SunKeeper Manual
Contents
1. voltage will NOT be 14 1V The output voltage is a pulsed waveform The multimeter will display the average or RMS of the waveform If there is no voltage output the SunKeeper may be damaged Keep the solar module connected and connect the battery to the Battery output leads If the sunKeeper is in Bulk charge solid green LED the voltage on the Solar Input terminals should be the same as the voltage on the Battery output leads If the SunKeeper is in Regulation blinking green LED the battery voltage should be maintained at full charge voltage 18 6 2 Flashing Red LED Installation Error or Operation Fault SunKeeper is not damaged A red flashing LED indicates that a fault exists in the system or the SunKeeper faulted during operation Corrective action is needed Check the system for the following conditions Reverse Battery The battery connection is reversed at the SunKeeper or at the battery terminals Disconnect the battery connection at the SunKeeper and measure the voltage with a voltmeter Verify correct polarity Connecting the battery with correct polarity will clear the fault condition RTS Disconnected If a Remote Temperature Sensor is wired to the SunKeeper the cable may be pinched or broken Inspect the RTS cable and connections for frays or breaks Properly reconnecting the RTS will clear the fault condition Over current Condition The charging current exceeds the current rating of the SunKeepe
2. SunKeeper continuously monitors for system faults blinking red LED and critical SunKeeper internal circuit faults solid red LED This section explains how to test a SunKeeper for correct operation and provides troubleshooting checklists for both types of faults 6 1 Testing for Correct Operation The SunKeeper operation can be verified by simply measuring a few voltages You will need a volt or multi meter to take voltage measurements If testing the SunKeeper on a bench a power supply which is current limited to 2A and 15V can be used instead of a solar module 1 Disconnect the battery and solar module from the SunKeeper 2 Connect a battery 11V or more to the sunKeeper battery leads Verify that the LED blinks green 3 times on power up The LED should remain off after start up Night condition 3 Measure the voltage on the SunKeeper Solar input leads Solar to Common The voltage on the Solar input leads should be approximately half of the measured battery voltage If the voltage is zero volts or about the same as 17 battery voltage there is a problem with the SunKeeper Disconnect the battery Connect the solar module in full sun to the SunKeeper Solar input leads The LED should blink 3 times After a few seconds the LED should begin blinking green Regulation Measure the output voltage on the open Battery leads Battery to Common Voltage should exist on the Battery leads however the output
3. Wiring may differ slightly depending on the solar module manufacturer Terminal locations and the number of terminals may also differ Splices may not be necessary if extra junction terminals are provided Refer to the documentation supplied with the solar module In the battery box wire an in line fuse holder and fuse to the Battery cable Connect the battery cables to the battery lugs Refer to section 2 1 Installation Notes System Fusing If a Morningstar RTS is used secure the RTS terminal lug to a battery lug Uncover the solar module and replace the j box cover 2 3 Surface Mounting CAUTION To conform to Class 1 Division 2 Group A B C D hazardous location requirements the SunKeeper and wiring must be contained inside an approved enclosure 1 Plastic mounting feet are included with the sunKeeper to allow for surface mounting Figure 3 Mounting Feet Assembly 2 Assemble the SunKeeper mounting feet and locknut as shown in Figure 3 3 Place the SunKeeper on the surface where it will be mounted and determine where the wires will be routed Be sure there is sufficient bending room for the wires With a pen or pencil mark the location of the screws 4 With a drill and 1 8 3 mm bit drill pilot holes for both mounting screws where marked in step three 3 10 5 Place the SunKeeper onto the surface and align the two 2 mounting feet slots with the pilot holes Use 10 M5 pan head screws no
4. SK 12 Self consumption Current Battery Operating Range Battery Charging Setpoints Regulation Voltage Float Voltage Temperature Compensation Maximum Charge Voltage Limit Mechanical Power Wires red yellow black RTS Wire Loop blue Leads Conductor Material Weight Dimensions Knockout Size Environmental Ambient Temperature Range Storage Temperature Range Humidity Oxygen Concentration Atmospheric Pressure 22 12V 30 V 6A 12A lt 7 0 mA charging 2 0 mA night 0 15V 14 10 V 25C 13 70 V 25C 30 mV C 15V 2 0 mm 14 AWG 0 13 mm 22 AWG Copper 0 11 kg 0 25 Ibs 99x51x13 mm 3 9x2 0x0 5 in M20 PG 13 5 72 40 C 40 F to 70C 158 F 55C 67 F to 85C 185 F 100 lt 21 by vol 1 atm Protections Reverse Polarity Solar and Battery Short Circuit Solar Charging Over current High Temperature shut down Temperature Sensor Failure Nighttime Reverse Current Leakage no blocking diode needed Certifications CE UL 1604 and CSA 22 2 No 213 M1987 for use in Class 1 Division 2 Groups A B C D hazardous locations Specifications subject to change without notice MS ZMAN SKO01 A DEC 2005 23
5. SUNKEEPER Solar Charge Controller Installation and Operation Manual Junction Box J Box Mounted Solar Controller Models SunKeeper 6 6A 12V SunKeeper 12 12A 12V MORNINGSTAR 1098 Washington Crossing Road Washington Crossing PA 18977 USA www morningstarcorp com Table of Contents 1 0 Safety Instructions 3 2 0 Installation 4 2 1 Installation Notes 4 2 2 Mounting to a J box 6 2 3 Surface Mounting 9 3 0 LED Indications 12 4 0 Operation 13 4 1 Operator s Tasks 13 4 2 Charging Algorithm 13 4 3 Charging Features 14 4 4 Protections 15 5 0 Inspection and Maintenance 16 6 0 Troubleshooting 17 6 1 Testing for Correct Operation 17 6 2 Flashing Red LED 19 6 3 Solid Red LED 20 7 0 Warranty 21 8 0 Technical Specifications 22 1 0 Safety Instructions SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed for proper installation and maintenance Read all of the instructions and cautions in the manual before starting the installation WARNING Be very careful when working with batteries Lead acid batteries can generate explosive gases and short circuits can potentially draw hundreds or thousands of amps from the battery Do not exceed the voltage or current ratings of the controller Use only with a 12V battery There are no user serviceable parts in the SunKeeper Do not disassemble or attempt to repair The negative system conductor should be properly gro
6. e product to your authorized Morningstar distributor with shipping charges prepaid Provide proof of date and place of purchase To obtain service under this warranty the returned products must include the model serial number and detailed reason for the failure This information is critical to a rapid disposition of your warranty claim Morningstar will pay the return shipping charges if the repairs or replacement are covered by the warranty WARRANTY EXCLUSIONS AND LIMITATIONS This warranty does not apply under the following conditions Damage by accident negligence abuse or improper use Unauthorized product modification or attempted repair Damage occurring during shipment THE WARRANTY AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE AND IN LIEU OF ALL OTHERS EXPRESS OR IMPLIED MORNINGSTAR SPECIFICALLY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES INCLUDING WITHOUT LIMITATION WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE No Morningstar distributor agent or employee is authorized to make any modification or extension to this warranty MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING BUT NOT LIMITED TO LOST PROFITS DOWNTIME GOODWILL OR DAMAGE TO EQUIPMENT OR PROPERTY 21 8 0 Technical Specifications i Electrical Nominal System Voltage Maximum Solar Input Voltage Rated Solar Input SK 6
7. l transition to Float stage and the green LED will continue blinking No LED OFF Night condition No solar power is available for charging The SunKeeper is in sleep mode until solar power becomes available A single blink of the green LED every 5 seconds indicates that the SunKeeper is still powered and operational Red blinking LED System installation error and or operation fault See Section 6 2 in Troubleshooting Red ON LED Critical fault See Section 6 3 in Troubleshooting 12 4 0 Operation 4 1 Operator s Tasks The SunKeeper is a fully automatic solar charge controller that includes many electronic functions to protect both the controller and the system The only manual tasks performed by the operator are a Installation see section 2 0 b Temperature Compensation selection see section 2 1 Temperature Compensation Select c Routine Maintenance see section 5 0 4 2 Charging Algorithm The SunKeeper battery charging algorithm is optimized for sealed lead acid batteries There are four main stages to the charging algorithm Night There is no solar power available the solar module is disconnected from the battery to prevent nighttime reverse current leakage Bulk Charge Solar power is available the battery is recharging and has not yet reached full state of charge Regulation The battery has charged to the Regulation setpoint the SunKeeper is limiting 13 solar charging current
8. open No temperature compensation Insulate cap loose ends Loop cut connected to RTS Remote Temperature Sensor RTS used for temperature compensation The RTS is an optional Morningstar accessory purchased separately Only use a Morningstar RTS with the SunKeeper Cover the Solar Module s Keep the solar module out of sunlight or covered with an opaque sheet until installation is complete SunKeeper Wire Lead Definitions Solar Yellow Battery Red Common Negative Black RTS Option Blue Loop NOTE The RTS connection has no polarity The red and black RTS wires may be wired to either of the blue Temperature Compensation Loop leads 2 2 Mounting to a J box NOTE Complete steps 1 through 7 before mounting the solar module SOLAR MODULE BOTTOM VIEW CONDUIT Figure 1 Typical System 1 Remove the solar module j box cover refer to solar module documentation if necessary 2 Unscrew the SunKeeper locknut and remove the plastic mounting feet Store the mounting feet in a safe place They are not needed when mounting to a j box On the solar module j box choose knockouts or drill 7 8 inches 22 2 mm holes for the SunKeeper and 77 conduit entry into the j box If drilling holes choose locations that will allow easy wiring access to the solar module power terminals and easy exit into the 72 conduit Insert the SunKeeper leads into the ch
9. osen knockout or drilled hole Thread the SunKeeper leads through the locknut and slide the locknut down to meet the threaded neck of the SunKeeper Screw the locknut hand tight onto the threaded neck of the SunKeeper The rubber o ring should seat firmly against the j box outside wall around the perimeter of the hole forming a watertight seal When satisfied that a good seal is made fully tighten the locknut Pull 2 cables for battery positive and battery negative as well as the RTS sensor lead if using an RTS through the conduit On the SunKeeper select the temperature compensation configuration required Refer to section 2 1 nstallation Notes Temperature Compensation Select If using an RTS a Cut the blue Temperature Compensation Loop on the SunKeeper in the middle of the loop creating two 2 equal length wire leads T Common Black 5 l SuNKEEPER 6 ET SOLAR CONTROLLER RTS Connection Blue Optional terpercettion Refer to section 2 1 Installation Notes System Wiring Refer to section 2 1 Installation Notes Temperature Compensation Select Figure 2 J Box Wiring 10 11 12 b Strip 72 13 mm of insulation off each of the leads c Crimp or splice the two 2 blue wire leads to the two RTS wires red amp black Polarity is not important Refer to section 2 1 nstallation Notes System Wiring Wire the SunKeeper as shown in Figure 2
10. r Be sure that the solar output from the solar module s does not exceed the 6A SK 6 or 12A SK 12 maximum charge current rating High Temperature Disconnect The SunKeeper internal temperature has exceeded safe limits This fault condition will automatically clear when 19 the SunKeeper internal temperature has cooled to a safe operating temperature 6 3 Solid Red LED Critical Faults SunKeeper may be damaged If the SunKeeper Status LED indicates a Solid Red critical fault the SunKeeper should be removed from service immediately Internal Temperature Sensor Failure The internal temperature sensor has failed The SunKeeper can no longer monitor internal temperature which is critical for proper battery charging Damaged Power Transistors Power transistors switch the charging current in the SunKeeper If the power transistors or the circuitry that control them is damaged the SunKeeper can no longer control current The SunKeeper may over charge the battery or not allow any charging current 20 7 0 Warranty The SunKeeper is warranted to be free from defects in material and workmanship for a period of FIVE 5 years from the date of shipment to the original end user Morningstar will at its option repair or replace any such defective products CLAIM PROCEDURE Before requesting warranty service check the Operator s Manual to be certain that there is a fault with the SunKeeper Return the defectiv
11. t Circuit Solar LED OFF stops charging until short clears or will enter Night stage LED OFF if fault persists Charging Over current red blinking LED charging current has exceeded SunKeeper current rating fully automatic recovery retry every 10 seconds High Temperature Condition red blinking LED ambient temperature is too high charging automatically resumes when SunKeeper has cooled to a safe temperature Temperature Sensor Failure red blinking LED detects a failure in the SunKeeper s internal temperature sensor or a disconnect of the Remote Temperature Sensor if used Fault persists until the problem is corrected 15 5 0 Inspection and Maintenance TT The following inspections and maintenance tasks are recommended at least once per year for best controller performance v nspect for loose or broken connections at the battery If an RTS is installed be sure the RTS terminal lug is secured to a battery terminal v Check the wires and cables for frays pinches or other insulation damage v Inspect the SunKeeper plastic case for damage v Verify that the o ring still maintains a seal against the j box outside wall Y Open the solar module j box and inspect for water ingress Also inspect the j box wiring for corrosion and loose connections v Check that the SunKeeper functions and the LED indicator are correct for the system conditions at that time 16 6 0 Troubleshooting The
12. t supplied to secure the SunKeeper to the surface 6 On the SunKeeper select the temperature compensation configuration required Refer to section 2 1 Installation Notes Temperature Compensation Select If using an RTS a Cut the blue Temperature Compensation Loop on the SunKeeper in the middle of the loop creating two 2 equal length wire leads b Strip 72 13 mm of insulation off each of the leads 7 Wire the SunKeeper to the RTS if used and the solar module Refer to section 2 1 Installation Notes SunKeeper Wire Definitions 8 In the battery box wire an in line fuse holder and fuse to the Battery cable Connect the battery cables to the battery lugs Refer to section 2 1 Installation Notes System Fusing 9 Ifa Morningstar RTS is used secure the RTS terminal lug to a battery lug 10 Uncover the solar module 11 3 0 LED Indications Green LED blinks 3 times Indicates correct installation Displayed at installation start up when solar or battery power is first applied Green LED ON Bulk charging stage Solar power is available and the battery is being charged A single blink of the green LED every 5 seconds indicates that the SunKeeper is still operational Green LED fast blinking Regulation Float stage The battery has charged to Regulation voltage solar power is being limited to prevent over charge When the battery is fully charged at Regulation voltage the sunKeeper wil
13. to prevent battery over charge while bringing the battery to full state of charge Float The battery has reached full state of charge and the SunKeeper has reduced battery voltage to the lower Float setpoint 4 3 Charging Features Temperature Compensation Lead acid battery chemistry changes with temperature The SunKeeper adjusts the Regulation and Float voltage setpoints as temperature changes so that the battery is correctly charged The user may choose to add an RTS purchased separately or use the internal temperature sensor Temperature compensation can also be disabled See section 2 1 for more information Maximum Charge Voltage The SunKeeper limits the charge voltage to 15V regardless of ambient temperature so that voltage sensitive DC loads are not damaged Night Disconnect The SunKeeper periodically checks for nighttime condition When night is detected the SunKeeper disconnects the solar module to prevent reverse current leakage An external blocking diode is not required 14 4 4 Protections The SunKeeper is fully protected against system faults listed below Recovery is automatic except where noted below Refer to section 3 0 for fault LED indications Reverse Polarity Solar LED OFF no charging disconnects solar module until wired with correct polarity Reverse Polarity Battery red blinking LED no charging displays fault until battery wired with correct polarity Shor
14. unded per U S National Electric Code NEC guidelines for most effective lightning protection 2 0 Installation Rm LL ELLIILMMALLEZJ 2 1 Installation Notes Hazardous Locations The SunKeeper family of charge controllers has been listed to UL1604 and CSA 22 2 No 213 M1987 for use in Class 1 Division 2 Groups A B C and D hazardous locations In order to comply with the UL and CSA standards the installation should follow the requirements of the National Electrical Code Article 501 4 b and or Canadian Electrical Code Article 18 156 when installing a SunKeeper in a Hazardous Classified Location System Wiring Use copper wire only Power conductors should be joined or spliced using insulated butt splice solderless crimp connectors or by brazing welding or soldering wire ends If soldered the spliced joint should be mechanically and electrically secure before soldering All splices and joints should be covered with insulation equivalent to that of the conductors System Fusing The battery positive lead should be fused no further than 12 inches 305 mm from the battery SK 6 8A fuse SK 12 16A fuse Temperature Compensation Select The SunKeeper has three temperature compensation options The blue Temperature Compensation Loop can be configured for the following temperature compensation options Loop not cut Internal temperature sensor used for temperature compensation factory default Loop cut left