American Power Conversion Bypass Static Switch User Manual

image

Contents

1. Arc www apc com Symmetra MW UPS w Internal Bypass Static Switch User Guide EN OOL E i A E E E CHE NN It Contents IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS 53 2eiredex REX E YGYx ea nue 1 Symbols used in this guide lt lt ooo 1 User Safety uo uote 2 SC a eta edd 2 UPS DIS DIAY rica Display Symbols and BUttONS lt o oo 3 Navigation symbols exu ERE E ERE RES 3 Screen symbols 2262 42 eras LR is av 3 BUCEONS e A a A 4 UPS summary SCIGeel x iia de Se ne DR an e E 5 Input Summary Screens 8 6 sine eae a a RE E res 6 Output Summary Screens 99 09 aa eS 7 Bypass Summary Screens ee eee ee eee 8 Battery Summary Screens llle 9 Operation SCreehn uae duro gom a A 10 UPS Starr UD Screens 541 25 2 0 9 xvV WE edu EB TR 11 UPS SHUtAOWA SCEE 6 4445 due A CRDI eee 12 Online to Static Bypass Screen ll 13 Static Bypass to Online Screen 14 Network Configuration Screens 15 Network Settings screen oo 15 E mail Settings screen ux oed om x LE ae ee a 16 SNMP Settings screen sn ul v RE ERET ac A 17 Remote Monitoring Service Settings screen 18 APC ISX Manager Settings screen nns 19 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Operation M
2. Enter new password Enter the new password Re enter the new password Re enter the password to validate the password If you forget the password contact your APC service representative who will be able to help you Note Modbus Settings screen The Modbus Settings screen allows monitoring of the UPS system by a Building Management System BMS Normal 4 Modbus Settings BMS modbus RTU address Communication Settings Baud rate Wi xxxx Parity Vi xxxx Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 21 UPS Display User Configuration Screens e BMS modbus RTU address The modbus slave address of the UPS device e Baud rate e Parity Regional Settings screen Normal User Configuration Regional Settings Temperature unit Yi xxxx Date format Wi MM DD YYYY Temperature unit Select Celsius or Fahrenheit Date format Select the preferred date format Apply Changes Press the Apply Changes button when selections have been made Battery Test screen From the Battery Test screen two different battery tests can be performed and the battery monitor can be reset Battery Test Battery monitor test WY xxxx Battery capacity test W xxxx Battery monitor reset 22 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 UPS Display User Configuration Screens Battery monitor test Setting this value to True results in an automatic batter
3. Screen symbols Delta Inverter Main Inverter AN Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 3 UPS Display Display Symbols and Buttons Buttons Press this button to switch ON the module Press this button to switch OFF the module EMO Emergency Module OFF button Use in emergency situations to shut down the UPS When the EMO button is engaged on the UPS AC and DC input and output are disabled 4 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 UPS Summary Screen The LCD touch screen UPS display is the user interface It is used to configure the UPS monitor the system and change the settings The display also provides the user with audible and visual alarms The UPS display is organized hierarchically and the UPS Summary screen is the apex of the hierarchy To navigate to the UPS Summary screen touch the house icon in the upper right corner of the screen The UPS Summary screen gives access to additional screens as shown below Normal 4 Symmetra MW APC AMET LETT TH A www apc c ooe Operation Configuration The screens on the following pages are examples only All values are not shown Note Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 5 Input Summary Screens The three Input Summary screens provide input specific status of voltage power current freque
4. 38 System Shutdown from Online to Manual Bypass Operation of dual mains utility systems Step by Step 38 Transfer from Online to Static Bypass Operation 39 Transfer from Static Bypass to Online Operation 40 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 WANING a1 m AI da D CD a p Oe a RC Rn 41 SEVERA qe dede sham A RM ee Se a pe 41 View active alarms c rrr nns 42 APC Symmetra MW Remote Display Starting web based remote session LL 44 Warrants Factory Warranty Lite SUPpport PONCY 52 923 era 46 ADDENADN A ER Air Filter Exchange Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This guide contains important instructions that should be followed when handling the UPS Battery Enclosures and Batteries Symbols used in this guide WARNING Indicates an electrical hazard which if not avoided could result in injury or death CAUTION Indicates a hazard which if not avoided could result in injury or death 1 Indicates important information Note Indicates that more information is available on this subject in a different section of this manual X Indicates that more information 1s available on the same subject in a different manual See also Symmetra MW with Internal Bypas
5. All instructions initially mre crm appear in red Once a command has been carried out successfully its text will change to green Follow the shut down instructions on the screen Load will be on manual bypass Open breaker Q5 SSW input Push UPS OFF button UPS power down Open breaker Q2 UPS output Open battery breakers Q7 and Q8 Isolate UPS from battery Open breaker Q1 UPS input Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 37 Operation Modes System Shutdown from Online to Manual Bypass Operation System Shutdown from Online to Manual Bypass Operation of single mains utility systems Step by Step l 2 Press Operation Configuration on the UPS Summary screen Select Shutdown on the Operation screen Press Initiate Transfer to initiate the transfer to Static Bypass Operation Ensure that the green H3 light is illuminated and close the Q3 maintenance bypass breaker Push OFF button on UPS display to power down the UPS Ensure that the H2 light is illuminated indicating that it 1s safe to operate the Q2 breaker and open the Q2 breaker Ensure that the green H7 and H8 lights are illuminated and open Q7 and Q8 breakers to isolate the UPS from battery power Open the QI breaker System Shutdown from Online to Manual Bypass Operation of dual mains utility systems Step by Step l 2 38 Press Operation Configuration on the UPS Summary screen Se
6. User Guide 990 1756A 001 UPS Display Network Configuration Screens Apply Changes Select this button after all changes have been made All entries will appear in red until Apply Changes is pressed e Send Test E mail When this button is pressed a test E mail is sent to all configured E mail recipients This button can be used to validate the e mail settings SNMP Settings screen The UPS can be set to send SNMP traps if UPS alarm conditions occur and when the conditions return to normal afterwards Each trap contains a description of the alarm condition Up to 10 Trap Receivers can be entered The Trap Receiver must have the APC PowerNet MIB version 3 6 1 or later The latest version of the PowerNet MIB can be downloaded from www apc com 1 Network Settings must be configured prior to configuring the SNMP Settings Note SNMP Settings Enable SNMP 1 of 10 trap receivers Trap Recelvers XXX XXX XXX XX Informational Page 3 of 5 Enable SNMP Enable the SNMP functionality by selecting this checkbox To add a new Trap Receiver touch the Add New button type in the address and specify the minimum severity of alarm To edit or delete a Trap Receiver select the recipient as they appear in the recipient list Choose to either update or delete the Trap receiver Apply Changes Select this button after all changes have been made All entries will appear in red until Apply Changes is presse
7. on the network Standard letters a z and A Z digits 1 9 and hyphen can be used Domain name The DNS network domain that the UPS is on Standard letters a z and A Z digits 1 9 and hyphen can be used SMTP Settings From address The from address to be used when sending e mails SMTP server The SMTP server responsible for sending e mails select the Apply Changes button when all information has been entered E mail Settings screen Network Settings information must be configured prior to enabling e mail Note From the E mail Settings screen configure the e mail recipients to be notified of alarms which may occur on the system The severity of the alarms may be informational warning or severe and can be specified for each E mail recipient Up to 25 e mail recipients can be entered Symmetra MW Normal E mail Settings Y Enable E mail 1 of 25 addresses E mail Recipient s User1 company com Informational User2 company com Warning user3 company com Severe Page 2 of 5 Enable E mail Enable the e mail notifications by selecting this checkbox e To add a new e mail recipient touch the Add New button type in the e mail address and specify the minimum severity of alarm To edit or delete an e mail recipient select the recipient as they appear in the recipient list Choose to either update or delete the recipient 16 Symmetra MW with Internal Bypass Static Switch
8. single line diagram will appear on the screen The green line indicates the power flow from the utility supply through the UPS to the load CAUTION AN Do not open Q2 when the UPS is in on line operation as this action may result in a load drop or a failure of the UPS to support the load Q3 Bypass Static Switch Q1 AN Delta inverter pA XN Main inverter Q8 Q7 Battery Breaker Identification o UPS input breaker o Static bypass input breaker Q UPS output breaker Or Battery breaker 1 Manual bypass breaker QU Battery breaker 2 Only operate a breaker when the associated breaker lamp is on Note Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 31 Battery Operation During battery operation the load 1s supported by the inverters The inverters are supplied by battery power ensuring uninterrupted support to the load While the UPS is running in battery operation a single line diagram will appear on the screen with a green line indicating the power flow from the batteries through the main inverter to the load for as long as the batteries are energized CAUTION N Do not open Q2 Q7 or Q8 when the UPS is in battery operation as this action may result in a load drop or a failure of the UPS to support the load Q3 Bypass Static Switch n a Q1 Delta inverter Main inverter Breaker Identification QI UPS input breaker Static bypass input bre
9. 2 UPS output Open battery breakers Q7 and Q8 Isolate UPS from battery Open breaker Q1 UPS input The UPS Shutdown screen shows a list of actions which need to be completed in order to shut down the UPS The actions are initially indicated in red to show that they have not yet been completed A yellow bar will highlight the actions in the order in which they need to be completed As actions are completed they will change to green The Start Up procedure is described in System Shutdown from Online to Manual Bypass Operation Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Online to Static Bypass Screen From the Online to Static Bypass screen the power flow can be transferred from Online to Static Bypass Operation Symmetra MW i N O rmal 4 APC Online to Static Bypass Initiate transfer to static bypass In static bypass the load is powered directly by utility power There will be no UPS backup Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 13 Static Bypass to Online Screen From the Static Bypass to Online screen the power flow can be transferred from Static Bypass to Online Operation Static Bypass Static Bypass to Online Initiate transfer to online 14 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Network Configuration Screens There are five Network Configuration screens that will be des
10. C Cap Normal OK0046 AC Cap Normal OK0046 AC Cap Normal OK0046 AC Cap Normal OK0046 AC Cap Normal OK0046 AC Cap Normal OK0046 AC Cap Normal OK0046 AC Cap Normal 1 2 3 4 5 6 7 8 ERL Expected Remaining Lifetime Page 2 of 5 e Stress Status States the actual status of the Inverter AC Capacitors The possible values are Normal displaying in green Stressed displaying in yellow Major Stress displaying in red ERL months Predicts the expected remaining lifetime of the particular component Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 UPS Display Predictive Maintenance Screens Top Fans screen The Top Fans screen displays the actual status and Expected Remaining Lifetime ERL of the Top Fans It 1s possible to sort the data on the screen by touching either of the column labels Symmetra MW Normal y Predictive Maintenance www apc com Top Fans 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 490 00XX Top fan xxxx Normal 1 2 3 4 5 6 7 8 9 Zo A N O ERL Expected Remaining Lifetime Page 3 of 5 e Stress Status States the actual status of the Top Fans The p
11. Internet so that the security administrative control and caching service can be regulated Use Proxy Select this checkbox if the Internet connection method uses a HTTP proxy server to connect to the Internet Proxy server address Enter the fully qualified IP address or fully qualified domain name of the proxy server If you do not know the server address or port number contact your network administrator Proxy server port Enter the port number of the proxy server Use authentication Select this checkbox if the proxy server requires a login Then specify a Proxy server login user name and a Proxy server password 18 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 UPS Display Network Configuration Screens APC ISX Manager Settings screen Symmetra MW APC ISX Manager Settings Enable ISX Manager Discovery Community Name XXXXXX System Location XXXXXX System Contact XXXXX Page 5 of 5 The following settings have to be configured for the Symmetra MW to be discovered by the APC ISX Manager Community name Select the Enable ISX manager discovery check box e System Location optional e System Contact optional By default the community string is set to public Note Select the Apply Changes button after the APC ISX Manager screen has been completed Note Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 19 User Configuration
12. Screens There are five User Configuration screens Touch Screen Settings screen Password Settings screen Modbus Settings screen Regional Settings screen e Battery Test screen Touch Screen Settings screen The Touch Screen Settings screen is used to customize the brightness contrast and backlight of the display Touch Screen Settings Brightness 100 Contrast Backlight mode lv Always on Backlight timeout minutes w5 Brightness Put the finger on the indicator and slide to the left or right to the desired setting Contrast Put the finger on the indicator and slide to the left or right to the desired setting Backlight mode The backlight mode s default setting 1s that the light goes off after 5 minutes of inactivity Backlight timeout minutes The display backlight can be set to be always on or to turn off after a certain period of screen inactivity 20 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 UPS Display User Configuration Screens Password Settings screen Some of the UPS Display screens primarily configuration screens are protected by a password On installation the password is set to apc For security reasons it is recommended to change the password Normal 4 Password Settings Enter current password XXXX Enter new password XXXXXXXX Re enter new password XXXXXXXX Enter current password Enter the current password
13. aker Q2 UPS output breaker Battery breaker 1 s CN Manual bypass breaker Battery breaker 2 Only operate a breaker when the associated breaker lamp is on Note 32 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Bypass Operation During bypass operation the critical load is supplied directly by utility power A single line diagram will appear on the screen with an orange line indicating the power flow through the Bypass SSW to the load CAUTION AN Do not open Q2 or Q5 when the UPS is in bypass operation as this action may result in a load drop or a failure of the UPS to support the load Q3 Bypass Static Switch Q1 Delta inverter Main inverter Breaker Identification Q UPS input breaker o Static bypass input breaker Q UPS output breaker a Battery breaker 1 Manual bypass breaker CS Battery breaker 2 Only operate a breaker when the associated breaker lamp is on Note Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 33 Manual Bypass Operation 34 During manual bypass operation the critical load 1s supplied directly by utility power making it possible to isolate the UPS and the Bypass Static Switch for maintenance Battery power is not available as an alternate power source while the system is running in manual bypass operation Note A single line diagram will appear on the screen with an orange line indicating th
14. ater Stafkyde Autofyl Tilbage r Stop itofy kc S LL 1G http XXX XXX XXX XX APC Symmetra MW i www epe com The Symmetra MW Display application will start automatically once it is downloaded to your computer 5 3 m fag 3 5 3 2 2 a g i E 2 amp n 5 amp a e After a few seconds the UPS display is shown on the screen Use the mouse to touch the buttons to see other screens Close the window or the web browser to end the remote session For security reasons there is a time limit of 30 minutes for a remote session The connection will be disconnected after 30 minutes and reconnection is required Note Only one remote session at a time is allowed Note 44 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Factory Warranty APC warrants that the unit when properly installed and commissioned by APC or APC authorized service personnel shall be free from defects in materials and workmanship for a period of 1 year from the date of installation or maximum 18 months after manufacturing In the event that the unit fails to meet the foregoing warranty APC shall for a period of one 1 year repair or replace any defective parts without charge for on site labor and travel 1f trained amp authorized APC personnel has conducted start up of the unit An APC Start Up Service must be performed compl
15. atic Bypass to Online Operation Static Bypass UPS Summary Select Operation Configuration on UPS Summary screen Transfer from manual bypass to online o o Transfer from online to manual bypass Transfer from online to static bypass Transfer from static bypass to online Select Static Bypass gt Online on Operation screen Press Initiate transfer gt on Static Bypass to Online screen Initiate transfer to online 40 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Alarms Troubleshooting Alarm Types The color of the top of the screen switches from blue to red when an alarm situation occurs and the alarm symbol is shown at the top of the screen Alarm button Pressing the alarm button will take the user to a screen showing all active 4 alarms and how each alarm should be addressed The 3 different alarm levels are described below Hitting the alarm symbol or any other display button will automatically silence the alarm Info Symmetra MW Alarm Info UPS Summary www apc com 9 91 PM Informational Alarm No immediate need to take action Check the cause of the alarm at next maintenance visit Warning symmetra vw A EA ET Ale Normal www apc com UPS Summary Warning Alarm Example The UPS system may have gone into bypass The load remains supported but action must be taken Call Technical Support The area in the right side of t
16. ault 06 27 2004 13 00 50 0 Severe Bypass static switch fuse blown 06 27 2004 14 24 10 0 Severe Bypass static switch fan fault 03 17 2004 15 24 11 0 Severe Bypass isolation transformer temp high 04 14 2004 17 24 12 0 Severe Bypass voltage low 05 15 2004 18 24 10 0 Severe Bypass synchonization error 06 30 2004 19 24 02 0 Severe MC isolated SELV PSU fault 07 17 2004 20 30 10 0 Severe ABUS terminator fault 08 13 2004 13 24 15 0 Severe Discharging batteries 09 10 2004 13 24 15 0 Severe Section is disabled 10 27 2004 13 24 15 0 1 2 3 4 5 6 7 8 gt c I l3 2 2 2 l l3 l3 l3 l2 2 Refresh Select the Refresh button to update the Event Log e Stop only visible during update Select this button to stop the event log downloading E mail Event Log Press this button to e mail the event log to a specific e mail address Enter in the e mail address and press the Send button Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Predictive Maintenance Screens The Predictive Maintenance screens display the stress status and the Expected Remaining Lifetime ERL of the critical components of the Symmetra MW UPS system There are five Predictive Maintenance screens nverter DC Capacitors screen Inverter AC Capacitors screen Top Fans screen Inverter Fans screen Main Static Switch Fans screen Inverter DC Capacitors screen The Inverter DC Capacitor screen displays the actual status a
17. cribed below Network Settings screen E mail Settings screen SNMP Settings screen Remote Monitoring Service Settings screen APC ISX Manager Settings screen Network Settings screen All network settings information must be provided before any network functions can be used Symmetra MW Network Configuration 5 39 PM Network Settings 00 Y Enable network IP Settings Host Name Settings IP address XXX XXX XXX XXX Hostname UPS1 Subnet mask XXX XXX XXX X Domain name company com Gateway XXX XXX XXX X DNS Settings SMTP Settings y Primary DNS server XXX XXX XXX XXX From address xxxxxx xxxx Xxx xx Secondary DNS server XXX XXX XXX XXX SMTP server company com p Page 1 of 5 Enable Network Use the checkbox to connect or disconnect the UPS from the network IP Settings P address The static IP address e Subnet Mask The subnet mask for the network segment that the UPS is on e Gateway The network gateway for the segment that the UPS is on DNS Settings Primary DNS server The IP address of the DNS server to be used by the UPS optional e Secondary DNS server The IP address of a DNS server to use if the primary server is not available optional Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 15 UPS Display Network Configuration Screens Host Name Settings Host name The network host name for the system This uniquely identifies the system
18. d send Test SNMP When this button is pressed a test trap 1s sent to all configured Trap Receivers This button can be used to validate SNMP settings Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 17 UPS Display Network Configuration Screens Remote Monitoring Service Settings screen Network settings must be configured before the remote monitoring feature can be used Note The APC Remote Monitoring Service RMS is an APC professional service which securely monitors customer s power systems and surrounding environment from a remote 24x7 operation center responding to events according to a pre defined customer escalation procedure Visit rms apc com to learn more about this service Symmetra MW Network Configuration Remote Monitoring Service Settings A Y Enable APC RMS Use proxy Proxy server address Proxy server port XXXX A Use authentication Proxy server login Y Proxy server password A ip Page 4 of 5 Enable APC RMS Select this checkbox to start using the service Once selected information about your UPS will periodically be sent to APC s Remote Monitoring Service The APC Remote Monitoring Service uses HTTP protocol to post information to its database If a proxy server is used as Internet connection method then the required proxy server port settings must be specified a proxy server acts as an agent between a workstation user or other networked device and the
19. e Current high discharge 119 5 A Boost charge false Battery 2 Auto boost charge false Voltage 451 0 V Nominal charge 4200 V Voltage high 460 0 V Boost charge 450 V Voltage low 420 0 V Estimated charge time 65 m Current 515 A Estimated charge 100 Current high discharge 120 0 A Batt 1 charge current high 90 0 A o Settings Batt 2 charge current high 90 0 A Min voltage warning 370 V E Min voltage shutdown 320 V Temperature 3 Max voltage warning 460 V Battery 100 F e Max voltage shutdown 475 V Max battery 86 F Battery high 104 F Statistics Battery iow dii Battery charge Floating Power l Time on battery 0s Battery power 0 kW Runtime remaining 300m0 s Battery power high discharge 0 kW Total time on battery 0m Battery power high charge 0 kW Time hours Total of times on battery 0 Page 2 of 3 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 9 Operation Screen The Operation screen permits system operation and monitoring and provides the ability to change display settings as illustrated 1n the following menus Push the Operation Configuration button to open the Operation screen UPS Summary The Operation screen leads to the following screens UPS Start Up screen UPS Shutdown screen Online to Static Bypass screen Static Bypass to Online screen Network Configuration screens User Configuration screens View Event Log screen Predictive Maintenance
20. e power flow from the utility to the load via the Q3 breaker CAUTION AN Do not open Q3 when the UPS is in manual bypass operation as this action may result in a load drop or a failure of the UPS to support the load Breaker Identification UPS input breaker Static bypass input breaker UPS output breaker Battery breaker 1 Manual bypass breaker C Battery breaker 2 1 Only operate a breaker when the associated breaker lamp is on Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 System Start Up from Manual Bypass Operation If the UPS has been operating in manual bypass operation and no power is connected to the UPS the UPS display will be inactive To re start the system from manual bypass and achieve on line operation close Q1 in the external maintenance bypass panel This will power up the internal power supply Wait for the display to become active and follow the screen prompted instructions CAUTION Follow these instructions carefully Failure to do so could result in equipment damage Select Operation Configuration Select Start up Follow the start up instructions on the screen Manual bypass Off UPS Summary Manual Bypass Off d Aa o o Transfer from manual bypass to online Transfer from online to manual bypass Transfer from online to static bypass Transfer from static bypass to online mem Active commands initially appear in red Once a command has been carri
21. ed out successfully its text will change to green Important After pressing Initiate charge in step 2 wait until the green lights go on alongside battery breakers Q7 and Q8 on front of the Battery Breaker Box before closing the breakers UPS Startup Close Q1 Display will be off until Q1 closed Close breaker Q5 SSW input Charge DC Capacitors Close battery breakers Q7 and Q8 Connect battery Close breaker Q2 UPS output Initiate transfer to static bypass Open breaker Q3 Manual bypass Push UPS ON button UPS will power up Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 35 Operation Modes System Start Up from Manual Bypass Operation System Start Up from Manual Bypass to Online Operation of single mains utility system l Step by Step Close Q1 in the external maintenance bypass panel to power up the internal power supply Wait for the display to become active Press Operation Configuration on the UPS Summary screen on the UPS display Press Startup on Operation screen Press Initiate Charge on the UPS display to initiate the charging of the UPS DC capacitors When the green lights H7 and H8 are illuminated close battery breakers Q7 and Q8 to connect the battery system Close Q2 breaker Press Initiate Transfer on the UPS display to transfer to Static Bypass Operation Open maintenance bypass breaker Q3 Push ON button on the UPS to transfer to Online Operatio
22. es apply only to purchaser and are not extended to any third parties In no event shall APC its officers directors affiliates or employees be liable for any form of indirect special consequential or punitive damages arising out of the use service or installation of the products whether such damages arise in contract or tort irrespective of fault negligence or strict liability or whether APC has been advised in advance of the possibility of such damages Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 45 Life Support Policy 46 As a general policy American Power Conversion Corporation and its affiliates and subsidiaries worldwide APC do not recommend the use of any of its products in life support applications where failure or malfunction of the APC product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness APC does not recommend the use of any of its products in direct patient care APC will not knowingly sell its products for use in such applications Examples of devices considered to be life support devices are neonatal oxygen analysers nerve stimulators whether used for anesthesia pain relief or other purposes autotransfusion devices blood pumps defibrillators arrhythmia detectors and alarms pacemakers hemodialysis systems peritoneal dialysis systems neonatal ventilator incubators ventilators for both adult
23. eted by APC or by service personnel authorized by APC If not the on site factory warranty will be voided and replacement of defective parts only will be covered APC shall have no liability and no obligation to repair the installed unit if non authorized APC personnel performed the start up and such start up caused the unit to be defective APC shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by purchaser s or any third person s misuse negligence improper installation or testing unauthorized attempts to repair or modify or any other cause beyond the range of the intended use or by accident fire lightning or other hazard There are no warranties expressed or implied by operation of law or otherwise of products sold serviced or furnished under this agreement or in connection herewithin APC disclaims all implied warranties of merchantability satisfaction and fitness for a particular purpose A PC s express warranties will not be enlarged diminished or affected by and no obligation or liability will arise out of APC rendering of technical or other advice or service in connection with the products The foregoing warranties and remedies are exclusive and in lieu of all other warranties and remedies The warranties set forth above constitute APC s sole liability and purchaser s exclusive remedy for any breach of such warranties APC s warranti
24. he top screen alternates between blue and red Severe Normal 4 armenia Na Alarm Severe UPS Summary www apc com 3 51 PM Severe Alarm Take immediate action Call Technical Support The red area of the top of the screen alternates between blue and red Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 41 Alarms Troubleshooting Alarm Types View active alarms Symmetra MW Alarm E Severe UPS Summary Operation Configuration Normal Symmetra MW Severity Warning Warning Severe Severe Alarm Severe Active Alarms Suggested Action Mains static switch fan comm fault Call APC for service Battery temperature high Check temperature in the battery room Bypass unavailable Call APC for service Output off No output from UPS Normal 06 11 2003 15 45 06 11 2003 15 45 06 11 2003 15 44 06 11 2003 15 44 Press the red triangular alarm symbol to view active alarms Only active alarms will appear on the screen Pressing the alarm symbol will also mute audible alarms Previous alarms are stored in the Event Log which contains a detailed record of the system s last 1024 events In the Active Alarms list the user can see which actions to take to solve the problem Note 42 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 APC Symmetra MW Remote Display The read only display screens can be accessed via an Inter
25. lect Shutdown on the Operation screen Press Initiate Transfer to initiate the transfer to Static Bypass Operation Ensure that the green H3 light is illuminated and close the Q3 maintenance bypass breaker Open the Q5 static input switch breaker Push OFF button on UPS display to power down the UPS Ensure that the H2 light 1s illuminated indicating that it is safe to operate the Q2 breaker and open the Q2 breaker Ensure that the green H7 and H8 lights are illuminated and open Q7 and Q8 breakers to isolate the UPS from battery power Open the QI breaker Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Transfer from Online to Static Bypass Operation Follow the below procedure to transfer from Online to Static Bypass Operation Normal UPS Summary Select Operation Configuration on UPS Summary screen D Normal far Operation Transfer from manual bypass to online O o Transfer from online to manual bypass Select On ine gt Stati C Bypass Transfer from online to static bypass on Operation screen E Normal 3 Online to Static Bypass 0 00 AM Pre SS Initiate transfer to static bypass Initiate transfer to Online gt on Online to Static Bypass EM braun NM Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 39 Transfer from Static Bypass to Online Operation Follow the below procedure to transfer from St
26. ments in the APC Knowledge Base and to submit customer support requests www apc com Corporate Headquarters Connect to localized APC Web sites for specific countries each of which provides customer support information Wwww apc com support Global support searching APC Knowledge Base and using e support Contact an APC Customer Support center by telephone or e mail Regional centers Direct InfraStruXure Customer Support Line 1 877 537 0607 toll free APC headquarters U S Canada 1 800 800 4272 toll free Latin America 1 401 789 5735 USA Europe Middle East Africa 353 91 702000 Ireland Japan 0 35434 2021 Australia New Zealand South Pacific area 61 2 9955 9366 Australia Local country specific centers go to www apc com support contact for contact information Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support Entire contents O 2005 American Power Conversion All rights reserved Reproduction in whole or in part without permission 1s prohibited APC the APC logo and Symmetra are trademarks of American Power Conversion Corporation and may be registered in some jurisdictions All other trademarks product names and corporate names are the property of their respective owners and are used for informational purposes only 1 LULA EIL LU dicis
27. mmary Current A Current Current Current high Peak current Peak current high THD THD high Crest factor Crest factor high Voltage Voltage Voltage high Voltage low THD THD high Voltage tolerance Waveform tolerance Tolerance conditions Total Power Frequency kW kVA Hz Power Active power Active power high Apparent power Apparent power high Power factor Total active power Total apparent power Frequency Frequency Frequency high Frequency low Tolerance Load Load Load high Total load Total load high Page 2 of 3 The black bars represent real time data Yellow triangles represent the maximum values recorded to date and blue triangles represent the minimum values recorded to date These values will be reset when the output statistics are reset Normal APC Output Summary www apc com Ala WVYYVY Y KAMAN e 10 Time ms Page 3 of 3 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Bypass Summary Screens The two Bypass Summary screens provide status of voltage power current frequency etc Symmetra MW Bypass Summary Operation Configuration Symmetra MW Bypass Summary The black bars represent real time data Yellow triangles represent the maximum values recorded to date and blue triangles represent the minimum values recorded to date These values will be reset when the bypass statistics are reset Current V
28. n System Start Up from Manual Bypass to Online Operation of dual mains utility system l 36 Step by Step Close Q1 and Q5 in the external maintenance bypass panel to power up the internal power supply Wait for the display to become active Press Operation Configuration on the UPS Summary screen on the UPS display Press Startup on Operation screen Press Initiate Charge on the UPS display to initiate the charging of the UPS DC capacitors When the green lights H7 and H8 are illuminated close battery breakers Q7 and Q8 to connect the battery system Close Q2 breaker Press Initiate Transfer on the UPS display to transfer to Static Bypass Operation Open maintenance bypass breaker Q3 Push ON button on the UPS to transfer to Online Operation Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 System Shutdown from Online to Manual Bypass Operation To shut down the UPS transfer from on line operation to manual bypass operation follow the screen prompted instructions as illustrated CAUTION Do not open Q3 when the UPS is in manual bypass operation as this action may result in a load drop or a failure of the UPS to support the load UPS Summary Select Operation Configuration um Transfer from manual bypass to online 7 Transfer from online to manual bypass Transfer from online to static bypass Transfer from static bypass to online Select Shutdown
29. ncy etc The black bars represent real time data Yellow triangles represent the maximum values recorded to date and blue triangles represent the minimum values recorded to date These values will be reset when the input statistics are reset Current Voltage Total Power Frequency A V kW kVA Hz 0 L1 L2 L3 L1 2 L2 3 L3 1 Page 1 of 3 Symmetra MW i Normal Input Summary Input Summary www apc com Current Power Current 226 174 124 A Active power 410 410 402 kW Current high 90 2 77 8 724 A Active power high 700 700 701 kW THD 61 Apparent power 320 320 312 kVA THD high 4 0 4 9 5 9 Apparent power high 700 700 702 kVA THD low 1 0 1 0 1 0 Power factor 1 0 10 1 0 Mi Crest factor 224 2 27 237 Total active power 700 kW Crest factor high Total apparent power 0 0 V AAT Voltage Frequency Voltage 242 5 247 7 252 7 V Frequency 47 9 Hz Voltage high 260 2 265 1 270 1 V Frequency high 541 Hz Voltage low 199 8 2063 2115 V Frequency low 45 9 Hz THD 3 1 4 0 5 0 Tolerance 20 THD high 3 0 3 9 4 9 Voltage tolerance 0 0 0 0 0 0 Temperature Waveform tolerance 10 Mains SSW 129 F Tolerance conditions 10 Mains SSW high 127 F A HA JN Time ms Page 3 of 3 6 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Output Summary Screens The three Output Summary screens provide output specific status of voltage power current frequency etc UPS Su
30. nd Expected Remaining Lifetime ERL of the Inverter DC Capacitors It is possible to sort the data on the screen by touching any of the column labels Symmetra MW Inverter DC Capacitors 1 2 3 4 5 6 7 8 2 0 N 2 O ERL Expected Remaining Lifetime Predictive Maintenance OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap OK0046 DC Cap Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal 0909 Page 1 of 5 e Stress Status States the actual status of the Inverter DC Capacitors The possible values are Normal displaying in green Stressed displaying in yellow Major Stress displaying in red ERL months Predicts the expected remaining lifetime of the particular component Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 25 UPS Display Predictive Maintenance Screens Inverter AC Capacitors screen 26 The Inverter AC Capacitor screen displays the actual status and Expected Remaining Lifetime ERL of the Inverter AC Capacitors It is possible to sort the data on the screen by touching either of the column labels Symmetra MW Predictive Maintenance Inverter AC Capacitors 900 OK0046 AC Cap Normal OK0046 AC Cap Normal OK0046 AC Cap Normal OK0046 AC Cap Normal OK0046 A
31. net Browser by typing the IP address ofthe Symmetra MW display into the browser s address field The remote display feature provides a subset ofthe Symmetra MW display screens Configuration of the Symmetra MW or the display through the remote display is not supported The remote display feature requires Microsoft Internet Explorer 6 SP1 or greater For best results we recommend that the Sun JVM version 1 4 2 05 or greater be installed This 1s available from Sun s website The Netscape browser is not supported The following screens can be accessed during a remote session e UPS Summary screen Active alarms screen Event log screen Input Summary screens Output Summary screens e Battery Summary screens e Bypass Summary screens Operation configuration must be done at the UPS Note The event log screen can be accessed through the Operation screen Only the 50 most O recent events in the Event Log screen can be downloaded Note Network settings must be configured before the remote display feature can be used Note Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 43 APC Symmetra MW Remote Display Starting web based remote session e Start the web based remote session by entering the IP address of the APC Symmetra MW UPS in the web browser address field After a few seconds a new window will open and display the below screen Symmetra MW Opd
32. ode Sacco O User Configuration Screens l l oo 20 Touch Screen Settings screen o o ooooooooo o 20 Password Settings screen eere 21 Modbus Settings screen 00 ooo 21 Regional Settings screen o ooo ooo 22 Battery Test screen ooo te o 22 Event Log SCEOGD s 4 4 6 iiaa 0 ee o lr daa E 5 8 A arise 24 Predictive Maintenance Screens LL 25 Inverter DC Capacitors screen 25 Inverter AC Capacitors screen lr 26 TOD Fans screen s x uedox Rad ae a erae eee ee eS 27 Inverter Fans screen zie gue ERR RUE RR Ru x RUE TN E uen 28 Main Static Switch Fans screen rr 29 Omne Operallon ua x DE RN RU Uo PK uda e oe He 31 Battery Operauion 6 6 3 do oce D ace dde Be aa We 32 Bypass ODerallOll i o E vue Xd EY EX Sev EE E TP a 33 Manual Bypass Operation oo o oo 34 System Start Up from Manual Bypass Operation 35 System Start Up from Manual Bypass to Online Operation of single mains utility system Step by Step 36 System Start Up from Manual Bypass to Online Operation of dual mains utility system Step by Step 36 System Shutdown from Online to Manual Bypass Operation 37 System Shutdown from Online to Manual Bypass Operation of single mains utility systems Step by Step
33. oltage Total Power Frequency A V kW kVA Hz o LA IB 205 L1 2 L2 3 L3 1 Symmetra MW Bypass Summary Current Current Current high Peak Current Peak Current high Crest factor Crest factor high Power Power factor Active power Active power high Voltage Voltage Voltage high Voltage low THD Load Load Load high Total load Total load high Apparent power Apparent power high Total active power Total active power high Total apparent power Total apparent power high Frequency Frequency Frequency high Frequency low Temperature Mains SSW Mains SSW High Page 2 of 2 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Battery Summary Screens The three Battery Summary screens provide battery specific status of voltage current run time remaining temperature power etc Symmetra MW Normal y UPS Summary Operation Configuration The black bars represent real time data Yellow triangles represent the maximum values recorded to date and blue triangles represent the minimum values recorded to date These values will be reset when the 12m0s battery statistics are reset Normal Battery Summary p em Current Voltage uc A v Runtime remaining 0 Batt 1 Batt2 Batt1 Batt2 Page 1 of 3 Normal 4 Voltage and Current I i E Voltage 440 0 V Voltage high 450 0 V Voltage low 420 0 V Current 572 A Charg
34. ossible values are Normal displaying in green Stressed displaying in yellow Major Stress displaying in red ERL months Predicts the expected remaining lifetime of the particular component Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 27 UPS Display Predictive Maintenance Screens Inverter Fans screen 28 The Inverter Fans screen displays the actual status and Expected Remaining Lifetime ERL of the Inverter Fans It is possible to sort the data on the screen by touching either of the column labels Symmetra MW www apc co Predictive Maintenance Inverter Fans 1 2 3 4 5 6 7 8 ERL Expected Remaining Lifetime 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan 490 0039 PM Fan Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal 0909 Page 4 of 5 e Stress Status States the actual status of the Inverter Fans The possible values are Normal displaying in green Stressed displaying in yellow Major Stress displaying in red ERL months Predicts the expected remaining lifetime of the particular component Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Main Static Switch Fans screen UPS Display Predic
35. s Static Switch User Guide 990 1756A 001 1 Safety IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS User Safety WARNING User functions For safety reasons the user may only Remove the finishing panels for air filter exchange Operate the UPS display WARNING The UPS can be powered from more than one source CAUTION The system 1s equipped with an optional auto start function enabling the system to start without any warning when power is applied Typically the UPS installation will be connected to an EPO Emergency Power Off button located on a wall near the entrance to the room If activated the EPO switches off power to the UPS disconnects the UPS output and switches off power to the entire Note room This action will disconnect support to the load if the UPS is online OPP amp 2 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 UPS Display Display Symbols and Buttons Navigation symbols ES Home Press to go to the UPS Summary screen Back Press to go to previous screen o Help Press to access further details on current screen more screens on the same subject Page Up Press to go to previous screen on same subject only visible when there are Page Down Press to go to next screen on same subject only visible when there are more screens on the same subject Password logout Press to log out from password protected screens
36. s and infants anesthesia ventilators infusion pumps and any other device designated as critical by the U S F D A Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 Appendix A Air Filter Exchange Check air filters at regular intervals every 3 months under normal working conditions for accumulated dust on the surface facing the finishing panels Change all filters at the same time Q Pull lower part of top finishing panel free of the UPS Lift finishing panel free of the dead front panel and remove 6 Follow this procedure to remove the next finishing panel down until all panels in one row have been removed Use the same procedure for the next row of panels until all panels have been removed from the UPS system Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 47 Appendix A Air Filter Exchange Note the orientation of the filter Note Remove air filters and install new filters Refit finishing panels in reverse order Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 48 7A ww w apc com APC W orldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways Visit the APC Web site to access docu
37. screens f Normal Operation Transfer from manual bypass to online o 3 Transfer from online to manual bypass Transfer from online to static bypass Transfer from static bypass to online 10 Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 UPS Start Up Screen From the UPS Start Up screen the power flow can be transferred from Manual Bypass to Online Operation Manual bypass Off UPS Startup Close Q1 Display will be off until Q1 closed Close breaker Q5 SSW input Charge DC Capacitors Close battery breakers Q7 and Q8 Connect battery Close breaker Q2 UPS output Initiate transfer to static bypass Open breaker Q3 Manual bypass Push UPS ON button UPS will power up The UPS Start Up screen shows a list of actions which need to be completed in order to start up the UPS from Manual Bypass Operation The actions are initially indicated in red to show that they have not yet been completed A yellow bar will highlight the actions in the order in which they need to be completed As actions are completed they will change to green The Start Up procedure is described in System Start Up from Manual Bypass Operation Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 11 UPS Shutdown screen Normal UPS Shutdown Close breaker Q3 Load will be on manual bypass Open breaker Q5 SSW input Push UPS OFF button UPS power down Open breaker Q
38. tive Maintenance Screens The Main Static Switch Fans screen displays the actual status and Expected Remaining Lifetime ERL of the Main Static Switch Fans It 1s possible to sort the data on the screen by touching either of the column labels Symmetra MW Main Static Switch Fans Predictive Maintenance Normal 4 0909 1 2 3 4 5 6 7 8 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx 490 00XX SSW Fan xxx ERL Expected Remaining Lifetime Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Page 5 of 5 e Stress Status States the actual status of the Main Static Switch Fans The possible values are Normal displaying in green Stressed displaying in yellow Major Stress displaying in red ERL months Predicts the expected remaining lifetime of the particular component Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 29 Operation Modes On line Operation During on line operation the critical load is supported by the inverters The main inverter controls the output voltage and the delta inverter controls the input current The delta inverter also provides battery charging current While the UPS is running in this mode a
39. y monitor test being performed at regular intervals specified by the Service Engineer The three options are Auto battery test every N week s Auto battery test on one day of the week Auto battery test at a specific time of the day Battery capacity test Setting this value to True results in the batteries being discharged until a Battery Low Voltage Level 1s reached This test can only be performed manually The test is used to cycle the batteries in order to calibrate the backup time with the current load and battery modules installed Battery monitor reset In the event of a weak battery or another battery problem use this button to reset the battery monitor Symmetra MW with Internal Bypass Static Switch User Guide 990 1756A 001 23 Event Log Screen 24 The Event Log screen contains a detailed record of the system s last 1024 events This includes operation mode changes system alarms etc symmetra ww AMEN TT PEST T APC Event Log ae A LEL 242 event s downloaded No Severity_ Event Description_______________k_ Param Data DategTime Severe Bypass fast error detected 01 27 2004 11 00 41 0 Severe Bypass input frequency fault 03 01 2004 11 10 41 0 Severe Bypass static switch temperature fault 06 02 2004 11 14 41 0 Severe Bypass static switch fault 12 02 2004 11 30 47 0 Severe Bypass static switch backfeed protect on 06 27 2004 11 40 45 0 Severe Bypass static switch thyristor f