APC Smart-UPS 5000VA

image

Contents

1.
2. Move the UPS to a different outlet on a different circuit Inexpensive fuel powered generators may distort the voltage Test the input voltage with the utility voltage display see Operation in this manual If acceptable to the connected equipment reduce the UPS sensitivity Battery Charge and Load LEDs flash simultaneously The UPS has shut down The internal temperature of the UPS has exceeded the allowable threshold for safe operation Check that the room temperature is within the specified limits for operation Check that the UPS is properly installed allowing for adequate ventilation Allow the UPS to cool down Restart the UPS If the problem persists contact APC at www apc com Diagnostic utility voltage All five LEDs are illuminated The line voltage is extremely high and should be checked by an electrician There is no LED illumination On Line LED The line voltage is extremely low and should be checked by an electrician There is no LED illumination The UPS is running on battery or it must be turned on The LED is blinking The UPS is running an internal self test 18 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual M aintenance Transport and Service Maintenance Transport and Service Replace battery modules This UPS has easy to replace hot swappable battery modules Replacement is a safe procedure isolated from electrical hazards
3. No illumination low sensitivity Factory User Selectable Function Default Choices Description Automatic On startup and On startup and every Set the interval at which the UPS will execute a Self Test every 14 days 7 days 168 hours self test 336 hours there after there after On startup and every 14 days 336 hours there after On startup only No self test UPS ID UPS_IDEN Up to eight characters Uniquely identify the UPS i e server name or alphanumeric location for network management purposes Date of Last Manufacture mm dd yy Reset this date when you replace the battery Battery Date module Replacement Minimum Capacity 0 percent 0 60 Specify the percentage to which batteries will Before Return from 15 75 be charged following a low battery shutdown Shutdown 30 90 before powering connected equipment 45 Voltage Sensitivity High sensitivity Brightly Adjust by pressing the VOLTAGE SENSITIYIY The UPS detects Ped illuminated high switch rear panel Use a pointed object such and reacts to line ja sensitivity as a pen to do so voltage distortions Dimly illuminated Note In situations of poor power quality the by transferring to rt medium sensitivity UPS may frequently transfer to battery operation If the connected equipment can operate normally under such conditions reduce connected the sensitivity setting to conserve battery equipment capacity and service life Al
4. Material Authorization Number RMA Ifthe UPS is under warranty repairs are free Procedures for servicing or returning products may vary internationally Refer to the APC Web site for country specific instructions 3 Pack the UPS in its original packaging If this is not available Pack the UPS carefully to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transit is not covered under warranty 4 Always DISCONNECT THE UPS BATTERY before shipping in compliance with U S Department of Transportation DOT and IATA regulations The battery may remain in the UPS 5 Mark the RMA on the outside of the package 6 Return the UPS by insured prepaid carrier to the address given to you by Customer Support Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Two Year Warranty Two Year Warranty The limited warranty provided by American Power Conversion APC in this statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your business Terms of warranty APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase The obligation of APC under this warranty is limited to repairing or replacing at its sole discretion any such defective products This warranty does not apply to equipment that has been damaged by accident
5. 4 4 4 5 4 6 4 11 Applicable Council Directives 2006 95 EC 89 336 EEC 93 68 EEC Type of Equipment Uninterruptible Power Supply Model Numbers SUASO00RMISU Manufacturers American Power Conversion American Power Conversion APC Suzhou UPS Co Ltd Ballybritt Business Park 2nd Street 339 Suhong Zhong Lu Galway Ireland PEZA Cavite Economic Zone Suzhou Industrial Park Rosario Cavite Suzhou Jiangsu 215021 American Power Conversion Philippines P R China Breaffy Rd Castlebar American Power Conversion APC Power Infrastructure Co Ltd Co Mayo Ireland Lot 10 Block 16 Phase 4 1678 Ji Xian Road Tong An PEZA Rosario Cavite Xiamen Philippi American Power Conversion T FETES P R China 361100 132 Fairgrounds Rd West Kingston RI 02892 USA American Power Conversion Lot 3 Block 14 Phase 3 PEZA Rosario Cavite American Power Conversion Philippines 1600 Division Rd West Warwick RI 02892 USA APC Brazil LTDA AI Xingu 850 American Power Conversion Barueri 40 Catamore Blvd Alphaville Sao Paulo East Providence RI 02914 USA 06455 030 Brazil APC India Pvt Ltd 187 3 188 3 Jigani Industrial Area Jigani Bangalore 562106 Karnataka India Importer American Power Conversion A P C b v Ballybritt Business Park Galway Ireland Galway Ireland Ray S Ballard Managing Director Europe Y hal 5 Jan 07 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 23
6. Leave the UPS in the rack and connected equipment on during the replacement procedure Once the batteries are disconnected the connected equipment is not protected from power outages Refer to the appropriate replacement battery user manual for battery module installation instructions See your dealer or contact APC at www apc com for information on replacement battery modules Be sure to deliver the spent battery s to a recycling facility or ship it to APC in the replacement battery packing material Open battery doors Remove spent batteries from the UPS Pull the battery disconnect cords gt attached to the battery connectors DO NOT pull the battery cables to disconnect the batteries Battery disconnect cord Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 19 Maintenance Transport and Service Service If the UPS requires service do not return it to the dealer Follow these steps 20 1 Review the problems discussed in Troubleshooting in this manual to eliminate common problems 2 If the problem persists contact APC Customer Support through the APC Web site www apc com Note the model number of the UPS the serial number located on the back of the unit and the date purchased If you call APC Customer Support a technician will ask you to describe the problem and attempt to solve it over the phone If this is not possible the technician will issue a Returned
7. a dedicated branch circuit with a maximum of 32 A of over current protection either a circuit breaker of fuses A lower rated branch may be used depending on the requirements of the UPS load Allow an additional 600 W for the UPS during the battery replacement procedure Switch the circuit breaker OFF prior to connecting equipment and power to the UPS Remove the access panels located on the rear panel of the UPS Remove the knockout from the input access panel Use 10 AWG 5 mm Strip approximately six inches 152 4 mm of the outer jacket from the input cable exposing the wires Strip 5 inch 12 7 mm of the individual wire coverings Route the input cable through the hole in the input access panel Apply an appropriate strain relief Connect the ground wire prior to connecting the line wires Replace the access panels and secure each panel with three screws E O Terminal block no L1 L2 N O afd access panel access panel i ole i Accessories Install accessories prior to connecting power to the UPS Refer to the APC Web site www apc com for available accessories Input output hardwire kit Two post rack option Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 7 Installation Connect batteries Rack mount configur
8. negligence or misapplication or has been altered or modified in any way Repair or replacement of a defective product or part thereof does not extend the original warranty period Any parts furnished under this warranty may be new or factory remanufactured Non transferable warranty This warranty extends only to the original purchaser who must have properly registered the product The product may be registered at the APC Web site www apc com Exclusions APC shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse negligence improper installation or testing Further APC shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection inappropriate on site operation conditions corrosive atmosphere repair installation start up by non APC designated personnel a change in location or operating use exposure to the elements Acts of God fire theft or installation contrary to APC recommendations or specifications or in any event if the APC serial number has been altered defaced or removed or any other cause beyond the range of the intended use THERE ARE NO WARRANTIES EXPRESS OR IMPLIED BY OPERATION OF LAW OR OTHERWISE OF PRODUCTS SOLD SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH APC DISCLAIMS ALL IMPLIED WARRANTIES
9. to access documents in the APC Knowledge Base and to submit customer support requests www apc com Corporate Headquarters Connect to localized APC Web sites for specific countries each of which provides customer support information www apc com support Global support searching APC Knowledge Base and using e support Contact an APC Customer Support center by telephone or e mail Local country specific centers go to www apc com support contact for information Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support Entire contents copyright 2008 American Power Conversion Corporation All rights reserved Reproduction in whole or in part without permission is prohibited APC the APC logo Smart UPS and PowerChute are trademarks of American Power Conversion Corporation All other trademarks product names and corporate names are the property of their respective owners and are used for informational purposes only 22 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Regulatory Information APC 2007 www apc com EC Declaration of Conformity Date of product declaration We the undersigned declare under our sole responsibility that the equipment specified below conforms to the following standards and directives Harmonized Standards EN 60950 1 IEC 60950 1 EN 62040 1 1 EN 55022 EN 55024 IEC 61000 3 4 3 5 4 2 4 3
10. utility power supply to the UPS by plugging in a table lamp If the light is very dim have the utility voltage checked UPS will not turn off The UPS is experiencing an internal fault Do not attempt to use the UPS Unplug the UPS and have it serviced immediately UPS beeps occasionally Normal UPS operation when running on battery None The UPS is protecting the connected equipment Press the button to silence this alarm UPS is not providing expected backup time The UPS battery s are weak due to a recent power outage or battery s are near the end of their service life Charge the battery s Batteries require recharging after extended outages Batteries can wear faster when put into service often or when operated at elevated temperatures If the battery s are near the end of their service life consider replacing the battery s even if the replace battery LED is not yet illuminated The UPS is experiencing an internal fault All LEDs are illuminated and the UPS emits a constant beeping Do not attempt to use the UPS Unplug the UPS and have it serviced immediately Front panel LEDs flash sequentially The UPS has been shut down remotely through software or an optional accessory card None The UPS will restart automatically when utility power returns All LEDs are off and the UPS is plugged into a wall outlet The UPS is shut down or the battery is discharged from an extende
11. 24 hours Perform the self test procedure to confirm the replace battery condition The alarm stops and the LED clears if the battery passes the self test If the battery fails again it must be replaced The connected equipment is unaffected The input circuit breaker trips The connected equipment exceeds the specified maximum load as defined in Specifications on the APC Web site WWW apc com Unplug all nonessential equipment from the UPS Reset the circuit breaker The AVR Boost or AVR Trim LEDs are illuminated The system is experiencing very high or low utility voltage Have qualified service personnel check your facility for electrical problems If the problem persists contact the utility company for further assistance Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 17 Troubleshooting Problem and or Possible Cause Solution There is no utility power There is no utility power and the UPS is off Use the cold start feature to supply power to the connected equipment front the UPS battery s Press and hold the button There will be a short beep followed by a longer beep Release the button during the second beep UPS operates on battery although line voltage exists The UPS input circuit breaker trips Unplug all nonessential equipment from the UPS Reset the circuit breaker Your system is experiencing very high low or distorted line voltage
12. OF MERCHANTABILITY SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE APC EXPRESS WARRANTIES WILL NOT BE ENLARGED DIMINISHED OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF APC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES APC WARRANTIES EXTEND ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES IN NO EVENT SHALL APC ITS OFFICERS DIRECTORS AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES ARISING OUT OF THE USE SERVICE OR INSTALLATION OF THE PRODUCTS WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT IRRESPECTIVE OF FAULT NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES SPECIFICALLY APC IS NOT LIABLE FOR ANY COSTS SUCH AS LOST PROFITS OR REVENUE LOSS OF EQUIPMENT LOSS OF USE OF EQUIPMENT LOSS OF SOFTWARE LOSS OF DATA COSTS OF SUBSTITUENTS CLAIMS BY THIRD PARTIES OR OTHERWISE NO SALESMAN EMPLOYEE OR AGENT OF APC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY WARRANTY TERMS MAY BE MODIFIED IF AT ALL ONLY IN WRITING SIGNED BY AN APC OFFICER AND LEGAL DEPARTMENT Warranty claims Customers with warranty claims issues may acc
13. a ai ln aiia kq a a 14 Troubleshooting kk kk da cin kk kk kk kk kk kk TA kk kk kk kk kk Maintenance Transport and Service Replace battery modules OK eee 19 SENICE ou oq psa rm EE ea E rd tud idu dene ees Pete uod 20 Two Year Werraniy ssoedcee ecu edu 23 kk kk kk kk kk or bor kk dese Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Regulatory Information k kk kk kk KK KK KK RR 22 Regulatory Agency Approvals Radio Frequency Warnings Declaration of Conformity o ee om e RE chad on har K x n ay ae an We oe ee IR na 22 ii Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Introduction Introduction About this UPS The American Power Conversion APC Uninterruptible Power Supply UPS provides protection for electronic equipment from utility power blackouts brownouts sags and surges The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged Unpack Read the Safety Guide before installing the UPS Inspect the UPS upon receipt Notify the carrier and dealer if there is damage The packaging is recyclable save it for reuse or dispose of it properly The UPS and the battery modules a
14. arm Delay Enable Enable Mute ongoing alarms or disable all alarms Control Mute Disable Shutdown Delay 90 seconds 0s 360s Set the interval between the time when the UPS 90s 450 s receives a shutdown command and actual 1805 540 s shutdown 270s 630s 14 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Configuration Factory User Selectable Function Default Choices Description Low Battery 2 minutes Brightly The low battery warning beeps are continuous Warning je ba illuminated when two minutes of run time remain PowerChute low battery warning To change the default interval setting use a software interface provides automatic unattended shutdown when approximately two minutes of battery operated run time remains LED is located on rear panel level of about 2 minutes Dimly illuminated low battery warning level of about 5 minutes No illumination low battery warning level is about 8 minutes pointed object such as a pen to press the VOLTAGE SENSITIVIY switch rear panel while pressing the button front display Change the low battery warning interval setting to the time that the operating system or system software requires to safely shut down Synchronized 0 seconds 0s 240s Specify the time the UPS will wait after the Turn on Delay 60s 300 s return of utility power before start up to avoid 120s e 360 s branch circuit overload 180s 420 s Hig
15. at the battery Close and secure battery doors Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 5 Installation Rack mount to tower conversion procedure during installation Refer to the battery removal instructions on the packaging G The UPS and the battery modules are heavy Remove the battery modules to lighten the UPS Install stabilizer brackets Stand the UPS on the side with the embossed marks Secure a stabilizer bracket supplied to both sides of the UPS Secure each bracket with two pan head locking screws supplied Install two top covers Install the large top cover by placing it in the slots on the UPS and sliding the cover forward Install the small top cover by placing it in the slots on the UPS and sliding the cover forward Secure the top covers with a 8 black screw supplied Install batteries Connect only the first two batteries in the string of three batteries Be sure that the battery A connectors are fully engages Do not connect the single battery or the last battery installed in the string of three batteries Close and secure the battery doors 6 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Installation Input hardwire 230 V models only Hardwiring must be performed by a qualified electrician Adhere to all national and local regulations 1 nA BW N Use
16. ation Battery disconnect cord Tower configuration Battery disconnect cord After all of the batteries have been connected tuck the battery cables and the battery disconnect cord in the space provided in the battery doors This will ensure a secure fit of the bezel to the unit Configure bezel Snap the display out of the bezel Rotate the bezel and reinstall the display for a tower configuration Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Installation Connect display cable and install bezel Rack mount configuration Tower configuration Display cable Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 9 Start up Start up Connect Equipment and Power to the UPS 1 The UPS features a chassis ground connection screw located on the rear panel for connecting the ground leads on transient voltage devices Prior to connecting the grounding wire ensure that the UPS is NOT connected to utility or battery power 2 Connect equipment to the UPS 3 208 V models Plug the UPS into a two pole three wir
17. ch rail bracket and rail cleat to the UPS One rack mount bracket and one rail cleat must be secured to both sides of the UPS Rack mount brackets Rail cleat FS Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Installation Install unit in rack Ensure rack stability prior to installing devices in the rack When installing rails in the rack install two cage nuts above each rail see diagram below Secure the UPS in the rack using the four cage nuts and eight ornamental screws included in the package coool y n m H Second cage nut count three q fan n holes up from first cage nut 3 holes id Dean lej c 6 ds H 1 3 holes Y e 6 ID SUI 4 First cage nut count four holes 4 holes f B8 B 4 holes up from top edge of rail Ue germ o c Q P e j do o o O li c G G The UPS must be installed at the bottom of the rack 4 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Installation Install batteries connectors are fully engaged Do not connect the single battery or the last battery installed in the string of three batteries Connect only the first two batteries in the string of three batteries Be sure th
18. d outage None The UPS will restart automatically when utility power is restored and the battery has a sufficient charge 16 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Troubleshooting Problem and or Possible Cause Solution The Overload LED is illuminated and the UPS emits a sustained alarm tone The UPS is overloaded The connected equipment exceeds the specified maximum load as defined in Specifications on the APC Web site www apc com The alarm remains on until the overload is removed Disconnect nonessential equipment from the UPS to eliminate the overload condition The UPS continues to supply power as long as it is online and the circuit breaker does not trip the UPS will not provide power from batteries in the event of a utility voltage interruption The Disconnected Battery Replace Battery LED is illuminated The Disconnected Battery Replace Battery LED flashes and a short beep is emitted every two seconds to indicate the battery is disconnected Check that the battery connectors are fully engaged Weak battery Allow the battery to recharge for 24 hours and perform a self test If the problem persists after recharging replace the battery Failure of a battery self test Replace Battery Battery Disconnected LED illuminates and the UPS emits short beeps for one minute The UPS repeats the alarm every five hours Allow the battery to recharge for
19. e grounded receptacle only Avoid using extension cords 230 V models Refer to the Input Hardwire section in this manual 4 To use the UPS as a master on off switch be sure all connected equipment is switched on Rear Panels 208 V models j i I i 230 V models 3 O D 3 O SSH ese B mw oos OX XXX XX Bes 3 O 2 B Or Bee os Qe Di S e je OO OO nee GOGOOOOOOt zs OX Ox ey Qe Bee eeneesee 52 p O EES E a e Start the UPS 1 Press the button on the front panel to start the UPS The battery charges to 90 capacity during the first four hours of normal operation Do not expect full battery run capability during this initial charge period Refer to the APC Web site www apc com for battery runtimes 2 For optimal computer system security install PowerChute Smart UPS monitoring software 10 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Start up Communication ports SERIAL PORT Use only the supplied cable to connect to the serial port A standard serial NEN interface cable is incompatible with the UPS eje Emergency power off The emergency power off EPO feature is user configurable EPO provides immediate de energizing of connect
20. ed equipment from a remote location without switching to battery operation 1 Use the EPO connector supplied with the UPS 2 Use a normally open contact to connect the 24 terminal to the IN terminal External voltage is not required 3 Wire the four pin connector to the EPO system EPO PORT EPO located on rear panel Connector The EPO interface is a Safety Extra Low Voltage SELV circuit Connect it only to other SELV circuits The EPO interface monitors circuits that have no determined voltage potential Such closure circuits may be provided by a switch or relay properly isolated from the utility To avoid damage to the UPS do not connect the EPO interface to any circuit other than a closure type circuit Use one of the following cable types to connect the UPS to the EPO switch e CL2 Class 2 cable for general use e CL2P Plenum cable for use in ducts plenums and other spaces used for environmental air e CL2R Riser cable for use in a vertical run in a floor to floor shaft e CLEX Limited use cable for use in dwellings and for use in raceways For installation in Canada Use only CSA certified type ELC extra low voltage control cable For installation in other countries Use standard low voltage cable in accordance with national and local regulations Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 11 Operation Operation Display Pa
21. ess the APC customer support network through the Support page of the APC Web site www apc com support Select your country from the country selection pull down menu Open the Support tab at the top of the Web page to obtain contact information for customer support in your region Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 21 Regulatory Information Regulatory Information Regulatory Agency Approvals Radio Frequency Warnings Declaration of Conformity FCC Compliance Notice This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy If it is not installed and used in accordance with the instruction manual it may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case users will be required to take whatever measures may be necessary to correct the interference at their own expense 208 V models LISTE 1888888 42C2 E95463 230 V models CE C QE Co Qu APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways e Refer to the APC Web site
22. h Transfer Point 208 V models To avoid unnecessary use of the battery where 225 Vac 225 Vac 233 Vac utility voltage is chronically high set the high e 229 Vac 237 Vac transfer point higher if the connected 230 V models equipment can tolerate this condition 253 Vac 253 Vac 261 Vac 257 Vac 265 Vac Low Transfer Point 208 V models To avoid unnecessary use of the battery where 182 Vac 182 Vac 174 Vac utility voltage is chronically low set the low e 178 Vac e 170 Vac transfer point lower if the connected equipment 230 V models can tolerate this condition 208 Vac 196 Vac 204 Vac 200 Vac 208 Vac Output Voltage Set the output voltage of the UPS 230 V models 230 Vac 220 Vac 240 Vac 230 Vac Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 15 Troubleshooting Troubleshooting Use this chart to solve minor UPS installation and operation problems Refer to www apc com for assistance with complex UPS problems Problem and or Possible Cause UPS will not turn on Solution The battery is not connected properly Check that the battery connector is fully engaged button not pushed Press the button once to power up the UPS and connected equipment The UPS is not connected to utility power supply Check that the power cable from the UPS to the utility power supply is securely connected at both ends Very low or no utility voltage Check the
23. nels 208 V models 084 0 gQ 096 067 072 050 Q 048 033 024 016 L O lt 24 Load Battery Charge 230 V models 084 TEN 2 096 067 Z i 072 050 a 9 o 85 048 033 024 016 O 2496 Display Panel Indicators and Function Buttons ou Indicator Title Description AVR Trim The UPS is compensating for a high utility voltage Refer to the APC Web site www apc com for AVR settings On Line The UPS is supplying utility power to the connected equipment see Troubleshooting in this manual AVR Boost The UPS is compensating for a low utility voltage Refer to the APC Web site www apc com for AVR settings Overload The connected equipment is drawing more than the UPS power rating allows see Troubleshooting in this manual 5 2 2 On Battery The UPS is supplying battery power to the connected equipment le Disconnected Battery The battery is disconnected or must be replaced Replace Battery see Troubleshooting in this manual E 12 Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Operation Indicator LED Indicator Title Description 230v 208 v Diagnostic The UPS has a diagnostic feature that indicates the utility voltage 0266 0133 Utility Voltage The UPS starts a self test as part of this procedure The self test does not affect the 0248 0123 voltage display 0229 0115 0191
24. oo Press and hold the button to view the utility voltage bar graph indicator As _ Battery Charge soon as the on line LED starts flashing indicating a self test is in progress the five LED Battery Charge indicator will show the utility input voltage Refer to the figure on the left for the voltage reading Values are not listed on the UPS The indicator on the UPS shows the voltage is between the displayed value on the list and the next higher value see Troubleshooting in this manual Feature Button Feature Title Function Power On Press this button to turn on the UPS Continue reading for additional capabilities Self Test Automatic The UPS performs a self test automatically when turned on and every two weeks thereafter by default During the self test the UPS briefly operates the connected equipment on battery Manual Press and hold the button for a few seconds to initiate the self test Cold Start When there is no utility power and the UPS is off the cold start feature will switch the UPS and connected equipment onto battery power see Troubleshooting in this manual Power Off Press this button to turn off the UPS Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 13 Configuration Configuration UPS settings Settings are adjusted through PowerChute software or optional SmartSlot accessory cards battery operation to protect the
25. re heavy Remove the battery modules to lighten the UPS during installation Refer to battery removal instructions on the packaging Check the package contents UPS Two rack mount brackets used as Additional contents for Front bezel stabilizers in tower configuration 230 V models Display bezel Eight pan head locking screws EC power connector Top covers 2 and one screw Two rail cleats EC jumper cables tower configuration Eight pan head screws EPO connector Literature kit containing Serial cable Product documentation Eight ornamental screws for Smart UPS User Manuals CD securing the unit in the rack PowerChute Business Edition CD Four cage nuts Safety information Warranty information Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual 1 Specifications Hardware SD pan head screws for securing rail cleats to UPS AF UPS pan head locking screws for securing rack mount brackets stabilizer brackets to the IB pan head locking screw black for securing top covers to UPS ornamental screws for securing UPS to rack 4 cage nuts for rack installation rack mount brackets for rack mount configuration stabilizer brackets for tower configuration 2 rail cleats Specifications Temperature This unit is intended for indoor Operating 32 to 104 F 0 to 40 C u
26. se only Select a location sturdy Storage 5 to 86 F 15 to 30 C charge the UPS battery every six enough to handle the weight months Do not operate the UPS where 86 to 113 F 30 to 45 C charge the UPS battery every three there is excessive dust or the months temperature or humidity are Maximum outside the specified limits Elevation Environmental factors impact Operating 6562 ft 2 000 m battery life High temperatures Storage 50 000 ft 15 240 m poor utility power and frequent short duration discharges will shorten battery life Humidity 0 to 95 relative humidity non condensing Weight 215 lbs 98 kg with battery module 215 Ibs 98 kg ia 107 Ibs 49 kg without battery module 27 lbs 12 kg each battery module NOTE The model and serial numbers are located on a small rear panel label For some models an additional label is located on the chassis under the front bezel Smart UPS 5000 VA 208 230 Vac Tower Rack Mount 5U User Manual Installation Installation Rack mount configuration This unit is intended for mounting in a four post rack To order a two post rack mount kit contact your dealer or refer to the APC Web site www apc com The UPS and the battery modules are heavy Remove the battery modules to lighten the UPS during installation Refer to the battery removal instructions on the packaging Install rack mount brackets and rail cleats Four screws must be used to secure ea
27. www ape com Smart UPS Uninterruptible Power Supply Tower Rack Mount 5U 5000 VA 208 230 Vac English 990 8500A 04 2008 Contents Hmiclelllal l l MIR About this UPS llle ntn 1 Unpack 222 92 9k I REECRGxGE ee Se ee RU RLE ao 1 MPCCIICAUONS A Ax kk a aa aa RR a a k n ay RE d a E SRM EE Installation CL Rack mount configuration kk kk kk kk kk kk kk kk kk kk kk nnn 3 Rack mount to tower conversion procedure KK KI 6 Input hardwire 230 V models only kK kK KI RIK KK eee 7 AccessorieS 2 eee allkl a d eee ea Ee ee eee an al kk 7 Connect batteries kaka kk kk kk ka kk kk ak a a a a a a ak a a kk kk ka 8 Configure bezel s a s ak a xa k y al a a da b ee 8 Connect display cable and install bezel 00 000 ee eee KK K 9 StartUp 664 oh eer ee eevee ser um Connect Equipment and Power tothe UPS kK RR RR KK KK KS 10 Communication ports kk kk kk kk kk kk kK es 11 Emergency power off 4 kk kk kk kk kk kK kK kK es 11 OperallONl s xa sa saqa E a roura l le Ea e ana er kb le al ki WE esse Display Panels ss aa a anam a aka ak mr lal aha an aa da RR j a 12 Display Panel Indicators and Function Buttons 12 Configuration 4 gt ss ad s al ak ER ak apa a dag E RE ERES UPS settingS i kake a k kk aa RR al a da lan