American Power Conversion Automatic Disconnect Switch Switch User Manual
Contents
1. 8 Broadband Automatic Disconnect Switch User Manual Installation Coax Connection PI 17 x a LA e hy M M SS MEN o0 kL a oY i f e f k E e IL re re i 4 f H ls AA Coax Output T Coax Input Connects to 7 Connects to Cable System 3 Te FRP Output Broadband Automatic Disconnect Switch User Manual Installation Cable Modem Connection In The cable modem utility power F connector and USB connectors are located on the back of the cable modem Secure the appropriate cables to these connectors before installing the cable modem in the enclosure e er T USB Cable Connect the appropriate cables to the cable modem Tie Wrap Lance IEC receptacle the USB port and the F connector F Connector located on inside the enclosure Qe 4 USB Using the lance on the enclosure secure a tie wrap om i Connector to the USB cable if required E r Cable Modem CL Utility Power IEC Recepticle 10 Broadband Automatic Disconnect Switch User Manual Operation Start Up Primary Sec
2. in transit is not covered under warranty 4 Mark the RMA on the outside of the package Return the unit by insured prepaid carrier to the address given to you by Customer Support Contact APC Refer to the APC Web site www apc com Select the appropriate country from the country selection field and select the Support tab at the top of the web page Regulatory Agency Approvals and Radio Frequency Warnings FCC Compliance Notice This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy If it is not installed and used in accordance with the instruction manual it may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case users will be required to take whatever measures may be necessary to correct the interference at their own expense UL LISTED 42C2 E95463 Entire contents copyright 2004 by American Power Conversion Corporation All rights reserved Reproduction in whole or in part without permission is prohibited APC Smart UPS and PowerChute are registered trademarks of American Power Conversion Corporation All other trademarks are the pro
3. 94 Elevation 0 to 10 000 feet 0 to 3 000 meters Broadband Automatic Disconnect Switch User Manual Installation Electrical Specifications Utility Power Cable Input Connection Three Position Cable Adapter 5 8 24 PARECE Terminal Block Terminal Block to Coax Center Conductor Nominal Voltage 220 V 63V Allowable Input range 165 270 V 40 75 V Maximum Current 15A 18 A Input Current Limiting 10 A N A Output Connection Three Position Cable Adapter 5 8 24 cHo Terminal Block Terminal Block to Coax Center Conductor I Allowable Output range 40 75 V T Primary None Initial Connection Delay Secondary 5S sedonds Time to connect attached FRP N A 350 mS maximum to cable system after output failure Physical Specifications Characteristic Specification Height Width Depth 15 x 7 x 8 38 1 x 17 8 x 20 3 cm Weight 14 Ibs 6 4 kg Installation Unpack Read the Safety Guide before installing this unit The User Manual and Safety Guide are accessible on the APC Web site www apc com Inspect the unit upon receipt Notify the carrier and dealer if there is damage The packaging is recyclable save it for reuse or dispose of it properly Check the package contents 4 Broadband Automatic Disconnect Switch User Manual Installation Automatic Disconnect Switch enclosure e UPS literature kit containing e Two mounting brackets product documenta
4. Broadband Automatic Disconnect Switch www apc com User Manual 990 1929 09 2004 Introduction Introduction About this unit Redundant power and output voltage monitoring for Broadband cable systems is provided with the use of two APC Automatic Disconnect Switches and two Ferroresonant Power Supplies FRP Safety Electrical Warnings Do not work alone under hazardous conditions High current through conductive materials could cause severe burns Do not work alone under hazardous conditions High current through conductive materials could cause severe burns Do not handle any metallic connector before the power hs been disconnected When grounding cannot be verified disconnect the equipment from the utility power outlet before installing or connecting to other equipment Reconnect the power cord only after all connections are made Check that the power cord s plug s and socket s are in good condition Replacement of fuses or other parts must be with identical types and ratings Substitution of nonidentical parts may cause safety and fire hazards In order to maintain compliance with the EMC directive for products sold in Europe output cords attached to the UPS should not exceed 10 meters in length Specifications Environmental Specifications Temperature Operating 32 to 122 F 0 to 50 C Storage 5 to 122 F 15 to 50 C Humidity 0 to 95
5. ONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Specifically APC is not liable for any costs such as lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data costs of substitutes claims by third parties or otherwise Broadband Automatic Disconnect Switch User Manual 13 Troubleshooting Service Contact Warranty and Regulatory Information Service If the unit requires service do not return it to the dealer Follow these steps Review the problems discussed in Troubleshooting to eliminate common problems 2 If the problem persists contact APC Customer Support through the APC Web site www apc com Note the model number of the unit the serial number and the date purchased If you call APC Customer Support a technician will ask you to describe the problem and attempt to solve it over the phone If this is not possible the technician will issue a Returned Material Authorization Number RMA Ifthe unit is under warranty repairs are free Procedures for servicing or returning products may vary internationally Refer to the APC Web site for country specific instructions 3 Pack the unit in its original packaging If this is not available refer to the APC Web site for information about obtaining a new set Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained
6. RP Secondary Status e The secondary Automatic Disconnect Switch is supplying power to the cable system The Local Power LED will be illuminated The secondary Automatic Disconnect Switch will momentarily disconnect the local power from the cable system allowing the primary system to supply power If the primary system begins to supply power the secondary system will remain disconnected If the primary system fails to supply power the secondary system will immediately begin supplying power to the cable system e When the secondary Automatic Disconnect Switch is not supplying power to the cable system the Remote Power LED will be illuminated The Automatic Disconnect Switch will perform a test to measure the output voltage from the local FRP Local 63 V Fault Green LED indicates The FRP FLM output is outside the specified range during a test The output failed while the Automatic Disconnect Switch was supplying power Primary Secondary Select This control is used to establish the Automatic Disconnect Switch as the primary or secondary power source for the cable system Primary Green LED indicates that the Automatic Disconnect Switch is the primary power source Secondary Green LED indicates that the Automatic Disconnect Switch is the secondary power source 220 V Normal Green LED indicates that 220 V input is present and within specified limits Cable Modem The cable modem functions only when power is supplied by the Automatic Di
7. o the enclosure two screws must be used in each bracket Utility Power Connections Installation must be performed by a qualified electrician Adhere to all local state federal and or National Electric Code NEC regulations regarding location permits and electrical wiring Install an approved 20 A high magnetic circuit breaker on the input side of the Automatic Disconnect Switch Utility wiring panel with holes for wires Output Hardwire Input Hardwire Broadband Automatic Disconnect Switch User Manual Installation Hardwire the Automatic Disconnect Switch Step o Remove the utility wiring panel located on top of unit When required apply a strain relief grommet to the utility wiring panel holes Step eo e Route the building wiring through the holes in the utility wiring panel Connect the 220 V building wiring to the Input Hardwire terminal block Step e Route the input wiring for the FRP FLM through the hole in the utility wiring panel Connect the FRP FLM input wiring to the Output Hardwire terminal block Step o Reinstall the utility wiring panel Secure the panel with the screw removed in Step UV Broadband Automatic Disconnect Switch User Manual 7 Installation Cable System Connections USB Cable F Connector Connector Cable Modem Utility Power IEC Recepticle F Connector Installation
8. ondary Access Panel To remove the access panel covering the Primary Secondary Select button remove the screw that secures the panel to the enclosure Slide the access panel slightly to the right and then pull the access panel toward you Operation Indicators and Controls Circuit Breaker Local Power O Remote Power C Reset Test Local 63V Fault Primary Secondary Select Primary Secondary 220V Normal Circuit Breaker The circuit breaker protects the 220 V input from overload conditions Local Power Green LED indicates that the Automatic Disconnect Switch is providing power to the cable system Remote Power Green LED indicates the cable system is receiving power from a source other than the Automatic Disconnect Switch Broadband Automatic Disconnect Switch User Manual 11 Operation Reset Test Functionality of this control is dependant upon Automatic Disconnect Switch status Primary Status The primary Automatic Disconnect Switch is supplying power to the cable system The Local Power LED will be illuminated The Reset Test button will do nothing When the primary Automatic Disconnect Switch is not supplying power to the cable system the Remote Power LED will be illuminated The Automatic Disconnect Switch will perform a test to measure the output voltage from the local F
9. perty of their respective owners 14 Broadband Automatic Disconnect Switch User Manual
10. sconnect Switch to an FRP If the FRP fails the cable modem will continue to function 12 Broadband Automatic Disconnect Switch User Manual Troubleshooting Service Contact Warranty and Regulatory Information Troubleshooting Service Contact Warranty and Regulatory Information Troubleshooting Use this chart to solve minor installation and operation problems Refer to the APC Web site www apc com with complex problems Problem and or Possible Cause Solution Unit is on and the 220 V Normal LED is not illuminated The unit is not wired properly Check that the input and output wiring are not reversed The circuit breaker is tripped Reset the circuit breaker The 220 V power is outside the specified Check that the 220 V power is within specified limits Refer to Specifications in this limits manual Unit is on and the Local 63 V Fault LED is illuminated The unit is not connecting power to the cable Check that the coax connections are not reversed system Check that the FRP FLM output is within specified limits Refer to Specifications in this manual Secondary unit will not switch to Remote power when the Test button is pressed Remote power system is not functioning This is normal operation Verify that the Remote power system is working Primary unit is indicating Remote power Primary unit was powered up after the This is normal operation Press the Reset button on the secondary unit to tran
11. sfer secondary unit power to the primary unit The primary FRP FLM output is not within specified limits Refer to Specifications in this manual Limited Warranty American Power Conversion APC warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase Its obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products To obtain service under warranty you must obtain a Returned Material Authorization RMA number from customer support Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase EXCEPT AS PROVIDED HEREIN AMERICAN POWER CONVERSION MAKES NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some states do not permit limitation or exclusion of implied warranties therefore the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL APC BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR C
12. tion Four screws safety information warranty information One F Connector nut Schematic Overview of the Automatic Disconnect Switch System The user must designate the primary and secondary power supply Refer to Reset Test in the Operation section of this manual for details Primary FRP supplying power to two buildings Primary Power Supply Secondary Power 220 VAC 220 VAC FRP4 l FRP2 CS es 9 63 VAC 63 VAC 63 VAC 63 VAC cable blocking Power Power blocking K cable element E element Q Q 8 8 v N D D Z ks S 2 2 e a Broadband Automatic Disconnect Switch User Manual Installation Mount the Automatic Disconnect Switch on the Wall Do not operate the UPS where there is excessive dust or the temperature or humidity are outside the specified limits The Automatic Disconnect Switch enclosure has side vents To ensure adequate air flow in and around the unit there must be 1 2 5 cm of space on the right and left sides of the enclosure Mount the Automatic Disconnect Switch enclosure on the wall using screws appropriate for the weight of the unit and the mounting surface material Install the Mounting Brackets on the Automatic Disconnect Switch Enclosure When securing the mounting brackets t