Home

Combi 300 Polar user manual

image

Contents

1. nsket rumtemperatur 5 30 C Panelfgler T15 er styrende f ler wu Figure 11 The User select 2 menu page 14 af 26 A R N d OUTSTANDING INDOOR CLIMATE Setting of clock In case of power cut the clock will function for at least 24 hours If the time function is lost there will be an alarm Changing to daylight saving time has to be done manually indicates that the menu point flashes and can be set to another value Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on 09 05 26 ENTER YEAR ENTER YEAR ENTER TU 12 10 09 09 time after setting up the time function MINUTE ENTER MINUTE 10 10 Seconds are being reset when minutes are adjusted Figure 12 Setting of clock May be subject to change page 15 af 26 4 R N Dp OUTSTANDING INDOOR CLIMATE Week programme The unit is equipped with 3 standardized week programmes See page 17 The unit is set to programme 1 from the factory In addition to these programmes it is possible to program your own week programme which can be one of the standard programmes with minor alterations indicates that the menu point flashes and can be set to another value Use of the CTS602 panel pre
2. press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on in AUTO mode the unit automatically choses cooling or heating according to the desired room temperature AUTO AUTO 22 19 C gt 2 lt 19 C AUTO COOLING gt 2 lt 5 30 C gt 2 lt 19 C HEAT gt 2 lt 19 C Heating according to the desired room temperature The indicated ventilation step applies for the exhaust ENTER Main menu Cooling according to the desired room temperature between 5 to 30 C Desired room Bs set Figure 6 Headlines in the Main menu May be subject to change page 8 af 26 A R N d OUTSTANDING INDOOR CLIMATE Show alarms If the unit is in a state of alarm the yellow light emitting diode on the front of the CTS600 panel will flash The Show alarms menu indicates the type of alarm and the time of the alarm This is also the menu where the alarm should be reset SHOW ENTER ALARM 6 ENTER 06 05 30 ENTER 00 00 00 ALARMS DEFROST TI 11 32 j TM 00 00 ALARM 4 PRESSURE ALARM 13 BOILING critical alarms are shown first ENTER ENTER The list is erased if AL 1 06 05 30 the power is cut ALS RINDS DEFROST TI 10 28 Resetting of alarms Alarms should be reset individually Only active ala
3. C Y Minimum outside temperature at which the system runs in summer operating mode If the outside temperature is below 12 C the system will switch to winter operating mode Figure 20 The Temp control menu May be subject to change page 23 af 26 A R N OUTSTANDING INDOOR CLIMATE Setting of language In this menu you set which language to be used in the CTS602 panel indicates that the menu point flashes and can be set to another value Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on LANGUAGE SUOMI LANGUAGE NORWEG ENTER LANGUAGE DANISH LANGUAGE DANISH LANGUAGE SWEDISH LANGUAGE FRENCH LANGUAGE GERMAN LANGUAGE ENGLISH Figure 21 The Language menu May be subject to change page 24 af 26 R h OUTSTANDING INDOOR CLIMATE Filter change Outdoor and extract air filters are placed behind the front of the system The filters can be replaced as needed the units are configured from factory to the filters having a life span of 90 days The desired life span can be altered using the control panel Before change filter oj Always disconnect the power to the system Screws are
4. 19 af 26 A R N d OUTSTANDING INDOOR CLIMATE Humidity In the Humidity menu it is possible to regulate the ventilation step in accordance with the humidity level Low ventilation step is only active in wintertime and at humidity levels below 30 High step is activated by a change from 10 5 of average RH from 40 80 over the last 24 hours High ventilation step is deactivated when humidity drops 3 or more compared to the average humidity level the last 24 hours It can last up to 3 minutes before high low ventilation step i stabilized If there is a need for heat the low humidity is not activated indicates that the menu point flashes and can be set to another value Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on Option of choosing low ventilation step at low humidity The value can be set to OFF and 1 2 3 ENTER ENTER Adjustable range between 15 45 Standard is 30 96 HUMIDITY FLOW HUMIDITY LOW 1 LOW ub Option of choosing high ventilation step at high humidity The value can be set to OFF and 2 3 4 ENTER Due MIN Maximal duration for high ventilation step caused by high humidity Figure 17 The Humidity
5. EREET EEA EEN EEEE EKA 19 Figure 17 The Humidity Menu iae ocie unda einn a peo Yu Rok ERE ELDER Een kran d I M EPI E RR E YR MEE 20 Figure 18 The Air exchange Menu ueice eene retainer t danti nara paran a pups ana Reus Rn Ya ER ana REA Rn dag EEN 21 Figure 19 The Air filter menu sssesseesessseeeeseeeeenennnenennnn nennen nenne eenn 22 Figure 20 The Temp control Menu rmm 23 Figure 21 The Language maville cea beer cnn mami ED mun 24 Figure 22 Filter chang coisa os se cach od xa 25 R N p OUTSTANDING INDOOR CLIMATE Introduction Directions for assembly and use CTS 602 directions this document Electrical chart d Please control that the following documents have been delivered together with the unit The purpose of this manual is to clearly show the menus and possibilities of the CTS 602 control This manual may describe functions that are not accessible in your unit The directions can be used for all types of units described in figure 1 page 4 May be subject to change page 3 af 26 R N OUTSTANDING INDOOR CLIMATE Review of the thermometer sensors se Str mforsyning M N23N S0Hz nox 16A Skkerhedsafbryder T TLLUFT 7 TULOLMA SIS LLE lt A FRALUFT SS postouma TALOSTA 4 AFKASTLUFT 4 JATEILMA ULOS S UDELUFT lt RAITISILMA ULKOA Figure 1 Thermometer sensors Explanation f
6. I T WATER Warming up the hot water is not Contact service possible 24 I T HEAT Warming up the water for central Contact service heating is not possible 27 57 C T KURZ One of the temperature sensor of Please note which sensor T the device is shorted or defec x there is shorted and tive Tx 99 CT contact the customer ser vice 28 58 C T OFFEN One of the temperature sensor of Please note which sensor T the device is disconnected or X there is interruped and defect Tx 40 C contact the customer ser vice 70 W ANODE There is an error at the anode on Contact service the hot water tank It has not been connected correctly or it has cor roded 71 I DFR EXCH The maximum defrosting time for Contact our after sales the counter flow heat exchanger department if resetting the has been exceeded This could alarm does not help be due to the fact that the system If possible inform the after has been exposed to very low sales department of the temperatures current working tempera ture from the menu VIS DATA SHOW DATA 72 I EVAP LOW Abnormally low evaporator tem Check supply air valve perature 92 I PRESET Error by writing or input of the Contact service electrician s adjustments May be subject to change Figure 8 The Alarm Indicators menu page 11 af 26 4 R N d OUTSTANDING INDOOR CLIMATE Show data The actual operation data can be read in the Show data menu See rev
7. W ROOM LOW When room temperature drops Heat up the house and below 10 the unit will stop in reset the alarm order to protect the house from further cooling down The function is useful when the house is not occupied and the main heating has stopped May be subj ect to change page 10 af 26 4 R N d OUTSTANDING INDOOR CLIMATE Alarm Categori Text of Description cause How to remedy alarms code display 16 l SOFTWARE Error in software Contact service 17 l WATCHDOG Error in software Contact service 18 I CONFIG Parts of the programming are lost Reset alarm and can be caused by a longer Re programme the week period of power failure or light programme ning The unit will keep on Contact service if the unit operating on standard program does not operate as before ming Supplementary programs can be lost Only service can access the supplementary pro grams and menus 19 I FILTER The filter guard is set to give Clean replace filter and alarm when a pre set period of reset alarm time has occurred 20 I LEGIONEL Legionella temperature has not Contact service been reached within the time limit 21 I POWER Occurs if power has been cut off The week programme for a longer period of time should be checked and adjusted if necessary Reset alarm 22 I T AIR The pre set temperature of the Set a lower air inlet tem inlet air cannot be reached perature and reset alarm 23
8. loosened and the lid is removed The filters can be removed without using tools Figure 22 Filter change Condensation drain and water trap oj Always disconnect the power to the system Check if condensation drain and water trap is clear off filth if necessary clean drain and water trap May be subject to change page 25 af 26 Am R N d OUTSTANDING INDOOR CLIMATE Accessories spare parts Combi 300 Polar Filter types Qty Nilan item no Filter sheet G4 2 39530 Filter cassette F7 1 39520 May be subject to change page 26 af 26
9. menu May be subject to change page 20 af 26 Air exchange In the Air exchange menu it is possible to regulate the airflow in wintertime indicates that the menu point flashes and can be set to another value AIR EXCHANGE May be subject to change Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on The value can be set to OFF or from 15 C The compressor starts in heating mode at low outdoor temperature to 15 C ra COMP MIN ENTER OFF C COMP MIN OFF C A R N d OUTSTANDING INDOOR CLIMATE Possibility of low ventilation step at low outdoor temperatures The value can be set to OFF 1 23 WINTER LOW WINTER LOW 3 van WINTER lt 0 OG WINTER SODE Y v s s Outdoor temperature at which low ventilation step is activated Figure 18 The Air exchange menu page 21 af 26 A N OUTSTANDING INDOOR CLIMATE i Air filter In the Air filter menu it is possible to chose the interval of the filter guard The unit is factory configured to provide emergency with 90 days interval It is then possible to change this range if necessary After the deadline you will see Filter
10. programmes The unit will continue in AUTO mode without any week programme SELECT CLEAR SELECT PROG 3 SELECT PROG 2 SELECT PROG 1 SELECT OFF SELECT PROG 1 Here it is possible to make your own programme or adjust one of the standard programmes If there is more than one function at the same time only the last one is active OFF replaces 24 00 D one day to another It is possible to copy the values E Figure 14 The Week program menu May be subject to change page 17 af 26 A R N d OUTSTANDING INDOOR CLIMATE Heating surface The menu HEATING SURFACE is only accesssible when the system has a heating surface in stalled and when the control has been set up to a heating surface in the SERVICE MENU Options that flash are indicated by On the CTS600 control panel press ESC to return to the previous menu WA to scroll upwards or downwards through the menus or to adjust the setting of an activated menu option ENTER to activate a menu option ENTER to confirm a new menu option setting OFF to switch off the controls ON to switch on the controls When a heating surface is installed T2 is replaced with T7 which is the sensor placed in the inlet at the heating surface SELECT ENTER ON SELECT OFF ENTER ENTER SELECT OFF If you wish to disconnect the heating surface this position should be chosen The fro
11. User manual CTS 602 by Nilan NILAN oo outstanding Combi 300 Polar Version 10 00 13 04 2015 Software version 2 30 R OUTSTANDING INDOOR CLIMATE 4 R N p OUTSTANDING INDOOR CLIMATE Table of contents UMTS Of COMEM mc a a a ged dette ae ceaes 2 Figure table ee eee eer meee ie EA Ai et reer es 2 Intro dUCHON arena Em 3 Review of the thermometer Sensors Mr ee 4 CTS 602 panel M a a E A 5 How 10 use the Men TOTUM Tr 5 PGT overview P n 6 Operating mode mE T Errem 7 VU Ug ag 21 0 Peter er TTE 8 Show ala cec arc Tm 9 ufq 12 Bc debe HP M 13 4 01 poe 14 SWING OFC oe PEPERIT 15 Week programme s ee rere ree ter ee nee Pier oy reer cere errr DoD EL ASI EPI MUCH 16 Heating ea Ud e er rc 18 Sn e C 19 PMN M5 eae eios Se oie etes ote sse tc sul LL LE Mt 20 Air BRC NANOS m 21 mide te 22 BL Sag Rg go ee eee rcc T TT 23 Setting Ol language sco mese etica dia peso ep aep tima tab ERO FINERE bM eR Ie AD Urn Dina NA DEN MR Mina DE 24 Filter CHANGE me T NAERAN 25 Condensation drain and water trap seeesssssssssssssssseeee eene 25 Accessories spare DANS u
12. as an information alert indicates that the menu point flashes and can be set to another value Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on ALARM 360 DAYS ALARM 180 DAYS ALARM 90 DAYS ALARM 30 DAYS ENTER ENTER AIR ALARM FILTER 90 DAYS Figure 19 The Air filter menu May be subject to change page 22 af 26 4 B N OUTSTANDING INDOOR CLIMATE i Temp control In the Temp control menu it is possible to set the highest and lowest inlet temperature indicates that the menu point flashes and can be set to another value Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on lower than indicated the bypass valve owest inlet temperature in the summer If the outside temperature is will close ENTER SUMMER MIN 14 C TEMP CONTROL owest inlet temperature in the winter _ M the outside temperature is lower than indicated the bypass valve will close WINTER MIN 16
13. giver mulighed for slukke anl gget via ekstern kontaktfunktion Deo s ttes ud Y af funktion nsket rumtemperatur 5 30 C Panelfaler T15 er styrende f ler Figure 10 The User select menu May be subject to change page 13 af 26 User select 2 User select 2 as user select R N d OUTSTANDING INDOOR CLIMATE RE7 slutte kontakt for styring af emh tte spj ldmotor VALG T er EMH ETTE Mulighed for for at Mulighed for relaeudgang R8 s fremt denne udgang VALG ENTER er monteret Dette er kun muligt p tilleegsprint Temperaturen l gges til eller tr kkes fra setpunktet VALG ENTER k re h jere eller lavere hastighed H j prioritet VENTILAT Der v lges efterl bstid og EKS OFFS forskydning af BRUGER ENTER VALG ENTER VALG 2 FORLAENG f XFORL ENG valgte driftsfunktion skal 00 00 00 00 INE EAS J Der skal v lges tid 0g HAST ENTER HAST VALG hastighed pa samme 4 lt gt 4 lt FORL ENG m de som vist under C vare angivet i timer og minutter Max 8 timer nsket ventilationstrin 1 4 OFF giver mulighed for slukke anl gget via ekstern kontaktfunktion May be subject to change setpunkt for ekstern rumvarme V lges p samme m de som vist under VALG VALG ENTER UDSUG VALG FORLAENG 5 TEMP ENTER TEMP VALG EN rs 3 ERP SO OFF vBrugervalg s ttes ud af funktion
14. iew of thermometer sen sors at page 5 SHOW ENTER STATUS DATA HEAT BYPASS OPEN Anode condition ANODE OK ERROR or SERVICE OK z PANEL T T15 20 C EXTERNAT Temperature sensor T10 19 C T10 y HUMIDITY 37 CO2 492ppm INLET E T2 22 C FRESHAIR T1 9C OUTL EXH T4 5 C See sensor overview WATER T on figure 2 T11 50 C page 5 WATER B T12 40 C COND T5 40 C These sensors are only shown if they are installed Softwareversion in the unit EXHAUST FLOW 2 SOFTWARE 1 2 1 Softwareversion in the controlpanel SOFTWARE 2 1 01 TYPE VP18 Com Figure 9 The Show data menu May be subject to change page 12 af 26 A R N d OUTSTANDING INDOOR CLIMATE User select The menu CUSTOM OPTIONS overrides the operating mode of the main menu by activating an external switch VENTILAT There is a possibility here to run with a higher or lower speed on the air exhaust and air inlet for a limited amount of time The external pressure will activate the function The function has high priority exhaust and inlet These two options increase or reduce the velocity of the exhaust or inlet air respectively for a limited period of time The remaining functions of the operating mode remain unaltered An external switch activates the timer function Another external switch ensures that the fans remain at the desired ventilation level until the switch is t
15. inlet extend and OFF USER SELECT 2 User select 2 as user select 10 09 13 TM 12 10 PROGRAM Setting of clock 10 09 13 TM 12 10 Activating the week programme Setting of inlet temperature for cooling via bypassing the inlet air around the heat exchanger and via compressor if this is an option not possible on all types of units Offers the option to set a higher lower fan speed at a high low humidity level HUMIDITY Starts the compressor and enable you to choose a low fan speed when the outdoor air temperature is low AIR EXCHANGE AIR In the Air filter menu it is possible to chose the interval of FILTER the filter guard TEMP Setting of minimum inlet temperatures CONTROL Choose language shown in control panel LANGUAGE LANGUAGE ENGLISH ENGLISH Figure 4 Menu overview May be subject to change page 6 af 26 Am R N p OUTSTANDING INDOOR CLIMATE Operating mode The main menu shows 3 different values operating mode ventilation step and temperature Those values indicate the state of the unit and are selected by the user The main menu is automatically shown 15 seconds after the unit is electrically connected and is now ready to be set SELECT menu is active 1 2 3 week prog
16. oiscupi eov da us pud dps R ERE ua Ki Spur idu ufu i Gira el tds id 26 Figure table Fig re 2 Thermometer Sensors RR m 4 FUGUI 3 CTS OOZ DearS 5 Figure A Mend Overview acce 6 Figure ye Main VS MN res ad drew sc ed dso eee dad eae wea eee ceded ees 7 Figure 6 Headlines in the Main menu scccciccscceciccsrcasicesteesieercesinesteesixesreisinesreesneeresbieesteestxesreneexess 8 Figure 7 The Show alarms Telit ted nete docte RENE ENE Emi pui inxta disi ixl tI cM Ede 9 Figure 8 The Alarm Indicators Menu uuceccece secet tette peu kk kk ER Lei Ek pine ER ERNE RENE NERE E FER PIRE I pES ERES 11 Figure 9 The Show data mirilsuiie mo treten e nueve cena eri Ex tici err ne Kx Ra D Rae 12 Figure T0 The User select TWePIU siii doo prie r Pro Eier E oro ver kde ae 13 Figure 11 The User select 2 MENU uui ete ee eta ee viia ER eR nakana kiia ERE Rr pa nnd 14 Figure 12 Setting Of ClO em H 15 Figure 13 The Settings of Week program ssssssssssseseeseeeeennneem eene nnne nennen 16 Figure 14 The Week program Menu sienne npe eren Fam Rn kae Rma eg nna Fera E ep RR NREN REE ERE RR ER RER E EEN 17 Figure 15 The Heating surface Menu essei peer ret teta te tk ERE ERE beato REE ERE etta te erbe D Hbro E REE EN 18 Figure 16a The Cooling Menu E M 19 Figura 16b The Cooling MGM sicdcsisccconcbstecsceniaues ke iee casa E Ea ENE EE
17. or figure 2 T1 is the thermometer sensor for the fresh air and should be placed at the north side of the building T2 isthe thermometer sensor for the inlet air without heating surface T5 shows the temperature of the condenser T6 shows the temperature of the evaporator T7 is the thermometer sensor for the inlet air after a heating surface T10 isthe thermometer sensor for the exhaust air in a room accessory T15 isthe thermometer sensor in the CTS 602 panel The temperature of the sensors can be read in the Show data menu May be subject to change page 4 af 26 R N OUTSTANDING INDOOR CLIMATE CTS 602 panel Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on Figure 3 CTS 602 panel The following is indicated by the light emitting diode at the front of the CTS 602 panel Constant yellow light the compressor is in operation Flashing yellow the unit is in alarm condition The panel can show 2 lines of text with each 8 characters The upper line shows a guiding text The bottom line shows the matching values to the guiding text The text in the display in on as long as there is power to the unit and will not turn off even though the unit is set to off or has not been ope
18. ramme REN CRRA CES i j is active Operating modal OF W electrical heating Pon element is active HEAT L low ventilation NF x step at low outdoor temperature j AUTO CES PRAE v gt 2 lt 19 C x Desired roomtemperature 5 30 C Figure 5 Main menu Desired room temperature can be adjusted by pressing ENTER once The number at C flashes and the value can be set via A V The desired value must be approved by pressing ENTER once The operating mode can be adjusted by pressing ENTER twice The actual mode is flashing and can be set via A V and approved by pressing ENTER once In AUTO mode the bypass draught control is automatically opened or closed according to the temperature setting and the unit auto matically switches between cooling and heating As regards cooling there is a neutral zone of 5 C below room temperature before the unit actively cools via compressor For further information see page 20 The ventilation step can be adjusted by pressing ENTER three times The actual ventilation step is flashing and can be set via A V and approved by pressing ENTER once May be subject to change page 7 af 26 A R N Dp OUTSTANDING INDOOR CLIMATE Main menu The main menu is automatically shown 15 seconds after the unit is electrically connected indicates that the menu point flashes and can be set to another value Use of the CTS602 panel press ESC to go one step back in the menu
19. rated for a longer period of time How to use the menu It is possible to adjust a value or a function by finding the matching menu via A or V To activate the desired menu press ENTER To adjust the settings of the value press ENTER until the value flashes The adjustment can now be done viaA V To save the chosen value press ENTER It is advisable to have the panel and or the review of the menus near by during the reading of the menus If none of the press buttons are activated for one minute the control will automatically return to the main menu If you are in the middle of the programming when the control returns to the main menu all data will be saved if they previously are saved by pressing ENTER It is always possible to return to the programming to continue May be subject to change page 5 af 26 Am R N Dp OUTSTANDING INDOOR CLIMATE Menu overview The control will have the main menu as starting point the menu in the full drawn frame From here it is possible to go through the other menus via A V Submenu SHOW ALARMS Mainmenu SHOW ALARMS Showing of alarms and resetting of alarms Alarm log with the latest 16 alarms Operating mode heat auto cool temperatures fan speed and software version Main menu shows operating mode Press ESC to main menu AUTO W 1 gt 2 lt 19 C USER SELECT AUTO W 1 gt 2 lt 19 C yon d There are five custom options ext offs exhaust
20. rmostat If there has not been a fire Unit is stopped because the fire please contact service detecting thermostat has been activated 04 C PRESSURE High or low pressure switch in the Check for errors and reset cooling circuit has been triggered alarms probably caused by If you are unable to reset High pressure the alarm or if the alarm Extreme hot occurs often please contact Cloaked filter service Defective fan Low pressure Extreme cold Unit might have lost coolant Cloaked filter Defective fan 06 C DEFROST The unit is defrosting Contact service if reset The frost protection of the heat does not help Note the recovery system is insufficient actual sensor temperatures and the unit will stop This can be from the menu Show data caused by extreme low outdoor to help service temperatures 08 C FROST One of the temperature sensors in Note the sensor and con the unit is short circuit or defect tact service 09 C OVERTEMP One of the temperature sensors in Note the sensor and con the unit is disconnected or defect tact service 10 C OVERHEAT The electrical heating element is Check if air flows into the overheated Lack of airflow due to house cloaked filters cloaked air intake Check filter and air intake or defect inlet fan Reset alarm Contact service if the above does not help 11 C AIRFLOW Lacking inlet airflow See alarm code 10 13 C BOILING Boiling protection of the hot water Contact service 15
21. rms can be reset ALARM 0 indicates that all alarms are reset CST OF ALARMS Shows from 0 3 active alarms The newest and most a i i i i i i i i i i i i i 1 1 AL 2 STATUS ALARMLOG j PRESSURE ALARM vr The log is recovere after power cut and shows the 16 most recent alarms AL 1 is the newest AL 3 T1 20 C BOILING T2 20 C T3 0 00 AT4 0 00 ALARMLOGDATA Snapshots from the time of the alarm OUT 1 8 00000000 OUT 9 16 00000000 OUT 17 24 00000000 Figure 7 The Show alarms menu May be subject to change page 9 af 26 4 R N d OUTSTANDING INDOOR CLIMATE Alarm codes are given because of a fault situation or when it is important to inform the user The alarms are divided into the following categories C Critical Operation is partly or completely stopped as long as the alarm is active W Warning These types of alarms will become critical if the problem is not solved quickly Informative Normal operation is not affected Alarm disappears when it is reset Alarm Text in code Categori display Description cause How to remedy alarms 00 No alarms 01 C HARDWARE Error in control hardware Contact service if reset does not help 02 C TIMEOUT Warning alarm W has become a Note and reset the alarm critical alarm Contact service if alarm does not disappear 03 C FIRE Fire detecting the
22. ss ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on Programmes Weekday Function Time Ventilation step Temperature Programme 1 Monday 1 6 00 3 21 Friday 2 8 00 1 17 3 15 00 3 21 4 22 00 1 17 Saturday 1 8 00 3 21 Sunday 2 23 00 1 17 Programme 2 Monday 1 8 00 3 21 Sunday 2 23 00 1 17 Programme 3 Monday 1 7 00 3 21 Friday 2 16 00 OFF 21 Weekly program settings Program step 6 program steps are Week 1 day sen a i Time of program step activation j If a program step should not be used OFF should be chosen i MO 1 08 i iet fee OFF is located instead of 24 00 F an speed N 7 Required room temperature Figure 13 The Settings of Week program May be subject to change page 16 af 26 Here it is possible to chose one of the 3 standard programmes The 3 programmes can be altered but not deleted The original programme can always be found WEEK SELECT PROGRAM OFF The Unit operaters under the main menu r ENTER ENTER MO1 06 00 23 21 C MO2 08 00 gt 1 lt 177T MO3 OFF gt 1 lt 17 C Am R N Dp OUTSTANDING INDOOR CLIMATE Here it is possible to delete all user made
23. st protection is still active and T7 is the active temperature sensor for the inlet air HEATING SURFACE Figure 15 The Heating surface menu May be subject to change page 18 af 26 A R N d OUTSTANDING INDOOR CLIMATE Cooling In the Cooling menu it is possible to cool the inlet air by bypassing the inlet air around the counter flow heat exchanger See figure 16a If the unit has active cooling via compressor see figure 16b The COOLING menu gives the possibility of automatic high fan speed when high outside tempera tures indicates that the menu point flashes and can be set to another value Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on ENTER VENTILAT ENTER VENTILAT COOLING HE ER ME Here it is possible to chose high ventilation step when cooling The value can be set to OFF 2 3 4 Figure 16a The Cooling menu SET 34 The value can be set to OFF 1 2 43 45 7 410 It is recommended that the VENTILAT value is set to 3 Here it is possible to chose high ventilation step when cooling The value can be set to OFF 2 3 4 ENTER VENTILAT HIGH OFF Figure 16b The Cooling menu May be subject to change page
24. urned off extend This option controls the velocity of the exhaust and inlet air and can be used to change the temperature of the inlet air for a limited period of time An external switch activates the timer function OFF Deactivates the external switch ext offs Provides the possibility of choosing an afterflow time and changing the set point in exter nal rooms Use of the CTS602 panel press ESC to go one step back in the menu press W Ato move up or down in a menu or to adjust an activated menu press ENTER to activate a menu press ENTER to confirm a menu press OFF to turn off the unit press ON to turn the unit on ES RE1 slutte kontakt 1 styring af emh tte VALG EMH TTE spj ldmotor Mulighed for for at k re h jere eller lavere hastighed H j prioritet Der v lges efterl bstid og forskydning af setpunkt for ekstern rumvarme V lges p samme m de som vist under VALG NFORL ENG Mulighed for relaeudgang R8 s fremt denne udgang er monteret Dette er kun muligt p tilleegsprint Temperaturen l gges til eller tr kkes fra setpunktet VALG FORL NG BRUGER ENTER VALG nsket tidsrum som de valgte driftsfunktion skal vare angivet i timer og minutter Max 8 timer YDer skal v lges tid og hastighed p samme m de som vist under VALG FORL ENG P nsket ventilationstrin 1 4 OFF

Download Pdf Manuals

image

Related Search

Related Contents

Erste Inbetriebnahme KX-NCP1000  取扱説明書  "取扱説明書"  Viking F20288 User's Manual  Garland 36E User's Manual  BENDIX TCH-002-001 User's Manual  Pioneer HTZ232DVD User's Manual  CATALOGO 2015  Operating Instructions    

Copyright © All rights reserved.
Failed to retrieve file