Home
Hydro Unit
Contents
1. During the hot water supply or heating operation without reaching the set temperature the compressor operation frequency stays at a frequency of less than the maximum Hz or lowers down The Stop operation on the remote control will not stop the circulating pump The same for hot water supply heating and cooling on the remote control will not operate the compressor It will not operate even after the reboot delay timer elapsed When the power is turned it starts operation without on operating the remote control The compressor does not operate during the operation of the compressor reboot timer 3 min Even after the power activation the compressor reboot timer continues to be active It may be caused by the high temperature release control release protection control by the temperature of the water heat exchanger or the current release control In order to deal with the temperature increase in the heat exchanger after stopping the operation continues for 1 min after the compressor is stopped When the outdoor temperature TO sensor detection temperature is 20 C or lower the heat pump will not operate in order to protect the compressor and the heater will operate instead The auto restart operation may be working The antifreeze operation may be working If the TWI TWO or THO sensor detects a temperature below 4 C the operation changes from circulating pump gt gt circulating
2. C TEMP C Y buttons for four seconds or more to enter the remote controller function code setting mode 2 Set the function code number with the TEMP buttons Cv Gam CODE No 01 to 13 3 Set data with the TIME buttons 7 5 l 4 Press J to determine the settings CL 5 Note that the Clear button C is enabled only before the SET button is pressed and the function code is changed 6 Press 4 to exit the settings menu 25 Hydro Unit Quick Reference Guide Main setting items refer to Function code setting table shown below descriptions 1 Setting Hot Water Temperature Range function codes 18 to 1F e Set the temperature range for heating zone 1 zone 2 cooling and hot water The upper limit and lower limit temperatures of each mode can be set 2 Setting Heat Pump Operation Conditions for Hot Water Supply function codes 20 and 21 Set the heat pump start water temperature and heat pump stop water temperature e The heat pump starts working when the water temperature lowers below the set start water temperature It is recommended that the default value be used 3 Compensating Hot Water Temperature function codes 24 and 25 Compensate the target temperature from the remote controller set temperature when the hot water temperature lowers below the set outside air temperature 4 Setting Hot Water Boost function codes 08 and 09 e Set the co
3. lomp senec Floor heating ffer tank unit 2 zone heating with domestic hot water and boiler backup 1 zone Conventional Boiler Panel radiator Ie Hydro unit Sutdoor unit 1 zone heating with boiler backup The water circuit for a system without a buffer tank 1 2 3 5 requires 17 803XWH 13 0l min or more This water flowing requires 5 or more branches of Floor heating or Radiators etc Less than 5 branches may cause a flow deficiency In this case please provide a buffer tank and secondary pumps as shown in 4 Please check how to install the boiler Hydro Unit Quick Reference Guide Hydro Unit Exploded View CO gt Expansion vessel Hi Pressure switch 4 15 MPa Temperature sensor for Heat pump outlet TWO Pressure sensor Heat exchanger Flow switch 13 0 L min 17 5 L min Temperature sensor for refrigerant TC Temperature sensor for water inlet TWI Drain nipple Water inlet connection Refrigerant liquid connection Air relief valve Pressure relief valve 0 3 MPa 3 bar Thermal protector auto Temperature sensor for water outlet THO Thermal protector Single operation Water pump Backup heater 3 kW 3 kW x 2 3 kW x 3 Manometer Water outlet connection Refrigerant gas connection Hydro Unit Quick Reference Guide Refrigerant Pipe Length
4. Hydro Unit Installation Examples cont Quick Reference Guide 2 Zone Temperature Control with Domestic Hot Water The following shows an example of the 2 zone temperature control A buffer tank and a water pump are required for the 2 zone temperature control This example is Heating only if the Fan Coils are to be used for Cooling then a 2 Way valve must be fitted ee Ternperature Regulating Valve Mechanical Hi Pressure Zone 1 Diverbng Fan Coil Unit Heating Way or Cooling Motorized 2 Way Valve is required if fan coil units are in cooling operation Direct Buffer tank for Zone 2 Under Floor Heating Under floor Heating 2 Way Valve Control Hydro Unit Installation example of water circuit zone Hydro unit Floor heating Outdoor unit 1 zone heating 2 zones Panel radiato Shower Bath Kitchen Temp senso heating Cusdoeor unit 2 zone heating with domestic hot water 1 zone HEATIMG ONLY 2 way valve Parelradiate Shower Bath Kite hen racilator 3 Hot EE ater H EATING I Cutdcer unit 1 zone heating cooling with domestic hot water Quick Reference Guide 2 zone Shower Bath Kitchen Hot water tank heating utok unit 1 zone heating with domestic hot water 2 zones Paneglradiatot Conventional boiler Shower Bath
5. the discharge temperature sensor TD and the suction temperature sensor TS 1 Check the operation of the 4 way valve unit or the coil characteristics 2 Defect of the pulse motor 3 Check the resistance value of the heat exchange temperature sensor TE and the suction temperature sensor TS Hydro Unit Check code P20 P22 P26 P29 Operational cause High pressure protection operation When an abnormal stop occurs due to the high pressure release control When the heat exchange temperature sensor TL detects 63 C during the cooling operation When the water outlet sensor TWO detects 60 C during the heating or hot water supply operation Outdoor fan system error When a DC fan rotor position detection NG element short circuit loss of synchronization or abnormal motor current occurs Short circuit of the compressor driver element error When an abnormal short circuit of IGBT is detected Compressor rotor position error The rotor position in the compressor cannot be detected Diagnostic functional operation Backup present Remote controller check codes Diagnostic functional operation Check code displaying at operate by Operational cause Status of air conditionin Ho communication between hydro Stop Not unit an remote controller The remote contro wiring is not connected correctly The hydro unit has not been turned on all cannot the remate
6. the external booster heater This must be connected through the contacts on the field supplied contactor Hydro Unit Electrical connection for external additional pumps NCAUTION The maximum current available from the additional pump output is 1 A Do not connect the additional pump directly to Terminal Block 05 on the Hydro Unit A separate contactor supplied locally must be used to supply the additional pump e The Hydro Unit has the facility to connect an additional circulating pump if required into the heating or cooling system Install the pump so that its motive power does not affect the internal pump e The AC230 V 1 A output from the Hydro Unit must only be used to energize an external contactor supplied locally he output for the pump is synchronized with the operation of the main circulating pump P1 inside the Hydro Unit Ensure the pump is installed and set up in accordance with all Local National and International regulations Connect the additional pump P2 as shown in the diagram opposite The contactor will energize synchronously with operation of the main circulation pump P1 A separate dedicated electrical supply must be used for the pump This must be connected through the contacts on the field supplied contactor Hydro Unit 18 Hydro Unit Quick Reference Guide 3 way valve diverter connection Required Valve Specification Electrical Specification 230 V 50
7. 10 0 10 Outdoor Temperature The entire curve can be adjusted plus and minus 5 C by function code 27 8 Setting Frost Protection Temperature function codes 3A and 3B Remote controller 12 and 13 e Set the function when the FROST PROTECTION 4S button on the remote controller is pressed e Set enabling disabling of this function and the target water temperature FC3A and FC3B Set schedule end day and end time remote controller Fc12 and 13 If disabling is set the frost protection operation is not performed even when the FROST PROTECTION button is pressed 9 Setting Frequency of Output to Internal Backup Heater function codes 33 and 34 The increase decrease time is used to set the response time 10 Setting Night Setback function codes 26 Remote controller OF to 11 e Set the function when the NIGHT button on the remote controller is pressed Set enabling disabling of this function reduction temperature start time and end time If disabling is set the night setback operation is not performed even when the NIGHT button is pressed 26 Hydro Unit Quick Reference Guide Main setting item cont 11 Setting second remote controller room temperature measurement function codes 40 92 93 94 95 96 9D and remote control function codes 02 and 03 When system control is required using room air temperature make these settings to enable this function Enable the ro
8. 3 OPEN system stop System restart with remote controller 2 Contacts high gt low terminals 1 3 OPEN system stop Contacts low gt high terminals 1 3 CLOSE system restart 3 Contacts low gt high terminals 1 3 CLOSE E Stop Switch Logic system stop Contacts low gt high terminals 1 System Restart amp 3 CLOSE second time system restart TEMPO Control PULSE INPUT System Restart Logic TEMPO Control 0 System restarts in heating and hot water mode 1 System restarts in the last mode prior to stopping 2 System restarts in heating mode 3 System restarts in hot water mode 4 TEMPO Control 1 All electric heaters disabled 5 TEMPO Control 2 HP and all electric heaters disabled 0012 803XWH E Hydro Unit Capacity 0017 1403XWH E Setting Factory set but function code is needed for PCB replacement Allows A02 Error Detection to be Activated Deactivated When Boiler Output Is Enabled 0 A02 activated then boiler output OFF 1 A02 deactivated and boiler output stays ON Output Signal Setting with Optional PCB Connected to CN209 0 EMG terminals output On during defrost OPERATION terminals output ON when compressor is running 1 EMG terminals output ON when error detected OPERATION terminals output ON during operation remote controller ON Depends on Hydro Unit A02 Error Detection With Boiler Output Enabled Output Signal Setting Settings by Purpose Settings when hot water
9. Control parts specifications Default 2 wire spring return valve or 3 wire SPST valve Note 3 wire SPDT valve can be used by changing DIP switch valve AC 230 V 100 mA spring return type normally open Default Drive time 60sec to 90 Motorized mixing valve AC 230 V 100 mA Note 3 wire SPST or SPDT valves with drive times between for 2 zone T 30 240 seconds be used Valve drive time can be changed using function code 0 Motorized 3 way valve m P for hot water AC 230 V 100 mA Output line specifications rini Maximum Max Maximum TP w Output as required when outdoor air External boost heater AC230V 12m temperature is 20 C or less Output as required when outdoor air Non voltage temperature is 10 C or less The Boiler control eontacis g outdoor air temperature when the 1 DC24 V 12m boiler output is enabled can be changed using function code 23 ALARM Output nde ux c Compressor operation Non voltage AC230 V DC24 V noe 0 5 A AC230 V Defrost Output o Input line specifications Emergency stop control Non voltage Cylinder thermostat input Non voltage Cooling thermostat input Non voltage Heating thermostat input Non voltage 16 Hydro Unit Quick Reference Guide NCAUTION Earthing arrangements The Hydro Unit and related equipment must be earthed in accordance with your local and national electrical regulations It is essential
10. HWS 1403XWHMG E T6 E 06 T9 E Hydraulic heat exchanger 14kW QH characteristics Minimum flow rate Pump head m Out of 230V DN 19 45 50 55 60 65 Tow dita Hydro Unit Quick Reference Guide Water charging Charge water until the pressure gauge shows 0 2 MPa 2 bar Hydraulic pressure may drop when the trial run begins In that case add water Air may enter if the charged hydraulic pressure is low Loosen 2 turns for proper venting Loosen the Air relief valve cap by two turns to release air see diagram Loosen the cap of the pressure relief valve to release air Water may come out of the pressure relief valve Release the air completely from the water circuit Failure to do so may disable correct operation Water quality The water used must satisfy EN directive 98 83 EC Piping insulation It is recommended that insulation treatment be applied to all pipes To perform optional cooling operation apply insulation treatment of 20 t or more to all pipes 12 Hydro Unit Quick Reference Guide Electrical Connections E Box layout P C board 1511 Relay P C board MCC 1217 Option MG SW RY04 MG SW RY02 Relay P C board MCC 1217 Option F1 F2 F3 F4 F5 F6 F7 F8 g jee na ne Relay board E MCC 1431 Ee aa Relay P C board makanan MCC 1214 Option Power Lines Schematic Backup h
11. Hz 100 mA Valve Diameters Port A Port B 1 1 4 Return Mechanism 3 types of 3 way valve diverter can be used Set the 3 way valve in use with the DIP switch SW13 1 on the Hydro Unit board Diverter Valve Description SW13 31 Type 1 2 wire spring return Type 2 3 wire SPST Type 3 3 wire SPDT NOTE Continuous operation of the valve motor at the fully open position is not recommended e The 3 way diverter valve is used to select either domestic hot water or zone1 zone2 Connect the 3 way diverter valve in accordance with the diagram below Type 1 SPRING RETURN Type 2 SPST port A to Hot water port to Hot water cylinder I hole le cylinder je port AB to Hydro unit port AB to Hydro unit port B to Room heating port B to Room heating or cooling or cooling Type 3 SPDT port A to Hot water Hydro Unit port AB to Hydro unit a port B to Room heating or cooling 19 Hydro Unit Quick Reference Guide 3 way mixing valve connection Required Actuator Specification Electrical Specification 230 V 50 Hz 100 mA The 3 way mixing valve is used to achieve the temperature differential needed in a 2 zone heating system Connect the 3 way mixing valve in accordance with the diagrams below Type 1 SPDT Type 2 SPST port A to Zone 2 Heating port A to Zone 2 Heating r Hydro Unt TB 04 Hydro Unit port AB to
12. ZONE1 2 button and select heating with the OPERATE MODE button The pump is activated in 30 seconds If air is not released completely the flow switch is activated to stop operation Release air again according to the piping procedure Little air bite is discharged from the purge valve Check that the air bite sound disappears Check that the hydraulic pressure has become the predetermined pressure 0 1 to 0 2 MPa 1 to 2 bar If the hydraulic pressure is insufficient replenish water Heating operation starts Check that the hydro unit starts heating Press the OPERATE MODE button and select cooling Cooling operation starts Check that the hydro unit starts cooling and that the floor heating system is not cooled ZONE 1 2 e Press the ZONE1 2 button to stop operation HOT WATER Press the HOT WATER button to start hot water supply operation Check that there is no air bite Check that hot water is present at the connection port of the hot water cylinder HOT WATER Press the HOT WATER button to stop the hot water supply operation Press the TEST 4 button to exit the test mode 31 Hydro Unit Quick Reference Guide Sensor Temperature Monitoring Function The sensor sensing temperature is displayed on the remote controller This function allows you to make sure whether the sensor is installed properly CL 2 1 Press OF C buttons for four seconds or more lt lt 2 Sel
13. control Ho communication between hydro unit and remote controller Disconnection of the crossover between the remate control and the base unit af the indoor unit detected on the remote control side Defect in the signal transmission to the hydro unit Detected on the remote contro side Several remote control base units Detected on the remote contra side Stop Automatic reset Stop Automatic reset Stop The handset continues 38 Automatic reset Quick Reference Guide Defect frequency confirmation Determination and action 1 Check that the service valve is fully open 2 Defect of the pulse motor valve 3 Check the outdoor fan system including clogging 4 Over filling of refrigerant 5 Check the resistance value of the heat exchange temperature sensor TL and the water outlet temperature sensor TWO 10 1 Check the lock status of the motor fan 2 Check the connection of the fan motor cable connector 1 4 3 Check the power supply voltage AC230 V 23 V 1 P26 abnormality occurs when operating with the compressor wiring disconnected Check the control board 2 No abnormality occurs when operating with the compressor wiring disconnected Compressor rare short 1 Even if the connection lead wire of the compressor is disconnected it stops due to an abnormality in the position detection Replace the inverter control board 2 Check
14. sensor error When TWO TFI gt 30K is detected and TFI TWI 5K is detected Low pressure sensor error When 5 lt 0 07 MPa is detected for 90 sec or more cooling defrosting When PS 0 07 MPa is detected for 10 minutes or more hot water supply heating Backup present Heating x Cooling x Hot water O UJ uA Automatic Determination and action reset 1 No water heating without water or no water flow 2 Defect of the flow switch 3 Defect of the backup heater poor automatic reset thermostat 1 Almost no water flow 2 Defect of the flow switch 3 Check the water outlet temperature sensor TWO 1 Activated by a large load of heating or hot water supply 2 Check the heater power circuit backup or hot water cylinder heater Power supply voltage breaker power supply connection 1 Check remote control connection 2 Defect in the remote control 1 Check the serial circuit Miswiring of the crossover between the water heat exchanger and the outdoor unit 1 Check the resistance value and connection of the heat exchange temperature sensor TC 1 Check the resistance value and 1 Check the resistance value and connection of the water outlet temperature sensor TWO 1 Check the resistance value and connection of the hot water cylinder sensor TTW 1 Check the resistance value and connection of the floor inlet temperature sensor TFI 1 Check the r
15. that the equipment is earthed to prevent the electric shock and damage to the equipment Electrical connection to hydro unit e Remove the front cover and the electrical box cover from the Hydro Unit e The Hydro Unit power cable must be sized in accordance with refer to Electrical supply cable specifications Connect the Hydro Unit power cable to Terminal 02 as shown below Single Phase Units Live conductor Terminal L1 Neutral conductor Terminal L2 Earth conductor Earth terminal Three Phase Units Phase 1 conductor Terminal L1 Phase 2 conductor Terminal L2 Phase 3 conductor Terminal L3 Neutral conductor Terminal N Earth conductor Earth Ensure the Hydro Unit power cable is secured using the cable clamp fitted in the electrical box Ensure the Hydro Unit power cable connection terminals are tight Outdoor unit to hydro unit electrical connection HWS 803H E HWS 1103H E Outdoor unit HWS 1403H E Hydro unit Input power 220 230V 50Hz Leakage breaker HWS 1103H8 E H8R E Outdoor unit Hydro unit HWS 1403H8 E H8R E HWS 1603H8 E H8R E Input power 380 400V 3N 50Hz Leakage breaker Ensure electrical circuits are isolated before commencing work e The Outdoor Unit to Hydro Unit interconnecting cable must be sized in accordance with refer to Electrical supply cable specifications Connect the Outdoor Unit to Hydro Unit interconnecting cable as shown in the diagram abo
16. 1 Draft 22 10 10 TOSHIBA FILE NO A10 002P Leading Innovation gt gt gt uick Reference AIR TO WATER HEAT PUMP z ESTIA E TUBHIER sann Lucr WWW e pe z Hydro Unit Estia System Quick Reference Guide Hot Water Heating or Cooling K DN See f Radiator ESTIA JE B E N u E 3 TE Fan coil unit Heating or Cooling 7 am Outdoor unit N z Hydro unit Hot water Under floor heating cylinder Zone Control Estia Outdoor Unit HWS 803H E TR HWS 1103H E TR HWS 1403H E TR HWS 1103H8 E HWS 1403H8 E HWS 1603H8 E HWS 1103H8R E HWS 1403H8R E HWS 1603H8R E Estia Hydro Unit HWS 803XWHM3 E TR HWS 803XWHT6 E TR HWS 803XWHD6 E HWS 803XWHT9 E HWS 1403XWHM3 E TR HWS 1403XWHT6 E TR HWS 1403XWHD6 E HWS 1402XWHT9 E TR 8 0kW Inverter single phase 11 2kW Inverter single phase 14 0kW Inverter single phase 11 2kW Inverter three phase 14 0kW Inverter three phase 16 0kW inverter three phase 11 2kW Inverter three phase with heater cord 14 0kW Inverter three phase with heater cord 16 0kW Inverter three phase with heater cord Plate Heat exchanger and 3kW Backup Heater Plate Heat exchanger and 6kW Backup Heater Plate Heat exchanger and 6kW Backup Heater Plate Heat exchanger and 9kW Backup Heater Plate Heat exchanger and 3kW Backup Heater Plate Heat exchang
17. STEP 8 TEST button 2 9 FROST PROTECTION button NOTE E TEMP TIME w A SET CL Changes the set temperature for each operation mode ZONE1 ZONE2 HOT WATER by 1 step Sets the current time and scheduled weekly operation Changes time for current time setting and scheduled weekly operation setting with Y and A buttons Determines the entered current time setting and scheduled weekly operation setting Clears settings for the current time and scheduled weekly operation Sets days of the week for current time setting and scheduled weekly operation setting Specifies switching STEP number in a day for weekly schedule Used for test run or service Controls minimum operation for unused period going out absence etc for anti freezing ZONE 1 2 10 NIGHT button 11 AUTO TEMP button 12 OPERATE MODE button 13 ZONE1 2 button ZONE 1 2 14 ANTI BACTERIA button 15 HOT WATER BOOST button 16 HOT WATER button Hor waren 17 SELECT button lt DP Quick Reference Guide Controls the night set back operation Switches setting temperature automatically according to outside temperature Pressing this button long changes the mode to data setting mode Selects ZONE1 ZONE2 operation mode heating or cooling Turns on off the zone floor heating radiator FCU operation Regularly increases the hot water tempera
18. Thermostat for compressor activated e 9 e 9 C 14 Model data not set on the service P C board e 9 e o e 15 MCUMCU communication eror J e 9 e 41 410940 16 Discharge temperatureeror Je 9 9e e 140 2 abnormal voltage _18 Heatsinkoverheat o 9 e e o e e ie Te _19 refrigerantleakdetected 5 o J e 2 44 _20 awayvaivereverseeror 9 5 _ 21 High pressure release operation o 9 e e 2 22 Qutoorfanmotoremr o 9 e o e 23 Compressor driver short circuit protection o 9 9 e o L 90 Ea o RES et FLASHING N 39 Quick Reference Guide Hydro Unit 40 Hydro Unit Quick Reference Guide TOSHIBA Leading Innovation gt gt gt 42
19. ction Geode Address FO FO Function Code Setting Range Setting Temperature C Start Cycle Day Start Time Hour Operation Time min Outside Temperature T1 C Outside Temperature T2 C Outside Temperature T3 C Setting Temperature OAT 20 7 Heating Auto Curve Setting Temperature B T1 Settings Setting Temperature C OAT T2 Setting Temperature D OAT T3 C Setting Temperature E Q OAT 20 C Ratio Of Zone 2 In Zone 1 Auto Mode 96 Auto Curve Temperature Shift C Function O Invalid 1 2 Valid 0 1 Frost Protection Setting Temperature 10 20 Frost Protection Schedule End Day 0 20 Frost Protection Schedule End Time 0 23 Downtime Back Up Heater 0 5min b Anti Bacteria C C 8 Frost Protection 9 Back Up Heater 1 10min 2 15min 3 20min i d Control Uptime Back Up Heater 0 10 1 20 2 30min 3 40min Change Setback Temperature 26 5 10 Night Setback Zone selection O Zone 1 amp 2 1 Zone 1 Only 58 1 i etbac 9 Start Time Hour OE 22 End Time Hour OF 06 Room Temperature Control 0 Invalid 1 valid i n Setting Room Temperature Range m 92 _ 15 30 29 Cooling room temperature upper limit C setting Room Temperature Range A 93 _ 15 30 18 Cooling room temperature lower limit C setting Room Temperature Range _ 04 _ 15 30 29 Heating room temperature upper limit C S
20. eater Backup heater Backup heater 220 230V type 380 400V 3N 220 230V 3 3kW type type type 6 9kW type 6kW type Input power Input power 220 230V 220 230V 3N 50Hz 50Hz Input power 220 230V 3 Leakage breaker 30 Outdoor unit Hydro unit 13 Hydro Unit Quick Reference Guide Control Lines Schematic ws 7 Mixing Valve Mixing Valve type 1 type 2for 2 Zone for 2 zone control control Max 12 m 230 V 100 mA Temp sensor in hot I 0 75 mm or more I water cylinder Pump local TBO4 5 0 75 mm or more A T m n X Kw gt Max 12m EI 230V 1A 0 75 mm or more KR AY 2 GE ec I JT a 2Way Valve for 12m cooling stop 230 V 100 mA i 0 75 mm or more e _ bP 4 _ 5 m shielded wire 0 75 mm or a Ty more Booster heater Ul wd ape en Se local Max 12 m i 230V 1A 0 75 mm or more Max 50 shielded wire 0 75 mm or more EIER 3Way Valve for hot 010101010101910 mnm MOO water cylinder Max 12 m non i voltage 0 75 mm or m x MMC reu Alert output Boiler operation Defrost output Compressor local local local operation output local Terminal Block Connection
21. eating for 10 consecutive min The 4 way valve inversion error When the heat exchange temperature sensor TE exceeds 30 C or the suction temperature sensor TS exceeds 50 during the heat pump operation Operational cause Backup Automatic present reset ae H03 Defect in the current detection circuit x 1 Replace the outdoor inverter control board HH 37 Quick Reference Guide Defect frequency confirmation Determination and action 1 Defect of compressor lock Replace the compressor 2 Defect of compressor wiring open phase Co 1 Check the refrigeration cycle gas leak 2 Check the case thermostat and connector 3 Check that the service valve is fully open 4 Defect of the pulse motor valve 5 Check for kinked piping 1 Replace the outdoor control board 1 Check the refrigeration cycle gas leak 2 Defect of the pulse motor valve 3 Check the resistance value of the discharge temperature sensor TD 1 Check the power supply voltage AC230 V 23 V 1 Check the thread fastening and heat sink grease between the outdoor control board and the heat sink 2 Check the heat sink fan duct 3 Check the resistance value of the heat sink temperature sensor TH 1 Check the refrigeration cycle gas leak 2 Check that the service valve is fully open 3 Defect of the pulse motor 4 Check for kinked piping 5 Check the resistance value of
22. ect the Code No with the TEMP Cv 4 buttons r m OQ Ca 13 c Condensed temperature TC C 08 Water inlet temperature TWI C Hydro unit Water outlet temperature TWO C O Water heater outlet temperature THO C O Floor inlet temperature TFI C Hot water cylinder temperature sensor TTW C 0B Motorized mixing valve position step Lo pressure Ps x 100 MPa 860 Heat exchanger temperature TE C Outside air temperature TO C Refrigerant discharge temperature TD C Heat sink temperature THS C Outdoor unit Current value in the inverter A 8D _ Number of revolutions of outdoor fan lower rpm Number of revolutions of outdoor fan upper rpm 3 Press 4 button to exit the test mode 32 Hydro Unit Quick Reference Guide Non defective operation program operation No Check code displayed In order to control the heat pump unit there are the following operations as the built in program operations in the microcomputer If a claim occurs about the operation please confirm whether it falls under any of the contents in the following table If it does please understand that the symptom is not a defect of the equipment and it is an operation necessary for the control and maintenance of the heat pump unit Operation of the heat pump system Explanation The compressor sometimes does not operate even within the range of compressor
23. ective countries e Install water pipes in a freeze free place e Make sure that water pipes have sufficient pressure resistance The setting value of the pressure relief valve is 0 3 MPa CAUTION Do not use zinc plated water pipes When steel pipes are used insulate both ends of the pipes The water to be used must meet the water quality standards specified in EN directive 98 83 EC Water Circuit e Install a strainer with 30 to 40 meshes procure locally at O the water inlet ofthe Hydro Unit 1 11 a J 2 e Install drain cocks procure locally for water charge and discharge at the lower part of the Hydro Unit Make the piping route a closed circuit An open circuit may cause a failure Strainer 30 to 40 meshes Drain cock for water charge and discharge Local arrangement Hydro Unit Quick Reference Guide Water Piping Limitations lt 7 Design the water pipe length within the characteristics of the pump flow rate and pump head 2 L L c gt C Ss The maximum height difference for the water pipes is 7 metres Piping to hot water tank option Water supplied to the hot water cylinder is branched by a motorized 3 way valve procured locally Connect the hot water cylinder to port A open when energized of the valve to hydro un
24. ee eee cee ee C lm dp e emen sensor Manometer o Water vent valve i i gt Pressure switch Backup heater m 1 1 I 1 Compressor i 1 1 1 1 1 4 way valve Plate type DA422A3F 25M STF 0401 G n heat M exchanger Pulse motor valve UKV 25D100 r 1 1 Outdoor heat Flow switch exchanger VH 8705 1 1 2500 Hydro Unit Quick Reference Guide Outdoor Units HWS 1103H8 R E HWS 1403H8 R E HWS 1603H8 R E Hydro Units HAWS 1403XWH E Outdoor unit Hydro unit KE M _ Heating Hot water supply l Defrosting Cooling Low Expansion vessel pressure Muffler sensor Manometer 025 x L210 Pressure switch 025 x L180 gt B TWO dE o Water vent valve 4 way valve STF 0401G LI Air vent valve DA422A3F 27M 7 SW e NZ Backup heater Plate type water heat safety valve exchanger f Circulating pump V UPS25 80 130 Pulse motor valve THO UKV 25D100 m I 41 E T u Flow switch VH 8705 Outdoor heat M exchanger pm je ompressor i Accumulator 2500 l Water Pi AN WARNING e Install water pipes according to the regulations of resp
25. ent TD sensor error Open or short circuit in the 1 Check the resistance value F04 Ache om Sc and connection of the discharge 1 9 sensor TD 1 Check the resistance value F06 TE sensor error Open or short circuit in the and connection of the heat 1 heat exchange temperature sensor exchange temperature sensor TE 1 Check the resistance value F07 TL sensor error Open or short circuit in the and connection of the heat 1 exchange temperature sensor TL heat exchange temperature sensor 1 Check the resistance value and connection of the outdoor 1 temperature sensor TO TO sensor error F08 Open or short circuit in the outdoor temperature sensor 1 Check the resistance value and connection of the suction 1 TS sensor error F12 Open or short circuit in the suction temperature sensor temperature sensor TS 1 Check the resistance value and connection of the heat sink 1 temperature sensor TH TH sensor error F13 Open or short circuit in the heat sink temperature sensor 1 Check for any wrong installation of the heat exchange temperature sensor TE and the 1 suction temperature sensor TS TE TS sensors error F15 Open or short circuit in the temperature sensors F31 EEPROM error 1 Check the power supply voltage AC220 230 V 10 single phase type AC380 400V 1096 3 phase type 2 Over loaded condition of the refrigeration cycle 3 Check that the service valve is ful
26. er and 6kW Backup Heater Plate Heat exchanger and 6kW Backup Heater Plate Heat exchanger and 9kW Backup Heater Hydro Unit Quick Reference Guide Estia Hot Water Cylinder EU HWS 1501CSHM3 E 150L Stainless Steel Tank with EU Accessories HWS 2101CSHM3 E 210L Stainless Steel Tank with EU Accessories HWS 3001CSHM3 E 300L Stainless Steel Tank with EU Accessories Estia Hot Water Cylinder UK HWS 1501CSHM3 UK 1501 Stainless Steel Tank with UK Accessories HWS 2101CSHM3 UK 210L Stainless Steel Tank with UK Accessories HWS 3001CSHM3 UK 300L Stainless Steel Tank with UK Accessories Note Under floor heating Fan Coil units Radiators valves and Hot Water Piping are procured locally Notes on System Design The input water temperature to the Hydro Unit must be 55 C or less Especially be careful when there is an external heating source such as a boiler When hot water over 55 C returns it may result in a failure of the unit or water leakage The flow rate of the circulating water must meet the following range 11 14 and 16 kW 17 5 L minute or more 8 kW 13 L minute or more If the flow rate becomes less than the minimum the protective device is activated to stop operation Ensure the flow rate with a bypass valve etc when you use a flow rate valve for the Hydro Unit Do not drive water by power other than the pump built in the Hydro Unit he backup heater operates supplementary to exert a prescribed capacity when the
27. esistance value and connection of the heater outlet temperature sensor THO 1 Check for any disconnection of the heater outlet temperature sensor THO 1 Check the connection of the floor inlet temperature sensor TFI 1 Check the connection body or connection wiring of the low pressure sensor 2 Check the resistance value of the low pressure sensor connection of the water inlet temperature sensor TWI Defect frequency confirmation Hydro Unit Quick Reference Guide Diagnostic functional operation Defect Automatic Determination and action frequency SpSraHond GANSE present reset confirmation EEROM error Inconsistency is detected once without verify x x di live ACK after writing to EEPROM 9 1 Replace the water heat x x 1 exchange control board Communication error 1 Replace the water heat 1 Individual hydro units have a group line exchange control board 1 Check the setting of the FCO1 Communication error capability specifications The capability of the hydro unit has not been HWS 803xx E 0012 set HWS 1403xx E 0017 Setting error When ZONE1 has not been set while ZONE2 has been set 2B Possible Outdoor Unit check codes Not Possible Diagnostic functional operation Defect Check Determination and action frequency Automatic reset confirmation o o Backup Operational cause pres
28. etting Room Temperature Range 11 Room temperature Heating room temperature lower limit 9 I 19509 ie Remote Controller Room Temperature Offset Heating room temperature offset value Sensor 02 10 10 1 temperature control temperature C Room Temperature Offset Cooling room temperature offset value sensor 03 10 10 1 temperature control temperature C Initial Target Water Temperature Cooling Room temperature controller or external room 96 10 25 20 thermostat C Initial Target Water Temperature Heating Room temperature controller or external room 9D 20 55 40 thermostat C 28 Hydro Unit Quick Reference Guide Function Code Setting Address Range Default Function Code Setting Remote i Controller Cooling 2 Way Valve Operation Logic 12 Hydro elis VANE O Activated during cooling 1 Not activated 0 1 0 Operation Control during cooling 13 Hydro 3 Way 3 Way Diverting Valve Operation Logic Diverting Valve O Activated during hot water operation 1 not 54 0 1 Operation Control activated during hot water operation 14 2 Zone Mixing Valve Specified Drive Time for Mixing Valve x10sec OC 3 24 6 Drive Time Mixing valve OFF control time mins 59 1 30 4 External Boiler Heat Pump Synchronisation O Synchronised external boiler stops as temperature reaches hydro unit s temperature 3E 0 1 setting 1 Not synchronised 1 e 2 Boiler Heat Pump Electric Heater Operation y Du
29. f heater energization at the beginning of hot water supply operation If a long period is set it takes long time for heating water 17 Setting Cooling ON OFF function code 02 Set this function when performing cooling operation 18 Remote controller time indication function code Remote controller 05 24 hour or 12 hour notation is selected for the timer 19 Setting Nighttimes Quiet Operation function codes Remote controller 09 to OB ssue an instruction for low noise mode operation to the outdoor unit Enabling disabling of this function start time and end time can be set 20 Setting Alarm Tone function code Remote controller 11 The remote controller alarm tone can be set Function Code Setting Function Code Setting Address Function Code Setting Remote i Controller Heating Upper Limit Zone 1 37 55 C Heating Lower Limit Zone 1 20 37 C Heating Upper Limit Zone 2 37 55 C 1 Setting Temperature Heating Lower Limit Zone 2 20 37 C Range Cooling Upper Limit 18 30 C Cooling Lower Limit 10 20 C Hot Water Upper limit 60 80 C Hot Water Lower limit 40 60 C Heat Pump Start Temperature 20 45 3 Hot Water Temperature Compensation Outside Air 20 40 C Temperature Temperature Compensation Compensation Temperature 0 15 4 Hot Water Boost Setting Temperature 27 Hydro Unit Quick Reference Guide Function Function Code fun
30. heat pump cannot exert its capacity at a low outside temperature Install the Hydro Unit and water pipes in a place in which they do not freeze Make the water circuit closed Never use it as an open circuit prevent damage to the system the circulating water must be 20 litres or more If total water amount is not enough the unit may not function fully due to protective operation Components required for each function Toshiba Supply Procure locally Model code Radiator s Heating Fan coil s Under floor heating Heating amp Cooling Fansite ony Fan coil s plus Heating amp Cooling Radiator s partly heating only or Under floor heating Motorized 2 way valve Motorized 3 way valve Earth leakage breaker Motorized mixing valve 2 zone control Circulator pump Buffer tank Interlocking with boiler External output board Boiler Hydro Unit Quick Reference Guide Installation Examples Cooling and Heating with Domestic Hot Water When both cooling and heating are used install a 2 way valve for cooling to the pipe to the room for heating only NV N s 52 Vam Valve for Drain Cock for water Sanitary Hot Charge and Drain gt lt Water Tank lt J i Radiators Heating Only 2 Way Valve Control 2 Way Use it when do nat Valve operate cooling Alternative to Radiators Under fioor Heating Heating Only 2 Way Valve Control
31. it AB room heating or cooling ta hot water cylinder B Open when de energized Open when energized Piping to 2 zone operation option To perform 2 zone temperature control circulate water using another pump procured locally through a motorized mixing valve procured locally and a buffer tank procured locally Buffer tank hydro unit Water pump Procured locally Procured locally Open when A energized rum Motorized mixing valve Procured locally B Open when de eneraized hydro unit c n s gt Hydro Unit Quick Reference Guide Checking water volume and initial pressure of expansion vessel The expansion vessel of the Hydro Unit has a capacity of 12 litres The initial pressure of the expansion vessel is 0 1 MPa 1 bar The pressure of the safety valve is 0 3 MPa 3 bar Verify whether the capacity of the expansion vessel is sufficient using the following expression If the volume is insufficient install an appropriate external expansion vessel E X Vs x 00000 m Internal Expansion Vessel Size OK Internal Expansion Vessel Size too small Install appropriate external expansion vessel 2 gt 12 L V Necessary total vessel capacity L Water expansion coefficient at average hot water temperature Vs Total water volume in the closed system Do not include Hot Water Cylinder P1 System pressure at ta
32. lmost no or little water flow Not enough vent air Dirt clogging in the water piping system The water piping is too long Installation of buffer tank and secondary pump 1 Disconnection of the flow switch connector 2 Defect of the flow switch 1 Check the water inlet water outlet and heater outlet TWI TWO THO sensors 2 Defect of the backup heater defect automatic reset thermostat 1 Check the hot water cylinder sensor TTW 2 Check the hot water cylinder thermal cut out 1 Almost no or little water flow Dirt clogging in the water piping system The water piping is too long 2 Check the heater power circuit Power supply voltage breaker power supply connection 3 Set the presence of the backup heater 4 Check the water inlet water outlet and heat exchange TWI TWO TC sensors 1 Check the heater power circuit Power supply voltage breaker power supply connection 2 Check the water inlet water outlet and heater outlet sensors TWI TWO THO 3 Disconnection of the backup heater Heating 2 Hot water 2 Cooling 4 1 Almost no or little water flow 2 Defect of the flow switch 3 On load operation under the above conditions 4 Defect in the pressure switch 1 Almost no or little water flow 2 Defect of the flow switch 3 On load cooling or prolonged defrosting a lot of frost formation under the above conditions 4 Defect in the low pressure se
33. ly open Compressor breakdown 1 When the operation frequency lowers due to the current release 40 sec or later after the compressor activation and it stops by underrunning the minimum frequency 2 When the operation frequency lowers due to the current limit control and it stops by underrunning the minimum frequency 3 When an excess current is detected 0 8 sec or later after the compressor activation U ON Hydro Unit Check code H02 H04 Unset service PC board jumper Jumpers J800 J803 have not been cut 1 Cut 2800 4803 L29 P04 POS P07 P15 P19 Diagnostic functional operation Compressor lock When the input current is more than zero 20 sec or later after the compressor activation and the activation has not been completed Operation of case thermostat When the case thermostat exceeds 125 C The communication between the outdoor PC board MUCs error No communication signal between IPDU and CDB The outlet temperature error When the discharge temperature sensor TD exceeds 111 C The high pressure switch error The power supply voltage error When the power supply voltage is extremely high or low Overheating of heat sink error When the heat sink exceeds 105 Detection of gas leak When the discharge temperature sensor TD exceeds 106 C for consecutive 10 min When the suction temperature sensor TS exceeds 60 for cooling or 40 for h
34. ngs for 2 zone temperature control Procure a motorized mixing valve locally and perform piping Connect the valve cables as described in Electrical section Procure a buffer tank locally Procure a water pump locally and connect its cables as described in Electrical section To inhibit interlocking the water pump with the internal pump of the Hydro Unit set DIP SW10 3 on the Hydro Unit board to OFF e Set DIP SW12 3 on the Hydro Unit board to ON Attach the temperature sensor TFI connected to terminals C and D of the Hydro Unit near the hot water inlet of the Hydro Unit Fix TFI sensor on the room heating supply pipe by using the connector procured in locally Cover the cables with insulation tube minimum 1 mm or conduit so that the user cannot touch them directly e Cover the TFI sensor s cables and sensor with insulation tube minimum 1 mm shown in the diagram on the right Insulation tube minimum 1 mm TFI Sensor I i 37 P 2 Zone hot water supply pipe than 4 mm Under floor Heating 2 Way Valve Control Test Run Once you have competed the installation and system configuration conduct a test run see below Since the protection setting is disabled in the TEST mode do not continue a test run longer than 10 minutes Press the TEST 4 button the remote controller An indication TEST appears on remote controller ZONE 1 2 Press the
35. nk setting position Mpa abs Pipe inner pressure during pump operation before heating device operates water supply pressure P2 Maximum pressure used during operation at tank setting position MPa abs 7 safety valve setting pressure The absolute pressure value abs is obtained by adding the atmospheric pressure 0 1 MPa 1 bar to the gauge pressure Water temperature and expansion coefficient Water temperature and expansion coefficient Hot water temperature Expansion rate Hot water temperature Expansion rate 0 0002 0 0121 0 0145 60 0 0171 0 0198 0 0229 0 0258 A 0 0292 0 0324 90 0 0961 0 0967 p y O Example Maximum Hot Water temperature 55 C Initial water charge 0 2MPa System volume 200 L Calculate Vessel capacity V V 0 0145 x 200 1 0 2 0 1 0 3 0 1 a o 7 a 2 tn m c x LLI V 11 6L In this case V lt 12 L therefore the internal expansion vessel is sufficient so there is no need uot water temperature 55 C to install an external expansion vessel Water volume 10 Hydro Unit Quick Reference Guide Pump operation configuration HWS 803XWHM3 E 6 06 T9 E Hydraulic heat exchanger BkW QH characteristics Minimum flow rate E 72 e mm DL EN e DOO TE s 9 s m n3 n3 e lt Flow rate L min
36. nsor Hydro Unit Quick Reference Guide Check code Diagnostic functional operation Operational cause Overheat protection operation When the thermostat of the backup heater activates during the operation of the heat pump or backup heater When the thermostat operation is activated while it has been stopped Operation of the release protection When the TWO release counts to 10 Heating hot water heater The antifreeze control is detected under the condition of TWI lt 20 C while TWI gt 15 C TTW gt 20 C is not detected after the heater backup Regular communication error between hydro unit and remote controller When there is no regular communication from the remote control for 3 min or when no remote control is equipped Regular communication error between hydro unit and outdoor unit The serial signal cannot be received from outdoor TC sensor error Open or short circuit in the heat exchange temperature sensor TWI sensor error Open or short circuit in the water inlet temperature sensor TWO sensor error Open or short circuit in the water outlet temperature sensor TTW sensor error Open or short circuit in the hot water cylinder sensor TFI sensor error Open or short circuit in the floor temperature sensor THO sensor error Open or short circuit in the heater outlet temperature sensor Detection of THO disconnection error When gt 15 is detected and 30 sec elapsed TFI
37. ntrol time and target temperature when the HOT WATER BOOST 8 button on the remote controller is pressed 5 Setting Anti Bacteria function codes 0A and OB Remote controller and 0C Set the control for the hot water cylinder when ANTI BACTERIA 8 Jis set with the remote controller e Set the target temperature control period start time 24 hour notation and target temperature retention period Make this control setting according to regulations and rules of respective countries 6 Setting System Priority Mode function codes 22 23 and OF e Set the outside air temperature that changes the preferred operation mode Hot Water Heating Switching Temperature Heating operation takes precedence when the temperature lowers the set temperature Boiler HP Switching Temperature When the temperature lowers the set temperature the HP operation stops and the external boiler output is made Cooling Hot Water Priority Selection Set the priority mode between cooling and hot water when the system is running in cooling mode 7 Setting Heating Auto Mode Temperature function codes 27 to 31 Compensate the target temperature when Auto is set for temperature setting on the remote controller The outside air temperature can be set to one of three points T1 and customisable within a range of 15 to 15 The target temperature can be set to a value from 20 to 55 C e However gt B C D
38. om temperature control using FC40 Set upper and lower heating cooling temperature limits using FC s 92 93 94 and 95 Set initial target water temperatures for heating and cooling using FC s 96 and 9D Set room temperature offsets for heating and cooling using remote controller FC s 02 and 03 e Set remote controllers as header second and room temperature water temperature functions using DPSW s 1 and 2 on the remote controllers 12 Setting 2 Way Valve for Cooling Operation function code 3C e When using both cooling and heating operations and there is an indoor unit only for heating such as floor heating install the 2 way valve and set this function code 13 Setting 3 Way Valve Operation function code 54 This setting is not necessary for normal installation Make this setting to invert the logic circuit in case ports A and B of the 3 way valve are wrongly attached and it cannot be rectified on site 14 Mixing valve types and setting function code 0 e Set the time period from full close to full open of the 2 zone control mixing valve Set a value that is 1 10 of the actual time 15 Setting Heating Hot Water Switching when Boiler Is Used function code 3E When boiler is used make this setting to operate the Hydro Unit by the instruction from the boiler 16 Setting Heat Pump Operating Time for Hot Water Supply Operation function code 07 Set the time period from the start of heat pump run to the start o
39. play mode 1 not occurred now 3 Press SW800 for at least one second The LED status changes to 1 Set bit 1 of DIP switch SW803 to ON display mode 2 2 Jot down the states of LED800 to 4 Check the code whose display mode 1 equals the jotted LED status and LED804 Display mode 1 display mode 2 equals the current flashing status of LED800 to LED804 Press SW800 for at least one second from the following table to identify the cause The LED status changes to display The LEDs and DIP switches are located at the lower left of the P C board of the outdoor unit mode 2 L SW801 SW800 4 Find an error whose display mode 1 o Enlargedvew equals the jotted LED status and display ean mode 2 equals the current flashing status of LED800 to LED804 from the SW804 following table to identify the error An outside air temperature TO sensor error can be checked only while an error occurs 5 5 s tlt Heat erchengersersor Teyeror gt ptt 4 emecersmorf emr 5 5 tlt s jpustesrempemwresewortOemr 5 5 s o t LL c NNN B kee RCN RCM OC T 79 owdoorEEPROM enor a 2 cae 11 Compressoriock 12424 o 0 12 Curentaetectcircuteror o e e 4 40 4 13
40. port AB to Hydro unit Hydro unit an port BLANK OFF port B BLANK OFF Hot water cylinder connection optional Please refer to Electrical supply cable specifications for fuse cable size and for connection details Electrical Connection Hot Water Cylinder Electric Heater he electric heater incorporated in the hot water cylinder requires a separate supply to the Hydro Unit Connect the hot water cylinder heater electrical supply in accordance with shown below Live conductor Terminal L on Terminal Block 03 Neutral conductor Terminal N on Terminal Block 03 Earth Conductor Earth terminal on Terminal Block 03 Connect the hot water cylinder heater to the Hydro Unit as shown below Live conductor to hot water cylinder Terminal 1 on Terminal Block 03 Neutral conductor to hot water cylinder Terminal 2 on Terminal Block 03 Earth conductor to hot water cylinder Earth terminal on Terminal Block 03 Electrical Connection Hot Water Cylinder temperature Sensor Connect the hot water cylinder temperature sensor as shown below to terminals A amp B on Terminal Block 06 in the Hydro Unit Please ensure that the interconnecting cable between the Hydro Unit and the hot water cylinder is connected to earth at both ends of the cable using the shield wire Hot water cylinder Earth leakage breaker INPUT Power 230 V 50 Hz Hydro Unit 20 Hydro Unit Quick Reference G
41. pressed again the data set mode Lights when the unit enters the service Lights mney mode and goes out when the unit exits the service mode P1 Indicates scheduled operation 1 Lights when an error occurs and goes status including setting time e N out when the error is cleared Displays the scheduled operation H step when the scheduled operation OK S Oi C AE STEP1 5 program is set p Lights during time setting and S Lights for two seconds when settings ur scheduled operation setting failed Function Code Access Set function codes for various operation modes input using the remote controller There are 2 types of settings 1 Hydro Unit function code setting 2 Remote controller function code setting Setting procedure for Hydro Unit function code SEI d 1 Press and hold CAP buttons for four seconds or more to enter the hydro unit function code setting mode a 2 Set the function code number with the TEMP buttons C4 CODE No 01 to 91 A rp s 3 Set data with the TIME buttons ST A coven LILI SET G5 4 Press L to confirm the settings TAa NT CL 5 Note that the Clear button C is enabled only before the SET button is pressed and the function code is changed 6 Press to exit the settings menu Setting procedure for Remote Controller function code CL 1 Press and hold
42. pump heater Defective operation check codes How to determine from the check code on the remote control If the defect is limited by the check code displayed on the remote control please repair the defect based on the table on the next page The check codes are separated into two groups software and hardware errors Since a hardware error cannot be cancelled without a part replacement etc please perform a repair If its abnormality is determined the abnormality is noticed by indicating the check code on the remote control check code display part while letting off a buzzer aa gt ZONE 4 ZONE2 4 gt HOT WATER 4 onm HE EB LL apap 9i MO TU WE TH ER SA Su areg 1 7 al STEP Check code display part SCHEDULE m Le HOT WATER TIME SET CL How to cancel a check code on the remote controller ZONE 1 2 HOT WATER 1 Press or button on the operation side to clear the check code CL 2 Press stop buzzer for an abnormality only Although the above procedure cancels the check code the hardware error will be displayed again until the hardware repair is completed 33 Hydro Unit Hydro Unit check codes Diagnostic functional operation A01 A02 A03 A04 A05 07 08 Operational cause Pump or flowing quantity error 1 Detected by TC sensor TC 63 is detected in the heating or hot wa
43. rence Guide Start up and Configuration Setting DIP Switches on the Board in the Hydro Unit Detach the front cover and the electric parts box cover of P C board the Hydro Unit MCC 1511 e Set the DIP switches on the main board Description Default setting Alternate Pump P1 control during hot P1 stops when heat pump OFF ON P1 continuous water production stops cylinder heater ON operation Pump P1 control using outside aluo Normal Control OFF ON controlled by outside air temperature air temperature Continuous operation P2 Interlocked with the External P2 pump operation OFF when remote OFF ON internal pump controller OFF synchronised with P1 Description Default setting Alternate operation operation Booster heater output enabled disabled Enabled OFF Disabled 9 Default setting Alternate 3WV selection 2 wire SPST 2 wire spring return type ET or SPDT 3 wire SPST type B Rl 2 pole od Disabled OFF ON Enabled disabled Auto restart for power failure Auto restart Manual restart Description Default setting Alternate Boiler installation position Before 3 way valve OFF on After 3 way valve heating side 22 Hydro Unit Hydro Unit Remote Control Buttons 1 TEMP button qum C Y md 2 SCHEDULE button 3 TIME button Cv 4 4 SET button 5 CL button CL 6 DAY button 7 STEP button
44. ring Low Ambient Conditions controlled using FC23 5 0 HP amp boiler operation gt hu 1 Boiler operation only 2 Electric heater operation only 16 Maximum Operation Time Of Hot Water Heat Maximum Heat Pump Operation Time In Hot 1 120 p Water Operation Priority Mode minutes ump O Cooling 8 Heating Operation 1 Heating 17 Cooling Operation Only Operation Indication Low Noise Operation O Invalid 1 Valid Ss 1 19 Low Start Time Hour 22 p End Time Hour 0 23 20 Alarm Tone Tone Switching O OFF 1 ON Pump P2 Control in Cooling Mode 0 P2 continuous operation 64 0 1 1 P2 stops in cooling mode Synchronise Pump P1 with Room Temperature Control and External Room Thermostat Pump Control Control Synchronisation 0 P1 continuous operation 65 0 1 1 P1 synchronised with room temperature thermostat control P1 will stop when HP in thermo OFF mode Pump P1 Operation outside Air Temperature Control in Heating Mode 10 30 P1 stops when TO gt set value in FC9E with DPSW10 2 ON heating mode only Pump P2 Remote o_Not Shown 1 Shown Controller Display 29 Hydro Unit Quick Reference Guide Function Code Setting Address Hydro Remote Unit Controller Function Code Setting Range Forced stop input switch logic 0 Contacts low gt high terminals 1 3 CLOSE system stop System restart with remote controller 1 Contacts high gt low terminals 1
45. s IE mimi FR e mimi imam mimi M Rn c 4 SP KE LB j l j I y E l i TB 02 O e to Outdoor unit Input power Input power Input power Input power water 220 230 V 1220 230 V 380 400 V 3N 220 230 V cylinder 50 Hz 50 Hz 50 Hz 3 50Hz Sensor Qutdoor unit Hot water cylinder Backup heater connection connection power supply power supply 14 Hydro Unit Quick Reference Guide Electrical supply cable specifications Wiring specifications power line wem um conn n 220 230 V input 1603 380 400V 3N ower T AUUV aN 25 1403H8 E 380 400V 3N 1103 8 380 400V 3N input for TBO backup d 20 803XWHM3 E OH 16A 1 5 mm or more L M et ja je erem o jE Outdoor Hydro unit Ca C OKO obe oo 1 Wiring specification control line Maximum Connection 3 way valve control 2 line or 3 line 100 mA c 0 75 mm or more 2 valve control 2 valve control valve control 2 line 100 mA 0 5 mm or more 93 4 TBOS 2 zone thermo sensor 2 line 100 mA D 06 T ada x 2 GND shielded 5 Cylinder thermo sensor wire 100 mA 0 75 mm or more A TBOG Q 2 G Mixing valve control 3 line 100 mA 0 5 mm or more o A TB04 15 Hydro Unit Quick Reference Guide
46. s and Height The length and height of the refrigeration pipe must be within the following values As long as the Hydro Unit is installed within these ranges no additional refrigerant is required Minimum Pipe Length HWS 803H E om HWS 1103H E 5 HWS 1403H E Sm HWS 1603H E 5m Maximum Pipe Length and Height Max 30 m above or below L Max 30m Note The maximum pipe length cannot be increased using additional refrigerant Refrigeration and Water Cycle Diagrams Outdoor Unit HWS 803H E Hydro Units HWS 803XWH E Outdoor unit Hydro unit gt Heating Hot water supply Low gt Defrosting Cooling ae xpansion vesse sanadir Manometer I D gt TWO __ Air vent valve I nS NZ Backup heater Plate type water heat Safety valve exchanger N Circulating pump N UPS025 65 K 130 i 2 m DA220A2F 22L 7 STF 218G E o Water vent valve Pulse motor valv I 4 way valve I CAM B30YGTF THO gt m B I Outdoor haa Flow switch p I I Compressor 1 I exchanger VH 8706 1800 L i Outdoor Units HWS 1103H E HWS 1403H E Hydro Units HWS 1403XWH E Outdoor unit Hydro unit n 0 es come n
47. supply function is not used e When the hot water supply function is not used set DIP SW12 1 on the Hydro Unit board to ON refer to page 18 Setting for cooling For Space Conditioning Units that do not perform cooling radiators and Under floor heating etc procure a motorized 2 way valve for cooling locally and attach it to the water pipe that is not used for cooling Connect the valve cables to terminals 5 3 and 4 of the Hydro Unit Press and hold 4 switches on the remote controller to change the Hydro Unit function code and change address 02 to 0 and then press the SET button to enable the function Press the TEST amp button to exit the setting mode e Stick the optional insulation for cooling to the bottom of the Hydro Unit 30 Hydro Unit Quick Reference Guide Settings for hot water supply Prepare the optional hot water cylinder Procure a motorized 3 way diverter valve locally and perform piping Connect the valve cables as described in Electrical connection section e Set DIP SW12 1 on the Hydro Unit board to OFF Connect the power supply unit for the hot water cylinder heater to terminals L and of the Hydro Unit Connect cables between the Hydro Unit and the hot water cylinder as follows Hydro Unit terminals 1 2 and earth Hot water cylinder 1 2 and earth TBO6 A B and earth Hot water cylinder A B and earth Setti
48. ter supply heat pump operation except for defrosting 2 Detected by flow switch abnormality When no signal of the flow switch is showing 2 min after the built in pump operation started 3 Detection of chattering abnormality in the flow switch input Chattering detection Detects input changes OFF amp ON 4 times within 10 seconds during operation 4 Disconnection of the flow switch connector When the stopped built in pump starts its operation the flow switch status is detecting water flow Temperature increase error heating When one of the TWI TWO and THO sensors exceeds 70 Temperature increase error hot water supply When the TTW sensor exceeds 85 C Antifreeze operation 1 TWO gt 20 C condition 2xTC TWO lt 12 C is detected 2 TWO 20 C condition TC TWO lt 4 C is detected 3 TWI 10 C is detected during defrosting Piping antifreeze operation Activating the heater under the condition of TWO lt 4orTWI lt 4o0rTHO lt 4 does not achieve TWO TWI THO 5 C after 30 min elapsed Pressure switch operation The pressure switch operates for 300 sec continuously during the heat pump operation Low pressure sensor operation error The low pressure sensor detected 0 2 MPa or less Backup present Heating O Hot water x Heating O Hot water x Automatic reset Quick Reference Guide Possible x Not possible Defect frequency confirmation Determination and action 1 A
49. the wire wound resistor of the compressor Short circuit Replace the compressor Determination and action Condition Displayed when the abnormality is detected Displayed when the abnormality is detected Displayed when the abnormality is detected Defect in the remote control power supply 1 Check the remote controller wining Check the remote controller 1 Check the hydro unit power supply wiring 4 Check the water heat exchange control board Defect in the reception of the remote control 1 Check the remote control crossover 2 Check the remote control 3 Check the hydro power supply wiring 4 Check the water heat exchanger board Defect in the transmission of the remote control 1 Check the transmitter circuit inside the remote control Replace the remote control 1 2 Check several base units with the remote control The base unit is only one and others are handsets Hydro Unit Quick Reference Guide Outdoor Fault Diagnosis You can perform fault diagnosis of the outdoor unit with the LED s on the P C board of the outdoor unit in addition to check codes displayed on the wired remote controller of the hydro unit Use the LED s and check codes for various checks Check of the current abnormal status Check of the abnormal status in the 1 Check that DIP switch SW803 is set to all OFF past although the abnormal status is 2 Jot down the states of LED800 to LED804 Dis
50. ture in the tank for sterilization Pressing this button long changes the mode to data setting mode Boosts boiling when high tapping temperature is required temporarily Turns on off hot water operation Selects an operation mode when changing the set temperature of each operation mode Some functions are not provided depending on the system specification in use Hydro Unit Display Explanation 20 1 4 ZONE2 4 d ETY gt HOT WATER lt Fm i i ZD c 18 ZONE1 ZONE2 Display Description Lights when floor heater or radiator is connected when the system has floor heater or radiator ZONEI 4 ZONE1 selected for Temperature to be changed ZONE2 Lights when system configured to wa have 2 zones ZONE2 selected for Temperature gt ZONE2 4 to be changed Lights during heating or cooling operation using the heat pump EN EN EN e Lights when the internal heater is energized during heating operation Lights when heating is selected Lights when cooling is selected Lights when the FROST PROTECTION button is pressed and goes out when the button is pressed again Lights when Auto operation is selected Displays heating cooling set temperature Heating 20 to 55 C HH factory setting Auto cooling 10 to 30 Goes out when Auto operation is selected Lights when the set temperature or C sensor s water temperature is displayed
51. uide Second Remote Controller Installation optional It is possible to connect a second remote controller to the ESTIA system The remote controller can be set as either the header or second remote controller and to measure either water temperature or room air temperature Second Remote Controller Connection 2 core shielded cable 0 5 or more Maximum cable length 50m Terminal block 7 for remote controller connection to hydro unit Second remote controller connections Terminals A and B are non polar Remote Controller DIPS Switches Setting Remote controller inside rear DIP switch switch switch switch 1 Header remote Headerremote Secondremote Secondremote control Hot control Room control Hot control Room water temperature water temperature temperature temperature Set of the remote controllers as the header remote controller remote controller of hydro unit is preset as the header remote controller DPSW1 OFF Set the DPSW s on the other remote controller PC boards to second optional remote controller is preset as second DPSW1 ON For room air temperature measurement set function code 40 on the hydro unit to 1 Set DPSW2 to ON on the remote controller used for room temperature measurement Either the header or the second remote controller can be set for room temperature measurement 21 Hydro Unit Quick Refe
52. ve Ensure the Outdoor Unit to Hydro Unit interconnecting cable is secured using the cable clamp fitted in the electrical box Ensure the Outdoor Unit to Hydro Unit interconnecting cable connection terminals are tight 17 Hydro Unit Quick Reference Guide Electrical connection for external booster heater NCAUTION maximum current available from the booster heater output is 1 A Do not connect the booster heater directly to Terminal Block 05 on the Hydro Unit A separate contactor supplied locally must be used to supply the booster heater The booster heater can be installed only for room heating and cannot be used for hot water supply Install the booster heater downstream of the 3 way valve on the indoor unit side he booster heater is an external heater supplied locally used to assist the Hydro Unit during low ambient conditions e The AC230 V 1 A output from the Hydro Unit must only be used to energize an external contactor supplied locally The output from the Hydro Unit is only enabled when either the outdoor air temperature to be lower than 20 C Ensure the external booster heater is installed and set up in accordance with all Local National and International regulations Connect the external booster heater to the Hydro Unit according to the diagram shown opposite e The contactor will energize in the event of low ambient conditions A separate dedicated electrical supply must be used for
53. with the segment indicator rtt Li Lc UNIT No j J K Quick Reference Guide i CODE No Li e 20 HOT WATER Display Lights when hot water supply system is connected when the system has hot water supply gt HOT WATER 4 HOT WATER selected for Temperature to be changed Lights when hot water supply operation is performed by heat pump HOTWATER Lights when the internal heater is energized during hot water supply operation Lights during hot water supply operation Lights while hot water boost is activated Lights when the ANTI BACTERIA button is pressed and goes out when the button is pressed again m Lights when unit enters the data set Lights when the set temperature or G sensor s water temperature is displayed with the segment indicator Displays hot water set temperature 40 to 75 factory setting 65 24 Hydro Unit Quick Reference Guide Display Explanation cont 19 TIMER 21 CONTROL TT np Clock Displays the current time Lights while internal pump P1 or AM or PM external pump P2 is driven Displays days of the week Sunday d Lights during backup operation only by to Saturday the heater Lights when the NIGHT button is Lights when the unit enters the data set pressed and goes out when the SETTING mode and goes out when the unit exits button is
Download Pdf Manuals
Related Search
Related Contents
SPRAY GUN AZ3 HTE2, AZ3 HTE2 AV, AZ3 HTE2 HVLP FICHA DATOS TÉCNICOS PASTA DE COBRE VERY LARGE TELESCOPE QStar Owners Manual Tutorix Editor Benutzerhandbuch 全リストはこちら(PDF) Betriebsanleitung 印刷用PDF "user manual" USER GUIDE - loadritensw.com.au Copyright © All rights reserved.
Failed to retrieve file