1. How To Contact ABC 5 tee tte e eb adore ERES LASER 6 North Americas uite ree ree e Ree evt a 6 Latin America South America 6 Europe Middle East and Africa sese 6 Japan Asia Australia 5 nee hne area 6 Product OYetview iioi HR eget e HERRERA 7 Front View Component Identification eee 7 Rear View Component Identification eee 8 System Block Diagram sees ener 10 Chapter 3 Installation eee ee eee eee ente ette ette sten sten sette stas ta sena 11 Unpacking eet eee d teta Perdre 11 InSpectiOnl 1er ede eet oett leone tero dene e ere bate 11 C ODtents s riu eet eiae Pe c Eee ERU ee LE SER H Ma CERA ERR EHE ORE 11 Placement 25 eee Gn BRI ee HERR 11 Installing the Symmetra RM eere 11 Position the Symmetra RM eese 11 Connect the Symmetra RM to its Power Source 13 Wire the Emergency Power Off EPO Switch i 14 Install Modules Into the Symmetra RM Frame 15 Connect Equipment to the Symmetra RM eese 16 Appendix A Electrical Wiring Checklist rene 17 Table of Contents 990 1031 Revision 1 8 00 List of Figures Figure 1 Symmetra RM alal RR RH IR Ee dete eel 5 Figure 2 Front View of the Symmetra RM ii 7 Figure 3 Rear View of the Symmetra RM 200 208
2. Install Modules Into the Symmetra RM Frame 3c o Olo i lo Power Module Redundant Intelligence Module Main Intelligence Module O Battery Module o Figure 7 Bay Identification The intelligence modules are shipped in the Symmetra RM frame After the frame is installed in the rack you must install the power and battery modules into the frame 15 QD Install battery modules just prior to running the Symmetra RM The battery modules discharge slowly when loaded prematurely and can be damaged permanently Each battery module weighs 21 8 kg 48 lbs Two people are required to install or remove battery modules Battery Module With one person on either side of the battery module lift the module and slide it completely into the frame to engage the internal electrical connector The top of each battery module has a tab to align the module connector with the connector inside the bay This tab ensures that only battery modules will fit into the bay Tighten the two 2 screws to secure the module Position battery modules in the bays on the right before filling bays on the left Power Module Lift the power module and slide the module into a bay until flush with frame to engage the internal connector The side of the power module has a
3. These products must be hard wired to the input power Maintenance Bypass Switch When switched to the On position the maintenance bypass switch bypasses the Symmetra RM and causes the load equipment to be powered directly from utility power When it is switched to the Off position utility power flows into the Symmetra RM and conditioned power is delivered to the load equipment Under normal operating conditions the maintenance bypass switch remains in the Off position N The load equipment is unprotected when the maintenance bypass switch is in the On position Input Wiring Access Panels O Provides access to wiring terminal blocks for input wiring The 200 208 L1 L2 G version must be hard wired if the load is greater than 5 kVA The 220 230 240 L1 N G version must always be hard wired Input Power Cord O on 200 208 L1 L2 G versions only The 200 208 L1 L2 G version can use the line cord to connect to the power source if the load is less than 5 kVA If the load is greater than 5 kVA the unit must be hard wired to the power source The 220 230 240 L1 N G version must always be hard wired System Block Diagram Accessory DB9 COM Port External Battery Frame COM Cards COM Card Battery Module 120 VDC Battery Module 120 VDC Battery Module 120 VDC External Battery Power AC in 155 to 276 VAC Battery Monitor Power Module Power or Battery
4. 200 208 L1 L2 G unit with a load greater than 5 kVA QD Only an authorized electrician should install all power and control wiring according to Use flexible metal conduit to make maintenance and service easier 13 TE Make sure the main circuit breaker located on the rear Q panel is in the OFF position em el e 88 MN e 2 Select the appropriate wire size and connectors according to local codes For most applications 10 AWG 5 sq mm wire should be sufficient x 3 Remove the input wiring access door by unscrewing the single screw that holds the access panels in place The input wiring terminal is located on the rear panel of the Symmetra RM pi ICE ODUE pou 8938665 LS 4 Use a screwdriver or any hard object to detach the circular knockout in the wire input plate You may need to use pliers to fully detach the knockout 5 Feed the wire cable through the hole on the wire input plate Using a threaded lock nut fasten the plate to the selected cable po or conduit connector Fai n 5 zs ii 6 Use a knife to strip off the plastic on the end of the cable to Lui E expose the copper wire Strip all three wires l pu IRR 7 Usea flat head screwdriver to connect the wires to t
5. Vac L1 L2 G version shoWn iii 8 Fig re4 System Block Diagr m eene esee e A EAA AEN ERA 10 Figure 5 BPO Connection Option 2 i tte ete ette ea E Oe bete pe P EAEE pape toe 15 Figure 6 BPO Connection Option 2 seer itinere E eret Regen eset pe Hee e pe pede ee ore Ee eh uae Preces 15 Figure 7 Bay Identification neues ee RA ee eere erede ric te eee de s eo oe i 15 Figure 8 Power Distribution Panels esee eene nennen nennen tnter enr enr enne 16 990 1031 Revision 1 8 00 CHAPTER 1 SAFETY INFORMATION This Safety section contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries It is intended for APC customers who setup install relocate or maintain APC equipment Connection to the branch circuit mains must be performed by a Licensed Electrician Installation and removal of the Power Battery and Intelligence modules must be performed by service personnel Installation and removal of interface accessories must be performed by service personnel Operation of the Symmetra RM can be performed by any individual with no previous technical experience Conventions Used in this Manual This section defines the symbols used throughout this manual Carefully read all information boxes and abide by the instructions The WARNING sign denotes a serious hazard It calls attention to a procedure practice condition or the like w
6. APC Symmetra RM Installation Manual English WWwWW apcc coim 990 1031 Revision 1 8 00 Limited Warranty American Power Conversion APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase except in India where the period is one year for battery module s Its obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products To obtain service under warranty you must obtain a Returned Material Authorization RMA number from customer support see Service in the SYMMETRA RM OPERATION MANUAL Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not apply to equipment which has been damaged by accident negligence or misapplication or has been altered or modified in any way This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase EXCEPT AS PROVIDED HEREIN AMERICAN POWER CONVERSION MAKES NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the pu
7. Module Power or Battery Module Power or Battery Module Input Circuit Breaker Backfeed Relay Figure 4 System Block Diagram 10 ACCESSORY PASS THROUGH BUS Automatic Bypass Manual Bypass CHAPTER 3 INSTALLATION Unpacking APC has taken care to design robust packaging for your product However accidents and damage may occur during shipment Inspection Inspect the UPS upon receipt Notify the carrier and dealer if there is damage The packaging is recyclable save it for reuse or dispose of it properly Contents The shipping package contains the UPS one PowerView display bezel three blank bezels the mounting rail kit containing the mounting rails and hardware one blank panel kit containing five blank panels screws and instructions and a literature kit Placement Fant office environment Install it in a protected area that is free of excessive dust corrosion conductive contaminants and has adequate air flow Do not operate the UPS where the temperature and humidity are outside the specified limits l l immi NE ais The Symmetra RM is designed for use in a data center or other x QD Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the warranty Installing the Symmetra RM Installing the Symmetra RM is a five step process 1 Position the Symmet
8. Switzerland 0800 556177 Hungary 06800 12221 Turkey 0800 35390275 Israeli 177 353 2206 United Kingdom 0800 132990 Japan Asia Australia Australia New Zealand esses 61 2 9955 9366 1 800 652 725 Singapore Thailand Vietnam 65 398 1000 LIED 60 3 756 8786 Inn Jb 62 21 6500813 Dp EP 86 10 8529 9888 Hong Kong ener emite ile 85 2 2834 5001 TalW an lsiali iaia i iis 88 622 755 1945 India Nepal Sri Lanka Bangladesh Maldives 91 44 433 1124 Japan kesh DERE OO ani 81 3 5434 2021 lor mH E E RR 82 2 501 6492 Philippines sioni 63 2 813 2662 Product Overview Front View Component Identification I CD S Do 9000000000 000000000 9800908080 DO OO rer 500 000000000 2000000000 o 9999999990 060090000 Tele 99999999900 000000000 er oC ges O 2000000000 000000000 0000000000 i Figure 2 Front View of the Symmetra RM Power Module s The Symmetra RM can support between one and four power modules Each module provides 2 kVA 1 4 KW power Redundant Intelligence Module The redundant intelligence m
9. The PDU panel can be changed in the field by a qualified technician or electrician Input Circuit Breaker The input circuit breaker located at the back of the frame protects the Symmetra RM from extreme overloads When switched to Stand By the Symmetra RM is disconnected from incoming utility voltage When switched to the On position power flows from the utility source into the Symmetra RM Under normal operating conditions the input circuit breaker always remains in the On position Emergency Power Off EPO Switch Connection Use this connection to wire the Symmetra RM to an emergency power off switch located away from the unit This switch shuts off power to Symmetra RM and prevents the unit from operating on battery The terminal connections for the EPO switch are physically isolated from the primary circuitry of the Symmetra RM See Wire the Emergency Power Off EPO Switch page 14 for wiring instructions QD EPO wiring must be installed by a qualified electrician only Input Voltage Selection Switch Set this switch to the appropriate setting either 200 208 L1 L2 G or 220 230 240 L1 N G before powering up the Symmetra RM Products rated 200 208 are typically installed in North America 208 V phase to phase grounding conductor and Japan 200V phase to phase grounding conductor Products rated 2020 230 240 are typically installed in the rest of the world 220 V 230 V or 240 V phase to neutral protective earth
10. ass A FCC limits CHAPTER 2 BASICS About Your UPS The Symmetra RM is a high performance uninterruptible power system in a power array configuration designed to power high availability servers and other sensitive electronic equipment It provides conditioned reliable AC power to connected equipment and provides protection from power blackouts brownouts swells sags surges and interference The Symmetra RM is comprised of a frame and a variable set of modules A system can be configured to deliver a maximum output of 6 kVA N 1 redundant or 6 kVA non redundant Figure 1 Symmetra RM The Symmetra RM is modular in design and contains the following modular components e Power Processing System called the power module e Battery Source called the battery module User interface called the PowerView RM Table 1 End Item Configurations Complete System Battery Modules Power Modules Nominal Input Nominal Output End Item SKU Voltage Voltage SYH2K6RMT 1 1 208 240 208 240 SYH4K6RMT 2 2 208 240 208 240 SYH6K6RMT 3 3 208 240 208 240 SYH2K6RMI 1 1 230 230 SYH4K6RMI 2 2 230 230 SYH6K6RMI 3 3 230 230 SYH2K6RMT PI 1 1 208 240 120 208 SYHAK6RMT PI 2 2 208 240 120 208 SYH6K6RMT P1 3 3 208 240 120 208 Module End Item SKU Redundant Intelligence SYRIM3 Main Intelligence SYMIM3 Battery SYBT2 Power SYPM2KU Description Option End Item SKU St
11. contact APC Symmetra technical support Vin 1 Switch the maintenance bypass switch on Disregard any LED indicator or fault messages on the PowerView Record the output voltage below and compare the value with Vin 1 from step 5 If the two measurements are significantly different contact APC Symmetra technical support Reported Output Voltage Out V Hz Test the EPO switch The system enable switch should physically move to the Stand By position and the system should shut down completely If this does not occur check the connections and the EPO switch to ensure that they are installed and functioning properly Successful completion of steps 1 through 7 indicate that the system wiring is properly installed Turn off breakers and switches and shut down input power to the system Reinstall all wiring access panels on the frame 18
12. d Deliver the battery to an appropriate recycling facility or ship it to information e Store the battery module s in a cool ambient temperature of 25 C e When replacing batteries use only the same APC battery pack SYBT2 2 Recycling of Batteries See your dealer or Replacing Modules in the SYMMETRA RM OPERATION MANUAL for information on replacement battery kits and battery recycling QD e Do not install the battery module s in the frame until you are ready to power up the Symmetra RM Failure to so can result in a deep discharge of the batteries which may cause permanent damage e Store the battery module s in a cool ambient temperature of lt 25 C Radio Frequency Interference This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Shielded signal cables must be used with this product to ensure compliance with the Cl
13. ep Down Transformer 208 to 120 V SYTF2 PDU plate with 8 IEC C13 and 2 IEC C19 receptacles SYPDI PDU plate with 2 L6 20 and 1 L6 30 receptacles SYPD2 PDU plate can connect to other Matrix PDU options 5 How To Contact APC Internet http www apc com support North America Phone 1 800 800 4272 Fax 1 401 788 2743 Email apctech apcc com Latin America South America Argentina 0800 9 APCC 0800 9 2722 MEXICO 95 800 804 4283 Brazil 0800 12 72 21 Uruguay 000 413 598 2139 Colombia 980 15 39 47 Venezuela 8001 2544 Europe Middle East and Africa Phone 353 91 702020 Email apceurtech apcc com Fax 353 91 755275 Web support www apc com support eSupport Ireland 1 800 702000 x 2045 Italy nns 800 874 731 Austria 0800 29 64 80 Luxembourg 0800 2091 Belgium 0800 15063 NOrWay 800 11 632 Czech Republic 0800 102063 Poland 00800 353 1202 Denmark 800 18 153 Portugal 0800 853 182 Finland 9800 13 374 Russia 007 095 9167166 toll number France 0800 906 483 South Africa 0800 994206 Germany 0800 180 1227 Spain 900 95 35 33 Greece 00800 353 12206 Sweden 020 795 419 Holland 0800 0224655
14. hat all switches system enable maintenance bypass input circuit breaker and bypass circuit breaker are in the Off or Stand By position Turn off or unplug all equipment connected to the Symmetra RM Ensure that the input voltage selection switch is in the appropriate position 1 Apply power to the system input Measure the voltage at the input terminal block Record the measured voltages L1 L2 for 200 208 Vac OR L1 Neutral for 220 230 240 Vac QD The measured voltage must be between 184 and 265 V If itis not do not continue Verify the wiring from the power source to the input wiring connections Repeat step 1 L 2 Connect the PowerView display bezel 3 Switch the input circuit breaker then switch the system enable switch on The system will make some clicking sounds as it powers up and may display fault messages on the PowerView display Disregard the messages at this time 4 Press the escape key on the display until the top level menu screen appears Select Status Pressing the enter key opens the voltage status screen shown below Vin Vout lout 237 0 0 0 0 0A N The fault light on the display may remain on Disregard this visual indicator at this time 17 B 8 Electrical Installation Completed by Record input voltages below and compare the values with the measured voltages from step 1 If the two measurements are significantly different
15. he terminal pos P block O Loosen the screw then feed the copper wire into the Ld terminal block and tighten the screw Connect the protective earth ground to the terminal block at the position marked with the ground symbol Connect the three wires 8 Reconnect the wire input plate Align the plate position it into the grooves and slide it to the left 9 Inspect the connections and location of the excess wires before installing the access door 10 Replace the access door and fasten with the screw removed in step 3 Once the electrician is finishing wiring the unit complete the checklist in Appendix A Electrical Wiring Checklist page 17 for verification Wire the Emergency Power Off EPO Switch The Symmetra RM provides an emergency power switch connection that controls electrical power to the unit When this switch is turned on or enabled electrical power to the unit is turned off and the system will not switch to on battery operation You must physically reset the system enable switch on the front of the Symmetra RM to restart the unit Use only a qualified electrician to install the EPO wiring The EPO circuit is considered a Class 2 UL and CSA standards and SELV IEC standard circuit Class 2 Circuit Used in North America by UL and CSA It is defined in the National Electrical Code NFPA 70 Article 725 and in the Canadian Electrical Code C22 1 Section 16 SELV Circuit Used in Euro
16. hich if not correctly performed or adhered to could result in injury to personnel The CAUTION sign denotes a hazard It calls attention to an operating procedure practice or the like which if not correctly performed or adhered to could result in damage to or destruction of all or part of the product condition or the like which is essential to highlight The NOTE sign denotes important information It calls attention to a procedure practice Handling Safety e Be careful Do not lift heavy loads without assistance lt 18 kg lt 40 Ib 32 55 kg 70 120 lb l ae gt 18 32 kg 40 70 lb gt gt 55 kg gt 120 lb an e Equipment with casters is built to move on a smooth surface without any obstacles Do not use a ramp inclined at more than 10 e This equipment is intended for installation in a temperature controlled indoor area see Specifications in the SYMMETRA RM OPERATION MANUAL free of conductive contaminants Electrical Safety Do not work alone under hazardous conditions High short circuit current through conductive materials could cause severe burns A licensed electrician is required to install permanently wired equipment Check that the power cord s plug s and sockets are in good condition To reduce the risk of electric shock when grounding cannot be verified disconnect the equipment from the AC power outlet before installing or connecting t
17. ion shown System Fan The system fan can be replaced in the field Refer to Replacing the System Fan in the SYMMETRA RM OPERATION MANUAL for instructions Accessory Ports APC manufactures a set of auxiliary user interface accessories The Symmetra RM contains a total of three accessory ports The top slot is preloaded with the SYCC card that provides computer and battery ports Two unoccupied accessory slots is provided The Symmetra RM also includes a Web SNMP Management Card for accessing data via a network Other accessory options are available including e Out of Band Monitoring Card formerly named CallUPS initiates telephone notification of power event e Environmental Monitoring Card formerly named MeasureUPS monitors environmental conditions e Control UPS control and monitor via modem A Use only accessory devices labeled Symmetra compatible External Battery Cabinet Connector Connect an External Battery Cabinet to the Symmetra RM using this connector The Symmetra RM can connect to a maximum of seven external battery cabinets in a daisy chain fashion Power Distribution Panel PDU O The type of power panel depends on the voltage range of the Symmetra RM Figure 3 shows a Symmetra RM with a 200 208 Vac L1 L2 G power panel It contains one L6 30 and two L6 20 receptacles The 220 230 240 Vac L1 N G power panel contains eight IEC C13 and two IEC C19 receptacles Figure 8 page 16 shows the two PDU panels
18. k holes if necessary Racks with threaded holes require no preparation 77 Locate the designated U space and counting from a le the bottom mark holes 3 18 and 22 on each front post or ig If your rack has round holes insert clip nuts E A8 i provided into the marked holes If your rack has square holes insert either clip E or BOS 555555 5 555505085505 0 cage nuts into the marked holes cage nut shown These nuts will support the ornamental screws that attach the unit to the rack 1 Loosen the three 3 screws that hold the rails together so that the rails can slide outward Do not detach the rails 2 Align the bottom hole on the mounting rail with the fifth hole counting from the bottom in the U space Use the flat Phillips head screws 10 32 and conical washers to attach the front rail to the rack Expand the rails so that it spans from the front rack post to the back rack post 3 Attach the rail to the back rack post using the same hardware 10 32 flat head screws and conical washers used in step 2 Repeat the process for the other rails 4 Tighten the three 3 screws loosened in step 1 to secure the rails 12 Install the UPS into the Rack E 1 With two people supporting the Symmetra RM one on each side carefully align the cleats on the sides of the unit with the grooves on the T mounting rails Slide the unit into the rack completel
19. lever to help align the connector on the module with the connector inside the bay It also locks the power module in place Tighten the two 2 screws to secure the module A Install cover plates included with the unit over any unused bays Connect Equipment to the Symmetra RM Power is distributed to the connected equipment via the power distribution panel PDU on the rear panel of the Symmetra RM Labeling on the rear panel indicates the circuit breaker outlet groups 220 230 240 L1 N G PDU Panel 200 208 L1 L2 G PDU Panel MS Eight 8 x IEC 320 C13 Two 2 L6 20 OE i Two 2 IEC 320 C19 One 1 L6 30 lode eo ae E o iN rs 5 fol NE Ie E a e amp Figure 8 Power Distribution Panels Use your equipment s power cord to connect to the UPS Turn on all connected equipment the equipment will not be powered until the Symmetra RM is turned on Add accessories for the accessories slot See the literature accompanying the accessory for details accessories If a standard accessory is installed on this UPS follow the installation instructions included with the accessory This UPS is equipped with an accessory slot See the APC website apcc com for available 16 APPENDIX A ELECTRICAL WIRING CHECKLIST Complete this checklist to ensure that the Symmetra RM has been wired properly QD Ensure t
20. n devices blood pumps defibrillators arrhythmia detectors and alarms pacemakers hemodialysis systems peritoneal dialysis systems neonatal ventilator incubators ventilators for both adults and infants anesthesia ventilators infusion pumps and any other device designated as critical by the U S F D A Hospital grade wiring devices and leakage current may be ordered as options on many APC UPS systems APC does not claim that units with this modification are certified or listed as Hospital Grade by APC or any other organization Therefore these units do not meet the requirements for use in direct patient care Entire contents copyright 2000 by American Power Conversion Corporation All rights reserved Reproduction in whole or in part without permission is prohibited APC and PowerChute are registered trademarks of American Power Conversion Corporation All other trademarks are the property of their respective owners 990 1031 Revision 1 8 00 Chapter 1 Safety Information ccscccssccsscsscsscsscssssessscsssecssecees 1 Conventions Used in this Manual seen 1 Handling Safety nenn he aha e eet fee 1 Electrical Safety ila ete iena ian 1 D energizing Safety e Ue tei Cete a ieS aa 2 Battery Safety zer etri eee hee tereti te pete dest 2 Recycling of Batteries air cem Reese eie lira 3 Radio Frequency Interference 3 Chapter HIDE 5 About Y o r UPS e aene ee Re ERES ERR 5
21. o other equipment Reconnect the power cord only after all connections are made Do not handle any kind of metallic connector before the power has been removed Use one hand whenever possible to connect or disconnect signal cables to avoid a possible shock from touching two surfaces with different electrical grounds Connect the equipment to a three wire AC outlet two poles plus ground The receptacle must be connected to appropriate branch circuit mains protection fuse or circuit breaker Connection to any other type of receptacle may result in a shock hazard The protective earth conductor for the Symmetra RM carries the leakage current from the load devices computer equipment Therefore the size of the conductor must be at least as large as the wire required by TEC 950 IEC 950 states the following nominal cross sectional areas Cross sectional Area Rated Current Range mm AWG A 2 5 12 17 25 6 8 33 40 10 6 41 63 16 4 64 80 An insulated grounding conductor that is identical in size insulation material and thickness to the grounded and ungrounded branch circuit supply conductors except that it is green with or without a yellow stripe is to be installed as part of the branch circuit that supplies the Symmetra The grounding conductor described above is to be grounded to earth at the service equipment or if supplied by a separately derived system at the supply transformer or mot
22. odule RIM is a backup version of the main intelligence module MIM It provides redundancy in the event of a MIM failure or while a MIM is being replaced Main Intelligence Module The main intelligence module MIM is the computer of the Symmetra RM It gathers and processes data including monitoring the condition of each of the modules Battery Module s O Each battery module contains multiple batteries housed in the enclosure The Symmetra RM can house up to six battery modules three on the right and three in the lower bays on the left System Enable Switch The system enable switch regulates power to the intelligence modules It does not power the load When the switch is in the On position the Symmetra RM enters the load disconnect operating mode When the switch is in the Stand By position the intelligence modules are disconnected from the utility mains voltage The load is not powered until the Power the Load command is entered into the PowerView RM interface Mounting Rails OG The attached mounting rails one on either side support the Symmetra RM when it is mounted in a rack Mounting Bracket The mounting bracket allows you to secure the Symmetra RM in the rack PowerView RM The PowerView RM is the primary user interface for the Symmetra RM Rear View Component Identification Figure 3 Rear View of the Symmetra RM 200 208 Vac L1 L2 G vers
23. or generator set The attachment plug receptacles in the vicinity of the unit or subsystem are all to be of a grounding type and the grounding conductors serving these receptacles are to be connected to earth ground at the service equipment Deenergizing Safety To remove all power from the Symmetra RM Total Power Off the following series of events must occur in the order listed 1 Set the system enable switch to stand by 2 Set the input circuit breaker to stand by D 3 Remove the battery modules 4 Disconnect the external battery pack if provided 5 Disconnect the Symmetra RM from the mains circuit branch Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly effect its safety or effectiveness is not recommended Battery Safety QD e Risk of electrical shock and and energy hazard 120 V 5 ampere hour battery Before replacing batteries remove conductive jewelry such as chains wrist watches and rings High short circuit current through conductive materials could cause severe burns e Do not dispose of batteries in a fire The batteries may explode e Do not open or mutilate batteries They contain electrolyte that is toxic and harmful to the skin and eyes the supplier in the new battery s packing material See the new battery instructions for more i Batteries must be recycle
24. pe by IEC acronym for safety extra low voltage A SELV circuit is isolated from primary circuitry through an isolating transformer and designed so that under normal conditions the voltage is limited to 42 4 V peak or 60 V dc Both Class 2 and SELV circuits must be isolated from all primary circuitry Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is SELV or Class 2 If there is a question use a contact closure switch 14 Use one of the following cable types to connect the Symmetra RM to the EPO switch CL2 Class 2 cable for general use CL2P Plenum cable for use in ducts plenums and other spaces used for environmental air CL2R Riser cable for use in a vertical run in a shaft of from floor to floor CL2X Limited use cable for use in dwellings and for use in raceway For installation in Canada Use only CSA Certified type ELC extra low voltage control cable Connection Option 1 An electrician must connect to 2 Then both 3 and 4 must be connected to a normally open NO switch contact 200 Ohms PTC 1 2 120 V 24 Vdc m circuit breaker VMID trip coil 3 4 200 Ohms PTC Figure 5 EPO Connection Option 1 Connection Option 2 An electrician must connect the 12 Vdc source and a normally open NO switch contact to 2 and 3 200 Ohms PTC 1 34120 V 24 Vdc circuit breaker VMID trip coil 200 Ohms PTC 4 Figure 6 EPO Connection Option 2
25. ra RM where it will be used This step includes mounting it in a rack if desired Connect the Symmetra RM to its power source Wire the Emergency Power Off EPO switch Install modules into the Symmetra RM frame po uer IPS Connect equipment to the Symmetra RM This section describes each step in detail Position the Symmetra RM QD Do not install the battery module s in the frame until you are ready to power up the Symmetra RM Failure to do so can result in a deep discharge of the batteries which may cause permanent damage Mounting rails are included with the Symmetra RM The rails support the unit in the rack and provide adequate air flow N The Symmetra RM requires two people to install due to its weight 11 Determine the Location of the Symmetra RM in the Rack 1 Selecta location for the Symmetra RM in your NetShelter enclosure or other 19 inch 46 5 cm rack QD Select a location with adequate air flow that is free from excessive dust Ensure that the air vents on the sides of the Symmetra are not blocked e The Symmetra RM is heavy Select a rack location sturdy enough to handle the weight Mount the unit at or near the bottom of the rack Do not operate the unit where temperature or humidity are outside the limits listed in Specifications in the SYMMETRA RM OPERATION MANUAL e The Symmetra RM occupies a space of 8U Some racks have tick marks to indicate the U spaces 2 Prepare the rac
26. rchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL APC BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Specifically APC is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data costs of substitutes claims by third parties or otherwise This warranty gives you specific legal rights and you may also have other rights which vary from state to state Life Support Policy As a general policy American Power Conversion APC does not recommend the use of any of its products in life support applications where failure or malfunction of the APC product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness APC does not recommend the use of any of its products in direct patient care APC will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to APC that a the risks of injury or damage have been minimized b the customer assumes all such risks and c the liability of American Power Conversion is adequately protected under the circumstances Examples of devices considered to be life support devices are neonatal oxygen analyzers nerve stimulators whether used for anesthesia pain relief or other purposes autotransfusio
27. y 2 Use the six 6 ornamental screws supplied with the unit to attach the mounting brackets to the rack post Connect the Symmetra RM to its Power Source 200 208 240 Vac L1 L2 G Symmetra RM The input power can be supplied in two ways the attached line cord can be plugged into an appropriate outlet or the power can be hard wired Use the line cord if the load is 5 kVA If the load is greater than 5 kVA you must hard wire the input power 220 230 240 Vac L1 N G Symmetra RM The input power must be hard wired How to Connect the Input Line Cord If your Symmetra RM is configured for 200 208 Vac L1 L2 G and has a load of 5 kVA or less use the line cord to power the Symmetra RM No wiring is necessary 220 230 240 1 Set the input select switch to 200 208 L1 L2 G 200 208 2 Plug the standard 208 Vac L6 30 power cord into a 30 Amp 208 Vac outlet How to Hard Wire the Symmetra RM Verify that all incoming line voltage utility power and low voltage control circuits are de energized and locked out before installing cables or making connections whether in the junction box or to the Symmetra RM Verify that the battery modules have not been installed in the Symmetra RM If battery module s have been installed remove them before installing any wiring national and local regulations Hard wire the input power on all 220 230 240 Vac L1 N G units and on any
Download Pdf Manuals
Related Search
Related Contents
T S H ー ~` ~~~~ 東芝ネ オポール直付器具取扱説明書 保管用 P R O C E S - V E R B A L Kelowna Irrigation Parks Management System NEBULIZADOR - Twister Medical Assembly Instructions and User Manual Samsung HSB-B425DB User Manual DME-110AC/DC / DPE 110AC/DC / DPE 110AC/DC カネカ 簡易DNA抽出キット(植物用)取扱説明書 通信・信号用SPD Panasonic Mittelmotor Bedienungsanleitung 2013 Copyright © All rights reserved.