Home
BlueWalker PowerWalker VI 2000RT LCD
Contents
1. HE LCD Display String Description STbY UPS work at Standby mode IPVL Input voltage is too low IPVH Input voltage is too high IPFL Input frequency is too low IPFH Input frequency is too high NORM UPS work at Line mode AVR UPS work at AVR mode bATT UPS work at Battery mode TEST UPS work at battery life function test mode OPVH Battery mode the output is too high OPVL Battery mode the output is too low OPST Output short OVLD Overload bATH Battery voltage is too high bATL Battery voltage is too low OVTP Internal temperature is too high FNLK Fan is locked bTWK Batteries are weak User Setting String Description The following table shows the options that can be changed by user Table5 User Setting String 220 220V 230 230V 240 240V 000 Normal range mode 001 Wide range mode 002 Generator mode OPV Output voltage mode select AVR Input type select EbM External battery module 0 9 is the number of external battery EBM module TEST Auto self test 000 Disable 001 Enable AR Automatic restart 000 Disable 001 Enable GF Green function 000 Disable 001 Enable bZ Buzzer control 000 Disable 001 Enable LS1 Load segment 1 000 Turn off 001 Turn on LS2 Load segment 2 000 Turn off 001 Turn on aa O TA 4 2 Operating Mode Normal range mode Under Input mode the
2. aa TO 4 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel amp Connecting the EBM in a rack form 1 Using the same method as assembling UPS in a rack form assemble EBM into the rack mounting on the top or bottom of the UPS PP Power Walker 2 Connect the earth line from UPS port A to EBM port B D 09900 beceteReerese En sane Yj SP 3 Take off the LCD box and unscrew the internal screws aa O TO 4 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel CH 5 After installing the UPS into rack the load can then be connected to UPS Please make sure the load equipment is turned off before plugging all loads into the output receptacle amp Connecting the Multiple EBMs 1000VA 1500VA 2000VA and 3000VA UPS include external battery port that allows users to connect multiple EBM in order to provide additional backup time Follow the procedure to ins
3. gD Power Walker Line Interactive UPS PEN PowerWalker VI 1000RT LCD PowerWalker VI 1500RT LCD PowerWalker VI 2000RT LCD PowerWalker VI 3000RT LCD Manual EN a UK 72000 IMPORTANT SAFETY INSTRUCTIONS HEN THESE INSTRUCTIONS This manual contains important instructions for models PowerWalker VI 1000 1500 2000 3000 RT LCD that should be followed during installation and maintenance of the UPS and batteries e This product is specially designed for PCs and it is not recommended for use in any life supporting system and other specific important equipment e This equipment can be operated by any individual with no previous training e Do not plug household appliances such as hair dryers to UPS receptacles e This unit intended for installation in a controlled environment temperature controlled indoor area free of conductive contaminants Avoid installing the UPS in locations where there is standing or running water or excessive humidity e Risk of electric shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel e The utility power outlet shall be near the equipment and easily accessible To isolate UPS from AC input remove the plug from the utility power outlet e f UPS is to be stored for a long time it is recommended to recharge the batteries by connecting the utility power to UPS switch ON once a month for 24 hours to avoid a full battery disch
4. UPS is on and no power to load Output Jumpers is not connected correctly Check output Jumpers No power on output receptacle Check if the LS1 and LS2 are set up from 001 to 000 Backup time is short Battery is empty Re charge the battery at least 24 hours Battery aging Replace Battery Continuously sounding and display turn to red The UPS fails Please contact your local dealer Buttons does not work The setting mode is not a right path please see right configuring method Button is Broken Please contact your local dealer LD PowerWalker 9 Software Installation WinPower is UPS monitoring software featuring user friendly interface to monitor and control your UPS This unique software provides complete power protection for computer system while power failure With the software users can monitor any UPS status on the same LAN Furthermore a UPS can provide security protection for more than one computer on the same LAN at the same time such as shutting down system in security saving application data and shutting down the UPS when power fails Software Installation on your PC Connected by USB to a PC or notebook the Software enables communication between the UPS and the computer The UPS software monitors the status of the UPS shuts down the system before the UPS is exhausted and can remotely observe the UPS via the Network enabling users to m
5. 2 Emergency Power Off EPO EPO is used to shut down the load from a distance This feature can be used for shutting down the load on Emergency A Warning This circuit must be separated from hazardous voltage circuits by reinforced insulation r A Caution The EPO must not be connected to any utility connected circuits Reinforced insulation to the utility is required The EPO Switch must have a minimum rating of 24Vdc and 20mA and be a dedicated latching type switch not tied into any other circuit The EPO signal must remain active for at least 20ms for proper operation EPO Connections Wire Function Terminal Wire Size Rating Suggested Wire Size EPO 4 0 32mm 12 22AWG 0 82mm 18AWG Note Leave the EPO connector installed in the EPO port on the UPS even if the EPO function is not need EPO Connector 5 3 Network Management Card Optional Network Management Card allows the UPS to communicate in a variety of networking environments and with different types of devices The series UPS has one available communication slot for Webpower or other optional card to achieve remote management of the UPS through internet intranet Please contact your local dealer for further information a 6 UPS Maintenance 6 1 UPS and Battery Care EN For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the
6. UPS Initial Startup To start up the UPS EN Verify that the internal batteries are connected If optional EBMs are installed verify that tne EBMs are connected to the UPS 2 Plug the equipment to be protected onto the UPS but do not turn on the protected equipment CO Plug in the UPS input power cord The UPS front panel display illuminates and UPS status display shows STbY 4 Press and hold the button more than 3 seconds The UPS status display changes to NORM 6 Check the UPS display for active alarms or notices Resolve any active alarms before continuing See Troubleshooting 8 If optional EBMs are installed see Configuring UPS for EBM numbers on page 21 to set the number of installed EBMs 9 To change any other factory set defaults see Operation Note At initial startup the UPS sets system frequency according to input line frequency 4 Operation 4 1 Display Pan a Lo p8 EE S ON OFF Select FE Enter EO O O TA The UPS has a four button graphical LCD with dual color backlight Standard back light is used to light up the display with black text and a blue background When the UPS has a critical alarm the backlight changes the background to red See Figure below Control Buttons functions There are four buttons on the control panel D A UPS Test Alarm Silence Lt Cu E112 1 OUTPUT OUTPUT r The follow
7. 0000000000000000000000 DOO00000000000000000000000000 3 Te 4 saaa O 1000VA amp 1500VA Standard amp Super charger model rear panel TA o Function 2K 3KVA Standard amp Supper charger model AC Output Modem Network Surge Protection SNMP Port Fan AC Input RS232 Dry Contact Communication Port USB Port EPO oo A IN Earth Line Port aaa 1 ces pi o 00 2000VA Super charger model rear panel o o WON Ha Wa GG E opah Peg N LI kd 6 60 3000VA Standard amp Supper charger model rear panel P3 Power Walker The EBM rear panel description table and picture are shown as below No Function 36V amp 72V EBM Earth Line Port 2 0 0 0 0 0 0 9 0 0 0 0 0 0 9 0 0 0 0 0 800200 0700070007 070 070 70 0000 00000 2207070070020 000 0 0 0 0 0 0 0 0 0 0 0202070 0
8. 7070 070 070 070000 000 920707070700 07070700 0000 00 070 0 00 00 0 0 000 0 0 00 0 0 00 090000000000000000000 T T D 00000000000000000000 0 0 0 06 0 00 0 6 0 6 0 00 0 0 0 0 00000000000000000000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 00 000 00 00 00 0 0 0 0 0 0 0 0 0 6 0 0 0 00 0 0 0 0 060000600006006000 9 00000000000000000000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 200000090000000000 00 0 00 00000 00 000 00 00 0 0 00000000000000000000 0 0 0 0 0 0 0 0 00 0 0 0 0 0 0 0 0 00000000000000000000 D 00000000000000000000 7 0000000000000000000 00000000000000000000 36V amp 72V EBM rear panel 8 Trouble Shooting 8 1 Audible Alarm Trouble Shooting r Indication Cause Solution Sounding every 4 The UPS is on battery Check the inputvoltage seconds mode P 9 Sounding every Second and bATL on screen The battery voltage is low Save your work and turn off your equipment Sounding every second and OVLD on screen Output overload Check load level indicator and remove some load Continuously sounding and red display The UPS fails Please contact your local dealer 8 2 General Trouble Shooting Problem Cause Solution The UPS can t be turned on when power switch is pressed Internal fuse may be broken Please contact your local dealer
9. AH Optional Optional Optional Optional Optional r Table8 Indicators and Audible alarm AC Mode NORM normal mode Backup Mode Show bATT and sounding every 4 seconds Load Battery Level LCD showing Indicator jursraut LCD show red screen and LCD show red screen and OVLD Low Low Battery LCD show red screen and bTLW Backup Mode Sounding every 4seconds Low Battery Sounding every second Audible alarm UPS Faut Continuously Sounding Battery Replacement Sounding every second Table9 Operating Environment Temperature 0 to 40 C Humidity 20 80 relative humidity non condensing Altitude lt 1500m Storage Temperature 15 to 45 C Table10 Dimensions and weights Net weight kg EK Dimension mm 438X86 5x436 438X86 5x608 WxHxD Dimension mm 438X86 5x436 438X86 5x608 WxHxD ae The UPS rear panel description table and pictures are shown as below r a 7 2 Rear Panels TA o Function 1000VA amp 1500VA AC Output Modem Network Surge Protection SNMP Port AC Input RS232 Dry Contact Communication Port USB Port EPO OO IS U Bc Po gt Earth Line Port ODO000000000000000000000000000 CEE 1 ODO00000
10. ETETE TETE EEE EEEEE 22 6 UPS Maintenance 1111111 fjfqfifqi 2H EE 23 6 1 UPS and Battery Care sennnununnunnnnnnnnununnnnnnnnnnnnnununnnnnnnnnnnununnnnnnnnnnnunnnunnnnnnnnnnnunununnneer 23 6 2 Storing the UPS and Batteries ccc et teen nen nent ene ene 23 6 3 Time to Replace Batteries ee eee eee eee ee ee eee ee eee ee eee ee ee ee Tere eee ee eee ee eee eee TEE EEE 23 6 4 Replacing UPS Internal Batteries sssssmmns 24 6 5 Testing New Batteries eee YY Tere eee eee ee Teer ee 26 6 6 Recycling the Used Battery senennunununnnnnnnnnnnunununnnnnnnnnnnunununnnnnnnnnnnunnnnnnnnnnnnnnnunnnuneneee 26 7 Specification 27 TA Specification AA 27 72 Rear Pangls 111111111111111 AA 29 8 Trouble Shooting nunnuuunnnnnnunununnnunnnnnnnunununnnnnnnnnnnunununnnnmnmumumumumumumumnmumumumumumumumnmumumununnnnnnn 32 8 1 Audible Alarm Trouble Shooting sannnunnnnnnnnnnnnnnnnnnnnnnnnnnnnnununnnnnnnnennunununnnnnnnnnnnununnenneer 32 8 2 General Trouble Shooting vanenneunnvnennnnnnnnnennnenenennnnnnnununnnnnnnnennununnnnnnnnnnennununnnnnnnnnnnner 32 9 Software Installation s00s0000n0nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnennnnnnnennnnnennnnnnnnnnnen 33 PI Power Walker 1 Introduction This line interactive series is compact and pure sine wave UPS and it is designed Hie for essential applications and environment such as desktops servers workstations and other networking equipments These models are available in the
11. UPS accepts AC input voltage range for 20 Generator mode Under generator mode the low frequency transfer point can EN go as low as 40Hz and as high as 70Hz before being transferred to battery mode Wide range mode Under Input settings mode the UPS accepts AC input voltage range for 30 20 Battery mode When the UPS is operating during a power outage the alarm beeps once every four seconds and the LCD display string shows bATT to indicate the UPS work at battery mode If battery volume becomes low while in Battery mode the alarm beeps once every second and the LCD display string shows bATL Standby mode When the UPS is turned off and remains plugged into a power outlet the UPS is on Standby mode The LCD display string shows STbY to indicate that power is not available to your equipment The battery recharges when necessary 4 3 Configuring Load Segment Load segment are sets of receptacles that can be controlled through the display Each UPS has two configurable load segments See Rear Panels on page 30 for load segment for each UPS model Note This configuring can be operated when UPS is power on To configure the load segment through the display 1 Enter settings mode Press and hold the Enter button more than 3 seconds Then UPS will transfer to setting mode 2 Select settings items Press the Select button to select the setting items show as Table 5 3 Enter settings it
12. anage their system more effectively Upon AC failure or UPS battery low UPS takes all necessary actions without interven tion from the system administrator In addition to automatic file saving and system shut down functions it can also send warning messages via pager e mail etc e Use the bundled CD and follow the on screen instructions to install the software WinPower e Enter the following serial No to install software 511C1 01220 0100 478DF2A After the software is successfully installed the communication with UPS has been established and an green icon will appear in the system tray s 9 16 AM e Double click the icon to use the monitor software as above e You can schedule UPS shutdown start up and monitor UPS status through PC e Detail instructions please refer to the e manual in the software A Check www powerwalker com winpower html from time to time to get the latest version of monitoring software 614 08025 00
13. arge e Please do not use the UPS in excess of the rated load capacity e The UPS contains one two large capacity batteries So the shell shall not be opened otherwise such dangers as electric shock will be caused If any internal overhaul or replacement of the battery is required please contact the distributor e The internal short circuiting of the UPS will lead to dangers such as electric shock or fire therefore no water containers such as a water glass shall be placed on the top of the UPS so as to avoid such dangers as electric shock e Do not dispose of battery or batteries in a fire The battery may explode e Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic e Icon on the rating label stands for phase symbol e A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries D Power Walker e Remove watches rings or other metal objects from the hand e Use tools with insulated handles e Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries e When replacing batteries replace with the same type and number of the sealed lead acid batteries e The maximum ambient temperature rating is 40 C e This pluggable type A equipment wi
14. ck mount available for all models a aY 772 2 Circuit Configuration and Commonly used Symbols Following figure shows the basic internal circuit configuration of the UPS 2 1 Description of Commonly Used Symbols Some or all of the following Notations may be used in this manual and may appear in your application process Therefore all users should be familiar with them and understand their explanations Table1 Description of Commonly Used Symbols Recycle Keep UPS in a clear area 3 Installation 3 1 Inspection of Unit Inspect the UPS upon receiving If the UPS is apparently damaged during the ER shipment please keep the box and packing material in original form for the carrier and notify the carrier and dealer immediately 3 2 Unpacking the Cabinet To unpack the system 1 Open the outer carton and remove the accessories packaged with the cabinet 2 Carefully lift the cabinet out of the outer carton and set it on a flat stable surface 3 Discard or recycle the packaging in a responsible manner or store it for future use 3 3 UPS Setup All model series are designed for tower and rack purpose They can be installed into a 19 inches equipment rack Please follow the instruction for Tower Setup and Rack Mount Setup Tower setup This series of UPS can be placed horizontally and vertically As a tower configuration it is provided with the optional UPS stands to stabilize the UPS w
15. e batteries Released electrolyte is harmful to the skins and eyes It may be toxic A battery can present a risk of electrical shock and high short circuit current To recycle properly the used battery please do not discard the UPS battery pack and batteries into the trash bin Please follow your local laws and regulations you may contact your local recycling waste management center for further information to dispose properly of the used UPS battery pack and batteries Model Capacity Output Overload rating Internal battery External battery module EBM Interface 7 Specification 7 1 Specification Table7 Electrical Specification Watt Input voltage range Frequency range Voltage Voltage Regulation Batt Mode Frequency Waveform Line Mode Battery Mode Battery Type Backup Time at full load Recharge Time Battery Type RS 232 Dry Contact USB SNMP EPO 1000 1500 2000 3000 1000S 1500S 2000S 3000S 161 276VAC 50 60Hz 5Hz for Normal Mode 40 70Hz for Generator Mode 220 230 240VAC 5 50Hz or 60Hz Pure sinewave 110 0 8 shutdown after 3 minutes 150 0 10 shutdown after about 200ms 110 6 shutdown after 30 seconds 120 6 Shutdown after about 100ms 12V 7AH 12V 9AH 12V 7AH 12V 9AH 3 hours to 4 hours to 3 hours to 4 hours to 90 after 90 after 90 after 90 after discharged discharged discharged discharged 12V 7
16. em When the LCD display LS1 or LS2 press the enter button more than one second to enter the setting item and the settings string will flash 4 Select setting value Press the Select button to select the settings value Select the value 001 or 000 to set the desired load segment ON or OFF 5 Confirm settings Press and hold the Enter button for one second ups will return to current setting item aa aaa 7777272 6 Exit Settings mode Press and hold the Enter button for 3 seconds or button for 0 5 second to exit setting mode en 4 4 Configuring UPS for EBM Numbers To ensure the LCD displays the correct battery volume configure the UPS for the correct number of EBMs 1 Enter settings mode Press more than 3 seconds to enter setting mode 2 Select settings items Press to select setting items as EbM 3 Enter settings item Press more than one second to enter the setting item 4 Select setting value Press the Select button to select the number of EBM according to your UPS configuration 5 Confirm settings Press and hold the Enter button one second ups will return to current setting item 6 Exit Settings mode Press and hold the Enter button for 3 seconds or button for 0 5 second to exit setting mode 4 5 Configuring Green Function Green Function is that when an insignificant amount of load is detected the UPS will shut down output automatically on battery mode The green function is di
17. event is encountered aa TA LCD display functions The following table describes the functions of the LCD display Table3 Description of LCD display function No Description Function ox Input frequency and DE voltage oi Indicate the value of input frequency and voltage Input plug indicator Light on when the input power is at no loss Output frequency and Indicate the value of output frequency and Ban voltage voltage The UPS has two groups of outlets The output 1 Output plug indicator plug indicator will light on if there is output power respectively UPS status user Strings Indicate the UPS status see Table 4 4 eee setting display String Strings Indicate user setting options see Table 5 Warning indication Light on when the UPS is failure or alarm Settings Light on when the UPS under settings mode ATT Indicate the amount of battery volume Battery volume level remaining Each battery volume level bar SB ap f display indicates a 20 of total battery volume LOAD N Indicate the percentage of UPS load capacity 4 Load capacity level which is being used by the protected display equipment Each LCD level bar indicates a H 20 of the total UPS output capacity a 27 UPS Status Display String Description The following table shows the description of the LCD display string Table4 UPS Status Display String
18. hen the UPS is positioned in vertical The UPS stand must be attached to the bottom of the tower E CN 2 Use the following procedure to install UPS in UPS stands 1 Slide down the UPS vertically and put two UPS stands at the end of the tower SS gt DI 2 Place down the UPS into two stands carefully DT EN IM 3 Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel PI PowerWalker D Power Matter Rack mount setup The series can be installed in 19 inches racks Both the UPS and external battery enclosure need 2U of valuable rack space EN Use the following procedure to install UPS in a rack 1 Align the mounting ears with screw holes on the side of the UPS and tighten the screw 3 ENST y CEK KEKE KSKE KEKE EKSE EEEE m EO T O TO 3 Slide in the UPS into the rack rail and lock it in the rack enclosure r 3 4 EBM Installation Optional en amp Connecting the EBM in Tower form 1 Slide down the UPS and EBM vertically and place two UPS stands with the extend part at the end of the tower 2 Tighten the screw on the metal sheet for stabilization 3 Connect the Earth line from UPS port A to EBM port B 7 75 7
19. ing table describes the functions of the LCD control buttons Table2 Description of control button Control HE Buton Switch Function To turn on off the UPS Press and hold the button more than 3 seconds ON OFF To release the UPS from faulty mode Cut off input power and then press and hold the button more than 2 seconds to shut down the UPS To perform basic function test Press and hold the button for 3 seconds UPS Test To perform Battery life test Alarm Silence Press and hold the button for 10 seconds To disable alarm buzzer Press the button for one second Press the Select button to select the settings value one by one Enter settings mode Press and hold the button more than 3 seconds Enter settings item Press and hold the Enter button more than one second the UPS allows users to configure the Enter settings and the settings string will flash Confirm settings Press and hold the Enter button for one second Exit Settings mode Press and hold the Enter button for 3 seconds or button for 0 5 second G Select bad t Note Ensure the battery is fully charged during line mode when conducting functional tests Note A list of events shown as below is not able to disable alarm buzzer Low Battery Fan Failed Fan Fault Time Out and Overheat Note User can disable the alarm buzzer when it s sounding but an alarm will still sound when a new alarm
20. nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnenennnnnnnnenennnnnnnnnnnenenevnn 5 2 Safety Warning 2 en 2 1 Description of Commonly Used Symbols vanennnunnnunnnnnnnnnnnunnnunnnnnnnnnnnunnnnnnnennnnnununnnenene 2 3 Installation annnunuuunnnnnnnunnnunnnnmnmumumumumumumumnmumumumumumumumnmumuununnnnnnnnnununununnnnnnnununununnnnnnnnnununununnnn 3 3 1 Inspection of Unit svrnnnnununnnnnunnunnunnnnnunnvnnnnunnnnnunnnnnunnnnnunnnnnvnnunnnnunnnnnunnnnnunnnnnnnnunnnnnnnneee 3 3 2 Unpacking the Cabinet seen 3 3 3 UPS Setup ennnunnnnnnnnnnnunnnunnnnnnnnennunnenenennnenennnenenennnnnennnnnenennnnnanennnnnenennnnnenennnenennnnnnnnner 3 3 4 EBM Installation Optional 8 3 5 UPS Initial Startup AA YU eee ee 14 4 Operation nunuuuunnnnnnunununnnunnnnnnnumumumumumnmumumumumumnmumnmnmumumumumunnnnnnunununnnnnnvnnunununnnnunnnunnunununnnunn 15 4 1 Display Panel AA 15 42 Operating Mode EEE EEE 19 4 3 Configuring Load Segment CETETE TE ELEC EEE ETES EEE TEE ECEET ETES EEE EEE EEE ETES EEE EE EC EE TETE TETE EE EEEE EEE ET ETES 19 4 4 Configuring UPS for EBM Numbers 20 4 5 Configuring Green Function 20 5 Communication Port s ssxs0nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnvannnnnnnnvnvnnnnnnnvnnunnnnnnnnnunnnnnnvnnunen 21 5 1 RS 232 and USB Communication Ports mma 21 5 2 Emergency Power Off EPO sennnunnnnnnnnnnnunununnnnnnnnnnnunununnnnnnnnnnnununnnnnnnnnnnnnununnnnnnnnnnee 21 53 Network Management Card Optional CETETE TETE EC EC TES ETES ET EEE ELEC EET ETES ET EEE EEE E
21. output ratings of 1000VA 1500VA 2000VA and 3000VA The series protects your sensitive electronic equipments against power problems including power sags spike brownouts line noise and blackouts The series is convertible to rack and tower forms It can be placed either in Rack 2U or Tower form The front panel of the UPS includes LCD display and four control buttons that allow users to monitor configure and control the units On LCD it also includes a LCD graphical bar two status indications and four alarm indications A control button from the front panel allows users to silence off the AC fail alarm and initiate the UPS self test sequence as well The UPS case for 1000VA 3000VA is made of metal This series is powered from the AC mains and supply AC outputs via receptacles on the rear panel Communication and control of UPS is available through serial or USB ports located on the rear panel The serial port will support communications directly with a server Features m Microprocessor control guarantees high reliability Em High frequency design m Built in boost and buck AVR m Easy battery replacement design m Selectable input and output range m Cold start capability E Built in Dry contact RS 232 USB communication port EH SNMP allows for web based remote or monitoring management m Enable to extend runtime with scalable external battery module EBM E Overload short circuit and overheat protection m Rack Tower 2 in 1 Design M 19 inches ra
22. representative to order new batteries aa 220 e Do not dispose of battery in a fire Batteries may explode when exposed to flame e Proper disposal of batteries is required Refer to your local codes for disposal requirements en e Do not open or mutilate the battery Released toxic electrolyte is harmful to skin and eyes Note If you are not qualified service personnel to replace the battery do not attempt to open the battery cabin Please call local dealer or distributor immediately 6 4 Replacing UPS Internal Batteries Follow the steps and Charts as below to replace batteries 1 Take off the LCD box and remove the screws GD Poner ser 4 Remove the right inner battery bracket 6 Install new battery pack into UPS 7 Screw up the battery bracket and reconnect the battery cable A and B 8 Re install the front panel back to UPS r a 6 5 Testing New Batteries For a battery test please check EN e The batteries must be fully charged e The UPS must be in Normal mode with no active alarms e Don t take on off the load To test batteries 1 Connect the UPS to utility power for at least 48 hours to charge the batteries 2 Press and hold the button 10 seconds to start the battery test The status display string shows TEST 6 6 Recycling the Used Battery A Warning e Never dispose the batteries in a fire It may explode e Do not open or mutilate th
23. sabled on default mode and user can configure Green Function through the display 1 Enter settings mode Press more than 3 seconds to enter setting mode 2 Select settings items Press to select setting items as GF 3 Enter settings item Press more than one second to enter the setting item 4 Select setting value Press the Select button to select 001 5 Confirm settings Press and hold the Enter button for one second ups will return to current setting item 6 Exit Settings mode Press and hold the Enter button for 3 seconds or button for 0 5 second to exit setting mode aa O TO 5 Communication Port 5 1 RS 232 and USB Communication Ports CH To establish communication between the UPS and a computer connect your computer to one of the UPS communication ports using an appropriate communication cable When the communication cable is installed power management software can exchange data with the UPS The software polls the UPS for detailed information on the status of the power environment If a power emergency occurs the software initiates the saving of all data and an orderly shutdown of the equipment The cable pins for the RS 232 communication port are identified as below and the pin functions are described in Table 6 Table6 DB9 Female RS232 dry contact PIN 1 2 3 4 5 Common Common tied to chassis 6 7 g 8 Line fail 6006000 60600 RS232 Communication Port 5
24. system with a vacuum cleaner For long battery life keep the UPS at an ambient temperature of 25 C 77 F 6 2 Storing the UPS and Batteries When the UPS is intended to store for a long period recharge the battery every 6 months by connecting the UPS to utility power The batteries charge to 90 capacity in approximately 4 hours However it is recommended that the batteries charge for 48 hours after long term storage 6 3 Time to Replace Batteries When LCD backlight turns to red the screen displays bTWK and there is a continuous sounding the battery may need to be replaced Please check the battery connection or contact your local dealer to order new battery A WARNING e Turn off the UPS and disconnect the utility power cord from the wall outlet e Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries e Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Wear rubber gloves and boots 5 Disconnect the charging source prior to connecting or disconnecting battery terminal e When replacing batteries replace with the same type and number of batteries or battery packs Contact your service
25. tall multiple EBM as below aa aaa 7777272 Connecting multiple EBMs in Tower form 1 Connect Earth line between UPS and the first EBM and then connect Earth Line between the first EBM and the second EBM 2 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below And then connect the battery terminal D from the first EBM to the battery terminal E from the second EBM Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel p s D PowerWalker Connecting the Multiple EBMs in rack form 1 Connect Earth line between UPS and the first EBM and then connect Earth Line between the first EBM and the second EBM o a a fa NG 2 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below And then connect the battery terminal D from the first EBM to the battery terminal E from the second EBM Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel Note Three or more EBMs can be connected to the UPS in the same way as shown above aa 722272 3 5
26. th battery already installed by the supplier is operator installable and may be operated by laymen e During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3 5mA e Attention hazardous through electric shock Also with disconnection of this unit from the mains hazardous voltage still may be accessible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole of the battery when maintenance or service work inside the UPS is necessary e The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible e In case smoke is found coming out from the device please cut off the power supply quickly and contact the distributor e Do not keep or use this product in any of the following environments o Any area with combustible gas corrosive substance or heavy dust o Any area with extraordinarily high or low temperature above 40 C or below 0 C and humidity of more than 90 o Any area exposed to direct sunshine or near any heating apparatus o Any area with serious vibrations o Outdoor e In the event that there is fire occurring in the vicinity please use dry power extinguishers The use of liquid extinguishers may give rise to the danger of electric shock O PowerHaiker CONTENTS 1 Introduction xs00000000nnnnnnnnnnnnnnnnnnnnn
Download Pdf Manuals
Related Search
Related Contents
[浦和消費生活センター]総括表(PDF形式:13KB) MANUEL DE LA CAMPEUSE - La feuille d`olivier PoweMonic 20-30 User Manual 0804 GEFRAN_1600_1800 - User manual ITA 添付資料2 - CIAJ 一般社団法人 情報通信ネットワーク産業協会 SUPPORT MANUAL - BN elektronik ApS AEROMOTIVE Part # 17158 05`- Present Mustang Race Fuel la version pdf Copyright © All rights reserved.
Failed to retrieve file