Home
Fedders CH18ABD1 Heat Pump User Manual
Contents
1. 2 ELECTRICAL CONNECTIONS 2 SERVICE VALVE CONNECTIONS sescseceiaceccascccedsdcecsaanseaaendapanscachatiegaeiateresaseecasedeeencaeses 3 EVACUATION 2 aiseal a anaa aaia 3 Opening the Service Valve Step 3 Opening the Service Valve Straight 3 CONNECT REFRIGERANT PIPING 4 PRECAUTIONS ariaa Ea e 4 Liquid Line 5 2 4 SUCTION LIME SIZES iriseoir mupa ai araar at 4 SUBCOOLING CHARGING 5 FINAL CHECKS FOR 5 5 COOLING OPERATION onanirao tasirini iniaa 5 HEATING OPERATION 5 DEFROST 6 MAINTENANCE INSTRUCTIONS 6 CONDENSING UNIT NOMENCLATURE 6 LIMITED WARRANTY 7 NOTE THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OF THIS EQUIPMENT READ THE ENTIRE INSTRUCTION MANUAL THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION INTRODUCTION You have made a major investment in a fine piece of equipment Keep your investment sound by reading these instructions before installing this unit This will ensure that the full potential of this equipment is achieved It will also be he
2. All heating values are with frost free outdoor coil When the outdoor temperature is below 40 F manually defrost the unit before reading SUBCOOLING T2 T3 FINAL CHECKS FOR INSTALLER 1 Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub through or wire pinching 2 Ensure that all wiring and tubing is secure in unit before adding panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave this manual with owner Explain system operation and periodic maintenance requirements outlined in manual COOLING OPERATION Turn the thermostat heat cool switch to the cool position Set the desired temperature on the thermostat dial Do not operate the cooling unit for extended periods at indoor temperatures over 85 F The unit indoor design temperature range is between 70 F and 80 F in the cooling mode is not recommended to vary the temperature settings more than 5 F Varying the temperature more than 5 degrees or turning the thermostat off for periods less than 12 hours can actually cost you more in energy consumption than keeping the temperature constant Consider indoor plants and pets when varying the temperature from the normal comfort level HEATING OPERATION Turn the thermostat heat cool switch to the heat position Set the desired temperature on the thermostat dial Do not operate the heating unit at indoor temperatu
3. F Emergency heat This switch will turn the outdoor unit off and use the electric auxiliary heat only to provide heat If outdoor unit should malfunction turn the emergency heat switch to the ON position and contact your service person FEDDERS DEFROST OPERATION The heat pump has a control system designed to defrost the outdoor coil by warming it up to keep it clear of ice and operating efficiently When the temperature drops below 40 F the control system will sense that conditions are right for the formation of ice After a time period of 60 to 90 minutes the heat pump will go into the defrost mode At this time the outdoor coil may be heavily iced or no ice may be visible depending on the outdoor humidity When the unit starts the defrost mode the outdoor fan will turn off and a hissing noise may be heard that disappears as defrost continues As the outdoor coil warms you may notice steam coming off the coil When the coil reaches a predetermined temperature usually within 7 minutes the defrost cycle will end You may hear a hiss as the unit switches back to the normal heating mode CAUTION Wait at least 3 minutes after turning the heat pump off before trying to restart If an attempt is made to start the compressor before the refrigerant pressures are equalized the unit may fail to restart An additional waiting period will then be required before restarting MAINTENANCE INSTRUCTIONS For continuing hi
4. 1 208 230 Volts 1 Phase 60 Hz 2 230 Volts 1 Phase 50 Hz 3 208 230 Volts 3 Phase 60 Hz 4 460 Volts 3 Phase 60 Hz 5 230 Volts 3 Phase 50 Hz 6 380 Volts 3 Phase 50 Hz Variations D R 22 Refrigerant E R 407C Refrigerant F R 410A Refrigerant LIMITED WARRANTY Limited Five Year Warranty Fedders will provide a replacement part or component that proves to be defective in material or workmanship Warranty Limitations Limited Warranty does not include allowances for labor or travel expense connected with the installation of parts so furnished in this Limited Warranty or for field repair or servicing of the equipment nor for refrigerant used For warranty purposes the purchase date is established by a proof of purchase If a proof of purchase can not be verified then warranty period will be measured from the date of manufacture plus 6 months Cost of repair or replacement of consumable parts 15 not covered under the terms of this warranty Replacement parts are warranted only for the balance of the original warranty period Applies only to original installation and normal use and service within the 48 contiguous United States District of Columbia and Canada Applies to service performed by an authorized servicer Warranty is Void if Serial plate is defaced Product has defect or damage due to product alteration connection to an improper electric
5. from joists and studs with a rigid wire or strap which comes in direct contact with tubing When necessary use hanger straps which are 1 in wide and conform to shape of tubing insulation Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation Condensing units are available with pre charged sweat type copper connecting fittings Units are factory charged for 15 of line set tubing Adjust charge 0 66 oz per foot of variation from chart for 3 8 3 4 line set Adjust charge 0 67 oz foot of variation from chart for 3 8 and 7 8 line set Adjust charge 0 72 oz per foot of variation from chart for 1 2 and 1 1 8 line set Liquid Line Sizes HEAT PUMP LINE SET LENGTH AND SIZE MODEL 15 FT 25 FT 50 FT 75 NUMBER SET LINE SET LINE SET LINE SET CRED Suction Line Sizes HEAT PUMP LINE SET LENGTH AND SIZE L 7 CHA2ACD1 K DO NOT EXCEED 75 FT MAXIMUM LINE SET LENGTH SUB COOLING CHARGING For proper sub cooling readings a standard high side gauge is required for pressure readings Use the charts below to determine the required sub cooling value INSTRUCTIONS 1 Measure the outdoor air temperature T1 2 Measure the liquid line pressure and determine the liquid refrigerant temperature by the scale on the high side pressure gauge T2 In cooling mode take reading at the i
6. 3 23 0419N 011
7. E MADE ALL IMPLIED WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR IMPLIED WARRANTIES OTHERWISE ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE IN NO EVENT SHALL FEDDERS BE LIABLE FOR ANY INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES EVEN IF ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES NO WARRANTIES EXPRESS OR IMPLIED ARE MADE TO ANY BUYER UPON RESALE SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS OR DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY FROM STATE TO STATE NO WARRANTIES ARE MADE FOR UNITS SOLD OUTSIDE THE ABOVE STATED AREAS YOUR DISTRIBUTOR OR FINAL SELLER MAY PROVIDE A WARRANTY ON UNITS SOLD OUTSIDE OF THESE AREAS The information in this manual supersedes and replaces the previous instruction operation manual Illustrations cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any time without notice For replacement parts please consult the installing dealer or contractor Fedders Corporation 505 Martinsville Rd Liberty Corner NJ 07938 REV 7 06 2
8. Installation Operation and Maintenance FEDDERS 1 5 Through 5 Ton Heat Pump TABLE OF CONTENTS INTRODUCTION joi gee 1 NOTES INSTALLER 1 CODES 1 RECOGNIZE SAFETY SYMBOLS WORDS AND LABELS 1 INSPECTION AND 1 INSTALLATION CIOARANCES painiin anere eaa aright eee 2 SUPDOME 2 9 2 Proximity
9. ORMING ANY WORK ON THIS EQUIPMENT POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK INJURY DAMAGE TO EQUIPMENT OR DEATH CONSULT A QUALIFIED INSTALLER FOR INFORMATION OR ASSISTANCE CODES The installer SHALL comply with all local state and federal codes and or regulations pertaining to this type of equipment and its installation Such codes and or regulations should take precedence over any recommendations contained herein in lieu of local codes Installations SHALL be made in accordance with the National Electrical Code local codes and recommendations made by the National Board of Fire Underwriters Consult local building codes and National Electrical Code NEC for special requirements INSPECTION AND UNPACKING A thorough inspection of the shipping container should be made immediately upon receiving your unit Look for any punctures or openings and if it appears damage has occurred note it on the freight bill before signing Contact the delivering carrier immediately to inspect damage and no installation work should begin until this inspection is completed Locate rating plate on unit corner panel It contains information needed to properly install unit Check rating plate to be sure unit matches job specification Rating plate located inside l control box cover 34 N INSTALLATION Condensing Unit Location The cond
10. ZE JOINTS DRY NITROGEN SHOULD BE USED TO LEAK CHECK A WARNING A ALWAYS HAVE A FIRE EXTINGUISHER AVAILABLE WHEN WORKING WITH AN OPEN FLAME ALWAYS USE SAFETY GLASSES PROTECTIVE CLOTHING AND WORK GLOVES Br Quenching cloth Evacuation The outdoor unit is factory charged Evacuation is necessary on the uncharged portions of the total system Purge the system with dry nitrogen Then connect a vacuum pump and a vacuum gage capable of accurately measuring below 1 000 microns vacuum depth The deep vacuum method is the most positive way of assuring a system is free of air and liquid water A WARNING A IF THE INSTALLER IS MAKING UP HIS OWN LINE SETS HE MUST MAKE SURE THE TUBING IS CLEAN OF ANY IMPURITIES OR MOISTURE Opening the Service Valve Step Valve NOTE This is not a back seating valve 1 Remove the valve cap using an adjustable wrench 2 Open the valve by inserting a hex wrench 3 16 for the liquid line 5 16 for the vapor line into the stem and back out counter clockwise until the valve stem just touches the retaining ring Do not over tighten 3 Replace the valve cap finger tight then tighten an additional 1 12 turn or 1 2 hex flat A metal to metal seal is now complete F Schrader valve port Remove cap Open valve Replace cap Opening the Service Valve Straight Valve NOTE This is not a back seating valve Open the valve by using an adjustable wrench to tur
11. al supply shipping and handling fire flood lightning or other conditions beyond the control of Fedders Product is not installed according to Fedders instructions and specifications Product is operated in a corrosive environment containing concentrations of corrosive agents causing deterioration of components Product is operated with indoor unit or refrigerant control device that does not meet Fedders specifications Product is moved from original installation site Owner s Responsibilities Provide proof of purchase sales receipt Provide normal care and maintenance as outlined in this manual Make product reasonably accessible for service Pay for freight labor and travel expenses Pay for premium service costs for service outside servicer s normal business hours Pay for service calls related to product installation and maintenance This Warranty Does Not Cover Damage Caused By Improper installation Misuse of equipment e Negligent servicing Improper applications Preventative maintenance Unauthorized modifications Improper electrical supply Failure to follow manufacturer s instructions and rating plate information Accidents or other events beyond Fedders control ENTIRE WARRANTY THE ABOVE CONTAINS THE SOLE AND EXCLUSIVE STATEMENT OF THE EXPRESS WARRANTIES AND ASSOCIATED REMEDIES AVAILABLE WITH THE PRODUCTS DESCRIBED OTHER EXPRESS WARRANTIES AR
12. dditional SUCTION accessories LINE A WARNING A IF THE INSTALLER IS MAKING UP HIS OWN LINE SETS HE MUST MAKE SURE THE TUBING IS CLEAN OF ANY IMPURITIES OR MOISTURE USE ONLY CLEAN AIR CONDITIONING AND REFRIGERATION GRADE SEAMLESS COPPER TUBING PLUMBING GRADE COPPER 15 INADEQUATE TO ENSURE A CLEAN SYSTEM FREE OF ANY CONTAMINANTS PURGING WITH DRY NITROGEN AND A DEEP VACUUM IS NECESSARY ON ALL SWEAT TYPE MODELS AND ON THE UNCHARGED PORTIONS OF ALL MODELS NOT INCORPORATING PRECHARGED LINES IT IS DESIRABLE TO PULL A VACUUM TO 1 000 MICRONS 29 96 HG TO ENSURE TROUBLE FREE OPERATION Precautions Refer to the chart below for the minimum recommended tube outside diameter sizes on liquid and suction lines Ensure that vapor and liquid tube diameters are appropriate for unit capacity Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends Undersized line sets will increase the refrigerant pressure drop between the indoor evaporator and outdoor unit resulting in a decrease in system capacity Oversizing the line sets may result in excessive refrigerant charge thereby making the system more susceptible to liquid migration When passing refrigerant tubes through the wall seal opening with RTV or other pliable silicon based caulk Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls Do not suspend refrigerant tubing
13. ensing unit should be located outdoors as close as possible to the evaporator Consider the following factors Clearances The air inlet should be located at least 12 from a wall or other obstruction for unrestricted air flow The air outlet should be located so as to direct discharged air away from the building Three feet of clearance around the unit and a minimum of six feet clearance above the unit is required to avoid recirculation of condenser discharge air on vertical discharge models Avoid locating unit under low overhanging roofs Support Mount the unit on a sturdy base approximately four to six inches above the ground In areas known for snow accumulation the unit should be elevated at least 18 above the ground A concrete slab is recommended Concrete slab should not contact the building foundation to prevent possible sound or vibration transmission Rooftop installation is acceptable in areas of low snow accumulations provided the roof will support the unit and provisions are made for water drainage and the noise or vibration through the structure Exposure If practical unit should be located on the south side of the structure away from northerly winds to minimize the effects of blowing snowdrifts and freezing rain A wind screen or wind block can also be used Placement of the unit should be in a well drained area or the unit must be supported high enough so run off will not enter the unit Avoid installatio
14. gh performance and to minimize possible equipment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as coastal applications WARNING BE SURE THE UNIT DISCONNECT 15 IN THE POSITION AND THAT ALL ELECTRICAL POWER TO THE UNIT IS TURNED OFF BEFORE CLEANING THE SYSTEM OFF 1 Keep the outdoor unit clean Wash it down with a garden hose if necessary A WARNING A SERIOUS PERSONAL INJURY OR DEATH MAY RESULT IF WATER SPRAY IS DIRECTED TOWARD LIVE ELECTRICAL CONNECTIONS OR POWER SOURCES 2 Remove any loose grass leaves papers etc from the area around the condenser coil These could reduce the air supply through the coil and reduce the amount of cooling 3 Always install and keep system filters clean Consult your licensed Contractor for filter replacement schedules and instructions 10 CONDENSING UNIT NOMENCLATURE CH 24 A B D Poduct Type Air Conditoner CH Heat Pump Nominal Capacity 18 18000 BTU H 5 28 kW 24 24000 BTU H 7 03 kW 30 30000 BTU H 8 79 kW 36 36000 BTU H 10 55 kW 42 42000 BTU H 12 31 kW 48 48000 BTU H 14 07 kW 60 60000 BTU H 17 5 kW Series A Chassis Size B 21 1 2 W x 21 1 2 C 29 1 2 W x 29 1 2 D x H 1 V F Brand F Fedders Fitting Type V Sweat Electrical Designation
15. lpful in avoiding any needless service costs or operational problems Included in these instructions are safety rules installation operation and maintenance instructions Only the highest quality components were used in the construction of your unit With proper maintenance your system should provide years of economical trouble free service RECOGNIZE SAFETY SYMBOLS WORDS AND LABELS What You Need To Know About Safety Instructions Warning and Important Safety Instructions appearing in this manual are not meant to cover all possible conditions and situations that may occur Common sense caution and care must be exercised when operating or cleaning tools and equipment Always contact your dealer distributor service agent or manufacturer about problems or conditions you do not understand A this is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death A DANGER A DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates potentially hazardous situation which if not avoided could result in death or serious injury A CAUTION A CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury CAUTION CAUTION used without the safety alert symbol indicates a p
16. n the adjusting flange 1 4 turn counter clockwise The flange will come to a stop and the seal is now complete Adjusting flange Open valve CONNECT REFRIGERANT PIPING The following should be followed when installing refrigerant piping Comply with all local state and federal codes and or regulations pertaining to this type of equipment and its installation 1 Run the tubing by the most direct route and support every few feet Do not run the lines underground unless they are in a chase Leave enough material between structure and unit to absorb vibration 2 Insulate the vapor line to prevent sweating and line loss In underground chases the vapor line should be insulated to provide vibration isolation between the vapor and liquid line A minimum of 3 8 insulation is recommended in conditioned space and 1 2 to 3 4 in unconditioned space Ensure that tubing insulation is pliable and completely surrounds vapor tube 3 In general the piping should be sloped toward the outdoor unit to prevent oil trapping Where vertical risers occur a suction line trap should be located at the base of the riser to assure proper oil return A WARNING A REFRIGERANT LINE LENGTH MUST NOT EXCEED 75 ON HORIZONTAL RUNS AND 40 ON VERTICAL RISERS OUTDOOR SECTION LIQUID LINE Na Can only be 20 vertical N INDOOR separation COIL without x a
17. ndoor coil before TXV In heating mode take reading at the liquid line service valve on outdoor unit 3 Measure the liquid line temperature on the liquid line T3 In cooling mode take reading at the indoor coil before TXV In heating mode take reading at the liquid line service valve on outdoor unit 4 Subtract from T2 T2 T3 This is the subcooling value Compare this value and the outdoor temperature T1 to the charts below If the value is below the line add refrigerant If the value is above the line remove refrigerant charge When removing refrigerant always use standard reclaim procedures Adjusting TXV For the majority of installations no adjustment to the TXV setting is required However if the measured superheat at the indoor coil is less than 4 or greater than 8 an adjustment is required The adjustment stem is at the base of the valve under the flare nut To increase superheat tighten the stem clockwise and to decrease superheat back out the stem counter clockwise Use a 1 4 refrigeration service wrench for this function 9 SUB COOLING CHARTS FOR UNITS WITH COOLING MODE N SUBCOOLING T2 T3 D 60 F 70F 80 F 90F 100 F 110 F OUTDOOR TEMPERATURE 1 HEATING MODE 37 35 33 31 29 27 25 23 21 10 F 20 F 30 F 40 F 50 F 60 F OUTDOOR TEMPERATURE F 1 All values are for reference only and may vary up or down
18. ns under roof overhangs without guttering Water draining from the roof onto the unit could produce excessive noise and may cause ice to build up on the coil or fan during cold weather Locate unit away from windows patios decks etc where unit operation sound may disturb customer Do not locate where heat lint or exhaust fumes will be discharged on the unit as from dryer or furnace vent SE ES GS Rain Gutters a Six feet clearance ____ _ _ above the unit T Three feet clearance se Thies feet clearance Proximity to Evaporator Locating the condenser as close as possible to the evaporator will increase the system capacities by reducing the line set refrigerant pressure drop and will make the system less susceptible to liquid migrations due to less refrigerant charge Electrical Connections BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK INJURY DEATH OR DAMAGE TO EQUIPMENT ELECTRICAL EQUIPMENT SHOULD BE INSTALLED BY A QUALIFIED LICENSED ELECTRICIAN IMPROPER ELECTRICAL HOOK UP MAY DAMAGE EQUIPMENT CAN CREATE A HAZARD CAUSE PERSONAL INJURY OR DEATH AND WILL VOID THE WARRANTY 1 The installer shall check available power to make certain it matches the unit rating plate located inside control box cover and tha
19. odes Electrical Connections cont Connect control wiring 1 Route 24 volt control wires through control wiring grommet and connect leads to control wiring 2 Use No 18 AWG color coded insulated wire If thermostat is located more than 100 ft from unit as measured along the control voltage wires use No 16 AWG wire to avoid excessive voltage drop 3 All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power Note Use of available 24 volt accessories may exceed the minimum power requirement Determine total transformer load and increase the transformer capacity or split the load with an accessory transformer as required Final Wiring Check Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc SERVICE VALVE CONNECTIONS Braze Joints 1 Remove the valve core from the schrader port Wrap a quenching cloth around the service valve Clean and flux the joint and braze with brazing rod containing at least 10 silver such as silphos type brazing rod DO NOT USE SOFT SOLDER Replace the schrader valve core after brazing has cooled 2 Leak check all braze joints at approximately 80 psi pressure purge and evacuate the lines A WARNING A DO NOT USE AIR TO LEAK CHECK BRA
20. otentially hazardous situation which if not avoided may result in property damage NOTES TO INSTALLER The words SHALL and MUST indicate a requirement which is essential to satisfactory and safe product performance The words SHOULD and MAY indicate a recommendation or advice which is not essential and not required but which may be useful or helpful Installation and service personnel are required by some locales to be licensed Persons not qualified SHALL NOT install this equipment nor interpret these instructions This installation and maintenance manual is provided to ensure the proper installation and the most satisfactory performance of your equipment The instructions contained herein SHALL NOT be deemed to extend modify alter or expand any of the representations contained in the limited warranty A QUALIFIED INSTALLER MUST PERFORM INSTALLATION AND SERVICE IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE MAINTENANCE OR USE CAN CAUSE EXPLOSION FIRE ELECTRICAL SHOCK OR OTHER CONDITIONS WHICH MAY CAUSE DEATH PERSONAL INJURY OR PROPERTY DAMAGE AND WILL VOID THE WARRANTY REFER TO THIS MANUAL FOR PROPER INSTRUCTIONS DO NOT DESTROY THIS MANUAL PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS OR OTHER COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS OR ANY OTHER EQUIPMENT BEFORE PERF
21. res over 80 F The unit indoor design temperature range is between 65 F and 80 F in the heating mode Never operate the unit in the cooling mode at outdoor temperatures below 60 F without a low ambient control Never operate the unit in the heating mode at outdoor temperatures above 70 F Auxiliary heat Most heat pump installations include electric resistance heat for auxiliary heat when the outdoor temperature is too low for the heat pump to provide enough heat and for emergency heat the outdoor unit is not working On a properly sized installation the heat pump will supply all the heat needed during cool weather As the temperature drops the heat output from the heat pump will be reduced The auxiliary heat installed in the system will come on as needed to make up for this reduction of heat output The need for auxiliary heat is detected by the thermostat If the thermostat senses a temperature fall of more than 2 F below the set point the auxiliary heat will turn on For this reason setting the thermostat to the desired temperature and not changing the temperature during the day can be more economical than varying the thermostat setting If it is intended to set the temperature back at night consider that when the temperature is turned back up to the normal setting the system will be operating during the coldest time of the day early morning hours and may require auxiliary heat if the increase in temperature is above 2
22. t constant voltage can be maintained to the unit Unsatisfactory performance would otherwise result The local power company should be contacted regarding any problems or questions concerning power supply Ei Control box cover Opening for line voltage conduit or cable Opening for low voltage wiring Wiring diagram and rating ae plate are located inside control box cover N Install a line service disconnect switch within sight of the condensing unit The line voltage service wiring for the condensing unit should include a fused disconnect switch ad Use correct wire size and fuse size To ensure that adequate voltage will be available at the condensing unit the line voltage service wiring must be of adequate size Minimum recommended wire ampacities and maximum fuse sizes are listed on the unit name plate A Two holes are provided in the control box a One is for the connection of the line voltage conduit or cable The hole is sized for 3 4 conduit b One is for low voltage wiring Refer to the wiring diagram attached to electrical box cover for connection 5 Be sure to ground the condensing unit by securing the ground wire to the grounding lug inside the control box 6 Be sure to follow National Electrical Code and all local c
Download Pdf Manuals
Related Search
Related Contents
平成22年1月29日公表 Bedienungs-Wartungsanleitung-SanoClean Instruction Manual 取扱説明書 - ソニー製品情報 NucleoMag® 96 PCR - MACHEREY Bilora 204 screen protector User Manual Descargar Guía de Primeros Pasos Copyright © All rights reserved.
Failed to retrieve file