Home
Eaton 5P3000RT uninterruptible power supply (UPS)
Contents
1. D Pull the plastic tab to remove the battery block and replace it Mounting the new battery module Carry out the above instructions in reverse order To ensure safety and high performance use only batteries supplied by EATON Take care to firmly press together the two parts of the connector during remounting Page 23 5 Maintenance Battery tray removal on rack models This operation must be performed when the UPS is switched OFF A Remove the middle panel B Remove the left hand side of the front panel by pushing the button and then by sliding the part C Disconnect the battery module by separating the town connectors never pull on the wires D Remove the metal protection cover in front of the battery two screws E Pull the plastic tab to remove the battery block and replace it Mounting the new battery module Carry out the above instructions in reverse order To ensure safety and high performance use only batteries supplied by EATON Take care to firmly press together the two parts of the connector during remounting Page 24 620 00082 01 us en 6 Appendices 6 1 Technical specifications Transformer Filter AVR Charger Inverter a MN Battery Tower 5P 750 5P 1000 5P 1500 Rack 5P 550 R 5P 750 R 5P 1000 R 5P 1500 R Output Power 120 V 550 VA 750 VA 1000 VA 1440 VA 420 W 600 W 770 W 1100 W Output Po
2. QIO 1 2 3 4 5 USB communication port RS232 communication port Slot for optional communication card Connector for ROO remote ON OFF or RPO Remote Power OFF control Outlets for connection of critical equipment Primary group 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for 7 8 9 1 2 3 4 5 connection of equipment Attached 6 ft input power cord for AC power source 5 15P LED indicating site wiring fault SWF alarm Ground screw USB communication port RS232 communication port Slot for optional communication card Connector for ROO remote ON OFF or RPO Remote Power OFF control Outlets for connection of critical equipment Primary group 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for 7 8 connection of equipment Socket for connection to AC power source Ground screw 620 00082 01 us en 2 3 Rack rear panels 5P 550 R 5P 750 R 5P 1000 R QOG l pi ere le 5P 1500 R T SPEI 5P 850G R D Seton C I 5P 1550G R 620 00082 01 us en 2 Presentation 1 USB communication port 2 RS232 communication port 3 Slot for optional communication card 4 Connector for ROO remote ON OFF or RPO Remote Power OFF control 5 Ou
3. E T N Installation and user manual Tower models 5P 750 5P 1000 5P 1500 5P 850G 5P 1550G 1U Rack models 5P 550 R 5P 750 R 5P 1000 R 5P 1500 R 5P 850G R 5P 1550G R Copyright 2012 EATON All rights reserved Service and support Call your local service representative 620 00082 01 us en Page 2 620 00082 01 us en IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries The 5P models that are covered in this manual are intended for installation in an environment within 0 to 40 C free of conductive contaminant This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Certification Standards e UPS directives UL 1778 4 edition UL listed e Performance IEC 62040 3 2001
4. The UPS is in battery mode and the battery is running low This warning is approximate and the actual time to shutdown may vary significantly Depending on the UPS Load the Battery Low warning may occur before the battery reaches 20 96 capacity 620 00082 01 us en Page 11 2 Presentation 2 6 Display functions Press the Enter button to activate the menu options Use the two middle buttons A and W to scroll through the menu structure Press the Enter 40 button to select an option Press the ESC button to cancel or return to the previous menu Menu map for Display Functions Main menu Submenu Display information or Menu function Measurements Load W VA Load A pf Output V Hz Input V Hz Battery V min Efficiency Power usage Control Load Segments Group 1 ON OFF Group 2 ON OFF These commands overrule user settings for load segments Start battery test Starts a manual battery test Reset fault state Clears active faults UPS restart required Restore factory settings Returns all settings to original values Reset power usage Clears power usage measurements Settings Local settings Sets product general parameters Input output settings Sets Input and output parameters ON OFF settings Sets ON OFF conditions Battery settings Sets battery configuration Fault log Displays event log or alarms
5. e Radiated emission FCC CFR 47 part 15 subpart B Class A e Surges withstand ability IEEE ANSI C62 41 Category A2 UL Listed Special Symbols De x e E The following are examples of symbols used on the UPS or accessories to alert you to important information RISK OF ELECTRIC SHOCK Observe the warning associated with the risk of electric shock symbol Important instructions that must always be followed Do not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed as it s explain in this manual For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Information advice help 620 00082 01 us en Page 3 Safety of Persons The system has its own power source the battery Consequently the power outlets may be energized even if the systems is disconnected from the AC power source Dangerous voltage levels are present within the system It should be opened exclusively by qualified service personnel The system must be properly grounded The battery supplied with the system contains small amounts of toxic materials To avoid accidents the directives listed below must be observed servicing of batteries should be performed or su
6. 00082 01 us en
7. Identification Com card address UPS Type Part Number Serial Number Firmware release 2 7 User settings The following table displays the options that can be changed by the user Description Available settings Default settings Language English Francais Deutsch Italiano Portugu s Espanol Pycckun Menus status notices and alarms UPS fault Event Log data and settings are in all supported languages English User selectable when UPS is powered for the first time Local setti ia LCD settings Modify LCD screen brightness and contrast to adapt to room light conditions Audible alarm Enabled Disabled on battery Always disabled Enable or disable the buzzer if an alarm occurs Enabled Output voltage 100 V 120 V 125 V On G model 200 V 208 V 220 V 230 V 240 V User selectable when UPS is powered for the first time Input thresholds Normal mode Extended mode Extended mode reduces lower input voltage to 70 V before UPS transfers to battery This can be used if the load can withstand low voltage supply Normal mode Sensitivity In Out settings High Low High for sensitive equipment UPS will easily transfer to battery when utility conditions are becoming bad Low for equipment that can withstand bad utility conditions in that case the UPS will not transfer to battery High Load segmen
8. locking the push button C Attach the center panel 620 00082 01 us en Page 15 3 Installation 3 4 Installation of tower models 3 5 Installation of rack model for 2 post option Follow steps 1 to 5 for 2 post mounting Use optional 1U 2 post rail kit Page 16 620 00082 01 us en 3 Installation 3 6 Installation of rack models 550 R Follow steps 1 to 3 for rack mounting 3 7 Installation of rack models Follow steps 1 to 4 for module mounting on the rails i The rails and necessary hardware are supplied by EATON 620 00082 01 us en Page 17 3 Installation 3 8 Installation of rack model for wall mounting Page 18 620 00082 01 us en 3 Installation 3 9 Communication ports Connection of RS232 or USB communication port The RS232 and USB communication ports cannot operate simultaneously 1 Connect the RS232 5 or USB 6 communication cable to the serial or USB port on o gt W the computer equipment 5 2 Connect the other end of the communication cable 5 or 6 to the USB 1 or RS232 2 communication port on the UPS oM d The UPS can now communicate 9 N with EATON power management software D d e LANE Installation of the communication cards optional standard on the Network bundle models It is not necessary to shutdown the UPS before installing a c
9. m 1 5P UPS 2 Quick start and safety instructions 3 User manual and IPSS Intelligent Power Software Suite CD ROM 4 RS232 communication cable 5 USB communication cable 6 1U Rack kit ears only for 550 R model 7 Front panel parts 8 2 connection cables for the protected equipments 850G and 1550G models 9 Cable locking systems 1 x 4 outlets 850G R models 1 x 6 outlets 1550G R models Packing materials must be disposed of in compliance with all local regulations concerning waste Recycling symbols are printed on the packing materials to facilitate sorting Page 14 620 00082 01 us en 3 Installation 3 2 Battery module connection Tower Caution Before starting the UPS please connect the internal battery Note A small amount of arcing may occur when connecting the batteries This is normal and does not damage the UPS or present any safety concern A Remove front panel B Connect the battery module never pull on the wires C Attach the front panel 3 3 Battery module connection Rack Caution Before starting the UPS please connect the internal battery Note A small amount of arcing may occur when connecting the batteries This is normal and does not damage the UPS or present any safety concern A Connect the battery module never pull on the wires B Attach the left hand side of the front panel by sliding it then by
10. the 5P range we invite you to visit our web site at www eaton com powerquality or contact your EATON representative Environmental protection EATON has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFCs HCFCs or asbestos Packing To improve waste treatment and facilitate recycling separate the various packing components e The cardboard we use comprises over 50 of recycled cardboard e Sacks and bags are made of polyethylene e Packing materials are recyclable and bear the appropriate identification symbol S PET Materials Abbreviations Number in S the symbols Polyethylene terephthalat PET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local regulations for the disposal of packing materials End of life EATON will process products at the end of their service life in compliance with local regulations EATON works with companies in charge of collecting and eliminating our products at the end of their service life Product The product is made up of recyclable materials Dismantling and destruction must take place in compliance with all local regulations concerning waste At the end of its service life the product must be transported to a processing center for electrical and electr
11. when AC input power is no longer available The necessary energy is provided by the battery The and 7 indicator illuminates solid The audio alarm beeps every ten seconds nm The connected devices are supplied by the battery Page 20 620 00082 01 us en 4 Operation Low battery warning e The v and indicator illuminates solid e The audio alarm beeps every three seconds The remaining battery power is low Shut down all applications on the connected equipment because automatic UPS shutdown is imminent End of battery backup time e LCD displays End of backup time e All the LEDs go OFF The audio alarms stops 4 5 Return of AC Input Power Following an outage the UPS restarts automatically when AC input power returns unless the restart function has been disabled and the load is supplied again 4 6 UPS remote control functions The 5P offers a choice between two remote control functions e RPO Remote Power Off allow a remote contact to be used to disconnect all the equipment connected to the UPS Restarting the UPS requires manual intervention e ROO Remote ON OFF allows remote action of button D to shut down the UPS These functions are obtained by opening a contact connected between the appropriate pins of connector 4 on the rear panel of the UPS see figures below e5lIe r G Remote control connection and test 1 Check that the UPS is O
12. 0 00082 01 us en 6 2 Glossary Backup time Battery test Cold start Deep discharge Load Low battery warning Normal AC input Percent load Personalisation Programmable outlets UPS UPS ON OFF controlled by software 620 00082 01 us en 6 Appendices Time during which the load can be supplied by the UPS operating on battery power Internal UPS test to check battery status The devices connected to the UPS can be started even if AC input power is not available The UPS operates on battery power alone Battery discharge beyond the permissible limit resulting in irreversible damage to the battery Devices or equipment connected to the UPS output This is a battery voltage level indicating that battery power is low and that the user must take action in light of the imminent break in the supply of power to the load The AC power line supplying the UPS under normal conditions Ratio of the power effectively drawn by the load to the maximum output of the UPS It is possible to modify certain UPS parameters set in the factory Certain UPS functions can also be modified by the software to better suit user needs Controllable outlets for automatic load shedding remote shutdown and sequential restart personalised using software Uninterruptible Power System This function enables or disables initiation of UPS ON OFF control sequences by computer power management software Page 27 Page 28 620
13. FF and disconnected from the AC input source 2 Remove connector 4 3 Connect a normally closed volt free contact 60 V DC 30 V AC max 20 mA max 0 75 mm 18 AWG cable cross section between the two pins of connector 4 see diagram ROO Contact open UPS shutdown Contact closed UPS start up UPS connected to AC power and AC power is available Note The local ON OFF control using button D overrides the remote control function Contact open UPS shutdown LED A goes ON To return to normal operation deactivate the remote external contact and restart the UPS by pressing button o 4 Plug connector 4 into the back of the UPS 5 Connect and restart the UPS following the previously described procedures 6 Activate the external remote shutdown contact to test the function Warning This connector must only be connected to SELV Safety Extra Low Voltage circuits 620 00082 01 us en Page 21 5 Maintenance 5 1 Troubleshooting Operation status Possible cause Action Batteries disconnected The UPS does not recognize the internal batteries If the condition persists contact your service representative The batteries are disconnected Verify that all batteries are properly connected If the condition persists contact your service representative Overload Power requirements exceeds the UPS capacity greater than 105 of nominal Remove some of the equipme
14. aia NMN Battery Tower 5P 850G 5P 1550G Rack 5P 850G R 5P 1550G R Output Power 230 V 850 VA 1550 VA 600 W 1100 W Output Power capacity 765 VA 1395 VA 208 V 540 W 990 W Output Power 200 V 765 VA 1395 VA 540 W 990 W AC Input power Rated input voltage Input voltage range Input frequency range 47 to 70 Hz 50 Hz system 56 5 to 70 Hz 60 Hz system Single phase 200 240 V 160 to 294 V Output on battery power 200 208 220 230 240 V 10 6 96 Voltage 50 60 Hz 0 1 Hz Frequency Battery Tower sealed lead acid maintenance free e Standard 2x12V 3x12V 7 Ah 9 Ah Rack 4x6V 6x6V 9 Ah 9 Ah Environment Operating 0 to 35 C 0 to 40 C temperature range e Storage 15 to 50 C temperature range Relative humidity Noise level 20 to 90 without condensation 40 dBA 1 The high and low thresholds can be adjusted using UPS settings 2 Up to 40 Hz in low sensitivity mode programmable using UPS settings 3 Adjustable to 200 208 220 230 240 V must be set to the identical AC power source value When the appliance is used in EU area use an external circuit breaker in front of line with rating 16 A 250 V which is IEC EN 60898 1 standard compliant When the appliance is used in America area use an external circuit breaker in front of line with rating 20 A 250 V This product is designed for IT power distribution system 62
15. alarms Correct the alarms and restart if necessary Verify that the J indicator illuminates solid indicating that the UPS is operating normally and any loads are powered and protected The UPS should be in Normal mode 4 2 Starting the UPS on Battery at least once nm Before using this feature the UPS must have been powered by utility power with output enabled Battery start can be disabled See the Cold start setting in ON OFF Settings on page 13 To start the UPS on battery 1 Press the D button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting The UPS cycles through Standby mode to Battery mode The indicator illuminates solid The UPS supplies power to your equipment Check the UPS front panel display for active alarms or notices besides the Battery mode notice and notices that indicate missing utility power Resolve any active alarms before continuing See Troubleshooting on page 22 Check the UPS status from the front panel to view the active alarms Correct the alarms and restart if necessary 4 3 UPS Shutdown To shut down the UPS Press the D button on the front panel for three seconds The UPS starts to beep and shows a status of UPS shutting OFF The UPS then transfers to Standby mode and the indicator turns off 4 4 Operation on Battery Power Transfer to battery power The connected devices continue to be supplied by the UPS
16. ill shutdown after 5 min of back up time if no load is detected on the output Disable Sleep mode Disable Enable If disabled LCD and communication will turn OFF immediately after UPS is OFF If enabled LCD and communication stays ON 1h30 min after UPS is OFF Disable Remote command Disable Enable If enabled shutdown or restart commands from software are authorised Enable RPO delay 0 s 1s 2 s 180 s Delays remote power off command 0 s Battery settings Automatic battery test No test Every day Every week Every month Available only if battery charge mode is set to constant charge Every week in constant charge otherwise following ABM Low battery 1 96 2 96 100 96 20 96 warning The alarm triggers when the set percentage of battery capacity is reached during a back up time Restart battery 1 96 2 96 100 96 0 96 level If set automatic restart will occur only when percentage of battery charge is reached Battery charge ABM cycling Constant charge ABM cycling mode Deep discharge Yes No Yes protection If set to Yes the UPS automatically prevents battery from deep discharge by adapting end of back up time voltage threshold 620 00082 01 us en Page 13 3 Installation 3 1 Unpacking and contents check Tower models a Ss Rack models ee e m
17. l be installed near the equipment and shall be easily accessible Never install the system near liquids or in an excessively damp environment Never let a foreign body penetrate inside the system Never block the ventilation grates of the system Never expose the system to direct sunlight or source of heat If the system must be stored prior to installation storage must be in a dry place The admissible storage temperature range is 15 C to 50 C The system is not for use in a computer room AS DEFINED IN the standard for the Protection of Information Technology Equipment ANSI NFPA 75 US installations only Contact Eaton resellers to order a special battery kit if needed to meet the ANSI NFPA 75 requirement Special Precautions Page 4 All handling operations will require at least two people unpacking installation in rack system Before and after the installation if the UPS remains de energized for a long period the UPS must be energized for a period of 24 hours at least once every 6 months for a normal storage temperature less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the Battery Module it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety In case of doubt don t hesitate to contact your EATON representative 620 00082 01 us en Conten
18. mode Yellow 4 The UPS has an active alarm or fault See On troubleshooting on page 18 for additional Red information Page 10 620 00082 01 us en 2 5 LCD description Operation status Load equipment status Efficiency and load group information 2 Presentation m Battery status As default or after 5 minutes of inactivity the LCD displays the screen saver The backlight LCD automatically dims after 10 minutes of inactivity Press any button to restore the screen The following table describes the status information provided by the UPS Note If other indicator appears see troubleshooting on page 18 for additional information Operation status Possible cause Action Standby mode The UPS is OFF waiting for start up command from user Equipment is not powered until b button is pressed Normal mode The UPS is operating normally The UPS is powering and protecting the equipment Battery LED is on 1 beep every 10 seconds the UPS is in Battery mode In AVR mode The UPS is operating normally but The UPS is powering the the utility voltage is outside normal equipment through a Automatic mode thresholds Voltage Regulation device The equipment is still normally protected No beep On Battery A utility failure has occurred and The UPS is powering the equipment with the battery power Prepare your equipment for shutdown End of backup time 1 beep every 3 seconds
19. nt from the UPS The UPS continues to operate but may shutdown if the load increases The alarm resets when the condition becomes inactive End of battery life The end of the battery life is reached Contact your service representative for battery replacement Event An UPS event occurs Example Set the contact back to its normal Remote Power OFF the RPO position and press l button contact has been activated to restart to shutdown the UPS and now prevents restart UPS fault The UPS has an internal fault The UPS does not protect the equipment anymore Note The alarm message and the UPS Serial Number then contact your service representative Page 22 620 00082 01 us en 5 2 Battery module replacement 620 00082 01 us en 5 Maintenance Safety recommendations The battery can cause electrocution and high short circuit currents The following safety precautions are required before servicing the battery components remove watches rings bracelets and all other metal objects from the hands and arms e use tools with an insulated handle Battery tray removal on tower models This operation must be performed when the UPS is switched OFF A Remove the front panel B Disconnect the battery module by separating the town connectors never pull on the wires C Remove the plastique protection cover in front of the battery one screw
20. ommunication card secured by screws 2 Insert the communication card in the slot Ge 1 Remove the slot cover 3 3 Secure the card cover with D the 2 screws 5 Characteristics of the optocouplers communication port optional e Pins 1 3 4 5 6 10 not used e Pin 2 common user DH Pin 7 low battery JE Ve e Pin 8 operation on battery 2 lt Je power L H e Pin 9 UPS ON equipment supplied n o normally open contact When a signal is activated the contact is closed between the common pin 2 and the pin for the corresponding signal Contact characteristics optocoupler e Voltage 48V DC max e Current 25 mA max e Power 1 2 W 620 00082 01 us en Page 19 4 Operation 4 1 Start up and Normal operation To start the UPS 1 2 3 4 Verify that the UPS power cord is plugged in The UPS front panel display illuminates and shows EATON logo Verify that the UPS status screen shows 5 Press the D button on the UPS front panel for at least 2 seconds The UPS front panel display changes status to UPS starting Check the UPS front panel display for active alarms or notices Resolve any active alarms before continuing See Troubleshooting on page 22 If the N indicator is on do not proceed until all alarms are clear Check the UPS status from the front panel to view the active
21. onic waste Battery The product contains lead acid batteries that must be processed according to applicable local regulations concerning batteries The battery may be removed to comply with regulations and in view of correct disposal 620 00082 01 us en 2 1 Standard installations Tower models Description Weights Dimensions inch mm Ib kg DxWxH 5P 750 22 7 10 3 13 6 x 5 9 x 9 1 345 x 150 x 233 5P 1000 24 4 11 05 13 6 x 5 9 x 9 1 345 x 150 x 233 5P 1500 35 3 16 01 17 5 x 5 9 x 9 1 445 x 150 x 233 5P 850G 21 9 9 9 13 6 x 5 9 x 9 1 345 x 150 x 233 5P 1550G 35 2 15 9 17 5 x 5 9 x 9 1 445 x 150 x 233 Rack models Description Weights Dimensions inch mm Ib kg DxWxH 5P 550 R 17 80 8 08 14 3 x 17 2 x 1 7 363 x 438 x 43 5P 750 R 30 60 13 88 20 0 x 17 2 x 1 7 509 x 438 x 43 5P 1000 R 32 50 14 72 20 0 x 17 2 x 1 7 509 x 438 x 43 5P 1500 R 43 50 19 72 21 8 x 17 2 x 1 7 554 x 438 x 43 5P 850G R 30 4 13 8 20 0 x 17 2 x 1 7 509 x 438 x 43 5P 1550G R 42 7 19 4 21 8 x 17 2 x 1 7 554 x 438 x 43 620 00082 01 us en 2 Presentation Page 7 2 Presentation 2 2 Tower rear panels Page 8 5P 750 5P 1000 5P 1500 Oma oBefE li a 2 A Q B o le c
22. ormal operatori cette s eec eg o acd 20 4 2 Starting the UPS on Battery ssssssssssssssssssseseeeeeeenee nennen nennen 20 AS UPS Sh tdOWLis a siiin ie e deterior e oae rad pea EEEE ER ERR d es do edd hw E S 20 4 4 Operatiori on Battery POWER E E Haas RCRERR TEN RES Eu RR RAN ess 20 4 5 Return Of AC Input POWER essene dete bbc pete teg cob i ceret RR a ada 21 4 6 UPS remote control fUnetlOns se sante vete REPE rrt redegi re dx Exe d te e ea ANTES 21 5 Maintenance une ne mere sus oet e epa pinos s oenste su Sree reer aU 22 5 1 Troubleshooting coit reno TRE e EET E E Pret rene Sede YR 22 5 2 Battery module replacerient 4 etn theta i t stt dad ge ca RR RO d Ro 23 GAD DOM CIC S t Eaa 25 6 1 Technical SPECICATION ie saccccsvcndescessaseaseseseasieaetavesednsns apavegatencessandataasaniu dhowestapaeesaveaesianneses 25 G22 GIOSSANY T 27 620 00082 01 us en Page 5 1 Introduction 1 1 Page 6 Thank you for selecting an EATON product to protect your electrical equipment The 5P range has been designed with the utmost care We recommend that you take the time to read this manual to take full advantage of the many features of your UPS Uninterruptible Power System Before installing your 5P please read the booklet presenting the safety instructions Then follow the instructions in this manual To discover the entire range of EATON products and the options available for
23. pervised by personnel knowledgeable about betteries and the required precautions when replacing batteries replace with the same type and number of batteries or battery packs do not dispose of batteries in a fire The batteries may explode batteries constitute a danger electrical shock burns The short circuit current may be very high Precautions must be taken for all handling Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or disconnecting battery terminals Determine if battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equip ment and remote battery supplies not having a grounded supply circuit Product Safety The UPS connection instructions and operation described in the manual must be followed in the indicated order A protection circuit breaker must be installed upstream and be easily accessible The system can be disconnected from the AC power source by opening this circuit breaker Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the system For PLUGGABLE EQUIPMENT the socket outlet shal
24. tlets for connection of critical equipment Primary group 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for connection of equipment 7 Attached 6 ft input power cord for AC power source 5 15P 8 LED indicating site wiring fault SWF alarm 9 Ground screw 1 USB communication port 2 RS232 communication port 3 Slot for optional communication card 4 Connector for ROO remote ON OFF or RPO Remote Power OFF control 5 Outlets for connection equipment Primary group 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for connection of equipment 7 Socket for connection to AC power source 8 Ground screw Page 9 2 Presentation 2 4 Control panel The UPS has a five button graphical LCD It provides useful information about the UPS itself load status events measurements and settings Tower models Power On On battery Alarm Indicator Indicator yel Indicator red green low Escape Up Down Enter On Off button Rack models Alarm Up On Off Indicator red button On battery Indicator t Escape yellow E3 ES P b MPa Enter Power On Down Indicator green The following table shows the indicator status and description Indicator Status Description On The UPS is operating normally Green E3 On The UPS is on battery
25. ts 1 Introductio eM 6 11 Environmental DrOtGCtIOfI correr na E FERRE QUE one AIEEE EE aan PH ERR RR 6 2 Presentation as acetic EI E ND M ME E 7 2 1 Standard nmstallations cte a t ex Rete ER SORTE RECO HT d 7 2 2 lower rear panels peccet eer etc abide epe kb Rd gud doque NETEN EAEE EREA NNE 8 2 3 Rack rear PAN CIS uoc rege e cans sauna steep ace wee sac M etu xa uv noatro td 9 2 4 Control partiel ccs tenete eet euo eer ventos qure eco Te VY D Du CE RN e e Ea d D 10 220 EC D descritiOn somit eveshtes cute etes oque ade pede bep e ev deed Ee dea tetto Vea Npuebu n 11 2 6 Display fUFCEIDIS cerei tetuer cec ttr cn en cd c ze 12 2 User Setligs metior e theses Aere R E 12 EMI esi A e fed PEN RR TR 14 3 1 Unpacking and contents check ssssssssssssssssssseseeeeeeeeeeeeren nennen 14 3 2 Battery module connection Tower 15 3 3 Battery module connection RACK xs o ce tre Hei Lais eels 15 3 4 Installation of tower models eene eene eene nnn enne 16 3 5 Installation of rack model for 2 post option sssssssssssss 16 3 6 Installatior of rack models bbO R iit oca de aede iter er sued tede ce Ra ud eere 17 3 7 Installation of rack models sssssssssssssssseseeeee ener eene eene enne 17 3 8 Installation of rack model for wall mounting sssssssss 18 3 9 COMMUNICATION DOLES coro scene co possc qu tatu ances drip otn PR ea pe Ee Ree sEd EO RED PUR 19 Wal rig MeL 20 4 1 Start upsand N
26. ts Auto start delay No Delay 1 s 2 s 65354 s The connected load is powered after the specified delay Group 1 3s Group 2 6s Page 12 620 00082 01 us en 2 Presentation Description Available settings Default settings In Out settings Load segments Auto shutdown delay Disable 0s 1 s 2 s 65354 s During a power outage authorizes UPS to turn off power to equipment connected to Group 1 and or Group 2 outlets This feature allows the shedding of non critical loads in order to conserve battery power for critical loads connected to the Primary group Group 1 Disable Group 2 Disable Overload prealarm 10 96 15 96 20 96 100 105 96 Sets critical percentage of load where alarm overload alarm occurs 105 96 ON OFF settings Cold start Disable Enable Enables the product to be started on battery power First cold start isw always disabled Enable Forced reboot Disable Enable If mains recover during a shutdown sequence if enabled shutdown sequence will complete and wait 10 seconds prior to restart if disabled shutdown sequence will not complete and restart will occur immediately Enable Auto restart Disable Enable Enables the product to restart automatically when mains recovers after a complete battery discharge Enable Energy saving Disable Enable If enabled UPS w
27. wer capacity 550 VA 750 VA 1000 VA 1440 VA 125 V 420 W 600 W 770 W 1100 W Output Power 100 V 458 VA 625 VA 833 VA 1080 VA 350 W 500 W 641 W 825 W is pi dead Single phase 100 125 V ated input voltage 80 to 162 V Input voltage range Input frequency range 47 to 70 Hz 50 Hz system 56 5 to 70 Hz 60 Hz system Output on battery power 100 120 V 10 6 temperature range Relative humidity 0 to 90 without condensation e Voltage 50 60 Hz 0 1 Hz Frequency Battery Tower sealed lead acid maintenance free e Standard 2x12V 2x12V 3x12V 7 Ah 9 Ah 9 Ah Rack 2x6V 4x6V 4x6V 6x6V 9 Ah 7 Ah 9 Ah 9 Ah Environment Operating 0 to 35 C 0 to 40 C temperature range Storage 15 to 50 C Noise level 40 dBA 1 The high and low thresholds can be adjusted using UPS settings 2 Up to 40 Hz in low sensitivity mode programmable using UPS settings 3 Adjustable to 100 120 125 V must be set to the identical AC power source value For 5P Models CAUTION To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code ANSI NFPA 70 This product is designed for IT power distribution system 620 00082 01 us en Page 25 6 Appendices 6 1 Technical specifications Transformer Filter AVR Charger Inverter
Download Pdf Manuals
Related Search
Related Contents
Ibai Sistemas - Liburutegiak Snom 870 12lines TFT Wired handset Black TP Carte à puce mise en oeuvre 高耐久1200 高耐久1200 Axis Q1604 ZXR10 2920/2928/2952(V1.0) Access Switch User manual (Volume II) Datalogic Falcon X3 OM, Gardena, Triturador de jardim, Art 03984-20, Art 03984 DUO-CEL Application Guide Copyright © All rights reserved.
Failed to retrieve file