1. e Pay highly attention to the polarity marking on external battery terminal block and make sure the correct battery polarity is connected Wrong connection may cause permanent damage of the UPS m O PowerWalke e Make sure the protective earth ground wiring is correct The current spec color position connection and conductance reliability of wire should be checked carefully e Make sure the utility input amp output wiring is correct The current spec color position connection and conductance reliability of wire should be checked carefully Make sure the L N terminal is correct not reverse or short circuited 2 4 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown O stanak 3 Operations 3 1 Button Operation gt Turn on the UPS Press and hold the button more than 0 55 to turn on the UPS ON Enter Button gt Enter Key Press this button to confirm the selection in setting menu gt Turn off the UPS Press and hold the button more than 0 55 to turn off the UPS OFF ESC Button gt Esc key Press this button to return to last menu in setting menu gt Battery test Press and hold the button more than 0 5s to test the battery while Test Up Button in AC mode or CVCF mode gt UP key Press this button to display next selection in setting menu gt Mute the
2. M 5 253 SINGLE UPS INSTALLATION raran rara EAE a ANE 7 P SOFTWARE INSTALLATION A a a a A E 9 3 OPERATIONS rinnan AEE E AAAA 10 Sl POTON PRAT N r a a A O 10 3 2 LED INDICATORS AND LCD PANEL 10 3 3 AUDIBIE ALARM A A ut 12 Cs UPS OPERATION os A 13 3 5 ABBREVIATION MEANING IN LCD DISPLAY 25 e 15 m 16 3 7 OPERATING MODE STATUS DESCRIPTION 21 Os uu c NR 22 3 9 WARNING INDICATOR 23 4 TROUBLE SHOOTIN 2 iru iun EE E xx ME DEO VE SEES UNE 24 5 STORAGE AND MAINTENANLCE uu5 525225 x RM ERR ERA T EEUU ME
3. 1 5 Standards Safety IEC EN 62040 1 EMI Category C3 Category C3 Level 4 Warning This is a product for commercial and industrial application in the second environment installation restrictions or additional measures may be needed to prevent disturbances EO OOOO OA 2 Installation and Operation There are two different types of online UPS standard and long run models Please refer to the following model table Standard model model J 10KRL Unpack the package and check the package contents The shipping package contains e One UPS e One user manual e One monitoring software CD e One RS 232 cable option e One USB cable e One battery cable option NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts Please keep the original package in a safe place for future use 2 1 Unpacking and Inspection 2 2 Rear Panel View Diagram1 6K 10K Rear Panel QO Power Walke Diagram 2 6KL 10KL Rear Panel Diagram 3 6K L 10K L Input Output Termin
4. 3 Make sure the battery numbers setting on the control board Please refer to the section 3 4 12 for detailed setting is consistent to real connection 4 The charging current can be changed from 0 5A to 6A via LCD or software Please make sure that the charging current is suitable to battery specification 5 Battery mode operation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more than 2590 the buzzer will once every 4 seconds If the battery voltage drops to the alarm level the buzzer will beep quickly once every sec to remind users that the battery is at low level and the UPS will shut down automatically soon Users could switch off some non critical loads to disable the shutdown alarm and prolong the backup time If there is no more load to be switched off at that time you have to shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of data loss or load failure 2 In Battery mode if buzzer sound annoys users can press the Mute button to disable the buzzer 3 The backup time of the long run model depends on the external battery capacity 4 The backup time may vary from different environment temperature and load type 5 When setting backup time for 16 5 hours default value from LCD panel after discharging 16 5 hours UPS will shut down automatically to protect the battery This battery disc
5. Fault code is shown as 14 the icon The UPS shut down check output wiring and if automatically because short HORT i lights on LCD display circuit occurs on the Ups Connected devices are in short alarm beeps continuously output circuit status Other fault codes are shown on LCD UPS internal fault has display and alarm beeps continuously occurred ponte JOD Ged Charge the batteries at least 7 hours and then check capacity Battery backup time is shorter than If the problem still persists nominal value consult your dealer Batteries defect Contact your dealer to replace the battery Fan is locked or not working The icon LN ano flash on LCD or the UPS temperature is too Check fans and notify dealer display and alarm beeps every second high Batteries are not fully charged 24 m O PowerWalke 5 Storage and Maintenance 5 1 Storage Before storing charge the UPS at least 7 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 5 2 Maintenance The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Even after the unit is disconnected from the mains components inside the UPS system are still connected to the battery packs which are potentially dangerous Before
6. The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not CVCF mode If selected the output frequency will synchronize with the input frequency within 46754 Hz at 50Hz or within 56 64 Hz at 60Hz according to setting in parameter 2 If 50 Hz selected in parameter 2 UPS will transfer to battery mode when input frequency is not within 46754 Hz If 60Hz selected in parameter 2 UPS will transfer to battery mode when input frequency is not within 56764 Hz If Parameter 2 is ATO the Parameter 3 will show the current frequency Parameter 2 Set the acceptable low voltage for bypass Setting range is from 110V to 209V and the default value is 110V Parameter 3 Set the acceptable high voltage for bypass Setting range is from 231V to 276V and the default value is 264V 17 PowerWalke 04 Frequency range for bypass Parameter 2 Set the acceptable low frequency for bypass Ahle 50 Hz system Setting range is from 46 0Hz to 49 0Hz 350 60 Hz system Setting range is from 56 0Hz to 59 0Hz Gitte The default value is 46 0Hz 56 0Hz Parameter 3 Set the acceptable high frequency for bypass 50 Hz Setting range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected it s not
7. alarm Press and hold the button more than 0 5s to mute the buzzer Mute Down Button Please refer to section 3 4 9 for details gt Down key Press this button to display previous selection in setting menu Test Up gt Press and hold the two buttons simultaneous more than 1s to enter escape the Mute Down Button setting menu CVCF mode means converter mode 3 2 LED Indicators and LCD Panel LCD panel BYPASS LINE BATTERY FAULT un Q 3 9 LED indicators LED Indicators There are 4 LEDs on front panel to show the UPS working status Wok Bypass Une Fk e e e e e 9 9 9 mme 9 9 o 9 e 9 ome o e 9 9 mweywt e 9 ma e Note means LED is lighting and O means LED is faded 10 m O PowerWalke LCD Panel Backup Time Info Fault Info Input amp Battery Voltage Info Mute Operation Output amp Battery l i Voltage Info C LI LI Hz Battery Info lt Q i gt Load Info Y Mode Operation Info Display Function Backup time information H 1 T Indicates the backup time in numbers A tt L1 H hours M minutes S seconds Fault information N Indicates that the warning and fault occurs 68 Indicates the fault codes and the codes are listed in details in section 3 9 Mute operation Indi
8. allowed for running in Bypass mode under any situations Parameter 3 ENA Bypass enabled When selected Bypass mode is activated DIS Bypass disabled When selected automatic bypass is acceptable but manual bypass is not allowed Manual bypass means users manually operate UPS for Bypass mode For example pressing OFF button in AC mode to turn into Bypass mode 18 CMM 7 e 09 Battery maximum discharge time setting Parameter 3 000 999 Set the maximum discharge time from Omin to 999min UPS will shut down to protect battery after discharge time arrives The default value is 990min DIS Disable battery discharge protection and backup time will depend on battery capacity reserved reserved Parameter 2 Select Add or Sub function to calibrate battery voltage to real figure Parameter 3 the voltage range is from OV to 5 7V the default value is OV 19 14 Charger voltage adjustment Parameter 2 you may choose Add or Sub to adjust charger voltage Parameter 3 the voltage range is from OV to 6 4V the default value is OV Parameter 2 you may choose Add or Sub to calibrate inverter voltage Parameter 3 the voltage range is from OV to 6 4V the default value is OV Parameter 3 The maximum charging current could be adjusted Default value is 4A for long run model and 1A for standard model The setting range is 0 5A 6A for long run model and 0 5A 2A for standard model No
9. carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and the ground is present before maintenance or repair In this product the battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Batteries may cause electric shock and have a high short circuit current Please remove all wristwatches rings and other metal personal objects before maintenance or repair and only use tools with insulated grips and handles for maintaining or repairing When replace the batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion The batteries must be rightly deposed according to local regulation Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not disassemble UPS system 25 22 MLL 6 Specificati
10. or power failure UPS will backup power from battery and alarm will beep every 4 seconds LCD display T Oe Bypass mode Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes LCD display P Description When UPS is in AC mode or CVCF mode press Test key for more than 0 5s Then the UPS will beep once and start Battery Test The line between I P and inverter icons will blink to remind users This operation is used to check the battery status LCD display Fault status ot Lb 9 Description When UPS has fault happened it will display fault messages in LCD panel LCD display OVER LOAD 239 000 3 8 Fault Code Fault code Icon Fault event Fault code Icon Bus start failure EE None Inverter output short circuited 01 Bus over 02 Negative power fault Bus under Battery SCR short circuited 04 Bus unbalance 04 None Inverter relay short circuited 24 None 22 am 3 9 Warning Indicator Battery low Sp every second Battery unconnected Beeping every second Fe 7 EPO enable Beeping every second Fan failure Over temperature AN Beeping every second Charger failure Alel Beeping every second I P fuse broken Beeping every second Overload 3 times in 30min Beeping every seco
11. x 438 UPS unit 668 x 438 x 88 2U x 88 2U Dimension DXWXH mm 369 x 190 x 688 Battery pack 580 x 442x 190 x 688 Battery pack 580 x 438 x 133 3U 438 x 133 3U UPS unit 15 UPS unit 18 Long run Dimension DXWXH mm 369 x 190 x 318 580 x 438 x 88 2U 442x 190 x 318 668 x 438 x 88 20 Model Net Weight kgs ENVIRONMENT Operation Temperature 0 40 C i battery life cycle will be shorten when temperature is above 25 Operation Humidity 95 and non condensing Operation Altitude lt 1000m Acoustic Noise Level Less than 55dB 1 Meter Less than 58dB 1 Meter MANAGEMENT Smart RS 232 or USB Supports Windows A ad WindowsQ 7 Linux Unix and Optional SNMP Power management from SNMP manager and web browser Derate capacity to 60 of capacity in CVCF mode and to 90 when the output voltage is adjusted to 208VAC Tf the UPS is installed or used in a place where the altitude is above than 1000m the output power must be derated one percent per 100m Product specifications are subject to change without further notice D 26
12. 1 Turn on the UPS with utility power supply in AC mode 1 After power supply is connected correctly set the breaker of the battery pack at ON position the step only available for long run model Then set the input breaker at ON position At this time the fan is running and the UPS supplies power to the loads via the bypass The UPS is operating in Bypass mode NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on input breaker In Bypass mode the load is not protected by UPS To protect your precious devices you should turn on the UPS Refer to next step 2 Press and hold the ON button for 0 5s to turn on the UPS and the buzzer will beep once 3 A few seconds later the UPS will enter to AC mode If the utility power is abnormal the UPS will operate in Battery mode without interruption NOTE When the UPS is running out battery it will shut down automatically at Battery mode When the utility power is restored the UPS will auto restart in AC mode 2 Turn on the UPS without utility power supply in Battery mode 1 Make sure that the breaker of the battery pack is at ON position only for long run model 2 Press and hold the ON button for 0 5s to turn on the UPS and the buzzer will beep once 3 A few seconds later the UPS will be turned on and enter to Battery mode 3 Connect devices to UPS After the UPS is turned on you can conne
13. OoOo 22 Power Walker Online UPS PowerWalker 6000C LCD PowerWalker 10000C LCD PowerWalker VFI 6000C R LCD PowerWalker VFI 10000C R LCD Manual EN Uninterruptible Power Supply System 22 MLL Please comply with all warnings and operating Instructions in this manual strictly Save this manual properly and read carefully the following Instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully QO Power Walke Table of Contents 1 SAFETY AND EMC 3 TRANSPORTATION AND STORAGE mercero A A a AERAN 3 PREPARATION REN TERTII A A AAAA AEA A TEERAA ae 3 le AN OR E E 3 EAD AE RETRO ER E EE E EEE E E AE E E E A E A E E E 4 STANDARDS era 4 2 INSTALLATION AND OPERATION 2 2 889528 20x ua CREXMAERERN A REB MESS RF EN SEE 5 2 1 UNPACKING AND INSPECTION cc cnacacsvctcanconscaceniadeecsanseenenenca PPUDII ERR 5 2 2 REAR PANEL VIEW NER RTI K u LEEE
14. SA MEER ERE CERE UNE FARE RS NN MS EMEN ER 25 Yd STIORAUE SL EIE LAM E 25 E AM INTE INCE 25 MEI a Glue quio fee 26 am O PowerWalke 1 Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit 1 1 Transportation and Storage AN Please transport the UPS system only in the original package to protect against shock and impact AN The UPS must be stored in the room where it is ventilated and dry 1 2 Preparation AN Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist environments Do not install the UPS system where it would be exposed to direct sunlight or nearby heater Do not block ventilation holes in the UPS housing 1 3 Installation AN Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not block air vents in the housing of UPS The UPS must be installed in a location with good v
15. al Diagram 4 6KR L 10KR L Rear Panel Diagram 5 Rack Input Output Terminal Diagram 6 Rack Battery Pack Rear Panel 1 2 2 4 5 6 7 8 9 10 Output terminal External battery connector RS 232 communication port Intelligent slot USB communication Emergency power off function connector EPO connector Cooling fan Input circuit breaker Input Output terminal Refer to Diagram 3 and 5 for the details Maintenance bypass switch cam O PowerWalke 11 Grounding terminal 12 Utility input terminal 13 External maintenance bypass switch port 14 Battery pack output circuit breaker 2 3 Single UPS Installation Installation and wiring must be performed in accordance with the local electric laws regulations and execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are in compliance with the standard of rated capacity of UPS to avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all the connected devices before connecting to the UPS 4 Prepare wires based on the following table Wiring spec AWG ode UE Battery Ground NOTE 1 The cable for 6K 6KL sho
16. ast 0 5s If you press it again after the buzzer is muted the buzzer will beep again 2 Some warning alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 14 m O PowerWalke 10 Operation in warning status 1 When Fault LED flashes and the buzzer beeps once every second it means that there are some problems for UPS operation Users can get the fault code from LCD panel Please check the trouble shooting table in chapter 4 for details 2 Some warning alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 11 Operation in Fault mode 1 When Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Users can get the fault code from display panel Please check the trouble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery and so on after the fault occurs Don t try to turn on the UPS again before solving the problems Tf the problems can t be fixed please contact the distributor or service people immediately 3 For emergency case please cut off the connection from utility external battery and output immediately to avoid more risk or danger 12 Operation of changing battery numbers 1 This operation is only available for professional or qualified technicians 2 Turn off the UPS If the load couldn t be cut off you should remove the cover o
17. cates that the UPS alarm is disabled Output amp Battery voltage information LI Indicates the output voltage frequency or battery voltage CIC GU Vac output voltage Vdc battery voltage Hz frequency OUTP Load information Ey Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload SHORT Indicates the load or the output is short Mode operation information Indicates the UPS connects to the mains Indicates the battery is working lt X3 Indicates the bypass circuit is working EA Indicates the Inverter circuit is working a Indicates the output is working O P VM MEL Indicates the Battery capacity by 0 25 26 50 51 75 and 76 100 BATT AUT Indicates the battery is fault LOW BATT Indicates low battery level and low battery voltage Input amp Battery voltage information me Indicates the input voltage or frequency or battery voltage LI LLLI Vac Input voltage Vdc battery voltage Hz input frequency 3 3 Audible Alarm Description Buzzerstatus Muted Bypass mode Beeping once every 2 minutes Yes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Fan failure Over temperature Beeping once every second Bus start failure Inverter soft start failure CPU communication failure Bus under 12 m O PowerWalke 3 4 Single UPS Operation
18. ct devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel will display total load level 2 If it is necessary to connect the inductive loads such as a printer the in rush current should be calculated carefully to see if it meets the capacity of the UPS because the power consumption of this kind of loads is too big 3 If the UPS is overload the buzzer will beep twice every second 4 When the UPS is overload please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 80 of its nominal power capacity to prevent overload for system safety 5 If the overload time is over acceptable time listed in spec at AC mode the UPS will automatically transfer to Bypass mode After the overload is removed it will return to AC mode If the overload time is over acceptable time listed in spec at Battery mode the UPS will become fault status At this time if bypass is enabled the UPS will power to the load via bypass If bypass function is disabled or the input power is not within bypass acceptable range it will cut off output directly 4 Charge the batteries 1 After the UPS is connected to the utility power the charger will charge the batteries automatically except in Battery mode or during battery self test 2 Suggest to charge batteries at least 10 hours before use Otherwise the backup time may be shorter than expected time 13 am LLL
19. entilation Ensure enough space on each side for ventilation UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets The UPS can be installed only by qualified maintenance personnel An appropriate disconnect device as short circuit backup protection should be provided in the building wiring installation An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation Connect the earth before connecting to the building wiring terminal Installation and Wiring must be performed in accordance with the local electrical laws and regulations O PowerWalke 1 4 Operation AN Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fully disconnect the UPS system first press the OFF button and then disconnect the mains AN Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience
20. f maintenance bypass switch on the rear panel and turn the maintenance switch to BPS position first 3 Switch off the input breaker and switch off the battery breaker only available for long run model or disconnect battery wire for standard model 4 Remove the cabinet cover and then modify the jumpers JP1 153 on the control board to set the battery numbers as following table Battery Number ai y pini amp pin2 pin3 amp pin4 Pin5 amp pin6 pin7 amp pin8 X X 0 0 Note 1 connect with jumper 0 no jumper x the pins are for other functions 5 Modify the battery pack for the setting number carefully After complete it put the cover back and switch on the battery breaker for long run model 6 Switch on the input breaker and the UPS will enter Bypass mode If the UPS is in maintenance Bypass mode turn the maintenance switch to UPS position and then turn on the UPS 3 5 Abbreviation Meaning in LCD Display Abbreviation Display content Meaning Enable Disable 22 Normal mode not CVCF mode CVCF mode Subtract Reserved 3 6 LCD Setting There are three parameters to set up the UPS Refer to following diagram Parameter 1 It s for program alternatives Refer Parameter 1 to below table for the programs to set up Parameter 2 and parameter 3 are the setting options or values for each program Note Please select Up or Down button to change the
21. harge protection can be enabled or disabled through LCD panel control Refer to 3 7 LCD setting section 6 Test the batteries 1 If you need to check the battery status when the UPS is running AC mode CVCF mode you could press the Test button to let the UPS do battery self test 2 Users also can set battery self test through monitoring software 7 Turn off the UPS with utility power supply in AC mode 1 Turn off the inverter of the UPS by pressing OFF button for at least 0 5s and then the buzzer will beep once The UPS will turn into Bypass mode NOTE 1 If the UPS has been set to enable the bypass output it will bypass voltage from utility power to output sockets and terminal even though you have turned off the UPS inverter NOTE 2 After turning off the UPS please be aware that the UPS is working at Bypass mode and there is risk of power loss for connected devices 2 In Bypass mode output voltage of the UPS is still present In order to cut off the output switch off the input breaker A few seconds later there is no display shown on the display panel and UPS is complete off 8 Turn off the UPS without utility power supply in Battery mode 1 Turn off the UPS by pressing OFF button for at least 0 5s and then the buzzer will beep once 2 Then UPS will cut off power to output and there is no display shown on the display panel 9 Mute the buzzer 1 To mute the buzzer please press the Mute button for at le
22. nd 23 a O PowerWialke 4 Trouble Shooting If the UPS system does not operate correctly please solve the problem by using the table below Symptom Remedy o Indication and alarm in the The AC input power is not Check input cable firmly display panel even though the mains is d well d h ora connected well connected to the mains The icon and the warning code Set the circuit in closed Aash on LCD display and alarm EPO function is enabled position to disable EPO function beeps every second The external or internal battery 15 incorrectly connected UPS is overload Remove excess loads from UPS output UPS is overloaded Devices OVER LOAD connected to the UPS are fed Remove excess loads from UPS The icon and CET flash directly by the electrical output LCD display and alarm beeps twice network via the Bypass every second After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains The icon Zi and BATT FAULT flash on LCD display and alarm beeps every second Check if all batteries are connected well Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon UPS is overload too long and OVER LOAD lights on LCD display and becomes fault Then UPS shut alarm beeps continuously down automatically Remove excess loads from UPS output and restart it
23. nect them together it maybe causes the hazard of electric shock or fire AN Warning Only for long run model e Make sure a DC breaker or other protection device between UPS and external battery pack is installed If not please install it carefully Switch off the battery breaker before installation AN Warning e For standard battery pack there are one DC breaker to disconnect the battery pack and the UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external battery pack is installed Tf not please install it carefully Switch off the battery breaker before installation NOTE Set the battery pack breaker in OFF position and then install the battery pack b ww Fy e Pay highly attention to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultaneously The connection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correct
24. ons MODEL PowerWalker PowerWalker VFI PowerWalker PowerWalker VFI 6000 6000C R LCD 10000 10000C R LCD CAPACITY 6000 VA 4800 W 10000 VA 8000 W INPUT 110 VAC 3 at 50 Load Low Line Loss 176 VAC 3 at 100 Load Voltage Range Low Line Loss Voltage 10V 300 3 96 High Line Loss Voltage 10V 56Hz 64 Hz 60Hz system Single phase with ground 0 99 at 100 Load OUTPUT OUTPUT 0 0000 O Output voltage 208 220 230 240VAC AC Voltage Regulation Frequency Range Synchronized Range 46Hz 54 Hz 50Hz system 56Hz 64 Hz 2 60Hz system Frequency Range Batt Mode 50 Hz 0 1 Hz or 60Hz 0 1 Hz 10096711096 10min 11096713096 imin gt 130 1sec 100 110 30sec 110 130 10sec gt 130 1 Transfer Time m 0 ms EFFICIENCY gt 89 gt 90 BATTERY ype amp Numbers 12V 9Ahx 16 12V 9 Ah x 20 Recharge Time 9 hours recover to 9096 capacity 9 hours recover to 9096 capacity Default 10 Charging Current Max 2A 10 Charging Voltage 218 4 VDC 1 273 VDC 1 Depending on applications 16 20 adjustable Numbers Note When using internal batteries from 16 to 19 the unit will de rate according to the Long run i imd following formula P Prating x N 20 Model INPUNE Default 4 A 1090 ging Max 6A 1090 Charging Voltage 273 VDC 1 based on 20pcs batteries PHYSICAL PHYSICAL 000000 00000000 UPS unit 580
25. programs or parameters Parameter 2 Parameter 3 Programs available list for parameter 1 Bypass Y j Y Y Y 06 Reserved os Bypass mode seting Y 09 Battery maximum discharge time setting Y Y Y Y 16 m O PowerWalke Battery capacity and groups setting Y Backup time calibration Y Y means that this program can be set in this mode 01 Output voltage Parameter 3 Output voltage You may choose the following output voltage in parameter 3 208 Presents output voltage is 208Vac 220 Presents output voltage is 220Vac 230 Presents output voltage is 230Vac 240 Presents output voltage is 240Vac Parameter 2 Output Frequency 60 Hz CVCF mode Setting the output frequency You may choose following three Ha options in parameter 2 m ali 50 0Hz The output frequency is setting for 50 0Hz Hii d 60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output frequency will be 60 0Hz ATO is default setting Parameter 3 Frequency mode Setting output frequency at CVCF mode or not CVCF mode You may choose following two options in parameter 3 CF Setting UPS to CVCF mode If selected the output frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2
26. te Any modification should be suitable to battery specifications If input voltage is below 200VAC the UPS will reduce charging current to 4A automatically even though the setting is 6A 20 19 Battery capacity and groups setting Parameter 2 Set the battery capacity such as 7AH 9AH 10AH 12AH 17AH 26AH 40AH 65AH 100AH and so on The default value is 9AH Parameter 3 Set battery group range from 1 to 6 The default value is 1 group These parameters are for the battery backup time calculation Parameter 3 Calibrate the displayed backup time by adjusting this multiplier factor The formulation is listed below Displayed backup time Original calculated backup time x Multiplier factor The default value of multiplier factor is 1 0 and the range is from 0 5 to 2 3 7 Operating Mode Status Description Operating mode status AC mode Description When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at AC mode LCD display SAT CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode LCD display T PE n OCJ SUB E Q E MES m s 21 VM MEL Battery mode Description When the input voltage is beyond the acceptable range
27. uld be able to withstand over 50A current It is recommended to use 10AWG or thicker wire for safety and efficiency NOTE 2 The cable for 10K 10KL should be able to withstand over 63A current It is recommended to use 8AWG or thicker wire for safety and efficiency NOTE 3 The selections for color of wires should be followed by the local electrical laws and regulations 5 Remove the terminal block cover on the rear panel of UPS Then connect the wires according to following terminal block diagrams Connect the earth wire first when making wire connection Disconnect the earth wire last when making wire disconnection Input Neutral Output Line l Input Line Output Neutral Ground Terminal Block wiring diagram for 6K L 10K L NOTE 1 Make sure that the wires are connected tightly with the terminals am LLL NOTE 2 Please install the output breaker between the output terminal and the load and the breaker should be qualified with leakage current protective function if necessary 6 Putthe terminal block cover back to the rear panel of the UPS AN Warning Only for standard model e Make sure the UPS is not turned on before installation The UPS should not be turned on during wiring connection e Do not try to modify the standard model to the long run model Particularly do not try to connect the standard internal battery to the external battery The battery type and voltage and numbers may be different If you con

Download Pdf Manuals

image

Related Search

Related Contents

Samsung 27" WQHD-skärm för maximal produktivitet Bruksanvisning  Eton E5 Deep silver  Sonorous v2.0 by Nel-Tech Labs, Inc. Installation & User Manual  4-取付アダプター (プロジェクター一体) を取付 田  Scythe Kaze Master II  Samsung Smart Camera NX2000 18-55mm objektiv Bruksanvisning  "user manual"  Hunter 99112 Instructions / Assembly    角膜形状/屈折力解析装置 OPD  