Emerson 1000 Power Supply User Manual
Contents
1. 24 Table 9 Troubleshooting problems causes and solutions 26 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and mainte nance of the UPS ntended for installation in a temperature controlled indoor area free of conductive contaminants Maximum ambient temperature 104 F 40 C Read this manual thoroughly before attempting to install or operate this UPS The equipment can be installed and operated by individuals without previous training Size of Branch Circuit Overcurrent Protection A CAUTION To reduce the risk of fire connect PS8000RT3 120XR models only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code ANSI NFPA 70 Other Liebert PSI models must be connected to a circuit with 20 amperes maximum branch circuit overcurrent protection A WARNING Operate the UPS only from a properly grounded earthed 110 127VAC 50Hz or 60Hz AC supply Some components are live even when AC power is disconnected For service contact a properly trained and qualified technician Do not remove the cover the UPS has no user serviceable parts inside except the internal battery pack A WARNING Although the UPS has been designed and manufactured to ensure personal safety improper u
2. 19 6 4 UPS Comm nications i eoram s Rat ca chc e kama umn aa Cant e 20 6 5 UPS Inverter Transfer Voltage Configurations 20 7 0 BATTERY MAINTENANCE ewe POSES pa puwa su CAE Oe 21 7 1 Battery Charging Storage sac cu ve id enn tot hata E aee aue des 21 7 2 Internal Battery Replacement Procedure 21 8 0 SPECIFICATIONS Su za e 86 ee RIPE WWW A ERA M w a Ou E 22 9 0 TROUBLESHOOTING cid cu x ox ata aaa ake mate C alae eee eS 26 FIGURES Figure Front views0t u nsa p ncaa be lec gt esce a alea ied a ds menda d OU ae tte ble 4 Figure 2 1000 and 1500 rear view hr s 4 meures 2200 ear views sca auch they uo ou sts dalle oat oe andes ste una uth 5 Figured n S000 rear View sdb esee he eee ties ee cok Gee eos a a tao Wena hh duh te a tee 5 Figure 5 Accessories oras cement e cent Ure dod aS 6 Figure6 Placing the Liebert ehh raa 7 Figure7 Tower configuration attach Tower Stands 8 Figure8 Convert the Liebert PSI XR for rack installation 9 Figure9 Orienting the UPS display 222 sy uo uka eee hae 10 Figure 10 Connect input power and load nasr eiae aaa
3. Run times are in minutes assume fully charged batteries and are typical at 77 F 25 C with resistive loads 25 Troubleshooting 9 0 TROUBLESHOOTING The information below indicates various symptoms a user may encounter if the Liebert PSI XR expe riences a problem See Table 9 for suggested solutions 1 An alarm sounds alerting that the UPS requires attention The alarm can be silenced except for low battery overload warning and fault 2 Oneor more additional indicators will be illuminated to provide a diagnostic aid to the operator as described below If the UPS fails to operate properly turn Off the unit and repeat the steps in 3 0 Installation If the problem persists refer to Table 9 Table 9 Troubleshooting problems causes and solutions Problem UPS will not start Cause Short circuit Solution Check the circuit breaker on the rear of the UPS If it is tripped reset it and restart the UPS For help contact your local dealer local Emerson representative or Channel Support Applications Battery is disconnected or completely discharged Check for proper connection of battery or batteries UPS starts on battery but will not switch to AC dark start UPS not plugged in Plug in the power cord securely Circuit breaker tripped Reset the circuit breaker and restart the UPS AC overvoltage Wait until voltage drops to an appropriate level o
4. Network surge Network surge protection OUT jack protection IN Jack 3 8 Connect Communication Interface Determine what type of communication connection to use to manage the UPS The Liebert PSI XR can be monitored with any of these communication methods Contact closure USB SNMP requires optional IS WEBRTS card Connect the appropriate factory supplied cable to the interface port on the rear of the UPS and to the computer interface port See 3 9 Set Up Liebert MultiLink software for details and installation information Also refer to 6 4 UPS Communications Figure 12 Connect communication interface 11 Installation 3 9 3 10 Set Up Liebert MultiLink software To start using Liebert MultiLink software and user manual available at multilink liebert com Install the software See the Liebert MultiLink quick start guide or user manual for installation instructions Connect one end of the USB cable supplied to the USB port on the rear of the UPS Connect the other end to a USB port on the computer See the Liebert MultiLink user manual for operating instructions Emerson recommends connecting the USB cable directly the computer WITHOUT using USB hub EPO Switch The Liebert PSI XR is equipped with an Emergency Power Off EPO switch The user must supply a means of interfacing with the EPO circuit to allow disconnecting the UPS input feeder break
5. ee ee eee eee 15 4 1 Control BUttOns A dies D egrave Ga hae er SN Dedi carn ohare te e a tle 16 4 1 1 On Alarm Silence Manual Self Diagnostic Test 16 41 2 Oft Boom dare e sio A sae Roe oe aleae ret od dons du bee 16 4 2 Status Indicators ae ry v eu Ru C eta S LA CORE a ee 16 4 21 Status Change Button ud dee ere ee ee erate ON BLOB NES 16 4 2 2 Load Level Indicator ek Ee ue e e euer ee ee bead ee te he 16 4 2 8 Battery Level Indicator y u u uka ec enn ene a S Qan ayaman 17 4 2 4 UPS Status Indicators ocea a e i e en e hh S QU 17 5 0 OPERATIONAL 5 43 58 Oe eee ea kta os Rcx ee e e Rod ardt 18 5 1 Normal Mod 4a sue c tace eS UD den RR M ata opa 18 5 2 Boost Modes uev omes s Rr e s 18 5 3 Battery Ao PRU VAR EUR ERE PCT AERO USE ENS 18 5 4 Battery Recharge Operation uya usa utu ipu a Pu eens 18 6 0 COMMUNICATION aca dg rc at ec c OE S E wu S wee er Behn a ave AC RR a 19 6 1 D BO Connector u ooi tdt dera adds A Cand aes le Ba eet CA d 19 6 2 Remote Shutdown Via the DB 9 19 6 2 1 Mode Shutdown Via Pins5B amp 6 19 6 2 2 Battery Mode Shutdown ViaPins4 amp 5 19 6 3 Network Surge Protection Connectors
6. AC Power For Business Critical Continuity Liebert PSI User Manual 1000 1500 2200 3000 120VAC gt EMERSON TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS lees hinh nnns 1 GLOSSARY OF SYMBOLS uya u See ole Ow Pe eG ERE Q 3 1 0 INTRODUCTIONS 3 scd ciii ade Qo RU Scene REC wa de UR COR Gl o dC C e ER o na cab e d 4 2 0 WHAT S INCEUDED i2 ru S GERE EE CC CC ae Ba e ERO OR aD d RU 6 3 0 INSTALLATION ed odor ee Veneta ap e PL uM cire h We 7 3 1 Preparations cou sese k ua SU Ve BOS A OS od w ESAs 7 3 2 Tower UPS Installatiot er fe coh a Su a aa as bares EEE WEE E ARS 8 3 8 Rack Mount UPS Conversion and Installation 9 3 4 Orient Display for Installation 10 3 5 Charge Batteries and Perform Battery 10 3 6 Connect Input Power and es 10 9 7 Connect Network Surge protection 11 3 8 Connect Communication Interface NER 11 3 9 Set Up Liebert MultiLink software 12 DID DEPO SWIUGDUS utaya phu n aa Te Spe Marte E PACA SA SY am Ee 12 3 11 External Battery Cabinet Installation 13 4 0 CONTROLS AND
7. Do not connect equipment that could overload the UPS or demand half wave rectification from the UPS such as electric drills vacuum cleaners laserjet printers and hair dryers GLOSSARY OF SYMBOLS A A PbH2SO4 mS Risk of electrical shock Indicates caution followed by important instructions Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Alarm Silence Manual Self Diagnostic Test OFF Status Change Button Introduction 1 0 INTRODUCTION The Liebert PSI XR is a 2U line interactive UPS that may be installed in a rack or used as a tower UPS Status indicators on the front of the Liebert PSI XR display load level battery level buck boost site wiring fault overload battery status and UPS operation Controls include a combination On Alarm Silence Manual Self Diagnostic Test button an Off button and a Status Change button The Liebert PSI XR has USB DB 9 contact closure and Liebert IntelliSlot ports The DB 9 and USB ports provide detailed operating information including voltages currents and alarm status to the host system when used in conjunction with Liebert MultiLink software The Liebert PSI XR is compliant with the Restriction of Hazardous Substances Directive ROHS prohibiting use of six hazardous materials manufacturing of electronics including lead free so
8. 16 90 43 26 17 14 100 32 18 15 12 10 439 357 242 205 20 275 212 152 127 30 200 150 111 92 40 157 116 82 68 50 129 95 68 56 60 110 76 57 47 70 96 65 50 33 80 80 58 44 30 90 71 52 32 26 100 65 47 29 18 10 614 492 322 267 20 385 291 202 166 30 280 207 147 120 40 220 160 116 94 50 181 131 96 73 60 154 111 77 62 70 134 95 67 54 80 119 79 59 47 90 106 71 53 43 100 96 64 48 31 Run times are in minutes assume fully charged batteries and are typical at 77 F 25 C with resistive loads 24 Specifications Table 8 Liebert PSI XR battery run times continued Number of Batteries Internal battery 4 External Battery Cabinets Internal battery 5 External Battery Cabinets Internal battery 6 External Battery Cabinets Load 1000 1500 2200 3000 10 790 627 483 330 20 494 371 303 204 30 360 264 221 148 40 283 204 174 116 50 233 167 143 95 60 198 141 122 76 70 172 122 106 66 80 152 108 94 59 90 137 96 79 52 100 124 82 72 48 10 965 762 564 392 20 605 452 354 243 30 440 320 258 176 40 346 248 203 138 50 265 203 167 113 60 242 171 142 96 70 211 148 124 79 80 186 131 110 70 90 167 117 98 62 100 151 106 84 56 10 1140 897 644 454 20 714 531 405 281 30 520 377 295 204 40 408 292 232 160 50 337 239 191 131 60 286 202 163 112 70 249 175 142 97 80 220 154 125 81 90 197 138 112 72 100 179 124 102 65
9. UPS Operation in Battery Mode 11 LED 11 UPS Fault UPS Fault 15 Controls and Indicators 4 1 4 2 4 2 2 Control Buttons 4 1 4 On Alarm Silence Manual Self Diagnostic Test This button controls output power to connected load s It has three functions On Alarm Silence Manual Self Diagnostic Test ON Start the UPS by pressing this button for more than seconds then releasing the button an alarm will sound briefly If the ON button is pressed and utility is outside input parameters the UPS will start on battery dark start Alarm Silence Silence a battery mode audible alarm by pressing this button for longer than one second then releasing it Manual Self Diagnostic Test To initiate a Manual Self Diagnostic press this button for at least three 3 seconds while operating from utility power UPS will switch to Battery Mode to detect bat tery voltage and whether the UPS is operating normally If LED indicates the battery is weak Allow the UPS to recharge the batteries for 8 hours Retest the battery after recharge If LED still indicates the battery is weak after the battery has been retested contact your local dealer local Emerson representative or Channel Support Applications If LED indicates a Battery Fault Contact your local dealer local Emerson representative or Channel Support Applications If LED indicates a UPS Fault Remove the load retest the self diagnostic test
10. 00RT3120XRW PS2200RT3120XRW PS1500RT3 120XR PS3000RT3 120XR PS1500RT3120XRW PS3000RT3120XRW Unit 17 3 x 19 3 x 3 5 440 x 490 5 x 88 Shipping 22 x 26 6 x 9 560 x 675 x 228 Weight Ib kg Unit 64 29 Shipping 73 33 Batteries Type Valve regulated nonspillable lead acid Quantity x Voltage x Ah 8 x 12 x 7 2 8x 12x 7 2 Manufacturer CSB YUASA or Equivalent Environmental Operating Temperature F C 32 to 104 0 to 40 Storage Temperature F C 5 to 104 15 to 40 Relative Humidity 0 to 90 non condensing Maximum Operating Altitude 10 000 ft 3000m Agency Safety UL 1778 c UL Listed Emissions FCC Part 15 Class A Transportation ISTA Procedure 1A Certification 23 Specifications Table 8 Liebert PSI XR battery run times Number of Batteries Internal Battery Internal battery 1 External Battery Cabinets Internal battery 2 External Battery Cabinets Internal battery 3 External Battery Cabinets Load 1000 1500 2200 3000 10 83 82 76 75 20 52 48 48 47 30 31 28 28 28 40 18 17 17 17 50 15 13 14 13 60 12 11 11 11 70 11 9 9 9 80 7 8 7 90 6 7 6 100 6 5 5 5 10 263 222 161 143 20 165 131 101 83 30 120 93 69 60 40 95 68 55 47 50 73 56 45 32 60 62 47 31 27 70 54 33 27 18 80 48 29 18
11. EON uc aa a Q aY Uwe 10 Figure 11 Connect network surge 11 Figure 12 Connect communication interface 11 Figure 13 EPO connection for normally open operation 12 Figure 14 Install the external battery cabinet in tower installation 13 Figure 15 Connect battery cabinets to UPS 14 Figure 16 Display and status indicators 15 Figure 17 DIP switch settings for 120V system 20 Figure 18 Battery replacement o hh 21 TABLES Table 1 Battery cabinet connector color 13 Table 2 Display and status indicators function 15 Table 3 Status indicators color illumination mode 17 Table 4 DB 9 pin assignmerbt g supi atau arta E ER D NOR REV a SEN AU e P ed 19 Table 5 Voltage configurations cues veu E ERR RR Mu uua e RE eae uris 20 Table 6 Liebert PSI XR specifications s 22 Table 7 Battery cabinet specifications cese es 23 Table 8 Liebert PSI XR battery run times
12. Status LED 1 LED 2 LED 3 LED 4 LED 5 LED 9 LED 10 LED 11 Green Steady Green Green Flashes Steady Normal Mode AVR Boost Green Green AVR Buck Flashes Steady Battery Mode Yellow dark start Steady Yellow Flashes Weak Battery Yellow Site Wiring Fault Flashes Red Overload Flashes Battery Fault Yellow Red Shutdown Steady Steady Overload Red Red Shutdown Steady Steady UPS Output Abnormal Shutdown Yellow Red Steady Steady 17 Operational Modes 5 0 OPERATIONAL MODES 5 1 5 2 5 3 5 4 Normal Mode When the UPS is in Normal Mode the Normal Mode Indicator illuminates green Buck Boost Mode The Automatic Voltage Regulator AVR circuitry compensates for fluctuations in utility power such as voltage surges and sags When the Liebert PSI XR detects an abnormality it raises the undervolt age boost or lowers the overvoltage buck as needed The AVR operates automatically and main tains the output voltage to the connected equipment without utilizing the batteries LED 1 flashes green and LED 9 illuminates steady green when the UPS is in Boost Mode LED 2 flashes green and LED 9 illuminates steady green when the UPS is in Buck Mode see 9 0 Trouble shooting for details Battery Mode The UPS switches to Battery Mode in the event of an extreme input voltage frequency condition or utility failure When the
13. UPS is in Battery Mode the Battery Indicator illuminates amber and an alarm sounds at two second intervals As capacity decreases fewer indicators remain illuminated When a Low Battery condition occurs the Battery Indicator flashes amber and an alarm sounds at one second intervals Refer to Table 8 for approximate battery run times Battery Recharge Operation Once utility power is restored the UPS resumes normal operation and the Battery Charger begins recharging the batteries 18 Communication 6 0 COMMUNICATION 6 1 DB 9 Connector The UPS has a DB 9 9 pin female connector on the rear to allow UPS status communications with a computer running Liebert MultiLink software in contact closure mode The connection provides On Battery and Low Battery notification When power is interrupted and battery power is low Liebert MultiLink software can signal the host computer to gracefully shut down the operating system Table 4 DB 9 pin assignment DB 9 Pin Assignment Description Low Battery open collector 2 UPS TxD not used 3 UPS RxD not used 4 Remote Shutdown 5 12V on battery operation 5 Common 6 Output Off short to Pin 5 non latching any mode operation 7 Low Battery open emitter 8 Utility Fail open emitter 9 Utility Fail open collector Pin Assignment Collector to Emitter Coe Eun 6 2 Remote Shutdown Via the DB 9 Connector The Liebert PSI XR can be shut down r
14. aker 15A Output Circuit Breaker Receptacles 1 and 2 for Receptacles 5 amp 6 15A Output Circuit Breaker for Receptacles 3 amp 4 Receptacles 3 and 4 NEMA 5 15R Receptacles 1 and 2 30A Input NEMA 5 20R T Slot Receptacles Circuit Breaker 5 and 6 NEMA 5 15R DC 48V External Battery Cabinet Connector 15A Output Circuit Breaker for Receptacles 5 amp 6 20A Output Circuit Breaker Receptacles 1 and 2 What s Included 20 WhHAT S INCLUDED The Liebert PSI XR is shipped with the following items Multi Language User Manual on CD Liebert MultiLink Software and User Manual downloadable at multilink liebert com Contact Closure ML9P9S Cable USB Cable Tower Stands Mounting Hardware Rack Mount Handles Fixed Mounting Rails EPO Connector Battery UPS Tab Figure5 Accessories Z 2 h w J Y Tower Stands Contact Closure USB cable ML9P9S Cable 6 ft 1 8m 6 ft 1 8m Rack Mount Handles Mounting Hardware Screws and Washers Mounting Rails EPO Connector Battery UPS Tab Installation 3 0 INSTALLATION 3 1 Preparation A CAUTION The UPS and battery cabinets are heavy see Table 6 and Table 7 Take proper precautions when lifting or moving either the UPS or battery cabinets The Liebert PSI XR may be installed in either a tower or rack configuration Determine the method that suits the application and proceed Deci
15. ation 108 Gloucester Road All rights reserved throughout the world Specifications subject to change Wanchai without notice Liebert is a registered trademark of Liebert Corporation 852 Y 9 All names referred to are trademarks or registered trademarks of their respective owners Fax 852 2519 9210 1 23315 REVO3 07 09 Emerson Network Power The global leader in enabling Business Critical Continuity EmersonNetworkPower com AC Power l Embedded Computing l Outside Plant Racks amp Integrated Cabinets Connectivity I Embedded Power Power Switching amp Controls Services DC Power I Monitoring Precision Cooling Surge Protection Business Critical Continuity Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co 2008 Emerson Electric Co
16. connectors that are a different color from the battery connector on the UPS Table 1 Battery cabinet connector color key UPS Model Nominal System Voltage connector color External Battery Cabine Model PS1000RT3 120XR PS1000RT3120XRW PS1500RT3 120XR PS1500RT3120XRW PS2200RT3 120XR PS2200RT3120XRW PS3000RT3 120XR PS3000RT3120XRW 24VDC Red PSRT3 24VBXR 48VDC Gray PSRT3 48VBXR 13 Installation Figure 15 Connect battery cabinets to UPS See Table 8 for approximate battery run times 14 Controls and Indicators 4 0 CONTROLS AND INDICATORS Buttons on the front panel display control the Liebert PSI XR Eight LEDs indicate the UPS s status Refer to Figure 16 and Table 2 Figure 16 Display and status indicators Load Level Battery Level 4 6 7 8 9 10 11 Table 2 Display and status indicators function legend Item Name Status Indicators Description 1 LED 1 AVR Boost UPS Operation in AVR Boost Mode 2 LED 2 AVR Buck UPS Operation in AVR Buck Mode 3 LED 3 Battery Condition Battery Fault Weak 4 LED 4 Grounding Site Wiring Fault UPS Grounding Site Wiring Fault 5 LED 5 Overload UPS Overload 1to5 Load Battery Level Indicate Load Battery Level 6 Status Change Button P BEI rae BU Level Indicators 7 OFF Button UPS Off 8 ON Button eet Gane Normal Mode 9 LED 9 Normal Mode UPS Operation in Normal Mode 10 LED 10 Battery Mode
17. de where to install the Liebert PSI XR The UPS must be installed indoors in a controlled envi ronment Place it in an area with unrestricted airflow around the unit away from water flammable liquids gases corrosives and conductive contaminants see Figure 6 Maintain a minimum clearance of 12 inches 305mm in the front and rear of the UPS Maintain an ambient temperature range of 32 F to 104 F 0 C to 40 C Figure6 Placing the Liebert PSI XR 32 F 0 C 104F 40 C Relative humidity 0 90 non condensing Installation 3 2 Tower UPS Installation See Figure 7 when using the Liebert PSI XR in a tower configuration Figure7 Tower configuration attach Tower Stands Step 2 Installation 3 3 Rack Mount UPS Conversion and Installation See Figure 8 when installing the Liebert PSI XR in a rack External battery cabinets are installed in same manner Figure8 Convert the Liebert PSI XR for rack installation Step 1 Step 2 LE A WARNING Placing heavy equipment near the top of a rack may increase the risk of tipping Place the UPS and battery cabinet if one is being used in the bottom of the rack A CAUTION Lifting equipment into rack may be a two person job depending on weight of equipment NOTICE When rack mounted the UPS must be supported by a shelf slide rails brackets or fixed rails on each side The rack mount handles WILL NOT support the weight of the UPS They a
18. ds connecting the UPS to input power for at least 8 hours every four to six months to keep the batteries charged Emerson recommends performing a monthly manual self diagnostic test via the Web card or the front panel display Internal Battery Replacement Procedure NOTICE This UPS is equipped with internal batteries that the user can replace without shutting down the UPS or connected loads hot swappable Caution must be exercised when replacing the batteries because the load is unprotected from power fluctuations and power failures To replace the batteries Remove the two screws on the left side of the front bezel Pull the front bezel off the UPS Remove the screw on the battery connector holder Remove the two screws on the battery bracket Disconnect the two slotted red gray and black battery connectors Grasp the battery pack assembly by the handle and pull it out of the front of the UPS Unpack the new battery assembly taking care not to destroy the packing Compare the new and old battery assemblies to make sure they are the same If so proceed with replacement If they are different STOP and contact your local dealer local Emerson representative or Channel Support Applications 9 Slide the new battery pack into the UPS 10 Reattach the battery bracket with the two screws 11 Reconnect the slotted red gray and black battery connectors 12 Reinsert the screw on the battery connector holder 13 Reattach the fro
19. emotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB 9 connector 6 2 1 Any Mode Shutdown Via Pins 5 amp 6 When Pin 6 is shorted to Pin 5 the UPS output is shut Off no matter what mode the UPS 1s operating in The UPS cannot be started as long as the pins are shorted When the short is removed the UPS output can be enabled by pressing the ON Alarm Silence Manual Self Diagnostic Test button 6 2 2 Battery Mode Shutdown Via Pins 4 amp 5 While the UPS is operating on battery a 5 12VDC signal for 2 seconds or longer is required to signal a shutdown Signals for less than 2 seconds are ignored After Pin 4 receives the shutdown signal a 2 minute shutdown timer begins a countdown The shut down timer cannot be stopped If utility power returns during the 2 minute countdown the shutdown timer continues until the end of 2 minutes and the UPS turns Off The UPS will restart 10 seconds after utility power returns 6 3 Network Surge Protection Connectors Network in and out connectors on the rear of the UPS provide transient voltage surge suppression TVSS for network devices 19 Communication 6 4 UPS Communications The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication and monitoring options Liebert MultiLink software continually monitors the UPS and can shut down your computer or server via USB contact closure and SNMP via IS WEBRTS card in the event of an extended power fail
20. er to interrupt all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations Figure 13 EPO connection for normally open operation 2 Ground 1 Short Pin 1 and Pin 2 to enable the EPO function 12 Installation 3 11 External Battery Cabinet Installation Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS The batteries have a maximum run time of three hours at full load 1 Install the external battery cabinet in tower or rack configuration see Figure 14 or 3 3 Rack Mount UPS Conversion and Installation 2 Connect the external battery cabinet cable to the rear of the external battery cabinet then to the rear of the UPS see Figure 15 Figure 14 Install the external battery cabinet in tower installation Connect the top of the UPS to the top of the battery cabinet with the Battery UPS Tab and hardware If two or more battery cabinets are used in a tower setup the tower stand must be extended with the spacers included with each battery cabinet Connect tower stand and set the UPS and battery cabinet in them check to ensure stability NOTICE External battery cabinet power connectors are color coded as noted in Table 1 Do not try to install external battery cabinets with
21. five seconds after the Status Change button is pressed The LEDs show the battery capacity as a range 596 The LEDs battery level meanings and colors are LED 1 LED 2 LED 3 LED 4 LED 5 100 7696 Green 75 51 Green 50 26 Yellow 25 11 Yellow 10 or less Red UPS Status Indicators LEDs on the display panel illuminate with a steady glow or flash to indicate the UPS s status Normal Mode The Normal Mode indicator illuminates LED 9 with a steady glow when utility power is available and within the input specifications Battery Mode The Battery Indicator illuminates LED 10 with a steady glow when the UPS is operating on battery AVR Boost AVR Buck When the UPS is in AVR Boost Buck Mode the LED display will indicate the relative load level on the output of the UPS and will flash LED 1 boost or LED 2 buck to indi cate which mode the UPS is in Weak Battery When the UPS battery voltage is low the LED display will indicate the relative load level on the output of the UPS and LED 8 will flash as a warning Site Wiring Fault In case of a site wiring fault the LED display will indicate the relative load level on the output of the UPS and LED 4 will flash as a warning Overload When UPS operates in overload status the LED display will indicate the relative load level on the output of the UPS and LED 5 will flash as a warning Table 3 Status indicators color illumination mode
22. for use with life sup port and other designated critical devices Maximum load must not exceed that shown on the UPS rating label If uncertain consult your local dealer local Emerson Network Power representative or Channel Support Applications When installing the UPS or making input and output connections comply with all relevant safety codes and standards e g UL 1778 Placing magnetic storage media on top of the UPS may result in data corruption ELECTROMAGNETIC COMPATIBILITY The Liebert PSI XR complies with part 15 of the FCC Rules Operation is subject to the following two conditions This device may not cause harmful interference and This device must accept any interference received including interference that may cause unde sired operation This equipment uses generates and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference with radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna ncrease the separation between the UPS and the receiver Connect the UPS to an outlet on a circuit different from the one the receiver is connected to NOTICE
23. if LED indicated UPS Fault Contact your local dealer local Emerson representative or Channel Support Applica tions Refer to Figure 16 and Table 2 for details about the LEDs meaning 4 1 2 Off Button When the UPS is operating in either Normal Mode or Battery Mode pressing the Off button for more than three seconds will shut down the UPS Status Indicators 4 2 4 Status Change Button The Status Change button determines the information displayed by the five LEDs on the front panel The default information shown by the LEDs 1s the load level on the UPS Pressing the Status Change button while the UPS is On prompts the LED display to show battery capacity for 5 seconds This function assists in assessing the meaning of status indicators as described in 4 2 4 UPS Status Indicators See Figure 16 and Table 2 for the Status Change button s location Load Level Indicator The five LEDs at the top of the front panel illuminate with a steady glow to indicate the load level on the output of the UPS The LEDs show the load level as a range 5 The LEDs load level meanings and colors are LED 1 LED 2 LED 3 LED 4 LED 5 10 24 Green 25 49 Green 50 74 Yellow 75 99 Yellow 100 or greater Red 16 Controls and Indicators 4 2 3 4 2 4 Battery Level Indicator The five LEDs illuminate with a steady glow to indicate battery capacity Battery capacity is shown for
24. ity x Voltage x Ah 4x12x72 4x12x9 8x12x7 2 8x12x9 Recharge Time 5 hours to 90 of rated capacity after full discharge into resistive load Battery Backup Time Full Load 5 minutes Half Load 10 minutes Environmental Operating Temperature F C 32 to 104 0 to 40 Storage Temperature F C Relative Humidity 5 to 104 15 to 40 096 to 9096 non condensing Operating Altitude Up to 10 000 ft 3000m Audible Noise 45 dBA Agency Safety UL 1778 c UL Listed Surge ANSI C62 41 CatA Lev3 surges IEC61000 4 5 ESD IEC61000 4 2 Susceptibility IEC61000 4 3 Electrical Fast Transient IEC61000 4 4 Emissions FCC Part 15 Class A Conducted Immunity IEC61000 4 6 Harmonics IEC61000 3 2 Network surge UL 497 B Transportation ISTA Procedure 1A Certification Environmental ROHS compliant NEC limits the input current rating of the PS2200RT3 120XR and PS2200RT3120XRW models to 80 of the input plug s rating Up to 2200VA 1980W is available by contacting a certified electrician to change the input plug to 30A plug Emerson Network Power assumes no liability for damage caused by miswiring or misapplication of the input plug 22 Specifications Table 7 Battery cabinet specifications Model Number PSRT3 24VBXR PSRT3 48VBXR Used w UPS Model Dimensions W x D x H in mm PS1000RT3 120XR PS2200RT3 120XR PS10
25. lder Figure1 Front view of UPS Liebert PSI XR rack mount configuration Display rotates for use as tower Liebert PSI XR tower configuration Display rotates for use in rack Figure2 1000 and 1500 rear view DB 9 Port Liebert Input Circuit Breaker Output Circuit Breaker Contact IntelliSlot 12A for 1000VA 8A for 1000VA Receptacles Closure Port 15A for 1500VA 15A for 1500VA NEMA 5 15R USB Port X III Voltage Configuration Network Surge External Battery Power Cord 5 15P DIP Switch Protection Cabinet Connector not shown for clarity Introduction Figure3 2200 view Power Cord 5 20P DB 9 Port not shown for clarity Contact Closure Liebert IntelliSlot Port 3 EPO USB Port Voltage Configuration Network Surge DIP Switch Protection Figure4 3000 rear view Power Cord L5 30P not shown for clarity NEMA L5 30R Liebert IntelliSlot Receptacle Port DB 9 Port Contact Closure 3 USB Port EPO Network Voltage Configuration DIP Switch Protection lli 9 E 15A Output Circuit Breaker for Receptacles 3 amp 4 Receptacles 3 and 4 NEMA 5 15R Receptacles 1 and 2 Receptacles NEMA 5 20R T Slot 5 and 6 30A Input NEMA 5 15R Circuit Breaker amin P 9 5 ee DC 48V External Battery Cabinet Connector 20A Input Circuit Bre
26. nt bezel Oe t uev CS eps Figure 18 Battery replacement Step 1 21 Specifications 8 0 SPECIFICATIONS Table 6 Liebert PSI XR specifications Model Number Power Rating VA W PS1000RT3 120XR PS1000RT3120XRW PS1500RT3120XRW PS2200RT3120XRW PS1500RT3 120XR PS2200RT3 120XR PS3000RT3 120XR PS3000RT3120XRW 3000VA 2700W 1000VA 900W 1500VA 1350W 1920VA 1920W Dimensions W x D x H in mm Unit 17 3 x 19 3 x 3 5 440 x 490 5 x 88 17 3 x 27 6 x 8 5 440 x 700 5 x 88 Shipping 22 x 24 1 x 9 560 x 612 x 228 22 x 34 8 x 9 0 560 x 884 x 228 Weight Ib kg Unit 56 25 62 28 92 42 105 48 Shipping 64 29 70 32 101 46 115 52 Input AC Parameters Surge Protection 570J Voltage Range Without Battery Operation 83 159 VAC configurable Frequency Range 45 65Hz 0 5Hz Input Power Cord 10ft 3m attached NEMA 5 15P plug NEMA 5 20P plug NEMA L5 30P plug Output Receptacles 4 NEMA 5 15R 2 NEMA 5 20R T Slot accepts15A Plug 1 NEMA L5 30R 4 NEMA 5 15R 2 NEMA 5 20R T Slot accepts15A Plug 6 NEMA 5 15R Voltage Normal Mode 110 120 127 VAC configurable Voltage Battery Mode 110 120 127 VAC 5 before low battery warning Transfer Time 4 6 ms typical Waveform Sinewave Battery Parameters Type Valve regulated nonspillable lead acid Quant
27. r have the utility power checked by a properly trained and qualified electrician UPS shuts down Short circuit or UPS output is abnormal LED 10 and LED 11 illuminate and sound audible alarm Remove the load and turn on the UPS again For help contact your local dealer local Emerson representative or Channel Support Applications Overload LED 5 and LED 11 illuminate and sound audible alarm Check load level display and remove nonessential loads Recalculate the load and reduce equipment connected to UPS the total wattage must not exceed the capacity of the UPS LED 3 and LED 11 illuminate and sound audible alarm Recharge the battery for 8 hours then turn ON the UPS Liebert MultiLink software Consult the Liebert MultiLink user manual or contact your LAN administrator Site Wiring Fault LED LED 4 flashing Site Wiring Fault UPS detected a line to neutral reversal or a loss of proper grounding Have the utility checked by a properly trained and qualified electrician Battery weak LED LED 3 flashing NOTE Batteries weak Recharge batteries Batteries need to be replaced Replace batteries The PS2200RT3 120XR UPS will sound an Overload alarm under certain Low Line conditions when it is fully loaded and it exceeds the input current rating Unless the load is reduced the condition will trip the branch circuit breaker 26 Ensuring The High Availabilit
28. re used to move the UPS into and out of the rack Installation 3 4 Orient Display for Installation The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installations To set the display for your installation pull out on the display and rotate it until it is oriented correctly then press it into the UPS until it is seated Figure9 Orienting the UPS display 3 5 3 6 Charge Batteries and Perform Battery Startup Before connecting input power or connecting the load Emerson recommends these steps Charge the battery for at least 8 hours Start the UPS on battery to ensure the battery is fully functional and charged Turn the unit Off and proceed to 3 6 Connect Input Power and Load Connect Input Power and Load Connect input power to the UPS then plug the equipment into the outlets on the rear of the UPS These UPS outlets provide battery backup and surge protection to the equipment when utility power fails spikes or sags see Figure 10 Figure 10 Connect input power and load 10 Installation 3 7 Connect Network Surge protection Connect a 10 base T 100 network cable to the network surge protection IN jack on the rear of the UPS Connect from the OUT jack with network cabling to network equipment see Figure 11 Figure 11 Connect network surge protection Network Equipment NO Dc24v
29. se can result in electrical shock or fire To ensure safety observe the following rules Turn Off and unplug the UPS before cleaning it Clean the UPS with a dry cloth Do not use liquid or aerosol cleaners Do not install or operate the UPS in or near water Never block or insert any objects into the ventilation holes or other openings of the UPS Keep all vents free of dust accumulation that could restrict air flow Do not place UPS power cord anywhere it might be damaged Battery Handling Precautions A WARNING Batteries should be replaced only by properly trained and qualified personnel knowledgeable of batteries and required precautions A battery can present a risk of electrical shock and high short circuit current The following precautions must be observed when working on batteries Remove watches rings and other metal objects Use tools with insulated handles Do not dispose of the battery or batteries in a fire The battery may explode Do not open or mutilate the battery or batteries Released electrolyte is toxic It may cause injury to the skin and eyes When replacing the battery use the same type of battery as is listed in Table 5 Handle transport and recycle batteries in accordance with local regulations CONDITIONS USE The input supply outlet must be within 6 ft 1 8m of the UPS and be eas ily accessed This UPS provides conditioned power to connected equipment It is not intended
30. ure The Liebert IS WEBRTS provides SNMP and Web based monitoring and control of the UPS across the network 4 NOTE The USB SNMP and contact closure communications can operate in parallel 65 UPS Inverter Transfer Voltage Configurations A two pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal volt ages of 110V 120V or 127V This feature will change the high and low points at which the UPS switches to battery power It also changes the UPS output voltage when the UPS is operating in bat tery mode The factory default setting is 120 VAC Turn Off the UPS before making any changes to the voltage configuration Figure 17 DIP switch settings for 120V system FUNCTION Voltage 110V Voltage 120V Voltage 120V IDE Voltage 127V 5 Voltage configurations Setting Input Voltage Range Output Voltage Battery Mode 110 83 138 110VAC 120 90 150 120VAC 127 96 159 127VAC 20 Battery Maintenance 7 0 BATTERY MAINTENANCE 7 1 7 2 Battery Charging Storage The batteries are valve regulated nonspillable lead acid and must be kept charged to retain their design life The Liebert PSI XR continuously charges the batteries when connected to the utility sup ply even while the UPS is switched Off If the Liebert PSI XR will be stored for an extended period Emerson recommen
31. y Of Mission Critical Data And Applications Emerson Network Power the global leader in enabling business critical Technical Support Service continuity ensures network resiliency and adaptability through _ Web Site a family of technologies including Liebert power and cooling www liebert com Monitoring technologies that protect and support business critical systems Liebert solutions employ an adaptive architecture that responds pense ua Liebert monitoring emerson com to changes in criticality density and capacity Enterprises benefit Outside the US 614 841 6755 from greater IT system availability operational flexibility and Single Phase UPS reduced capital equipment and operating costs 800 222 5877 upstech emersonnetworkpower com Outside the US 614 841 6755 Three Phase UPS 800 543 2378 powertech emersonnetworkpower com Environmental Systems 800 543 2778 Outside the United States 614 888 0246 Locations United States 1050 Dearborn Drive P O Box 29186 Columbus OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco PD Italy 39 0499719111 While every precaution has been taken to ensure the accuracy Fax 39 049 5841 257 and completeness of this literature Liebert Corporation assumes no Asia responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 7 F Dah Sing Financial Centre 2008 Liebert Corpor