Home
NuTone VX1000C vacuum cleaner
Contents
1. WALL INLET INSTALLATION The wall inlet design allows you to work outside the wall where assembly is easy and all the parts you need are accessible First you make a cutout into the wall and locate the flexible tubing attached to the inlet line which you previously threaded into the wall Then you attach the flexible tubing to the inlet mounting plate assemble the other inlet parts and make the wiring connections You place the inlet assembly into the wall cutout sandwiching the wall between the inner and outer parts and secure the inlet tightly to the wall with two screws Assemble and install the wall inlet as shown in the illustrations and as explained in the next few pages Be careful and patient as you make your first cutout and install your first inlet by following the procedure step by step the other inlets will be easy to install in very little time Making the Wall Inlet Cutout The wall inlet should be located 18 on center from the floor and directly in line with the attic or basement inlet tubing hole you have already drilled in the wall plate or header the wall inlet cutout must be exactly 3 high by 2 wide It is crucial that you make an accurate cutout and we have supplied a template to help you Place the template against the wall so that it is 18 on center from the floor Use a level along the top edge of the template to make sure it is square to the wall Mark your wall for the cutout
2. The tubing which connects the inlet into the trunk line is threaded through interior partition walls After you ve chosen an inlet location make sure the wall doesn t contain some hidden obstacle which will prevent you from running tubing to the inlet 12 FIGURE 30 Exterior Walls The insulation in these walls will prevent you from running tubing through them Electrical Wiring Wiring may not obstruct your tubing but you should always make sure that tubing does not damage the wiring Electrical outlets and wall switches are signs of wiring Ductwork Avoid choosing a section of wall that contains ducting If you see signs of ductwork such as floor or ceiling registers move your inlet location to another section of the wall Plumbing Plumbing may or may not prevent you from running tubing through a wall If you must choose a plumbing wall for an inlet location be extremely careful when making a cutout in the wall Wall Studs Make sure your location is between wall studs Locate studs by tapping walls looking for electrical outlet usually fastened to studs or noticing finishing nails in the floor molding INSTALLING THE INLET TUBING When your planning is complete you will have to determine where all the inlets and the power unit will be located You have also mapped out the location of your trunk line and found the access you need to run vertical tubing from one level of your house to another lev
3. access hole positioned so that final piping connections can be made by reaching through the access hole A generic cover plate can be used to cover the hole after installation sold separately e Attach low voltage wires to ORIGINAL VACPAN terminal connections marked low voltage only e Slide ORIGINAL VACPAN into mounting slot and secure to wall using two no 6 screws provided e Reach through access hole and make final fitting connections IN WALL INSTALLATIONS SV3828 UNIVERSAL SHORT 90 ELBOW ORIGINAL VACPAN FIGURE 47 AHO0002A 22 y PLATE a 1 ORIGINAL VACUSWEEP INLET VALVE INSTALLATION INSTRUCTIONS CONNECTION FROM BELOW Refer to Figure 48 Turn the power to the vacuum unit OFF Measure distance X between the kickplate face and the inside edge of the cabinet Then add 237 to the measured distance See Figure 48 1 Measure out the new distance X 234 from the cabinet door to the reference mark Drill a small reference hole straight down through to the basement See Figure 48 2 Locate the reference hole in the basement and verify that there are no obstructions within 2 of either side and 4 behind Cut a 2 diameter hole from the basement up into the base of the counter using the reference hole as a center See Figure 48 3 Using the reference hole as a center cut a 2 high x 6 wide rough opening in the kickplace face See Figure 48 4 Glue the long soc
4. 2 Run the inlet wire to the adjacent electric box If you must run wire through a stud drill directly through the center of the stud D 3 See Figure 28 Place the exposed ends of the two wires into the electrical box through a strain relief channel E Tighten the strain relief channel do not overtighten on the white sheathing leaving 1 2 of this sheathing exposed inside of the outlet box Fold the 6 of black and white wire into the outlet box Leave the wires to be connected by the electrician when plug receptacles are being installed Attention Power tools such as routers are not recommended for use with the inlet installation as removal of drywall with these devices may cause damage to the mounting plate and or inlet plug 4 Once drywall and finishing processes have been completed remove molded plug from mounting plate with the aid of a slot screwdriver and snap it into the wing slot at the back of the inlet F NOTE molded plug fits one way only with the narrow opening at the top Insert inlet into the mounting plate and secure inlet to mounting plate with screws provided NOTE All electrical devices such as the electrified inlet should be reported to the construction electrician for listing on the inspection report for building inspection purposes NOTE Plumb inlet to tubing using NuTone Model CF382S 90 ELL fitting A WARNING All location and installation direct connect electrified wall valves must
5. tube hole line up Figure 32 FIGURE 32 NOTE If the wall for mounting the Model 360 inlet is less than 1 2 a spacer must be used See Figure 23 on page 9 as a guide 2 Cut a length of tubing that will extend from inlet opening to a point below floor level or above ceiling level in attic installation Tape low voltage wire to tube and insert tube through predrilled hole to a level opposite the wall opening 3 Apply cement to tube and install flanged wall fitting Make sure fitting is well seated and sealed Figure 33 FLANGED FITTING FIGURE 33 4 Remove plaster frame from mounting bracket Pull low voltage wire through hole in bracket and insert bracket into cutout Secure bracket to flanged fitting with 4 screws provided Be sure seal is secure between flange fitting and mounting bracket Figure 34 FIGURE 34 5 Attach the low voltage wires to terminal screws on back 6 Refer to Figure 40 Align inlet mounting holes with of wall inlet Figure 35 If using 361 Rough in with CI370 mounting plate holes place inlet into mounting plate and Series Inlets refer to instructions on page 7 step 3 secure with provided screws shown in Figure 10 35 mm 6 mm FIGURE 37 FIGURE 38 FIGURE 35 MOUNTING 6 Insert wall inlet into bracket and secure with the two screws provided Figure 36 MOUNTING MOUNTING e PLATE HOLE 2 FIGURE 39 FIGURE 40 NOTE If CF382S shorter radius el
6. 10 into MOUNTING PLATE 11 At the same time push ELECTRICAL CONDUCTORS 12 and connectors 8 into WIRING COMPARTMENT 4 Back out the two screws that hold the wiring compartment in place Slip upper FINISHED WALL CLIP 13 under the screw heads and tightly fasten both wiring compartment and upper finished wall clip 13 with MOUNTING SCREWS supplied 5 Install the lower FINISHED WALL CLIP 14 with screws supplied 6 Secure Inlet Valve face plate 10 to mounting plate 11 using the two supplied color matched SCREWS 15 GR No LR 61865 No 2722 Finished Construction After pipe low voltage relay control wire electrical building wires and opening in wall has been cut 1 Remove mounting plate NAILING FLANGE 16 Use a hack saw or score with razor knife along dotted line and snap off Repeat step one from NEW CONSTRUCTION Install modified mounting plate with short 90 ELL glued in position into wall opening Repeat steps 2 6 from NEW CONSTRUCTION 9 I9 11 INSTALLATION IN EXISTING CONSTRUCTION LOCATING ACCESS KEYS IN EXISTING CONSTRUCTION Unless your home is a ranch style house where a single trunk line can run directly through the attic or basement you should first investigate your house to find the key to running your tubing from level to level Look for an accessible area free from obstructions that will accommodate the 2 tubing If you understand how your existing home is constructed it can be
7. by tracing around the inside of the template Then use your pencil to mark the screw hole locations through punched holes at the top and bottom of the template Remove the template from the wall Use an awl or icepick to punch pilot holes where you marked the two hole locations Now drill two 98 diameter holes using the pilot holes as the centers Locate and drill these holes exactly as marked with the template Also drill four pilot holes in the four corners of the marked area Make sure these holes are located inside the marked line Then using a utility knife score along the inside of the marked line For plaster walls score the plaster deeply being careful to stay inside the marked line Pilot holes must be inside marked line Next use a keyhole saw or a sabersaw to make the cutout Again be extremely along careful to cut along the W inside inside of the marked of marked line line CAUTION When cutting into plaster walls make sure the plaster is firm and secure around the cutout area Attaching the Inlet Mounting Plate Reach through the inlet hole and locate the inlet tubing Raise it up inside the wall until you locate the inlet tubing If the inlet is connected from the basement have a helper insert the inlet tubing into the access hole until you can see the flexible tubing Then pull the flexible tubing through the inlet hole and remove the low voltage wiring from insi
8. conform with all local and municipal building codes ES TAN VV LN SELL et NS Em AN FIGURE 27 FIGURE 28 10 C1358 SUPERVALVE WALL INLET amp ROUGH IN KIT see Figure 29 s JHAYDEN _ U S PAT 4 758 170 C Ah PAT 1 26 7 17 E 5 fy Li 9 CENTRAL VACUUM CLEANING SYSTEM WALL VALVE TYPE A FIGURE 29 ALO0008 SAFETY INSTRUCTIONS FOR HOUSEHOLD USE ONLY INSTALL ONLY ON A NOMINAL 120 V 60 Hz 7 A SUPPLY PROTECTED BY A MAXIMUM 15 A OVERCURRENT PROTECTIVE DEVICE THE PIN CONNECTOR ON THIS TYPE A WALL VALVE IS INTENDED FOR USE ON A NOMINAL 120 V 60 Hz 7 A SUPPLY ONLY IT IS REQUIRED TO BE WIRED BY A QUALIFIED ELECTRICIAN AND IS REQUIRED TO CONFIRM TO LOCAL ELECTRICAL CODES A WARNING Do not operate on wet surfaces New Construction 1 Install BUILDING WIRE CONDUCTORS 1 through the approved type electrical CONNECTOR 2 supplied until they protrude approximately six inches from connector Seat connector firmly into the opening atop the WIRING COMPARTMENT 4 Insert and secure LOCKING TAB 3 2 Splice wires from INLET VALVE RECEPTACLE 7 to the protruding building wire conductors with no 31 TWIST ON WIRE CONNECTORS 8 not supplied NOTE WHITE wire to WHITE wire amp BLACK wire to BLACK wire 3 Feed LOW VOLTAGE RELAY WIRES 5 through opening in the LVT COVER PLATE 6 and connect to the two contact screws of INLET VALVE FACE PLATE 9 4 Push Inlet Valve face plate
9. house It is recommended to vent the vacuum exhaust air to the outside of the house Exterior vented exhaust lines should be terminated using Model 393 wall caps or CI330 wall caps DIMENSIONAL CHART BAGGED EXHAUST B CENTER OF EXHAUST TO MOUNTING BRACKET HOLES MOUNTING BRACKET HOLES INTAKE u edd t SAT OVERALL HEIGHT FIGURE 53 AD0073 CYCLONIC EXHAUST B CENTER OF EXHAUST TO MOUNTING BRACKET HOLES CYCLONIC BAGGED CYCLONIC BAGGED BE vX475C VX475 VX550C 1000C VX550 1000 DENM 36 9 16 369 16 39 9 16 36 9 16 INTAKE 10 7 8 2 1 8 10 7 8 2 1 8 AD0004A FIGURE 54 32 WIRING This section refers to Figures 55 and 56 Grounding Instructions This appliance must be grounded If it should malfunction or break down grounding provides a path of least resistance for electric current to reduce the risk of electric shock This appliance is equipped with a cord having an equipment grounding conductor and grounding plug The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances A WARNING Improper connection of the equipment grounding conductor can result in a risk of electric shock Check with a qualified electrician or service person if you are in doubt as to whether the outlet is properly grounded Do not modify the plug provided with the appliance if it will not fit th
10. location so that final piping connections can be made UNDER CABINET INSTALLATIONS Refer to Figure 46 e ORIGINAL VACPAN requires a minimum 2 toe kick height e Once the ORIGINAL VACPAN location is determined cut a 6 long x 124 high slot in the cabinet toe kick to accept the ORIGINAL VACPAN e Run vacuum tube piping and low voltage wire from the main piping line to the ORIGINAL VACPAN location e Access for final piping connections must be made Access From Below If access is available from below cut an access hole through the subfloor underneath the cabinet positioned so that final piping connections can be made by reaching through the access hole Access Through Cabinet Floor Access can be made through the finished cabinet floor Cut a 2 x 3 access hole positioned so that final piping connections can be made by reaching through the access hole CI366 Trim Plate can be used to cover the hole after installation Access Through Cabinet Toe Kick Access can be made through the cabinet toe kick by cutting up to 10 x 4 slot and using the ORIGINAL VACPAN Quick Trim Cover Plate CI366 Trim Plate sold separately If required score back of Quick Trim Cover Plate with a knife and snap along grooves for height adjustment e Attach low voltage wires to ORIGINAL VACPAN terminal connections marked low voltage only e Slide ORIGINAL VACPAN into mounting slot and secure to toe kick using two no 6 scre
11. possible between located studs drill a small reference hole through the floor and subfloor Locate this reference hole from beneath and measure over approximately 1 to center of base plate of wall Ensure you have 1 clearance from any obstacles if connecting from below See Figure 50 2 EA Emm LZ CUT 8 203 mm ACCESS HOLE BEHIND REFERENCE 8 HOLE 203 mm REFERENCE HOLE 8 203 mm ACCESS HOLE 3 If installation is from below use a 2 diameter hole saw to remove wood floor and keka ries di ut base plate sufficient to locate VacuSweep Inlet Valve centered over the reference hole See Figure 50 3 Using the reference hole as a center cut a 2 51 mm CENTRAL VAC PIPE COUPLING DO NOT GLUE THIS CONNECTION 2 51 mm CENTRAL VAC PIPE 4 COUPLING TERMINAL CONNECTIONS GLUE THIS ERES E ERIE DULL 2 high x 65 wide rough opening in the wall Vi COUPLING PIPE DEEE I aeu NET VALVE HE o ie and baseboard See Figure 50 4 gt p ENERO 5 Glue the long socket of the tight elbow 6 wisconvection access NES part no CF382S onto a section of 2 central AD0046A HOLE vacuum pipe Make the terminal connections to the VacuSweep Inlet Valve by sliding the lowvoltage wire into wire clips Turn the power FIGURE 49 to the vacuum unit on to test the connection After successful completion of the test turn power to the vacuum unit OFF Wrap a p
12. vary from state to state This warranty supersedes all prior warranties WARRANTY SERVICE To qualify for warranty service you must a notify NuTone at the address stated below or telephone 1 800 543 8687 b give the model number and part identification and c describe the nature of any defect in the product or part At the time of requesting warranty service you must present evidence of the original purchase date Date of Installation Builder or Installer Model Number and Product Description IF YOU NEED ASSISTANCE OR SERVICE For the location of your nearest NuTone Independant Authorized Service Center Residents of the contiguous United States Dial Free 1 800 543 8687 Please be prepared to provide Product model number Date and proof of purchase The nature of the difficulty Residents of Alaska or Hawai should write to NuTone Inc Attn Department of National Field Service 926 West State Street Hartford WI 53027 Rev 06 2009 For Models VX1000 amp VX1000C Nulone Eight Year Limited Warranty WARRANTY OWNER NuTone warrants to the original consumer purchaser of its products that such products will be free from defects in materials and workmanship for a period of eight 8 years from the date of original purchase THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE During this time period NuTone will at its option repair
13. 800 543 8687 b give the model number and part identification and c describe the nature of any defect in the product or part At the time of requesting warranty service you must present evidence of the original purchase date Date of Installation Builder or Installer Model Number and Product Description IF YOU NEED ASSISTANCE OR SERVICE For the location of your nearest NuTone Independant Authorized Service Center Residents of the contiguous United States Dial Free 1 800 543 8687 Please be prepared to provide Product model number Date and proof of purchase The nature of the difficulty Residents of Alaska or Hawai should write to NuTone Inc Attn Department of National Field Service 926 West State Street Hartford WI 53027 Rev 06 2009 TROUBLESHOOTING GUIDE Read Before Calling Service Center Trouble Possible Cause 1 Loss or decrease of vacuum 1a Disposable filter bag or debris bucket are completely full occurs 1b Obstruction in the hose A blockage in the hose can be determined by inserting the hose into any wall inlet and while power unit is running check each additional inlet for normal suction by holding the palm of your hand over the open inlet If normal suction is felt at all other inlets insert the hose into a second inlet If the blockage still exists it is located in the hose However if the blockage does not occur when the hose is changed the blockage is probably located in the tubing system leading to t
14. ARRANTIES EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE During this time period NuTone will at its option repair or replace without charge any product or part which is found to be defective under normal use and service THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP STARTERS OR TUBES FILTERS DUCT ROOF CAPS WALL CAPS AND OTHER ACCESSORIES FOR DUCTING This warranty does not cover a normal maintenance and service or b any products or parts which have been subject to misuse negligence accident improper maintenance or repair other than by NuTone faulty installation or installation contrary to recommended installation instructions The duration of any implied warranty is limited to the four year period as specified for the express warranty Some states do not allow limitation on how long an implied warranty lasts so the above limitation may not apply to you NUTONE S OBLIGATION TO REPAIR OR REPLACE AT NUTONE S OPTION SHALL BE THE PURCHASER S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE Some states do not allow the exclusion or limitation of incidential or consequential damages so the above limitation or exclusion may not apply to you This warranty gives you specific legal rights and you may also have other rights which
15. BM T Nulone BUILT IN CENTRAL CLEANING SYSTEM INSTALLATION INSTRUCTIONS For Power Unit Models VX475 VX550 VX1000 VX475C VX550C and VX1000C Broan NuTone LLC 01 095 rd Wisconsin www nutone com 888 336 3948 To register this product visit www nutone com 2 5 3l Ill s Part No 30042322 rev 08 TABLE OF CONTENTS SYSTEM PLANNING AND LAYOUT sseeele ehh 3 4 Cs 3 LOCAUING ING POWEMUMIL T 4 Tubing and Wall Inlet Locations swa ase s ae hic cond PEDES TEE ENTE eUREESO ENITAT AUTERA RP ERE EE 4 GENERAL INSTALLATION GUIDE eseeee eere 5 6 WOO MISUING PRCPTr m 5 Working with Plasti TUDING 22225254464 250 cu ees Ede sd ee oa ee A RUE Rd E bet Bases eens eee 5 6 INSTALLATION IN NEW CONSTRUCTION 0 0 ccc eee hrs 7 11 Wall Nlet THOBOIIH S s24 65a ew een eae eed cane cee ee od bam ohare a EDERE RA E eee eee ees 7 MSMO Me TUDING s css ans eee ee ace ee ho Se a we eee eee ae eee IDOL ee mE ee eee ae Bene Ae kare Bes 8 rcg acu TTP L OOIfO pre 9 Models CI370 amp 360 WallInlets lllllllleeee RR RIRIRIRIRRRRI Il 9 Model 330 WAlLINGT PP C IPETTRrP 9 Model CI395RK Electravalve Electrified Inlet Insta
16. DO NOT GLUE THIS CONNECTION GLUE THIS CONNECTION LONG SOCKET PIPE VacuSweep INLET VALVE 2 51 mm CENTRAL VAC PIPE FIGURE 48 TERMINAL CONNECTIONS Eae cix um L3 SCREWS V2 002022222 GLUE THIS DO NOT GLUE CONNECTION THIS CONNECTION T 51 mm CENTRAL VAC PIPE 6 N TERMINAL WIRES AD0045A 23 CONNECTION FROM BEHIND 4 Using the reference hole as a center cut a 2 high x 6 wide rough opening in the kickplate face See Figure 49 4 Refer to Figure 49 gn op J p 9 5 Insert a coupling part no CF388 onto the rear of the k TUER Me power a9 the vacuum unit Orr ee S housing DO NOT glue this connection Designed for location under the cabinet for the VacuSweep Inlet friction fit See Figure 49 5 Make the terminal Valve so that It put be connected to the central bodega connections to the VacuSweep Inlet Valve by sliding the Pipe Measure distance X between the kickplate face low voltage wire into wire clips Turn the power to the and the inside edge of the cabinet Then add 234 to the vacuum unit on to test the connection After successful measured distance See Figure 49 1 Measure out the di X 4 294 f h bi d h completion of the test turn power to the vacuum unit NEW OISTANCE Us aula On Secolo Goer tothe OFF Insert the VacuSweep Inlet Valve into the cabinet reference mark l base and pipe 2 Drill a small reference hole straight down through to
17. GROUNDED OUTLET BOX NEMA 6 20R TO OTHER INLETS AE0004A LOW VOLTAGE WIRE HARNESS LOW VOLTAGE WIRE BP z 5 CRIMP CONNECTORS FIGURE 56 FINAL SYSTEM CHECK Be sure all inlets are closed and soil bag for VX475 VX550 amp VX1000 models is in place Check switch on power unit for manual on off operation Check that indicator light on side of power unit is lit and is in green mode Check each wall inlet to be sure contacts activate power unit when hose is inserted and switched on if applicable If using CI370 or C1358 Indicating Inlet be sure LED on inlet is green when hose is inserted switched on If Central Cleaning hose is not available at the time a short piece of wire can be used to short contacts in wall inlet to activate power unit Check each wall inlet and tubing connection for air leaks Check power unit for leaks around inlet tube and dirt receptacle 34 Make sure the filter bag is properly installed in the power unit according to directions printed on the bag or in homeowner s manual Remove the extra bag and owner s manual from the power unit dirt receptacle It may be convenient to store them with the cleaning tools and accessories Now it s time to enjoy the benefits of a NuTone Central Cleaning System See Homeowners Manual for operating and care information WARRANTY For Models VX475 amp VX475C Nulone Two Year Limited Warranty WARRANTY OWNER NuTone warrants to t
18. LEARANCES L D4 i 24 RT VX475 Series 11 VX550 and VX1000 Series 13 75 Z 24 MINIMUM TO CEILING i FRONT VIEW UTILITY BER VALVE MINIMUM ABOVE FLOOR AD0072 FIGURE 51 3 4 TYP UPPER MOUNTING HOLES 4374s MIN HEIGHT LOWER MOUNTING 1 TYP HOLES AD0044A FIGURE 52 TUBING CONNECTIONS AT POWER UNIT This section refers to Figures 53 and 54 Your VX Series power units are capable of being connected to the intake vacuum trunk line from either side Select the intake connection to be used On some installations you may connect the vacuum air intake into both intakes CAUTION Models VX475 VX550 and VX1000 will attach to the upper intake connections See Figure 53 Models VX475C VX550C and VX1000C will attach to the lower intake connections See Figure 54 1 Using provided coupling part no V127 attach the utility valve assembly with the vacuum trunk line feeding into the power unit The utility valve can be installed on the left or right hand side V 127 2 Cap off the unused intake tube with the green plastic cap provided 3 Attach exhaust tube to power unit using provided coupling part no V127 if vented to the outside 4 Make sure all tubing connections are air tight 5 The exhaust should NOT be vented into a wall ceiling or concealed space in the
19. allow several rooms to be cleaned from a single inlet using a 30 foot long hose The tubing installation should consist of a main trunk line running from the farthest wall inlet to the power unit location with branch lines running to each additional inlet Keep all tubing lines as straight as possible and use as few fittings as possible Beginning at the area farthest from the power unit choose a tentative inlet location Measure 30 feet from the proposed inlet location to the farthest corner of the rooms to be cleaned by that inlet to determine if inlet location is proper If working from blueprints or building plans drawn at 14 1 ft scale use a 7 chain as your guide to determine inlet locations Locate inlets within six feet of an electrical receptacle to allow use of optional current carrying hose Be sure inlets will not be blocked by doors or furniture Be sure inlets will not interfere with electrical plumbing or other mechanical installations Move tentative inlet location if necessary Use the same procedure to determine each additional inlet location always working toward the power unit GENERAL INSTALLATION GUIDE ANWARNING When applicable local regulations comprise more restrictive installation and or certification requirements the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expenses TOOL LISTING Depending on your installati
20. an complete the network of tubing that connects your inlets to the power unit This network consists of the following parts 90 Elbows Used for connecting the inlet lines to the branch lines Also used for making smooth 90 turns in branch lines or trunk lines 45 Elbows Used for a 45 tubing turn in branch or trunk lines 90 Tees Used to connect branch lines to the trunk lines Stop Couplings Used to join two lengths of tubing Flexible Tubing Used to bypass obstacles or to make difficult S turns in branch lines This tubing is supplied in a 36 length it is not the same as the inlet flex tube PVC Tubing 8 straight sections of tubing used for inlet branch and trunk lines Use the tubing and fittings to run branch lines from the inlet tubing to a main trunk line Begin at the farthest inlet from the power unit and work your way toward the power unit When you assemble sections with elbows and tees make sure the curve in the fitting is aligned so that the air flows toward the power unit Assemble the entire network of tubing and fittings making sure every joint is accurately cut and aligned Then go back and cement all the joints You may run the wiring and make the wiring connections after the network is assembled and cemented or you may make the wiring connections as you assemble the network Use the method that best suits your needs 26 Beginning the Trunk Line Start the inlet line wh
21. ave drilled for the power unit s intake tube Place a 90 elbow over the hole and cut the trunk line to fit into this final elbow Allow 5 8 of tubing to fit into the elbow s collar Connect the elbow to the trunk line so that it aligns over the intake access hole You will make the intake tube connection itself after you have installed the power unit E Mid Mie gt E M ay 4 Esdr rA GS When you are satisfied that all fittings and tubing are aligned for maximum air flow make sure that all your cuts are square and that all joints are tight Then prepare the tubing and cement the joints as described in Working With Plastic Tubing page 5 Connecting the Low Voltage Wiring Ideally you will run the wiring and make all the wiring connections after you have completed the tubing system Of course the inlet wiring must be run at the time the inlet tubing is threaded through the walls Run the low voltage wiring along the trunk line at approximately 12 18 intervals use electrical tape to secure the wire to the tubing Then run wiring along the branch lines from the inlet lines to the trunk line Also secure this wiring with electrical tape At the joint of the inlet line and the branch line make a two wire connection Use wire nuts to make the connections and insulate each connection with electrical tape At the junction of every branch line and the trunk line cut the trunk line wire and con
22. bow is used it may be necessary to use the short mounting screw to avoid interference with elbow FIGURE 36 MODEL 330 amp CI335 SERIES WALL INLET INSTALLATION CF329 ROUGH IN 1 Make cutout according to dimensions in Figure 37 2 Refer to Figure 38 Break off nail plate at scored line 3 Refer to Figure 39 Glue elbow to mounting plate place assembly into cutout and attach elbow to tubing inside the wall 4 Make sure mounting holes are exactly at top and bottom 5 Connect 2 conductor low voltage wire to terminal screws on back of wall inlet 19 FLOOR INLET INSTALLATION IN NEW amp EXISTING CONSTRUCTION Model CI370 or 360 Series Inlets 361 Rough In 1 Refer to Figures 41 and 42 After floor inlet location has been selected cut a 3 x 2 square hole in floor Center line of inlet must be located at least 212 from wall to allow cover to be opened when hose is inserted Determine direction of tubing and attach appropriate flanged fitting to mounting bracket with four 4 screws supplied Be sure mounting bracket flange does not interfere with tubing and seal is securely in place Refer to Figure 43 Position bracket with frame and flanged fitting assembly into cutout from below and secure to sub floor Refer to Figure 44 Large end of Model 399 extension sleeve should be cut to length to allow proper seating of inlet against floor or carpet Refer to Figure 45 Pull low voltage 2 conductor wire th
23. branch line to length and insert it into the tee Check to make sure the cut is straight and even Connect the next section of tubing to the out take side of the tee fitting Continue the trunk line until you come to another branch line junction point Branch Line Make sure air flows toward Power Unit DET LI LA Q gt He LB To Power Unit Circumventing an Obstacle Wherever possible the branch lines should connect to the trunk line in straight paths The fewer turns in a tubing system the more efficient air flow Accordingly you should locate the inlets to avoid zig zags in the branch lines But sometimes when you just can t avoid an obstacle you are required to construct the tubing around it In the example illustrated here you might run the branch line at an angle to avoid a chimney Then once the branch line has run past the chimney you can use a 45 elbow to turn the branch line back perpendicular to the trunk line Again the branch line and the trunk line connect with a 90 tee You can also use the supplied 36 piece of flexible tubing to run a branch line around an obstacle See Using Flexible Tubing on page 30 Completing the Trunk Line Continue to run the trunk line toward the power unit connecting all branch lines as you go along Again make sure you connect all fittings with the air flow toward the power unit Bring the trunk line to the access hole you h
24. de the tube If the end of the flexible tubing is not even trim it so that it is exactly even Now remove the nail flange used for new construction from the inlet mounting plate Use pliers to bend this flange along the scored lines until you can break it off Nail Flange Apply cement to both the inside of the flexible tubing and to the outside of the mounting plate s tube ring Insert the mounting plate s tube ring in the flexible tubing and twisting the pieces as you join them to spread the cement and align the mounting plate in a vertical position Hold the assembly in place for a few minutes as the cement sets allow 5 minutes for the cement to completely dry Now strip the ends of the two low voltage wires and then connect the wires to the screw terminals on the back of the inlet cover Make sure the wires are tightly secured under the terminal screws When the wiring is complete assemble the inlet cover to the tube guard and mounting plate Insert the top screw through the entire inlet assembly until the screw engages the mounting plate Completing Inlet Assembly Once you have attached the mounting plate to the flexible tubing pull the low voltage wire through the top wiring hole in the mounting plate MOUNTING PLATE 17 Installing the Inlet When you place the inlet into the wall cutout the mounting plate and tube guard slip inside the wall the inlet cover remains on th
25. e outlet have a proper outlet installed by a qualified electrician This appliance is for use on a standard 120 V a c dedicated 20 amp branch circuit with a NEMA 5 20R receptacle for VX475 and VX550 models For VX1000 models a nominal 240 V a c dedicated 20 amp branch circuit with NEMA 6 20R receptacle is required Make sure that the appliance is connected to an outlet and has a grounding attachment plug that looks like the plug shown in either Figure 55 or 56 depending on the model No adapter should be used with this appliance 1 Using crimping pliers connect low voltage wire 18 gauge 2 conductor model 376 UL to crimp connectors 2 Connect the low voltage wire to the low voltage wire harness located at the back of the power unit the use of long nose pliers is recommended See Figure 57 3 The power unit is equipped with a 6 foot grounded cord Ensure power cord is plugged into a properly grounded receptacle VX475 amp VX550 SERIES NOTE INLET LEADS TO BE CONNECTED TO POWER UNIT TERMINALS USING CRIMP CONNECTORS AND LOW VOLTAGE NORTH AMERICA AC ELECTRIC WIRE HARNESS OUTLET WIRE HARNESS 120 VOLT GROUNDED BB e OUTLET BOX L 1 INLETS AE0003A LOW VOLTAGE Qus LOW VOLTAGE WIRE ee CRIMP CONNECTORS FIGURE 55 VX1000 SERIES NOTE INLET LEADS TO BE CONNECTED TO POWER UNIT TERMINALS USING CRIMP CONNECTORS AND LOW VOLTAGE WIRE HARNESS NORTH AMERICA AC ELECTRIC OUTLET 240 VOLT
26. e outside Holding the inlet assembly between your thumbs and fingers angle the bottom of the mounting plate into the cutout Push the assembly downward until you have clearance at the top of the cutout Push the top of the mount ing plate into the cutout and lift the assembly upward until the top screw seats in the predrilled hole At this point the wall should be sandwiched between the mounting plate and the frame plate Insert the bottom screw into the inlet cover and through the other parts Give the screw a few turns until it firmly engages in the mounting plate Now level and slightly lower the assembly Make sure the wall is sandwiched between the inner and outer parts you ll be able to feel if mounting plate is firmly centered on the inside of the wall Hold the inlet in place and gradually tighten down each screw a little bit at a time If you completely tighten down one screw at a time the mounting plate may pull away from the wall at the loose end and slip back into the cutout Complete all your wall inlet installations in this manner If your cutouts are accurate each wall inlet will install more quickly and easily CI370 OR 360 SERIES INLETS CF361 OR CF361F ROUGH IN NOTE If 330 wall inlet is being used refer to Models 330 amp CI335 Series Wall Inlet on next page 1 If area is clear cut an inlet opening in the wall approximately 18 above the floor Make sure wall opening and 272
27. ed to circumvent an obstacle or to make a difficult turn In the example illustrated here the flexible tubing is used in order to run a branch line under a support beam Attach this tubing to the PVC tubing cementing only the outside of the PVC tubing as you would for a hard fitting connection Whenever you use the flexible tubing you must secure both ends of it with support strapping POWER UNIT INSTALLATION Refer to page 4 for information on locating the power unit MOUNTING This section refers to Figures 51 and 52 CAUTION On models VX475 VX550 and VX1000 DO NOT REMOVE either of the grey seals covering the BOTTOM red cap plugs Removing these seals will void the warranty Only remove and use the outlets covered by the TOP green plugs For VX475C VX550C and VX1000C models DO NOT REMOVE either of the grey seals covering the TOP red cap plugs Removing these seals will void the warranty Only remove and use the outlets covered by the BOTTOM green plugs DO NOT REMOVE WARRANTY VOID IF SEAL IS BROKEN NE PAS ENLEVER GARANTIE ANNUL E SI CE SCEAU EST BRIS Your power unit mounts to the wall using a mounting system The wall mounting bracket provided with your power unit mounts to the wall It has 4 fingers at the top and 4 others at the bottom The power unit has 4 upper openings and 4 lower openings which are designed to slide onto the fingers of the wall mounting bracket Be sure to follow the instructions b
28. ees P3 ed SEU TUE Sa a 58s 34 WARRANTY aoauescneedndPueon reads ach Uu euh Seok Gres Gans Stach U eet Ge Hs Stews Sed Seok Gee Seok Seed Ed 35 TROUBLESHOOTING GUIDE 0 0 eee eee tenet hn hrs 36 37 SYSTEM PLANNING AND LAYOUT The NuTone central cleaning system consists of a power unit PVC tubing and fittings wall inlets a flexible hose and various cleaning attachments The power unit is designed to be wall mounted away from the living area of the home and connected to the living area by means of permanently installed in wall tubing fittings and inlets Generally an installation will require 3 to 4 inlets and 16 to 20 feet of tubing per inlet It is suggested that a floor plan be used to more accurately determine the quantity of materials needed Use the following examples as an aid in planning the installation in either new or existing construction You should be able to adapt the examples shown to your specific home layout THE RANCH STYLE HOUSE Here the power unit is mounted in the garage The intake and exhaust tubing the only exposed tubing in the installation runs up the garage wall and EXHAUST into the attic The trunk line runs INLET LINE horizontally through the attic from the 7 power unit to the farthest inlet location Branch lines spread throughout the attic connecting the trunk line to the a inlet tubing Each inlet tube is threaded A vertically through an inside wall Located i in hallways and i
29. el You should have acquainted yourself with the methods of joining plastic tubing and acquired the tools you ll need to install your NuTone Central Vacuum System Now you can begin installation The first step to install the inlet tubing which connects the wall inlets to the branch lines As explained before the inlet lines run inside interior walls You will find access to these walls through your attic or basement Briefly you want to find the exact location in the wall drill an access hole through the wall plate or header and insert the tubing into the wall cavity This part of your installation requires close observation and careful measurements Take your time and make sure you accurately line up your access holes with the locations you ve chosen for your wall inlets Locating Attic Access Holes Drill the access holes directly above the inlet location To accurately locate the access hole you must find the space between wall studs where the inlet is to be located Observe the area around the inlet location Look for references you might be able to find in the attic electrical wiring ductwork doorways etc Measure and note the distance from these references to the inlet location Enter the attic and find the inlet wall Have a helper downstairs knock on the top of the wall right above the inlet location locate the general area by following the sound Most likely you will have to clear away insulation Ask your helper to con
30. elow for proper installation 1 Locate power unit within six feet 1 82 m of a grounded electrical outlet NuTone s models VX475 and VX550 Series require a 120V dedicated 20 amp branch circuit with a NEMA 5 20R receptacle VX1000 Series require a 240 VAC dedicated 20 amp branch circuit with a NEMA 6 20R receptacle 2 Refer to Figure 51 to maintain minimum wall clearance dimensions CAUTION Make sure to fix the wall mounting bracket with the screws directly onto a stud for a solid installation 3 Position and install the wall mounting bracket with the provided screws Refer to Figure 52 for proper mounting dimensions 4 Using the provided mounting screws secure the mounting bracket on the wall through two upper and two lower mounting holes 5 Prior to installing the power unit onto the wall you must do the wiring see page 33 for more details 6 Hang power unit onto wall mounting bracket Make sure both upper and lower mounting openings on the back of the power unit are engaged with corresponding wall bracket fingers Pull down the power unit to secure 7 Open the door on the front side of the power unit For VX475 VX550 amp VX1000 models make sure bag is installed properly on bag holder and holder is locked in upright position For models VX475C VX550C amp VX1000C make sure the cyclonic filter media is properly seated See Homeowners Guide if necessary Close the door 31 A WARNING MINIMUM WALL C
31. er the opposite end of the hose When you can feel the suction increase hold your hand over the hose end for a few seconds and then quickly remove your hand This procedure repeated several time should clear the obstruction If the blockage is not cleared contact your nearest Service Center 1d Check all wall inlet covers to be sure they are closed and sealed tightly 1e Inspect and remove any blockages 2a Replace defective wall inlet 2b Turn unit off for 20 minutes then plug unit back in If unit does not start look for the tripped circuit breaker behind the unit a white button has popped up push it back to reset it If circuit breaker trips again unplug your unit and contact your local Service Center 2c Replace fuse or reset circuit breaker on wall panel 2d Replace hose as required 2e 1 Push Reset button while unit is engaged OR 2 Unplug unit completely for 60 seconds 2f Contact your local Service Center 2g Remove and replace disposable filter bag as described in Homeowner s Guide 3a A complete check of all wall inlet and power unit low voltage control lead connections Contact your local authorized Service Center 4a Check and close direct door and make sure debris bucket handles are fully locked 5a Check all other wall inlets utility valve at power unit and sweep inlet valve NOTES NOTES N
32. he original consumer purchaser of its products that such products will be a from defects in materials and workmanship for a period of two 2 years from the date of original purchase THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE During this time period NuTone will at its option repair or replace without charge any product or part which is found to be defective under normal use and service THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP STARTERS OR TUBES FILTERS DUCT ROOF CAPS WALL CAPS AND OTHER ACCESSORIES FOR DUCTING This warranty does not cover a normal maintenance and service or b any products or parts which have been subject to misuse negligence accident improper maintenance or repair other than by NuTone faulty installation or installation contrary to recommended installation instructions The duration of any implied warranty is limited to the two year period as specified for the express warranty Some states do not allow limitation on how long an implied warranty lasts so the above limitation may not apply to you NUTONE S OBLIGATION TO REPAIR OR REPLACE AT NUTONE S OPTION SHALL BE THE PURCHASER S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE Some states do not allow the exclus
33. he original inlet 1c Obstruction in the tubing system inside the walls 1d Wall inlet cover not properly sealed 1e Exhaust tubing or vent clogged 2 Power unit does not start 2a Defective inlet Check other wall inlets or shuts off during normal operation with no LED showing 2b Thermoprotector has been activated OH there is a tripped circuit breaker on the unit red or illuminated 2C Blown fuse or tripped circuit breaker on house electrical panel 2d Defective hose 2e NOTE This would apply only to the VX550 amp VX1000 microprocessor lockup 2f Low line voltage 2g Bag full sensing has been activated 3 Power unit fails to stop when the 3a An electrical short has occurred somewhere in the system hose is removed 4 Power unit shuts off during 4a Debris bucket and or direct door not fully closed or attached normal operation lights on unit wall valve and hose are all red 5 For VX550 amp VX1000 Series All 5a Two or more hoses may be plugged into system lights on control panel flash when unit is first plugged in Possible Remedy 1a Remove disposable filter bag or empty debris bucket as described in Homeowners Guide and install replacement 1b Insert handle end of hose into utility valve at power unit Turn unit on This will reverse normal air flow through the hose and dislodge any clogs 1c Insert hose end into any inlet with power unit running place the palm of your hand ov
34. ich is farthest from the power unit Place 90 elbow onto a section of tubing and align it with the inlet tubing at the height it will run across the attic joists Mark the inlet tubing where the elbow will join allowing 5 8 for the tubing that inserts into the fitting collar Now cut the inlet tubing at the marked line Make sure the cut is straight and even Attach the elbow and check its fit Then insert the first section of tubing into the other end of the elbow NAE MEA UE D ia P Joining Straight Lengths of Tubing Both branch lines and the trunk lines may require lengths of tubing longer than those 8 sections supplied Use stop couplings to join two straight lengths of tubing Insert one end of the tubing into the stop coupling join the second length of tubing into the other end of the stop coupling Stop couplings are also used to join long vertical branches which run from one level to another level of a house Connecting a Branch Line A branch line connects the inlet line to the trunk line Follow the methods previously described for aligning marking and cutting the inlet tubing Attach a 90 elbow and run tubing from the inlet line to the trunk line To align and measure the branch line attach a 90 tee fitting to the trunk line Make sure the tee connects with the air flow going toward the power unit Align measure and mark the branch line for inserting it into the tee fitting Then cut the
35. iece of wire string around the pipe Using the 24 wire string to temporarily hold the pipe and elbow in VacuSweep Inlet Valve place insert the VacuSweep Inlet Valve into the opening Rough in Template at the base of the wall and elbow DO NOT glue this connection Designed for friction fit See Figure 50 5 6 Remove the wire string With the door in an open using no 6 screws See Figure 50 6 Ensure that the spring on the electrical connector has 1 8 clearance to rough opening Continue with remainder of central vacuum connections When the vacuum system is complete turn the power to the vacuum unit on h xt position secure the VacuSweep Inlet Valve to the wall oF Y INLET VALVE 2 CENTRAI j VAC PIPE i cO es w 23 GH f I y Ti A gt xx E The E Lt Re Nn d d j s NE ar f gt VEFERENCE H CE JOIST i I l AS CENTEF JM A SHORT SOCKET DO NOT GLUE THIS END OF ELBOW t VacuSweep E cy CONNECTION INLET VALVE b GLUE THIS que C NNECTI NS P Lg CONNECTION TER 4 E LONG 2 96 SCREW aix S s SOCKET PIPE re ac ELBOW EN WIRE STRING p pl E cO J THIS j e edi NINE N ra e VacuSneep j i C 7 CENTRAL VA Fiet NAI L AD0047A FIGURE 50 ARO0036 1 1 16 25 ASSEMBLING THE TUBING SYSTEM Once you have installed all your inlets you c
36. ion or limitation of incidential or consequential damages so the above limitation or exclusion may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state This warranty supersedes all prior warranties WARRANTY SERVICE To qualify for warranty service you must a notify NuTone at the address stated below or telephone 1 800 543 8687 b give the model number and part identification and c describe the nature of any defect in the product or part At the time of requesting warranty service you must present evidence of the original purchase date Date of Installation Builder or Installer Model Number and Product Description IF YOU NEED ASSISTANCE OR SERVICE For the location of your nearest NuTone Independant Authorized Service Center Residents of the contiguous United States Dial Free 1 800 543 8687 Please be prepared to provide Product model number Date and proof of purchase The nature of the difficulty Rev 06 2009 Residents of Alaska or Hawai should write to NuTone Inc Attn Department of National Field Service 926 West State Street Hartford WI 53027 For Models VX550 amp VX550C Nulone Four Year Limited Warranty WARRANTY OWNER NuTone warrants to the original consumer purchaser of its products that such products will be free from defects in materials and workmanship for a period of four 4 years from the date of original purchase THERE ARE NO OTHER W
37. ket of the tight elbow part no CF382S onto a section of 2 central vacuum pipe Make the terminal connections to the VacuSweep Inlet Valve by sliding the low voltage wire into wire clips Turn the power to the vacuum unit on to test the connection After successful completion of the test turn power to the vacuum unit OFF Wrap a piece of wire string around the pipe Using the wire string to temporarily hold the pipe and elbow in place insert the VacuSweep Inlet Valve into the cabinet base and elbow DO NOT glue this connection Designed for friction fit See Figure 48 5 Remove the wire string With the door in an open position secure the VacuSweep Inlet Valve to the cabinet base using no 6 screws See Figure 48 6 Ensure that the spring on the electrical connector has 1 8 clearance to rough opening Continue with remainder of central vacuum connections When the vacuum system is complete turn the power to the vacuum unit on x 2 3 4 70 mm CABINET REFERENCE 2 3 4 70 mm DDR KICKPLATE SUB FLOOR JOIST REFERENCE REFERENCE CABINET SUB FLOOR REFERENCE HOLE SEEN FROM BASEMENT 2 1 2 64 mm DIA iia z nuum zi DRILL 2 1 2 64 mm DIA HOLE i USING THE REFERENCE HOLE AS CENTER e 1 2 64 mm DIA HOLE CUTA23 8 HX6 5 8 W 60 mHx168 mm W ROUGH OPENING USING THE SHORT SOCKET REFERENCE HOLE AS CENTER END OF ELBOW
38. line which drops through an upstairs wall and down into the third level utility room to service this entire level See Figure 3 AH0004A LOCATING THE POWER UNIT e Locate the power unit at the lowest possible position away from the general living area in an accessible location for changing the filter bag or debris bucket e When planning remember the power unit is equipped with an inlet to service a garage basement utility room etc wherever it is located Locate the power unit within six feet of a grounded electrical outlet The VX475 and VX550 power units require a 120 V dedicated 20 amp branch circuit with a NEMA 5 20R receptacle The VX1000 power unit requires a 240 VAC dedicated 20 amp branch circuit with a NEMA 6 20R receptacle Do not locate the power unit close to a source of extreme heat i e water heater or in an area with a high ambient temperature i e attic furnace room If the power unit is located in a closet or a small utility room make sure the area is well ventilated i e with door louvers Exhausting the power unit to the outside is recommended for optimal performance The exhaust should not be vented into a wall a ceiling or a concealed space in the house The exhaust line should be vented outside the home using a Model 393 or CI330 wall caps BRANCH VERTICAL FIGURE 3 TUBING AND WALL INLET LOCATIONS 1 Locate inlets on interior walls choosing central locations which
39. llation eee 10 Model CI358 Supervalve Wall Inlet amp Rough In liliis 11 INSTALLATION IN EXISTING CONSTRUCTION sssssseeee ehh 12 19 Locating Access Keys in Existing Construction llle 12 Avoiding In Wall ODSTacleS 2 2 25 3 225 0046 ier RES Deux babes ORER ES ERI Oe ee SSS 55 Sed debe oh bee eos ki 12 ASANG Miel TUDING sers eee ee opere ones bee See eee eee ened Go he E ae eee ee Ge een eae 13 15 Wall Inlet Installation MMM 15 18 Models C1370 amp 360 Wall Inlets naaa 18 19 Model 330 amp C1335 Wall INEtS wise ced onder SU Eua oad othe ip 8 9 6 Ok Sneha pE eeni oio eR 19 Floor Inlet Installation in New and Existing Construction 0 0 ccc e 20 Original VacPan Installation Instructions llle 21 22 ORIGINAL VACUSWEEP INLET VALVE INSTALLATION INSTRUCTIONS 0 0 00 eae 23 25 ASSEMBLING THE TUBING SYSTEM sseseeee erras 26 30 POWER UNIT INSTALLATION sess hahaha rans 31 33 MOUNINO NEP NER TREO LOT LoT ITERUM 31 Tubing Connections at Power Unit 0 0 0 eee ee eee eee een hrs 32 DiMenSiOnal ON so s4 os ase te Gok ot ee Soe ee oe ee Sok eh Soe oe T TIL TT So ae SS eG Sh Eh 32 Aaa a ese E E E EE E E E E eres ce he ea ES IN ek ee ee eee E E ae Eee 33 PINAL SYSTEM CHECK cc peeces 54584 be oeu ledre iesse anis oa ees X29 3 9 Epa d
40. n large rooms the inlets UNI won are placed to provide maximum access TES FIGURE 1 to all cleaning areas See Figure 1 AHO003A BRANCH LINE TRUNK LINE THE TWO STORY HOUSE ATTIC A double trunk line system is commonly used in two story houses In the installation shown at right the power unit is mounted in the basement The intake tubing runs up the pian basement wall and connects to the main trunk line which runs along the unfinished basement ceiling Two first floor inlets are connected to the basement trunk line by vertical inlet lines run through interior walls In the center of the house a vertical branch line runs from the basement trunk line through stacked closets up into the attic A second trunk line runs across the attic and two branch lines connect to inlet lines which are dropped down through upstairs interior walls See Figure 2 SEME TRUNK LINE AH0005A FIGURE 2 THE SPLIT LEVEL HOUSE Like the two story house the split level installation commonly calls for a two level trunk line Here the power unit is located in the garage The intake tubing runs exposed up the garage wall and into the ground level section s attic Two branch lines connect this part of the trunk line to inlet lines which are dropped inside interior walls A vertical branch line runs to the upstairs attic where the trunk line branches into a T shape This trunk line connects to two upstairs inlet lines and to one inlet
41. nect it to the branch line wire Connect this wiring in groups of 3 one branch wire one in coming trunk line wire and one outgoing trunk line wire Insulate all wire connections with electrical tape Assembling a Basement Trunk Line Basically the tubing network is assemble the same way for a basement installation Begin the trunk line at the farthest inlet line from the power unit Measure and cut the inlet tubing to the length required to align the trunk line with the joists or ceiling Cement the inlet tubing and connect at 90 elbow Then run the trunk line until you reach a branch line junction point Complete all wiring connections up to the power unit s intake access hole You will make this connection when you mount and connect the power unit If for some reason you want to connect the wire as you go along make the same two wire and three wire connections where required 29 Attach the tubing to the joists or ceiling with either perforated metal or support strapping support strapping is available from NuTone Make all branch line connections in the same way you would an attic installation Make sure that all branch lines enter the trunk line at an angle that is at least levelled with the trunk line Make sure all the fittings are oriented so the air flows toward the power unit Complete the trunk line to the power unit location Using Flexible Tubing The supplied 36 length of flexible tubing may be us
42. on Refer to Figure 24 For extra thick walls use Model 399 Extension Sleeve to connect inlet to the flanged fitting Model 360 Wall Inlet CF361 and CF361F Rough In 1 Follow steps 1 2 as above 2 Refer to Figure 25 Connect 2 conductor low voltage wire to terminal screws on back of wall inlet 3 Follow steps 4 5 above Model 330 Wall Inlet CF 329 Rough In See Figure 26 1 Connect 2 conductor low voltage wire to terminal screws on back of wall inlet 2 Align inlet mounting holes with holes in mounting plate See Figure 26 3 Place inlet into mounting plate and secure with two provided screws See Figure 26 SPACER INLET MOUNTING WALL LESS THAN BRACKET op Td 1 THICK FIGURE 23 MODEL CF365 DOUBLE FLANGED SHORTEN MOUNTING BRACKET MOUNTING PLATE FIGURE 26 CI390 amp CI395 ELECTRAVALVE ELECTRIFIED INLET INSTALLATION CI395RK ROUGH IN 1 See Figure 27 Fasten the mounting plate to a stud within three studs 48 of an electrical outlet box Measure and mark the wire 10 from the plug A Feed the wire through the top hole in the mounting plate just above the circular opening Snap the molded plug into the mounting plate as pictured B This will keep it secure and out of harm s way during drywalling and finishing Line up the wire at the previously measured 10 mark with the strain of relief channel on the back of the mounting plate Secure it in place with the supplied wire tie C
43. on you may require the use of these tools The power tools are recommended to make your installation proceed quickly Also plan a mask when cutting ducting PVC dust and gloves when using glue Wire Strippers 1 4 Drill Level Flashlight Utility Knife Putty Knife Drill Bit Electrical Tape Knife Hammer Screwdriver Safety Glasses 2 2 Hole Saw Keyhole Saw Wrench Hacksaw 1 2 Drill Cold Chisel Tape Measurer WORKING WITH PLASTIC TUBING Cutting the Tubing Before you cut a length of tube accurately measure the length you need Allow 5 8 of tubing for inserting into fittings and 1 for placing into flexible tubing Cut the plastic tubing with a hacksaw making sure that the cut is exactly square You can use a tube cutter if one is available Use wire cutters or tin snips to cut flexible tubing The 8 lengths of flexible tubing supplied with each inlet should not be cut See Figure 4 FIGURE 5 Use a small knife to remove any burrs from the inside of the tube You can also use steel wool to remove burrs The burrs must be removed or they may impede air flow of form clogs by snagging hair and carpet thread See Figure 5 FIGURE 4 FIGURE 6 Next use a file to slightly bevel the outside of the tube so that it will easily slide into the fitting Use steel wool or a light grained sandpaper to buff the surface of the tube which will be glued This will clean the tube and assure a good seal See Figure 6 Making a Join
44. or replace without charge any product or part which is found to be defective under normal use and service THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP STARTERS OR TUBES FILTERS DUCT ROOF CAPS WALL CAPS AND OTHER ACCESSORIES FOR DUCTING This warranty does not cover a normal maintenance and service or b any products or parts which have been subject to misuse negligence accident improper maintenance or repair other than by NuTone faulty installation or installation contrary to recommended installation instructions The duration of any implied warranty is limited to the eight year period as specified for the express warranty Some states do not allow limitation on how long an implied warranty lasts so the above limitation may not apply to you NUTONE S OBLIGATION TO REPAIR OR REPLACE AT NUTONE S OPTION SHALL BE THE PURCHASER S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE Some states do not allow the exclusion or limitation of incidential or consequential damages so the above limitation or exclusion may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state This warranty supersedes all prior warranties WARRANTY SERVICE To qualify for warranty service you must a notify NuTone at the address stated below or telephone 1
45. oving mounting screws NOTE When using the model CF361 and CF361F inlet bracket on walls thinner than 1 2 use a 1 4 spacer not furnished between the wall and the inlet bracket See Figure 23 Spacer may be made from plywood Masonite M etc Contact cement may be used to hold spacer in place during assembly Configuration of spacer may vary depending upon installation 3 Refer to Figure 21 Connect the red striped wire of the 2 conductor low voltage cable to the unused terminal screw on the inlet Connect the remaining wire to the black pigtail wire Cap off both wires using wire nut supplied NOTE The LED indicator light used in the CI370 is polarity sensitive If the 2 conductor cable used to connect the inlet to the power unit does not have a polarity marking and the CI370 is wired backwards no damage will result however the indicator will light RED instead of GREEN when the hose is inserted into the inlet To correct this condition simply reverse the 2 conductor connections at the CI370 inlet 4 Guide excess wire back through the hole in inlet bracket and flanged fitting 5 Refer to Figure 26 Place inlet into mounting bracket and Secure NOTE When wall inlets are installed in walls that are less than 1 2 thick or when inlets are installed back to back in a wall the tube of the wall inlet may extend into elbow area of the flanged fitting and cause blockage Shorten the wall inlet tube to prevent this conditi
46. relatively easy to find access routes to run the tubing Refer again to the illustrations on pages 3 4 as you consider your home construction Some of the keys you might find in your home are illustrated here Stacked Closets or Laundry Chute Many homes will have an upstairs closet located directly above a downstairs closet It is easy to run the tubing from one floor level to another inside these stacked closets In these installations the tubing is often left exposed inside the closets See Figure 30 A laundry chute could also provide access from basement to upper floors You may also want to consider running exposed tubing through cabinets or cupboards Cold Air Return A cold air return often provides a straight run from basement to other levels of the house See Figure 31 The ductwork is easily cut for access Seal around the tube when completing the installation Use the following procedures for installation in existing construction Wall inlets in existing construction may be accessed from below basement or crawl space or from above attic Instructions apply to either method Starting from farthest wall inlet location install each inlet as described below Working back toward power unit connect each inlet line and branch line into main trunk line See page 26 Complete low voltage wiring as main trunk line is continued back to power unit Mount power unit and complete wiring See pages 31 33 AVOIDING IN WALL OBSTACLES
47. rical tape Tuck the 6 wire lead inside the flexible tubing so that it will not snag inside the wall If space permits you can assemble the entire inlet line by joining two sections of tubing with a stop coupling before dropping the assembly into the access hole Remember to only glue the outside of the tubing when join ing two pieces of PVC tubing Oftentimes tight attic spaces require you to begin your drop and then join the second sec tion of tubing Of course the order of assembly and the length of tubing required depend on your attic space and your wall height Whatever the case insert the completed inlet line into the access hole and thread it down inside the wall The inlet line should be long enough so that it extends above the joists in the attic at this height it can be easily connected to the branch and truck lines When cutting the inlet tubing to length remember that your inlet will be placed at 18 above the floor For a basement installation assemble the tubing to the inlet flexible tubing in the same way and insert it into the access hole A basement inlet line is necessarily shorter because it must only reach 18 from the floor to the inlet Most of the time Basement inlet lines are more easily installed by two people after the inlet hole has been cut in the interior wall See Wall Inlet Installation Complete all your inlet lines and then proceed to your inlet installations
48. rough mounting bracket and attach to terminal screws on back of floor inlet Cement extension sleeve to Model CI370 or 360 inlet Insert extension sleeve through vinyl gasket in mounting bracket and firmly seat into flanged fitting TOP VIEW SIDE VIEW 21 2 MIN APPROX vida Ly BRACKET NGE FIGURE 42 For convenience of operation floor inlet should be installed to open back toward wall Refer to Figure 43 Secure floor inlet in place with two Screws MOUNTING BRACKET FLANGED FIGURE 43 7 FITTING CUT TO LENGTH gt EXTENSION SLEEVE FLANGED FITTING FIGURE 44 uu A a x FIGURE 45 ORIGINAL VACPAN INSTALLATION INSTRUCTIONS NOTE Please read instructions prior to installation EUM TIPS Plan the location of your ORIGINAL VACPAN to be conveniently located for sweeping clean ups e Also consider ease of access of vacuum tube piping connections during installation The leading edge of the ORIGINAL VACPAN must sit flush with the finished floor e For maximum clearance use part no CV382S universal short 90 elbow for connection to VACPAN e Do not glue the connection between ORIGINAL VACPAN and elbow to allow for future removal Prior to final installation check for an airtight seal between ORIGINAL VACPAN and elbow Teflon tape may be used if required Allow for 1 2 vertical play in vacuum tube piping at ORIGINAL VACPAN
49. rt tubing installation at farthest inlet and work toward the power unit 2 Tubing run to the power unit should be as straight as possible 3 When assembling sections with elbows and tees make sure the curve in the fitting is aligned so that the air flows toward the power unit 4 Branch lines should always join the trunk line from above or from the same level Never join a branch line from an angle below the trunk line 5 Refer to Figure 25 on page 9 Run low voltage wiring Model 376UL and secure wiring to tubing as tubing is installed Model CF380 Pipe Support can be used to support long runs of tubing position near joists and to clip wire along tubing Secure tubing to joists or studs Leave approximately 6 of wire for connection to each inlet 6 Cut a 2 12 diameter hole in sole plate header or stud directly in line with opening of inlet bracket fitting NOTE See Figure 13 for center line dimensions 7 Refer to Figure 14 Measure length of tubing needed to connect inlet to trunk line Allow approximately 3 4 of tubing for inserting into fittings 8 Refer to Figure 15 Cut tubing keeping cut square 9 Refer to Figure 16 Remove burrs from both inside and outside of tubing 10 Before cementing pre assemble section to inlet fitting check for proper length 11 Refer to Figure 17 Apply PVC cement Model 379 to outside of tubing Coat tubing approximately 1 back Take care to keep cement from inside of t
50. st doorway measure the thickness of the wall including the baseboard In the basement measure a distance equal to half the thickness of the wall using the reference hole as a starting point Drilling the Access Holes Once you are certain that you ve located the center of the wall directly above the inlet location use a 212 hole saw to cut the access hole through the wall plate or header and into the wall cavity A 1 2 drill is recommended Carefully remove the drill from the hole Now use a flashlight to inspect the wall cavity through the access hole Make sure no hidden obstacles will interfere with the tube installation If this inspection reveals an obstacle find a new inlet location Repeat this procedure in your attic or basement until your access holes are drilled Assembling the Inlet Tubing Once you ve drilled the access holes you assemble the inlet tubing and insert it into the wall cavity Refer to Working With Plastic Tubing on pages 5 6 before you begin to assemble the inlet lines Select a section of plastic tubing and an 8 section of the flexible inlet tubing Apply cement to the outside of the plastic tubing and to the inside of the flexible tubing Join the two pieces together and allow 5 minutes for them to dry 14 Cut a piece of low voltage wire which is long enough for the complete inlet line allowing 6 for connections to the inlet wall plate Secure the wire to the tubing with elect
51. t Insert the tube into the fitting aligning the two parts as they will be installed Mark the tube and the fitting so that you can quickly realign the joint See Figure 7 FIGURE 7 Apply cement only to the outside of the tube Dab the cement generously in an inch wide band Insert the tube into the fitting with the alignment marks a quarter turn apart and then quickly push and turn the fitting to align the marks and spread the cement Allow one minute for the joint to dry You may also use electrical tape or duct tape to further seal the joint See Figure 8 Cementing Flexible Tubing Make sure the ends of the flexible tubing are even trim if necessary When you join flexible tubing to plastic tubing or to an inlet mounting plate apply cement to both the inside of the flexible tubing and the outside of the plastic tubing or mounting plate tubing ring Twist the two pieces as you join them to evenly spread the glue Allow five minutes for the cement to set in flexible tubing You may also use electrical tape or duct tape to further seal the joint Secure Wire to Tubing The low voltage power wiring is run along with the tubing To insure that the wire is secure and will not hang up in a wall use electrical tape to attach the wire to the tubing Tape the wire approximately every 12 18 inches See Figure 9 FIGURE 9 INSTALLATION IN NEW CONSTRUCTION WALL INLET ROUGH IN Once the locations for the wall inlets ha
52. the 6 b Gee Fi neos ae hole j With the door in an open position secure the n MA bad rani Oodle DO TEIETEHE MI VacuSweep Inlet Valve to the cabinet base using no 6 the basement and verify that there are no obstructions screws See Figure 49 6 Ensure that the spring on the 3 Using a reciprocating saw cut an access hole in the floor electrical connector has 1 8 clearance to rough under the cabinet and approximately 8 behind the opening From the basement reach through the access location of the VacuSweep Inlet Valve reference hole so hole and glue a section of 2 central vacuum pipe to the that the VacuSweep Inlet Valve can be connected to coupling Continue with remainder of central vacuum vacuum plpe by reaching through the access hole connections When the vacuum system is complete turn See Figure 49 3 the power to the vacuum unit on CABINET x 2 3 4 70 mm DOOR REFERENCE MARK CONNECTION IN A WALL Refer to Figure 50 on page 25 e 1 Turn the power to the vacuum unit OFF e Remove the baseboard and locate studs in the wall where VacuSweep Inlet Valve will be f installed Locate a position where the inlet will vere o A be clear of vertical studs and have free access either up or down dependent on location of central vacuum connection to the nad rest of the system See Figure 50 1 REFERENCE HOLE SEEN FROM BASEMENT 2 Holding the drill at a 45 angle and as close to the wall as
53. tinue knocking until you locate the area between wall studs directly above the inlet location Next measure the thickness of the wall Mark the exact center of the wall where you will drill the access hole Remember that the access hole must be placed exactly in the center of the wall Drywall Drywall Wall Plate Locating Basement Access Holes To locate access holes in the basement remove the toe molding or baseboard at the base of the inlet wall Carefully loosen the molding or baseboard by inserting the blade of a putty knife behind it Force another putty knife between the first knife and the baseboard or wall Gently hammer a cold chisel between the two knife blades prying the loosened molding away from the baseboard or the baseboard away from the wall Directly below the inlet location drill a 1 16 reference hole through the floor into the basement If you re drilling through carpet use an awl to slightly open the weave This will keep the carpet from wrapping itself around the drill bit Insert a piece of scrap wire or a clothes hanger into the reference hole so you can easily find the hole in the basement Once you ve found the location in the partition wall you must center the access hole in the middle of the wall Measure half the thickness of the wall and mark the center of the wall where you will drill the access hole If you cannot see the plate you can determine this measurement from upstairs At the neare
54. ube 12 Refer to Figure 18 Insert tubing into fitting with a twisting motion to evenly spread cement Be sure tubing is firmly seated in fitting 13 If fittings have been attached to tubing at the end opposite the inlet bracket be sure alignment is proper before cement sets 14 Refer to Figure 19 Tape wire to tubing to hold in place and insert through hole in inlet bracket 15 Connect each inlet line and branch line into main trunk line Complete low voltage wiring as main trunk line is continued back to power unit CAUTION When tubing is run through the wall stud sole plate headers or else where building materials will be attached place a nail Model 378 over that area on both sides if necessary to prevent nails from piercing tubing MODEL CF361 MOUNTING 2 DIA HOLE THROUGH SOLE PLATE 2 3 8 Dy i C SIDE MOUNTING FACE MOUNTING MODEL CF329 MOUNTING 212 DIA HOLE THROUGH SOLE PLATE 2 Tq AE 113 16 AD0055 FACE MOUNTING FIGURE 13 INCLUDE FITTING RECESS IN MEASUREMENT TUBING MEASUREMENT E FITTING i FITTING AD0017A FIGURE 14 FIGURE 19 WALL INLET INSTALLATION Model CI370 Wall Inlet CF361 and CF361F Rough In 1 Remove the cardboard plaster guard 2 Refer to Figure 20 For some drywall or panel construction the plaster frame will extend beyond the finished wall In this case remove plaster frame from mounting bracket by rem
55. ulone 926 WEST STATE STREET HARTFORD WI 53027 WWW NUTONE COM WARRANTY All VX Power Units are covered by a NuTone 2 4 or 8 year warranty Refer to your Model Number for which warranty you have Tools and Accessories warranted for one year from date of purchase See page 35 for details Product specifications subject to change without notice
56. ve been determined mount all inlet brackets 1 Choose the appropriate mounting bracket for the inlet being installed See chart 395 396 1 396 3 CI3301RK CI3303RK CF329 CF361 CF361F CI395RK sof x x x LLL sof X X x ffi xf x Los L CC C1358 Rough in and wall valve sold together cso CC T K CC A css SQ OC 2 To locate a bracket on a wall stud measure approximately 18 up from finished floor level Height may vary according to individual preference Wall Valve Series MODEL CF361 amp CF361F For Use with CI370 and 360 Inlets 3 Refer to Figure 10 Nail bracket to the side of the stud so that the front edge of the bracket is flush to the front of the stud The bracket may also be nailed to the front edge of the stud See face mounting illustrated For face mounting use locating tabs on bracket for proper alignment FIGURE 11 MODEL CF361 amp CF361F SIDE FACE 4 Refer to Figure 11 Remove cardboard from plaster MOUNTING MOUNTING guard frame Using four 4 provided screws attach the appropriate flanged fitting and inlet seal to back of inlet 5 Replace cardboard in plaster guard frame MODEL CF329 For Use with 330 Inlets 6 When using Model CF329 glue elbow to mounting plate Attach to stud as shown in Figure 12 FIGURE 10 FIGURE 12 INSTALLING THE TUBING Use the following installation guidelines when installing tubing 1 Sta
57. ws provided e Reach through access hole and make final piping connections UNDER CABINET INSTALLATIONS QUICK TRIM COVER PLATE CV382S UNIVERSAL SHORT 90 ELBOW ORIGINAL VACPAN SUB FLOOR FIGURE 46 AHO001A C1366 TRIM PLATE OPTIONS mE XL ROUGH IN 7 IN WALL INSTALLATIONS Refer to Figure 47 ORIGINAL VACPAN can be installed between wall studs in side walls ORIGINAL VACPAN should be located tight to one side in stud space Once the ORIGINAL VACPAN location is determined cut a 6 long x 134 high slot in the wall and baseboard to accept the ORIGINAL VACPAN The 2 x 4 wall bottom plate between the 2 studs must be removed This can be achieved from below using a hole saw In new home construction the bottom wall plate can be removed directly A 624 length of 2 x 4 can be used as a temporary rough in block that will force all trades to finish around leaving a slot for the ORIGINAL VACPAN Floor contractor must run flooring under block Run vacuum tube piping and low voltage wire from the main line to ORIGINAL VACPAN location Access for final piping connections must be made Access from Below If access is available from below cut an access hole through the subfloor underneath the wall between the studs positioned so that final piping connections can be made by reaching through the access hole Access Through Wall Access can be made through the finished wall Cut a 2 34 x 3
Download Pdf Manuals
Related Search
Related Contents
Lightolier IS:CS100 User's Manual Toshiba PDR-3310 User Guide Manual pdf Trisa Electronics Comfort Clean T6416 Reconnaissance de la parole et modélisation statistique expérience Samsung RT5962DTBWW İki kapılı 10 Yıl Kompresör Garantili No-Frost Buzdolabı Kullanıcı Klavuzu f14 multivalve fuel pump service manual HP EliteBook B8V08UT notebook ATISAE Manuel d`utilisation Copyright © All rights reserved.
Failed to retrieve file