Liebert® IntelliSlot Unity Card
Contents
1. 9 Click Save to confirm the changes or click on Cancel to discard them 10 Configure the BACnet interface chosen refer to Configure BACnet IP Protocol or Configure BACnet MSTP Protocol For additional details see 5 6 Protocols Folder BACnet Folder Figure 3 4 BACnet protocol settings Welcome Liebert Administrator NI EMERSON Network Power GXT4 1000RT120 Sensor Communications E le be rt BACnet Updated February 9 2015 10 16 03AM Settings Units i Managed Device Write Access i BACnet Interface Identification Uninitialized Uninitialized Uninitialized i Device Object Instance Number atea i Device Object Name i APDU Timeout iy APDU Retries GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications E Summary Active Events Downloads Configuration Protocols CI BACnet IP IBACnet MSTP 3 1 2 1 Configure BACnet IP Protocol Contact your system administrator if you are uncertain about the settings l 2 3 4 Select Communications Tab gt Protocols gt BACnet IP Click on Edit and enter a User name and password if required Set the BACnetIP Port Number If the Liebert IntelliSlot Unity card is on a different subnet a possibility when the monitored units are part of a Liebert SiteScan network or other third party monitoring service a Choose whether to enable Register as Foreign Device b
2. E Summary Active Events Bypass Battery Output Outlet Group 2 EcoMode System The Managed Device Tab will display Status Events or Settings for the applicable equipment only Environmental information is shown in this Managed Device Tab for Thermal Management equipment NS AS EMERSON Network Power Identification Unity Unity Communications C Liebert CRV Normal Operation Sensor Normal Operation Communications Normal Operation Liebert CRV Summary EJ Active Events Downloads Air Temperature Humidity Fans Remote Sensors 10 C3 Compressor C3Reheater C Condenser Chilled Water C System Info System Operations Event Configuration System Events Asset Management Time Supported Status Supply Humidity Return Humidity Supported Events High Return Humidity Low Return Humidity Humidifier Hours Exceeded Dehumidifier Hours Exceeded Humidifier Under Current Humidifier Over Current Humidifier Low Water Humidifier Cylinder Worn Humidifier Issue Ext Humidifier Lockout Humidifier Control Board Not Detected Return Humidity Out Of Proportional Band Dehumidifier Disabled Dehumidifier 12 Hour Lock Out Dehumidifier Enabled Humidifier Disabled Humidifier Enabled Supported Settings Humidity Set Point Humidification Proportional Band Dehumidification Proportional Band Humidity Dead Band High Return Humidity Threshold Low Return H
3. Password IPv4 Settings Shown Login Cancel Enter the Administrator Name and Password defaults are Liebert and Liebert These should have been changed to enhance security see 2 2 Change User Names and Passwords Immediately 2 4 Save and Cancel Buttons Welcome Lieber Administrator Legout Liebert Updated f elyuary 9 2015 10 04 22AM GXT4 1000R 1 20 Communications if T Identification Settings IPv4 Protocol Units Uninitialized Uninitialized Uninitialized IP Address Method Static IP Address O i a a V Subnet Mask GXT4 1000RT120 J f Gateway Normal Operation Y Defeuli Gateway Sens U UNS Server Address Source y Primary ONS Server D Secondary ONS Server 10 20 64 11 Sensor Normal Operation Communications P Summary Active Events A Downloads CX Configuration System User Sa Network _jIPv4 C3IPv6 Installing Multiple Liebert IntelliSlot Unity Cards in a System More than one Liebert IntelliSlot card may be installed in a system but circular routes and duplicate node ID s must be avoided during installation The instructions below apply if the second card to be installed 1s a Liebert IntelliSlot Unity card If the second card is not a Liebert IntelliSlot Unity card follow instructions in the user manual for that card Before beginning installation of a second Liebert IntelliSlot card verify that the first card functions prop
4. computer and type 169 254 24 7 the card s default Autoconfiguration IPv4 Address in the URL address field The card s Web page will appear Figure 2 1 Command prompt access Ethernet adapter Local Area Connection Connection specific DHS Suffix Description Physical Address a DHCP Enabled Autoconfiguration Enabled Link local Pub Address Autoconfiguration lIPv4 Address Subnet Mask Default Gateway DHCPu amp IAID DHCPu Client DUID Intel lt R 82579LM Gigabit Network Connection EH DB 55 E2 3F 54 Yes Yes fFfeBB idcA 2a66 amM1f f9 2 a 11icPreferred gt 169 254 249 Preferred 255 255 0 0 266374453 5 e a E a rr A 2 1 3 Connect an RS 485 Serial Cable 2 2 For Building Management Systems using serial network connections an RS 485 serial cable connection will be used Liebert IntelliSlot Unity cards come with an Adapter RJ 45 2POS Terminal Block The adapter has two screw terminals to attach the ends of a RS 485 cable for communicating to a building management system 1 Find the serial cable from the building management system If it already has an RJ 45 connector on the end determine whether it uses the same pinout as the Liebert IntelliSlot Unity card s connector If the pinout is the same as the Liebert IntelliSlot Unity card connector s pinout skip to Step 7 2 Strip the ends of the positive typically red and negative typical
5. f TM TM Liebert IntelliSlot Unity Card User Manual Web SNMP Modbus BACnet YDN23 wmm pos wr am j o UU l UPC 20 130 5 5 i Jue ua Activity Link 1 A EMERSON Network Power Table of Content IMPORTANT SAFETY INSTRUCTIONS 2 000 c cee eere hh hh nnn 1 LO INTRODUCTION cultas Aa qst a is 2 LEPOLO oy aso how II E esa 2 1 2 Compatibility With Other Emerson Products and Communication Protocols 3 Lo pupport tor Liebert oN DEN Or ener Ar 4 2 0 INSTALLATION 6 rd dai Ed Ed Etc ibam 5 2 1 Installing the Liebert IntelliSlot Unity Card o oooooo ooo o 5 21 Assionins the Cards IF Address iria slats 5 2 1 2 Connect an Ethernet Cable 45 arre yA AA a 6 2 1 9 Connect an RS 485 Serial Cables iii id id 7 2 2 Change User Names and Passwords Immediately o ooooooooo momo oo o T 2 OMMOURE TNC JEOex Soc bU a A A AAA 8 2 4 Installing Multiple Liebert IntelliSlot Unity Cards in a System 9 3 0 ENABLE COMMUNICATION PROTOCOLS lesen nnn 11 oJ Ton Ler POLOCDIS Cons tase ok b adt a he a eheu arce qa ah ee ak Oy a a eh ae a 11 sal Enable Modbus Protocols aes AR EHE RUE I ck I ERE a udo A A 12 o I lobcontsure Modbus TOP acci a edu oA OAR i Fed ah eS 12 o 1 1 2 Confiture Modbus RTU 44x eode d te ab ODES EMER DA CR OSS aU Rn 13 9 12 Enable BACnet Protocols a4 xu rear d ERE Ao b dH SE A ER CES 14 3 1 2 1 Configure BACnet IP Pro
6. COMMUNICATION PROTOCOLS The Liebert IntelliSlot Unity card will communicate with equipment and third party systems over these protocols 3 1 BACnet IP BACnet MSTP Modbus TCP Modbus RTU SNMP YDN23 NOTE No more than two protocols may be enabled on one card Only one version of BACnet may be selected either BACnet IP or BACnet MSTP Only one version of Modbus may be selected either Modbus TCP or Modbus RTU Only one of the protocols can use the 485 port choosing two 485 protocols will cause conflicts NOTE Some Building Management Systems can be configured to send continuous updates for device setpoints usually setting the same value The BMS should be configured to send on a sustained average no more than two writes per second to the device This will allow the device to catch up after a burst of updates when required while allowing other communication with the device to proceed Enable Protocols Protocols may be enabled after a card has been installed and configured After a protocol is enabled it must be configured which requires opening that protocol s folder Communications Tab Protocols desired protocol To enable two communication protocols 1 2 3 Select Communications Tab gt Protocols Click on Edit and enter the administrator user name and password Put a check mark 9 in the desired protocols Only two may be enabled only one of the two can use the 485 port Click S
7. City 1605 Philippines 63 26876615 Fax 63 2 730 9572 www EmersonNetworkPower com
8. Current Firmware Label IS UNITY_4 0 0 0 83532 Uninitialized iy Current Firmware Date Feb 28 2014 15 33 57 ij Alternate Firmware Version 41 040 Status i u Alternate Firmware Label IS UNITY 3 1 0 0 82316 APS i Alternate Firmware Date Jan 9 2014 15 52 31 Hormal Operation Normal Operation TIPS Enable Enable Button i Run Alternate Firmware Run Alternate i Firmware Update Unity Web button becomes active when enabled and administrator s user name and password are entered Summary EJ Active Events Downloads 9 Configuration Support Protocols Folder Administrator login is required Username Firmware Update td ri unie User name and Password password must be entered to update Login Cancel firmware Revert to Alternate Firmware The Liebert IntelliSlot Unity card has two areas in flash memory for the firmware and the configuration One area 1s currently operating on the card The other area is considered an alternate When a card s firmware 1s updated the previous firmware and configuration are moved to the alternate area The Liebert IntelliSlot Unity card allows returning to the firmware version and configuration that are kept in the alternate area NOTE Reverting to an alternate firmware version will not be possible if the currently operating firmware is the initial version loaded on the Liebert IntelliSlot Unity card If the initially loaded firmware is stil
9. Enter the IP address of the BBMD BACnet Broadcast Management Device c Entera time in seconds for Foreign Device Time to Live Click Save to confirm the changes or click on Cancel to discard them Liebert IntelliSlot Unity Card User Manual 15 6 Restart the card to activate the changes a Select the Communications Tab gt Support b Enable the commands c Click on Restart Figure 3 5 BACnet IP A NS EMERSON Network Power Identification Uninitialized Uninitialized Uninitialized Status GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications E Summary Active Events Downloads Configuration amp yProtocols gt 3IBACnet PTEN IBACnet MSTP Modbus Enable Communication Protocols Welcome Liebert Administrator GXT4 1000RT120 Sensor mmm Liebert BACnet IP Settings iy BACnet IP Port Number i Register as Foreign Device ij IP Address of BBMD ij Foreign Device Time to Live 3 1 2 2 Configure BACnet MSTP Protocol Contact your system administrator if you are uncertain about the settings Po Se Ee d do 16 Updated February 9 2015 10 18 17AM Edit Save Cancel Units 47808 T enabled 1800 sec Select Communications Tab gt Protocols gt BACnet MSTP Click on Edit and enter a user name and password if required Set the BACnet MSTP Node ID The ID default is 1 Set t
10. IPv6 Global Address i i i 52 fe80 200 68ff fe10 114f 0 sec Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration Active Networking Ethernet MAC Address Ethernet MAC Address for the Liebert IntelliSlot card IPv4 Address Presently used IPv4 network address IPv4 Default Gateway Presently used IPv4 network address of the gateway for network traffic destined for other networks or subnets Primary DNS Presently used IPv4 Primary DNS Secondary DNS Presently used IPv4 Secondary DNS Last DHCP BOOTP Address Last known IPv4 address assigned by DHCP Last DHCP Lease Lease time of last known DHCP address IPv6 Global Address Shows 1f DHCPv6 or Static address 1s presently being used StateLess Address AutoConfiguration IPv6 SLAAC 1s assigned automatically from Router Advertisement if A flag is set combining Prefix with EUI 64 MAC Link Local Presently used IPv6 Link Local Address IPv6 Default Gateway Presently used IPv6 network address of the gateway for network traffic destined for other networks or subnets Primary DNS Server IPv6 Primary DNS Secondary DNS Server Presently used IPv6 Secondary DNS Last DHCPv6 Last known IPv6 address assigned by DHCPv6 Last DHCPv6 Lease Lease time of last known DHCPv6 address 5 11 2 Communications Tab Support Folder Firmware Update The Firmware Update folder supports updating the firmware of the Liebert Intel
11. Tr sted IP bist 226243 35 42 A eat Oh A ete arg ob 13 PICU o Modbus ROAST re lud eo ed anie don b ate opm ira t ean d c A IU EON col E diu Ee a 14 Figure 3 4 BACnet protocol SEUS wa DUREE ODER BREE ORA REAL ERS ERE NE RIA RR ERG Ru 15 Eisure 6 0 BAGBOU EDD ec a PPS PME de ds ded aet Vui tiet das quideni eei a 16 Eisurew o6 BAC CHet NESST Pu eE Cu ear em re RES De RS ACA SONITUS TU AIG EO Busto Ne EE d t Fome o ONM P is a A ai e a A A oe A aio 18 Figure 0 9 9NMPY23 User Sethe char qe reti A A ede gU Qoa RR UR A A d erga 19 Inseure 2 94 NMPVIL trap Sethi eS esssiba dede Sta a e XE ES E db ved SE E ET ex dede 20 FE3suje 3 10 SNMPVIIVZCAOCOSS setto Srs quio aes eod dr on ee Peed ew hee Pam EST RS 21 Figure 4 1 Web page sections UPS example llle I e ass 23 Figure 4 2 Web page sections Thermal Management unit example lees 23 Figure 4 3 Managed Device Web page withoutsensors lees 24 Figure 4 4 Help text on mouse over lees Re s 25 Figure 4 5 Managed Device Tab examples Liebert GXT4 and Liebert CRV 0 cece eee eee eee 26 Figure 4 6 Sencor Fan MEA d do Sud A eres AA Heese dte deeb eae A AA 28 Figure 4 7 Sensor Tab Summary page layout 0 cc ee ee n 29 Figure 4 8 Sensor details Door closure and temperature sensor examples o oooooooo oo 30 Figure 4 9 Changing Sensor Ode ns 6444 26 40 AA RR A ORE GC EA RE S eA ud deus 31 Figure 5 1 Editing configuration settings 32 Figure
12. address of the gateway for network traffic destined for other networks or subnets DNS Server Address Source Source of DNS server identification None Automatic Configured Primary DNS Server Secondary DNS Server IPv6 Settings IPv6 Protocol Enables IPv6 in the card IP Address Method Mode the card boots into to be a network ready device Static Auto Static IP Address Network address for the interface Prefix Length Prefix length for the address that divides a network into manageable segments Default Gateway IP address of the gateway for network traffic destined for other networks or subnets DNS Server Address Source Source of DNS server identification None Automatic Configured Primary DNS Server Secondary DNS Server 36 Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 3 3 2 Domain Name Server DNS Test The Domain Name Server Test checks key points of a Domain Name Server DNS setup for a given domain E Summary Communications Active Events E Ga Downloads Status Value Units Cy Configuration i Last Query Response aSystem User Settings Save Gance Units 3 Network i Type of Query Hostname 3IPv4 C3IPv6 i Query Value Domain Name Server DNS Test Web Server Domain Name Server DNS Test Settings Last Query Response Response from a domain name server DNS to the last query Example gxtwebdemo liebert com resolv
13. pane to change a value Updated February 26 2015 03 21 30PM Value Units 246 C Status Units C C C C Editing a Door Closure Sensor A label indicating the sensor s location can be added The alarm configuration offers a drop down menu to choose when an alarm will be activated Liebert IntelliSlot Unity Card User Manual Liebert IntelliSlot Unity Card Web Page Layout 46 Changing Sensor Order Sensors are listed in the order they are installed The order can be changed to put sensors deemed more important at the top of the list To change the order of the sensor list 1 Click on Sensor Tab gt Sensor Order 2 Click on Edit 3 Enter the user name and password 4 Select the sensor to be moved higher or lower in the list This highlights the radio button beside the sensor to be changed 5 Use the arrows at the right side of the list to move the sensor up or down 6 Click on Save Repeat the steps for any other sensors to be moved higher or lower in the list Figure 4 9 Changing sensor order A Welcome Liebert Administrator by EMERSON os Network Power GXT4 1000RT120 MES Liebert Sensor Order Updated February 9 2015 12 05 23PM Identification Sana Cancel pararse ID Select Type Name Serial Number Uninitialized 1 Temperature 127 6 F000000003769742 2 Temperature 127 9 A70000000368FA42 124 1 Front This arrow Status 3 Door Closure 124 1 Back B90000000DE10420 moves
14. settings in this folder permit configuring the card for various types of SNMP communication including access traps and other user settings Status Value Units Communications i SNMPv3 Engine ID a00001DC03000068123451 E Summary au di aga I a Gq Active Events Settings Edit ave Cancel Units Downloads i SNMMPv1 v2c Enable I enabled C Configuration 3 G3 Protocols i SNMPv3 Enable F enabled CgBACnet i Authentication Traps enabled pin x Heartbeat Trap Interval 24 hours x RFC 1528 MIB enabled LE9 SNMPv3 User 20 i 3 C9 SNMPv1 Trap 20 i T i v y C9SNMPv1 v2c Access 20 ES eee ee eps M enabled C3 YDN23 i Liebert Global Products LGP MIB F enabled Status i LGP MIB Traps 7 enabled Support i LGP MIB System Notify Trap F enabled SNMP Settings SNMPv3 Engine ID The SNMPv3 engine ID assigned automatically SNMP v1 v2c Enable Enable or Disable SNMP v1 v2c SNMP v3 Enable Enable or Disable SNMPv3 Authentication Traps An Authentication Trap is sent if an SNMP host tries to access the card via SNMP but either the host address is not 1n the SNMP Access Settings or it 1s using the wrong Community String Heartbeat Trap Interval Enable or Disable and set interval 5 minutes 30 minutes 1 hour 4 hours 8 hours 12 hours and 24 hours RFC 1628 MIB Enable or Disable support for retrieval of data from the RFC 1628 MIB objects Required for proper operation of Liebert MultiLink and applies onl
15. the general user are User and User To change either click on Edit enter the default username and password and enter the new information Click on Save to accept the changes or click Cancel to discard the changes Settings Units Communications i Administrator Username Summary ui i Administrator Password TELLI Active Events f3 Downloads i Reenter Administrator Password mmT 7 io General User Username Tse O ystem C User 4 General User Password orm Network 1 Reenter General User Password mm 5 3 3 Configuration Folder Network The top level of the Network subfolder displays Speed Duplex Domain Name Suffix List Telnet Server The Speed Duplex item selects the speed and duplex configuration of the card s Ethernet port It 1s set to Auto by default If 1t requires changing contact the system administrator for the proper settings The Domain Name Suffix List 1s a listing of domain name suffixes for resolution of hostnames If it requires changing contact the system administrator for the proper setting The Telnet Server item allows disabling telnet access to the card to prevent unauthorized changes The default setting enables telnet access The Network subfolder contains three subfolders related to communication Communications gt gt E Summary Active Events Downloads gt Configuration Settings Edit Units ot ia i Speed Duplex Sy Network i Domain Name Suffix List 2 i Tel
16. under IP Settings SMTP Server Port SMTP server port Note Typically the default of 25 should be used Include IP Address in Message lIf checked the IP Address of the agent card will be included in outgoing messages Include Event Description in Message If checked SNMP event description will be included in outgoing messages Include Name in Message If checked the agent card Name will be included in outgoing messages Include Contact in Message If checked the agent card Contact will be included in outgoing messages Include Location in Message lIf checked the agent card Location will be included in outgoing messages Include Description in Message lIf checked the agent card Description will be included in outgoing messages Include Web Link in Message If checked a Web link to the agent card and Web Server listening port number will be included in outgoing messages Enable Event Consolidation If checked multiple events will be sent per outgoing message Consolidation Time Limit If Event Consolidation 1s enabled a message will be sent when Consolidation Time Limit seconds has passed since the first buffered event was received Consolidation Event Limit If Event Consolidation 1s enabled a message will be sent when the number of buffered events reaches the Consolidation Event Limit 40 Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 4 4 Messagin
17. with val life calllnterval hours Call Trials Number The number of attempts to retry a call after it fails before rescheduling the call UPS State SMS Messaging Configuration CO Desorption OSC The amount of time to delay sending an SMS after a Load is on Bypass if pode pass woe the condition still exists Gate Settings CO scription SSCS Settings Description Call Interval Minutes 58 Liebert IntelliSlot Unity Card User Manual Configuration Folder LIFE Sub folder Advanced a Description Device State Whether the device is connected or unconnected The connection status of the Remote Service Delivery application system Connection Status interface This is the interface by which Remote Service Delivery services communicates with the Unity system software Call Type The type of call currently in progress with the LIFE Watch Station server Scheduled Call Delay Time The delay time before the next call to the LIFE Watch Station server Heartbeat Status Device status as determined by heartbeat traps Date and Time UTC of Last The date and time in UTC of the LIFE Watch Station that was retrieved when Call the last successful call was made YY MM DD HH MM SS Make Manual Call Sends all currently collected events a Scheduled Call Delay Forces a rescheduled call to be done immediately Reset Activity and Data Resets all LIFE in progress activity and deletes all LIFE data Settings De
18. 0 disabled io SNMPv3 Authentication Secret C3 SNMPv3 User 3 i SNMPv3 Privacy None gt CISNMPVv3 User 4 COSNMPv3 User 5 i SNMPv3 Privacy Secret i SNMPv3 Trap Targets io SNMPv3 Trap Port 162 SNMPv3 User Settings SNMPv3 User Enable Select to enable read write or sending notifications with the user s credentials SNMPv3 Username The User name the authentication and privacy settings apply to This string can be composed of printable characters except colon tab double quote and question mark e SNMPv3 Access Type Read Only Read Write or Traps only e SNMPv3 Authentication Cryptographic algorithm used for authentication None MD6 or SHA 1 SNMPv3 Authentication Secret Pass phrase or password used for SNMPv3 Get request This string can be composed of printable characters with the exception of colon tab double quote and question mark Note The entry must be 8 or more characters but not more than 64 SNMPv3 Privacy Cryptographic algorithm used for encryption None or DES 46 Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration e SNMPv3 Privacy Secret Pass phrase or password used for SNMPv3 Get request This string can be composed of printable characters with the exception of colon tab double quote and question mark Note The entry must be 8 or more characters but not more than 64 SNMPv3 Trap Target Addresses Network h
19. 11426 Srvr Room 7 Humidity 16 2 RH Emm m sensor selected Communications Normal Operation Voor Closure Sensor 1 Updated March 27 2015 01 26 20PM Details about the selected sensor the Value Units 1 Status Measurement Position Sensor E Summary Active Events Door Closure State Closed Downloads value will match tpi omi i Events Status Ack the value in the C Sensor Change Sensor Order Door Open Normal Summary pane Settings Door Closure Sensor User Assigned Label Selected sensor s settings click Edit to change a value requires password qe Door Closure Sensor Asset Tag 01 Door Closure Sensor Asset Tag 02 Door Closure State Alarm Config 4 5 2 Sensor Tab Summary Page Details Pane The Details pane of the Sensor Tab window appears when the Summary folder 1s selected The area shows the status of all connected sensors see Figure 4 7 Supported sensors include Temperature Humidity Door Closure Contact Closure Leak Detection Lieberf IntelliSlot Unity Card User Manual 29 Liebert IntelliSlot Unity Card Web Page Layout Selecting a sensor displays details for that sensor The content of the details section 1s specific to the type of sensor selected For example a temperature sensor would show the temperature of the area where it is installed and a door sensor would show whether the door is open
20. 46 30AM Identification Status Value Units Uninitialized ij System Status Normal Operation Uninitialized Uninitialized Events Status Ack System Restart Required Normal Status ume identity changed LIFE TM needs to be aen GXT4 1000RT120 Normal Operation RS 485 Port Conflict Normal Sensor Duplicate Emerson Protocol MSTP Node ID Normal Normal Operation Duplicate BACnet MSTP Node ID Normal Communications Normal Operation Communications E Summary Active Events Downloads Configuration Cg Protocols Status Support 5 11 Configuration Communications Tab Support Folder The Support folder permits restarting the Liebert IntelliSlot Unity card resetting the card to its factory defaults and updating the card s firmware Agent refers to the Liebert IntelliSlot Unity card The folder also displays information about the card for help in troubleshooting such as the card s firmware version label MAC address and related 1nformation M Welcome Liebert Administrator EMERSON ae Network Power GXT4 1000RT120 Sensor mum Liebert Support Updated February 9 2015 11 35 29AM Identification Status Value Units Uninitialized ij Agent Date and Time 2015 02 09 16 35 27 Uninitialized i Agent Model Unity Platform MER i Agent App Firmware Version 5 0 0 0 i Agent App Firmware Label IS UNITY 5 0 0 0 90595 Status i Agent Boot Firmware Version 1 0 0 0 GXT4 1000RT120 ij Agent Boot Firm
21. 5 2 Configuration folder System subfolder o 34 Figure 5 3 Configuration folder System subfolder Time Service 0 0 0 ccc cee eee eee 34 Figure gt 4 IPSATIPVO SObDLIHBS Vibrador dsp weeds 36 Figure 5 5 Editie SNMP tables ais A Oyen wes Ee eee ion aes 47 bisure 621 Ethernet por AS AAA wand datos dem s 55 Figure 6 2 Firmware update screen 0 ee ee eee rs 56 Lieberf CRV IntelliSlot Card User Manual iii List of Tables Table 1 1 Compatibility with Liebert equipment 3 Table 1 2 Liebert IntelliSlot card communication protocolsS ccc ee o 3 Table 4 1 Help text and 16008439 24 ene xis nad het Moa A AR AA A ia A ASA Bees 24 Table 4 2 Communications Tab MenUS c oed or trica wh re ea Lone s oS bk ed LU RRS 24 Table to sensor TabXoldePS x 2 vt dioe ee taa edu ea 28 iv Lieberf IntelliSlot Unity Card User Manual Important Safety Instructions IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS A WARNING Risk of improper installation Can cause equipment damage injury or death Only a qualified service professional should install these products Emerson recommends having an Emerson Network Power Liebert Services representative perform the installation in large UPS s Contact Liebert Services at 1 800 LIEBERT 1 800 543 2378 A WARNING Risk of electric shock Can cause equipment damage injury or death Service and maintenance work must be performed only by properly t
22. 6 1 Relative Humidity 6A000000FCC11426 Nrvr Room 7 Humidity 16 2 RH NEN Graphs show Communications bassi cando Door Closure Sensor 1 Updated March 27 2015 01 26 20PM merece measurements Sensor Status Value Units in relation to E i Measurement Position 1 thresholds for Active Events i Door Closure State Closed temperature Downloads and humidity Sensor Subsystem CES OPUS mm Sensor Change Sensor Order Door Open Normal Settings Units Door Closure Sensor User Assigned Label c Door Closure Sensor Asset Tag 01 Door Closure Sensor Asset Tag 02 Door Closure State Alarm Config qe Table 4 3 Sensor Tab folders Summary Displays a list of currently discovered sensors with their status and values Also displays a detail section about the sensor that is currently selected Active Events Displays a list of sensor events that are currently active Downloads Displays a list of text files that can be downloaded The files available are dependent on the current state of the card Sensor Server System Model Number System Status Too Many Sensors Displays overall information about the sensors Slots Not Available Acknowledge Sensor Changes Sensor Change Lists events showing sensors that have been added or removed If the list has any entries an Acknowledge button appears Clicking the Acknowledge button clears the list The Acknowledge button on this page has the same behavior as the Acknow
23. Change User Names and Passwords Immediately for details SNMP Support The Liebert IntelliSlot Unity card enables SNMP management of Liebert equipment To integrate the card into a SNMP implementation import or compile the Liebert Global Products MIB on the network management station NMS The Liebert Global Products MIB is available at Liebert s Web site www liebert com it supports both Windows 192436P1 and Unix 192435P1 file formats Web Support The Liebert IntelliSlot Unity card delivers Web management and control to Liebert equipment over HTTP and HTTPS All authorized users on your network will be able to view status information Modbus TCP and Modbus RTU Support The Liebert IntelliSlot Unity card supports Modbus TCP and Modbus RTU for the full range of information available from the managed device The Modbus protocol mapping document SL 28170 is available at Liebert s Web site www liebert com Liebert IntelliSlot Unity Card User Manual 3 1 3 Introduction BACnet IP and BACnet MSTP Support The Liebert IntelliSlot Unity card supports BACnet IP and BACnet MSTP for the full range of information available from the managed device The BACnet protocol mapping document SL 28170 is available at Liebert s Web site www liebert com This document includes the BACnet Protocol Implementation Conformance Statement PICS document as a guide to implementing the BACnet protocol YDN23 Support The Liebert Int
24. Email Selections in Email determine how the card sends e mails about events qe q qe dm qe q qe q qe de de de de de OMNI Settings Email From Address Email To Address Email Subject Type Custom Subject Text SMTP Server Address SMTP Server Port Include IP Address in Message Include Event Description in Message Include Name in Message Include Contact in Message Include Location in Message Include Description in Message Include Web Link in Message Enable Event Consolidation Consolidation Time Limit Consolidation Event Limit Units DEFAULT SUBJECT 0 0 0 0 38 Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 4 2 Em ail Settings Email From Address Sender s email address In most cases this will be the email address of the person to whom replies should be sent Example Support company com Email To Address Email address of the recipient Multiple email addresses should be separated by a semicolon The maximum length for an email address is 64 characters Email Subject Type Subject of the email This value will default to the event description The subject line can be customized Custom Subject Text The subject of the email can be changed SMTP Server Address Fully qualified domain name or IP address of the server used for relaying email messages The maximum length for this entry 1s 32 charac
25. L Liebert IS UNITY DP Liebert exM Liebert GXT3 Liebert GXT4 Liebert HPC Liebert Liebert IS UNITY LIFE HPC S M R W Generic Liebert HPM Liebert NX 225 600 kVA Liebert NXC Liebert NXL Liebert NXR Liebert PCW PDX Liebert PeX Liebert XDC Liebert XDP Liebert XDP Cray The Liebert IntelliSlot Unity DP platform supports the following protocols Table 1 2 Liebert IntelliSlot card communication protocols Liebert IntelliSlot Communication Protocols Available Card Part HTTP Emerson Delivery HTTPS Protocol Protocol Liebert IS UNITY DP Liebert IS UNITY LIFE wwe Y Y Y gt gt gt gt YDN23 applicable only to Liebert PeX and Liebert NXL The Liebert IntelliSlot Unity platform supports both 10Mbit and 100Mbit communication speeds and either half or full duplex Sensor Support The Liebert IntelliSlot Unity platform supports these sensors Liebert SN 2D Liebert SN 3C Liebert SN L Liebert SN T Liebert SN TH Liebert SN Z01 Liebert SN Z02 and Liebert SN Z03 Password Protection Control and configuration capabilities are protected by an administrator s username and password combination Optionally status information can be password protected The default user name for the administrator is Liebert and the default password 1s also Liebert The user name and password can be changed with the Web interface See 2 2
26. R 45 DO LONMEVo User Sete sd d wax EU vnu Te oA de a Ie t ts 46 0 0 2 Editie SNNDIPVO Table hs a CEA dde me c SERA ad 47 ooo a Ms a AA UNS SU iM NP EDS Eu RAM AY SS 48 o c DON ViPY LIV ZUECOS iua REACHED ARE SOAM AW A P RC EI Pa e A EC AUC dA 49 5 9 Protocols Bolder YDN239 Protocol i a4 2b ks aser dd DC ar acie ERR a 50 5 10 Configuration Communications Tab Status Folder oooooooooo o 51 5 11 Configuration Communications Tab Support Folder o ooooooo ooo 51 5 11 1 Communications Tab Support Folder Active Networkin8 52 5 11 2 Communications Tab Support Folder Firmware Update 53 ii Liebert CRV IntelliSlot Card User Manual 6 0 FIRMWARE UPDATES 000000 o did 55 6 1 Updating the Liebert IntelliSlot Unity Card s Firmware eee 55 6 2 Revert to Alternate Firmware 56 APPENDIX A CONFIGURATION FOLDER LIFE SUBFOLDER esee 58 Lieber CRV IntelliSlot Card User Manual iii List of Figures Figure 1 1 Liebert IntelliSlot Unity DP card features llle eee 2 Figure 2 1 Command prompt accesar ad is ai A doa eae a eet A 7 Figure 2 2 Change administrator and general user names and passwords o ooooooo ooo ooo 8 Figure 2 3 Enabling the communication protocol IPv4 or IPv6 oooooooooo momo oo oo 9 Figure 3 1 Enable protocols enable commands lle 12 Fistre 29 2 Modbus TOP
27. RFC 1628 MIB Traps enabled i Liebert Global Products LGP MIB enabled iy LGP MIB Traps enabled i LGP MIB System Notify Trap enabled Configure SNMP Settings SNMPv3 Users or SNMPvl v2c Trap and Access settings must be made before SNMP access or notifications can occur The Liebert IntelliSlot Unity card permits up to 20 SNMPv3 Users up to 20 SNMPv1 Trap targets and up to 20 SNMPv1 v2c Access addresses The required changes vary according to the type of SNMP protocol used For SNMPv1 trap settings must be made SNMPv2c must have Access settings made SMPv3 users must have settings configured SNMPv1 trap settings are separate from the access settings for SNMPv1 v2c 3 1 3 2 Configure SNMPv3 The settings must be made for each user who will receive notifications l Select Communications Tab gt Protocols gt SNMP gt SNMPv3 Users Setting 20 gt SNMPv3 Users Setting 1 Click on Edit and enter a User name and password if required Enter the information and set the permissions appropriate to the user Refer to Figure 3 8 for the information required Click Save to confirm the changes or click on Cancel to discard them 18 Liebert IntelliSlot Unity Card User Manual Enable Communication Protocols Repeat Steps 1 through 4 for any additional users Restart the card to activate the changes a Select the Communications Tab gt Support b Enable the commands c Click on Restart Figure 3 8 SNMPv3 user set
28. The Unit of Measure used to display the temperature values 1s defined in the Display Temperature Units setting under Communications tab gt Configuration gt System See 5 3 1 Configuration Folder System Details for the sensors include the current state or reading event status and whether the reading 1s above or below the threshold established 1n the Settings pane Figure 4 8 Sensor details Door closure and temperature sensor examples i i i i Updated February 26 2015 03 17 01PM Door Closure Sensor 1 Status Measurement Position Door Closure State Events Door Open Settings Door Closure Sensor User Assigned Label Door Closure Sensor Asset Tag 01 Door Closure Sensor Asset Tag 02 e Door Closure State Alarm Config Temperature Sensor Status i Temperature Events Over Temperature Under Temperature Settings Temperature Sensor User Assigned Label Temperature Sensor Asset Tag 01 Temperature Sensor Asset Tag 02 TE Over Temperature Alarm Threshold Over Temperature Warning Threshold TE Under Temperature Warning Threshold Under Temperature Alarm Threshold qe Settings Save Cancel Units Door Closure Sensor User Assigned Label Door Closure Sensor Asset Tag 01 Door Closure Sensor Asset Tag 02 Door Closure State Alarm Config none alarm when open 30 Value Units 1 Closed Status Ack Normal Click Edit in the Settings
29. The card s product sequence identifier Commands Enable Cancel Restart Card Restart card and implement configuration changes Reset Card to Factory Defaults Reset the card s configuration to its factory defaults Generate and download diagnostic file Generate a file containing diagnostic information and download 1t with a Web browser 5 11 1 Communications Tab Support Folder Active Networking Status of the currently active IP network settings for the Liebert IntelliSlot Unity card along with some previous values for troubleshooting IP communication issues Y EMERSON Network Power GXT4 1000RT120 Sensor cov Liebert Active Networking Updated February 9 2015 09 56 57AM identification Value Units 00 00 68 10 11 4f 126 4 212 175 Status Ethernet MAC IPv4 Address Uninitialized Uninitialized Uninitialized IPv4 Default Gateway 126 4 212 1 IPv4 Primary DNS Server 10 203 52 131 Status ij IPv4 Secondary DNS Server 10 20 64 11 GXT4 1000RT120 iy Last DHCP BOOTP Address Normal Operation ip Last DHCP Lease 0 sec Sensor Normal Operation Communications Normal Operation Communications Summary Active Events Downloads Cg Configuration Protocols Status Support Firmware Update i IPv6 SLAAC Address IPv6 Link Local Address ij IPv6 Default Gateway ip IPv6 Primary DNS Server i IPv6 Secondary DNS Server i Last DHCPv6 Address iy Last DHCPv6 Lease iy i V i i
30. YD T 1363 specification using an RS 485 network connection A AS EMERSON Network Power Identification Uninitialized Uninitialized Uninitialized Status GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications E Summary Active Events Downloads CJ Configuration amp yProtocols C3BACnet 3Modbus SNMP CQYDN23 Status Cg Support YDN23 Protocol Managed Device Write Access Enable or Disable the YDN23 server to write to the managed device GXT4 1000RT120 Sensor Communications YDN23 Settings i Managed Device Write Access i Device Address i Data Rate Device Address YDN23 device address Baud Rate The communications rate in bps 50 Edit the Liebert IntelliSlot Unity Card Configuration Welcome Liebert Administrator Liebert Updated February 9 2015 11 32 53AM 3 Units Lieberf IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 10 Configuration Communications Tab Status Folder The Status folder contains no configurable items It displays the System Status of the Liebert IntelliSlot Unity card and a list of events that affect the card s status A green check mark 9 indicates the status 1s Normal as shown in the Status column N b EMERSON Network Power GXT4 1000RT120 Sensor MEET Liebert Status Updated February 9 2015 10
31. ancel to discard the changes AN Welcome Liebert Administrator S EMERSON s Network Power GXT4 1000RT120 Sensor Communications Liebert SNMPv3 User 1 Updated February 9 2015 10 23 01AM Identification Clieh nere te aatimosvesens dienlayed in the table Uninitialized Uninitialized Uninitialized Report SNMPv3 User Enable T T SNMPv3 User 1 disabled SNMPv3 User 2 disabled Status SNMPv3 User 3 disabled V GXT4 1000RT120 SNMPv3 User 4 Saia ss Normal Operation SNMPv3 User 5 disabled reia A SNMPv3 User 6 disabled ormal Operation ES OS SNMPv3 User 7 disabled Normal Operation SNMPv3 User 8 disabled SNMPv3 User 9 disabled SNMPv3 User 10 disabled SNMPv3 User 11 disabled Click on a SNMPv3 User folder or Communications E Summary SNMPv3 User 12 disabled a link to get this settings page siii SNMPv3 User 13 disabled Downloads SNMPv3 User 13 disable 7 s Cd Configuration SNMPv3 User i disabled aiu evt Save Cancel oe H E SNMPv3 User 15 pese i SNMPv3 User Enable enabled ne Modbus SNMPv3 User 16 disabled i SNMPv3 Username A V idi r EISNMP SNMPv3 User 17 disabled ij SNMPv3 Access Type Y SNMPv3 User 20 SNMPv3 User 18 disabled C3SNMPv3 User 1 SNMPv3 User 19 disabled Y AAA eCa Neue C SNMPv3 User 2 SNMPy3 User 2
32. aps put a check mark 9 in the box 4 To change the Heartbeat Trap Interval choose a time from the drop down list or choose Disabled to prevent any heartbeat traps from being sent p The interval times offered are 5 minutes 30 minutes or 1 4 8 12 or 24 hours Choose whether to disable the traps or to set the interval to one of the periods on the menu Lieberf IntelliSlot Unity Card User Manual 17 Enable Communication Protocols 7 Click Save to confirm the changes or click on Cancel to discard them 8 Restart the card to activate the changes Select the Communications Tab gt Support b Enable the commands Click on Restart Figure 3 7 SNMP 3 1 3 1 X N EMERSON Network Power Identification Uninitialized Uninitialized Uninitialized Status GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications E Summary Active Events Downloads Cd Configuration Protocols CgBACnet _JSNMPv3 User 20 C9 SNMPv1 Trap 20 C9SNMPv1 v2c Access 20 Welcome Liebert Administrator GXT4 1000RT120 Sensor a Liebert SNMP Updated February 9 2015 10 20 31AM Status Value Units ip SNMPv3 Engine ID 800001DC0300006810114F Settings INCE Units i SNMPv1 v2c Enable enabled i SNMPv3 Enable enabled i Authentication Traps enabled i Heartbeat Trap Interval i RFC 1628 MIB enabled i
33. arted before another user s settings may be changed a Select the Communications Tab gt Support b Enable the commands c Click on Restart Figure 3 10 SNMPv1 v2c Access settings 3 2 A Welcome Liebert Administrator NNI EMERSON DOTEA Network Power GXT4 1000RT120 Sensor Communications Liebert SNMPv1 v2c Access 1 Updated February 9 2015 10 27 16AM Identification Settings Edit Units i SNMP Access Host i SNMP Access Type i SNMP Access Community String Uninitialized Uninitialized Uninitialized Status GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications E Summary Active Events Downloads Cd Configuration Protocols BACnet Modbus SNMP ASNMPv3 User 20 JSNMPvi Trap 20 2 31 SNMPv1 v2c Access LEE Selecting the SNMPv1 v2c Access folder will bring up the settings that may be changed A erred Z9 SNMPv1 v2c Access r1 Download Protocol Mappings The Liebert IntelliSlot Unity Card s permits downloading files listing information available from a managed device for each enabled protocol The listings identify the data available from the device and how that data will be represented or mapped into a particular protocol To download a data mapping list click on the Managed Device tab then Summary Downloads The Data Mapping Files heading will show mapping files for each enabled pr
34. assign a static IP address use the Ethernet connection to configure the card Proceed to 2 1 2 Connect an Ethernet Cable and 2 2 Change User Names and Passwords Immediately 2 1 2 Connect an Ethernet Cable 1 Connect a computer running a Microsoft Windows operating system Microsoft Windows XP with SP2 64 bit or SP3 32 bit or later to the card by plugging a network cable into the RJ 45 port on the computer and the Liebert IntelliSlot Unity card 2 Autoconfiguration which is normally enabled on computers running Microsoft Windows operating systems will automatically negotiate the communication settings This takes about one minute A NOTE Open the Command Prompt window from the computer s Start menu If the computer does not automatically connect verify that autoconfiguration is enabled by Enter ipconfig all to verify that Autoconfiguration is enabled on the computer and that an Autoconfisuration IPv4 Address has been assigned Enabled Yes see Figure 2 1 An Autoconfiguration IPv4 Address begins with 169 254 Lieberf IntelliSlot Unity Card User Manual Installation 9 If the Ethernet adapter being used to attach to the card does not show an Autoconfiguration IPv4 Address open a new Command Prompt and type ipconfig renew and press Enter This forces the computer to acquire an Autoconfiguration IPv4 Address 4 When the computer has an Autoconfiguration IPv4 Address open a browser window on the
35. ave to confirm the changes or click on Cancel to discard them Configure the protocols selected For details refer to 5 0 Edit the Liebert IntelliSlot Unity Card Configuration Lieberf IntelliSlot Unity Card User Manual 11 Enable Communication Protocols 6 Restart the card refer to 5 11 Configuration Communications Tab Support Folder a Select Communications Tab gt Support b Enable the commands c Click on Restart Figure 3 1 Enable protocols enable commands NS Welcome Liebert Administrator S EMERSON aa Network Power GXT4 1000RT120 Sensor Communications Liebert Protocols Updated February 9 2015 10 06 56AM Identification Settings Units Enable Two rre i BACnet Protocol enabled Protocols Uninitialized ij Modbus Protocol enabled ij SNMP Protocol enable Enable Commands Status iy YDN23 Protocol enabled Communications GXT4 1000RT120 Tab gt Support Folder Normal Operation Sensor Normal Operation Communications Normal Operation Summary gt C Enable zs ommands Enable C Ey Active Events repo Downloads i Restart Card Resta El Summary Configuration _A gt 2 aa Active Events 9 Protocols 4 Reset Card to Factory Defaults Reset to Factory Defaults mot Status i Generate and download diagnostic file C Configuration S4 Support emeret x zgBACnet Modbus C9 SNMP CJYDN23 Firmware Update 3 1 1 Enable Modbus Proto
36. bay on your Liebert equipment It may have a plastic cover 2 Insert the card into the Liebert IntelliSlot bay NOTE The card will only fit one way in the Liebert IntelliSlot bay because the circuit board is not centered on the faceplate The slot in the Liebert IntelliSlot bay also is not centered Secure the card with the screws supplied with the cover plate 4 Connect an Ethernet cable to the card s Ethernet RJ 45 port for IP communication interfaces Connect a serial cable to the card s 485 RJ 45 port for RS 485 communication interfaces see 2 1 3 Connect an RS 485 Serial Cable Assigning the Card s IP Address DHCP The Liebert IntelliSlot Unity card 1s factory configured for DHCP If a Static or BootP network configuration 1s required change the Boot Mode as described in Static IP on page 6 Connect an RJ 45 cable to the card and it will receive an IP address from the DHCP server Contact the DHCP administrator to obtain the IP address using the Liebert IntelliSlot Unity card s MAC address The MAC address 1s printed on the card s faceplate Liebert IntelliSlot Unity Card User Manual 5 If the DHCP administrator is not available or there is no way of determining the IP address assigned by the DHCP server use a computer with a direct Ethernet connection to the Liebert IntelliSlot Unity card and the Autoconfiguration IPv4 Address convention described in 2 1 2 Connect an Ethernet Cable to access the card s Web page and
37. by hovering a mouse pointer over the icon to the left of the Status Events or Settings row as shown below The Web page may display any of six 1cons beside the Status Events or Setting entry Table 4 1 Help text and icons a check mark 9 on a green button Event Normal an i on a blue button Event Information an x on a red button Event Alarm an exclamation point on a yellow shield Event Warning an exclamation point on a red button Event Critical an i in a word balloon Tool Tip 24 Liebert IntelliSlot Unity Card User Manual Liebert IntelliSlot Unity Card Web Page Layout Figure 4 4 Help text on mouse over A Welcome Liebert Administrator AN EMERSON l Input Updated February 9 2015 10 36 03AM Hovering a mouse Status Value Units pointer over the icon uninitialized System Input RMS A N 119 0 VAC reveals information Bi Uninitialized System Input RMS Current Phase A 14 AAC about that entry Uninitialized System Input Frequency 59 9 Hz System Input Max Voltage A N 121 0 VAC Status System Input Min Voltage A N 118 0 VAC GXT4 1000RT 120 System Input Nominal Voltage 120 VAC 8AAC 60 Hz Normal Operation Sensor Normal Operation Communications The nominal or rated system input frequency alas Status Ack Help text about the System Input Nominal Frequency entry on the Managed Device Tab Input Menu Input Undervoltage Normal Input Ov
38. c ee eee eee eee nee 34 Yok d Dime Service Sets AA AAA AAA in 34 5 3 2 Configuration Folder User cec e 35 5 3 3 Configuration Folder Network ccc eee ee 35 D Ox UP VAP O oer ab wade be OSE OL EG Oe ONES iol ie qaod e dest d deg 36 5 3 3 2 Domain Name Server DNS Test eee 37 5 3 4 Configuration Folder Web Server 0 0000 eee eee e 37 5 3 5 Configuration Folder LIFE gt Pa sita Da OU Meu tet Rau NG RG LE AA d E 38 5 3 6 Configuration Folder Emerson Protocol llle 38 5 4 Configuration Folder Messaging 0 00 ccc ee es 38 PATE A O eed Sneed este Ss Gk a tS te ea Ge eG ee tee de te A 38 A CU AA oa TS T TEDITOC wad ho QE Anda AES ke ee wana eae 39 ie NES gets or aa ee es tS dei deed a E E redi dy e III 40 DAA Mess APIO CSE aic desc qe oa rei done bade DO ee AA ae Undo fo EC Ao Re dod dede s 41 5 5 Communications Tab Protocols a 23 a dea oe He ED Id o Code dE d 41 5 6 Protocols Folder BACnet Folder cle RR ese 42 5 6 1 Protocols Folder BACnet IP Folder lee 42 5 6 2 Protocols Folder BACnet MSTP Folder eeeee ooo 43 D bErotocols Bolder NMOODilBSa dac o cic ea Wesce p Ru Al aa CHE aS 43 De MOG DUS 5l aia oat a euch ache als eae ok Cae a ee oda ae AES Be eee eee 43 Dur 2 NTOODUE RU Les deti at eiu aed aba Pea art ias Gd SR odor ad a es 44 5 8 Protocols Folder SNMP Subfolder R
39. card to confirm the changes a Select the Communications Tab gt Support b Enable the commands c Click on Restart Figure 3 9 SNMPv1 trap settings SS Welcome Liebert Administrator EMERSON Network Power GXT4 1000RT120 Sensor MSE Liebert SNMPv1 Trap 1 Updated February 9 2015 10 24 53AM Identification 7 Settings i SNMP Trap Target iy SNMP Trap Port iy SNMP Trap Community String Uninitialized Uninitialized Uninitialized Settings required for each address that will receive SNMP notifications Status GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications E Summary Active Events Downloads Cd Configuration Protocols BACnet Modbus 3S SNMP 3SNMPv3 User 20 SYSNMPVv1 Trap 20 CJSNMPv1 Trap 1 C3 SNMPv1 Trap 2 Mm 3 1 3 4 Configure SNMPv1 v2c Access Settings l Select Communications Tab gt Protocols gt SNMP gt SNMPvl v2c Access 20 gt SNMPv1 v2c Access 1 Click on Edit and enter a User name and password if required Enter the information and set the permissions appropriate to the user Refer to Figure 3 9 for the information required 20 Lieberf IntelliSlot Unity Card User Manual Enable Communication Protocols 4 Click Save to confirm the changes or click on Cancel to discard them Restart the card to confirm the changes The card must be rest
40. ce Tab Sensor Tab Card in a Liebert CRV N NS EMERSON Network Power Liebert CRY Sensor Communications Liebert Summary Updated March 11 2014 03 08 30PM Communications Tab Y Identification ixi aes Information on Identification rM 0 Liebert CRV Opening Screen a 0 COND depends on type of Return Air A it bei i Status aS qur unit being monitored pom Operation e iiid Next Maintenance jo mm Operation AK 0 0 RH Reheating A ASS CRV Server Supply Air Dehumidifying Tab Menu psm gt e Wo changes Sten 00M Humisiin according to B 55s 1 Fans monitored Remote Sensors 10 Powered by equipment HIS sbertiCOMm E Condenser FAChillad Water Liebert IntelliSlot Unity Card User Manual 23 Liebert IntelliSlot Unity Card Web Page Layout Figure 4 3 Managed Device Web page without sensors A EMERSON Ho Updated March 10 2015 11 30 41AM X ECO Mode Enabled lw Sensor Tab not displayed Identification Uninitialized Uninitialized Uninitialized Status GXT4 1000RT120 Normal Operation Communications Normal Operation Input Output LN 119 0 VAC LN 118 0 VAC Amps 1 7 A AC Amps 1 7 A AC Freq 59 9 Hz Load 0 0 x Sensor Status gt not displayed 4 2 Help Text Each Web page shown by the Liebert IntelliSlot Unity DP card has informational text that 1s revealed
41. col Protocols may be enabled after a card has been installed and configured To enable Modbus protocol Select Communications Tab gt Protocols gt Modbus Click on Edit and enter a User name and password Select the access level Read Only or Read Write Select the Modbus interface Modbus TCP or Modbus RTU Click Save to confirm the changes or click on Cancel to discard the changes TT PA Ser A oe Configure the Modbus interface chosen refer to Configure Modbus TCP or Configure Modbus RTU For additional details see 5 7 Protocols Folder Modbus 3 1 1 1 Configure Modbus TCP 1 Select the Communications Tab gt Protocols gt Modbus TCP 2 Click on Edit and enter a User name and password if required 3 Set the Limit Network Access Type by choosing from the drop down list Open Same Subnet Trusted IP List Refer to 5 7 Protocols Folder Modbus for additional details 4 Enter the port to be used by the Modbus Server to listen for and respond to Modbus protocol requests based on limit Network Access Type setting 5 Enter the Maximum Client Connection Count 12 Liebert IntelliSlot Unity Card User Manual Enable Communication Protocols 6 Click Save to confirm the changes or click on Cancel to discard them Restart the card to confirm the changes a Select Communications Tab gt Support b Enable the commands c Click on Restart Figure 3 2 Modbus TCP Trusted IP List A Welcome Lieb
42. configure the card To see the card s last DHCP assigned IP address click on the Communications Tab then on the left side menu select Support gt Active Networking The table of information will show the last IP address assigned by the DHCP server The card may retain that IP address when it reconnects to the DHCP network because most DHCP systems reuse the same IP address for the same device SN y EMERSON Network Power GXT4 1000RT120 Sensor Liebert Active Networking Updated February 9 2015 09 56 57AM identification Value Units 00 00 68 10 11 4f 126 4 212 175 Status i Ethernet MAC i IPv4 Address Uninitialized Uninitialized Uninitialized iy IPv4 Default Gateway 126 4 212 1 ij IPv4 Primary DNS Server 10 203 52 131 Status ij IPv4 Secondary DNS Server 10 20 64 11 i Last DHCP BOOTP Address ij Last DHCP Lease 0 sec i IPv6 Global Address ip IPv6 SLAAC Address i IPv6 Link Local Address i IPv6 Default Gateway ip IPv6 Primary DNS Server i IPv6 Secondary DNS Server GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation fe80 200 68fffe10 114f Communications e oin i Last DHCPv6 Address Support gt Active esae iy Last DHCPv6 Lease 0 sec LJ Configuration Networking s JProtocols Static IP Installation EMERSON Network Power IS UNITY DP lt y Communications Tab Last DHCP Address To
43. der BACnet Folder Communications settings Units Summary gt gt i Managed Device Write Access gActive Events i BACnet Interface E aoc i Device Object Instance Number 1130000 E S Protocols i Device Object Name Devicel130000 BACnet iy APDU Timeout 3000 BACnet IP C3BACnet MSTP CDU Penes FHEA Madhe BACnet Settings Managed Device Write Access Enable or Disable the BACnet server to write to the managed device BACnet Interface BACnet server interface BACnet IP or BACnet MSTP Device Object Instance Number The instance number 0 4194302 of the BACnet server s device object Device Object Name The name of the BACnet server s device object APDU Timeout The timeout in milliseconds between APDU retries 1 655395 e APDU Retries The number of times to retransmit an APDU after the initial attempt 0 8 5 6 1 Protocols Folder BACnet IP Folder Communications Summary Settings Units RERE E ij BACnet IP Port Number 17808 Configuration i Register as Foreign Device enabled i an i P Address of BBMD EF ne Canet iB i Foreign Device Time to Live heu sec ABACnet MSTP HEA Modbus BACnet IP Settings BACnet IP Port Number The port for the BACnet server s UDP IP connection Register as Foreign Device Enable or Disable registration as a foreign device P Address of BBMD IP Address of the BACnet Broadcast Management Device BBMD to be accessed for Forei
44. ed to 126 4 208 284 Type of Query Type of DNS query Hostname IP Address Query Value Value for the domain name server DNS to resolve Example gxtwebdemo liebert com 5 3 4 Configuration Folder Web Server The Web Server Settings permits making some security settings such as HTTP or HTTPS and password enabling Communications Settings Units Summary T i Web Server Protocol HTTE DActive Events Downloads ly HTTP Port zE lt Configuration i HTTPS Port 143 System Ga User i Password Protected Site enabled Network S i Session Idle Timeout E min Web Server LALIFE TM Web Server Settings Web Server Protocol Select the operation mode of the Web Server HTTP HTTPS HTTP Port Standard web port not encrypted Required if HTTP is enabled as Web Server Protocol HTTPS Port Standard secure Web port all communication is encrypted Required if HTTPS is enabled as Web Server Protocol Password Protect Site When enabled a login session is required before any device information 1s displayed to the user User level credentials will allow only viewing of device information Administrator level credentials are required to make any changes Session Idle Timeout The interval the software will wait before logging off a user unless there 1s user activity Default is 5 min Liebert IntelliSlot Unity Card User Manual 37 5 3 5 Configuration Folder LIFE The LIFE subfolder contains sett
45. elliSlot Unity card supports YD T 1363 specification for the full range of information available from managed Liebert NXL or Liebert PeX units Trellis Support The Liebert IntelliSlot Unity DP card communicates a rich set of Emerson Protocol information to the Trellis DCIM platform Trellis can manage and control Liebert equipment using SNMP Modbus or the Emerson Protocol This allows monitoring all Liebert equipment using Liebert IntelliSlot Web Liebert IntelliSlot 485 Liebert IntelliSlot IPBML Liebert IntelliSlot Web ADPT or Liebert IntelliSlot Unity platform communication interfaces Liebert Nform Support Utilizing the Emerson Protocol or SNMP and Web technologies built into each Liebert IntelliSlot Unity card Liebert Nform will centrally manage alarm notifications to provide an easy interface to access critical equipment information A downloadable version is available online at nform liebert com Liebert MultiLink Support The Liebert IntelliSlot Unity card integrates with Liebert s MultiLink software to provide unattended graceful operating system shutdown of PCs servers and workstations The card can be monitored by Liebert MultiLink over the network eliminating the need for serial cables For more information on Liebert MultiLink and a downloadable version of Liebert MultiLink software visit multilink liebert com Support for Liebert SN Sensors The Liebert IntelliSlot Unity card supports connection and mo
46. erly If the first card 1s a Liebert IntelliSlot card but not a Liebert IntelliSlot Unity card and if both cards connect to the same Ethernet network then you should disable the router function on the first card This will avoid circular routes Follow instructions 1n the user manual for the first card If the first and second cards are both Liebert IntelliSlot Unity cards steps must be taken to avoid duplicate Emerson Protocol MSTP node ID s By default the two cards would use the same node ID and one or both cards would report a duplicate node error and fail to communicate with the system The default node ID for a Liebert IntelliSlot Unity card is 0 so the second card should use 1 or 2 preferably or 127 if necessary Contact your system administrator about the proper node ID for the second card then perform the steps below 1 Open a Web browser and navigate to the second Liebert IntelliSlot Unity card Click on Communications Tab gt Configuration gt Emerson Protocol gt MSTP 2 3 Click on Edit and enter a password and username 1f required 4 Enter the new node ID Liebert IntelliSlot Unity Card User Manual Installation 5 Click Save to confirm the changes or click Cancel to discard them 6 Restart the card as follows a Select the Communications Tab gt Support b Click on Enable c Click on Restart 10 Liebert IntelliSlot Unity Card User Manual Enable Communication Protocols 3 0 ENABLE
47. ert Administrator S EMERSON S Network Power GXT4 1000RT120 Sensor Communications Liebert Modbus TCP Updated February 9 2015 10 11 39AM Settings ve Units i Limit Network Access Type 3 Port Identification Uninitialized Uninitialized Uninitialized i iy Maximum Client Connection Count Status GXT4 1000RT120 A eese Trusted IP List 1 Sensor Normal Operation Communications Settings Edit Save Cancel Units Normal Operation A i IP Address fi27 0 0 1 Communications brings up a screen Summary where this information Monac may be entered Configuration Clickingon f asaca one of the five f iModbus Trusted IP Modbus TCP List folders FaTrusted IP ist 21 3 1 1 2 Configure Modbus RTU 1 Select the Communications Tab gt Protocols gt Modbus RTU 2 Click on Edit and enter a user name and password 1f required 3 Set the Node ID and the Baud Rate 4 The Node ID defaults to 1 but must have a value from 1 to 255 that 1s unique among devices connected through the RS 485 interface The default baud rate 1s 9600 19200 and 38400 also available dh Contact your system administrator if you are uncertain about the settings Lieberf IntelliSlot Unity Card User Manual 13 Figure 3 3 Enable Communication Protocols Click Save to confirm the changes or click on Cancel to discard them Restart the card to confirm the changes a Select Communicatio
48. ervoltage Normal GXT4 1000RT120 E Summary Active Events Downloads Lieberf IntelliSlot Unity Card User Manual 25 4 3 Managed Device Tab Menus Menus on the Managed Device Tab list only data that 1s relevant to the equipment being monitored Liebert IntelliSlot Unity Card Web Page Layout For example menus shown by a Liebert IntelliSlot Unity card installed in a UPS differ from menus shown by a card installed in Thermal Management equipment Information on those menus will also differ depending on the equipment the card is installed in Figure 4 5 Managed Device Tab examples Liebert GXT4 and Liebert CRV A EMERSON Network Power Input Welcome Liebert Administrator GXT4 1000RT120 a Updated February 9 2015 10 38 29AM y entification Status Value Units Uninitialized 4 System Input RMS A N 119 0 vac Uninitialized i System Input RMS Current Phase A 14 AAC Uninitialized i System Input Frequency 59 9 Hz i System Input Max Voltage A N 121 0 VAC Status i System Input Min Voltage A N 118 0 VAC GXT4 1000RT120 i System Input Nominal Voltage 120 VAC eee Operation amp System Input Nominal Current BAAC Normal Operation iy System Input Nominal Frequency 60 Hz Communications Normal Operation Events Status Ack Input Undervoltage Normal GXT4 1000RT120 Input Overvoltage Normal E ue ew edge A usi Gui Mua jussi nai l
49. ess clients on the same subnet as the Liebert IntelliSlot Unity card clients with specific IP addresses Trusted IP Lists only five addresses are permitted Communications E Summary 2n Active Events Settings Units Downloads J Configuration i Limit Network Access Type Protocols i Port BACnet wit 9 Modbus i Maximum Client Connection Count 4 K oceccesceccceccececocccoseecoeeseoseos 3Trusted IP List 5 Liebert IntelliSlot Unity Card User Manual 43 Edit the Liebert IntelliSlot Unity Card Configuration Modbus TCP Settings Limit Network Access Type P Access List Open Same Subnet Trusted IP List Port The TCP port used by the Modbus Server to listen for and respond to Modbus protocol requests based on Limit Network Access Type setting e Maximum Client Connection Count 5 7 2 Modbus RTU Communications E Summary Active Events Downloads Cg Configuration Protocols BACnet 5 Modbus Modbus TCP CdModbus RTU FASNMP Modbus RTU Settings Node ID Modbus Server ID for the interface obtain from network administrator Baud Rate Communication rate 9600 19200 38400 Parity Check The communication parity check None Even Odd Settings i Mode ID i Baud Rate i Parity Check 44 Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 8 Protocols Folder SNMP Subfolder Folders and
50. g Test 9 9 Selections here permit testing the setup for e mail and SMS messages If the test fails incorrect settings should be changed to ensure that the Liebert IntelliSlot Unity card sends proper notifications if an event should occur Status Value Units i Messaging Test Results Settings Edit Save Cancel Units i Send Test Message Communications Tab Protocols The Protocols folder displays the types of protocols that may be enabled for a Liebert IntelliSlot Unity card Not all protocols are available at the same time Some protocols may not be available for some types of managed devices see 1 2 Compatibility With Other Emerson Products and Communication Protocols The Liebert IntelliSlot Unity card allows selecting two third party protocols Communications E Summary gt gt Settings Edit Save Units acti i BACnet Protocol I enabled C3 Configuration i Modbus Protocol I enabled bem i SNMP Protocol F enabled ne a Modbus i YDN23 Protocol l enabled C39 SNMP CgYDN23 The folders contained by the Protocols folder are BACnet BACnet IP e BACnet MSTP Modbus Modbus TCP e Modbus RTU SNMP SNMPv3 User 20 SNMPvl1 Trap 20 SNMPvl v2c Access 20 YDN23 Settings in each permit configuring the protocols available on the Liebert IntelliSlot Unity card Lieberf IntelliSlot Unity Card User Manual 41 Edit the Liebert IntelliSlot Unity Card Configuration 5 6 Protocols Fol
51. gn Device Registration Foreign Device Time to Live Time to remain in the BBMD Foreign Device table after registration 42 Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 6 2 Protocols Folder BACnet MSTP Folder 9 7 9 7 1 Communications Summary Tw apuy Active Events i Node ID Downloads Ld Configuration i Data Rate Protocols i Max Master Address 127 Meus t IP i Max Info Frames ER ne _JBACnet MSTP mn aaa J BACnet MSTP Settings Node ID The BACnet server s MS TP node ID MAC Data Rate The BACnet MSTP communication rate bits per second e Max Master Address The maximum node ID MAC in use on the MS TP network Max Info Frames Maximum number of information frames this node may send before it must pass the token Protocols Folder Modbus Communications E Summary Active Events Settings Edit Save Cancel Units i Modbus Interface Modbus TCE 3 Downloads Cd Configuration amp yProtocols CgBACnet Modbus SNMP C3YDN23 i Managed Device Write Access Modbus Settings e Managed Device Write Access Enable or Disable the Modbus server to write to the managed device Modbus Interface Select the Modbus interface either Modbus TCP or Modbus RTU Modbus TCP The Modbus TCP permits connection to the card by any client Open permits communication by any IP addr
52. hat will receive SNMPv1 traps Up to 20 trap recipients may be enabled and configured Like the SNMPv3 pages the settings for each target may be reached by clicking on the links in the Detail portion of the page or by clicking on the folders for the trap targets Also data shown in the table may be changed by clicking on the link above the table E Welcome Liebert Administrator EMERSON ME Network Power GXT4 1000RT120 EE Liebert SNMP v1 Trap 1 Table Updated February 9 2015 10 24 534M Identification Click here to edit columns displayed in the table 4 4 Click on this link to change the information Report SNMP Trap Target shown in the table SNMPv1 Trap 1 126 4 202 194 SNMPv1 Trap 2 Status SNMPv1 Trap 3 GXT4 1000RT120 SNMPvi Trap 4 Normal Operation SNMP wi Trap 5 Sensor Normal Operation SNMPv1 Trap 6 Communications SMMPv1 Trap 7 Normal Operation SNMPw1 Trap 8 SNMPv1 Trap 3 SMNMPv1 Trap 10 SNMPv1 Trap 11 SMMPv1 Trap 12 SNMPvi Trap 13 SMMPv1 Trap 14 Uninitialized Uninitialized Uninitialized Communications Summary E Configuration E 3 Protocols SNMP T 15 Click on a SNMPv1 Trap 1 BACnet A folder or a link to get this em SNMPv1 Trap 16 settings page m SNMP SNMPv1 Trap 17 29 SNMPv3 User 20 SNMPv1 Trap 18 Settings Units ES ae SNMPv1 Trap 19 4j SNMP Trap Target a SNMP Tran 1201 i SNMP Trap Port F EASNMPY
53. he BACnet MSTP Data Rate Set the BACnet MSTP Max Master Address Set the BACnet MSTP Max Info Frames The default is 8 Lieber IntelliSlot Unity Card User Manual Enable Communication Protocols Click Save to confirm the changes or click on Cancel to discard them 8 Restart the card to activate the changes a Select Communications Tab gt Support b Enable the commands c Click on Restart Figure 3 6 BACnet MSTP A Welcome Liebert Administrator EMERSON Network Power GXT4 1000RT120 Sensor MA Liebert BACnet MSTP Updated February 9 2015 10 17 17AM Identification Settings Uninitialized Uninitialized i Node ID Uninitialized ij Data Rate 38400 ip Max Master Address 27 oo of Status i Max Info Frames le GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications E Summary Active Events Downloads Configuration Protocols CXBACnet IBACnet IP CJBACnet MSTP m Saas A 3 1 3 Enable SNMP SNMPv1 v2c and SNMPv3 are enabled by default The protocols may be configured or their default values may be accepted Authentication Traps are not enabled by default The default Heartbeat Trap interval 1s 24 hours this can be disabled or the interval may be changed 1 Select the Communications Tab gt Protocols gt SNMP 2 Click on Edit and enter a User name and password if required 3 To enable Authentication Tr
54. ings that affect use of the Emerson LIFE Technology a remote monitoring and diagnostic service for Emerson Network Power units The LIFE settings are for use by trained Emerson Network Power personnel only and require no user changes For information about the LIFE settings refer to Appendix A Configuration Folder LIFE Sub folder Edit the Liebert IntelliSlot Unity Card Configuration 5 3 6 Configuration Folder Emerson Protocol Emerson Protocol contains four subfolders Managed Device MSTP Ethernet and Internal NOTE With the exception of changing the node ID when multiple cards are used the settings in the Emerson Protocol subfolders should not be modified unless directed by an Emerson representative 5 4 Configuration Folder Messaging The Messaging subfolder permits enabling e mail and text messaging about events The subfolder also contains a test to determine whether notifications are sent Settings for the two notification methods permit specifying who gets the notifications the format and other details Communications Summary Ey Active Events Downloads 43 Configuration E System 3 Network EJWeb Server amp E3LIFE TM a 3 Emerson Protocol Messaging Email ISMS Messaging Test gt gt gt Settings Edit Save Units i Email enabled i SMS l enabled Email May be enabled to send e mail messages about events e SMS May be enabled to send text messages about events 5 4 1
55. initialized Report SNMP Access Host SHMPv1 v2c Access 1 0 0 0 0 SHMPv1 v2c Access 2 Status SHMPv1 v2c Access 3 GXT4 1000RT120 SNMPv1A 2c Access 4 Normal Operation SNMPv1 v2c Access 5 jede Meer SNMPv1 2c Access 6 A ERR SNMPv1 2c Access T Normal Operation SNMPv1 v2c Access o SNHMPv1 v2c Access 9 SHMPv1 v2c Access 10 SHMPv1 v2c Access 11 SNHMPv1 v2c Access 12 SHMPv1 v2c Access 13 SNMPv1 v2c Access 14 Communications Summary E Configuration Protocols SNMPvtiv2c Access 15 9 BACnet ES Modbus SNMPv1 v2c Access 16 EHES SNMP SNMPviiv2c Access 17 3 SNMPv3 User 20 SNMPv1 v2c Access 18 Click on a SNMPv1 v2c Access SN VI Irap 20 SNMPviWv2c Access 19 folder or a link to get this 30 Mr A UE PVRs SNMPv1 v2c Access 20 settings page E SNMPv1 v2c Access 1 i MTI Access Settings Edit Save Cancel Units z i SNMP Access Host 0 0 0 0 ZISNMPv1 v2c Access 2 A ij SNMP Access Type z i SNMP Access Community String ee SNMPv1 v2c Access Settings SNMP Access IP Address Configure network hosts interested in device information access The host can be identified as either an IP address or the host s network name SNMP Access Type SNMPvl v2C access type Read Only or Read Write SNMP Access Community String SNMP Community String Liebert IntelliSlot Unity Card User Manual 49 9 9 Protocols Folder YDN23 Protocol The YDN23 protocol supported 1s based on the
56. l running on the card the Alternate Version fields will be blank and it will not be possible to revert to an alternate version 1 Select the Communications Tab at the top of the screen 2 Select the Support folder then select the Update Firmware folder 56 Liebert IntelliSlot Unity Card User Manual Firmware Updates Select the Enable button 4 Enter the user name and password in the security dialog box that appears use the administrator user name and password from the user settings 5 Click on the Run Alternate button and a confirmation dialog box will appear 6 Click the OK button on the confirmation dialog box NOTE The card will reboot After the reboot the card will be running the previous version of the firmware and configuration which had been stored in flash memory The previous firmware and configuration will have been moved to the alternate area Liebert IntelliSlot Unity Card User Manual 57 Configuration Folder LIFE Sub folder APPENDIX A CONFIGURATION FOLDER LIFE SUB FOLDER The LIFE sub folder contains settings that affect use of the Emerson LIFE Technology a remote monitoring and diagnostic service for Emerson units The LIFE settings are for use by trained Emerson Network Power personnel only and require no user changes Seus Besclbin F Settings Description SCS Number of minutes between routine LIFE Watch Station calls This value is used in conjunction
57. ledge button on the Sensor Server page Sensor Order Displays a list of sensors and allows setting the order in which the sensors are displayed on the Summary page 28 Liebert IntelliSlot Unity Card User Manual Liebert IntelliSlot Unity Card Web Page Layout 4 5 1 Sensor Tab Summary Page The Sensor Tab Summary Page shows the status of all installed sensors details about any selected sensor and a Setting pane that permits changing a sensor s label thresholds if applicable alarm configuration and acknowledging alarms and events Selecting a sensor permits changing its settings at the lower part of the window Events may also be acknowledged on this window Figure 4 7 Sensor Tab Summary page layout NM NS EMERSON Network Power GXT4 1000RT120 Sensor Liebert Door Closure Summary Updated March 27 2015 01 26 25PM status icons Identification ID Type Serial Number Label Value Status One open Uninitialized Q 1 1 Srvr Room 7 Front Closed os One closed PEPES 12 Door Closure B90000000DE10420 A son A G raph ical Q 2 1 Temperature 11000000054F5742 Rack 7 12c Top 31 7 C SS display of Status O 3 1 Temperature FFO00000054B9542 Rack7 12c Midde 275 C Mp temperature GXT4 1000RT120 O 4 1 Temperature D8000000054E7142 Rack7 12cBottom 243 C PEs sensor value Kareg ii O 5 1 Temperature A70000000368FA42 Srvr Room 7 Ambient 24 3 C HH Temperatu re Normal Operation 6 1 Relative Humidity 6A000000FCC
58. liSlot Unity card or reverting to an alternate firmware version and configuration if the current firmware is not the initial load A Welcome Liebert Administrator Los EMERSON SS Network Power GXT4 1000RT120 Sensor Communications Liebert Firmware Update Updated February 26 2015 03 30 19PM Identification Status Value Units Uninitialized i Current Firmware Version 5 0 0 0 Uninitialized ij Current Firmware Label IS UNITY 5 0 0 0 90905 wien ij Current Firmware Date Feb 23 2015 16 23 59 i Alternate Firmware Version 5 0 0 0 Status ij Alternate Firmware Label IS UNITY 5 0 0 0 00000 DB GXT4 1000RT120 i Alternate Firmware Date Feb 17 2015 10 40 24 Normal Operation Sensor Commands Enable Cancel Normal Operation canoe Communications i Run Alternate Firmware Normal Operation ij Firmware Update Web Communications Summary E Configuration E E Protocols Firmware Update Liebert IntelliSlot Unity Card User Manual 53 Edit the Liebert IntelliSlot Unity Card Configuration Firmware Update Current Firmware Version The version of the firmware running on the card Current Firmware Label The label of the firmware running on the card Current Firmware Date The build date of the firmware running on the card Alternate Firmware Version The version of the firmware in the alternate area Alternate Firmware Label The label of the firmware in the alternate area A
59. lternate Firmware Date The build date of the firmware in the alternate area Commands Run Alternate Firmware Return the card s firmware to a version in the alternate area the version in use before the most recent firmware update Firmware Update Update the card s firmware to a new version Commands i Run Alternate Firmware i Firmware Update 54 Liebert IntelliSlot Unity Card User Manual Firmware Updates 6 0 FIRMWARE UPDATES The Liebert IntelliSlot Unity card has two areas in flash memory for the firmware and the configuration One area is currently operating on the card The other area is the previous firmware on the card and 1s considered an alternate For information on the alternate firmware see 6 2 Revert to Alternate Firmware 6 1 Updating the Liebert IntelliSlot Unity Card s Firmware To update the Liebert IntelliSlot Unity card s firmware 1 Download onto your computer the latest Liebert IntelliSlot Unity card firmware update from the Liebert software download Web site at ww w liebert com 2 Ifthecard s DHCP or Static IP address 1s known type the IP address in the Web browser address window 3 Ifthe card does not have a known IP address and it is configured for DHCP connect the card to a computer with an Ethernet cable and open a Web browser The card has an Ethernet RJ 45 connector on the front see Figure 6 1 The card and computer will automatically negotiate communications which will take abou
60. ly black leads on the RS 485 cable so that enough bare wire is exposed for connection about 1 4 6mm NOTE No bare wire should be exposed when the connection is completed 3 Position the adapter so the side with the positive and negative marks is face up The small markings are on the same side as the screw heads as shown at right 4 Loosen the screw to the positive terminal and insert the red wire far enough to insert the bare wires into the terminal block under the screw then tighten the screw 5 Becareful not to break the wires 6 Repeat Step 3 with the negative terminal and the black wire 7 Plug the cable into the 485 RJ 45 port on the Liebert IntelliSlot Unity card Change User Names and Passwords Immediately Emerson recommends changing the administrative user name and password immediately to safeguard protected configuration and control areas of the Liebert IntelliSlot Unity card The user name and password are set at the factory each 1s Liebert case sensitive All printable characters are valid except gt lt gt Liebert IntelliSlot Unity Card User Manual 7 Installation A general user name and password are also set at the factory User and User case sensitive This may be left at the factory default or changed The general user has access only to non protected configuration and control areas of the Liebert IntelliSlot Unity card To change the default user names 1 Select the Comm
61. net Server enabled v Domain Name Server DNS Test Web Server Liebert IntelliSlot Unity Card User Manual 35 9 3 Edit the Liebert IntelliSlot Unity Card Configuration 3 1 IPv4 IPv6 The IPv4 and IPv6 settings determine which Internet Protocol will be used for communication over the network connected to the Ethernet port IPv4 and IPv6 networks will run in parallel dual stack network but the protocols are different See your network administrator to determine which protocol should be enabled and to determine the correct settings Figure 5 4 IPvA IPv6 settings a IE ar c t diia Settings IPyd Protocol Boot Mode Card Static IP Address Subnet Mask Default Gateway DNS Server Address Source IPv4 Primary DNS Server IPy4 Secondary DNS Server Edit Save Units Settings Edit Save Units enabled i Pv6 Protocol I enabled CHCE i Boot Mode Auto i Card Static IP Address ff i Prefix Length a i Default Gateway t __ a DNS Server Address Source Automatic x IPv6 Primary DNS Server i IPv6 Secondary DNS Server IPv4 Settings IPv6 Settings i IPv4 Settings IPv4 Protocol Enables IPv4 in the card IP Address Method Mode the card boots into to be a network ready device Static DHCP BootP Static IP Address Network address for the interface Subnet Mask Network mask for the interface which divides a network into manageable segments Default Gateway IP
62. nications Tab N S EMERSON a Network Power GXT4 1000RT120 Sensor Communications Liebert Email Updated February 9 2015 10 50 18AM Identification Settings Units Uninitialized Uninitialized Uninitialized i Email From Address i Email To Address Email Subject Type V Stat R nsn ij Custom Subject Text Edit GXT4 1000RT120 Normal Operation iy SMTP Server Address Button Sensor iy SMTP Server Port Normal Operation Communications i Include IP Address in Message Normal Operation i Include Event Description in Message i Include Name in Message Communications iy Include Contact in Message xi ene i i Include Location in Message ctive Events Downloads i Include Description in Message bp deos i Include Web Link in Message a Syst a i Enable Event Consolidation JNetwork i Consolidation Time Limit Tab Menu E reins ao i Consolidation Event Limit containing the Emerson Protocol T setting to be Ec Messaging Administrator login is required changed T Username PO Messaging Test Protocols Enter Password Password Status Dialog Box from caper clicking on Edit _Login Cancel Active Networking Firmware Update 32 Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 1 Web Page Communications Tab Folders The Communications Tab contains information about the overall event statu
63. nitoring up to 10 Liebert SN modular and integrated sensors Available sensor types include temperature humidity door closure contact closure and leak detection Sensor Tab menus permit configuring sensors and putting them in order for easier checking of high priority conditions 4 Liebert IntelliSlot Unity Card User Manual Installation 2 0 2 1 INSTALLATION A WARNING Risk of improper installation Can cause equipment damage injury or death Only a qualified service professional should install these products Emerson recommends having an Emerson Network Power Liebert Services representative perform the installation in large UPS s Contact Liebert Services at 1 800 LIEBERT 1 800 543 2378 NOTICE Risk of duplicate node ID s if two or more Liebert IntelliSlot cards are installed Can cause network conflicts An internal networking conflict may occur within a device when multiple communication cards with duplicate Node IDs are installed in the device Each Liebert IntelliSlot card must have a unique node ID This will not be a problem if only one card is installed on your system Duplicate node ID s are easily averted with the procedure detailed in 2 4 Installing Multiple Liebert IntelliSlot Unity Cards in a System Installing the Liebert IntelliSlot Unity Card The Liebert IntelliSlot Unity card may be installed at the factory or field installed To perform a field installation 1 Find the Liebert IntelliSlot
64. ns Tab gt Support b Enable the commands c Click on Restart Modbus RS 485 gt Welcome Liebert Administrator N EMERSON nn Network Power EXT4 1000RT120 Sensor ESSE Lu Liebert Modbus RTU Updated February 9 2015 10 14 46AM Settings Units i Node ID oo Node ID must be unique on the RS 485 bus this card is connected to Identification Uninitialized Uninitialized Uninitialized i Data Rate i Parity Check Status GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications E Summary Active Events Downloads Configuration Protocols CgBACnet Modbus Modbus TCP CdModbus RTU C9SNMP C3YDN23 9 Status 3 1 2 Enable BACnet Protocol Contact your system administrator or building management system administrator 1f you are uncertain about the settings l 2 P ox E x Select Communications Tab gt Protocols gt BACnet Click on Edit and enter a user name and password 1f required Enter the Managed Device Write Access level Read Only or Read Write This determines a user s ability to change settings in the Liebert IntelliSlot Unity card Choose the BACnet interface either BACnet IP or BACnet MSTP Set the Device Object Instance Number Set the Device Object Name Set the APDU Timeout Set the APDU Retries 14 Liebert IntelliSlot Unity Card User Manual Enable Communication Protocols
65. nt App Firmware Label Agent Boot Firmware Version Agent Boot Firmware Label Agent Serial Number Agent Manufacture Date Agent Hardware Version GDD Version FDM Version Product Sequence ID Restart Card Reset Card to Factory Defaults see Note below Generate and download diagnostic file Firmware Update Active Networking NOTE times within 10 seconds Downloading files to text accessible comma delimited or tab delimited files ease troubleshooting Displays information about the system setup access network connections Emerson Protocol settings and whether e mail and SMS messaging are enabled Lists information and settings related to available third party protocols employed to monitor equipment Shows the overall condition of the system and whether a restart is needed to activate configuration changes restart is performed only from the Support Folder Shows information needed for maintenance or troubleshooting and shortcuts to reboot the card reset the Liebert IntelliSlot Unity card to its factory defaults and to update the card s firmware page 51 Firmware Update also on page 55 The card may be reset to factory defaults manually by briefly pressing the reset button five Do not hold the reset button too long Pressing the reset button and holding it for 5 seconds will restart the card without resetting it to factory defaults To perform either function insert a straight non conductive tool into the small h
66. ntelliSlot Unity Card User Manual 39 Edit the Liebert IntelliSlot Unity Card Configuration 5 4 3 SMS Selections in SMS determine how the card sends text messages about events Settings SMS From Address SMS To Address SMS Subject Type Custom Subject Text DEFAULT SUBJECT SMTP Server Address FE SMTP Server Port Include IP Address in Message t in i m bus Include Event Description in Message Include Name in Message t Include Contact in Message sd Include Location in Message ya Include Description in Message sd Include Web Link in Message Rn Enable Event Consolidation E Consolidation Time Limit c r2 Consolidation Event Limit SMS Settings SMS From Address Sender s SMS address In most cases this will be the SMS address of the person to whom replies should be sent For example Support company com SMS To Address SMS address of the recipient Multiple SMS addresses should be separated by a semicolon Note The maximum length for an SMS address entry 1s 64 characters SMS Subject Type Subject of the message either Default or Custom Custom Subject Text The subject of the message can be customized by the customer SMTP Server Address Fully qualified domain name or IP address of the server used for relaying SMS messages The maximum length for this entry 1s 32 characters Note 2 If using a server name a DNS server must be configured
67. ocol 1 1 IS UNITY DP Button Reboot or reset to factory defaults 7 Liebert Sensor Network J Protocols Each card supports the Emerson Protocol Remote Service Delivery Protocol and HTTP Web by default The Liebert IntelliSlot Unity DP supports selecting two third party protocols the Liebert IntelliSlot Unity LIFE card supports the default protocols only Emerson Protocol Remote Service Delivery Protocol and HTTP Web Available protocols are BACnet IP BACnet over Internet Protocol BACnet MSTP BACnet Master Slave Token Passing MSTP communications protocol over a RS 485 serial network also known as BACnet MSTP RS 485 Modbus RTU Modbus Remote Terminal Unit RTU communication protocol over a RS 485 serial network also known as Modbus RTU RS 485 Modbus TCP Modbus Transmission Control Protocol over Internet Protocol also known as Modbus TCP IP SNMP e YDN23 YD T 1363 specification protocol also known as YD T 1363 2 Lieberf IntelliSlot Unity Card User Manual Introduction 1 2 Compatibility With Other Emerson Products and Communication Protocols The Liebert IntelliSlot Unity platform includes Table 1 1 Compatibility with Liebert equipment Liebert IntelliSlot Card Compatible with Liebert APM Liebert APS Liebert Challenger 3000 Liebert CRV Liebert CW Liebert DCP Liebert Deluxe System 3 Liebert DS Liebert DSE Liebert eX
68. ole on the front of the card see Figure 1 1 for the Reset Button s location Liebert IntelliSlot Unity Card User Manual 27 Liebert IntelliSlot Unity Card Web Page Layout 45 Sensor Tab Menus Shown Only if a Sensor is Connected When Liebert SN sensors are installed and connected to the sensor port on the Liebert IntelliSlot Unity card the Sensor Tab appears It contains folders showing an overview of the installed sensors the event status of the sensors download links for log files and sensor configuration settings as detailed below Figure 4 6 Sensor Tab menu Labels may be assigned to sensors to aid in monitoring ada Actual sensor values such as adding its location EN EMERSON Network Power GXT4 1000RT120 Sensor Liebert leons for door Summary Updatsd March 7 2015 01 26 25PM closure and Type Serial Number Value Status contact closure Srvr Room 7 Front Closed sensors The Door Closure B90000000DE10420 lower sensor Srvr Room 7 Side Open oo identification 5 Uninitialized 11 Uninitialized O 12 Uninitialized m p shows the door Q 2 1 Temperature 11000000054F5742 Rack 7 12c Top 31 7 C y is open Status O 3 1 Temperature FF000000054B9542 Rack 7 12c Middle 215 4 GXT4 1000RT120 O 4 1 Temperature D8000000054E7142 Rack 7 12c Bottom 243 C cum E n O 5 1 Temperature A70000000368FA42 Srvr Room 7 Ambient 243 C Eo mpm Normal Operation
69. ored equipment the Liebert IntelliSlot Unity card and any Liebert SN sensors connected to the card Tab Menus The Liebert IntelliSlot Unity card has two tabs by default the Managed Device Tab which will display the name of the monitored equipment and the Communications Tab A third tab the Sensor Tab appears if Liebert SN sensors have been installed The tab selected determines the menu shown Managed Device Tab Information pertaining to the equipment being monitored and controlled Refer to 4 3 Managed Device Tab Menus for details The tab label refers to the type of Liebert unit the card 1s installed in For example the Managed Device Tab for a card installed in a Liebert GXT4 1000 RT120 UPS will be labeled GXT4 1000 RT120 see Figure 4 1 for this example Figure 4 2 shows a Web page for a Liebert IntelliSlot Unity card installed in a Liebert CRV Communications Tab Information about the Liebert IntelliSlot Unity card such as the overall event status of the equipment and communication interface logs of third party information communication settings third party protocol settings and system status Refer to 4 4 Communications Tab Menus for details Sensor Tab Information about Liebert SN sensors if any are installed including status or data from each sensor and sensor configuration settings When sensors are connected to the card this tab appears between the Managed Device Tab and the Communications Tab The tab is no
70. osts that will receive SNMPv8 traps identified with either a network name or IP address Multiple addresses must be separated by commas The field has a maximum length of 125 characters e SNMPv3 Trap Port Port used by the target host for receiving SNMPv8 traps default is 162 5 8 2 Edit the SNMPv3 Table The table on the SNMPv3 User Settings 20 page may be altered to provide more or less information To do so click on the command above the table Click here to edit columns displayed in this table Put a check mark 9 in the boxes beside the desired information see Figure 5 5 The choices permit showing the same information in this screen that is displayed by clicking on a SNMPv3 User Settings folder or a SNMPv3 User Settings link Figure 5 5 Edit the SNMPv3 table Click on this link to change the information shown in the table Click here to edit M s displayed in the table SNMPv3 User Enable disabled disabled disabled disabled disabled disabled disabled Report SNMPv3 User 1 SHMPv3 User 2 SNMPv3 User 3 SMMPv3 User 4 SNMPv3 User 5 ONMPv3 User 6 SNMPv3 User 7 SNMPv3 User 8 disabled SHMPv3 User 9 disabled SHMPv3 User 10 disabled SNMPv3 User 11 disabled SNMPv3 User 12 disabled SHMPv3 User 13 disabled ONMPv3 User 14 disabled SMMPvy3 User 15 disabled SNMPv3 User 16 disabled SNMPv3 User 17 disabled SHMPv3 User 15 disabled SHMPw3 User 19 disabled SNMPv3 User 20 di
71. otocol BACnetDataMap txt for BACnet IP and BACnet MSTP ModbusDataMap txt for Modbus TCP and Modbus RTU SNMP_Events txt SNMP Parameters txt SNMP upsMibEvents txt and SNMP upsParams txt for SNMP v1 v2c v3 Ydn23DataMap txt for YDN23 More information about BACnet and Modbus protocol mapping 1s available 1n the Liebert IntelliSlot Modbus RTU Modbus TCP BACnet MSTP and BACnet IP Reference Guide SL 28170 at Liebert s Web site ww w liebert com The SNMP MIB files are also available for download from the Web site Lieberf IntelliSlot Unity Card User Manual 21 4 0 4 1 Liebert IntelliSlot Unity Card Web Page Layout LIEBERT INTELLISLOT UNITY CARD WEB PAGE LAYOUT Default settings in the Liebert IntelliSlot Unity card permit using it immediately after installation to monitor the equipment the card is installed 1n The Web interface permits customizing the information to ease monitoring the equipment and troubleshooting problems Users can name the equipment enter a location set up e mail and text alerts and change equipment settings NOTE The Edit button will be grayed out if the settings on a menu cannot be changed Web Page Sections Each Web page displayed by the Liebert IntelliSlot Unity card has these main areas see Figure 4 1 dentification Status Tab Menus Detail Identification Displays the System Name System Location and System Description Status Displays the status of the monit
72. rained and qualified personnel and in accordance with applicable regulations and manufacturers specifications Opening or removing the covers to any equipment may expose personnel to lethal voltages within the unit even when it 1s apparently not operating and the input wiring 1s disconnected from the electrical source Check the circuits with a voltmeter before beginning installation Liebert IntelliSlot Unity Card User Manual 1 1 0 Introduction INTRODUCTION This Liebert IntelliSlot Unity platform delivers enhanced communication and control of AC Power Power Distribution and Thermal Management products The platform communicates withEmerson Network Power software tools and services including Trellis LIFE Services Liebert SiteScan Web and Liebert Nform The platform includes the Liebert IntelliSlot Unity DP and Liebert IntelliSlot Unity LIFE cards Each card employs the Emerson Protocol to monitor and manage a wide range of operating parameters alarms and notifications about power distribution and cooling equipment The cards also communicate with Building Management Systems and Network Management Systems Liebert IntelliSlot Unity cards support monitoring of sensors to improve system reliability and efficiency Figure 1 1 Liebert IntelliSlot Unity DP card features RJ 45 Ethernet HTTP Modbus TCP Modbus RTU BACnet MSTP Micro USB AB BACnet IP SNMPv1 v2c v3 YDN23 future release Emerson Prot
73. ration Folder The Configuration folder s top level displays the System Model Name of the Liebert IntelliSlot Unity card This name 1s factory set and cannot be Communications changed the Edit button is grayed out The Configuration folder Summary contains seven subfolders System User Network amp 3LIFE TM E Emerson Protocol Web Server 1 Messaging LIFE Emerson Protocol Messaging Liebert IntelliSlot Unity Card User Manual 33 Edit the Liebert IntelliSlot Unity Card Configuration 5 3 1 Configuration Folder System The System subfolder displays general information about the monitored and managed device and the display of some data Refer to Figure 5 2 The data displayed is set by the user and can assist in troubleshooting To alter the information displayed click on the Edit button enter the administrator name and password and make changes Click Save to save the changes click Cancel to discard the changes Figure 5 2 Configuration folder System subfolder Communications Settings Units Summary 3 EJ Active Events i System Name Uninitialized 3 Downloads i a Configuration iy Contact Information Ininitialized System i System Location Uninitialized zjTime Service iy System Description JUser i Display T ture Unit 2 3 Network i Display Temperature Units z3Web Server r C3LIFE TM Enter the information in the dialog boxes and choose A Pal temperature di
74. rator User Updated February 9 2015 09 59 41AM Name and Password Edit Units General User Name and Password The Liebert IntelliSlot Unity card requires minor configuration such as choosing the IP Web communication interface serial RS 485 communication interface or both The default for IP Web communication is IPv4 but this can be changed to IPv6 for greater security contact your network administrator to determine whether it is compatible with your network To choose the communication interface refer to Figure 2 3 1 Select Communications Tab gt Configuration gt Network Lieberf IntelliSlot Unity Card User Manual Installation 2 Enable the protocol either IPv4 or IPv6 that will be used to communicate with the Liebert IntelliSlot Unity card and with the Liebert equipment Click on either IPv4 or IPv6 Click the Edit button c When prompted with a login display enter the user name and password the defaults are Liebert and Liebert d Puta check mark 9 in the enabled box e Insert the desired or assigned IP address along with the rest of the required networking information contact your system administrator if necessary 3 Click on Save to confirm the changes or click on Cancel to discard them The changes will take effect after the card 1s restarted Figure 2 3 Enabling the communication protocol IPv4 or IPv6 Edit Button Edit Dialog Box Administrator login is required Username i
75. s of the equipment and communication interface It presents logs of third party information communication settings third party protocol Communications H E Configuration settings and system status information Ere c Status The Communications Tab folders are shown at right Ga Support 5 1 1 Communications Tab Active Events Folder The Communications Tab s Active Events folder contains no configurable settings The folder displays events affecting the Liebert IntelliSlot Unity card 5 2 Communications Tab Downloads Folder The Communications Tab s Downloads folder contains no configurable settings The folder displays links to download logs of third party protocols that are enabled on the Liebert IntelliSlot Unity card The logs help in configuring and troubleshooting communication between the Network Management or Building Management Systems being used to monitor the managed device A Y EMERSON o Network Power GXT4 1000RT120 Sensor UNA Liebert Downloads Updated February 9 2015 10 42 37AM Identification Please click to download or open a file Uninitialized Agent Logs Uninitialized Uninitialized SNMP Traps log SystemEvents lo Status GXT4 1000RT 120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications Summary Active Events m A resheeebct ee C3 Configuration C Protocols fit ea aL 5 3 Communications Tab Configu
76. sabled SNMPv3 User SNMPv3 SNMPv3 Enable Username Access Type disabled D Read Only SNMPv3 Authentication Choose data points to be displayed as columns in the table and hit Update button To exit without changes hit Cancel button Note Information is saved as browser cookies 2 SNMPv3 User Enable SNMPv3 Username SNMPv3 Access Type SNMPv3 Authentication SNMPv3 Authentication Secret SNMPv3 Privacy SNMPv3 Privacy Secret SNMPv3 Trap Targets SNMPv3 Trap Port Advanced Settings Number oftables i v Hide column text Useful to reduce a width of table Update Cancel SNMPv3 Authentication Secret SNMPv3 Privacy SNMPv3 Privacy Secret Targets Checking all choices will display the information below on the SNMPv3 User page SNMPv3 Trap SNMPv3 Trap Port The information in the table for one user may be viewed by clicking on a SNMPv3 User Settings folder or a SNMPv3 User Settings link as shown at right Liebert IntelliSlot Unity Card User Manual Settings i SNMPv3 User Enable i SNMPv3 Username i SNMPv3 Access Type i SNMPv3 Authentication io SNMPv3 Authentication Secret iji SNMPv3 Privacy ip SNMPv3 Privacy Secret is SNMPv3 Trap Targets i SNMPv3 Trap Port 47 Edit l enabled Units Edit the Liebert IntelliSlot Unity Card Configuration 5 8 3 SNMPv1 Trap Settings This page contains settings for network hosts t
77. scription Enable or Disable LIFE service Mode Liebert IntelliSlot Unity Card User Manual 59 While every precaution has been taken to ensure the accuracy and completeness of this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions O 2013 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert is a registered trademark of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners SL52645_REV5 Emerson Network Power Division Liebert Web www emerson com Technical Support Service Web Site www liebert com Monitoring liebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS amp Server Cabinets liebert upstech emerson com 800 222 5877 Outside North America 00800 1155 4499 Three Phase UPS amp Power Systems 800 543 2378 Outside North America 614 841 6598 Environmental Systems 800 543 2778 Outside the United States 614 888 0246 Locations United States 1050 Dearborn Drive P O Box 29186 Columbus OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco PD Italy 39 049 9719111 Fax 39 049 5841 257 Asia 29 F The Orient Square Building F Ortigas r Road Ortigas Center Pasig
78. splay either Celsius or Fahrenheit is i 5 3 1 1 Time Service Settings The System Subfolder contains one folder Time Service Each setting offers either a menu of choices or an enable disable check box Users can set these parameters Figure 5 3 Configuration folder System subfolder Time Service Settings Edit Save External Time Source ITD Sarver NTP Time Server NTP Time Sync Rate Time Zone Units Enable Auto Sync To Managed Device enabled m i Managed Device Auto Sync Rate External Time Source The external source to be used for time synchronization NTP Time Server Network Time Server NTP URL or IP address NTP Time Sync Rate The rate at which time will be synchronized with the Network Time Protocol server if NTP is the external time source Time Zone Time zone where the device is located Enable Auto Sync to Managed Device Enable automatic writing time to the managed device Managed Device Auto Sync Rate Rate at which time will be written to the managed device if an external time source has been selected 34 Liebert IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 3 2 Configuration Folder User The User subfolder displays the administrator s and general user s name and password Each can be changed The default user name and password for the administrator are Liebert and Liebert The defaults for
79. t one minute for details on autoconfiguration see 2 1 2 Connect an Ethernet Cable When communication 1s established open a Web browser and enter the address 169 254 24 7 the card s default Autoconfiguration IPv4 Address The card s Web page will appear Figure 6 1 Ethernet port Liebert IntelliSlot Card Ethernet Port IS UNITY DP amp EMERSON Network Power 4 Select the Communications Tab at the top of the screen then the Support folder from the Communications folders on the left of the screen and then the Firmware Update folder Select the Enable button 6 Enter the administrator user name and password selected previously see 2 2 Change User Names and Passwords Immediately in the security dialog box that appears Liebert IntelliSlot Unity Card User Manual 55 Firmware Updates 7 Click on the Web button and the firmware update screen will appear 8 Browse to the firmware file to update select 1t and click the Update Firmware button NOTE Do not navigate away from the Firmware Update screen and do not close the browser once the update begins Either action will interrupt the download Figure 6 2 Firmware update screen 6 2 N Welcome Liebert Administrator v EMERSON Metwork Power APS Unity L e be rt Firmware Update Updated March 11 2014 04 20 26PM Identification Status Value Units Uninitialized i Current Firmware Version 4000 Uninitialized ij
80. t shown when no sensors are connected to the card see Figure 4 3 Refer to 4 5 Sensor Tab Menus Shown Only if a Sensor is Connected for details 22 Liebert IntelliSlot Unity Card User Manual Liebert IntelliSlot Unity Card Web Page Layout Detail Displays detailed information about the device based on the menu selection made in the Tab Menu area Edits to the device and its configuration are made in this section Figure 4 1 Web page sections UPS example Managed Device Tab Sensor Tab mm Card in a Liebert GXT4 N y Communications Tab M bi EMERSON Summary Updated March 10 2015 11 30 41AM Identification Information on the a Uninitialized Opening Screen enue Uninitialized daa depends on type of unit Enabled being monitored Status E is Status GXT4 1 000RT120 Input Output Status of Demi crie LN 1190 vac Y BN Va equipment Normal Operation 13 AAC 17 AAC un Communications 59 9 Hz 0 0 96 sensors if any Normal Operation 209 VA are installed and ps GXT4 1000RT120 59 9 Hz communications sms se Battery a o DS Voltage 54 VDC Downloads Charge 100 GS Normal Tab Menu input Time Remaining 32 min Absent C3 Bypass changes Seater according to ff Souter coup JECO Mod Active Events Updated March 10 2015 11 30 40AM monitored MS equipme nt Select all No Active Events Figure 4 2 Web page sections Thermal Management unit example Managed Devi
81. ters If using a server name a DNS server must be configured under Network Settings SMTP Server Port SMTP server port Note Typically the default of 25 should be used Include IP Address in Message If checked the IP Address of the agent card will be included in outgoing messages Include Event Description in Message If checked SNMP event description will be included in outgoing messages Include Name in Message lIf checked the agent card Name will be included in outgoing messages Include Contact in Message lIf checked the agent card Contact will be included in outgoing messages Include Location in Message If checked the agent card Location will be included in outgoing messages Include Description in Message If checked the agent card Description will be included in outgoing messages Include Web Link in Message If checked a Web link to the agent card and Web Server listening port number will be included in outgoing messages Enable Event Consolidation If checked multiple events will be sent per outgoing message Consolidation Time Limit If Event Consolidation 1s enabled a message will be sent when Consolidation Time Limit seconds has passed since the first buffered event was received Consolidation Event Limit If Event Consolidation is enabled a message will be sent when the number of buffered events reaches the Consolidation Event Limit Liebert I
82. the GXT4 1000RT120 4 selected oer opos 5 Temperature 124 1 0000000004323342 sensor higher Normal Operation 6 Temperature 124 5 54000000046B9142 in the list Communications 7 Relative Humidity ambient 6A000000FCC11426 Normal Operation 2 S i ensor 10 This arrow E Summary moves the lesan Click on a radio button to selected Ga Sensor Subsystem select a sensor to move up sensor lower Sensor Change or down the list in the list Sensor Order Liebert IntelliSlot Unity Card User Manual 31 Edit the Liebert IntelliSlot Unity Card Configuration 5 0 EDIT THE LIEBERT INTELLISLOT UNITY CARD CONFIGURATION The Web based interface can be used to change settings for the Liebert IntelliSlot Unity card and for the monitored equipment The following steps apply to making changes in all sections of the Liebert IntelliSlot Unity card To edit the configuration 1 Open a Web browser and enter the card s IP address 2 Click on the Communications Tab 3 Select the menu in the Tab Menu area that contains the configuration setting to be changed 4 Click the Edit button near the top of the Web page see Figure 5 1 5 Enter the administrator name and password for the Liebert IntelliSlot Unity card in the dialog box that opens the default settings are Liebert and Liebert Click OK 7 Change the settings ET 8 Click on Save to apply the changes or click Cancel to discard them Figure 5 1 Editing configuration settings Select Commu
83. tings GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation E Summary Active Events Downloads Cd Configuration Protocols BACnet Modbus SNMP Uninitialized Uninitialized Uninitialized A Welcome Liebert Administrator NS EMERSON x Network Power GXT4 1000RT120 Sensor Communications Liebert SNMPv3 User 1 Updated February 9 2015 10 23 01AM Identification Settings Edit SNMPv3 User Enable enabled SNMPv3 Username SNMPv3 Access Type SNMPv3 Authentication SNMPv3 Authentication Secret SNMPv3 Privacy i SNMPv3 Privacy Secret ij SNMPv3 Trap Targets SNMPv3 Trap Port Units Status Communications gt gt m 3ISNMPv3 User 20 CJSNMP v3 User 1 C3 SNMPv3 User 2 C9 SNMP v3 User 3 CI SNMPv3 User 4 COSNMPv3 User 5 3 1 3 3 Configure SNMPv1 Trap Settings l 2 Select Communications Tab gt Protocols gt SNMP gt SNMPv1 Trap 20 Click on Edit and enter a User name and password if required Settings are required for each user Enter the information and set the permissions appropriate to the user Refer to Figure 3 9 for the information required Click Save to confirm the changes or click on Cancel to discard them Lieberf IntelliSlot Unity Card User Manual 19 Enable Communication Protocols Repeat Steps 1 through 4 for any additional users Restart the
84. tocol llle 15 0 12 2 Contisure BACnet MSTP Protocol ius ara ai ERE SEE ke 16 A SA O A dea aa a a nee 17 3 31 Configure SNMP Settings rod eet E eee ota dede ee ded Oe RES 18 ovo 2 Configure SNMP o ce velvet aU o Ud RC RUE USA 18 3 1 3 3 Configure SNMPv1 Trap Settings eee 19 3 1 3 4 Configure SNMPvl v2c Access Settings o o ooooooo ooo ees 20 3 2 Download Protocol Mappings 44122 ba ek mE wade Ow Roe a OE ROS a e 21 4 0 LIEBERT INTELLISLOT UNITY CARD WEB PAGE LAYOUT leeren 22 Al NV CDP ACC Sections a it ir do Be Made d 22 49 Managed Device Lab Menus 24244 tarado di ia A ada 26 AA Communications Tab Menus is air ts Dd a a td Vea coda a 21 4 5 Sensor Tab Menus Shown Only if a Sensor is Connected o ooo ooo 28 40 Sensor labusumimary Ba Oi ud a AA e RUPEE RUP EU i 29 4 5 2 Sensor Tab Summary Page Details Pane lee 29 AG hanoin Sensor Order 4 oie elas dario EROR Spe RS en Ee atra Sot ono atate aol ira os ROS 31 Lieber CRV IntelliSlot Card User Manual i 5 0 EDIT THE LIEBERT INTELLISLOT UNITY CARD CONFIGURATION eee 32 5 1 Web Page Communications Tab Folders lle 39 5 1 1 Communications Tab Active Events Folder llle 99 5 2 Communications Tab Downloads Folder llle 33 5 3 Communications Tab Configuration Folder 0 0 0 0 ccc eee eens 33 5 3 1 Configuration Folder System 0 0 00 cc
85. umidity Threshold The Managed Device Tab will display Status or Events for the applicable equipment only Power information is shown in this Managed Device Tab for a UPS Edit Save Cancel r Value Units 71 5 RH 41 0 RH Status Ack Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Normal Value Units 45 RH 5 RH 5 96 RH fo RH 60 0 96 RH 15 0 96 RH Lieberf IntelliSlot Unity Card User Manual Liebert IntelliSlot Unity Card Web Page Layout 4 4 Communications Tab Menus The Communications Tab shows the overall event status of the equipment and communication interface It contains logs of third party information communications settings third party protocol settings and system status information as detailed below Table 4 2 Communications Tab menus Communications Tab Menus See Details Active Events Displays the current event activity page 33 Downloads Agent or Unity Card Logs Event Logs Data Logs Other files Configuration System User Network Web Server LIFE Emerson Protocol Messaging Protocols Modbus BACnet SNMP YDN23 Status System Status System Restart Required needs to LIFE device identity changed LIFE be reconfigured RS 485 Port Conflict Duplicate Emerson Protocol MSTP Node ID Duplicate BACnet MSTP Node ID Support Agent time and Date Agent Model Agent App Firmware Version Age
86. unications Tab gt Configuration gt User 2 Click the Edit button and enter the factory set administrator user name Liebert and password Liebert Click OK pe En ot Se RE So XE Optional General User Name Change Enter a new general user name and password Enter a new administrator user name and password Re enter the administrator password to confirm it Re enter the general user s password to confirm it Click the Save button to confirm the changes or click Cancel to discard them NOTE Record the new user names and passwords and save them in a secure place where they can be found 1f forgotten A lost password cannot be retrieved If the password is lost the card must be reset to factory defaults and reconfigured Figure 2 2 Change administrator and general user names and passwords 2 3 SN SS EMERSON _ Network Power GXT4 1000RT120 Sensor Com User Identification Uninitialized Uninitialized Uninitialized Status GXT4 1000RT120 Normal Operation Sensor Normal Operation Communications Normal Operation Communications Summary Active Events Downloads c Configuration System oret Network Configure the Card Settings iv Administrator Username ij Administrator Password i Reenter Administrator Password i General User Username i General User Password i Reenter General User Password Liebert munications Administ
87. v1 Tran 2 E i SNMP Trap Community String xx SNMPv1 Trap Settings SNMP Trap Target Addresses Configure network hosts that will receive alert notifications 1 e SNMP Traps The host can be identified as either an IP address or the host s network name SNMP Trap Port Port used by the target host for receiving notifications default is 162 SNMP Trap Community String String identifying a secret known only by those hosts that want to be notified of device status changes 48 Lieberf IntelliSlot Unity Card User Manual Edit the Liebert IntelliSlot Unity Card Configuration 5 8 4 SNMPv1 v2c Access This page contains settings for network hosts that can access data using SNMPv1 v2c Up to 20 access hosts can be enabled and configured Like the SNMPv3 pages the setting for each host may be reached by clicking on the links in the data portion of the page or by clicking on the folders for the access hosts Also data shown in the table may be changed by clicking on the link above the table A MA E TEE Logout EMERSON M T MAS Network Power GXT4 1000RT120 Sensor Communications Liebert SNMPv1 v2c Access 1 Table Updated February 9 2015 10 27 16AM Identification Click here to edit columns displayed in the table Click on this link to change the information shown in the table on this page to the information shown below Uninitialized Uninitialized Un
88. ware Label UNITY HID1 1 0 0 0 00000 Normal Operation ij Agent Serial Number 4178318201D2012MAY 310001 os pera ij Agent Manufacture Date MAY 31 2012 Communications i Agent Hardware Version 1 Normal Operation i GDD Version 99569 i FDM Version 941 Communications i Product Sequence ID 11 1 E as Commands Cance Ca Downloads i Restart Card Restart E Configuration Protocols i Reset Card to Factory Defaults Reset to Factory Defaults dimin A Generate and download diagnostic file Get File Lieberf IntelliSlot Unity Card User Manual 51 Edit the Liebert IntelliSlot Unity Card Configuration Support Folder Settings Agent Date and Time Date and time setting for the card Agent Model The card s model Unity Platform Agent App Firmware Version The card s firmware version 2 0 or higher Agent App Firmware Label The card s firmware label Agent Boot Firmware Version The card s Boot firmware version Agent Boot Firmware Label The card s boot firmware label Agent Serial Number The card s serial number Agent Manufacture Date The card s manufacture date Agent Hardware Version The card s hardware version GDD Version The card s GDD version current when the card s firmware was installed the GDD 1s a proprietary reference document for device data FDM Version The card s FDM version the FDM 1s a data model document that defines data supported by devices that use the Emerson Protocol Product Sequence ID
89. y to managed UPS equipment RFC 1628 MIB Traps Enable or Disable support for sending RFC 1628 traps Required for proper operation of Liebert MultiLink and applies only to managed UPS equipment Liebert Global Products LGP MIB Enable or Disable support for getting and setting data using the Liebert Global Products MIB LGP MIB Traps Enable or Disable support for Liebert Global Products MIB traps LGP traps will not be sent unless LGP MIB 1s enabled LGP MIB System Notify Trap Enable or Disable support for the LGP System Notification trap This is a single trap sent each time an alarm or warning is added or removed from the conditions table It provides a text description of the event in a varbind of the trap message LGP System Notify Traps will not be generated unless the LGP MIB 1s enabled Liebert IntelliSlot Unity Card User Manual 45 Edit the Liebert IntelliSlot Unity Card Configuration 5 8 1 SNMPv3 User Settings The Liebert IntelliSlot Unity card supports up to 20 SNMPv3 users The top level page has a table with settings for all 20 The page displays a link to edit the table columns displayed for each SNMPv3 user The same settings may be accessed by clicking on a folder for a user such as SNMPv3 User 1 The Web page below shows the settings that can be changed for a SNMPv3 user To display the settings click on any of the SNMPv3 User links After making any changes click Save to make the changes effective click C