Home
installation and maintenance instructions for compact unit
Contents
1. COMPACT Top Power unit Control unit GB COMPACTUT 101208 54 www swegon com Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 www swegon com 55 Transformer Yellow Yellow OO 201202 Supply air fan Blue Brown 3A Yellow Green ogogo PEJ L NJPE L N OJOO T Mosse30e Jajeau JIV 4 4 Ee ue se Ajddns osuas ainssald Jeuiuu481 ODI f j pjay puey uone iunuluo TI e Ley Ue JI eNXS Iosuas aJnssaJd aunyesadua E E Jie 3oe1 xe josues aJnjejeduua S Jie jddns sosu s 7 ME I Sh Jie Jo0pino suas a1nyejeduua E 3 a a gt peg e finog 40SSa22 09 Josuas o es mo 09 774 DOA P Q Ke nooooo O o E o H m E MOIS c il n 18UAJOJSUEJ
2. Difference SA EA C 3 0 Step 2 Breakpoint C 22 0 X1 15 0 Y1 20 0 x2 20 0 Y2 18 0 x3 22 0 Y3 14 0 Setpoint C 21 5 21 5 Min SA temp C 15 0 Min SA temp C 28 0 Outdoor temp compensation X Inactive Active Inactive Active Temperature Winter comp Y1 C 3 0 End point winter X1 C 20 0 Starting point winter X2 C 10 0 Startpoint summer X3 C 25 0 Endpoint summer X4 C 40 0 Summer comp Y2 C 2 0 Summer night cooling X Inactive Active Inactive Active EA temp start C 22 0 EA temp stop C 16 0 Outdoor air temp stop C 10 0 SA Setpoint C 10 0 In oper time start hh mm 23 00 In oper stop hh mm 06 00 Intermittent night time heating Inactive IN Active Inactive L Active EA Room start C 16 0 EA Room stop C 18 0 SA Night setpoint C 28 0 SA flow m s Pa 1 SA flow m2 s Pa 0 0 Damper output 0 Morning BOOST Time hh mm 00 00 Damper X Inactive Active Inactive Active EA fan X Inactive __ Active __ Inactive __ Active EA Room temp 22 0 C EA min 15 0 C SA max 28 0 C External sensor External EA Room X Inactive IQnom Comm Inactive IQnom Comm External outdoor X Inactive IQnom Comm Inactive IQnom Comm 60 www swegon com Registered design The company reserves the right to make design changes without prior notice Sweg
3. AUTO OPERATION MANUAL LOW SPEED MANUAL HIGH SPEED COMPACT U TUE14 40 STOP MAN AUTO OP SETTINGS USER LEVEL INSTALLATION LEVEL Registered design The company reserves the right to make design changes without prior notice Swegon 7 USER LEVEL 7 1 Temperature The basic functions can be preset at INSTALLATION LE VEL and the values can be read and set at USER LEVEL See also Section 9 2 in which the functions for temperature are described in detail IMPORTANT If you intend to substantially alter the tempera ture settings you should first stop the air handling unit before doing so 7 1 1 Readings Used for checking the performance 7 1 2 Settings ERS REGULATION 1 The control unit regulates the relationship between the supply air and the extract air temperatures according to a factory preset curve Settings see the chart to the right as well Value Setting Factory range settings Step 1 4 1 EA SA Differential 1 5 C 2 C Breakpoint refers to 15 23 C 20 C extract air temperature ERS REGULATION 2 The control unit regulates the relationship between the supply air and extract air temperatures according to a custom plotted curve The curve has three adjustable breakpoints Settings see the chart to the right as well Value Setting Factory range settings Extract air temperature X1 10 40 C 15 C X2 10 40 C 20 C x3 10 40 C 22 C Supply air temperatu
4. Supply air temperature setpoint C 15 20 25 Extract air temperature C Factory setting means If the extract air temperature is below 20 C breakpoint the supply air temperature setpoint will be automatically regulated to be 2 C EA SA differential lower If the extract air temperature is above 20 C the supply air temperature setpoint will follow the curve according to Step 1 ERS regulation 2 22 d 9 20 5 HE c Q E Ma 2 g amp 15 a hb amp o Q Q un 1 gt 10 9 12 15 20 25 27 X Extract air temperature C Breakpoints according to factory setting means If the extract air temperature is below 15 C X1 the set point for supply air temperature is constant 20 C Y1 If the extract air temperature is 20 C X2 the supply air temperature set point will be 18 C Y2 If the extract air temperature is above 22 C X3 the supply air temperature setpoint will be constantly 14 C Y3 www swegon com 23 Swegon 9 2 1 2 Supply Air Regulation Supply air regulation involves keeping a constant supply air temperature without consideration to the load in the premises This type of regulation can be used when the load and temperatures of the premises are predictable In most cases a reheating coil needs to be installed possibly a cooling coil as
5. 1 GENERAL 1 1 Range of Application The COMPACT Unit and COMPACT Top are complete air handling units with built in control equipment The air handling units are designed for comfort ventilation and can be utilised in smaller buildings such as offices schools day nurseries public buildings shops and residential build ings The COMPACT Unit air handling units have duct connec tion spigots on their end panels whereas the COMPACT Top units have them at the top The type of unit can therefore be selected on the basis of the amount of space available for installing it and for arranging the ducts The COMPACT Unit and COMPACT Top are one piece air handling units If supplementary function sections such as dampers and air coolers are required they must be in stalled in the ductwork In order to fully obtain all the benefits the COMPACT system has to offer it is important keep in mind the air handling unit s special characteristics in conjunction with designing the project installing the unit adjusting it and operating the system The unit must be installed indoors Important Always read the safety precautions in Section 2 that explain the risks involved in running the unit and designate who shall be permitted to operate and service the unit and carefully follow the installation instructions provided in each paragraph The product identification plate is situated on the top of the air handling unit Refer to the particu
6. SUPPLY AIR Intermittent night time heating with air recirculation section If the extract airflow is set to O and the damper output is not activated the following takes place When conditions for start are met outdoor air and ex haust air shut off dampers remain closed The damper in the air recirculation section is opened The extract air fan is idle The supply air fan operates according to the preset supply airflow and the heating coil downstream of the air hand ling unit operates according to the supply air temperature setpoint until the conditions for stop are met www swegon com 27 Swegon 9 2 5 Morning BOOST The unit is utilised to heat the premises during a preset period prior to the switch in time set on the switch clock The function is used if the air recirculation section is instal led The unit starts early and uses the same operation and temperature regulation settings as it would at the regular start time If the extract air fan is not required to operate the extract airflow can be set to O Damper output can be set to be inactive This means that connected dampers e g outdoor air and exhaust air shut off dampers are not affected Normally these dampers are closed when the unit is stopped and thus they remain closed At the same time the damper in the air recirculation sec tion if included will open Settings Value Setting Factory range setting Time for start prior to regu
7. 3 3 1 Hand held Micro Terminal The hand held micro terminal is equipped a 3 m long cable and a quick fit connector For particulars of the electrical connections see 20 3 1 A holder for the hand held micro terminal is supplied together with the air handling unit The holder can be secured to the outside of the air handling unit or at another appropriate place 3 3 2 Supply Air Sensor The sensor is equipped with a 7 m long cable and a quick fit connector For mounting see 3 6 3 3 3 Document Pocket Secure the document pocket to the exterior of the air handling unit or at another appropriate place 3 4 Location The air handling unit must be mounted horizontally on a flat and firm supporting surface and this surface must be constructed in a way enabling it to support the weight of the unit The design of the COMPACT Unit makes it necessary to mount it on a stand or some other form of base Other wise it will not be possible to open the inspection doors The stand is available as an accessory Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 When installing the air handling unit and connecting pipe work and electric cables make sure that adequate free space is provided for opening the inspection doors and covers and withdrawing functional sections such as filter cassettes and fan assemblies clear of the unit casing Inspection space required COM
8. Economy Cooling BOOST Economy first uses a higher airflow to cool the premises before a start signal is transmitted to the cooling machines The function can also operate without the cooling func tion being activated On a cooling load the flows are slowly increased up to preset maximum flow When the flows are up to max and if a cooing load is still present the output contacts for cooling are activated The cooling boost function requires an outdoor air tem perature of at least 2 C lower than the extract air tempe rature for it to be activated Normal cooling operation is activated if the temperature difference is too small Sequence The cooling BOOST Sequence is used if a cooling machine is sized for a higher than normal cooling flow If there is a cooling load the flow is increased up to the preset max flow before the cooling function is activated The cooling function is delayed 1 minute after the airflow is increased The cooling boost sequence is blocked if no cooling func tion has been selected Comfort Economy Cooling BOOST Comfort Economy is a combination of the two variants for increasing the airflow If the conditions for Cooling BOOST Economy are met the unit will begin increasing the airflow before the cooling unit starts up If the conditions for outdoor air are not met the flow in crease will begin when the supply air temperature reaches the preset Min permissible temperature Economy
9. A A 105 10s 22 23 SA FREQUENCY CONV HALL SENSOR DEFECTIVE HALL SENSOR DEFECTIVE EA FREQUENCY CONV Internal fault in hall sensor A A 10s 10s lt lt 24 25 EA FREQUENCY CONV BLOCKED EA FREQUENCY CONV BLOCKED Motor does not rotate during start up A A 3s 3s Ex 26 27 EA FREQUENCY CONV START UP FAILURE START UP FAILURE EA FREQUENCY CONV Wrong rotation during start up A A 3s 3s Ex 30 EXT EA ROOM TEMP SENSOR DEFECTIVE Temperature sensor in extract air duct or room is not connected Internal bus 1 contact or is faulty or has been selected with communication Applicable if the External sensor extract air room or Intermittent night time heating function is selected A 3s 31 EXT OUTDOOR TEMP SENSOR DEFECTIVE Temperature sensor for outdoor temperature is not connected Internal bus 1 contact or is faulty or has been selected with communication Applicable if the External outdoor sensor function is selected B 3s 34 35 OVER CURRENT IN R HX CONTROLLER Current above the normal level is supplied to the rotary heat exchanger drive motor UNDER VOLTAGE IN R HX CONTROLLER Feed voltage 25V is supplied to the rotary heat exchanger drive motor A KKK A KKK 35 35 36 OVER VOLTAGE IN R HX CONTROLLER Voltage above the normal level 55 V is supplied to the rotary heat excha
10. Size 02 0 2 m3 s Size 03 0 3 m3 s 30 www swegon com GB COMPACTUT 101208 FUNCTIONS TEMPERATURE AIR FLOW PRESSURE FILTER AIRFLOW PRESSURE SA FAN REGULATION OPERATION HEATING EA FAN REGULATION COOLING g j CLEAN AIR CONTROL 1 IN OUTPUTS OUTDOOR TEMP COMP _ 1 NiQnomic Plus 7 SA DOWN REGULATION _ Pepe eh ya 1 SLAVE CONTROL i 2000 E 1500 eo C FEN z g c o o Oo 1000 U 400 10 20 30 40 50 60 70 80 90 VOC Example 800 ppm is equivalent to approx 30 VOC If influenced by other emissions impurities in the air such as cooking odours cigarette smoke etc the VOC content increases in relation to the CO content Registered design The company reserves the right to make design changes without prior notice Swegon 9 3 2 Outdoor Temperature Compensation Airflow Outdoor temperature compensation of the airflow can be activated if it is desired to reduce the airflow in the winter time In the flow regulation mode the current airflow is redu ced In the pressure regulation mode the current setpoint for pressure is reduced The function has no effect if the airflow is demand con trolled The airflow is reduced as a percentage of the current airflow pressure Settings Value Setting Factory range setting Y1 max permissible reduction 0 50 30 96 X1
11. gt Extract air v Exhaust air GB COMPACTUT 101208 The arrangement of the components and their designations OANA MN AWN Supply air fan with motor and motor control system Pressure sensor supply air fan Position on function selector switch 2 Rotation monitor sensor Drive motor rotary heat exchanger Rotary heat exchanger Sensor outdoor air temperature Supply air filter Supply air temp sensor to be mounted in supply air duct Hand held micro terminal Extract air fan with motor and motor control system Pressure sensor extract air fan Position on function selector switch 1 Electrical equipm cubicle with control unit Sensor extract air temperature Extract air filter OUTDOOR AIR EXTRACT AIR SUPPLY AIR EXHAUST AIR Main switch Safety switch www swegon com 5 Swegon 2 SAFETY PRECAUTIONS All staff concerned must acquaint themselves with these instructions before beginning any work on the unit Any damages to the unit or parts of it due to improper han dling or misuse by the purchaser or the fitter cannot be considered subject to guarantee if these instructions have not been followed correctly Warning Only a qualified electrician or service personnel trained by Swegon shall be permitted to modify the air handling unit in conjunction with electrical installations or the wiring of external functions 2 1 Safety switch Main Switch On COMPACT Unit the safety switch is ext
12. COOLING OPERATION MODE COOL REGULATION PERIODIC OPERATION REGULATION SPEED UTC LLA2 VFOUTDOORTEMP LIMIT 1 Onomic Plus TRESTARTTIME COOL MIN AIR FLOW _ _ NEUTRALZONE __ I COOLING BOOST On a decreasing cooling load Cooling relay 1 drops when cooling load is below 60 it is energised again when cooling load is below 30 and drops again when cooling load is below 2 Cooling relay 2 drops when cooling load is below 30 The output for 0 10 V DC control signals terminals 42 43 opera tes in parallel with the 0 100 cooling load and can be used for indicating the cooling demana for instance Settings for cooling functions on this page and the next Value Setting Factory range settings Inactive active Inactive Stepless 0 10 V On Off 1 step Stepless10 0 V On Off 1 step On Off 2 step On Off 3 step binary Operation mode Cooling regulation Periodic operation Cooling relay 1 Inactive pump Inactive pump valve valve Inactive pump Inactive pump valve valve Exercise period 1 60 min Cooling relay 2 3 min Interval 1 168 hrs 24 hrs Regulation speed between steps 0 600 sec 300 sec Outdoor temperature limit Step 1 0 25 C 3 C Step 2 0 25 C 59C Step 3 0 25 C 7 C Restart time 0 900 sec 480 sec Cooling min air flow Supply air 0 Max flow Extract air 0 Max flow Neutral zone 0 10 C 2 0 C Cooling BOOST Inactive Inactive Comfort Economy Sequence Comfor
13. Min SA max 16 50 C 25 C Max SA max 16 50 C 45 C For ERS regulation 1 Breakpoint min 12 26 C 15 C Breakpoint max 12 26 C 23 C EA SA Diff min 1 7 C 1 C EA SA Diff max 1 7 C Bre EA Extract air SA Supply air ERS Extract air temperature related supply air temperature re gulation Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 HAND TERMINAL HANDTERMINAL SET LANGUAGE AIR FLOW UNIT MIN MAX SETTING BASE SETTINGS I ee ee ew ew ee ee ee a 14 4 Base Settings Used for saving and resetting the settings BASE SETTINGS 1 and 2 are two levels where the user him herself saves current settings and activates them when needed The two base settings can be used as a summer setting and as a winter setting of the air handling unit The values in INITIAL SETTING 1 and 2 saved in the internal memory can be transferred to the external MMC memory by entering SAVE SETTINGS EXTERNAL MEMORY The values can be transferred from the external MMC memory to the internal memory by entering FETCH EX TERNAL MEMORY INITIAL SETTING 1 and 2 must be downloaded into the control unit by entering INTERNAL MEMORY LOAD NEW SETTINGS Under SAVE EXTERNAL MEMORY there is a function that can save current settings to the MMC memory Current settings can be stored directly in the control unit under FETCH EXTERNAL MEMORY FACTORY SETTINGS resets the a
14. ES 43 EXT ALARM No 2 TRIPPED B 0 1 Set time M External alarm connected to control unit input Inp or Inp 2 has tripped 44 SA DUCT PRESSURE BELOW SETPOINT Bret 0 1 20m 45 EA DUCT PRESSURE BELOW SETPOINT Bree 0 1 20m Pressure in supply extract air duct if pressure trans ducers are connected has been more than 1096 below its setpoint for more than 20 minutes lt lt 46 SA DUCT PRESSURE ABOVE SETPOINT Bere 0 1 20m 47 EA DUCT PRESSURE ABOVE SETPOINT Bree 0 1 20m Pressure in supply extract air duct if pressure trans ducers are connected has been more than 1096 above its setpoint for more than 20 minutes lt lt 48 SUPPLY AIRFLOW BELOW SETPOINT B 0 1 20m 49 EXTRACT AIRFLOW BELOW SETPOINT Bee 0 1 20m The supply extract airflow has been more than 1096 below its setpoint for more than 20 minutes lt lt 50 SUPPLY AIRFLOW ABOVE SETPOINT B5 0 1 20m 51 EXTRACT AIRFLOW ABOVE SETPOINT Bree 0 1 20m The supply extract airflow has been more than 1096 above its setpoint for more than 20 minutes lt lt 52 SUPPLY AIR FILTER DIRTY B 10m 53 EXTRACT AIR FILTER DIRTY Bete 0 1 10m The pressure across the supply extract air filters has exceeded the preset alarm limit for more than 10 minutes o lt lt 54 SERVICE PERIOD PAST ALARM LIMIT B 0 1 Set time M The preset service period has expired If the alarm is RESET via the hand held micro termi nal the alarm
15. GB COMPACTUT 101208 Function Factory preset value Adjusted value Alarm setting Fire alarm function Internal fire alarms X Inactive Active Inactive Active External fire alarm Alarm resetting X Man Auto Wian Ate Fan oper in the event of a fire X nactive SA EA SA EA Inactive SA EA SA EA SA fan speed in event of fire 100 EA fan speed in event of fire 100 External alarms Time delay Alarm 1 s 10 Alarm on closure Alarm 1 1 Alarm reset Man Auto Man Auto Time delay Alarm 2 s 10 Alarm on closure Alarm 2 1 Alarm reset X Man Auto Man Auto Alarm limit temperature Deviation SA setpoint 5 0 Min EA temperature 15 0 Filter function Filter alarm limit SA Pa 10 100 EA Pa 10 100 H EXCH defrosting Alarm limit Pa 50 Service period Alarm limit month 12 Alarm priority See the following pages Hand held micro terminal settings Language English Flow unit l s X m s m h l s m s m h Min max setting Setpoint SA EA C 15 0 40 0 Min limit SA C 13 0 18 0 Max limit SA C 25 0 45 0 Break point ERS Regulation C 15 0
16. Sequence Cooling BOOST Economy Sequence is a combination of the two variants for increasing the airflow If the conditions for Cooling BOOST Economy are met the unit will begin increasing the airflow before the cooling unit starts up If the conditions for outdoor air are not met the unit will begin increasing the airflow when the cooling unit starts up www swegon com 37 Swegon 9 8 Input output connections Outputs The control unit has two relay controlled outputs termi nals 1 2 and 3 4 They must be individually set to the function they are to have Important A maximum of two of the functions below can be combined Optional functions Damper output For control of the outdoor air exhaust air damper Operation output For indicating unit in operation Low speed output For indicating low speed operation High speed output For indicating high speed operation A Alarm output For group alarm A B Alarm output For group alarm B Heating output For indicating that the reheater is ope rating Cooling output 1 For controlling external cooling Cooling output 2 For controlling external cooling Inputs The control unit has two digital outputs terminals 5 6 and 7 8 They must be individually set to the function they are to have Important A maximum of two of the functions below can be combined Optional functions External stop The unit will stop if the input is
17. rIN OUTPUTS 7777 7 MORNING BOOST 7 MQnomic Plus EXT SENSORS Temperature displacement C Y 30 20 10 0 10 20 30 40 50 X Outdoor temperature C Winter compensation in accordance with factory setting involves Outdoor temperature 10 C Breakpoint X2 Compen sation starts and gradually takes place between 0 3 C down to outdoor temperature 20 C Outdoor temperature 20 C Breakpoint X1 Constant compensation takes place with 3 C temperature displa cement Y1 Summer compensation in accordance with factory setting involves Outdoor temperature 25 C Breakpoint X3 Compensa tion starts and gradually takes place between 0 2 C up to outdoor temperature 40 C Outdoor temperature 40 C Breakpoint X4 Constant compensation takes place with 2 C temperature displa cement Y2 www swegon com 25 Registered design The company reserves the right to make design changes without prior notice Swegon 9 2 3 Summer Night Cooling The lower temperature at night is utilised to cool down the building structure This reduces the cooling load during the first hours of the day If a cooling unit is instal led its in operation hours will be minimised thus offering savings If no cooling unit is installed a certain cooling effect will still be realised When summer night cooling function is activated the unit fans operate at high speed with a supply air setpoint of
18. 1 10s A The air handling unit s control unit cannot establish correct communication with frequency inverter 12 OVER CURRENT IN SA FREQUENCY CONV AERE 1 3s M 13 OVER CURRENT IN EA FREQUENCY CONV A 1 3s M Current above the normal level is supplied to the motors 14 UNDER VOLTAGE IN SA FREQUENCY CONV AC 1 3s M 15 UNDER VOLTAGE IN EA FREQUENCY CONV A 1 3s M Voltage below the normal level is supplied Not adjustable always stops the air handling unit Not adjustable stops the air handling unit if the temperature to below 5 C Blocked if the hand terminal does not display the main menu Cannot be blocked Registered design The company reserves the right to make design changes without prior notice www swegon com 47 Swegon GB COMPACTUT 101208 Alarm no Alarm text Function Priority Stop Indication LED Delay Resetting O blocked O In operat OzOff s seconds M manual A A alarm 1 Stop IZON m minutes A automatic B B alarm OVER TEMPERATURE IN SA FREQUENCY CONV OVER TEMPERATURE IN EA FREQUENCY CONV High temperature inside the inverter A KKK A KKK 35 35 20 21 NO COMMUNICATION WITH SA FREQUENCY CONV GATEWAY NO COMMUNICATION WITH EA FREQUENCY CONV GATEWAY The air handling unit s control unit cannot establish correct communication with the fan s communication gateway
19. 5 Control Inaccuracy Temperature 1 C Airflow 5 Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 www swegon com 57 a Swegon M M GB COMPACTUT 101208 21 ANNEXES 21 1 Compliancy Declaration We Swegon AB Box 300 535 23 Kv num declare under our own sole responsibility that Air handling units with the following designation COMPACT Air COMPACT Heat COMPACT Unit COMPACT Top and any accessories to the respective designation covered by these directives comply with the Machinery Directive 2006 42 EC and also to the following directives 2004 108 EC EMC Electromagnetic Compatibility 2006 95 EC LVD the Low Voltage Directive The following harmonised standards have been applied EN ISO 12100 1 2 Safety of machinery general principles for design EN ISO 13857 2008 Safety distances EN ISO 14121 1 2007 Risk assessment EN 60204 1 Electrical equipment of machines EN 61000 6 2 3 Electromagnetic compatibility The following other standards and specifications have been applied EN 1886 2007 Ventilation for buildings air handling units EN 13053 2006 Ventilation for buildings air handling Person authorised to compile the technical documentation Dan rtengren Box 300 535 23 Kvanum This declaration is applicable only if the air handling unit s has have been installed ac
20. 64 www swegon com Registered design The company reserves the right to make design changes without prior notice G B COMPACTUT 101208 Factory preset value Adjusted value Priority Indication Effect Priority Indication Effect E Function Ozblocked LED 0 Operat O blockedt LED 0 Operat S A A alarm 0 Off 1 Stop A A alarm 0 Off 1 Stop li B B alarm 1 On B B alarm 1 On 1 External fire alarm tripped AFTER 1 j 2 Internal fire alarm tripped Aes 1 ilic 3 Frost protection below alarm limit Aree 1 1 4 R hx speed monitor tripped A 1 07 5 Frost protection sensor defective A 1 1 6 Supply air temp sensor defective A 1 1 7 Extract air temp sensor defective A 1 1 8 Outdoor air temp sensor defective B 1 0 9 No communication to r hx controller A 1 1 10 No communication to SA frequency conv AFTE 1 1 1 No communication to EA frequency conv A 1 1 12 Over current in SA frequency conv A 1 1 3 Over current in EA frequency conv A 1 1 14 Under voltage in SA frequency conv A 1 1 5 Under voltage in EA frequency conv A s 1 1 18 Excess temperature in SA frequency inverter A 1 1 9 Excess temperature in EA frequency inverter A 1 1 20 No communication SA frequency range gateway A 1 1 21 No communication EA frequency range gateway A 1 1 22 Hall sensor
21. 9 3 in which the func tions for flow pressure are described in detail 7 2 1 Readings Used for performance checks 7 2 2 Settings The functions selected at INSTALLATION LEVEL and the min and max airflows of each unit size see the table below determine which values can be set Values for airflow I s m3 s m3 h pressure Pa or input signal strength can be preset depending on the func tion selected LOW SPEED Must always be preset The value for low fan speed can not be higher than the value for high speed Low speed can be set to 0 which means that the fan is standing still HIGH SPEED Must always be preset The value or pressure for high fan speed cannot be lower than the value for low fan speed MAX SPEED Max speed is only appropriate for functions such as pres sure regulation Heating BOOST or Cooling BOOST The value for max fan speed cannot be lower than the value for high fan speed MIN MAX SPEED Min max fan speed is only appropriate for demand con trolled operation The lowest and highest permissible flows are preset for each of the fans This means that the fans will not operate outside these limits regardless the load Min Max Airflows AIRFLOW MIN FLOW MIN FLOW COMPACT UNIT COMPACT UNIT AND COMPACT TOP AND COMPACT TOP meh m s m 3 h m s 0 08 800 0 23 0 08 1300 0 36 When entering settings round off the values to the nearest adjustable step 18 www swegon com GB CO
22. MORNING BOOST r Qnomic Plus 7 HTXNDEEMEED I Registered design The company reserves the right to make design changes without prior notice Swegon 9 2 4 Intermittent Night time Heating The unit is utilised to heat the premises when it is normally stopped by the switch clock The function requires that an external room sensor is connected and that the air handling unit is provided with air heater for reheating the air Connect the TBLZ 1 24 2 Room sensor by means of the modular cable supplied to an optional connection marked Internal BUS 1 The capac ity of the function will be best if the COMPACT is provided with a recirculation damper not Swegon supply and a shut off damper for outdoor air and exhaust air When the function is activated the air handling unit de tects when the room temperature drops below the preset start temperature The unit starts with preset flows and the supply air temperature setpoint If extract air fan operation is not desirable the extract airflow can be set to O The damper output can be set to 0 This means that the connected dampers such as shut off dampers for outdoor air and extract air will not be affected These dampers are normally closed when the air handling unit is stopped and they also remain closed At the same time the damper in the air recirculation sec tion if included will open Conditions to be met for intermittent night time heating to start The uni
23. Now adjust the air devices in branch duct C Air device C4 should be fully open throttle the others to the same ratio Adjust the air devices in branch duct A The index air device here is air device A3 which means that you first throttle air device A4 the reference device to device A3 s ratio Thereafter the others are adjusted to the same ratio as air device A4 q 430 l s Throttle branch damper B to the same ratio as branch damper A throttle branch damper C to the same ratio as branch damper A Check that all dampers have the same ratio When the adjustment has been completed 3 air devices and one branch damper should stand fully open to obtain the lowest possible pressure in the system Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 When you ve completed the adjustments one air device in every branch one branch damper and one main damper should consequently be fully open 3 Start adjusting the main duct that has the highest ratio and the branch duct in the main duct that has the highest ratio Starting from this point enables you to press the air in front of you toward the sections of the system that have the least air 4 Adjust the last air device on the duct branch so that it will have the same ratio as the index device This air device will serve as the REFERENCE AIR DEVICE Often itis the last air device on the branch that has the
24. SA temp C 3 0 Cooling x Inactive Auto Inactive Auto operation Operation Cooling unit controls Stepless Stepless Stepless Stepless 0 10 V 10 0 V 0 10 V 10 0 V X On off On off On off On off 1 step 2 step 1 step 2 step On off On off 3 step binary mode 3 step binary mode Exercising Cooling relay 1 X Inactive Pump P V Valve Inactive Pump P V Valve Cooling relay 2 X Inactive Pump P V Valve Inactive Pump P V Valve Exercise period 3 Min Interval 24 hrs Control reaction speed Step duration s 300 Outdoor temp limit Step 1 C 3 0 Step 2 C 5 0 Step 3 C 7 0 Reset time s 480 Cool min SA flow m3s 0 1 Cool min EA flow m3s 0 1 Neutral zone C 2 0 Cooling BOOST x Inactive Comf Econ Sequ Inactive Comf Econ Sequ Comf econ Econ sequ Comf econ Econ sequ Start limit SA temp C 3 0 Inputs Outputs Relay 1 A Alarm output 4 Relay 2 B Alarm output 4 nput 1 External low speed 5 nput 2 External high speed 5 IQnomic Plus O Module No 3 Ext monitoring X Inactive Active Inactive Active O Module No 6 Ext cooling X Inactive Active Inactive Active O Module No 9 Preheating X Inactive Active Inactive Active 62 www swegon com Registered design The company reserves the right to make design changes without prior notice Swegon
25. When the air handling unit is energised for the first time the VOC sensor is initialised and this involves transmitting a steady signal of approx 5096 VOC for 6 hours applies to the VOC sensors with Part No 328964 01 VOC sen sors with Part No 328964 02 are initiated at the factory If the unit at a later time is de energised and is subse quently reenergised the sensor is reinitialised for 15 minu tes provided that initialisation during the first energising occasion was not interrupted When the VOC sensor measures contents of emissions impurities that are lower than the preset value the air handling unit s supply air and extract air flows are then equivalent to the preset min flows When the VOC sensor instead measures contents of emissions impurities that are higher than the preset value the supply air and extract air flows are variably increased until the preset value or max flow is reached When the Clean Air Control function is activated the fan regulation modes are automatically selected extract air fan demand controlled supply air fan slave controlled Later on they can only be read under Functions in the menu Settings Value Setting Factory range setting Clean Air Control Inactive Active Inactive VOC low speed 10 90 96 50 96 VOC high speed 10 90 96 30 96 Min flow m3 s 0 08 m3 s Max flow m3 s 0 2 0 3 m3 s The setting range is the same as the min max setting of the air handling unit
26. breakpoint 30 10 C 20 C X2 breakpoint 10 415 C 410 C Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 TEMPERATURE AIR FLOW PRESSURE FILTER AIRFLOW PRESSURE SA FAN REGULATION LOPERATION ___ 2L EA FAN REGULATION CLEAN AIR CONTROL 0 10 20 30 40 50 Reduction of the airflow in Y 30 20 10 0 10 20 X Outdoor air temperature C Outdoor air compensation according to factory settings involves Outdoor temperature 10 C Breakpoint X2 Compensa tion starts and gradually proceeds between 0 30 down to outdoor air temperature 20 C Outdoor air temperature 20 C Breakpoint X1 Constant compensation proceeds at 30 max reduction Y1 www swegon com 31 Swegon 9 3 3 Downspeed Control of Fan Speed to Min Set Point Airflow pressure Regulation of the supply airflow to a lower flow rate is the last step in the regulation sequence on increasing hea ting load for ERS regulation or supply air regulation The extract air fan cannot be selected alone only the supply air fan or both the supply air and extract air fans can be selected See Section 9 2 as well An adjustable temperature decrease allows a lower supply air temperature setpoint before down regulation begins This neutral zone can be set on line NZ SA DOWN REGU LATION in the appropriate me
27. defective SA frequency range Y in 1 1 23 Hall sensor defective EA frequency range A 1 1 24 SA frequency range blocked A 1 1 25 EA frequency range blocked A 1 1 26 Start up failure SA frequency range Agee 1 1 27 Over voltage in EA 2 frequency conv A 1 1 30 Ext EA room temp sensor defective A 1 1 31 Ext outdoor temp sensor defective Bsa 1 0 34 Over current in r hx controller A 1 1 35 Under voltage in r hx controller A 1 1 36 Over voltage in r hx controller A 1 1 37 Over temperature in r hx controller A 1 1 38 R hx pressure drop above alarm limit B 1 0 39 El heating coil tripped A 1 1 40 Extract air temp below alarm limit A 1 1 41 Supply air temp below setpoint A 1 1 42 Ext alarm No 1 tripped Axe 1 1 Registered design The company reserves the right to make design changes without prior notice www swegon com 65 G B COMPACTUT 101208 Factory preset value Adjusted value z Priority Indication Effect Priority Indication Effect E Function O blocked LED O Operat O blockedt LED 0 Operat 5 A A alarm 0 0ff 1 Stop A A alarm 0 Off 1 Stop g B B alarm 1 On B B alarm 1 On 43 Ext alarm No 2 tripped Bw 1 0 44 SA duct pressure below setpoint B 1 0 45 EA duct pressure below setpoint B 1 0 46 SA duct pressure abo
28. inputs Inp 1 or Inp 2 2 INTERNAL FIRE ALARM TRIPPED ACCESS ij 1 3S M The air handling unit s supply air sensor measures a temperature more than 70 C and or its extract air sensor measures a temperature more than 50 C The function must be activated manually in the ALARM SETTINGS menu 3 FROST PROTECTION BELOW ALARM LIMIT AC 1 1 3s M The anti frosting monitor sensor measures a tempe rature lower than the preset temperature Factory setting 7 C 4 R HX SPEED MONITOR TRIPPED A Ose 1 3s M No impulses from the rotation detector are registered with the heat exchanger controller The air handling unit will be switched out only if the outdoor tempe rature drops below 5 C 5 FROST PROTECTION SENSOR DEFECTIVE A 1 35 A The anti frosting monitor temperature sensor is lack ing is not connected or is faulty an air heater for hot water is connected 6 SUPPLY AIR TEMP SENSOR DEFECTIVE A 1 1 3s A 7 EXTRACT AIR TEMP SENSOR DEFECTIVE A 1 1 3s A The supply air extract air temperature sensor is not connected or is faulty 8 OUTDOOR AIR TEMP SENSOR DEFECTIVE B 0 1 3s A The outdoor air temperature sensor is not connected or is faulty 9 NO COMMUNICATION TO R HX CONTROLLER A 1 1 10s A The air handling unit s control unit cannot establish correct communication with the heat exchanger controller 10 NO COMMUNICATION TO SA FREQUENCY CONV A RER 1 10s A 11 NO COMMUNICATION TO EA FREQUENCY CONV A
29. lowest ratio and should be open In this case the same air device serves as the index device and reference device 5 Throttle the other air devices in the branch to the same ratio as the reference device Note The ratio in the reference device will change every time another air device is throttled so in practice the ratio for the reference device can be set slightly higher The reference device must be measured in between each air device throttled 6 Go to the branch that had the next highest ratio and adjust the air devices there etc Note All branch dampers should be fully open until all air devices have been adjusted 7 Throttle the branch damper that had the highest ratio to the same ratio that the branch of the lowest ratio had Note Keep in mind that the index damper changes ratio proceed as described in item 5 8 When all branches have been adjusted throttle the main dampers in the same manner Also see the example below on how to carry out adjust ments A A1 A2 A3 A4 d dn 082 K 165 45 40 40 40 q 161 50 43 35 33 q 0 97 1 11 1 07 0 87 0 82 K q design airflow l s q airflow reading l s K Ratio Im 9 www swegon com 11 7 Swegon s GB COMPACTUT 101208 4 3 To Adjust the Pressure Balance Adjustment plate 4 3 1 General COMPACT Unit The air handling unit is equipped with an adjustment plate designed for achieving a correct air leakage direction across the heat exchanger This p
30. not closed External LS For external overtime operation via timer switch clock from stop to low speed operation External HS For external overtime operation via timer switch clock from stop or low speed operation to high speed operation External Alarm 1 For connection of External Alarm 1 External Alarm 2 For connection of External Alarm 2 External reset For connection of pushbutton for reset ting a tripped alarm External fire alarm A fire alarm will trip if the input is not connected GB COMPACTUT 101208 FUNCTIONS TEMPERATURE AIR FLOW PRESSURE FILTER OPERATION 1 1 HEATING 1 COOLING 38 www swegon com Registered design The company reserves the right to make design changes without prior notice I Swegon M M GB COMPACTUT 101208 9 9 IQnomic Plus IQnomic Plus is a name given to additional modules for extra control functions See special instructions FUNCTIONS TEMPERATURE AIR FLOW PRESSURE FILTER 1 OPERATION I i IN OUTPUTS IQnomic Plus IQNOMIC PLUS Registered design The company reserves the right to make design changes without prior notice www swegon com 39 Swegon 10 AUTOMATIC FUNCTIONS 10 1 General The COMPACT has a number of automatic functions The operation of the unit is influenced when certain functions are activated 10 1 1 Starting Sequence The COMPACT has a starting s
31. the main menu 50 www swegon com Registered design The company reserves the right to make design changes without prior notice I Swegon E GqB COMPACTUT 101208 91 FROST PROTECTION PREHEATING BELOW ALARM LIMIT A 1 1 3s M The sensor for the frost protection monitor prehea ting has measured a temperature lower than the preset temperature Factory setting 7 C 92 FROST PROTECTION PREHEATING SENSOR DEFECTIVE A 1 1 35 A The sensor for the frosting protection monitor pre heating is lacking is not connected or is faulty if an air heater for hot water is connected 93 PREHEATING SENSOR DEFECTIVE A 1 1 3s A The sensor for preheating is lacking is not connected or is faulty if an air heater for hot water is connec ted 94 EL AIR HEATER PREHEATING TRIPPED At 1 1 3s M The thermal overload protection for the connected electric air preheater has tripped or is not connected 95 PREHEATING BELOW SETPOINT ASER 1 1 20m M The preheating temperature is below the preset set point for ERS and Supply air control or Min SA temp for Extract air control longer than 0 minutes 99 TIME LOCK TRIPPED ES kde k M Contact Swegon or their representative Blocked if the hand terminal does not display the main menu Adjustable 0 99 months Registered design The company reserves the right to make design changes wit
32. well The following settings can be entered at USER LEVEL un der TEMPERATURE SETTINGS Value Setting Factory range setting Supply air temperature setpoint 15 40 C 21 5 Setting range for the setpoint is limited by Min and Max settings at INSTALLATION LEVEL under HAND TERMINAL 9 2 1 3 Extract Air Regulation Extract air regulation involves keeping a constant tempe rature in the extract air duct premises by regulating the supply air temperature This provides a uniform tempera ture in the premises regardless of the load and this type of regulation requires the installation of a reheating coil possibly a cooling coil as well The extract air temperature is measured by the tempera ture sensor inside the COMPACT unit If this internal temperature sensor does not give an ad equate representative extract air temperature readings an external room temperature sensor can be installed and wired to the control unit s connection marked Internal Bus 1 The following settings can be entered at USER LEVEL un der TEMPERATURE SETTINGS Value Setting Factory range setting Extract air room temp setpoint 15 40 C 21 59C Min Supply air temperature 13 18 C 159C Max Supply air temperature 25 45 C 28 C Setting range for the various values is limited by Min and Max settings at INSTALLATION LEVEL under HAND TERMI NAL GB COMPACTUT 101208 24 www swegon com Registered design The company reserves the right to m
33. will be initiated again after 7 days A new service period can be set in the ALARM SET TINGS menu Blocked if the hand terminal does not display the main menu Registered design The company reserves the right to make design changes without prior notice www swegon com 49 7 Swegon SSS GB COMPACTUT 101208 Priority Stop Indication Delay Resetting Alarm text LED Function O blocked O In operat O Off s seconds M manual A A alarm 1 Stop 1 On m minutes A automatic B B alarm Alarm no 55 NO COMM SA AIR FLOW PRESSURE SENSOR Ax 1 1 10s A 56 NO COMM EA AIR FLOW PRESSURE SENSOR A 1 1 10s A The air handling unit s control unit cannot establish correct communication with the supply extract air flow pressure transducer 57 NO COMM SA FILTER PRESSURE SENSOR B 1 1 10s 58 NO COMM EA FILTER PRESSURE SENSOR Bee 1 1 10s The air handling unit s control unit cannot establish correct communication with the supply extract air filter pressure transducer 59 NO COMM SA DUCT PRESSURE SENSOR A 1 1 10s 60 NO COMM EA DUCT PRESSURE SENSOR A 1 1 10s The air handling unit s control unit cannot establish correct communication with the pressure transducer connected in the supply extract air ducting Applicable to SA EA pressure regulation only 61 NO COMM R HX PRESSURE SENSOR B 0 1 10s The air handling unit s control unit cannot establish correct communication with th
34. 0 8 INSTALLATION LEVEL 8 1 Menu SUtvey ere eee 21 9 FUNCTIONS Ori TEMPO ACU Gh css cocco peor e eee 9 2 Temperature Regulation shit 9 2 1 1 ERS Regulation sioti 9 2 1 2 Supply Air Regulation 24 9 2 1 3 Extract Air Regulation 24 9 2 2 Outdoor Temperature COMPENSA OM a ucc tte Repente 25 9 2 3 Summer Night Cooling 26 9 2 4 Intermittent Night time Heating 27 9 2 5 Morning BOOS P esserci 9 2 6 External Temperature Sensors 9 3 FloW PIeSSUte cuc e e eet 9 3 1 Fan Regulation sseni 9 3 1 1 Flow Regulation s 9 3 1 2 Pressure Regulation 9 3 1 3 Demand Control 9 3 1 4 Slave Control aua 9 3 1 5 Clean Air Control 9 3 2 Outdoor Temperature Compensation cst e 31 9 3 3 Downspeed Control of Fan Speed to Min Set Point Airflow pressure 32 9 3 4 To adjust the flow of the slave fan 32 9 4 To Activate the GOLD SD Filter Monitoring Function sssss 32 9 5 Operation sis 9 54 Switch ClOCK i tte 33 9 5 2 Extended Operation 33 9 5 3 Summer time Winter time i 9 6 Heating sco ecd e to tenet nk 9 6 1 Heat exchanger siisii 34 8 6 1 1 Defrosting the rotary heat exchanger 9 6 2 Pre Reheating sssssssss 9 6 3 Heating BOOST ssi 9 7 Cooling cc
35. 10 C from the preset time until the conditions necessary for stop are satisfied Conditions to be met to start summer night cooling at the preset time The extract air temperature should be higher than the preset value e The extract air should be at least 2 C warmer than the outdoor air The outdoor temperature should be above the preset value Heating has not been required between 12 00 23 00 hours The unit must not operate in the high speed mode or be stopped from an external source or manually from the hand held micro terminal Conditions to be met to stop summer night cooling at the preset time The extract air temperature drops below the preset value The outdoor temperature drops below the preset value e Switch clock or external input calls for high speed e The extract air is less than 1 C warmer than the outdoor air The function starts once per set time period Settings Value Setting Factory range setting Extract air temperature for start 17 27 C 22 C Extract air temperature for stop 12 22 C 16 C Outdoor temperature for stop 5 15 C 10 C Supply air setpoint 10 20 C 10 C Operating period 00 00 00 00 23 00 06 00 26 www swegon com GB COMPACTUT 101208 FUNCTIONS TEMPERATURE z AIR FLOW PRESSURE TEMPERATURE FILTER TEMPERATURE REG OUTDOOR TEMP COMP i OPERATION SUMMER NIGHT COOL HEATING TCOOLNG 7 7 7 UNTERM NIGHT HEAT 5 FINJOUTPUTS
36. 12 V DC to GND Max permissible load 500 mA 34 PWM input for Clean Air Control VOC sensor 35 Measuring zero GND 36 Output fixed power supply 10 V DC out 10 V DC to GND Max permissible load 20 mA 37 Input 0 10 V DC for demand controlled Air quality sensor control of the airflow DIL selector switches COMPACT Unit right hand version DIL switch 4 must be set to the ON position the other switches must be set to the OFF position COMPACT Unit left hand version DIL switches 1 and 4 must be set to the ON position the other switches must be set to the OFF position COMPACT Top DIL switch 3 must be set to the ON position the other switches must be set to the OFF position 56 www swegon com Registered design The company reserves the right to make design changes without prior notice Network connection Temperature sensor supply air Swegon 20 4 Electrical Data 20 4 1 Air Handling Unit MIN POWER SUPPLY 1 phase 3 wire 230 V 10 15 50 Hz 10 AT 20 4 2 Fans RATED DATA PER FAN Size 02 1 x 230 V 50 60 Hz 0 5 kW 0 28 kW Size 03 1 x 230 V 50 60 Hz 0 5 kW 0 43 kW The motor controls limit the output power to the value speci fied 20 4 3 Electrical equipment cubicle One 2 pole 3A Automatic circuit breaker for 230V control current 20 4 4 Heat Exchanger Motor Step motor 3 phase 5 8 A 2A 62 V max 90 V The motor controls limit the output power to the value speci fied 20 4
37. 23 0 SA EA Difference C 1 0 5 0 Initial setting Communication EIA 485 Protocol Modbus RTU Address 1 PLA Exoline 1 ELA Exoline 1 Speed 9600 Parity None Stop bit 1 Registered design The company reserves the right to make design changes without prior notice www swegon com 63 7 Swegon SSS GB COMPACTUT 101208 Function Factory preset value Adjusted value Ethernet Mac Id Individual DHCP server Inactive P address 10 200 1 1 Port no 80 Net mask 255 0 0 0 GateWay 000 000 000 000 DNS server No 1 000 000 000 000 No 2 000 000 000 000 Modbus TCP P 000 000 000 000 Port no 502 Net mask 000 000 000 000 BACNet IP Function Inactive Device ID 0000000 Port nr 47808 The values by turns refer to sizes 02 03 1 Applies to COMPACT Heat only 2 Only in combination with Cooling BOOST 0 2 mls 0 3 m s 3 Only in combination with Demand control 0 08 m s 0 08 mls 4 Possible options Control of outdoor air exhaust air damper in operation indication low speed operation indication indication or high speed operation group alarm A group alarm B control of external heating control of external cooling 5 Possible options External stop external low speed operation external high speed operation external alarm 1 external alarm 2 external reset external heating external fire alarm 6 Only in combination with forcing
38. ACTIVE ALARMS ALARM HISTORY Registered design The company reserves the right to make design changes without prior notice I Swegon M GB COMPACTUT 101208 8 INSTALLATION LEVEL Important The appearance of the menus varies depending 8 1 Menu Survey on the type of air handling unit and functions selected INSTALLATION Q INSTALLATION FUNCTIONS FUNCTIONS CODE 0000 TEMPERATURE Section 9 AIR FLOW PRESSURE FILTER Code 1111 READINGS i OPERATION MANUAL TEST ____ E L ALARM SET 1 SERVICELEV b READINGS TEMPERATURE Section 11 FANS HEAT EXCHANGE 1 REGULATION SIGNALS Section 10 Automatic functions MANUAL TEST TEMPERATURE Section 12 FANS HEAT EXCHANGE ALARM SETTINGS FIRE ALARM EXTERNAL ALARMS ALARM LIMITS E ALARM PRIORITY Section 13 HAND TERMINAL INST LANGUAGE Section 14 AIR FLOW UNIT MIN MAX SETTING BASE SETTINGS COMMUNICATION EIA 485 Section 15 ETHERNET SERVICE LEV CODE 0000 Section 16 Registered design The company reserves the right to make design changes without prior notice www swegon com 21 Swegon 9 FUNCTIONS 9 1 Temperature Basic functions can be set at INSTALLATION LEVEL and values are read and set at USER LEVEL IMPORTANT If you intend to substantially alter the tem perature settings you should first stop the air handling unit before doing so 9 2 Tem
39. ACTUT 101208 9 5 Operation 9 5 1 Switch clock Basic functions are set at INSTALLATION LEVEL and the values are read and set at USER LEVEL FUNCTIONS TEMPERATURE AIR FLOW PRESSURE The switch clock controls the operating times of the unit FEIER The following two basic functions can be set SMS be OPERATION FUNCTION LOW SPEED HIGH SPEED voe Ree ms ee SWITCH CLOCK i ENUGIEBUTPE Cem EXTENDED OPERATION Low speed is the basic level and times for high speed ope LIN OUTPUTS SUMMER WINTER TIME ration are set at USER LEVEL under SWITCH CLOCK IQnomic Plus LE STOP LOW SPEED HIGH SPEED Stop is basic level and times for low speed and high speed operation are set at USER LEVEL under SWITCH CLOCK Settings Value Setting range Factory settings Function Low speed High speed Low speed High speed Stop Low speed High speed 9 5 2 Extended Operation The inputs for external low speed and external high speed OPERATION FUNCTION respectively can be supplemented with extended opera SWITCH CLOCK tion They can be used for overtime running activated by a EXTENDED OPERATION pushbutton for example SUMMER WINTER TIME Desired time in hours and minutes can be set as follows Settings Value Setting Factory range settings External low speed 0 00 23 59 0 00 External high speed 0 00 23 59 0 05 hour min hour min 9 5 3 Summer time Winter time OPERATION FUNCTION 3 SWITCH CLOCK The tim
40. I Swegon M _GB COMPACTUT 101208 INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR COMPACT UNIT amp COMPACT TOP Applicable to program version 2 03 and newer versions COMPACT Top COMPACT Unit The document was originally written in Swedish Registered design The company reserves the right to make design changes without prior notice www swegon com 1 Swegon Content 1 GENERAL oerte 1 1 Range of Application 1 2 Mechanical Design 1 3 Control System sssus 1 4 Environmental Documentation 1 5 The Components of the Air Handling Units 4 1 5 1 COMPACT Unit ssssssssse 4 1 52 COMPACT TOP e tociens 5 2 SAFETY PRECAUTIONS 6 2 1 Safety switch ssssssssssssssssese 6 Main Switch ssssssssssee 6 2 2 Risks 2 3 Safety Guards 3 INSTALLATION 7 9 1 Genetal oo e ehe ede 7 3 2 Transport Within the Site sus 7 3 3 Parts Packed Together with theRoomUnits onera oen ee 7 3 3 1 Hand held Micro Terminal 7 3 3 2 Supply Air SENSO csee 7 3 3 3 Document Pocket s 7 3 4 EOCAtIOEI a Lect t e eese eges 7 3 4 1 COMPACT Unit nettes 7 3 4 1 1 Airflow Direction ss 7 3 4 1 2 Conversion to the Left hand Version if required ce 8 3 5 Connecting ductwork to the Air Handling U
41. LEVEL 17 MAINTENANCE 45 17 1 Filter Change sssssssse 45 17 1 1 To remove the Filters 45 17 1 2 To fit new filters 45 17 2 Cleaning and Inspection 45 17 2 1 General 45 17 2 2 Filter Space 45 17 2 3 Heat exchangers 45 17 2 4 Fans and Fan Space ss 45 7 3 Performance Checks sssss 45 18 ALARMS AND FAULT TRACING 8 1 General 18 1 1 A and B Alarms 18 1 2 Resetting of alarms ss 46 18 1 3 Changing Alarm Settings 46 8 2 Alarm Descriptions with Factory Settings sssssssssssssse 47 19 INFORMATIVE MESSAGES 52 20 TECHNICAL DATA 53 20 1 Dimensions COMPACT Unit one piece unit 53 20 2 Dimensions COMPACT Top One piece Unit 20 3 Electrical Equipment Cubicle 20 3 1 Internal Connections 20 3 2 Connection to Terminal Blocks 56 20 4 Electrical Data 20 4 1 Air Handling Unit 20 47 FANS us aieo eet on SEE 20 4 3 Electrical equipment cubicle 20 4 4 Heat Exchanger Motor 20 4 5 Control Inaccuracy ssss 21 ANNEXES een 21 1 Compliancy Declaration 21 2 Commissioning Record Registered design The company reserves the right to make design changes without prior notice Swegon
42. MPACTUT 101208 AIR FLOW PRESSURE FLOW PRESSURE READINGS SETTINGS FLOW PRESSURE READINGS SETTINGS i MIN MAX SPEED Registered design The company reserves the right to make design changes without prior notice Swegon 7 3 Switch clock Basic functions for the switch clock can be preset N at INSTALLATION LEVEL under FUNCTIONS OPERA TION and the values can be read and set at USER LEVEL TIME DATE The current date and time can be set and adjusted whenever required The switch clock automatically takes leap years into considera tion Automatic changeover between summer time winter time to EU Standard has been preset This changeover function can be blocked at INSTALLATION LEVEL under FUNCTIONS OPERATION TIME CHANNEL Times and days can be set when the unit is to run at high speed low speed or be stopped Eight different time channels can be set If the same in operation times are to apply every day of the week Mon Sun you need only program one time channel Different operation times for each day of the week can be programmed by programming a time channel for each day Mon Fri Sat Sun or Mon Tues Wed etc The time can be set as 00 00 00 00 if the deviating in operation period is desirable for the entire 24 hours period YEAR CHANNEL The year channels make it possible to set deviating in service times for parts of the day during certain parts of the year Eight different year channels
43. PACT Unit A clear space of 800 mm must be pro vided in front of the unit for opening the inspection doors and at least 200 mm must be provided above the unit for opening the junction hood COMPACT Top A clear space of 1 000 mm should be pro vided in front of the unit for opening the inspection door right hung 3 4 1 COMPACT Unit 3 4 1 1 Airflow Direction The COMPACT Units are produced in one single variant where fans heat exchanger and filters always are arranged at their given physical location inside the unit The air handling units are delivered in the right hand ver sion but can easily be converted to the left hand version See below All that is needed to be done is to move a DIL Switch on the control unit see 3 4 1 2 The COMPACT Unit can also be installed vertically The stand is available as an accessory Right hand version Extract air Exhaust air Outdoor air Supply air The air handling units are supplied in the right hand version The unit can be easily converted to the left hand version at the building site The air handling unit can be installed vertically This provides six different installation alternatives www swegon com 7 Swegon 3 4 1 2 Conversion to the Left hand Version if re quired 1 Stop the air handling unit in the hand held micro termi nal Close the safety isolating switch 2 Wait until the fans have stopped rota
44. WO OV A PZ UBeTD MOTER 5 cj j JouuoJsuem WO DY A 8l Hen J9UJOJSUeJ WOI DY A 9E ZE 2 L 14 Pee o O d o c c 8 JOSU S JO UOW U0OI1 2 0Y amp E m E E o T i Jo3ouJ J9bueu xe 1eaH o m S z a UW r Brown Yellow Green Blue Extract air fan Registered design The company reserves the right to make design changes without prior notice Swegon 20 3 2 Connection to Terminal Blocks External sensor and GB COMPACTUT 101208 Memory card for log IQnomic Plus modules DIL selector switch ging and upgrading 3 4 s 6ll7 slo 1011213 UH ec NO Communication hand held micro terminal dguu Controller air heater NO Pressure sensor extract air fan Pressure sensor supply air fan o o E 181920 O ED LL 2122 23242526 272829 303132 3334353637 Digital inputs terminals 5 8 are of extra low voltage type Ana logue inputs terminal 37 has an input impedance of 66 k Q Temperature sensor outdoor air Te
45. ake design changes without prior notice Swegon 9 2 2 Outdoor Temperature Compensation Temperature Outdoor temperature compensation can be activated if the premises are abnormally subjected to the effects of seasonal cold air or hot air due to leakage through large windows for instance The supply air temperature setpoint is compensated if the air handling unit is operating in the supply air regulation mode and the extract air temperature setpoint is compen sated if the air handling unit is operating in the extract air regulation mode This function will have no effect if the unit is operating in the ERS regulation mode The preset temperature setpoint is influenced if the out door temperature drops below the preset X2 breakpoint winter compensation and above the preset X3 break point summer compensation See the chart to the right It is possible to set negative summer compensation Settings Value Setting Factory range setting Winter compensation Temperature displacement Y1 0 4 10 C 43 C Breakpoint X1 30 10 C 20 C Breakpoint X2 10 415 C 410 C Summer compensation Breakpoint X3 15 425 C 425 C Breakpoint X4 25 40 C 40 C Temperature displacement Y2 10 10 C 2 C GB COMPACTUT 101208 FUNCTIONS TEMPERATURE AIR FLOW PRESSURE TEMPERATURE FILTER TEMPERATURE REG OUTDOOR TEMP COMP OPERATION _ HEATING 55777 SUMMER NIGHT COOL f COOLING LINTERM NIGHT HEAT 1
46. ately be remedied Consider whether the air handling unit can continue to operate until the fault has been remedied Choose to block the alarm and or to change it from STOP to OPERA TION See Section 12 Alarm settings 18 1 1 A and B Alarms For particulars of type A alarm indication to output for Alarm Relay A Inp 1 and Inp 2 see also 9 8 For particulars of type B alarm indication to output for Alarm Relay B Inp 1 and Inp 2 see also 9 8 From these terminals alarms can be forwarded with dif ferent priority 18 1 2 Resetting of alarms Alarms that require manual resetting can be reset from the hand held micro terminal Select RESET in the current alarm menu Alarms that reset themselves automatically do so as soon as the fault has been remedied Alarms can also be reset via a Communication network 18 1 3 Changing Alarm Settings See Section 13 Alarm Settings GB COMPACTUT 101208 46 www swegon com Registered design The company reserves the right to make design changes without prior notice 7 Swegon sss GB COMPACTUT 101208 18 2 Alarm Descriptions with Factory Settings Priority Stop Indication Delay Resetting c Alarm text LED e g Function O blocked 0 In operat 0 Off s seconds M manual um A EA N A Lar amp A A alarm 1 Stop ZON m minutes A automatic lt B B alarm 1 EXTERNAL FIRE ALARM TRIPPED A 1 1 3s M For the fire protection function connected to
47. ation Time switch clock function X 1 Low high 2 Stop low high 1 Low high 2 Stop low high Slave control C Factor 1 0 Filter function Inact SA EA SA EA Inact SA EA SA EA Prefilter X Inact SA EA SA EA Inact SA EA SA EA Extended operation External low speed h mm 0 00 External low speed h mm 0 00 Not used for Clean Air Control Registered design The company reserves the right to make design changes without prior notice www swegon com 61 Swegon GB COMPACTUT 101208 Function Factory preset value Adjusted value Summer winter time Inactive X Active Inactive Active Heating Heat exchanger Defrosting X Inactive Active Inactive Active Reheating Exercising X Inact Pump Valve P V Inact Pump Valve P V Exercise period 3 Min Interval 24 hrs Heating BOOST Function Off On X Inactive Active Inactive Active Start limit
48. ave several lines and these are shown line for line as Fanti e USE Position indicator you press the ADVANCE DOWNWARD button The posi tion indicator shows where you are in the menu STOP 5 1 4 Abbreviations The following abbreviations are used in the menus SA Supply air E g SA FAN Supply air fan EA Extract air OUTD Outdoor air FV Anti frosting monitor HEAT EXCH Heat exchanger 14 www swegon com Registered design The company reserves the right to make design changes without prior notice I Swegon M GB COMPACTUT 101208 5 2 Menu tree Oo COMPACT U TUE 14 4 Important The appearance of STOP VANUA OPERATION the menus varies depending on the type of air handling unit and functions selected MAIN COMPACT U TUE 14 40 MANUAL OPERATION MENU STOP Section 6 MAN AUTO OP AUTO OPERATION MANUAL LOW SPEED MANUAL HIGH SPEED COMPACT U TUE 14 40 STOP MAN AUTO OP SETTINGS USER LEVEL TEMPERATURE Section 7 TEMPERATURE READINGS SETTINGS FLOW PRESSURE READINGS SETTINGS SWITCH CLOCK TIME DATE TIME CHANNEL FILTERS YEAR CHANNEL FILTERS READINGS CALIBRATION AIR TUR AIR ADJUSTMENT LOCKS FAN SPEED TIME SETTING Oh ALARMS Q ALARMS e ACTIVE ALARMS y ARM HISTORY INSTALLATION LEVEL INSTALLATION Section 8 16 Registered design The company reserves the right to make design changes without p
49. below room temperature ERS REGULATION 1 The control unit regulates the relationship between the supply air and extract air temperatures according to a factory preset curve See the chart to the right The steps breakpoint and EA SA differential plotted in the curve can be changed at USER LEVEL under TEMPERA TURE SETTINGS Settings Value Setting Factory range setting Step 1 4 1 Breakpoint 15 23 C 20 C refers to extract air temp EA SA Differential 1 5 C 2C The setting range for the breakpoint and EA SA differen tial is limited by the Min and Max settings at NSTALLA TION LEVEL under HAND TERMINAL ERS REGULATION 2 This is used when special needs and conditions are such that the factory preset ERS regulation 1 curve cannot pro vide the results required Conditional on which settings are made it may be necessary to install a post heating coil An individually adapted curve regulates the relationship between the supply air and extract air temperature See the chart to the right The following settings are possible at USER LEVEL under TEMPERATURE SETTINGS Value Setting Factory range setting Extract air temperature X110 38 C 15 C X211 39 C 20 C X312 40 C 22 C Supply air temperature setpoint Y110 40 C 20 C Y210 40 C 18 C Y310 40 C 14 C Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 FRT reglering 1
50. calculated from the time when a relay is energised to when it is allowed to be energised again The 0 10 V signal is delayed during the same period 9 7 7 Cooling Min Air Flow In order for the cooling function to operate the supply air and extract air airflows must be greater than their respec tive limit values preset at USER LEVEL under FLOW PRES SURE The cooling min flow function can be blocked by setting both flow limits to O 9 7 8 Neutral Zone The neutral zone prevents the cooling and heating systems from counteracting each other Preset neutral zone is added to the setpoint for heating and the sum of these provides the setpoint for cooling 9 7 9 Cooling BOOST Cooling BOOST means that the supply air and extract air airflows are increased to convey more cooling energy to the premises Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 Cooling BOOST cannot be combined with pressure regu lation The flow increase takes place between current flow and preset max flow The function can be selected in five variants as follows Comfort The cooling outputs are activated if there is a cooling load When the cooling function is active and the temperature in the supply air drops toward the preset SA min tempera ture the flow will steplessly increase The GOLD runs at preset max flow when the supply air temperature is same as the min temperature
51. cation is lost 28 www swegon com GB COMPACTUT 101208 FUNCTIONS TEMPERATURE AIR FLOW PRESSURE TEMPERATURE Fined TEMPERATURE REG OUTDOOR TEMP COMP OPERATION SUMMER NIGHT COOL FUNCTIONS TEMPERATURE TEMPERATURE Ai TEMPERATURE REG OUTDOOR TEMP COMP OPERATION SUMMER NIGHT COOL Settings Value Setting range Factory setting External Extract air Room Inactive IQnomic Inactive Communication External Outdoor Inactive IQnomic Inactive Communication Alarms 0 9990 min 5 min Registered design The company reserves the right to make design changes without prior notice Swegon 9 3 Flow Pressure Basic functions are set at INSTALLATION LEVEL and the values are read and set at USER LEVEL 9 3 1 Fan Regulation The type of regulation used for the supply air fan and the extract air fan respectively can be selected individually 9 3 1 1 Flow Regulation Flow regulation involves operating the air handling unit to keep the preset airflow constant The speed of the fans is automatically regulated to provide correct airflow even if the filters begin to become clogged air devices are blocked etc Constant airflow is advantageous since the airflow always is exactly as it was from the beginning It should however be noted that everything that increases the pressure drop in the ventilation system such as the blocking of air devices and dust accumulating in the fil t
52. conjunction with commissioning when the duct system air devices and eventual adjustment plates have been fitted and adjusted after that every time the filter media are changed Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 SWITCH CLOCK TIME DATE TIME CHANNEL YEAR CHANNEL Settings Value Setting Factory range setting TIME DATE Day Mon Sun Automatic Time 00 00 23 59 Current Date Day Month Year Current TIME CHANNEL 1 8 Operation Low speed High speed High speed Time 00 00 23 59 00 00 00 00 Period Not active Not active Mon Tues Wed etc Mon Fri Mon Sun Sat Sun YEAR CHANNEL 1 8 Operation Not active Not active Stop Low sp High sp Time 00 00 23 59 00 00 00 00 Period From Day Month Year 01 01 2005 To Day Month Year 01 01 2005 Shows Stop Low speed High speed if this function is selected at INSTALLATION LEVEL under FUNCTIONS OPERATION FILTERS READINGS CALIBRATION FILTERS READINGS CALIBRATION fF FILTER CALIBRATION STD FILTER PREFILTER HEAT EXCHANGER Calibration should be activated for both the supply air and the extract air if both filters are changed or for only for one airflow direction if only one filter has been changed When filter calibration has been activated the unit runs at high speed for about 3 minutes After the filter has been calibrated a speed increase of 1096 or a pressure rise fouling o
53. cording to Swegon s instructions and provided that the air handling unit s has have not been modified in any way AR Kv num 31 05 2010 Thord Gustafsson Quality and Environmental Manager Swegon AB 58 www swegon com Registered design The company reserves the right to make design changes without prior notice I Swegon T M GB COMPACTUT 101208 21 2 Commissioning Record Company Our reference Gene we T Filter calibration done Time switch clock current time Other controls Settings time channels scheduling time switch clock Operating mode Week day E Stop Ll High Low ive Stop High Low ive Stop High Low ive Stop High Low ive Stop High Low ive Stop Es High Low ive Stop High Low we Stop E High Low Registered design The company reserves the right to make design changes without prior notice www swegon com 59 Function Temperature Temp Reg Control function Factory preset value x gs 1 fers2 SA LI EA GB COMPACTUT 101208 Adjusted value Jew ens2 SA LI EA
54. d Settings Value Setting range Modbus RTU Address speed parity stop bits Metasys N2 OPEN Lon Works Exolinc 15 2 Ethernet Protocol and settings for Ethernet is specified Settings Value Setting range Ethernet MAC ID DHCP SERVER active or inactive IP ADDRESS static or dynamic SUBNETM GATEWAY DNS SERVER MODBUS TCP CLIENT IP address netmask and port number BACNet IP active or inactive Device ID Port no 16 SERVICE LEVEL e SERVICE LEV A code and special training are required for access to this menu group SERVICE LEV CODE 0000 44 www swegon com Registered design The company reserves the right to make design changes without prior notice Swegon 17 MAINTENANCE Warning Before carrying out any work make sure that the power supply to the unit has been isolated 17 1 Filter Change The filters should be changed when the filter alarm has been activated Order new filters from Swegon or its representative State the size of the air handling unit and whether the change involves one or two air directions 17 1 1 To remove the Filters Pull out the handles to free the filters from the filter holder Withdraw the filters It is advisable to clean inside the filter space while the filters are gone 17 1 2 To fit new filters Insert the filters into the filter holder Insert the filters as far as possible into the unit and press lightly on the filter frames so that they w
55. e white pressure measurement tapping is used for measur ing the negative pressure in the supply air section Note that both pressure measurement tappings are used for measuring negative pressure MEASURED VALUES The negative pressure in the extract air section should be greater or the same as the negative pressure in the supply air section If the negative pressure in the extract air section is the same or up to 20 Pa greater than the negative pressure in the supply air section then you ve finished this adjust ment DEVIATIONS If the negative pressure in the extract air section is less than that in the supply air section the adjustment plate must be readjusted as follows 1 Stop the air handling unit open the inspection door and slightly close the adjustment plate in the air han dling unit s extract air inlet 3 Close the inspection door and restart the unit 4 Measure the pressures Repeat this procedure until the negative pressure in the extract air section is the just as high or up to 20 Pa higher than the negative pressure in the supply air sec tion 0 20 Pa 5 If the negative pressure in the extract air section is higher than 20 Pa compared to the supply air section although the adjustment plate is completely open the leakage and purging air flow will be more than antici pated This means that the actual extract air flow will deviate from the preset extract airflow The deviation increases as the pressure d
56. e and date readings include factory preset automa EXTENDED OPERATION tic changeover from summer time to normal time and vice SUMMER WINTER TIME versa thus conforming to EU standard the last Sunday in March and the last Sunday in October respectively This automatic changeover can be blocked and set as inac tive Settings Value Setting Factory range settings Summer time Winter time Inactive active Active Registered design The company reserves the right to make design changes without prior notice www swegon com 33 Swegon 9 6 Heating 9 6 1 Heat exchanger 8 6 1 1 Defrosting the rotary heat exchanger In environments where the extract air can occasionally be humid the defrosting function can be activated to protect the heat exchanger from frosting The function continu ously monitors the condition of the heat exchanger rotor to prevent condensate from freezing in the rotor passages and clogging them The function requires a separate pressure transducer preset for heat exchanger defrosting wired to the control unit inputs for external BUS communication and connec ted by hoses to the pressure measuring tappings of the unit See special installation instruction for the TBLZ 1 23 aa Pressure sensor The pressure drop across the rotor must then be calibra ted to establish a reference pressure drop for monitoring purposes See 7 4 3 Calibration Heat exchanger When the function is activated the pressure dro
57. e cooling relays of the air handling unit operate in parallel with the signal and are energised when the cooling signal exceeds 0 5 V DC and are de energised when the signal drops below 0 2 V DC The output for Cooling Relay 1 is connected to IQnomic Plus termi nals 1 2 and for Cooling Relay 2 to terminals 4 5 Stepless 10 0 V DC Same as above but the control signal is inverted where a 10 V output signal means a 0 96 cooling load On off 1 step Used if cooling in one step is connected Connect to the IQnomic Plus module Cooling relay 1 terminals 1 2 The cooling controller of the air handling unit regulates the cooling load at 1 100 Cooling relays 1 and 2 are energised when the cooling load exceeds 5 96 and are de energised when the cooling load is less than 2 96 The 0 10 V DC control signal output operates in parallel with the 0 100 96 cooling demand and can be used for indicating the cooling demand for instance Connect to the IQnomic Plus module termi nals 15 16 On off 2 steps Used when cooling in 2 steps is connected Connect to the IQnomic Plus module Cooling relay 1 terminals 1 2 and Cooling relay 2 terminals 4 5 The cooling controller of the unit regulates the cooling demand at 0 100 96 Cooling relay 1 is energised when the cooling load exceeds 5 96 and is de energised when the cooling load is less than 2 96 Cooling relay 2 is energised when the cooling load exceeds 55 96 and is de ener gised when the cooling l
58. e pressure transducer connected for the heat exchanger Applicable to the defrosting function only 62 71 NO COMMUNICATION TO I O MODUL NR 1 9 B 0 1 3s The air handling unit s control unit cannot establish correct communication with the connected I O module 1 9 72 Correct communication can be established between A 1 1 30s the CPU circuit card and the control unit s 1 0 processor 83 SA PREFILTER FOULED B 0 1 600 s The pressure across the supply air prefilter has con stantly exceeded the preset alarm limit for O minutes 84 EA PREFILTER FOULED pasz 0 1 600 s M The pressure across the extract air prefilter has con stantly exceeded the preset alarm limit for O minutes 85 COOLING OUTPUT 1 TRIPPED A 0 1 3s M Broken signal is obtained at D11 for l 0 module 6 Motor protection or pressure switch may have trip ped 86 COOLING OUTPUT 2 TRIPPED A 0 1 3s M Broken signal is obtained at DI2 for I O module 6 The motor protection or pressure switch may have tripped 89 NO COMM SA PREFILTER PRESS SENSOR Bete 0 1 10s A The air handling unit s control unit cannot establish correct communication with supply air prefilter pres sure sensor 90 NO COMM EA PREFILTER PRESS SENSOR B 0 1 10s A The air handling unit s control unit cannot establish correct communication with extract air prefilter pres sure sensor Blocked if the hand terminal does not display
59. eplace the drive belt if it feels loose or worn and slightly slips if it meets resistance Contact service personnel trained by Swe gon 17 2 4 Fans and Fan Space Inspect and clean the fan impellers to remove possible dirt depo sits Check the impeller to make sure that it is not out of balance Clean or brush off the fan motor It can also be cleaned by carefully wiping it with a damp cloth that has been dipped in a solution of water and dishwashing detergent Clean the fan space if needed 17 3 Performance Checks General performance checks should be carried out in conjunc tion with filter change or at least once a year It is then appropriate to compare the current performance values of the unit with the Commissioning Record Eventual deviations should be remedied www swegon com 45 Swegon 18 ALARMS AND FAULT TRACING 18 1 General Alarms are indicated by an alarm text and flashing LED in the hand held micro terminal Fire alarms and frost alarms are shown in all the menu images Other alarms are only shown if you are in the Main menu Active but time delayed alarms can be viewed quickly at USER LEVEL under ALARMS The 10 most recently initiated alarms can also be read in this menu A fault can be traced by examining the function or func tion section indicated in the alarm text Faults can also be traced via the READINGS menu or the MANUAL TEST menu at Installation level If the fault cannot immedi
60. equence with factory preset time delay between every step as follows 1 The damper relay is energised and opens the shut off damper if installed Time delay 30 seconds 2 The extract air fan starts and the heat exchanger is controlled to provide max heat recovery Additional hea ting if installed is activated to generate 40 of its max capacity Time delay 90 seconds 3 The supply air fan starts Time delay 180 seconds from the time when the extract air fan has started 4 The temperature regulation function begins according to Its regular settings The starting sequence prevents the extract air fan from starting if the shut off damper is closed By starting the extract air fan first and the heat exchanger as well the system also avoids chilling the premises with cool supply air under cold weather conditions 10 1 2 Cooling Recovery Cooling energy recovery is an automatic function that helps the air handling unit utilize the relative cooling energy that may be present indoors if cooling is required and the outdoor temperature is high The heat exchanger rotates at max speed and in this way recovers the relative cooling energy or chilliness in the extract air The conditions for this function to be activated are that there is a cooling demand and that the outdoor tempe rature is 1 C higher than the extract air The function is switched out when the cooling load ceases to exist or when the outdoor tem
61. ernally posi tioned on the junction hood On the COMPACT Top the safety switch is positioned on the top front edge of the air handling unit The air handling unit must normally be started and stopped from the hand held micro terminal not by switching the safety isolating switch on and off Always switch off the safety isolating switch before serv icing the unit if not otherwise specified in the pertinent instructions 6 www swegon com GB COMPACTUT 101208 2 2 Risks Warning Before carrying out any work make sure that the power supply to the air handling unit has been switched off Risk areas with moving parts Typical moving parts are fan impellers and drive pulleys of the rotary heat exchanger Inspection doors can only be opened using a special key they therefore function as safety guards for fans and the heat exchanger If the ducts are not connected to the fan outlets the outlets must be fitted with a safety guard wire mesh screen Warning The inspection doors on the filter fan sections must not be opened while the unit is in operation Under normal operating conditions use the stop button on the hand held terminal to stop the air handling unit Wait until the fans have stopped rotating before opening the inspection door The air pressure inside the filter fan section is posi tive which means that the door can fly open 2 3 Safety Guards The lockable inspection door serves as a safety guard
62. ers causes the fans to run at a higher speed This causes higher power consumption and may also cause discomfort in the form of noise 9 3 1 2 Pressure Regulation The airflow automatically varies to provide constant pres sure in the ducting This type of regulation is also called VAV regulation Variable Air Volume Pressure regulation is used when damper operations in crease the air volume in parts of the ventilation system The duct pressure is measured by an external in duct pres sure transducer which is wired to the BUS communication of the control unit The setpoint setting required separate for low speed and high speed is entered in Pa The function can be limited so that the fan speed will not exceed the preset max permissible values 9 3 1 3 Demand Control The flow demand is regulated via a 0 10 V input signal from an external sensor such as a carbon dioxide sensor that is wired to control unit terminals 35 and 37 The required setpoint separate for low speed and high speed is set as a percentage of the input signal The function can be limited so that the flow will not be higher or lower than the preset max and min permissible values respectively 9 3 1 4 Slave Control The flow is constantly regulated to be the same from the one fan as from the other fan If one fan is pressure con trolled or demand controlled the other one can be con trolled as a slave to generate the same airflow The performa
63. ess to the control unit remove the cover plate in front of the heat exchanger Remove the upper section of the junction hood Cables from external sources can be run in to the electric cubicle through the rubber dia phragm on the backside of the junction hood N B Cables for external communication outside the air handling unit must be arranged at a minimum distance of 100 mm from any current carrying live cable 3 7 2 COMPACT Top To gain access to the power unit remove the cover plate in the unit s extract air duct Cables from external sources can be run into the air han dling unit through the rubber diaphragm by the extract air intake located at the top of the unit The external cables can be extended in the existing cable protection in the extract air duct of the unit Bundling straps are pre fitted inside the cable protection After running the cables secure them by pulling the bundling straps tight Cables can be run in to the electric cubicle according to appropriate hole indication in the rubber diaphragm N B Cables for external communication outside the air handling unit must be arranged at a minimum distance of 100 mm from any current carrying live cable Cable protection Extract air duct of the air han dling unit mu ee Cover plate am Electrical equip ment cubicle www swegon com 9 Swegon 4 COMMISSIONING 4 1 General Se
64. f the filters of 100 Pa is permissible after which an alarm is initiated indicating a fouled filter The alarm limit can be changed at INSTALLATION LEVEL under ALARM SETTINGS 7 4 3 Calibration Rotary Heat Exchanger If the anti frosting function accessory for heat exchanger is in stalled see 9 6 1 1 calibration can be selected from this menu When calibration R HX is activated the fans are accelerated to high speed for about 3 minutes www swegon com 19 Swegon 7 5 Air Adjustment The speed of the fans can be locked for up to 72 hours This is practical when making air adjustments in the duct system and air devices The period desired is preset but can be interrupted earlier by selecting STOP in the menu or by changing the time setting to 0 7 6 Alarms If an alarm is initiated this is shown in the hand held ter minal both as clear text and by a blinking red diode This menu enables you to read alarms quickly ACTIVE ALARMS Shows alarms that are active but have not initiated an alarm signal in the display This applies to alarms that have a long delay i e airflow or temperature alarms ALARM HISTORY The 10 most recent tripped alarms are shown Alarm settings can be entered at INSTALLATION LEVEL under ALARM SETTINGS For complete description of alarms see Section 18 20 www swegon com GB COMPACTUT 101208 AIR ADJUSTMENT AIR ADJUSTMENT LOCKS FAN SPEED TIME SETTING Oh ALARMS
65. for fans heat exchangers The cover over the power supply unit in the electric equip ment cubicle serves as a safety guard for this unit Only a qualified electrician or trained service technicians shall be allowed to remove the safety guards Warning The power supply to the unit shall be isolated by switching off the safety isolating switch before removing the safety guard As long as the air handling unit is operating the safety guards must always be mounted all inspec tion doors must be closed and the junction hood COMPACT Unit on the top of the unit must be mounted Registered design The company reserves the right to make design changes without prior notice Swegon 3 INSTALLATION 3 1 General The air handling unit is delivered with packaging standing on a wooden pallet Any accessories that have been ordered with the unit are supplied in unmounted condition Do not remove the air handling unit s protective plastic foil packaging until you ve finished installing it 3 2 Transport Within the Site Before removing the transport pallet from the unit deter mine whether a forklift truck or a pallet transporter will be used for further transporting the unit to where it is to be placed 3 3 Parts Packed Together with the Room Units Components such as the hand held micro terminal supply air sensor and document pocket are supplied in separate packaging and delivered together with the air handling unit
66. g of the unit When preset flow for low speed is near the min flow rate the effect of this regulation to a lower rate will be small Control sequence for Extract air regulation 1 The temperature efficiency of the air handling unit s heat exchanger is modulated to provide max heat recovery 2 After that the re heating coil if installed will begin to generate heat FUNCTIONS TEMPERATURE AIR FLOW PRESSURE ETENIPERATURE FILTER TEMPERATURE REG GB COMPACTUT 101208 OUTDOOR TEMP COMP SUMMER NIGHT COOL Important The appearance of the menus varies depending on the type of air handling unit and functions selected 22 www swegon com Registered design The company reserves the right to make design changes without prior notice Swegon 9 2 1 1 ERS Regulation ERS regulation means Extract air temperature Related Supply air temperature regulation This means that the temperature of the supply air is regulated in relation to the temperature of the extract air Under normal circumstanc es the supply air temperature is regulated to be a few de grees lower than the extract air temperature In this way the heat exchanger will provide optimal performance and this means excellent operating economy ERS regulation is suitable for use when there is excess heat in the premises generated for example by machinery lighting or people and the supply air devices in the premises are suitable dif fusing air
67. ger etc Used when the air handling unit is first installed to make sure that all the connections have been correctly wired Modo i Most alarms functions and normal control modes will be blocked while manual testing is in progress On a return to the other menu groups the controller resu mes normal operation and all settings for manual testing will be terminated Each menu indicates which functions can be test run Registered design The company reserves the right to make design changes without prior notice www swegon com 41 Swegon 13 ALARM SETTINGS 13 1 Fire Alarms EXTERNAL FIRE ALARM The Inp 1 and Inp 2 inputs can be used for external fire protection equipment The resetting of alarms can be selected to occur manu ally or automatically INTERNAL FIRE ALARM The air handling unit s internal temperature sensors serve as fire protection thermostats An alarm is initiated if the supply air tem perature sensor registers more than 70 C or when the extract air temperature sensor registers more than 50 C If an external Extract air Room temperature sensor is connected and activated this works parallel with the extract air temperature sensor of the unit FANS IN THE EVENT OF A FIRE The fans in the air handling unit can be used for evacuating gases etc The activated function works together with the External fire smoke function or Internal fire alarm If the air handling unit is idle the pre selected fans wi
68. hout prior notice www swegon com 51 Swegon GB COMPACTUT 101208 19 INFORMATIVE MESSAGES Informative messages are displayed in the hand held micro terminal Informative messages are displayed only when the user is viewing the Main menu Informative messages provide particulars about neces sary settings that have not been entered or unfavourable operating scenarios for instance 1 FILTER CALIBRATION NOT EXECUTED The pressure across the filters was not calibrated after the first start Recurrent at 24 hour intervals The mes sage will not be received after the pressure across the filters has been calibrated 2 H EXCH CALIBRATION NOT EXECUTED The pressure across the heat exchanger was not calibrated after the function was activated for the first time Recurrent at 24 hour intervals The message will not be received after the pressure across the heat exchanger has been calibrated SPARE 4 INCORRECT DIP SWITCH SETTINGS DIL switches on the control circuit card are set in a forbidden combination 5 SPARE E MAIL ERROR Error when e mail is being delivered The message will be displayed after ten attempts 7 PREFILTER CAL NOT EXECUTED The pressure across the prefilters was not calibrated after the first start Recurrent at 24 hour intervals The message will not be received after the pressure across the prefilters has been calibrated 52 www swegon com Registered design The company reserves the righ
69. ifferential increases Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 Pressure measurement tappings leakage direction COMPACT Unit Unit shown in the blue right hand version White blue ty White www swegon com 13 4 Swegon M GB COMPACTUT 101208 5 HAND HELD MICRO TERMINAL AND HOW TO USE THE MENUS TUE 14 40 5 1 HAND HELD MICRO TERMINAL STOP MANUAL OPERATION 3T General The hand held micro terminal consists of an encapsulated control box with a 3 metre long cable for connection to the air handling unit by means of a quick connector The hand held terminal has an illuminated display 6 push buttons and a red LED for indicating alarms 5 1 2 Buttons The buttons have the following functions e ENTER confirms your selection and proceeds to next menu level x ESCAPE reverts to the previous menu Q ADVANCE UPWARD or to the LEFT ADVANCE DOWNWARD or to the RIGHT DECREASES the value of the highlighted setting _ INCREASES the value of the highlighted setting 5 1 3 Display Screen The display screen has 4 lines Many of the menus howe COMPACT U TUE 14 40 PPS ver h
70. ill fit tightly Push in the handles so that the filters are clamped in place in the filter holder Carry out a filter calibration as described in Section 7 4 2 17 2 Cleaning and Inspection 17 2 1 General Clean the interior of the air handling unit as the need arises Inspect the air handling unit thoroughly at the same time that you replace the filters or at least twice a year 17 2 2 Filter Space Cleaning is most appropriate when you change the filters 17 2 3 Heat exchangers Check at least twice a year whether cleaning is necessary The cleaning work is carried out from the filter space The heat exchanger should preferably be cleaned by vacuum Cleaning with a soft nozzle to prevent damaging the air passages in the rotor Turn the rotor by hand to enable you to vacuum clean its entire surface If the heat exchanger is substantially fouled it can be blown clean with compressed air If necessary the heat exchanger can be withdrawn from the unit casing and washed with degreasing solvent Only service person nel trained by Swegon shall be permitted to use this cleaning method Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 FABRIC SEAL Lift up the fabric seal and inspect its underside Clean if needed by brushing or vacuum cleaning If the fabric seal is worn or substantially fouled it should be replaced Do not lubricate it BELT TENSION R
71. imit 0 99 months 12 months Depending on the choice of monitor function 13 4 Alarm Priority There should be special reasons for alteration of alarm prio rity and you should be aware of the consequences Changes in priority should only be made if you have special reasons for doing so and you should be aware of the conse quences The priority of certain alarms cannot be changed Settings See 18 2 Alarm Descriptions Registered design The company reserves the right to make design changes without prior notice Swegon 14 HAND HELD TERMINAL 14 1 Language The language desired can be set here Normally this set ting is entered when the air handling unit is started for the first time and the question ANDRA CHANGE automati cally appears in the hand held terminal However the language setting can be changed at any time Settings Value Setting Factory range settings Language Current languages English is listed in the menu 14 2 Air flow unit The air flow unit desired can be set here Settings Value Setting Factory range settings Flow unit I s m3 s m3 s m3 h 14 3 Min Max Adjustment Used for restricting the setting range at user level for set points as well as for min and max temperature limits Settings Value Setting Factory range settings For EA and SA regulation Setpoint min 10 30 C 15 C Setpoint max 10 40 C 40 C For EA regulation Min SA min 8 20 C 13 C Max SA min 8 20 C 18 C
72. ir handling unit s settings to the original values it had when it was supplied See 21 2 Commissioning Record The preset values for communication and alarm priority are not reset if the factory settings are reinstated Settings Value Save fetch setting Setting range Save setting internal memory Save new setting 1 Save new setting 2 Save setting 1 Save setting 2 Save current setting Save all external memory Load fetch internal memory Load new setting 1 Load new setting 2 Fetch setting 1 Fetch setting 2 Fetch current setting Fetch all external memory Factory setting Activate www swegon com 43 7 Swegon GB COMPACTUT 101208 15 COMMUNICATION COMMUNICATION Provision for communication and supervision is integrated as standard into the COMPACT The unit is ready to be connected via EIA 485 and Ethernet For particulars of connecting and wiring the air handling unit see Section 20 3 2 Wiring to Termi nals Communication can also be established via Ether net without software other than an ordinary web browser such as Internet Explorer Further information about interfaces proto col and configuration is available at www swegon se com under Products Air handling units COMPACT air handling units Documen tation COMMUNICATION EIA 485 ETHERNET 15 1 EIA 485 Protocol and settings for EIA 485 is specifie
73. lar start time according to switch clock hour min 00 00 Damper output Inactive Inactive Extract air fan Inactive Inactive FL Rum temp 10 30 C 22 C TL min 8 20 C 15 C TL max 16 50 C 28 C 9 2 6 External Temperature Sensors The IQnomic control unit has provision for wiring an ex ternal room sensor and or external outdoor sensor The sensor can be used when the internal sensor of the unit does not provide representative values External Extract air Room can measure the extract air temperature in a larger room instead of the temperature inside the air handling unit External Outdoor measures the outdoor air temperature outdoors instead of the temperature inside the air han dling unit Connect the TBLZ 1 24 2 sensor by means of the modular cable supplied to an optional connection marked Internal BUS 1 Sensor TBLZ 1 24 2 can be used both as a room sensor and an outdoor sensor They must therefore be addressed according to function using the function selector switch on the sensor The function selector switch must be in Position 1 if the sensor is used as a room sensor and in Position 2 if it is used as an outdoor sensor If the TBLZ 1 24 2 sensor is installed outdoors it must be mounted inside an air tight enclosure As an alternative a temperature reading can be commu nicated to the air handling via communication from e g a main system The alarm setting indicates how long the alarm will be delayed if communi
74. lars on the prod uct identification plate when you contact Swegon Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 1 2 Mechanical Design The COMPACT is available in one physical size and for two airflow ranges The external sheet metal surfaces of the unit are painted white NCS S 0502 G except for the rear of the COM PACT Top unit which consists of an aluminium zinc plated sheet steel casing panel The upper section of the junction hood of the COMPACT Unit is light grey NCS 3502 B and the lower section is dark grey NCS S6010 R90B The inner skin is predominantly made of aluminium zinc plated sheet steel The casing has 30 mm thick intervening mineral wool insulation the inspection doors have 50 mm thick insulation The COMPACT Unit and the COMPACT Top are equipped with pleated Class F7 filters The type RECOnomic rotary heat exchanger is variable speed controlled and has a temperature efficiency of up to 8596 The supply air and extract air fans are direct driven plug fans The fans are equipped with EC motors that provide high efficiency across the entire operating range 1 3 Control System The IQnomic control system is microprocessor based and is integrated into the unit It controls and regulates the fans heat exchanger temperatures airflows operating times and a large number of internal and external functions as well as alarms 1 4 En
75. ll start up regardless of whether External Stop or Manual Stop has been activated in the hand held micro terminal The damper relay in the air handling unit is energised and the operating relay drops The dampers pre selected for service in the event of a fire should be wired to the damper relay and these dampers will open The dampers that are meant to close in the event of a fire should be wired to the in operation relay and these dampers will close FAN SPEED IN THE EVENT OF FIRE Will be activated automatically if the fans have been activated in event of fire see above and make it possible to restrict the max speed of the fans Settings Value Setting range Factory setting Internal fire alarm O inactive 0 1 activated External fire alarm auto manual manual Fan in event of fire Inactive EA SA Inactive SA EA Fan speed in event of 10 100 100 fire SA Fan speed in event of 10 100 100 fire EA 13 2 External Alarms EXTERNAL ALARMS 1 and 2 Input Inp 1 and Inp 2 can be used for external alarms can be selected under Inputs Outputs Typical uses Motor protection for the circulation pump in the heating or cooling circuit Service alarm actuated by smoke detectors Set the time delay and set whether the alarm shall be activated on closure or disconnection of the input Settings Value Setting Factory range settings Time delay 1 600 sec 10 sec Alarm at closure 1 closure 1 O disconnection Alar
76. m reset O auto 1 man 0 42 www swegon com GB COMPACTUT 101208 ALARM SET ALARM SETTINGS FIRE ALARM EXTERNAL ALARMS ALARM LIMITS ALARM PRIORITY 1 I ee a 13 3 Alarm Limits Changes in the factory preset alarm limits should only be made if you have special reasons for doing so and you should be aware of the consequences TEMPERATURE DEVIATION SA TEMP deviating supply air temperature indicates how much the supply air temperature is allowed to be below the supply air temperature setpoint before an alarm is initiated MIN EA TEMP min extract air temperature indicates how low the extract air temperature is allowed to be before alarm is initiated FILTERS SUPPLY AIR EXTRACT AIR indicates at which level of contamination in the supply air filter that an alarm will trip HEAT EXCHANGER ALARM LIMIT indicates at which pressure rise an alarm will trip if there is an extra installed pressure transducer for the defrosting function of the heat exchanger SERVICE PERIOD SERVICE PERIOD indicates the period until the next service Settings Value Setting Factory range settings TEMPERATURE Deviating supply air temp 2 15 C 5 C Min extract air temp 8 20 C 15 C FILTERS Supply air 50 300 Pa 100 Pa 5 20 10 Extract air 50 300 Pa 100 Pa 5 20 10 Supply air prefilter 50 300 Pa 100 Pa Extract air prefilter 50 300 Pa 100 Pa HEAT EXCHANGER Alarm limit 30 100 Pa 50 Pa SERVICE PERIOD Alarm l
77. mperature sensor extract air COMPACT Unit The designations apply to the right hand version In the left hand version the sensors change function and designation the components are named according to whether they are for supply air or extract air Terminal Function Remarks 1 2 Output 1 Select function individually Independent contact max 5 A AC1 1A AC3 250 V AC 3 4 Output 2 Select function individually Independent contact max 5 A AC1 1A AC3 250 V AC 5 6 Input 1 Select function individually 7 8 Input 2 Select function individually 9 10 Control voltage Control voltage 24 V AC max permissible load 28 VA 9 G 10 GO 11 12 13 Connections for EIA 485 11 communication connection A RT 12 communication connection B RT 13 2 GND COM 14 15 16 17 Heat exchanger motor 14 Earth 15 Red 16 Yellow 17 Black 18 19 20 Rotation monitor sensor 18 Brown 19 Blue 20 Black 21 22 Supply voltage H EXCH control 36 V AC in 23 24 Supply voltage control unit 18 V AC in 25 26 Supply voltage outputs 24 V 24 V AC in 27 28 29 Damper actuator change over damper 27 GO Black 24 V AC 28 G Red 24 V AC 29 NO White 24 V AC out if Applies to COMPACT Heat only active 30 31 32 Damper actuator air recirculation damper 30 GO Black 24 V AC 31 G Red 24 V AC 32 NO White 24 V AC out if active 33 Output fixed power supply 12 V DC out
78. nce of the fan controlled as a slave can be restricted if its maximum flow is set to a lower airflow rate Both fans cannot be controlled as slaves If both are selec ted by mistake the extract air fan will be forced to operate in the flow regulation mode Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 FUNCTIONS TEMPERATURE AIR FLOW PRESSURE FILTER AIRFLOW PRESSURE SA FAN REGULATION 1 OPERATION FUEATING 7777 EA FAN REGULATION Eoo oe CLEAN AIR CONTROL QIN OUTPUTS 77 OUTDOOR TEMP COMP 1 AIRFLOW PRESSURE SA FAN REGULATION EA FAN REGULATION CLEAN AIR CONTROL OUTDOOR TEMP COMP _ 1 SA DOWN REGULATION _ L SLAVE CONTROL Settings Value Detting Fan regulation SA EA Flow regulation Pressure regulation Demand control Slave control www swegon com 29 Swegon 9 3 1 5 Clean Air Control The Clean Air Control function is used in ventilation sys tems where the aim is to regulate the airflow according to the content of emission impurities in the room air The TBLZ 1 60 VOC sensor accessory Volatile Organic Compounds is required The VOC sensor measures the content of emissions impurities in 96 VOC When an occupant emits CO this creates a proportional amount of emissions impurities which are measurable by the VOC sensor For an approximate translation of the 96 VOC to CO content see the diagram
79. nger s drive motor A KKK 35 37 OVER TEMPERATURE IN R HX CONTROLLER High internal temperature 90 C for the rotary heat exchangers controller A KKK 35 38 R HX PRESSURE DROP ABOVE ALARM LIMIT The heat exchanger s defrosting function has operated for the full max period 6 times during one 24 hour period B KKK 35 Blocked if the hand terminal does not display the main menu 48 www swegon com Registered design The company reserves the right to make design changes without prior notice 7 Swegon GB COMPACTUT 101208 Priority Stop Indication Delay Resetting Alarm text LED Function O blocked O In operat 0 Off seconds M manual A A alarm 1 Stop 1 On m minutes A automatic B B alarm Alarm no UJ M o EL HEATING COIL TRIPPED A Ree 1 35 M The thermal overload protection has tripped or is not connected 40 EXTRACT AIR TEMP BELOW ALARM LIMIT ARRE 1 20m M The extract air temperature is below preset alarm limit for more than 20 minutes 41 SUPPLY AIR TEMP BELOW SETPOINT A 1 20m M The supply air temperature is below the preset set point for ERS and Supply air regulation or Min SA temp for Extract air regulation longer than 20 minutes 42 EXT ALARM No 1 TRIPPED A 1 1 Set time M External alarm connected to control unit input Inp or Inp 2 has tripped
80. nit 5 o coe 3 6 To Mount the Supply Air Sensor 3 7 Connection to the Electric Power Grid 9 3 71 ACCESS acc Gode e eque o ea pes 3 7 2 Electrical Connections 3 8 To Connect External Cables 4 COMMISSIONING 4 1 General rcs cte tbt atenta 4 2 Adjusting the Duct System and Air Devices iis 4 2 1 Adjustment Sequence 11 4 2 2 Adjustment Procedure 4 3 To Adjust the Pressure Balance oe 4 3 A General e eet ts 4 3 2 To Ensure the Correct Leakage Direction ars 13 5 HAND HELD MICRO TERMINAL AND HOW TO USE THE MENUS 5 1 HAND HELD MICRO TERMINAL 5 1 1 General tetti bl 2 BUttOlls cott tec beoe e es 5 1 3 Display Screen 5 1 4 Abbreviations 5 2 Men the hes sicci c ce me a 6 MAIN MENU nnn 16 EEE e iet res 6 2 Selection of Language ssssse 6 3 Changing Operating Mode 6 4 Settings eener res 7 USER LEVEL iiinis FV Ternperature 5er exe 7 1 1 Readings 7 1 2 Settings 7 2 Air flow Pressure 7 2 1 Readings iu 4 22 Seti gs certe seeded 2 www swegon com 7 3 Switch clock 7 4 Filters 7 4 1 Readings 7 4 2 Calibration Filters sssss 19 7 4 3 Calibration Rotary Heat Exchanger 19 7 5 Air Adjustment 20 7 6 ALANS si ie rhet ere 2
81. nu Settings Value Setting Factory range settings Function Inactive SA SA EA Active Neutral zone 0 0 10 0 C 0 0 C 9 3 4 To adjust the flow of the slave fan It is possible to preset the set point of the slave fan to provide a higher or lower airflow than the current airflow of the controlling fan The deviation from the airflow of the controlling fan can be preset by entering a COP A cooling COP of 0 5 denotes that the airflow of the slave will be 50 of the master fan s airflow Settings Value Setting Factory range settings Cooling COP 0 5 1 5 1 0 9 4 To Activate the GOLD SD Filter Monito ring Function The filter monitoring function must be activated for the filters that are to be monitored Settings Value Setting Factory range settings Standard filter Inactive SA EA SA EA SA EA Prefilter Inactive SA EA SA EA SA EA 32 www swegon com GB COMPACTUT 101208 FUNCTIONS TEMPERATURE AIR FLOW PRESSURE AIRFLOW PRESSURE FLIER SA FAN REGULATION OPERATION gt 22L EA FAN REGULATION CLEAN AIR CONTROL FUNCTIONS TEMPERATURE a Sa ae A IRFLOW PRESSURE SA FAN REGULATION OPERATION ___ EA FAN REGULATION CLEAN AIR CONTROL FUNCTIONS TEMPERATURE AIR FLOW PRESSURE FILTER OP ERATI Ol N 24 I NHEATING 2 2222 4 COOLING 7 TTT E IN OUTPUTS I Registered design The company reserves the right to make design changes without prior notice 7 Swegon SSS GB COMP
82. oad is less than 50 96 The 0 10 V DC control signal output operates in parallel with the 0 100 96 cooling demand and can be used for indicating the cooling demand for instance Connect to the IQnomic Plus module termi nals 15 16 On off 3 Steps Binary Used when cooling with two inputs controlled with three binary steps is connected Connect to the IQnomic Plus module Cooling relay 1 terminals 1 2 and Cooling relay 2 terminals 4 5 The cooling con troller of the unit regulates the cooling demand at 0 100 On an increasing cooling load Cooling relay 1 is energised when the cooling load is above 5 96 and is de energised when the cooling load is between 40 70 96 Cooling relay 2 is energised when the cooling load is above 40 96 Cooling relay 1 is energised again together with cooling relay 2 when the cooling load is above 7096 On a decreasing cooling load Cooling relay 1 is deenergised when cooling load is below 60 it is energised again when cooling load is below 30 96 and is deener gised again when cooling load is below 2 96 Cooling relay 2 drops when cooling load is below 30 96 The 0 10 V DC control signal output operates in parallel with the 0 100 96 cooling demand and can be used for indicating the cooling demand for instance Connect to the IQnomic Plus module termi nals 15 16 36 www swegon com GB COMPACTUT 101208 FUNCTIONS TEMPERATURE AIR FLOW PRESSURE FILTER 1 OPERATION
83. on Function Factory preset value GB COMPACTUT 101208 Adjusted value Flow pressure Fan Regulation SA X Flow Pressure Need Slave Flow Pressure Need Slave Fan Regulation EA X Flow Pressure Need Slave Flow Pressure Need Slave Flow low speed 1 1 1 1 Flow high speed 2 2 2 2 Flow max speed 4 3 4 4 3 4 Flow min speed 5 5 Pressure low speed 100 100 Pressure high speed 200 200 Max fan speed 100 100 Pressure max speed 400 6 400 6 Demand contr low speed 25 25 Demand contr high speed 50 50 Clean Air Control x Inactive Active Inactive Active Outdoor temp compen x Inactive Active Inactive Active Flow Winter compens Y1 30 End point winter X1 C 20 Start point winter X2 C 10 Down speed regulation Function J inactive x sa SA EA Inactive SA SA EA Neutral zone C 0 0 In oper
84. oost the flow is controlled by the function that transmits the highest output signal to the fans This function cannot be combined with pressure regula tion The flow increase starts steplessly when there is a differen ce of 2 10 C 3 C is factory preset to preset max supply air temperature When max supply air temperature has been reached the unit runs at preset max flow For parti culars of how to set the max flow see Section 7 2 2 Settings Value Setting Factory range settings Heating BOOST Inactive active Inactive Start limit 2 10 C 37C Registered design The company reserves the right to make design changes without prior notice AIR FLOW PRESSURE AIR FLOW PRESSURE GB COMPACTUT 101208 HEATING HEAT EXCHANGER PRE REHEAT HEATING BOOST HEATING HEAT EXCHANGER PRE REHEAT HEATING BOOST www swegon com 35 Swegon 9 7 Cooling Control of cooling units is primarily wired to Outp 1 or Outp 2 If none of these outputs are vacant connect the control means to the IQnomic Plus module The module s function selector switch must be set to Position 6 9 7 1 Operation Activate the cooling function 9 7 2 Cooling Regulation Control Stepless 0 10 V DC Used when variable cooling control is connected The COMPACT air handling unit s cooling controller modulates a 0 10 V DC signal that is linear with the cooling load Connect to the IQnomic Plus module terminals 15 16 Both th
85. p across the heat exchanger is continuously measured and the value is compared with the calibration value If the pres sure drop exceeds the preset limit value a defrosting se quence is implemented where the rotor speed is gradually ramped down ramp time of max 4 minutes to the speed at which the pressure drop across the heat exchanger has decreased to half of the preset limit value The rotor speed can be 0 5 rpm but not slower During the defrosting op eration warm extract air thaws any possible ice coating A time delay of 4 minutes gives the heat exchanger a chance to dry before the rotor once again is ramped up ramp time max 4 minutes to its ordinary speed The max duration of the defrosting operation is 30 min utes If the pressure drop has not decreased within this max duration on six occasions during a 24 hour period an alarm is tripped Note that the heat exchanger performs less efficiently while defrosting is in progress and that the supply air tem perature will decrease downstream of the heat exchanger Settings Value Setting Factory range settings Defrosting Inactive active Inactive GB COMPACTUT 101208 FUNCTIONS TEMPERATURE AIR FLOW PRESSURE FILTER 1 OPERATION 1 HEATING HEAT EXCHANGER PRE REHEAT HEATING BOOST EXTRACT AIR Defrosting function with separate pressure transducers in principle 34 www swegon com Regi
86. perature Regulation Select ERS Regulation Supply air regulation or Extract air regulation If ERS Regulation is selected select between 1 and 2 Control sequence for ERS regulation and Supply air regu lation 1 The temperature efficiency of the air handling unit s heat exchanger is modulated to provide max heat recovery 2 After that the air heater if installed will begin to generate heat 3 If a downstream heating coil is not installed or if the its output is not adequate the supply air fan will be automatically and variably downspeed regulated to convey air at a lower flow rate A neutral zone can be preset which allows a lower supply air temperature setpoint before regulation to a lower flow rate begins See 8 3 4 When the supply airflow is regulated to a lower rate the heat exchanger will have excess heat i e warm extract air giving it capacity to maintain the supply air tempera ture required As the supply airflow is regulated to a lower rate the air pressure in the premises will become negative and this will instead cause outdoor air to be sucked in through lea kage spots such as doors and windows This outdoor air will then be heated by the ordinary heating system of the premises Downspeed regulation to lower the airflow rate occurs from the current preset flow high speed or low speed down to half of this flow rate The degree of regulation to a lower rate is also limited by the min flow settin
87. perature is the same as that of the extract air The text COOLING RECOVERY is shown in the hand held micro terminal 10 1 3 Zero Point Calibration The pressure transducer of the unit is automatically cali brated This calibration is carried out 3 minutes after the unit has been stopped The text ZERO PT CALIBR is shown in the hand held micro terminal The fans cannot start while calibration is in progress 40 www swegon com GB COMPACTUT 101208 10 1 4 Anti frost Monitoring Function Air Heater for Hot Water The anti frost monitoring function is always active if the air heater for hot water connected has been supplied by Swegon The function activates a heating device that maintains 13 C in the coil while the air handling unit is in operation and 25 C in the coil when the unit is stopped An alarm is initiated and the unit is stopped if the temperature sensor senses a temperature below 7 C 10 1 5 Additional cooling Electric Air Heater The fans continue to operate at min speed for 3 minutes after the air handling unit has been stopped to cool the electric heating elements if the electric air heater has been operating The text ADD COOLING appears in the hand held micro terminal 10 1 6 Additional running Heat Exchanger The rotary heat exchanger automatically continues to rotate ca 1 minute after the air handling unit has been stopped It takes a little time for the fans to stop rotating after a stop o
88. quence for commissioning 1 Check that there are no foreign objects in unit ducting system or functional sections 2 Turn the safety isolating switch to the ON position I 3 Select the language desired if you have not already done so See Section 6 2 or 14 1 4 The unit has factory settings which make it ready to use See Section 21 2 Commissioning record However in many cases these settings need to be adjusted to suit the current installation Program the switch clock operating conditions temperatures airflows and functions according to the procedures in Sections 5 16 Select whether I s m3 s or m3 h shall be used as the flow unit INSTALLATION LEVEL in the HAND HELD MICRO TERMINAL menu Fill out the Commissioning Record and save it in the document pocket of the unit 5 Activate if needed manual or auto operation MAIN MENU or lock the speed of the fans AIR ADJUSTMENT menu Adjust the ducting system and air devices as described in Section 4 2 6 Finish off with a filter calibration as described in Section 7 4 2 GB COMPACTUT 101208 10 www swegon com Registered design The company reserves the right to make design changes without prior notice Swegon 4 2 Adjusting the Duct System and Air Devices In order to prevent the fans from consuming more power than necessary it is important to keep the pressure drop in the system as low as possible It is also important that ducting systems and air de
89. r must be positioned 1 5 metres from the unit measured from these components 1 Measure and mark where the sensor is to be placed 2 Drill an 11 mm dia hole in the supply air duct 3 Apply sealing compound around the hole and secure the sensor by means of 2 self tapping screws 4 Connect the sensor s quick fit connector to the socket at the top of the air handling unit see 20 3 1 An extension cable is available as an accessory Sealing compound Self tapping screw Registered design The company reserves the right to make design changes without prior notice Swegon 3 7 Connection to the Electric Power Grid Connection of the power supply cable from the mains must be wired across a safety isolating switch 3 7 1 Access COMPACT Unit Remove the upper section of the junction hood Run the cable through the cable gland on the backside of the junc tion hood Junction hood Cable gland Safety isolating switch COMPACT Top Open the inspection panel and dismantle the cover Run the cable through the cable gland by the safety isolating switch Safety isolating switch Cable gland Cover 3 7 2 Electrical Connections 1 phase 3 wire 230 V 10 15 50 Hz 10 AT L1 Safety isolating switch Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 3 8 To Connect External Cables 3 7 1 COMPACT Unit To gain acc
90. rder has been entered in the micro terminal This prevents the admission of cool supply air into the premi ses 10 1 7 Density corrected Airflow The density of the air is different at different temperatures This means that a specific volume of air will change at dif ferent air densities The COMPACT automatically corrects this so that correct air volume is always obtained The control equipment always shows the corrected air flow Registered design The company reserves the right to make design changes without prior notice 7 Swegon sss GB COMPACTUT 101208 11 READINGS The operating status and the values can be read Used for performance checks and for generally checking values settings power consumption etc E READINGS READINGS No values can be altered in this menu group TEMPERATURE NT FANS Each menu indicates which values can be read HEAT EXCHANGE The operation times per 24 hour period are given under REGULATION SIGNALS the OPERATION TIME menu FINOUTPUTIS 5 1 UQnomic Plus 3 pose UU Use od PROGRAMVERSIONS 12 MANUAL TEST Note Manual test running can cause indoor com fort problems There is also risk of overloading the system The responsibility for discomfort and over load rests totally on the person who activates the function MANUAL TEST TEMPERATURE FANS Manual test run can take place for testing the inputs and HEAT EXCHANGE outputs fans and heat exchan
91. re Y1 10 40 C 20 C Y2 10 40 C 18 C Y3 10 40 C 14 C SUPPLY AIR REG Settings Value Setting Factory range settings Supply air temperature setpoint 15 40 C 21 5 C EXTRACT AIR REG Settings Value Setting Factory range settings Extract air room temp Setpoint 15 40 C 21 5 C Min supply air temperature 13 25 C 159 Max supply air temperature 18 45 C 28 C The setting range can be changed See 14 3 Min Max Adjustment GB COMPACTUT 101208 Important The appearance of the menus varies depending on the type of air handling unit and functions selected TEMPERATURE TEMPERATURE READINGS SETTINGS TEMPERATURE READINGS SETTINGS ERS REGULATION 1 ERS REGULATION 2 SUPPLY AIR REG EXTRACT AIR REG ERS Regulation 1 Supply air temperature setpoint C 15 20 25 Extract air temperature C ERS Regulation 2 o 22 o o 20 o 4 wo wu wo c 2 m c 2 15 E wo 5 o S J 10 Lu 9 gt 12 15 20 25 27 X Extract air temperature C www swegon com 17 Registered design The company reserves the right to make design changes without prior notice Swegon 7 2 Air flow Pressure Basic functions are set at INSTALLATION LEVEL and values are read and set at USER LEVEL Therefore see also Section
92. re named according to whether they are for supply air or extract air The arrangement of the components and their designations 1 OUTDOOR AIR Left hand version Extract air EXHAUST AIR Left hand version Supply air Extract air fan with motor and motor control system Pressure sensor extract air fan Position on function selector switch 1 Electrical equipm cubicle with control unit Hand held micro terminal Main switch Safety switch Extract air filter BWN ON AW DA a www swegon com BRWN O O OND U1 Left hand version EXTRACT AIR Left hand version Outdoor air SUPPLY AIR Left hand version Exhaust air Supply air temp sensor to be mounted in supply air duct Supply air fan with motor and motor control system Extract air temperature sensor Pressure sensor supply air fan Position on function selector switch 2 Heat exchanger Drive motor heat exchanger Sensor rotation monitor Outdoor air temperature sensor Supply air filter Registered design The company reserves the right to make design changes without prior notice Swegon 1 5 2 COMPACT Top The individual components each specified below in a simplified and diagrammatical description View from the above gt Outdoor air Registered design The company reserves the right to make design changes without prior notice gt Supply air
93. revents the extract air from being carried over to the supply air The pressure balance in the unit should be adjusted when the ventilation system has been fully installed and all the air diffusers have been airflow adjusted as well as for the supply air and extract air flows that prevail while the air handling unit is operating normally COMPACT Top _ Le OPEN CLOSE 12 www swegon com Registered design The company reserves the right to make design changes without prior notice Swegon 4 3 2 To Ensure the Correct Leakage Direction The pressure balance in the unit is adjusted by means of a adjustment plate mounted in the extract air inlet IMPORTANT If you change COMPACT Unit to the left hand version you must move the pressure adjusting plate must always be situated in the extract air inlet Connect a pressure gauge to the pressure measurement tappings of the unit The COMPACT Unit has four pressure measurement tappings Use the two tappings nearest the extract air duct See illustration The COMPACT Top has two pressure measurement tappings See illustration The blue pressure measurement tapping is used for measur ing the negative pressure in the extract air section and th
94. rior notice www swegon com 15 Swegon 6 MAIN MENU 6 1 General The main menu is normally shown if no other menu has been selected The display automatically returns to the main menu after 30 minutes The content in the menu changes depending on the operating mode selected other functions that affect the present operating mode and possible tripped alarms 6 2 Selection of Language When the air handling unit is started up for the first time a language selection menu is displayed Select the language desired If you want to change language at a later oppor tunity or if you ve selected the wrong language you can change the language at INSTALLATION LEVEL under HAND TERMINAL See Section 14 1 6 3 Changing Operating Mode You can start and stop the air handling unit or change over to manual or automatic operation from the main menu The air handling unit should normally be started and stopped from the hand held micro terminal not by switching the safety isolating switch on and off When the air handling unit is started up menus for the various delays that are part of the starting sequence are shown See also Section 10 1 1 Starting Sequence 6 4 Settings When selecting SETTINGS in the main menu you will advance to User Level and Installation Level See Section 7 16 www swegon com GB COMPACTUT 101208 COMPACT U TUE 14 40 STOP MANUAL OPERATION l COMPACT U TUE14 40 MANUAL ES
95. sor by EA prefilter B 1 0 91 Frost prot for preheating below alarm limit A 1 1 66 www swegon com Registered design The company reserves the right to make design changes without prior notice I Swegon E GqB COMPACTUT 101208 92 Frost prot for preheating sensor faulty A 1 1 93 Preheating sensor faulty A 1 1 94 Electric air heater for preheating tripped A 1 1 95 Preheating below setpoint A 1 1 99 Time lock tripped A 1 1 Not adjustable always stops the air handling unit Not adjustable stops the air handling unit at temperature below 5 C Blocked if the hand terminal does not display the main menu Cannot be blocked Adjustments carried out by Date Company Name Registered design The company reserves the right to make design changes without prior notice www swegon com 67 7 Swegon S GB COMPACTUT 101208 All documentation is available in digital form and can be downloaded from WWVW Swegon com 68 www swegon com Registered design The company reserves the right to make design changes without prior notice
96. stered design The company reserves the right to make design changes without prior notice Swegon 9 6 2 Pre Reheating AIR HEATER FOR HOT WATER On selecting the exercising pump or pump valve function the selected relay output will be activated if reheating is needed and this starts the circulation pump of the air heater If the outdoor temperature is low colder than 12 C the pump output contact is continuously activated During other times the pump output contact is activated 2 min 24 hours for exercising of circulation pump ELECTRIC AIR HEATER If pump exercising mode inactive has been selected the relay output is activated whenever heating is required The relay output can be used for indicating or blocking the external function EXERCISING MODE Settings Value Setting Factory range settings Function Inactive pump Pump pump valve valve Exercise period 1 60 min 3 min Interval 1 168 hrs 24 hrs 9 6 3 Heating BOOST Heating boost means that the air handling unit operating in the normal flow regulation mode increases both the supply airflow and the extract airflow in order to carry more heat into the premises The fans are allowed to work in the range between cur rent flows low speed high speed and preset max speed flow The function only works if the air handling unit is opera ting in the extract air regulation mode If demand control or boost is selected in combination with heating b
97. t economy Economy sequence Start limit in connection to min supply air temp 2 10 C 3 C Registered design The company reserves the right to make design changes without prior notice Swegon See preceding page for possibilities of setting 9 7 3 Periodic Operation Can be selected to run pumps if cooling relay 1 and or 2 are used The exercising mode can be selected for pump pump valve or valve only 0 10 V output The pumps are exercised 2 minutes per day if this is activated 9 7 4 Regulation Speed The required delay period between the various cooling steps can be set This is done so that a compressor for instance will have time generate required cooling capacity before the next cooling step is switched in This applies to changeover from step 1 to step 2 and from step 2 to step 3 and only on an increasing cooling load 9 7 5 Outdoor Temperature Limit Provision is available for setting an outdoor temperature related blocking function in 3 steps If the outdoor tempe rature is below each step limit the function of the cooling relays will be blocked This function also restricts the 0 10 V output signal to transmission in steps Step 1 maximises the output signal to 2 5 V step 2 to 5 0 V and step 3 to 7 5 V 9 7 6 Restart Time The time should be set in such a way that it follows the recommendations of the cooling machine supplier for the number of starts per hour The restart time is
98. t should operate in a time channel switch clock stop e The room temperature should be below set start tempe rature Conditions to be met for intermittent night time heating to stop High speed or external manual stop should be activated Room temperature should be above the preset stop temperature Alarm with preset stop priority has tripped If the needed the air handling unit fans will continue to operate to cool the electric air heater although other con ditions for stop have been met Settings Value Setting Factory range setting Room temperature for start 5 25 C 16 C Room temperature for stop 5 25 C 18 C Supply air temperature setpoint 10 40 C 28 C Supply airflow m3 s Pa m3 s Pa Extract airflow m3 s Pa 0 m3 s Pa Damper output Oznot activated 0 1 activated O IQnomic 0 1 zIQnomic Plus The setting range is the same as the min max settings of the air handling unit According to the setting for low speed at USER LEVEL under FLOW PRESSURE Control output Registered design The company reserves the right to make design changes without prior notice GB COMPACTUT 101208 FUNCTIONS TEMPERATURE z AIR FLOW PRESSURE TEMPERATURE FITER TEMPERATURE REG OUTDOOR TEMP COMP LOPERATION ae SUMMER NIGHT COOL PEANO o n INTERM NIGHT HEAT ONE z MORNING BOOST T IN OUTPUTS MORNING BOOST __ __ iQnomic Plus 1 EXT SENSORS i occ E e a
99. t tecta ose 9 7 1 Operation tec 9 7 2 Cooling Regulation Control 9 7 3 Periodic Operation sssss 37 9 7 4 Regulation Speed sssss 9 7 5 Outdoor Temperature Limit she 9 7 6 Restart TME ssec t eet ente 9 7 7 Cooling Min Air Flow 9 7 8 Neutral Zone sie 9 79 Cooling BOOST sissies coe 9 8 Input output connections 38 9 OU OBONmIC Pls cuius eet met e eoe 39 10 AUTOMATIC FUNCTIONS 40 10 1 General e 10 1 1 Starting Sequence Si 10 1 2 Cooling Recovery sssse 10 1 3 Zero Point Calibration 40 10 1 4 Anti frost Monitoring Function Air Heater for Hot Water ssss 40 10 1 5 Additional cooling Electric Air Heater eee 40 10 1 6 Additional running Heat Exchanger eae 40 10 1 7 Density corrected Airflow 40 GB COMPACTUT 101208 11 READINGS sssscccceseeeneneenenenes 41 12 MANUAL TEST 41 13 ALARM SETTINGS 42 3 1 Fire Alanms a coser tres 3 2 External Alarms 3 3 Alarm Limits 3 4 Alarm Priority ea 14 HAND HELD TERMINAL 43 As Eangage sor epe eet enun e A Z Air Tow Unit ccce como ees 4 3 Min Max Adjustment 4 4 Base Settings 15 COMMUNICATION 5 1 EIA 485 cn 5 2 Ellierhiet s asso ro ep oce reco add 16 SERVICE
100. t to make design changes without prior notice I Swegon l qB COMPACTUT 101208 20 TECHNICAL DATA 20 1 Dimensions COMPACT Unit one piece unit Weight 160 kg A clear space of 800 mm must be provided in front of the unit for opening the inspection doors and at least 200 mm must be provided above the unit for opening the junction hood 20 2 Dimensions COMPACT Top One piece Unit Weight 200 kg 250 x4 A clear space of 1 000 mm should be provided in front of the e unit for opening the inspection doors Registered design The company reserves the right to make design changes without prior notice www swegon com 53 Swegon 20 3 Electrical Equipment Cubicle The electrical equipment cubicle contains two units the control unit and the power unit On the COMPACT Unit the control unit is positioned behind the cover plate of the heat exchanger This must be dismantled to gain access The power unit is positioned behind the control unit The power unit in the COMPACT Unit is accessible after removing the junction hood from the top of the air han dling unit On the COMPACT Top unit remove the cover plate by the cable entries in the air handling unit s extract air duct See the illustration COMPACT Unit Power unit Control unit
101. ting Open the inspection doors 3 Remove the screws that secure the cover plate of the heat exchanger for access to the DIL switch 4 Set DIL switch No 1 to the ON position see 20 3 for the left hand version see 3 4 1 1 5 Refit and secure the cover plate 6 Rotate the rotary heat exchanger by hand to rotate downwards This is sufficient tp rotate the rotor approx one quarter of a revolution 7 Close the inspection doors 8 Switch on the safety isolating switch 9 Start the air handling unit 3 5 Connecting ductwork to the Air Han dling Unit The air handling unit s connection spigots are circular and can be connected to ducts by means of insertion joints fitted with a rubber ring seal Spiral duct bends fitted with a rubber ring seal can be con nected directly without any insertion joint The insertion joint duct bend must be secured by pop rivets or tape in the spigot of the air handling unit The ducts should be insulated according to local regula tions and customary trade standards Duct EE Duct bend oe Insertion joint Duct 1 f 8 www swegon com GB COMPACTUT 101208 3 6 To Mount the Supply Air Sensor Supply air temp sensor must be mounted inside the sup ply air duct The sensor must be positioned at a spot that is at least 1 5 metres from the air handling unit Important If an air heater and or air cooler if required is installed in the system the senso
102. ve setpoint B 1 0 47 EA duct pressure above setpoint Bx 1 0 48 Supply airflow below setpoint Bese 1 0 49 Extract airflow below setpoint B 1 0 50 Supply airflow above setpoint Bes 1 0 51 Extract airflow above setpoint B 1 0 52 Supply air filter dirty B 1 0 53 Extract air filter dirty pes 1 0 54 Service period past alarm limit Be 1 0 55 No comm SA air flow pressure sensor At 1 1 56 No comm EA air flow pressure sensor A ane 1 1 57 No comm SA filter pressure sensor B 1 0 58 No comm EA filter pressure sensor Ber 1 0 59 No comm SA duct pressure sensor A 1 1 60 No comm EA duct pressure sensor aa 1 1 61 No comm r hx pressure sensor Birex 1 0 62 No communication to O module No 0 Bee 1 0 63 No communication to O module No 1 pov 1 0 64 No communication to O module No 2 pex 1 0 65 No communication to O module No 3 Barx 1 0 66 No communication to l O module No 4 Beare 1 0 67 No communication to O module No 5 Bey 1 0 68 No communication to O module No 6 pr 1 0 69 No communication to O module No 7 pce 1 0 70 No communication to O module No 8 Be 1 0 71 No communication to O module No 9 B 1 0 72 No communication to main controller I O A 1 1 83 Supply air prefilter fouled B 1 0 84 Exhaust air prefilter fouled B 1 0 85 Cooling Output 1 tripped A 1 0 86 Cooling Output 2 tripped A 1 0 89 No comm with press sensor by SA prefilter B 1 0 90 No comm with press sen
103. vices are correctly adjusted to provide the comfort expected When adjusting air devices and the duct system installed in combination with the GOLD it is appropriate to follow the proportionality method This means that the proportion between the airflows in branch ducts stays constant even if the airflow in the main ducts is changed The same proportion applies to the air devices in the installation When adjusting the ducting system there is provision for locking the speed of the fans in the unit to a specific pre set flow rate see Section 6 5 4 2 1 Adjustment Sequence The system should be adjusted in the following order 1 Adjust of the air devices in each branch duct 2 Adjust the branch ducts 3 Adjust the main ducts 4 2 2 Adjustment Procedure 1 Set all the air devices and dampers to the fully open position 2 Calculate the ratio of the airflow reading to the design airflow of all the air devices branch ducts and main ducts The air device in every branch that has the lowest ratio should be fully open Use this air device as an INDEX AIR DEVICE The same applies to branch dampers and main dampers Example on how to carry out adjustments Start adjusting duct branch B since this one has the highest ratio The last air device B3 has the lowest ratio and should be fully open Adjust the other air devices B1 and B2 so that these will have the same ratio as air device B3 see item 5 above
104. vironmental Documentation Environmental Documentation with the Dismantling Instructions for Recycling and the Environmental Product Declaration can be downloaded from our website www Swegon com The air handling unit is designed in such a way that it can be dismantled into its natural parts for scrapping When the unit has ended its useful product life the services of an accredited recycling company should be utilised for disposal Approximately 9496 of the parts in COMPACT air handling units are recyclable Swegon AB is associated with the REPA Register No 5560778465 Contact Swegon AB Phone 46 0 512 322 00 if you have any questions regarding the dismantling instructions or the air handling unit s impact on the environment www swegon com 3 Swegon 1 5 The Components of the Air Handling Units 1 5 1 COMPACT Unit GB COMPACTUT 101208 The individual components each specified below in a simplified and diagrammatical description Fig 1a gt gt Outdoor air Extract air Exhaust air Supply air The air handling units are supplied in the right hand ver sion as shown in Fig 1a Coversion to the left hand version as shown in Fig can be carried out via a simple adjustment in the control equip ment See 3 4 1 2 The air handling unit can be installed vertically See 3 4 1 1 In the left hand version Fig 1b the components marked with an asterisk change function and designation the components a
105. yearly time schedules can be set The year channels over modulate the time channel during the hours of the day and the days that the year channel is active The year channel dates indicate the dates between which the year chan nel shall apply and the year channel hours indicate the hours of the day between which the year channel will steer the controller to operate the rotary heat exchanger at a specified speed Other times within the year channel still apply to that time channel The time can be set as 00 00 00 00 if the deviating in operation period is desirable for the entire 24 hours period Functions for summer night cooling prolonged operation etc operate also when the year channel is active 7 4 Filters and anti frosting function of rotary heat exchanger There are two types of filter monitoring Calculated filter monitoring preset at factory monitors the fan s speed increase conditional on the degree of fouling in the filter The calibration involves taking airflow and fan speed readings An alarm is initiated when the fan speed has increased by 1096 above the preset alarm limit Filter monitoring with a pressure sensor accessory measures the pressure drop across the filter The alarm limit is preset in Pa 7 4 1 Readings When reading the filter status the first value shows current value and the second value shows current alarm limit 7 4 2 Calibration Filters The filters should be calibrated for the first time in
Download Pdf Manuals
Related Search
Related Contents
Philips 6000 series Electric shaver HQ6950 取扱説明書 mode d`emploi User`s manual Sinus 200 Bedienungsanleitung Vapo Rapido - Migros TrailLite Mini 印刷用cs2_ol Saint-Lys et Vous n°17 TCP/IP に係る既知の脆弱性検証ツールの開発 Dell 1N016 Personal Computer User Manual Copyright © All rights reserved.
Failed to retrieve file