Home
GST-FT8WN Fire Telephone Panel Installation and Operation Manual
Contents
1. Call LED 1 8 Red indicating the conversation status between panel and corresponding Zone gt Flashing in the process of connection gt On under conversation gt Off no conversation Ring In LED Red fast flash when there is call in from network or zone Fault LED 1 8 Yellow lit on when corresponding zone in Fault condition Network Fault LED Yellow lit on when there is network fault Page 3 DU GST FTSWN IP Fire Telephone Panel The Intelligent Solution Power LED Green lit based on usual power supply Mute Red lit when panel sound alarm silenced Green lit when panel receiving network data Red lit when panel sending network data Rev and Trans LED located at the back of the door Description On the main panel the first digit indicates the quantity of panels in the network the last digit indicates Network Free its network address On sub panel only the last digit will show its network address r The first digit indicates the address Network Call 7 7b of the calling panel The C at the last digit means Calling The sample at the left shows the Network HE E l l conversation state between No 1 Conversation panel and No 2 panel The others will show BUSY The first digit indicates the address of failed panel The E means Error Network Failure 4 Fire Telephone System Design 4 1 Stand Alone Fire Telephone Syst
2. 5 1 shows the mounting holes of the panel gt Hole distance in the vertical direction 318mm gt Hole distance in the horizontal direction 218 mm gt Diameter of the hole 12mm 5 4 Terminals on the panel Power 24 GND 24VDC power in polarized E GND Network Network polari zed ae NER HP Hl Ge Hl Ge 7 ON 24 GND o OFF Network E Power Power Z1 Zl Z2 Z2 Z3 Z3 Z4 Z4 25 Z5 Z6 Z6 Z7 Z7 Z8 Z8 dd i sjeje e Fig 5 2 Zn Zn Zone Terminals connecting with handsets a 10KQ 0 5KQ resistor is required to the last point of each zone Page 6 Soop GST FTSWN Teme IP Fire Telephone Panel The Intelligent Solution 5 5 System Commissioning Please Make Sure the Correct Wiring before Commissioning Set panel address gt For standalone fire telephone system the address can be assigned 1 or keep the default setting gt There must be one panel assigned 1 in the network fire telephone system gt Opening the door of the panel the red PIN switch in the left corner is using for panel address setting The addresses range is from 1 to 8 Please refer to Fig 5 3 i y Ber 1 or E rw BD ON 1 om om ory m BB co WE RR Fig 5 3 Note Th
3. IP Fire Telephone Panel The Intelligent Solution 7 Troubleshooting 7 1 Zone Fault The zone fault shows an open or short circuit between panel and handsets or the End of Line Resistor not connected Check the cable by multi meter whether the resistance is roughly 10kQ 7 2 Network Fault The panel shows network fault when there is any of the panels powered off or network cable fault Check the malfunction panel and wiring Page 9 GST China Gulf Security Technology Co Ltd No 80 Changjiang East Road QETDZ Qinhuangdao Hebei P R China 066004 Tel 86 0 335 8502528 Fax 86 0 335 8508942 Email sales gst com cn www gst com cn GST UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email _info gst uk com www gst uk com GST Dubai Global System Technology PLC PO Box 17998 Unit ZA04 JEBEL ALI Free Zone Dubai UAE Tel 971 0 4 8833050 Fax 971 0 4 8833053 Email _info gst uk com www gst uk com
4. 3 CALL TELEPHONE PANELS IN NETWORK 0cceccecescescesceces 6 4 PET ML 7 TROUBLESHOOTING 2 cccccccccccccccccccccccccccccccccccccccccccees 7 1 MIE Lae nee me oe ee ne eee ee en 7 2 NETWORK FAULT ccceccsceccececcececcscscescecescscecescucescecescsecs Page Il 0 22 DD GS 3 The Intelligent Solution DU GST FTSWN IP Fire Telephone Panel The Intelligent Solution 1 General GST FT8WN fire telephone panel is specialized for emergency communication builds up convenient and prompt 2 way communication in case of fire and other abnormal conditions It is an indispensable device in fire protection system The panel has features as below Easy wall mount installation 24VDC power supply Receiving and calling out with fire telephone handsets Networkable fire telephone panels achieve internal communication gt gt Call from handset will be transferred to networked fire telephone panels automatically after not answered by the dedicated panel The handset zones are fully monitored for fault of short circuit and open circuit Panel will show the fault by sound and indicator lt gt Failure of one zone will not effect on other zones lt The network communication is monitored When sub panel fails to communicate with the main panel the main panel will get the failure message and broadcast to other networked sub panels both main panel and sub panels will indicate by sound and light ind
5. GST FT8WN Fire Telephone Panel Installation and Operation Manual GST FT8WN Fire Telephone Panel CONTENTS 1 GENER Nedenes 2 TECHNICAL SPECIFICATIONS ccccccccccccccccccccces 3 PANEL INSTRUCTION j cccccccccccccccccccccccccccccccccccsccees 3 1 APPEARANCE AND STRUCTURE cccccsceccsceccececcececescecescececs is ae TPE Ths RES Boal SU Gs Chena ne ace ee rae er 3 3 TN 3 4 DIT 3 5 DIGITRON DISPLAY cccececcsceccsceccccececcscescscecescucescecescececs 4 FIRE TELEPHONE SYSTEM DESIGN ccccccscceeee 4 1 STAND ALONE FIRE TELEPHONE SYSTEM cescecceceecesceccecs 42 NETWORKED FIRE TELEPHONE SYSTEM ececeececececeeceeecs 5 MOUNTING amp COMMISSION sccccccccccscccccccccccccccccees 5 1 SE EN AG E 5 2 WIRING REQUIREMENT ccccsccsscsscsscssccsccssesscsscsscescescessens 53 MOUNTING HOLESG csccscescescecceccscescsceccscescesceccscescescesens 5 4 TERMINALS ON THE PANEL ececcececceceecececcececcecucescucescecess 5 5 SYSTEM COMMISSIONING scecsosioudsccceovecsdvecediceveoseccdaeoseaceasexecs Set panel 0210 0 EEE Register the Network Panels rrrrrrrrrrnnnnvrrvrrnrnnnrrrrrrnnnvrnnrnr Test FUNCTIONS 00 cccccccccccccccccccccccccccccccuccccucsccasccusccesesccuccceuaess 6 USER GUIDE Lise 6 1 CALL HANDSET eiccccventsioacivsantseitnatdansinmantacinaselanawbentited docatencivants 6 2 CALL TELEPHONE PANE asii 6
6. e panel addresses can not be repeated in same network Register the Network Panels After assigning the addresses power on the sub panels first Press and hold the Network Call button on the main panel and power on The main panel will register all networked sub panels automatically Subsequently the first digit of the digitron will show the number of networked panels including the main panel Check whether all panels have been registered according to the shown number If no consistency check the wiring and repeat the above mentioned process The registration information is saved in non volatile memory will not loss on power off The registration should be carried out again in case adding or removing network panels Not necessary for registration on sub panel Test Functions Test the other functions according to Operation Manual after commissioning Page 7 Soop GST FTSWN Teme IP Fire Telephone Panel The Intelligent Solution 6 User Guide 6 1 Panel Call Handset Press a key of zone 1 to 8 the corresponded zone will be called with Cal LED slow flashing The conversation will be set when handset picked up with Call LED lit showing status During the conversation press the key again will stop the call The call LED won t go out until hanging up the handset If the handset is hung up first the conversation will stop immediately with Call goes out The panel can make call to handsets in other zones
7. em Fig 4 1 shows a standalone fire telephone system The panel can connect maximum 8 zones with each zone maximum 5 handsets Zone 1 Handset Telephone Panel Zone 8 Handset Fig 4 1 Page 4 Soop GST FTSWN IP Fire Telephone Panel The Intelligent Solution 4 2 Networked Fire Telephone System The system consists of a group of panels as many as 8 The panel with the address 1 is the main panel and the rests are sub panels Please refer to commission section for setting up addresses Handset Telephone Panel Main Address 1 5 Handset Handset e Telephone Panel Slave j e Address 4 Handset Handset Telephone Panel Slave e Address 8 Handset Fig 4 2 5 Mounting amp Commission 5 1 Initial Check Check the appearance of the panel after open the box Then power on and check working state 5 2 Wiring Requirement Cross section area of the power cable not less than 1 5mm Twisted pair cable connecting panel and handset with SA not less than 1 0 mm Twisted pair cable for the network with SA not less than 1 0 mm2 VV v V The cable selection must comply with local code Page 5 GST FT8WN Fire Telephone Panel The Intelligent Solution Note the impedance of single line not more than 200 5 3 Mounting Holes Fig 5 1 Fig
8. ication When the fault happens on main panel all sub panels will show the fault message and meanwhile the network call will be inhibited 2 Technical Specifications Page 1 Soy GST FTSWN IP Fire Telephone Panel The Intelligent Solution Notes words using within this file Fire Telephone Panel Panel Installed in fire control center the device can communicate with field terminals such as GST FT8WN Handset Field device which can communicate with fire control center such as P 9911 F and P 9911 M Main panel The No 1 panel in the fire telephone panel network Sub panel Panels other than No 1 in the fire telephone panel network 3 Panel Instruction 3 1 Appearance and Structure GST FT8WN fire telephone panel is wall mount type the appearance is shown in Fig 3 1 OSTFT AN FIRE TELEPHONE PANEL 400 100 Page 2 Ss GST FTSWN Bre IP Fire Telephone Panel The Intelligent Solution 3 2 The front surface TATT Power Ring In Network N py Fault OFault Fault Fault Fault p we PG Lo fo EE we Pa f N S N F N i f N a 7 N NG ae Jf ay eo ee Vg y tE pa j a N F t rau rau w rau v rau M ae Network Fig 3 2 3 3 The Keys Stop the alarm sound caused by fault Network Call Answer or start network call Answer call or hang up the corresponding zone 3 4 Indicators indicator Description
9. when a conversation is underway 6 2 Handset Call Panel Once the handset is picked up without being called the call will go to the panel The panel will ring with Call and Ring In LED fast flashing Press the relative key and enter into conversation with Call being on Ring In goes out Meanwhile if there are other zones calling panel Ring In will keep fast flashing Hang up the handset or press the relative key on the panel will stop the conversation 6 3 Call Panels in Network If the handset call is not answered by the panel within 12s and the network is available the call will be transferred to other networked panels Press Network Call and start the conversation Stop the conversation by handset hanging up or Network Call repressed 6 4 Panel to Panel Call When network is available press Network Call will send the call to entire network with the LED indicator fast flashing Meanwhile the digitron on other networked panels will show by flashing X GC X The calling panel the Ring In and Network Call LED will fast flash with ringing sound Press Network Call button and then start the conversation The digitron of the panels not attending conversation will show BUSY and the ring tone stops Panel in conversation will show the address of the other one Either part can stop the conversation by pressing Network Call Page 8 Soy GST FTSWN