Home
TAEevo015÷351 - Chiller Hire
Contents
1. Process water inlet a Process water outlet When filling the circuit with liquid check to ensure the absence of air bubbles and l PLUG contaminants If the pump runs noisily or emits anomalous noise it may be necessary to a bleed the liquid circuit in order to prime the pump The procedure is as follows unscrew the filler breather plug at the top of the pump e fill the hydraulic circuit until water starts to overflow from the filled hole e refit the plug and tighten it Repeat the operation if the pump continues to run noisily in such a way as to eliminate any air that had previously remained trapped in the impeller vanes In the event of double pump keep particular attention during priming the pump It is necessary to verify first the pump positioned on the top 5 5 Expansion tank If the hydraulic circuit is of closed type it is necessary to install an expansion tank The expansion tank must always be connected at pump inlet To calculate the minimum volume of the expansion tank required for a given installation the formula below cab be used and is valid if the pressure is less than or equal to 0 5 bar when the pump is stopped and the maximum working pressure of the expansion tank is greater than or equal to 4 bar The volume of the expansion tank V in litres is given by the formula V 2 Vt Ptmin
2. TAEevo 051 161 TAEevo 201 351 TAEevo 201 351 TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 9 Operation and maintenance 34 9 4 Emptying the process water circuit Use the cock installed on the unit lower side if the storage tank need to be emptied for maintenance purposes in models fitted with a hydraulic unit ATTENTION The water circuit must be emptied when a unit that has no heating elements or anti freeze liquid is to be left inactive for a certain period of time in an environment where the temperature may fall low enough to freeze the water in the evaporator with the risk of breaking the evaporator 9 5 Maintenance schedule E OPERATION gt 5 x 3 S oe Check for any alarm signals x Check that the water outlet temperature is within the envisaged range x Check that the water inlet temperature is in accordance with the value used for selecting the unit x In units with hydraulic group check that the pressure in the tank with pump stopped if present is at least x 0 5 bar with the circuit closed In units with hydraulic group check that the difference between the discharge and the suction pressure of the pump measured on the manometer with the pump stopped is within exp
3. Water outlet temperature up to Ethylene Glycol C F in weight 5 41 0 0 32 19 5 23 27 10 14 34 15 5 39 20 4 44 Table 7 ADDITION OF ETHYLENE GLYCOL ACCORDING TO THE WATER OUTLET TEMPERATURE ATTENTION Carry out the level sensor calibration when the unit is activated the first time Repeat the operation each time the composition of the process liquid changes TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 18 MAINTENANCE AND OPERATING MANUAL Chapter 5 Installation 5 3 1 Operating limits The operating limits are decided at the time of sale Refer to the contract data Minimum Maximum ambient air temperature C JeF 5 23 43 109 4 Standard version ambient ils C JeF 20 4 43 109 4 evaporator inlet water oC JeF 5 23 35 95 temperature evaporator outlet water oC JeF 10 14 30 86 temperature With outlet water to a temperature of 15 C Not present in models with 460 3 60 supply With unit equipped with condensing pressure control For temperatures below 5 C 41 F use antifreeze solutions 5 4 Hydraulic connections NOTE All hydraulic connections must be carried out by the customer 1 Connect the unit to the water pipelines respecting the water flow direction as indicated in the annexed over
4. No reactivity if used with the relative instructions Materials to avoid Alkaline metal earthy alkaline metals granulated metals salts Al Zn Be etc in powder Hazardous decomposition products Halogen acids traces of carbonyl halides TOXICOLOGICAL INFORMATION Acute toxicity R32 LC50 inhalation 4 hours lab rats gt 760 ml 1 R125 LC50 inhalation 4 hours lab rats gt 3480 mg l R134a ALC inhalation 4 hours lab rats 567 ml l Local effects Concentrations substantially above the TLV can cause narcotic effects Inhalation of products in decomposition can lead to respiratory difficulty pulmonary oedema Long term toxicity Has not shown any cancerogenic teratogenic or mutagenic effects in experiments on animals ECOLOGICAL INFORMATION Global warming potential HGWP R11 1 Ozone depletion potential ODP R11 1 R125 0 84 R134a 0 28 0 CONSIDERATIONS ON DISPOSAL Usable with reconditioning TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 9 Chapter 3 Technical data CHAPTER 3 oo O TECHNICAL DATA The main technical data are given on the machine data plate MODEL and CODE They identify the size of the unit and the type of construction MANUAL This is the code number of the manual SERIAL NUMBER This is the construction
5. Ptmax where Vt total volume of the circuit in litres Ptmin specific weight at the minimum temperature obtainable by water over the year in C even with the plant stopped Ptmax specific weight at the maximum temperature obtainable by water over the year in C even with the plant stopped Example of calculation Vt 200 litres percentage of ethylene glycol in volume 30 tmin 5 C from the table Ptmin 1 045 1 041 2 1 043 tmax 40 C from the table Ptmax 1 0282 V 2 200 1 043 1 0282 5 92 litres Table of specific weights P Glycol 0 10 20 30 40 20 4 1 0036 1 0195 1 0353 1 0511 1 0669 o 10 14 1 0024 1 0177 1 033 1 0483 1 0635 z 0 32 1 0008 1 0155 1 0303 1 045 1 0598 5 10 50 0 9988 1 013 1 0272 1 0414 1 0556 z 20 68 0 9964 1 0101 1 0237 1 0374 1 051 30 86 0 9936 1 0067 1 0199 1 033 1 0461 40 104 0 9905 1 003 1 0156 1 0282 1 0408 Table 8 SPECIFIC WEIGHTS TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 20 MAINTENANCE AND OPERATING MANUAL Chapter 5 Installation 5 6 Electrical connections The connection of the unit to the power supply network must be done in conformity with the laws and prescriptions in force in the installation place The power supply voltage the frequency and the phase number must be as shown on the unit data plate The powe
6. Technical data The values in the table may vary in relation to the model and configuration of the unit In this case reference should be made to the data in the offer NOTE The head is the head available to the user It is possible for the pump installed to be different from the standard There are two numbers for the flow rate and pressure the first number refers to the nominal conditions while the second to the maximum conditions 3 1 3 Sound Level Measurements Fan Lp dB A Lw dB A TAEevo 015 axial 67 4 80 4 TAEevo 020 axial 67 4 80 4 axial 68 1 81 1 TAEevo 031 centrifugal 73 8 86 8 AA axial 68 1 81 1 TAEevo 051 centrifugal 73 8 86 8 A axial 68 6 81 6 TAEevo 081 centrifugal 76 2 89 2 axial 69 1 82 1 TAEevo 101 centrifugal 76 2 89 2 axial 69 1 82 1 TAEevo 121 centrifugal 76 2 89 2 axial 70 0 83 TAEevo 161 centrifugal 76 2 89 2 axial 71 3 84 3 TAEevo 201 centrifugal 78 1 91 1 axial 71 3 84 3 TAEevo 251 centrifugal 78 1 91 1 axial 73 0 86 TAEevo 301 centrifugal 78 1 91 1 axial 73 0 86 TAEevo 351 centrifugal 78 1 91 1 at distance of 1 metre 3 2 FT global NOT present with 460 3 60 Hz supply Test conditions Noise levels refer to operation of the unit at full load in nominal conditions Sound pressure level in hemispherical irradiation con
7. ALoG 3 Upload the parameters from the unit to the key 4 Display the operating hours of the controlled loads Reset the operating hours of the controlled loads 7 12 1 Access to Function menu Press and release M button menu The icon Menu will appear 7 12 2 Exit Function menu Press and release M button or wait for time out 30 seconds The icon Menu disappears 7 12 3 How to display the alarms ALrM 1 Press to enter Function menu 2 Press or to select ALrM function 3 Press and release button 4 Press or to scroll all alarms 5 To exit press M or wait for time out 30 seconds 7 12 4 How to reset an alarm rSt 1 Press to enter Function menu Select ALrM function Press SET in the bottom of the display it appears the alarm code Use or button to scroll all the alarms 2 3 4 Ifthe alarm can be reset in the top of the display it appears the Label rSt it the alarm can not be reset it appears the Label NO 5 6 When the Label rSt is displayed press to reset the alarm and go to the following one 7 To exit press M button or wait for time out 30 seconds 7 12 5 How to display the alarm historic ALoG 1 Press button to enter Function menu 2 Use A or button to select the function ALoG SET will appear in the top of the display 4 Using or button scroll all the alarms 3 Press until the Label with the ala
8. 1 1 Display icons ICON MEANING ICON MEANING Celsius degrees If displayed Low pressure alarm C Fahrenheit degrees If not displayed Antifreeze resistance a a Bar Psi Pump on Compressor 1 Flow Flow meter alarm Stand by unit Fans on bar 1 BD compressor 2 CD Time to defrost starting a h A General alarm Menu Indication for Function Menu entering High pressure alarm 7 2 Function of buttons BUTTON FUNCTION It selects water temperature and ambient air temperatures in the top part of the display During programming phase it scrolls the parameter s codes or increases their values If pressed for 5 seconds it allows to switch on or off the unit in chiller modality It selects water temperature in the top part of the display During programming phase it scrolls the parameter s codes or decreases their values SET If pressed for 5 seconds it allows to display or modify the set point During programming phase it selects a parameter of confirms a value It allows to enter Function Menu TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 7 Electronic Board 24 7 2 1 Function of combined buttons BUTTONS FUNCTION To enter programming phase pressed for 5 sec To exit progra
9. 1 8 21 1 2 6 21 1 4 4 57 2 5 7 57 2 ump head 5 4 2 9 5 4 2 9 5 4 3 1 5 3 3 2 5 2 2 8 5 1 3 1 PUMP P5 ie 79 4 42 1 79 4 42 1 78 9 45 4 78 3 46 6 f 75 8 40 6 75 7 45 8 water flow rate nominal power nominal power number of fans AXIAL FANS total air flow 4050 3500 6900 6400 9200 50 60 Hz 17831 15410 30380 28178 40506 number of fans CENTRIFUGAL FANS available head NOT present with 460 3 60 Hz supply total air flow Model Trae 3 0 18 4 9 27 5 5 27 ee Owe 7 0 79 3 8 4 79 3 8 8 79 3 8 8 79 3 9 11 0 118 9 11 4 118 9 2 8 1 6 2 8 1 7 2 8 2 0 2 8 2 0 3 3 0 9 3 2 0 8 pump head PUMP P3 41 5 24 2 41 4 25 1 41 4 29 8 41 4 29 8 48 8 13 3 48 7 12 3 nominal power 1 85 1 85 1 85 1 85 2 2 2 2 1 85 1 85 1 85 3 0 13 3 7 13 3 9 30 4 4 30 4 9 30 5 5 30 7 0 57 2 8 4 57 2 8 8 132 1 8 8 132 1 f 11 0 132 1 f 11 4 132 1 5 1 3 1 5 0 3 2 5 2 1 8 5 1 1 8 5 1 1 9 5 1 1 8 water flow rate PUMP P5 p mp head 75 6 45 8 f 75 4 47 1 76 5 27 1 76 5 27 1 67 2 27 3 76 1 26 1 nominal power 4 4 number of fans AXIAL FANS total air flow 15000 23700 23700 50 60 Hz 66043 104347 104347 CENTRIFUGAL FANS NOT present with 460 3 60 Hz supply Table 5 CHARACTERISTICS OF STANDARD UNITS TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved NOTE MAINTENANCE AND OPERATING MANUAL 11 Chapter 3
10. and more generally all critical points open joints in order to prevent possible leakage of refrigerant gas 2 7 Refrigerant gases R407C is used as refrigerant in these units Never attempt to mix refrigerant gases The manufacturer s instructions and local safety regulations should always be observed when handling and storing high pressure gas cylinders 2 7 1 Refrigerant safety schedule R407C Denomination 23 Difluoromethane R32 25 Pentafluoroethane R125 52 R134a INDICATION OF THE DANGERS Major dangers Asphyxia Specific dangers Rapid evaporation can cause freezing FIRST AID MEASURES General information Do not give anything to unconscious persons Inhalation Take the person outdoors Use oxygen or artificial respiration if necessary Do not administer adrenaline or similar substances Contact with the eyes Thoroughly wash with plenty of water for at least 15 minutes and call a doctor Contact with the skin Wash immediately with plenty of water Remove contaminated clothing immediately FIRE FIGHTING MEASURES Means of extinction Any means Specific dangers Pressure increase Specific methods Cool the containers with water sprays MEASURES IN THE EVENT OF ACCIDENTAL LEAKAGE Individual precautions Evacuate personnel to safe areas Provide adequate ventilation Use means of personal protection Environmental pr
11. caccudie a adnidexoeueatavetsunacaxesqeiaceseiuadecesehtaxauaeelecasaaaaaes epee idee oaceler 23 7 2 1 Function of combined buttons ccccccccceccccesceseeseeseeseesceseseeneceeeseeessecseeseesenecesensseesaeeneeecneenecieeseeeeeseenneentes 24 7 3 Symbols and leds on the display svesiccsocrnecesaennceeapaseecsersaaisosaeatneea neice 24 TA Remote terminal a cstvsccspvncetscsastencdswinesuestensesssaerinessadeunsdueiardeeusceendswantoad NEEE ES E REE 24 TAA F nchom OF buttons crisser ina i E EEEE EE T RER ae ha nb E E eh 24 TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 2 MAINTENANCE AND OPERATING MANUAL Index 7 5 Displaying during an alarm ss vevacsveassnccnssannecs uneven vunceoacensevmnassuutvavannannncerneteeensrenannentancensamrbianears 24 TDA Alarm ICONS so esicen fet eah uaedeng date Does eas a NEEE EEEN EEE aa Ei Eiaa de EEE KESEN OE EEEE EEEE iE 25 T6 Howto sile ice the UZ ZL ses scsesesrsn sanre oirein sai sraide r e eea EKE EETA AEs rai 25 TA First statt Us siaaciavecaicesshexnaeameveahsaccananpbanspbantocaunds E E EE E EEEE 25 Tos Programming DY Keyboard oyccduewesccinctuptdsaiases dia iswanszcatenesaeasaacel euesanedarapeaeeheduishontenoesnaaensver 25 7 8 1 Access to Pri parameters User level ccccccccsccsccssessessesseseesessesseescesecceceecueeecnessesseesesseceeaserceseneeeeeas 25 7 8 2 How to modify a parameter s V
12. number of the unit MANUFACTURING YEAR This is the year of the final test of the unit VOLTAGE PHASE FREQUENCY Electric alimentation characteristics MAX CONSUMPTION I max This is electrical current consumed by the unit during the limit working conditions INSTALLED POWER P max It is the power absorbed by the unit during the limit working conditions PROTECTION As defined by the EN 60529 European standard REFRIGERANT This is the refrigerant fluid in the unit REFRIGERANT QUANTITY This is the quantity of refrigerant fluid contained in the unit MAX COOLING PRESSURE This is the design pressure of the refrigeration circuit MAX COOLING TEMPERATURE This is the design temperature of the refrigeration circuit MAX COOLING PRESSURE HP SIDE This is the design pressure of the refrigeration circuit of the high pressure side MAX COOLING PRESSURE LP SIDE This is the design pressure of the refrigeration circuit of the low pressure side USER CIRCUIT FLUID Fluid used by the unit normally water MAX UTILIZATION PRESSURE Max designed pressure of the utilization circuit MAX TEMPERATURE Design temperature of the user circuit this should not be confused with the maximum working temperature which is established when the offer is made CONDENSER COOLING FLUID Fluid the machine uses to cool the condenser MAX WORKING PRESSURE Maximum design pressure of the condenser cooling circuit MAX TEMPERATURE Maximum designed temperature of the cooling cir
13. present in models with 460 3 60 supply Can be installed exclusively on models higher than TAEevo031 These are double drive fans with the fanwheel coupled directly to the motor shaft and they feature ON OFF control The delivery port is located on the top of the unit The delivery direction can be modified on models TAEevo201 351 4 9 Casing The base uprights and panels are made of galvanized carbon steel and held together by screws and or rivets All panels undergo a phosphor degreasing process followed by epoxy polyester powder coating The frame is designed to allow easy access to all machine components TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 15 Chapter 4 Description 4 10 Materials in contact with the liquid to be cooled There can be two different groups Standard refrigerators carbon steel copper aluminium zinc brass stainless steel and plastics in particular evaporator with copper tubes aluminium fins and shoulders in galvanised steel e tank in carbon steel Refrigerators with non ferrous water circuit stainless steel AISI 304 copper brass and plastics in particular evaporator with tubes and fins in copper and brass shoulders e tank in AISI 304 stainless steel alternatively e external plate evaporator prismatic atmospheric tank The pump mechanical seals are made of cerami
14. process water circuit Use the electrical diagram accompanying this manual to for the connection to the power grid 2 5 Precautions during operation Operation must be carried out by competent personnel under a qualified supervisor All the water piping must be painted or clearly marked in accordance with local safety regulations in the place of installation ATTENTION Never remove or tamper with the safety devices guards or insulation materials fitted to the unit or auxiliary equipment All electrical connections must comply with local codes The unit and auxiliary equipment must be earthen and protected by fuses against short circuits and overloading When mains power is switched on lethal voltages are present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the electrical system Do not open any electrical panels or cabinets or touch any electrical components or associated equipment while voltage is applied unless it is necessary for measurements tests or adjustments Such work should be carried out only by a qualified electrician equipped with the proper tools and wearing appropriate body protection against electrical hazards 2 6 Maintenance and repair precautions ATTENTION When disposing of parts and waste material of any kind make sure that there is no pollution of any drain or natural water course and that no burning of waste takes place which could cause polluti
15. the control board the problem contact the nearest components display and all LEDs service centre remain unlit H H1 H1 1 Check that the temperature Alarm displayed Probe BEWOT BTWOT e See problem probe is correctly connected to P1 P2 P3 P4 BAT1 damaged inal lay tipped the control board terminals e main alarm relay tripped and that the cable is undamaged If necessary replace the probe I I1 I1 1 Identify and remove the cause Alarm displayed Low water outlet e See problem which provoked BTWOT temperature decreasing to a value lower than Ar03 A04 temperature The value fixed by the e the compressor stops and parameter is lower than restarts the one measured by the e main alarm relay tripped probe e the led of general alarm icon lights up I2 I2 1 Increase the water flow Too low water flow e See problem e the compressor stops and restarts e main alarm relay tripped J Ji J1 1 Reset the thermal protection Alarm displayed The pump s thermal e See problem device f A08 protection device has amain alamn relay tripped Increase the pressure drop in pump thermal protection tripped because the water j y tripped the hydraulic circuit for flow is too high e the refrigerant compressor example by partially closing and pump stop the pump output valve e the indication A08 appears on the display alternated to BTWOT value e the pressure difference read on the machine gauge with the pump stopped a
16. the pressure transducer will measure a decreasing of the condensing pressure This pressure decreasing is sent to the speed regulator which will reduce the fan speed and consequently the condenser air flow will be reduced Analogously when the air temperature to the condenser and the condensing pressure increase the regulator will increase continuously the fan speed to increase the air flow through the condenser The following graphic shows the progress of the fan rotation speed according to the condensing pressure changings of rotation speed Vmax Vmin _ 0 0 P min P max ai condensing pressure bar g TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 31 Chapter 8 Other components setting 8 5 Level sensor ATTENTION Take all the necessary precautionary measures to avoid accidental contact with powered elements The voltage values inside the electric panel can be lethal for humans The manufacturer is responsible for level sensor calibration and therefore further modifications are not necessary Key 1 is sealed to prevent tampering by the user The level sensor indicates the absence of process water inside the tank An alarm with relative blocking of the unit appears on the control display Level sensor calibration to be performed only on instruction by the MTA Service Ce
17. three phases e main alarm relay tripped Follow the alarm reset supply procedure to star up the unit again chapter Electronic Board c3 C3 1 Invert the water inlet outlet Water inlet outlet inverted e see C1 1 Follow the alarm reset units without hydraulic i procedure to star up the unit kit e main alarm relay tripped again chapter Electronic Board TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 36 MAINTENANCE AND OPERATING MANUAL Chapter 10 Trouble shooting PROBLEM CAUSE SYMPTOM REMEDY D D1 D1 1 Repair or replace the fan High pressure switch The fan doesn t work e Refrigerant compressor Verify the eventual heat tripped HP stops protection of the fan s he i di ian ROH Follow the alarm reset Alarm displayed Sme h ra P ito procedure to star up the unit A01 on the display alternated to again chapter Electronic BTWOT value Board e main alarm relay tripped Check the fan speed regulation system e the led of icon H lights up D2 D2 1 In the event of installation in a Ambient air temperature e Air ambient temperature _ Closed place reduce the too high higher than maximum ambient temperature to within permitted value design limits for example by increasing local ventilation e see D1 1 Follow the alarm reset procedure to star u
18. 4 at the beginning of the electrical supply cable must be installed protection devices that protect against overcurrents short circuit see information in the electrical wiring 5 use conductors which transform the max current required to the max operating ambient temperature according to the selected installation type IEC 364 5 523 see information in the electrical wiring 6 protection devices must be installed to limit the short circuit current to peaks of 17 kA corresponding to the specified interruption power if the short circuit current envisaged at the point of installation is greater than an effective value of 10 kA Indications of electrical wiring A max size permitted for the fuse type gG In general the fuses can be replaced with an automatic switch regulated by means of the unit max absorbed current contact the manufacturer if necessary B section and type of the power supply cable if not already supplied installation insulated conductors multipolar cable in duct in air or over masonry C type in compliance with IEC 364 5 523 1983 or without no other cable in contract working temperature the max working ambient temperature of the unit cable type copper conductors PVC insulation from 70 C if not specified or EPR insulation from 90 C Consult the enclosed electrical diagram for additional information TAEevo015 351 The data inside this manual are not binding and they can be modified by the manuf
19. 5 4 11 Minimum distances from walls in the installation ambient cccccescceeeeeeeeseeeseeeteeeeees 15 ANZ Electrical CCUM ss ascsactsasnssvssssnniesuendonssidiveetsaastpmncsuebvebespasssctuasuessaniatecnteeaunesunncdaceuntscsuepiseastae 15 4 13 Negative ambient temperatures not present in models for 460 3 60 power supply 15 INSTALLATION ssissssssssssssssssassssssoncssssscssssscsssesszsssaesessoscesssssesssosssacosese ciesessssossses soaanessee sss deeses seseess sescessoesseseesssses 17 5l T spection sereni ative uses cca R EEE E oedema 17 52 POSMONNE eese e cc eps aa pas E ear canes ure eE E e ew eat Ge 17 5 3 Antifre prot tio eseese a e EEEE EE EEEE AE EER 17 3 3L Operatino UMS Sepse EKE E AOE EE E OERE ao 18 5 4 Hydraulic connections essit en E EE EEE AEEA a R EEEE O EE 18 5 EXPansion taK asrorin iier srn era EE ENE EE EEEE EE ENE Ea 19 5 6 Electrical COM SOHO S sac dacs adenntcnsncaecaseiereseeaivavsnendanseecentaeesuaten terns ie ane 20 START UP sss sassssisssdescsssecsasesovasssscscesssocscsassssasecs sass sosdssescevecs sdeceaseaescassencesssesaceessndesasesesese nasesssisavesenscssadssesesesses 21 ELECTRONIC BOARD sssssssssssssssncsssssosssssccssossasssaesessossecssssesssosssacesose s ssossssbseses soaaaasseesesdeesessssessssssssesessssssaoees se 23 Tl Display aie ccsateies dass aga aan R T asec ocak a ae 23 Filed DISPlAV ICONS srein ik av ta wes camete A EEE gs aes aa eee 23 Ta Function of DUWONS s5cnsa5c5
20. 5 Compressor parameters Parameter Level Description Min Max Udm Resolution Factory setting EVAPORATOR UNLOADING CONDENSER UNLOADING Pr2 Password 000 999 11 1 6 Fan parameters Parameter Level Description Min Max Udm Resolution Factory setting HOT START Pr2 Password 000 999 11 1 7 Antifreeze support resistance parameters Parameter Level Description Min Max Udm Resolution Factory setting Ar03 U Antifreeze alarm set Ar01 j Ar02 C Dec F Int 38 BOILER FUNCTION NOT ENABLED Pr2 Password 000 999 11 1 8 Defrost parameters NOT ENABLED FUNCTION Parameter Level Description Min Max Udm Resolution Factory setting Pr2 Password 000 999 11 1 9 Alarm parameters Parameter Level Description Min Max Udm Resolution Factory setting Pr2 Password 000 999 11 1 10 LASER parameters NOT ENABLED FUNCTION Parameter Level Description Min Max Udm Resolution Factory setting Pr2 Password 000 999 TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved CHAPTER 1 2 ALARMS 12 1 Alarm codes and actions See chapter 7 12 3 How to display the alarms
21. ALUC ccccecsccscseseesesessevsseseesesseeseesceseesceceeceeeaecessesseeaesessesseesenseeeseaeaeeneeas 25 T9 Values displayed iceren oni eE EE E EEE EE EE E AE 26 TIO Unit switching on ET oa stenechn Sarasin atin dond casvesuioieie E E ARE E Aia 26 7 11 How to put the unit in stand by oo eee ccccceceesceeseeceseceseeeeeeeeseecsaecnseceeaeeeseecsaecneeeeseesseeesaees 26 7 12 Function menu Hutton nennen ET ees 27 TAZA Access to Function MENU sisirin enr aeae EE EEE EE A AEE aae eS ee E e 27 7 122 Exit FPUNCHON Menu senintenee bee ban dusiavaiaecssanashdes cosestngisaGidke duthdblateuiennicesdecabsadg sanatlpaceosenbabae nat 27 7 12 3 How to display the alarms ALIM ccccccccceccecsssseseesesetseeseeeeseeseeseeseneeeesencasenesensrenessecasesenesnesersereeesatentes 27 724 HOW toteset an alarni PSE iiai EEE i a E dent sioch A E ER S 27 7 12 5 How to display the alarm historic ALOG ccccccceccesseseessesenseseensenecseeeenecsecseeeeeseeseeeeesseseneeaesneeenseeetenentes 27 7 12 6 How to reset the alarm history ArSt ccccccccscsscesceseusceeensensesevseeceseesesseesevseeeesseeceeeseeseesnecaesasereneeeetanentes 27 7 12 7 Displaying the operating hours of loads C1Hr C2Hr PF Hr oocccccccccccccceeecrreren 28 7 13 Other functions by keyboard cisasssccinecsanccanasincevvaszanscnastalcanaapacctedpspaccinssasdiacimamesaiicanmianusenies 28 7 13 1 How to display the Set POint sariini eia ee ieie 28 7 13 2 How to modify the Set Point
22. ALrM and 7 12 4 How to reset an alarm rSt MAINTENANCE AND OPERATING MANUAL Chapter 12 alarms oOo O CODE MEANING CAUSE ACTION RESET PI Alarm of BEWOT Probe damaged or open collector outlet alarm relay is Automatic probe resistive value out of activated If the resistive value returns within the range The buzzer is activated envisaged range The icon for general alarm flashes The alarm code is displayed P2 Alarm of BTWOT Probe damaged or open collector outlet alarm relay is Automatic probe resistive value out of activated If the resistive value returns within the range The buzzer is activated envisaged range The icon for general alarm flashes The alarm code is displayed P4 Alarm of BAT1 Probe damaged or open collector outlet alarm relay is Automatic probe resistive value out of activated If the resistive value returns within the range The buzzer is activated envisaged range The icon for general alarm flashes The alarm code is displayed A01 High pressure Digital input high open collector outlet alarm relay is Manual switch alarm pressure switch activated The digital input is disabled and the enabled The buzzer is activated resetting procedure is carried out The icon for high pressure alarm flashes The alarm code is displayed Condensation fan Digital input open collector outlet alarm relay is Manual thermal protection jenabled activate
23. FIMTA Cooling conditioning purifying WATER REFRIGERATORS TAEevo015 351 MAINTENANCE AND OPERATING MANUAL ce amp 38178800419 Original instructions MAINTENANCE AND OPERATING MANUAL 1 Index INDEX INDEX E E E EEEE OAE EE 1 GENERAL INFORMATION sisssisssicisssssscestcccesessessecstocssascaseesvascosesassaadessscseseesaesesceosoassaceansesssestedaceusecssssaawacesbeess 3 Ail How tointerpret the m delsiissernin nri eE EA A 4 noT T TA D AENEASE E EEAS E 5 Ded General eenean E EE ERE E EE EE TO AE ENE 5 2 2 Liquids of the user CITC insiccn qieraccennsantoveandexyesusecteaneuseseswncautcasssaneaccnnansdtwrasuieentanr cars eseearonernaes 5 2 3 Lifting and carriage precautions aij cca uiaiacunaskannigetenaneecauwheasseea nlavactnddecivibnearee aera aataceienndeteas 5 2 4 Installation pre Ca ton x oxsesssusvacinnsane cvsn tna anca wiwacartanentenaaseacessacaketnaateaasealnaianbericanenceacensceaiees 6 2 5 Precautions during OPELAUION xjrcsssdicncesanssasssanszinceseabeateiedsssuissediacesdandsnnaacusndeseina diamines 6 2 6 Maintenance and repair precautions wx susvindcssrivnscsouresssutsavsdysndsanisdsseniodeudvensevenvoteesnenwsstdverrsativan 6 og 2T ARGTMBELANL CASES xicacvanescasecendeancneadianscandesusspsnsnncecptinanccupsssdacandinddesedandesanindacasbeaagieasesiadecats snares 7 274 Refrigerant safety sehedule 5scvesesssadesdacasassaseveesnctsdecsiencetheovidensnauveayevasadedssdaas e i eiia Nae EdE Eia 7 A TEC
24. HNICAL DATA sisisssscsssovssssonsossenscsssstcssssseeevessecectendsssssssssssessonsoeceseecaosssssssteestss esbeuseseocsetsssssssessssseerseusesseseeees 9 3 1 Other data relative to the standard machines ccccccccsceceseceeeceeseeeseeceaeceeeeeseeceeeceseeeeeeeeaeees 9 3 11 Dimensi ns senenn E tones Eoi aS eoa E ESERE KEA EA E ASEA UAE ERE EOR RESENS 9 3 1 2 Characteristics of pumps and of the fans ccccccccccccceccseesceseesscesesceesecaeecseeseessecsaeeseeseeseceeeseeeeseeeseaeeeensees 10 3 1 3 Sound Level Measurements ccccccccccccscccsscccsscsescccssesssseeseeesssscsecceseessesesseceseccsseceseeeseeessecsseecsecessesssecsseeenaes Il DESCRIPTION scssssssssissssstssassocstecncssecssssssessssoonvesestaossetsssssusessisepeeseusceseesedteusesssssedcsesecdeeseenedssedsssseesesssserevesseeses 13 4l Components ssori E a ea EE EE rE ERR EEEE 13 42 Cooling cirCUitiesnien een E R E ESE 13 43 COMPLESSOLS areenaa e E cmc E O E E E 13 AA Condense sccsdcracesasscassnsekveaseuniancesvbucancksnck and cuntianneese biadecinahantesu sasnedsouianeenuniaacumenaeiennaenadinads 13 AD EE VADOVALOM sssctinccondoncsxeninusesicnunsuvsnsinedersnesnesunesiencusuusgededatsubesdsuneheseubenwincsuaivendesancstecuuesendszeunineuads 13 AG VAN E E T E E A 13 4l PUMP eneee a E A E A E E es 14 AS Pans eree E E E E 14 4 9 EASTING an en a N A E E E EN 14 4 10 Materials in contact with the liquid to be cooled oo eee cecceeeceeeeeececeaeceeceeeeeeseecsaeeneeseees 1
25. U Default top displaying 0 8 1 0 BEWIT 1 BEWOT e 2 none 3 BATI 4 unit setpoint e 5 unit status e 6 Laser set 7 none 8 operating differential CF42 U _ Default bottom displaying 0 8 4 0 BEWOT 1 BTWOT 2 BCPI1 3 BATI 4 unit setpoint e 5 unit status e 6 Laser set e 7 none 8 operating differential CF43 U Default top displaying of remote terminal 0 8 1 0 BEWOT 1 BTWOT 2 BCP1 3 BATI 4 unit setpoint e 5 unit status e 6 Laser set 7 none 8 operating differential TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 40 MAINTENANCE AND OPERATING MANUAL Chapter 11 Setting tables Parameter Level Description Min Max Udm Resolution Factory setting CF44 U Default bottom displaying of remote terminal 0 6 4 0 BEWOT 1 BTWOT e 2 none 3 BATI 4 unit setpoint e 5 unit status e 6 Laser set 7 none 8 operating differential Pr2 Password 0 999 11 1 3 Dymanic set point parameters NBCP10T ENABLED FUNCTION Parameter Level Description Min Max Udm Resolution Factory setting Pr2 Password 0 999 11 1 4 Energy Saving parameters NOT ENABLED FUNCTION CZ S E 11 1
26. acturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 6 Start up CHAPTER 6 START UP ATTENTION O Oo O Before starting up these units be sure that all personnel have read and understood the Chapter 2 Safety un A U N 11 12 13 14 15 16 Check that the machine s on off valves are open Check that the tank is completely full of water and properly vented Carry out the level sensor calibration as indicated in the 8 5 Level sensor paragraph Check that the ambient temperature is within the limits indicated in the machine data plate It is possible to check that the pressure is about 0 5 bar on the manometer located on the back of the unit only if the water circuit is of the closed type 6 Check that the main switch is in the OFF position 0 7 Check that the power supply voltage is correct 8 Power the machine by means of the supply line protection device 9 Turn the machine main switch ON T 10 Check that the water flows across the evaporator Press button for 5 seconds if you want to start the unit The led flashes for 5 seconds and then it remains lit key To power off the machine press the In three phase units check that compressor works correctly it must not be noisy or overheated and check that the fans and the pump if installed rotation direction is correct If necessary invert two phases of supply Check t
27. all use or maintain the unit The machine contains electrical components which operate at the line voltage and also moving parts It must therefore be isolated from the electricity supply network before being opened Maintenance operations involving work inside the machine must be performed by skilled and adequately qualified personnel equipped with suitable protection means active and passive e g work gloves ton ensure work in maximum safety Do not allow extraneous persons such as children where the machine is installed 2 1 General When handling or maintaining the unit and all auxiliary equipment the personnel must operate with care observing all instructions concerning health and safety at installation site ATTENTION Most accidents which occur during the operation and maintenance of the machinery are a result of failure to observe basic safety rules or precautions An accident can often be avoided by recognising a situation that is potentially hazardous The user should make sure that all personnel concerned with operation and maintenance of the unit and all auxiliary equipment have read and understood all warnings cautions prohibitions and notes written in this manual as well as on the unit Improper operation or maintenance of the unit and auxiliary equipment could be dangerous and result in an accident causing injury or death We cannot anticipate every possible circumstance which might represent a potential hazard The warnin
28. all dimension drawings 2 Provide two cocks one at the inlet and one at the outlet for excluding the unit when maintaining without emptying the user water circuit 3 Fill the tank with water using e A remote discharge system In this case it is necessary to leak manually the air from the tank by operating on the manual valve Ifthere are frequent air infiltrations into the water circuit it is advisable to install an automatic bleed valve 4 Ifthe machine is supplied without a pump make sure that the pump installed by the user has the suction directly connected to the tank outlet NOTE The pump must never run dry ATTENTION If the unit is furnished without hydraulic group it is necessary to install a pump for the evaporation water circuit For maintenance purposes we recommend installing a water drainage cock in the lower part of the circuit Evaporator water connection size Evaporator water IN OUT Rp 3 4 connections ATTENTION For correct operation we strongly recommend the installation of a water filter to be connected to the inlet pipe to avoid the entry of solid particles that could damage the pumps The non observance of this prescription can cause big damages to the evaporator TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 19 Chapter 5 Installation
29. and RESET values of the pressure switch depend upon the refrigerant gas used and are listed in the table below Axial fans TRIP RESET Pressure switch Refrigerant bar PSI C F bar PSI C F oe a R407C 18 261 46 4 115 5 14 203 37 0 98 6 Centrifugal fans NOT present in models with 460 3 60 supply TRIP RESET Pressure switch Refrigerant bar PSI C F bar PSI C F Centrifugal fans TAEevo 031 051 R407C 18 261 46 4 115 5 14 203 37 0 98 6 FP Centrifugal fans TAEevo 081 351 R407C 16 3 236 4 42 6 108 7 12 5 181 2 32 9 91 2 FP1 Centrifugal fans TAEevo 081 351 R407C 18 261 46 4 115 5 14 203 0 37 0 98 6 FP2 TAEevo 201 351 TAEevo 051 161 FP1 FP2 1 1 ELECTRICAL ee E BOARD cena ai ELECTRICAL SIDE a af BOARD gE SIDE BE EA DE M Speed regulator NOT present in models with 460 3 60 Hz supply with centrifugal fans and in TAEevo 015 020 The unit is furnished with a speed regulator of fan rotation which operates to maintain the condensing pressure within a pre fixed value These units are furnished with a pressure transducer positioned on the refrigerant compressor outlet pipeline It commutates the measured pressure value into an electric signal sent to the speed regulator For example if the temperature of the air sent to the condenser decreases
30. auton Gesu soxautdaieaarteacereiahetaraeee 34 11 1 Parameter Setting oes sees a A E ha cas ud eda ea nee 39 11 1 1 Thermoregulation parameters ccccccccccececceeseesensesseseseseneceeeteecsesseesecseeeeescesenecetenssnesaesessesteseseeeeeesentetents 39 1142 Configuration parameters isoine niie ie vat Ea aaa i n EEEa 39 11 1 3 Dymanic set point parameters NBCPIOT ENABLED FUNCTION ccce 40 11 1 4 Energy Saving parameters NOT ENABLED FUNCTION ocer 40 LLL 9 Compressor PAV AMELETS o isisccecsucssncnsdenevsndedoosnsnentioudn ies vetnetedsstnnp it coynatinsien pking stesscucinesslantslinte phew ages woniieatien one 40 LL TIO Fan par meters creecis enracinar oitan i othine AEN A lana ste EAEE A ai 40 11 1 7 Antifreeze support resistance parameters eccccccccecceceesersceseetenetsevseesesieescetensceesetenesaeeseceesesateceeaeeseesennentents 40 11 1 8 Defrost parameters NOT ENABLED FUNCTION c secsssssessessseseeseeseesenseneveeeneeesaesareaeeaeesenseneeeaeneeeneats 40 TELI Alarm parameters eneeroreirin t ie ene EE E EA E E RR E pest AS 40 11 1 10LASER parameters NOT ENABLED FUNCTION o cssscssssssesessseseeseeseeeenecneceeeesessesaeesesaeesenseneeesennetents 40 12 1 Alarm codes and actions 0 0 00 cccceeseeessssssssssssssssssssssssssssssssssssssssssssscssssssssssssasssssssssesesssestsneeaea 41 12 2 Outlet Bleking sci a ener a E E E E E E EEE EE Ri 44 TAEevo015 351 The data inside this manual are not binding and they can be modified by the
31. chapter 7 12 5 How to display the alarm historic ALoG TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved
32. comes manual after tripping per hour units Not enabled The buzzer is activated Manual The icon for general alarm flashes Disabling digital input not enabled The alarm code is displayed resetting procedure A08 Flow meter alarm Digital input open collector outlet alarm relay is Automatic and pump thermal enabled activated It becomes manual after tripping per hour alarm air water or jenabled for time The buzzer is activated Manual water water units se The icon for flow meter alarm flashes Disabling Digital input disabled for time The alarm code is displayed set and reset procedure A09 Compressor 1 Digital input open collector outlet alarm relay is Manual thermal alarm enabled activated Digital input disabled and the resetting The buzzer is activated procedure is carried out The icon for general alarm flashes The alarm code is displayed A10 Compressor 2 Digital input open collector outlet alarm relay is Manual thermal alarm enabled activated Digital input disabled and the resetting The buzzer is activated procedure is carried out The icon for general alarm flashes The alarm code is displayed A09 Compressor 1 2 The alarm is Relay alarm buzzer activated If ID is not activated A10 thermal alarm visualized but not Manual enabled during To reset the alarm enter the programming compressor thermal delay time after compressor start up All Condensation fan Digital input open collector outle
33. cs graphite and or EPDM 4 11 Minimum distances from walls in the installation ambient N See enclosures 2 4 12 Electrical circuit o For the electrical connections see Chapter 5 Installation Installation and consult the enclosed drawings 4 13 Negative ambient temperatures not present in models for 460 3 60 power supply In the presence of sub zero ambient temperatures 20 the unit is equipped with a system that assures perfect operation also in the presence of A harsh temperatures The additional elements fitted are e electronic fans speed control crankcase heaters e electrical cabinet heaters The pump and tank can be equipped with electrical heaters to prevent icing up instead of using glycol solutions TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 16 MAINTENANCE AND OPERATING MANUAL Chapter 4 Description TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 5 Installation 17 CHAPTER 5 INSTALLATION ATTENTION Before carrying out the installation or operating on this machine ensure that all the personnel has read and understood the Chapter 2 Safety in this manual O 0O O 5 1 Inspection Immediately after uncrating inspect the unit 5 2 Posit
34. cuit of the condenser SOUND PRESSURE LEVEL Sound pressure level in a free field in hemispherical irradiation conditions open field at a distance of 1 m from the machine condenser side and at 1 6 m from the ground AMBIENT TEMPERATURE Min and max cooling air temperature value WEIGHT This is the approximate weight of the unit before packing Table 3 DATA PLATE AND MEANING OF ABBREVIATIONS ATTENTION The performance of the unit mainly depends on the flow and temperature of the water in the user circuit and on the temperature of the thermal exchanger fluid of the condenser These data are defined during the offer stage 3 1 Other data relative to the standard machines 3 1 1 Dimensions See enclosures TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 3 Technical data 10 3 1 2 Characteristics of pumps and of the fans TSA OO TO TG Pakam TETA litres 60 60 115 115 140 255 pacity galUS 16 16 30 30 37 67 0 3 4 8 0 5 4 8 0 7 6 1 0 6 1 8 9 6 2 3 9 6 mater flowrate 1 1 21 1 1 1 21 1 18 264 2 6 26 4 4 4 42 3 5 7 423 wai head 3 2 1 4 3 2 1 4 3 1 1 5 3 0 1 4 2 9 1 3 2 9 1 5 PUMP P3 ee 43 8 20 6 J 43 8 20 6 J 44 9 22 6 44 5 21 3 f 44 2 19 0 f 43 8 22 6 nominal power 0 55 0 55 0 75 0 75 nominal power 0 3 4 8 0 5 4 8 0 7 4 8 1 0 4 8 1 8 13 2 3 13 1 1 21 1 1 1 21 1
35. d Digital input disabled and the resetting The buzzer is activated procedure is carried out The icon for general alarm flashes The alarm code is displayed A02 Low pressure Digital input low open collector outlet alarm relay is Automatic switch alarm pressure switch activated It becomes manual after the value set of enabled The buzzer is activated tripping per hour The icon for low pressure alarm flashes Manual The alarm code is displayed The digital input is disabled and the resetting procedure is carried out A03 Ambient air low Analogue input open collector outlet alarm relay is Automatic temperature alarm enabled activated The buzzer is activated The icon for general alarm flashes The alarm code is displayed A04 Unit outlet air low Analogue input open collector outlet alarm relay is Automatic temperature alarm enabled activated It becomes manual after nr tripping per not enabled The buzzer is activated hour The icon for general alarm flashes The alarm code is displayed A05 High temperature Analogue input open collector outlet alarm relay is Manual High pressure enabled if BAT1 gt Jactivated Disabled if BAT1 lt than set value and the of set value The buzzer is activated resetting procedure is carried out The icon for high pressure alarm flashes The alarm code is displayed A06 Low pressure Analogue input open collector outlet alarm relay is Automatic temperature alarm enabl
36. digital inputs open collector outlet alarm relay is Automatic with the same activated With correct re programming configuration The buzzer is activated The icon for general alarm flashes The alarm code is displayed ACF4 Configuration alarm CF28 1 and the open collector outlet alarm relay is Automatic digital input not activated With correct re programming configured or The buzzer is activated CF28 2 probe The icon for general alarm flashes BAT1 different from The alarm code is displayed 3 FErr Operating alarm with two digital The buzzer is activated Manual inputs enabled at the The icon for general alarm flashes Disabling of digital inputs reset procedure same time AFr Net frequency Net frequency out of open collector outlet alarm relay is Automatic alarm range activated Net frequency into operating range The buzzer is activated The icon for general alarm flashes The alarm code is displayed ALOC General alarm ID configured as Relay alarm buzzer activated ID configured as unit blocked generic alarm fixed time Automatic It becomes manual after tripping per hour set reset procedure in function menu It is memorized in the alarm historic only with manual rearm TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 43 44 MAINTENANCE AND OPERATING MANUAL Chapter 12 alarms 12 2 Outlet block
37. ditions at a distance of 1 m 3 2 FT from the condenser side of the unit and height of 1 6 m 5 2 FT from the ground Values tolerance 2 dB Sound power level in compliance with ISO 3744 TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 12 MAINTENANCE AND OPERATING MANUAL Chapter 3 Technical data TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 13 Chapter 4 Description CHAPTER 4 DESCRIPTION 4 1 Components The data relating to the materials refer to standard machines In case of particular units special materials are used so it is necessary to refer to the O oOo O data on the offer The machines essentially consist of the following components e Refrigerant compressor Condenser e Evaporator Tank Pump Frame outer panelling Electronic controller 4 2 Cooling circuit rw Models TAEevo have a single refrigerant circuit with one or two compressors connected in parallel tandem The circuits consist of the following components A e refrigerant fluid used R407C 8 piston hermetic compressor or scroll compressor e fan pressure switch with on off regulation pressure switches for high and low refrigerant pressure high pressure transducer for fan electronical regulation and
38. ecautions Evaporates Cleaning methods Evaporates HANDLING AND STORAGE Handling technical measures precautions Ensure sufficient air change and or extraction in the work areas TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 2 Safety recommendations for safe use Do not inhale vapours or aerosols Storage Close properly and store in a cool dry well ventilated place Store in its original containers Incompatible products explosives flammable materials organic peroxide CONTROL OF EXPOSURE INDIVIDUAL PROTECTION Control parameters AEL 8 h e 12 h TWA 1000 ml m3 for each of the three components Respiratory protection For rescue and maintenance work in tanks use autonomous breathing apparatus The vapours are heavier than air and can cause suffocation reducing the oxygen available for breathing Protection of the eyes Safety goggles Protection of the hands Rubber gloves Hygiene measures Do not smoke PHYSICAL AND CHEMICAL PROPERTIES Colour Colourless Odour Similar to ether Boiling point 43 9 C at atm press Flammability point Non flammable Relative density 1 138 kg l at 25 C Solubility in water Negligible STABILITY AND REACTIVITY Stability
39. ected limits and in particular x that it is not lower than the value corresponding to the maximum flow capacity Clean the water filter x We recommend to clean the filter after a week from the unit starting Check that the liquid indicator if present is full or with a small stream of bubbles when the compressor is i running Check that the unit current absorption is within the values on the data plate x Carry out visual inspection of refrigerant circuit looking out for any deterioration of the piping or any traces of oil which might indicate a refrigerant leak Check the condition and security of piping connections x Check the condition and security of electrical connections x Using a spanner check that the connections between the compressor inlet and outlet pipelines have not i slackened Check that the ambient air temperature is within the unit capacities x Check that the environment is well ventilated Check that fan is automatically switched on Thoroughly clean the fins of the condenser with soft brush and or jet of clean compressed air x Check that the grilles of the unit are free from dirt and any other obstructions Clean condenser fins with a mild detergent x ATTENTION This plan is based on an average working situation In some installations it may be necessary to increase the frequency of maintenance TAEevo015 351 The data inside this manual are not binding and they can be m
40. ed if BAT1 lt activated It becomes manual after tripping per hour set value The buzzer is activated Manual The icon for low pressure alarm flashes Disabled if BAT1 gt than set value and the The alarm code is displayed resetting procedure is carried out The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved TAEevo015 351 41 Our lis 42 MAINTENANCE AND OPERATING MANUAL Chapter 12 alarms CODE MEANING CAUSE ACTION RESET A07 Antifreeze alarm Digital input open collector outlet alarm relay is Automatic enabled if BTWOT activated It becomes manual after tripping per hour lt set value and The buzzer is activated Manual actives for the time The icon for general alarm flashes Disabling set The alarm code is displayed when the antifreeze regulation probe BTWOT gt set value in chiller modality and resetting procedure A07 Antifreeze alarm _ __ Digital input open collector outlet alarm relay is Automatic enabled activated It becomes manual after tripping per hour The buzzer is activated Manual The icon for general alarm flashes Disabling digital input not enabled The alarm code is displayed resetting procedure A07 Antifreeze alarm Digital input open collector outlet alarm relay is Automatic motocondensing enabled activated It be
41. er s groups indicated by some Label are divided as follows LABEL ACTION ALL It displays all parameters ST It displays Thermoregulation parameters CF It displays Configuration parameters Sd It displays only the parameters of the Dynamic Setpoint NOT ENABLED FUNCTION ES It displays only the parameters of the Energy Saving NOT ENABLED FUNCTION co It displays Compressor parameters FA It displays Fan parameters Ar It displays only the parameters of the Antifreeze Resistance dF It displays only the parameters of the Defrosting NOT ENABLED FUNCTION AL It displays only the Alarm parameters LS It displays only the LASER parameters NOT ENABLED FUNCTION 7 8 1 Access to Pri parameters User level To enter the menu of Pr1 parameters which can be access by the user abe Vv 000 aie 1 Press for some seconds Ga v buttons h and start flashing in the top of the display appears ALL the first group of parameters 2 Select the various groups using and buttons 3 After selecting a group press button if the selected group is part of the selected menu or any parameter of this group has been moved in this menu in the bottom of the display it appears the Label and the code of the group s first parameter present in Pr1 its value appears in the top of the display It will not be possible to enter a parameter s group which is not part of this men
42. erant bar PSI C F bar PSI oC F HP 27 2 394 5 63 4 146 1 20 5 297 3 51 5 124 7 R407C LP 1 7 24 6 17 3 0 9 2 7 39 1 8 8 16 2 8 3 Compressor operation The thermoregulation used is of proportional type After fixing the temperature and differential values the compressor will start when the value measured will exceed the sum of temperature differential It will stop when the value will be lower than the temperature differential The same logic will be applied also in two compressor units 8 3 1 Compressor regulation graphic in Chiller mode With 1 compressor With 2 compressors Ta1 ST01 STO09 RL1 ON gt OFF PBr PBr l PEN ST02 ST02 ST02 ST09 2 TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 8 Other components setting 8 4 Fan speed regulation The fan speed regulation can be carried out by means of a pressure switch FP in ON OFF modality or by means of a pressure transducer speed 30 regulator 1 Fan pressure switch FP In these units a pressure switch detects the refrigerant compressor outlet pressure and controls the fan operation powering them on or off The pressure switch FP is screwed to the refrigerant circuit piping with SCHRAEDER valves with needle which prevent leakage during replacement The TRIP
43. excess of system capacity The consequent system overload would require the start up of all the compressors at once which would be forced to operate in near limit conditions The overburdened compressors would thus be subject to dangerous overheating which would cause the activation of the thermal protections or the pressure of the refrigerant gas could reach alarm levels which would cause the machine to shut down This function enables the machine to run through the switch off or capacity step operation of the compressors even when the temperature of the water at the evaporator s inlet is high summer start up with hot water accumulation preventing the possible triggering of high pressure alarms It is not present in one compressor units The following messages will flash on the display AEUn evaporator unloading function ACUn condensation unloading function 7 15 Probe key In this chapter are indicated the probes BEWOT BTWOT BCP1 and BATI1 for their positioning consult the refrigerant drawing Their description is indicated in the following table Name in the manual Borne name Description BEWOT PB1 EVAPORATOR WATER OUTLET TEMPERATURE PROBE BTWOT PB2 TANK WATER OUTLET TEMPERATURE PROBE BCP1 PB3 CONDENSING PRESSURE TRANSDUCER only with electronic regulation BAT1 PB4 AMBIENT AIR TEMPERATURE PROBE Only with antifreeze protection function TAEevo015 351 The data inside this manual are not binding and th
44. exchanger is protected against the formation of ice caused by low evaporation temperatures through an anti freeze function in the electronic controller A probe monitors the temperature of the evaporator outlet water If it is necessary to achieve a negative ambient water temperatures a mixture of water and glycol must be used To drain the circuit see Chapter 9 4 Emptying the process water circuit 4 6 Tank The storage tank is cylindrical Alternatively a prismatic atmospheric tank can be supplied The tank can be protected against freezing by means of an electric heater managed by the electronic controller A level sensor in the tank serves to signal low water level conditions The standard supply includes anti condensation cladding a drain valve and an air bleed valve An internal bypass between the water delivery and return connections makes it possible to read the anti freeze probe if the unit s process water inlet and outlet connections are inadvertently closed In this case the unit stops due to tripping of the antifreeze alarm and the shut off valves must be reopened The bypass serves exclusively to allow an antifreeze alarm to trip if present and to allow the pump to run with a reduced water flow rate without damage It is advisable to avoid repeated antifreeze alarm trip cycles in the foregoing conditions TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All r
45. ey can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 29 Chapter 8 Other components setting CHAPTER 8 OTHER COMPONENTS SETTING 8 1 Compressor integral protection PI For each compressor this protection consists of three or six thermistor probes each inserted in the winding of a motor phase they are connected O oOo O in series and depending on the model the terminals can be external This system ensures complete protection against most of the problems which can give rise to burning of the windings When it trips it is necessary to find and eliminate the cause then you can start the machine again by pressing ON OFF button 8 2 Refrigerant high and low pressure switches The units are fitted with the following pressure switches 1 low pressure switch LP This monitors refrigerant compressor suction pressure and will trip to avoid that values dangerous for compressor normal operation are reached It is of an automatic reset type The alarm A02 see chapter 12 1 Alarm codes and actions produced by this pressure switch tripping can have a delay time after the compressor starting to avoid simple intake pressure fluctuations or false alarms interfere with the unit normal operation After the time set the pressure switch tripping will be detected by the electronic board which will display the alarm signal A02 see chapter 12 1 Alarm codes and actions band will stop the compre
46. for unloading NOT present with 460 3 60 supply centrifugal fans and in TAEevo015 020 liquid solenoid valve with prismatic tank and plate type evaporator thermostatic throttle valve with external equalization in models without prismatic tank present only from TAEevo03 1 e dryer filter e liquid flow sight glass in models without prismatic tank present only from TAEevo031 e lamination capillary only for TAEevo015 020 e refrigerant manometers TAEevo031 e Schrader service valves Consult the enclosed drawings for additional information 4 3 Compressors All the machines are equipped with piston or SCROLL hermetic compressors which are distinguished for their high energy efficiency low vibrations and consequent silence in normal operation They are cooled by the aspirated gas protected against overheating of the windings by an internal module that monitors their temperature and upstream by magnetothermic circuit breakers These components are housed in a closed but easily accessible compartment 4 4 Condenser Condensation occurs through fin pack coils consisting of copper tubes and collectors aluminium fins and shoulders in galvanised sheet 4 5 Evaporator The evaporator is a finned pack type the water flows in contact with the finned surface and at a speed that guarantees low pressure drops while the refrigerant fluid flows inside the tubes A plate exchanger can be fitted as an alternative In the TAEevo models the
47. gs in this manual are therefore not all inclusive If the user employs an operating procedure an item of equipment or a method of working which is not specifically recommended he must ensure that the unit and auxiliary equipment will not be damaged or made unsafe and that there is no risk to persons or property Any improper use of the machine will relieve the manufacturer from any liability for possible personal injury or property damage Arbitrary modifications made to the unit will automatically invalidate all forms of guarantee provided by the manufacturer 2 2 Liquids of the user circuit The liquids of the user circuit must be compatible with the materials used These can be water or mixtures of water and glycol for example Additives and glycol suppliers must guarantee compatibility with the materials For further information refer to 4 10 Materials in contact with the liquid to be cooled ATTENTION If the liquids of the user circuit contains dangerous substances e g ethylene glycol is very important to collect any liquid which leaks because it could cause damages to the ambient Furthermore when the refrigerator is no longer used dangerous liquids must be disposed of by firms specialised and authorised for treating them 2 3 Lifting and carriage precautions Avoid injury by using a hoist to lift heavy loads Check all chains hooks shackles and slings are in good condition and are of the correct capacity They must be
48. hat the pressure difference between the value read on the manometer located on the machine control panel with the pump in motion and the value read with the pump stopped is higher than the available pressure with the pump s maximum flow capacity If this difference is lower it means that the water flow capacity is higher than the maximum value allowed In order not to damage the pump it is necessary to increase the pressure drop of the hydraulic circuit by for example partially closing a pump discharge cock Models with centrifugal fans Check that the output of the centrifugal fans is correctly ducted and that the pressure drop of the ducting system is about equal to the available head If the pressure drops are greater this means that there is a reduction in the flow of cooling air with a consequent drop in machine performance and the possibility of protection devices tripping even at relatively low ambient temperatures lower this means that the air flow may be too high for the fan and this could be dangerous for the centrifugal fan motor If with the first start up there is a high ambient temperature and the temperature of the water in the hydraulic circuit is much higher than the working value e g 25 30 C this means that the refrigerator starts up overloaded with the consequence of possible tripping of the protection devices To reduce this overload a refrigerator outlet valve can be gradually but not totally closed to reduce the flo
49. he top part of the display Parameter CF36 CF43 3 In the top part of the display it appears the probe BAT1 Parameter CF36 CF43 4 In the top part of the display it appears the chiller set off when unit in stand by Parameter CF36 CF43 5 In the top part of the display it appears OnC when the unit is operating off when unit in stand by Parameter CF36 CF43 6 In the top part of the display it appears the LASER set FUNCTION NOT ENABLED Parameter CF36 CF43 7 No value will appear in the top part of the display Parameter CF36 CF43 8 In the top part of the display it appears the operating differential Parameter CF42 CF44 0 In the bottom part of the display it appears the probe BEWOT Parameter CF42 CF44 1 In the bottom part of the display it appears the probe BTWOT Parameter CF42 CF44 2 In the bottom part of the display it appears the probe PCP1 Parameter CF42 CF44 3 In the bottom part of the display it appears the probe BAT1 Parameter CF42 CF44 4 In the bottom part of the display it appears the chiller set off when unit in stand by Parameter CF42 CF44 5 In the bottom part of the display it appears OnC when the unit is operating Parameter CF42 CF44 6 In the bottom part of the display it appears the LASER set FUNCTION NOT ENABLED Parameter CF42 CF44 7 No value will appear in the bottom part of the display Parameter CF42 CF44 8 In the bottom part of the display it appears the operati
50. he unit is dirty if installed F Fi Fi 1 Call a qualified refrigeration Compressor protection Thermal load too high e The head and the body of engineer to check for leaks trips combined with a shortage the compressor are very and replenish refrigerant of refrigerant also see hot charge pe ae A5 e the compressor stops and tries to restart after a short period even a few seconds e compressor thermal protection trips e the indication A09 or A10 appears on the display e the led of general alarm icon lights up F2 F2 1 Invert two phases of the power The rotation direction of The refrigerant fluid is supply scroll compressor is wrong not compressed and the only three phase units unit doesn t cool TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 37 Chapter 10 Trouble shooting PROBLEM CAUSE SYMPTOM REMEDY G G1 G1 1 Check the causes of the fuse Digital display and all LEDs Auxiliary circuit fuse Measuring with a tester tripping off although P1 main tripping the voltage at the Replace the fuse switch On I transformer secondary winding connector there will be not tension survey G2 G2 1 Try to turn the unit OFF and Abnormal power Despite presence of ON again consumption by one or power at the connectors If this doesn t solve the more of the control board of
51. ights reserved 14 MAINTENANCE AND OPERATING MANUAL Chapter 4 Description With the prismatic atmospheric tank process water e filling is performed utilising a kit comprising a semi transparent plastic container secured to the rear of the machine In steady state operating conditions the liquid level must be about half way up the container 4 7 Pump Centrifugal pumps are installed and it is possible to choose between 2 different types which provide two different pressures based on requirements a 3 or 5 barg pump It is also possible to have units without pump The tandem pump can be installed in certain models The management procedure is manual The selector for pumps rotation is located inside the electrical cabinet For more information consult the attached diagrams The pump seals are made of ceramics treated carbon EPDM ATTENTION p Bleed the circuit by unscrewing the bleed cap on the pump whenever the water circuit is filled See 5 4 Collegamenti idraulici NOTE The pump must never run dry 4 8 Fans Axial fans The fans of axial type consist of a die cast aluminium fan with sickle profile The protection rating of the fans is IP54 The protection rating of the fans is IP44 for TAEevo015 020 All fans have F insulation class to assure the external working with all types of climates The assembly is completed with a superior support to the fan safety protection grill Centrifugal fans NOT
52. ing Alarm code Alarm Description Comp 1 Comp 2 os Pump P1 BEWOT probe Yes Yes Yes P2 BTWOT probe Yes Yes Yes P3 BCP1 probe Yes Yes Yes P4 BATI probe Yes Yes Yes AO1 High pressure switch Yes Yes Fan thermal protection Yes Yes A02 Low pressure switch Yes Yes A03 Ambient air low temperature A04 Air low temperature at unit Yes Yes Yes outlet A05 High temperature High Yes Yes pressure A06 Low pressure Low Yes Yes temperature A07 Analogue input antifreeze Yes Yes A07 Digital input antifreeze Yes Yes A07 Motorcondensing antifreeze Yes Yes A08 Flow meter pump thermal Yes Yes Boiler Res Yes protection Yes A09 Compressor 1 thermal Yes protection A10 Compressor 2 thermal Yes protection A09 A10 Compressor 1 2 thermal Yes Yes protection A13 Compressor 1 maintenance A14 Compressor 2 maintenance A15 Water pump maintenance A20 Low water temperature BTWOT A21 High water temperature BTWOT rtC Clock alarm rtF Clock alarm EE Eeprom error Yes Yes Yes Yes ACF2 Configuration alarm Yes Yes Yes Yes ACF3 Configuration alarm Yes Yes Yes Yes ACF4 Configuration alarm Yes Yes Yes Yes ACF6 Configuration alarm Yes Yes Yes Yes FErr Operating error Yes Yes Yes motorcond Afr Net frequency alarm Yes Yes Yes Yes ALOC Generic alarm Yes Yes Yes Yes NOTE The electronic control board is furnished with a history loop see
53. ioning 1 The unit may be installed both outdoors and indoors 2 If installed indoors the room must be well ventilated and with a sufficient height which allows the air to be expelled by fans In some cases it may be necessary to install fans or extractors to limit the temperature of the room 3 The minimum and maximum working ambient temperature are specified on the unit data plate In extreme temperature conditions the protection devices may trip 4 The machine must be positioned on any flat surface capable of supporting its weight 5 Leave at least one metre around the unit to permit access during service operations 6 Do not obstruct or disturb the condenser s flow of thermal exchanging air 5 3 Antifreeze protection Even if the minimum working ambient temperature is above 0 C it is possible for the machine during stoppages in the cold seasons to find itself in an environment with a temperature below 0 C In these cases if the machine is not emptied antifreeze ethylene glycol must be added in the following percentages to prevent the formation of ice Ambient temperature up to Ethylene Glycol C F in weight 0 32 0 5 23 15 10 14 25 15 5 30 20 4 40 Table 6 ADDING ETHYLENE GLYCOL BASED ON THE AMBIENT TEMPERATURE Add the following anti freeze ethylene glycol percentages in order to avoid freezing when operating at low water outlet temperature
54. m when an alarm occurs the alarm code and the appropriate icon flash in the bottom part of the display alternated to the temperature pressure TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 25 Chapter 7 Electronic Board 7 5 1 Alarm icons There are four icons for alarm signalling a General alarm H L High pressure alarm Low pressure alarm Flow Flow meter alarm 7 6 How to silence the buzzer Automatic silencing it happens when the cause of the alarm has been eliminated Manual silencing press and release one of the four buttons the buzzer silences even if the alarm condition persists 7 7 First start up At the first start up of the unit in the bottom part of the display it could appear the message C alternated with the temperature It indicates that it is necessary to regulate the clock If the probes used to control the unit are not connected or are damaged the appropriate alarm will be displayed However it is possible to regulate the clock or to programme the unit 7 8 Programming by keyboard The parameters of electronic control are divided in two groups and in two levels 1 USER Prl 2 SERVICE Pr2 USER level allows to access user parameters SERVICE level allows to access the parameters of unit configuration it is protected by a password The paramet
55. manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 3 Chapter 1 General Information CHAPTER 1 GENERAL INFORMATION The machines described in this manual are called WATER REFRIGERATORS This manual is written for those responsible for the installation use and maintenance of the unit O O The components used are of high quality and all the projecting process from the production to the unit checking has been manufactured in conformity with ISO 9001 norms In most applications the liquid of the user circuit is water and the term WATER will be used even if the liquid of the user circuit is different from water e g a mixture of water and glycol Here below the term PRESSURE will be used to indicate the gauge pressure The following symbols are shown on the stickers on the unit as well as on the overall dimension drawing and refrigeration circuits in this manual Their meaning is the following Process water inlet Process water outlet Indications for lifting the unit Water drainage point from the machine Electric shock risk Risk of burns from contact with high temperature surfaces Direction of the refrigerant fluid and water circuit Direction of pump rotation if installed Water filling point Air vent Hole for inserting bars for lifting the machine Dati e dA Table 1 SYMBOLS TAEevo015 351 The data inside this man
56. mming phase If pressed for more than 5 seconds they allow to start a manual defrosting cycle function not present 7 3 Symbols and leds on the display LED LED STATUS MEANING LED LED STATUS MEANING T Not enabled QO Not enabled RA Eo Steady Unit on in chiller modality 0 Not enabled 2 1 Programming phase if flashes f s Flashing p Clock adjustment F together with led S my Not enabled 7 4 Remote terminal 7 4 1 Function of buttons BUTTON FUNCTION It allows to enter Function Menu If pressed for 5 sec it allows to display or modify the set point During programming phase it selects a parameter or confirms a value It selects water temperature in the top part of the display During programming phase it scrolls the parameter s codes or increases their values It selects water temperature in the top part of the display During programming phase it scrolls the parameter s codes or decreases their values If pressed for 5 seconds it allows to switch on or off the unit co 0 6 66 Not enabled If there is no communication between the unit and the remote terminal in the top part of the display it appears the message OL no link NOTE The displaying depends on the setting of parameter CF43 CF44 see chapter 7 9 Values displayed 7 5 Displaying during an alarm During normal operation no alar
57. nd pump running is lower than the available head with maximum pump flow J2 J2 1 Reset the thermal protection The grille through which e See problem device k the pump cooling air Free the grille passes is obstructed e main alarm relay tripped e the refrigerant compressor and pump stop J3 J3 1 Reset the thermal protection The pump is defective e See problem device Replace the pump e main alarm relay tripped e the refrigerant compressor and pump stop e the current absorbed by the pump is greater than the nominal rating e the pump may be noisy K K1 K1 1 Turn off and turn on the unit Alarm Configuration error ACFx flashes on the If this does not solve the ACF1 ACF2 ACF3 display and unit problem contact the nearest ACF4 ACF5 blocked service centre L L1 L1 1 Turn off and turn on the unit Alarm The processor does not e The machine does not If this does not solve the EE memorize the data in the work problem contact the nearest right way service centre e EE flashes on the display e the led of general alarm icon lights up TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 38 MAINTENANCE AND OPERATING MANUAL Chapter 10 Trouble shooting TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights re
58. ng differential If the probe BTWOT has been selected has default every time you press for 30 sec the top display visualizes the BEWOT probe in the bottom part of the display it will appear the Label Pb2 than the default value will return to be displayed If the probe BEWOT has been selected has default every time you press for 30 sec the top display visualizes the BTWOT probe in the bottom part of the display it will appear the Label Pb1 than the default value will return to be displayed 7 10 Unit switching on off The pressure or hd button for 5 seconds allows to switch on or off the unit The led of icon flashes for 5 seconds then it remains lit 7 11 How to put the unit in stand by Stand by modality is obtained every time the unit is switched off It is indicated by the symbol fa lit Also in stand by modality the controller can 1 Display the measured values 2 Manage the alarms by displaying and signalling TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 27 Chapter 7 Electronic Board 7 12 Function menu 0 button The access to Function Menu allows to 1 Display and reset the alarms see 7 12 3 How to display the alarms ALrM Reset the alarms see How to reset an alarm rSt 2 Display the alarm history see 7 12 5 How to display the alarm historic
59. ntre 1 Make sure the level probe is immersed in the liquid at least 1 cm AS FOODS 2 Power on the system green LED 3 ve vO At 49 140 44 will illuminate steadily A Lamo amain W 3 Amber LED 2 may illuminate or e X remain off ce Teach 4 Press black Teach pushbutton 1 and hold down for more than 2 seconds 3 5 Green LED 3 will flash while amber LED 2 can e illuminate if it was previously off e remain illuminated if it was previously lit 6 This sequence of steps causes the device to self calibrate in accordance with the electrical resistance of the liquid NOTE If the electrical resistance of the liquid is outside the maximum range of the control device green LED 3 will flash rapidly for 2 seconds while amber LED 2 remains off thus signalling a teach in error ATTENTION The level sensor has been calibrated by MTA to operate at maximum sensitivity admissible on the instrument 220kOhm Modifications to this setting may impair correct operation TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 32 MAINTENANCE AND OPERATING MANUAL Chapter 8 Other components setting TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 33 Chapter 9 Opera
60. odified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 35 Chapter 10 Trouble shooting CHAPTER 10 oO Oo PROBLEM CAUSE SYMPTOM REMEDY A Al A1 1 Restore the thermal load to Tank water outlet Thermal load too high Temperature BTWOT Within the preset limits temperature BTWOT greater than expected higher than the expected value value A2 A2 1 In the event of installation in a Ambient temperature too See Al 1 closed place if it is possible high increase the change air flow into the installation location to restore the ambient temperature to within the preset limits A3 A3 1 Clean the condenser fins Condenser fins are dirty See Al 1 A4 A4 1 Free the front surface of the Front surface of the See Al 1 condenser condenser obstructed A5 A5 1 Get a refrigerator technician to Lack of refrigerant in the e See A1 1 check for leaks and eliminate plant i them e evaporating pressure too Fil the plant low e a lot of bubbles in the liquid indicator A6 A6 1 Get a refrigerator technician to Compressor protection e The head and the body of Check for leaks and eliminate trips the compressor are very them hot Fill the plant e the compressor stops and try to start up again after few seconds B B1 B1 1 Reduce water flow to within Low pressure drop water Water flow too high e Possible increase in the the preset limits for example pressure at p
61. on of the air Protect the environment by using only approved methods of disposal Keep a written record of all maintenance and repair work carried out on the unit and auxiliary equipment The frequency and the nature of the work required over a period can reveal adverse operating conditions which should be corrected ATTENTION Use only refrigerant gas specified on the specification plate of the unit Make sure that all instructions concerning operation and maintenance are strictly followed and that the complete unit with all accessories and safety devices is kept in good working order The accuracy of pressure and temperature gauges must be regularly checked They must be renewed when acceptable tolerances are exceeded ATTENTION Do not weld or carry out any operation which produces heat near a system which contains oil or flammable liquids The systems which may contain oil or flammable liquids must be completely drained and cleaned with steam for example before carrying out these operations TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 7 Chapter 2 Safety The adjacent components must always be screened with non flammable material and if the operation is to be carried out near any part of the lubrication system or close to a component which may contain oil the system must first be tho
62. p the unit again chapter Electronic Board D3 D3 1 Change the position of the unit Recirculation of warm air e Condenser thermal or the position of any adjacent due to incorrect exchanging air temperature Obstructions to avoid installation location higher than the permitted recirculation value Follow the alarm reset procedure to star up the unit e see D1 1 again chapter Electronic Board D4 D4 1 Clean the condenser fins See A3 See D1 1 Follow the alarm reset procedure to star up the unit again chapter Electronic Board D5 D5 1 Clean the front surface of the See A4 See D1 1 condenser Follow the alarm reset procedure to star up the unit again chapter Electronic Board D6 D6 1 If possible reduce the thermal Thermal load too high e Water outlet temperature 0ad to within the design too high limits Follow the alarm reset e refrigerant compressor procedure to star up the unit stops again chapter Electronic e main alarm relay tripped Board E E1 E1 1 Call a qualified refrigeration Low pressure switch Lack of refrigerant see e Refrigerant compressor engineer to check for leaks tripped LP also A5 stops and replenish refrigerant h Alarm displayed e the indication A02 appears eee A02 prayer on the display alternated to BTWOT value e main alarm relay tripped e the led of icon L lights up E2 E2 1 Clean or replace the water The filter upstream from See E1 1 inlet filter if installed t
63. r supply voltage must not be also for short periods out of the tolerances given in the wiring diagram Except for different indications the frequency tolerance is 1 of the nominal value 2 for short periods In the event of three phase supply the system must be symmetrical equal effective voltage values and equal phase angles among consecutive phases In particular except for different indication the max unbalance between each phase is 2 The unbalance is calculated as following Max difference of each phase from Vavg x100 Vavg Vavg average of voltage phases In the event of single phase supply check that there is a neutral line in the electrical installation and it is earthen in the transformer cabin TN system in compliance with IEC 364 or that this is done by the electricity supply company TT system in compliance with IEC 364 The phase conductor and the neutral wire must not be confused For the electrical supply 1 connect the unit PE terminal in the electrical panel to the earthed system of the building 2 guarantee the automatic interruption of the power supply in the event of insulation failure protection against indirect contacts in compliance with IEC 364 by means of a differential device normally with operation nominal current of 0 03 A 3 at the beginning of the electrical supply cable must be guaranteed a protection against direct contacts with a protection degree of IP2X or IPXXB at least
64. rm code will appear in the bottom of the display and the Label n with a progressive number 5 To exit ALoG function and to return to normal displaying press M button or wait for time out 30 seconds The memory contains until 50 alarms a further alarm will cancel from the memory the oldest one the displaying is in increasing order from the oldest one to the most recent one 7 12 6 How to reset the alarm history ArSt 1 Enter Function menu Select ALoG function in the bottom of the display 25 3 Press button 4 Inside ALoG function using or button select the function ArSt in the bottom of the display and PAS in the top of the display Press Gai the password is required In the bottom of the display it appears PAS 0 flashes in the top of the display vy 6 Insert the password for resetting 7 Ifthe password is correct the Label ArSt flashes for 5 seconds to confirm the resetting After resetting the unit returns to normal displaying TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 28 MAINTENANCE AND OPERATING MANUAL Chapter 7 Electronic Board 7 12 7 a ae the operating hours of loads C1Hr C2Hr PFHr 1 Press button to enter Function menu 2 Press or button until the Label of a single load appears in the bottom of the display C1Hr operating hours of compres
65. roughly purged preferably by steam cleaning Never use a light source with an open flame to inspect any part of the machine For every unit establish a suitable time schedule for cleaning operations ATTENTION If replacement parts are needed use only original spares Avoid to damage the safety valves and other pressure relief devices All guards must be reinstated after carrying out repair or maintenance work ATTENTION Check the direction of rotation of electric motors the pump if installed when starting up the unit initially and after any work on the electrical connections or switch gear ae Do not use flammable liquid to clean any component during operation If chlorinated hydrocarbon non flammable fluids are used for cleaning safety precautions must be taken against any toxic vapours which may be released ra ATTENTION Before removing any panels or dismantling any part of the unit carry out the following operations Isolate the unit from the main electrical power supply by disconnecting the cable from the electrical power source Lock the isolator in the OFF position with a lock Attach a warning label to the main isolator switch conveying WORK IN PROGRESS DON NOT APPLY VOLTAGE Do not switch on electrical power or attempt to start the unit if a warning label is attached Coloured tracers can be used in service maintenance operations Inspect all refrigerant circuit joints including connectors flanges
66. s unit blocked generic alarm time set AL21 CODE MEANING CAUSE ACTION RESET AZI High water Only units operating open collector outlet 7 alarm relay are Automatic temperature alarm if the temperature activated at evaporator outlet measured by PB2 is The buzzer is activated higher than AL24 The alarm code is displayed rtC Clock alarm Clock to be open collector outlet alarm relay is Manual regulated activated Clock regulation and resetting procedure The buzzer is activated The icon for general alarm flashes The alarm code is displayed rtF Clock alarm Clock damaged open collector outlet alarm relay is Manual Clock malfunction activated Resetting procedure The buzzer is activated If after resetting the alarm persists replace The icon for general alarm flashes the clock The alarm code is displayed EE Eeprom error alarm Memory data lost open collector outlet alarm relay is Manual activated Resetting procedure The buzzer is activated If after resetting the alarm persists the The icon for general alarm flashes device remains blocked The alarm code is displayed ACF2 Configuration alarm Unit configured as open collector outlet alarm relay is Automatic heat pump with activated With correct re programming commutation valve The buzzer is activated not configured The icon for general alarm flashes The alarm code is displayed ACF3 Configuration alarm Two
67. served MAINTENANCE AND OPERATING MANUAL 39 Chapter 11 Setting tables CHAPTER 11 SETTING TABLES The following tables show the list of all masks which contain adjustable parameters oo On Factory setting column are indicated the setting values set during the unit testing they are referred only to the unit which has the same serial number you can find on the label of the first page of this manual C DANGER 1 _ al The wrong programming of the electronic control could cause big damages to the unit The parameters can be modified by specialized personnel only 11 1 Parameter setting To modify the following parameters follow the procedure illustrated in Chapter 7 Access to Pr1 parameters User level and Chapter 7 How to modify a parameter s value 11 1 1 Thermoregulation parameters Parameter Level Description Min Max Udm Resolution Factory setting ST01 U__ Summer set point ST05 ST06 C Dec 9 with 1 compr F Int 48 with 1 compr PG 8 with 2 compr F 47 with 2 compr ST02 U Summer differential 00 0 25 0 C Dec 4 with 1 compr 00 0 45 0 F Int 7 with 1 compr C 2 with 2 compr F 4 with 2 compr ST05 Summer min set 40 0 STOI C Dec 5 0 40 0 F Int 41 Pr2 Password 0 999 11 1 2 Configuration parameters Parameter Level Description Min Max Udm Resolution Factory setting CF34 U Serial address 1 247 1 CF36
68. sor 1 C2Hr operating hours of compressor 2 PFHr operating hours of water pump and of outlet fan The operating hours will appear in the top of the display 3 The icon will be lit 7 12 7 4 Reset of the load operating hours 1 Press button to enter Function menu 2 Press or button until the Label of a single load appears in the bottom of the display C1Hr C2Hr only 201 351 units PFHr and the operating hours appear in the top of the display 3 Press button for 3 seconds in the top of the display it will appear 0 It indicates that the reset has happened 4 To exit Function menu press M button or wait for time out 15 seconds C5 5 For the other loads repeat the operations from point 2 to point 4 O 7 13 Other functions by keyboard Z 7 43 1 How to display the Set Point Press and release button In the bottom part of the display it appears SetC chiller set 7 13 2 How to modify the Set Point 1 Press SET button for 5 seconds at least 2 The set point will flash 3 Use or button to modify the set point value 4 To store the new set point value press button or wait for time out to exit programming procedure 7 14 Compressors unloading function This procedure is necessary when sudden peaks in cooling demand occur for instance if the machine is restarted after a long period of inactivity Under these conditions the evaporator inlet water temperature might be so high as to require a cooling delivery in
69. ss jiiosicssiate cade scavaa sasscuavascosessiun cubeaseutesdvateaTaasivies cides stat estsdestenustedlaaarlacweedss 28 FAA Compr ss ts unloading FUNC psccusavsoccoasdienesmranincduedivnsasonnongcuasebascsuoninaseeinedsumncnedueaspateseuniies 28 TAS PHOS GY esye O EE EE E E EAER 28 OTHER COMPONENTS SETTING sisssccsssssisssisssssossassessssscsastesasssosesteccsssessecnsncsdsssasssssenscssscossereassussccsescseetsassesnss 29 8 1 Compressor integral protection Pl ivccnsveresccatapsceenedaiadeainaie aes ea eanies 29 8 2 Refrigerant high and low pressure SWitChES ccccecceeseceseeeeceeseeceseceeceeeeeeseecaecnseeeeeeesaeenes 29 83 AIT SE SET I Fat asain esses en er E AE EA E EE ee 29 8 3 1 Compressor regulation graphic in Chiller mode o cccccscccscssssseeceeeeeeseesenseeseecuseeenteaeeaeeesieesesaeeeeeeneeeeeas 29 GA Fan speed regulation inosine inen aE RARE EEEE AE RE EEEE 30 8 5 Level SENSON sicssascreseasbsbncgsasncacant eian aea E E ERASER ER E EEE ETR EARE i 31 OPERATION AND MAINTENANCE sssssssscsccvcccesvoosescsessscossssssccosssenvocdesssassasssdssdseecedessenavoesssenssessssssseccecesesesisisssO 91 Op ratioi sassi ren i rene EEEE EEEE E E N E EE EEO 33 Dy PARTIC NAIC rninistr i A AEEA E a a a E i 33 93 O01 Ve oo n E a eR Aa NOR ERE OE 33 9 4 Emptying the process water circuit sc55 cass cs sesccesanteexpadeeceiednndeenanddaeeannes nee 34 9 5 Maintenance schedule 0p cacissunisecusianav Gente cemausledan deen cade eau sadelaeescuneeses
70. ssor s while the pump if it is installed will continue to operate After the alarm tripping if the compressor intake pressure increases and exceeds the pressure switch tripping value it will restart It will be possible to start up the unit again following the alarm reset procedure described in Chapter 7 Electronic Board If the cause of the pressure switch tripping has not removed this cycle will repeat continuously 2 high pressure switch HP This monitors the refrigerant compressor discharge pressure and prevents it increases to levels dangerous for compressor working and for people safety It is of an automatic reset type Its tripping is detected by the electronic board which will open the compressor power supply circuit and will display the alarm signal A01 see chapter 12 1 Alarm codes and actions When the compressor outlet pressure drops below the reset point it is reset It will be possible to start up the unit again following the alarm reset procedure described in Chapter 7 Electronic Board If the cause of the pressure switch tripping has not removed this cycle will repeat continuously The pressure switches LP and HP are screwed to the refrigerant circuit piping with SCHRAEDER valves with needle which prevent leakage during replacement The TRIP and RESET values of the pressure switches depend upon the refrigerant gas used and are listed in the table below TRIP RESET Pressure switch Refrig
71. t alarm relay is Manual Not enabled enabled activated Digital input disabled and the resetting The buzzer is activated procedure is carried out The icon for general alarm flashes The alarm code is displayed A12 Error alarm during Defrosting end Displayed code Automatic defrosting not max time Only signalling With following correct defrosting cycle enabled Manual Reset procedure A13 Compressor 1 Operating hours gt open collector outlet alarm relay is Manual maintenance alarm set threshold activated Operating hours reset The buzzer is activated The alarm code is displayed A14 Compressor 2 Operating hours gt open collector outlet alarm relay is Manual maintenance alarm set threshold activated Operating hours reset The buzzer is activated The alarm code is displayed A15 Water pump Operating hours gt open collector outlet alarm relay is Manual maintenance alarm set threshold activated Operating hours reset The buzzer is activated The alarm code is displayed A20 Low water Only units operating open collector outlet alarm relay Automatic temperature alarm ifthe temperature activated at evaporator outlet measured by PB2 is The buzzer is activated lower than AL23 The alarm code is displayed TAEevo015 351 The data inside this manual are not binding and they can be modified by t manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 12 alarm
72. tested and approved according to local safety regulations Cables chains or ropes must never be applied directly to lifting eyes Always use an appropriate shackle or hook properly positioned Arrange lifting cables so that there are no sharp bends Use a spreader bar to avoid side loads on hooks eyes and shackles When a load is on a hoist stay clear of the danger area beneath and around it Keep lifting acceleration and speed within safe limits and never leave a load hanging on a hoist for longer than is necessary The weight values shown in the following table were obtained with the unit empty pump P3 and axial fans The manufacturer does not supply bars belts and lifting hooks with the unit MODEL 015 020 031 051 081 101 121 161 201 251 301 351 Weight kg 127 132 200 220 331 386 405 416 533 650 740 757 Weight Ib 280 291 440 485 729 850 892 917 1219 1433 1631 1668 Table 2 WEIGHTS TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 5 6 MAINTENANCE AND OPERATING MANUAL Chapter 2 Safety Model 015 161 Model 201 351 NOTE Weight values are guideline with the water circuit empty The values may vary in relation to the configuration of the unit pump type supply type and ventilation type 2 4 Installation precautions The connections to be made are for the
73. tion and maintenance CHAPTER 9 OPERATION AND MAINTENANCE 9 1 Operation The machine operates in completely automatic mode O Oo There is not necessary to turn it off when there is no thermal load as it turns off automatically when the preset water outlet temperature has been reached 9 2 Maintenance ATTENTION Before proceeding with the installation or the maintenance of these units be sure that all personnel concerned have read and understood the Chapter 2 Safety 9 3 Unit access ATTENTION Everytime the panels must be removed the unit must be switched off and disconnected from power supply E To access the components of the refrigerant circuit use an appropriate key furnished with the unit and operate on the closing bolts of the front panel A The access to the evaporator and to the components of the hydraulic circuit can be carried out by unscrewing by a screwdriver the screws fixing the panel B To access the components of the electrical circuit remove the front panel C For models TAEevo201 and upper To access the components of the refrigerant circuit operate on the closing bolts of the panel A Furthermore it is possible to access the components of the refrigerant circuit removing the side panels B D The access to the evaporator and to the components of the hydraulic circuit can be carried out removing the back panel F or the side panels D E G or H TAEevo 015 020
74. u 4 It is possible to scroll or modify the parameters contained in the group 7 8 2 How to modify a parameter s value 1 Enter the programming procedure Select the desired parameter Press button to enable the value s adjustment Modify the value by means ot and buttons Press to store the new value and to pass to the code of the following parameter SN e To exit the procedure Press F when a parameter is displayed or wait about 240 seconds without pressing any button TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 26 MAINTENANCE AND OPERATING MANUAL Chapter 7 Electronic Board NOTE The new value is stored also when the programming procedure is terminated for time out without pressing button ATTENTION You can modify the parameter of the CF configuration parameters family only when the unit is in stand by 7 9 Values displayed The values visualized on the display change according to the configuration of parameters CF36 for the top part and CF42 for the bottom part For remote terminal it changes according to the configuration of parameters CF43 for the top part and CF44 for the bottom part Parameter CF36 CF43 0 In the top part of the display it appears the probe BEWOT Parameter CF36 CF43 1 In the top part of the display it appears the probe BTWOT Parameter CF36 CF43 2 No value will appear in t
75. ual are not binding and they can be modified by the manufacturer without notice All rights reserved 4 MAINTENANCE AND OPERATING MANUAL Chapter 1 General Information 1 1 How to interpret the model MODEL DESCRIPTION TAEevo XX 1 tL refrigerant with 1 refrigeration circuit power indicative of the refrigeration compressor in hp E hermetic type compressor A air cooled condenser T tank refrigerator with storage tank ATTENTION This manual provides the user installer and maintenance technician with all the technical information required for installation operation and carrying out routine maintenance operations to ensure long life If spare parts are required this must be original Requests for SPARE PARTS and for any INFORMATION concerning the unit must be sent to the distributor or to the nearest service centre providing the MODEL and MACHINE NUMBER shown on the machine data plate and on the first page of this manual TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL Chapter 2 Safety CHAPTER 2 SAFETY This machinery was designed to be safe in the use for which it was planned provided that it is installed started up and maintained in accordance O oOo O with the instructions contained in this manual The manual must therefore be studied by all those who want to inst
76. ump outlet Wrong working of the outlet temperature BTWOT by closing partially a pump pump high flow low see A1 1 outlet cock Reset the pump thermal protection and check the electrical absorption discharge head high absorption e with pump installed on the machine pressure difference read on the machine pressure gauge too low with pump stopped and pump running e possible tripping of pump thermal protection B2 B2 1 See point C See point C See point C B3 B3 1 Depending on the type of dirt Evaporator obstructed High water temperature e clean the evaporator by because of dirt transported difference between running a detergent by the utilization water input and outlet solution which is not aggressive for steel aluminium and copper e run a high water flow against the stream Install a filter upstream from the unit C C1 C1 1 Clean the upstream filter if Water differential pressure The filter upstream from e Water does not flow installed switch FLOW alarm trips the unit is obstructed if Pressure difference Follow the alarm reset installed between inlet and outlet procedure to star up the unit Alarm displayed lower than 25mbar again chapter Electronic Board ROS e Alarm displayed A08 e main alarm relay tripped C2 C2 1 Check the pump electrical The pump is defective or e See Cl 1 supply and if it is necessary rotate in the wrong es N invert the two phases direction
77. w of water passing through it Open the valve as the water temperature in the hydraulic circuit reaches the working value The machine is now ready for operating If the thermal load is lower than that produced by the unit the water temperature drops until it reaches the set point STO1 parameter set following the instruction of chapter Electronic Board When SET POINT value has been reached the electronic control controlling the water inlet temperature stops the compressor The water pump on the other hand is always in motion TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved 21 K _ S 22 MAINTENANCE AND OPERATING MANUAL Chapter 6 Start up TAEevo015 351 The data inside this manual are not binding and they can be modified by the manufacturer without notice All rights reserved MAINTENANCE AND OPERATING MANUAL 23 Chapter 7 Electronic Board CHAPTER 7 ELECTRONIC BOARD 7 1 Display The display is divided in 3 zones O O O It displays the temperature of temperature regulation probe NOTE The displaying depends on the setting of parameter CF36 see chapter 7 9 Values displayed It displays the operating setpoint OFF with stand by unit NOTE The displaying depends on the setting of parameter CF42 see chapter 7 9 Values displayed Signalling icons Right zone 7
Download Pdf Manuals
Related Search
Related Contents
Ponceuse à cylindre PON400 Leman USER'S MANUAL ENGLISH Curtis RCD-718 User's Manual CD Clock Radio TD 14 - Decitre 取扱説明書 - KOREA Mtt Sony XM-GS100 Operating Instructions Manual de instalação do Pan & Tilt e “Decoder” 低価格の電磁調理器対応鍋の加熱適性 Copyright © All rights reserved.
Failed to retrieve file