Home
Tripp Lite 25U SmartRack Standard-Depth Server Rack Enclosure Cabinet with doors & side panels
Contents
1. SS gt E POveviW 2 E e E E E Preparation 4 Unpacking 4 Placement 5 Leveling 6 Ground Connection 6 7H Adding or Removing Front and Rear Doors 7 Reversing Front Door 7 Adding or Removing Roof Panel 9 Adding or Removing Side Panels 9 Adjusting Mounting Rails and Cable Management Rails 10 Combining Baying Enclosures 11 Equipment Installation eC i 0 Installing or Removing Cage Nuts 12 Sa 1 3 Storage and Service 13 Warranty and Warranty Registration 13 Espanol 14 Fran ais 27 TRIPP LITE 1111 W 35th Street Chicago IL 60609 USA 773 869 1234 www tripplite com Copyright 2007 Tripp Lite All trademarks are the sole property of their respective owners Important Safety Instructions VAN SAVE THESE INSTRUCTIONS All sections of this manual contain instructions and warnings that should be followed during the installation and use of the SmartRack Enclosures described in this manual Read all instructions and warnings thoroughly before attempting to move install or use the SmartRack Enclosures described in this manual Failure to comply will create a risk of personal injury and property damage and may invalidate the warranty Keep the enclosure in a controlled indoor environment away from moisture temperature extremes flammable liquids and gasses conductive contaminants dust and direct sunlight Leave adequate space at the front and rear of the enclosure for proper ventilati
2. Casters EX and Levelers E Mounting Rails Provide horizontal and vertical mounting points for equipment Keys One for the doors and one for the side panels BR OAEON E Locking Reversible Front Door Not Shown Mounting hardware documentation shipping brackets and other shipping materials Enclosure Installation Caution Read All Instructions and Warnings Before Installation WARNING The rack enclosure is extremely heavy Do not attempt to unpack move or install the enclosure without assistance Until it has been properly installed and stabilized the enclosure is prone to tipping and could cause property damage and or personal injury Use extreme caution when handling the enclosure and be sure to follow all handling and installation instructions Do not attempt to install equipment without first stabilizing the enclosure Preparation The enclosure must be installed in a structurally sound area with a level floor that is able to bear the weight of the enclosure all the equipment that will be installed in the enclosure and any other enclosures and or equipment that will be installed nearby Before unpacking the enclosure you should transport the shipping container closer to the final installation location to minimize the distance you will need to move the unit after the protective packaging has been removed If you plan to store the enclosure for an extended period before installation follow the instructions in the Storage and Servic
3. Rack Height Side Panels Stock Pallet They feature adaptable heavy duty cabinets in 25U SR25UBEXP 25U No No 42U and 48U heights with or without side panels SR25UBSP1 25U Yes Yes Several models are available with an integrated shock SR25UBEXPSP1 25U No Yes pallet that allows resellers integrators and enterprise SR42UB 42U Yes No customers to pre configure equipment and re ship the SR42UBEXP 42U No No enclosures to the final installation site SR42UBSP1 42U Yes Yes SR42UBEXPSP1 42U No Yes SmartRack Enclosures have variable mounting depths SR48UB 48U Yes No ideal for servers Integrated baying hardware enables SR48UBEXP 48U No No cost effective orderly and efficient expansion The SR48UBSP1 48U Yes Yes cabinets include quick release doors and side panels SR48UBEXPSP1 48U No Yes for convenient maintenance and split rear doors for improved access and reduced clearance requirements See the Specifications section for more information Front access doors are reversible for installation flexibility Front and rear doors and side panels are lockable Feature Identification Model SR42UB is shown The other models have similar features with the differences noted Roof Panel Locking Split Rear Doors Locking Side Panels 25U enclosures use 2 side panels instead of 4 Side panels are not included with EXP models Cable Management Rails
4. proceeding toward the top of the enclosure never the reverse If using sliding equipment rails be careful when extending the rails Do not extend more than one set of sliding equipment rails at one time Avoid extending sliding equipment rails near the top of the enclosure Note The square holes at the middle of each rack unit are numbered and also include a small notch to aid identification A single rack unit includes the space occupied by the numbered hole and the holes directly above and below 25 OTON U 1 Rack Unit LIOOU WO Equipment Installation Installing or Removing Cage Nuts WARNING The flanges of the cage nuts should engage the sides of the square opening in the rail not the top and bottom Follow the instructions in your equipment documentation to ensure proper installation of your equipment Installing Cage Nuts El Locate the numbered square openings in the mounting rails where you plan to install your equipment You will install cage nuts included into the square openings in order to provide an attachment point for the mounting screws included Note Consult your equipment documentation to determine how many cage nuts will be required and where they will need to be installed E From the inside of the mounting rail insert one of the flanges of the cage nut through the squar
5. 3 kg 1022 kg 2261 mm 600 mm 1092 mm 2413 mm 705mm 1194 mm 163 2 kg SR48UBEXPSP1 3000 Ib 2250 Ib 89 in 23 63 in 43 in 95 in 27 75 in 47 in 261 Ib 1363 kg 1022 kg 2261 mm 600 mm 1092 mm 2413 mm 705mm 1194 mm 118 6 kg SP1 models include a shock pallet that allows the enclosure to be shipped with pre installed equipment The maximum shipping capacity is 1250 lb 568 kg including the weight of the enclosure and the pre installed equipment Storage and Service Storage The enclosure should be stored in a controlled indoor environment away from moisture temperature extremes flammable liquids and gasses conductive contaminants dust and direct sunlight Store the enclosure in its original shipping container if possible Service The enclosure is covered by the limited warranty described in this manual For more information call Tripp Lite Customer Service at 773 869 1234 Warranty and Warranty Registration 5 Year Limited Warranty Seller warrants this product if used in accordance with all applicable instructions to be free from original defects in material and workmanship for a period of 5 years from the date of initial purchase If the product should prove defective in material or workmanship within that period Seller will repair or replace the product in its sole discretion THIS WARRAN
6. Ib 2250 Ib 49 in 23 63 in 43 in 55 in 27 75 in 47 in 245 Ib 1363 kg 1022 kg 1245 mm 600 mm 1092 mm 1397 mm 705mm 1194 mm 111 4 kg SR25UBEXPSP1 3000 Ib 2250 Ib 49 in 23 63 in 43 in 55 in 27 75 in 47 in 199 Ib 1363 kg 1022 kg 1245 mm 600 mm 1092 mm 1397 mm 705mm 1194 mm 90 5 kg SR42UB 3000 Ib 2250 Ib 78 5 in 23 63 in 43 in 84 5 in 27 75 in 47 in 304 Ib 1363 kg 1022 kg 1994 mm 600 mm 1092 mm 2146 mm 705mm 1194 mm 138 2 kg SR42UBEXP 3000 Ib 2250 Ib 78 5 in 23 63 in 43 in 84 5 in 27 75 in 47 in 226 Ib 1363 kg 1022 kg 1994 mm 600 mm 1092 mm 2146 mm 705mm 1194 mm 102 7 kg SR42UBSP1 3000 Ib 2250 Ib 78 5 in 23 63 in 43 in 84 5 in 27 75 in 47 in 331 Ib 1363 kg 1022 kg 1994 mm 600 mm 1092 mm 2146 mm 705mm 1194 mm 150 5 kg SR42UBEXPSP1 3000 Ib 2250 Ib 78 5 in 23 63 in 43 in 84 5 in 27 75 in 47 in 253 Ib 1363 kg 1022 kg 1994 mm 600 mm 1092 mm 2146 mm 705mm 1194 mm 115 kg SR48UB 3000 Ib 2250 Ib 89 in 23 63 in 43 in 95 in 27 75 in 47 in 332 Ib 1363 kg 1022 kg 2261 mm 600 mm 1092 mm 2413 mm 705mm 1194 mm 150 9 kg SR48UBEXP 3000 Ib 2250 Ib 89 in 23 63 in 43 in 95 in 27 75 in 47 in 234 Ib 1363 kg 1022 kg 2261 mm 600 mm 1092 mm 2413 mm 705mm 1194 mm 106 4 kg SR48UBSP1 3000 Ib 2250 Ib 89 in 23 63 in 43 in 95 in 27 75 in 47 in 359 Ib 136
7. TY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW ALL IMPLIED WARRANTIES INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES Some states do not allow limitations on how long an implied warranty lasts and some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations or exclusions may not apply to you This warranty gives you specific legal rights and you may have other rights which vary from jurisdiction to jurisdiction WARNING The individual user should take care to determine prior to use whether this device is suitable adequate or safe for the use intended Since individual applications are subject to great variation the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application Warranty Registration Visit www tripplite com warranty today to register the warranty for your new Tripp Lite product You ll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product No purchase necessary Void where prohibited Some restrictions apply See Web site for details Tripp Lite has
8. a policy of continuous improvement Specifications are subject to change without notice Note on Labeling This symbol is used on the product Ground Connection TRIPP LITE 1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com 2009XXXXX 93 2723_EN
9. e opening Press it against the side of the square opening Each flange should engage one side of the square opening not the top or bottom El Compress the cage nut at the sides slightly to allow the remaining flange to fit through the square opening When the cage nut is properly installed both flanges will protrude through the square opening and will be visible on the outer surface of the mounting rail Repeat steps 1 3 until all required cage nuts are installed EJ After installing the required cage nuts use the included mounting screws and cup washers to secure your equipment to the rack rail Place the cup washers between the screws and the equipment mounting brackets Note Your equipment may also include mounting hardware Read the mounting instructions that came with your equipment before installing your equipment To Remove Cage Nuts Reverse Steps 1 3 Note You may wish to use a cage nut tool user supplied to aid cage nut installation and removal Load Capacity Unit Dimensions Shipping Dimensions Model Static Rolling Height Width Depth Height Width Depth Weight SR25UB 3000 Ib 2250 Ib 49 in 23 63 in 43 in 55 in 27 75 in 47 in 218 Ib 1363 kg 1022 kg 1245 mm 600 mm 1092 mm 1397 mm 705mm 1194 mm 99 1 kg SR25UBEXP 3000 Ib 2250 Ib 49 in 23 63 in 43 in 55 in 27 75 in 47 in 172 Ib 1363 kg 1022 kg 1245 mm 600 mm 1092 mm 1397 mm 705mm 1194 mm 78 2 kg SR25UBSP1 3000
10. e section You need several tools user supplied You also need the following hardware included 13 mm Open end Wrench e 60 Phillips head Mounting Screws M6 x 5 8 18 mm Open end Wrench 60 Cage Nuts M6 e Utility Blade e 60 Nylon Cup Washers e Carpenter s Level e Phillips head Screwdriver e 5 32 Allen Wrench Unpacking NOTE If the enclosure is an SP1 model with a shock pallet follow the special unpacking instructions attached to the shipping container instead of the unpacking instructions in this section All warnings still apply El Confirm that the shipping container is upright and stable then use a utility blade to cut the shrink wrap securing the corner protectors Apply the utility blade directly over the corner protectors to prevent the utility blade from scratching the enclosure or cutting the heavy protective plastic bag beneath the shrink wrap WARNING Do not scratch the enclosure or cut the heavy plastic bag beneath the shrink wrap Do not push or pull the enclosure while unpacking BV Remove the corner protectors Save all packing materials including the pallet for later use unless p p 2 g p you are certain they will not be required The packing materials are recyclable E Remove the heavy plastic bag surrounding the enclosure Examine the enclosure for any damage or loose parts Confirm that all parts are present If anything is missing or damaged contact Tripp Li
11. ginal position Rotate the door 180 degrees and reinstall it on the enclosure Remember to connect the ground wire to the inside of the door using the attachment point nearest the hinge at the top of the door The attachment point is marked with the ground connection symbol E Reinstall the door handle Enclosure Configuration Adding or Removing Roof Panel WARNING Do not attempt to use the roof panel for weight bearing purposes other than those explicitly described and approved by Tripp Lite Do not attempt to add or remove the roof panel without assistance Removing Roof Panel El Pull the 2 pins near the rear of the roof panel While holding the pins push the roof panel upward 1 EB Remove the roof panel tabs EX from the roof panel attachment slots E in the enclosure frame eS Te X s g El Lift the roof panel from the enclosure To Reinstall Roof Panel Reverse Steps 1 3 Adding or Removing Side Panels Removing Side Panel El Open the latch by sliding it downward B Tilt the top of the panel away from the enclosure il Enclosure Configuration Adding or Removing Side Panels continued El Lift the panel away from the brace that supports it To Reinstall Side Panel Reverse Steps 1 3 Adjusting Mounting Rails and Cable Management Rails WARNING Do not attempt to adjust rails without assistance Do not attempt to adjust rails while equipment is installed i
12. ing each leveler use the carpenter s level to confirm that the enclosure is level in all directions Adjust the levelers as required until the enclosure is level E Optional If you wish to provide an additional measure of stability you can attach the 2 shipping brackets using the hardware that attached the enclosure to the shipping pallet Use a 13 mm open end wrench to connect the brackets to the outer EY or inner E bracket mounting points of the enclosure Attach the brackets to secure mounting points in the floor using user supplied hardware or Tripp Lite s SmartRack Bolt Down Kit Part SR331 Ground Connection All the parts of the enclosure are grounded to the frame of the enclosure Use the enclosure s front or rear threaded grounding point EY and an M6 screw included to connect the frame of the enclosure directly to your facility s earth ground connection with an 8 AWG 3 264 mm wire Route the ground wire under the enclosure s frame to ensure unhindered door operation WARNING Attach each enclosure to earth ground separately Do not use the enclosure without an earth ground connection lt u ao EARTH mi GROUND Enclosure Configuration Adding or Removing Front and Rear Doors WARNING Do not attempt to add or remove doors without assistance El Disconnect the door s ground wire E Open the door until it is perpendicular 90 degrees to the front of the enclosure E Lift the door fro
13. m the hinges and remove it from the enclosure To Reinstall Door Reverse Steps 1 3 Optional If the enclosure is joined to another enclosure turn the door back toward the enclosure as you lift it from the hinges Reversing Front Door WARNING Do not attempt to reverse the front door without assistance El Remove the screw connecting the ground wire to the inside of the door E Remove the 2 screws connecting the door handle to the door Remove the door handle Enclosure Configuration Reversing Front Door continued E Remove the screw and washer from the rear of the door handle and remove the latching mechanism Rotate the latch washer counter clockwise 90 degrees and reverse the latch so it points in the opposite direction then use the screw and washer to re attach the latch to the rear of the door handle El Remove the door by following the steps in the previous section H Remove the door hinges from the enclosure rotate them 180 degrees and attach them on the opposite side of the enclosure Note The alternate door hinge attachment points have plastic plugs in the screw holes Remove the plugs and insert them in the original door hinge attachment points O Unscrew the 2 hinge mechanisms from the hinge openings inside the door then reattach each of them using the set of screw holes immediately opposite their ori
14. n the enclosure Do not attempt to use rails without screws installed 6 per rail The 4 mounting rails are pre installed to accommodate equipment with a mounting depth of 30 inches 762 mm Do not adjust the mounting rails unless your equipment requires a different mounting depth The front and rear sets of rails can be adjusted independently in 4 inch 6 mm increments for mounting depths between 4 inches 101 6 mm and 42 inches 1066 8 mm El Each rail is connected to the enclosure with 6 screws 1 pair at the upper beam EY 1 pair at the middle beam EJ and 1 pair at the lower beam A bom pi M I l in ome HJ E Remove the screws fastening each of the rear mounting rails to the enclosure If adjustment of the front rails is required you can also remove the screws from the front rails E Slide the mounting rails to the desired depth and reattach them using the screws you removed in Step 2 The rail attachment points are numbered El to help you align each pair of rails at the same depth The depth of the 2 cable management rails can be adjusted using the same method Enclosure Configuration Combining Baying Enclosures WARNING Combining enclosures is not a substitute for stabilizing the enclosures Each enclosure in a bay of combined enclosures requires the same stabilizing measures as a standalone enclosure El Arrange the enclosures in the correct position for baying B Each e
15. nclosure includes 4 baying brackets EN that correspond to baying connection points E on the adjoining enclosure The baying connection points already contain screws Remove the screw from each baying connection point in the adjoining enclosure El Loosen the screw in each baying bracket and turn each bracket 90 degrees toward the adjoining enclosure aligning each bracket with the corresponding baying connection point on the adjoining enclosure 90 DOB El Connect each bracket to the adjoining enclosure using the screws you removed in step 2 but do not tighten the screws completely Adjust the position of the enclosures as needed If you want the centers of the enclosures to be 24 inches 61 cm apart use the outside hole of the bracket 4 If you want the centers to be 60 cm 23 6 inches apart use the middle hole of the bracket BJ After connecting all brackets and confirming that the enclosures do not need further adjustment tighten all screws Note You may wish to remove the doors from the enclosures before combining them Reinstalling the doors afterward is optional Remove the interior side panels before baying enclosures if you wish to enable access between enclosures Equipment Installation WARNING Do not install equipment until you have stabilized the enclosure Install heavier equipment first and install it toward the bottom of the enclosure Install equipment starting from the bottom of the enclosure and
16. on Do not block cover or insert objects into the external ventilation openings of the enclosure e The enclosure is extremely heavy Use caution when handling the enclosure Do not attempt to unpack move or install it unassisted Use a mechanical device such as a forklift or pallet jack to move the enclosure in the shipping container Do not place any object on the enclosure especially containers of liquid and do not attempt to stack the enclosures Inspect the shipping container and the enclosure for shipping damage Do not use the enclosure if it is damaged Leave the enclosure in the shipping container until it has been moved as close to the final installation location as possible The casters are designed for minor position adjustments within the final installation area only The casters are not designed for moving the enclosure over longer distances The casters are not designed to provide long term support for the enclosure after final installation Use the levelers to provide long term support e Install the enclosure in a structurally sound area with a level floor that is able to bear the weight of the enclosure all equipment that will be installed in the enclosure and any other enclosures and or equipment that will be installed nearby Do not push the enclosure from the side panels to move it Pushing from the side panels will cause a tipping hazard e When rolling the enclosure on its casters always push it from behind neve
17. r pull it toward you e A rolling enclosure can cause personal injury and property damage if not properly supervised If rolling the enclosure down a ramp is required use extreme caution Do not attempt to use ramps that have a slope steeper than 1 12 Use caution when cutting packing materials The enclosure could be scratched causing damage not covered by the warranty e Save all packing materials for later use Repacking and shipping the enclosure without the original packing materials may cause product damage that will void the warranty Do not re ship the enclosure with additional equipment unless the enclosure was shipped with a special shock pallet SP1 models only The combined weight of the enclosure and installed equipment must not exceed the load capacity of the pallet Tripp Lite is not responsible for any damage that occurs during re shipment e Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence of a flammable anesthetic mixture with air oxygen or nitrous oxide Overview SmartRack Enclosures accommodate all standard 19 Available SmartRack Enclosures inch rackmount equipment regardless of vendor and z ship fully assembled for quick and easy deployment Moe
18. required the enclosure can be lifted by attaching 4 user supplied M8 diameter eye bolts to the threaded holes near the upper corners of the enclosure frame Use steel bolts with an ISO strength rating of 8 8 or higher The 4 bolts can support the weight of the enclosure and up to 1000 Ib 450 kg of installed equipment WARNING Only experienced equipment operators should attempt to lift the enclosure Use appropriate equipment and follow all applicable safety procedures and regulations Enclosure Installation Leveling WARNING Level the enclosure before attempting to install equipment The casters are not designed to provide long term support for the enclosure Use the levelers to provide long term support Install the enclosure in a structurally sound area with a level floor that is able to bear the weight of the enclosure all equipment that will be installed in the enclosure and any other enclosures and or equipment that will be installed nearby El After the enclosure has been moved to the installation location use a carpenter s level to check the slope of the floor If the floor slopes more than 1 choose an alternate installation site E Use an 18 mm open end wrench to lower each leveler EN until it reaches the floor There are 4 levelers 2 at the front and 2 at the rear Make sure each leveler contacts the floor solidly Note Lower a leveler by turning it clockwise raise a leveler by turning it counter clockwise E After lower
19. te for assistance Do not attempt to use the enclosure if it has been damaged Enclosure Installation Unpacking continued El Use the key to open the enclosure s doors and locate the 2 shipping brackets EN that attach the enclosure to the shipping pallet The brackets are located inside the enclosure Note The keys are attached to the front of the enclosure E Use a 13 mm open end wrench to remove the shipping brackets Be extremely careful as the enclosure could shift unexpectedly after bracket removal Save the brackets and bracket hardware for later use O Position at least one person at the front of the enclosure and one person at the rear of the enclosure Slowly push the enclosure toward the back of the shipping pallet until all four casters go over the edge of the pallet and touch the floor WARNING Use at least one assistant when removing the enclosure from the pallet Be extremely careful when moving the enclosure Placement El Use the casters to move the enclosure for a short distance over a level smooth stable surface by pushing it from the front or rear not the side panels Do not attempt to roll the enclosure over long distances The enclosure should be moved close to its installation location inside its shipping container before it is unpacked Use a forklift or pallet jack to move the shipping container WARNING Do not push or pull the enclosure at the side panels or pull the enclosure toward you If
Download Pdf Manuals
Related Search
Related Contents
Samsung 320P Priručnik za korisnike Bad Boy Mowers Lawn Mower 48031301 User's Manual MANUEL D`INSTRUCTIONS - Maison de la détection 日本語 - Kodak Para descargar la ficha técnica de la máquina, haga clic Installation guide Linksys WAP54GPE User's Manual Toshiba Satellite S55-B5266 Télécharger User`s Manual VE-1000-SIT Intensified Camera Copyright © All rights reserved.