm Tab NOTE The doors are relocked from the PC software resetting the Fire panel will have no effect on the system The Net2 Server MUST be running at all times for this method to work Fail open locks are required on fire doors Break glasses should be installed to drop power to the lock manually 8 RS485 data line cable layout Net2 classic and Net2 plus The data line must be wired in a daisy chain End of Line 1200hm resistors must be fitted switched across both pairs at each end of the line Repeaters must be used over 1000 metres and can be used to create a branch from the daisy chain Cat5 or Belden 8723 4 Core Twisted pair must be used for the data line The cable screen must be connected throughout for reliable communication Cat5 must have spare cores terminated in lieu of screen cable 9 Timesheet Why Time amp Attendance must have dedicated readers for logging in out In the vast majority of applications using the same reader for access and T amp A is not practical Traffic through the access points causes long unmanageable T amp A reports It is therefore NOT possible to set this up in the software Proximity or Cardlock readers set up as Clocking in or Clocking out readers have no effect on Relay 1 and will not app
11. d 12V Alarm output is active Exit Orange The exit button contacts are closed Contact Orange The door contacts are closed Tamper Orange The tamper contacts are closed PSU Orange The PSU contacts are closed OK Green flash The internal software is running Termination Red The on board resistors are in place across the RS485 data pairs Rx Red The ACU is receiving data TCP IP or RS485 See also FAQ section TX Green The ACU is responding to data TCP IP or RS485 Server Connected Green The TCP IP interface is communicating with the PC Net2 server Server Link Green 100 Mbit s Orange 10 Mbit s TCP IP speed Page 1 A Net2 plus can connect to the Net2 PC using either an un shielded RJ45 patch cable or an RS485 data line This greatly increases the number of installation options available to the installer One Net2 plus can also be used as the TCP IP interface for an RS485 daisy chain of Net2 plus and Net2 classic units When used with a TCP IP connection it must first be detected using the Net2 Server Configuration Utility See later section of this instruction and AN1006 Installing remote sites using TCP IP lt http paxton info 51 gt When used with an RS485 data line on board termination resistors can be put in circuit with a simple slide switch Ensure that units installed in the middle of the data line have this switch turned OFF
12. ear in Access levels Relay 2 will switch for half a second to allow confirmation by fitting an LED or sounder 10 TCP IP communication over a WAN We need to establish two way communications between a PC on site A and the TCP IP interface on Site B The paths that the PC and the TCP IP interface will use are different but they each need to know the IP address they are trying to locate on the other site as well as the gateway IP address that will route their requests from their own LAN to the other LAN TCP IP Interface set up Site B You need to set the IP address for the TCP IP interface that will define it within it s own LAN e g 10 10 0 25 You need to set the gateway IP address of the local router in the TCP IP interface This is so that the router will know that any reply from this interface needs to be sent back to the other LAN NOTE All the information required to get back to the sending PC on site A is done automatically by the network hardware the site A PC includes its own IP address in the outgoing message PC Set up Site A Most LAN addressing is set up such that different groups are reserved for specific remote sites It is then just a case of setting up the IP address of the TCP IP interface on site B 10 10 0 25 in the PCs Net2 Server Configuration Utility all the outward routing is done automatically by their network hardware Port 9999 must be allowed through any firewall software TCP IP
13. g a Multimeter measure the resistance across the White Green and Green pair at one end of the network A resistance of between 60 and 80 ohms is required Repeat the test for the White Orange and Orange pair This is vital for a stable and trouble free installation 2 ACU Reset No OK LED flashing The ACU has no factory reset condition as it does not contain any fixed settings The unit does have an operating program firmware that controls its functions and can be confirmed as running by means of the flashing OK LED If the OK LED is flashing steadily then there should be no reason to reset the unit If the OK LED is not flashing you need to clear the unit so that it can receive a firmware download from the PC Any other ACU s without OK LED s must be taken off the line or powered down Stop Net2 Server Net2 server icon Bottom right of screen Right mouse click Select Stop the Net2 Server Power down the Net2 ACU Insert a link wire between the Orange and Mauve terminals on reader 2 port Power up the ACU The OK LED flashes very quickly With the unit still powered remove the link Go to the PC and Start the Net2 Server and go into the Doors screen Click on the Detect button This should look for the ACU and then download its firmware This may take up to 5 minutes The OK LED Should now be flashing with a steady heartbeat This procedure must only be done for one ACU at a time Oe SI NOTE If this unit is using the TC
14. is continuous this provides the OV DC system reference Page 4 Software Configuration E Net Access Control ions Help Door name Name the Door aS A Door open time Set the door open time E k m Retesh 5 Print G Find D it c an A A ie Unlock the Door during Holds the door unlocked during Net Access Control Front Door this timezone Set to At No Time for normal user ES Events ACU serial number OUYA260 Operation S28 Users Door name ACC e o Door open time seconds 7 Cancel BA Administration z 8 Communications Unlock the door during Reader 1 Settings for Reader 1 and Keypad 1 on the ACU Sd Access levels Ss Timezones H Doors Reader 2 Settings for Reader 2 and Keypad 2 on the ACU Alarm Contains settings for the different types of alarm Codes Valid codes can be viewed added and removed EE Areas Reader 1 Reader 2 Alarm Can only be viewed when a keypad is active T Anti passback Reader details Events Shows the events for the control unit selected A IO Boards Name ont Door Ir Y Triggers and Actions Reader type ee E i keppad type Name Each reader can be named individually if required Rall call ee ey ne Reader type Set the reader type if applicable 3S Net operators Keypad type Set the keypad type if applicable Operating mode Token data format Select the data type being used on Reade ane int made the system New formats can be created Net actio
15. is not installed by a competent person Page 8
16. lete m 2e 4th unit 00 49 D6 DE 49 7F Net2 plus 0 12 0 05 __ Delete Rename 3rd unit 00 49 D6 0E 49 80 Net2 plus 0 12 0 05 Rename 2nd unit 00 49 D6 0E 49 87 Net2 plus 0 12 0 05 1st unit 00 49 D6 0E 49 86 Net2 plus 0 12 0 05 Detect Click Detect to automatically find any TCP IP nodes on your network Click Detect to automatically find any TCP IP nodes on your network Configuration IP address configuration Advanced Configuration IP address configuration Advanced IP Add Pn You can get an IP address assigned automatically if your network supports this capability Otherwise you need to ask ress 9 your network administrator for an IP address Download events Iv Firmware version 0 12 Obtain an IP address automatically use DHCP MAC address 00 0B D6 0E 49 7E Use the following IP address Interface mode RS 232 RS 485 New IP address 105 10 2 5 Ping Port number fi 0001 Subnet mask optional 255 255 0 0 v Default gateway optional OE AD AA oF Update firmware Cancel Click on Detect and the MAC address of the device s will appear in the table You must then use the IP address configuration tab to manually assign the IP address subnet mask and gateway Be aware that if the IP address that you give the device is not in the same IP range as the PC the device will no longer respond until you connect to it with a PC that is in the same IP range Some
17. ns E Open door E Timed operating modes This allows for different reader operation during a selected timezone Aoao aU ae ae Ald Reader operating mode Set the operating mode This reader will operate as s Timed operating modes A different operating Net details mode can be configured within a time window eee Reader action This i what will happen whetrecranracce PTET Relay 1 opens for door open time 3 Rela z Reader action Set the action required Net documentation e Baa when access is granted PC Installation The current specification for compatible PC hardware network and operating systems is available on our website at the following link http paxton info 720 Intruder alarm integration A dedicated port for input and output signals is provided when integrating a Net2 plus ACU with an alarm system Please see AN1035 Integrating Net2 with an intruder alarm system lt http paxton info 91 gt or call Technical Support for further information VON ON Arm Confirmation Push Button Wire across OV and Arm Sense Requires a voltage free loop across OV and Sense to confirm when alarm is active Set Relay provides contacts across COM and N O for a voltage free loop to set the alarm Page 5 Technical Help 1 RS485 Data line resistance check ACU not responding or fails to be detected First power down any data line converters and disconnect any ACU s that do not have a flashing OK LED Usin
Download Pdf Manuals
Related Search
Related Contents
2.5イ ンチSATA SSD 取扱説明書 Xerox WorkCentre 6015 Quick Reference Guide Politique des usages, II : « La politique, mode d`emploi ». Sunbeam 6166-33 Toaster User Manual DediProg SF Software User Manual government of sindh civil hospital, karachi tender Frame It All 300001080 Instructions / Assembly Copyright © All rights reserved.