1. 11 EARTH CABLE 2 SCREE CONTROI PRESSURE PANEL 777 TRANSDUCER TERMINALS FIGURE 1 Motor Wiring The motors must be wired in overall screened power cabling sized to suit the motor power requirement This type of cable provides the most protection against the emitting electrical noise produced by the Variable speed drive If the correct cable is not installed the installation will not comply with the C tick regulation radio waved could become interfered with which could cause radios amp television reception to become distorted The motors are to be connected in star or delta as instructed by the nameplate on the motor The cabling entering into the motor terminal box shall be glanded using EMC type glands to provide good earthing of the cables overall screen The cable entering the control panel end can be glanded using standard nylon glands amp run directly to the appropriate variable speed drive where the screen will be earth on the special earthing plate at the bottom of the drive terminals via an earthing saddle The motor cable are connected into the output terminals on the drive U T1 V T2 W T3 as shown in figure 2 below E SCREE e EARTHING SADDLE U T1 Vie p q W T3 EMC CABLE wl GLAND VSD ee MOTOR TERMINALS FAR THING r ola PLATE FIGURE 2 2 4 Maintenance The only general mainten
2. are reset after a low O50kPa discharge pressure shutdown Set Point System set point pressure that is to be maintained 600kPa Sensor 0 The Low Value of the Transducer input OkPa Sensor 100 The High Value of the Transducer input 1000kPa Wake Up Pressure setting at which Pressure the sleeping pumps are 575kPa turned back on Standby start The speed of the pump at speed which the next pump is call 400 on line to maintain set pressure Stop Minimum _ The speed of the duty Speed pump at which the standby 75 pump is told to stop Low Stop Timer The time delay to shutdown duty pump once agsec nd set pressure amp stop min speed reached High Start Timer The time delay before starting the standby pump 2seconds 2 Low Stop The time delay before Timer stopping the standby pump 1seconds 9 0 Warranty Statement The Products manufactured by Inca Control Pty Ltd is guaranteed against faulty workmanship for a period of 12 months from the date of delivery Our obligation assumed under this guarantee is limited to the replacement of parts which by our examination are proved to be defective amp have not been misused carelessly handled defaced or damaged This guarantee is VOID where the purchaser has modified or repairs have been made or attempted by anyone except an authorised representative of Inca Control Pty Ltd Products for attention under guarantee unless otherwise agreed must be returned to the factory freight paid and
3. entered Example say 67 Enter the setting screen press 6 press 7 press enter to accept The pump stop min speed is now set to 67 4 10 Low Stop Timer The low stop timer is the time delay added to the sleep mode shut off pressure This timer is required to help prevent short cycling when there is minimal draw off This time is factory set at 20seconds This time is displayed in minutes amp seconds To set a time of 40seconds enter the setting screen press 0 press 0 press 4 press 0 press enter to accept You have now set 40second as low stop time 4 11 High Start Timer The high start timer is the time delay added to the standby pump start to ensure that the pressure is still falling before starting the standby pump This timer is required to help prevent short cycling when there is minimal draw off This time is factory set at 2seconds This time is displayed in minutes amp seconds To set a time of 5seconds enter the settings screen press 0 press O press O press 5 press enter to accept You have now set 5second as high start time 4 12 2 Low Stop Timer The 2 Low Stop timer is the time delay added to the standby pump stop to ensure that the pressure is still rising or steady above the set point pressure before stopping the standby pump This timer is required to help prevent short cycling when there is minimal draw off This time is factory set at 1seconds This time is displayed in minutes amp seconds To set a time of 5second
4. if accepted for free repair will be returned to the customers address in Australia free of charge Equipment supplied by Inca Control Pty Ltd but manufactured by others is covered by their manufacturers warranty only When returning the product for service or repair a full description of the fault must be given and the mode of operation used when the product failed In addition to the above equipment manufactured installed amp commissioned by Inca Control Pty Ltd within the Sydney Metropolitan Area includes onsite replacement In any event Inca Control Pty Ltd has no other obligation or liability beyond replacement or repair of this product NOTES
5. press enter You now have entered 250kPa for Sensor 0 Sensor 100 the value in engineering terms related to the field device feedback signal The pressure transducer sends a 4 20mA signal to the controller This signal needs to be displayed in kPa to mean something to the operator The Sensor 100 is the engineering value when the transducer is at its highest value i e 20mA 8 will be factory set at 1000kPa This value can be altered to suit different applications as required Example 900kPa Enter the setting screen press 9 press 0 press 0 4 then press enter You now have entered 900kPa for Sensor 100 4 2 Setting Low Pressure Shutdown To adjust Low pressure stop there are 3 entry values LOW PRESSURE ON setting Enter the setting screen amp simply type in the appropriate pressure you want the low pressure shutdown to operate at example 200kPa Enter the setting screen Press 2 press 0 press 0 amp then press enter LOW PRESSURE OFF setting Enter the setting screen simply enter in the appropriate pressure you want the system to restart at This will reset the low pressure alarm amp allow the pumps to operate in automatic Example 250kPa Enter the setting screen press 2 press 5 press 0 4 then press enter LOW PRESSURE TIME setting Enter the setting screen amp simply enter in the appropriate time delay you want before the system will shutdown once the 11 pressure is below your low pressure on setting Example 30seco
6. INCA CONTROL PTY LTD Phone 02 9675 3815 UNIT 14 62 OWEN ST Fax 02 9675 1381 GLENDENNING NSW 2761 ELECTRICAL ENGINEERS Email sales incacontrol com au Design Manufacture of Custom built switchboards Electronic control equipment AC DC pumping controls Installation service INCA MODEL PV2 VARIABLE SPEED DRIVE CONSTANT PRESSURE CONTROLLER USER MANUAL Inca Reference PV2 Software Version 1 0 Technical Support Electrical amp Controls Inca Control Pty Ltd Phone 02 9675 1381 Inca Control Ref 149 8410 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 TABLE OF CONTENTS Control Panel OvervieW oooccoccoccoccoccocconooncononncnnacnnnnnnnannns e A etek ee ee oe Va ate lee 152 Descripcion ents lhstallatiO Men e a AE E ei 2 1 Mechanical installati0N oooocoococconccncononncononnonos 2 2 Sensor mmstllalON pdas 2 3 Electrical INSTAIAU OMS scaioina bo rs oi 2 4 MaINCHANGC li edades A A e sees alee aoa ete acta ad let Saar toa 3 1 Notes on value ntry cccceeceee eee eee eee eeeeeeeeeeneeneaees 3 2 Power up ASP io 3 3 Screen display layOUt ooooccoccococcconoccononnocnnnnnnnnnns 3 4 Operating the touch screen touch poiNtS oocooocccococ 3 9 PUN star aran dci Calibracion r aa e aa 4 1 Pressure Sensor CalibratiON ooocoococcocconocccononon os 4 2 Setting low pressure ShutdOWN oooocccccccccnccncnccncnccnnnncnos 4 3 Setting hig
7. aker is on 4 Pump Fail displayed on screen Reset VSD by turning associated pump circuit breaker off for 10seconds then back on If fault continues take note of the code in the VSD display amp call for service 5 VSD screen displaying fault OH overheat Check air inlet filter clean amp not blocked Check cooling fan is operating amp not failed Reset fault by turning pump circuit breaker off for 10 seconds amp then back on If fault continues call for service 6 System Produces a Low Pressure shutdown Select a pump to manual amp jack system up to operating pressure Reselect back to auto Check that mains water is available amp all valves are open 7 Pressure displaying a negative value Pressure transducer has open circuit 4 20mA loop or is faulty Check pressure transducer cabling connections replace transducer with the same unit or call for service 8 Pressure discharge unstable 8 Problems with pumps Perform auto tuning as per section 4 12 Check air pressure Pressure vessel should be approximately 70 of the set point pressure Refer to pump manual or contact Pump supplier for service 8 Controller settings sheet e Factory User Parameter Description settings Setting Low pressure Pressure at which pumps Shutdown are shutdown for low 200kPa discharge pressure Low pressure Pressure at which pumps Reset
8. al override arrangement in the event of a PLC failure or at any time as required Inside the control panel are switches marked MANUAL OVERRIDE Selecting the appropriate switch to override will shutdown the automatic control from the PLC controller amp allow manual control directly from the face of the selected VSD Press the RUN button on the VSD to start the pump The pump speed is now controlled via the Speed pot on the front of the drive Turning this dial in a clockwise direction will increase the speed 4 turning in an anticlockwise direction will decrease the pump speed Pressing the stop button on the face of the drive will turn the pump off Note lt is best if the speed pot dial is turn fully anticlockwise when turned off so as when selected to run next time it does not ramp to full speed or where ever the pot dial was last left 8 will have better control for the operator Turn the override switch back to normal operation so as the pump is again controlled automatically by the PLC 7 Trouble Shooting Condition Do This 1 Unit does not power up Check that power supply is on to panel and isolator is on Check that control circuit breaker is on 2 PLC Controller does not power up but power is on Check that 24VDC power supply is operating amp power supply plug on PLC controller is fully inserted 3 VSD does not power up Check that all pump circuit breakers are on Check that control circuit bre
9. ameter 4 10 above has timed out Standby Pump The standby pump requires 3 things to shut down 1 The system pressure has reached amp maintains set point pressure less 5kPa 2 The motor speed is less amp maintains less than the speed set in PUMP STOP MINIMUM SPEED parameter 4 9 above 3 Andthe time value entered into parameter SECOND LOW STOP TIMER parameter 4 12 above has timed out 15 5 2 Manual Off Auto Selector Switches Each pump has a Manual Off Auto selector switch Each function of the switch is selected by touching on the operation Manual Touching the MAN box will turn the pump on amp display UP amp DOWN arrows next to the MAN box The pump will not run until the UP arrow Is pressed amp the speed increased to the desired speed Pressing the DOWN arrow will decrease the speed Below the auto box will be text advising that MAN has been selected amp the speed the motor is running at Off Touching the OFF box will turn the pump off Below the Auto box will be text advising the switch is selected to off Auto Touching the AUTO box will select the pump on automatic amp is then controlled via the PID loop controller Below the auto box will be text advising that AUTO has been selected amp the speed the motor is running at 5 3 Duty Selector The duty selector allows the operator to select a given pump alternating pattern or automatic alternation If the system is selected to auto amp a pump fail
10. ance required to the control panel is to clean or replace the air inlet amp outlet filter Inlet filters must be cleaned or replaced every 6months 4 more often under high dust conditions Outlet filters can be cleaned amp replaced as required while cleaning of the Inlet filter occurs Failure to carry out regular cleaning of filters will reduce the operating life of the control equipment 3 0 Start up 3 1 Notes on Value Entry When entering a numeric value the cursor can be backspaced to correct mistakes by pressing the LEFT ARROW button Decimal points can only be entered on entries with decimal points in the display line The decimal point is entered by pressing the button on the bottom right corner of the numeric entry buttons You can only enter a value of as many digits as is displayed on the screen Example an input that displays 3 digits can only have 3 digit entered 3 2 Power Up Display On power up the screen will display information amp contact details for Inca Control Pty Ltd This information is displayed for 10seconds before moving onto the MAIN PAGE which displays the pressures switches operating information 3 3 Screen Display Layout The main page displays the basis of all operation that is happening in the system e Atthe top left of screen in bold letters is the SET PRESSURE This is the pressure the system is trying to maintain amp is displayed in kPa e Atthe top right of screen in bold letters is t
11. e until either this pump reaches amp maintains 100 speed for a short time delay At this point the second standby pump will be started amp ramp up amp down maintaining set pressure If the second standby pump reaches the amp maintains the pump stop criteria it will be turned off amp the first standby pump will then be release amp ramp up amp down to maintain the set point pressure If the first standby pump reaches amp maintains the pump stop criteria it will be turned off amp the original duty pump will then ramp up amp down to maintain the set point pressure until this pump reaches amp maintains the pump stop criteria plus a delay for 20seconds amp will then turn off stopping all pump operation until the wake up pressure is again reached The pressure will fall to the wake up pressure set point where the duty pump will then start the cycle once again Each time the system goes to sleep the duty pump will be alternated to the next pump ready for the next operation If a motor fails the first standby pump will be started amp will remain as duty until the faulted pump is put back on line Pump Stop Criteria Duty Pump The duty pump requires 3 things to shut down 1 The system pressure has reached maintains set point pressure less 5kPa 2 The motor speed is less amp maintains less than the speed set in PUMP STOP MINIMUM SPEED parameter 4 9 above 3 And the time value entered into LOW STOP TIMER par
12. h Pressure ShutdowWN oooooccccccccccccnccccoccnnnnnnoo 4 4 Setting the operational Set pOiMt oooooooccccccccccccccoccnconcnnos 4 0 PIB Control Tico o ee 4 6 Modulating 1 or BOth ooococccoccccccocccnccnnncnnconnnnnnnnns 4 7 Wake up POSSE e ate 4 8 Standby start spebO aviindosinasulrase seudo cases 4 9 SIONMIAOS PO ect ie 4 10 Low Stop IM a eds A a eae A222 Low Stop A A A TOON A A E a carotene eat A O O dns ie 5 1 System A eo rrrrrrrrrrrrrrernrrrnr erne 5 2 Manual off auto Selectors ooooooccococcccocconcononnconananons Bis A A A Variable speed driVES ocoocooccocccocconccnnoncnonnanccocnnnnannnnnnnoos 6 1 Manual Override ooooocococcoccocoocccncononncnnonnncnannnnn Trouble oO MN rinda nacer a Controller settings Sheet oocococccccocconcoconncononcconcnnananons Warranty Statement cccsvcenvent onixstendnorches foawala dai Drawing supplied separately O 09 o Y UN UN ON ONO WW 1 0 Control Panel Overview 1 1 Features e Vision 350 570 user friendly colour touch Screen e Display of system pressure e Display of pressure set point e Low pressure pump shutdown with flashing screen text e Display of manual off auto e Hour run meter for each motor resetable e Microprocessor controlled e PID loop control e Variable speed controlled e Useable with any 4 20mA loop powered Pressure Transducer e Usable with any 415V centrifugal motor amp pump combination 1 2 De
13. he SYSTEM PRESSURE This is the live signal from the discharge pressure transducer amp is displayed in kPa e Directly below the set pressure is the DUTY SELECTOR This text is within a box amp touching the screen within that box will transfer to the Duty Selector page On this page the sequence of the pumps can be selected e Directly below the System Pressure is the LOW PRESSURE alarm display Under normal operating conditions this area of the screen will be blank but if pressure in the discharge line falls to below the Low Pressure set point then LOW PRESSURE will be displayed and flashing The pumps will be shutdown This alarm is reset when the pressure is jacked up above the Low Pressure reset set point e Below the duty selector amp low pressure alarm are the MAN OFF AUTO selectors for each pump with the status of the associated pump located just above the MAN touch point Below the AUTO touch point for each pump is text that identifies which position the associated man off auto has been selected to the of speed the motor is running at amp the hours the pump has run in total 3 4 Operating The Touch Screen Touch Points Operating the touch screen is as simple as it sounds All touch point are displayed by having the appropriate text enclosed by a box amp simply touching within the box will operate the appropriate operation 3 5 Turning the Pumps On Initial turn on of the pumps should be carried out in manual Select the app
14. lled at the pump motors 2 1 Mechanical Installation Mount the control panel via the mounting holes in each corner at the back of the enclosure using minimum 6mm screws nuts locking washers Install in a dry well ventilated location that matches with environmental specification in 1 2 above 2 2 Sensor Installation Locate the pressure transducer in the pipe work as close as practical to the air pressure tank located on the pump discharge This should help in smoothing out any sudden fluctuations in discharge pressure 2 3 Electrical Installation Note All cable entries must enter v a the bottom of the cabinet If cables are entered via the roof Inca Control 8 Engineering Pty Ltd reserve the right to withdraw warranty because of the possibility of shaving entering sensitive electronic equipment Transducer wiring The pressure transducer must be wired in 1 pair overall screened data cable This type of cable provides the most protection against electrical noise that is generated by the variable speed drives Connect to the sensor as per data supplied by the sensor supplier or figure 1 below At the control panel connect the positive lead to the 24V supply generally terminal No10 amp the return signal to PLC side of the circuit generally terminal No11 The screen must be solidly earthed with a saddle clamp or earth terminal for best screening
15. nds Enter the setting screen press 0 press 0 press 3 press 0 amp then press enter You now have entered 200kPa low pressure alarm with a delay of 30seconds amp a reset of 250kPa 4 3 Setting High Pressure Shutdown To adjust high pressure stop there are 3 entry values HIGH PRESSURE ON setting Enter the setting screen amp simply type in the appropriate pressure you want the high pressure shutdown to operate at example 800kPa Enter the setting screen Press 8 press 0 press 0 amp then press enter HIGH PRESSURE OFF setting Enter the setting screen 8 simply enter in the appropriate pressure you want the system to restart at This will reset the high pressure alarm amp allow the pumps to operate in automatic Example 750kPa Enter the setting screen press 7 press 5 press 0 4 then press enter HIGH PRESSURE TIME setting Enter the setting screen amp simply enter in the appropriate time delay you want before the system will shutdown once the pressure is below your high pressure on setting Example 30seconds Enter the setting screen press 0 press 0 press 3 press 0 amp then press enter You now have entered 800kPa low pressure alarm with a delay of 30seconds amp a reset of 750kPa Touch the next page touch point to move onto the next page 4 4 Setting The Operational Set Point The Set Point amp PID Page will now be displayed Enter the setting screen for set point To enter your required pressure say 600kPa press 6 press 0
16. p earth power supply sized to suit the total load of all three motor amp must have a protection circuit breaker sized to suit the starting characteristics of all motor starting simultaneously via reduced starting current variable speed drive controllers Mechanical Specification Enclosure Dimension Pump Unit Mild steel powder coated RAL 7032 IP44 IP54 or stainless steel is available Up to dual 2 2kW 600Hx400Wx300D 3kW to 7 5kW 600Hx600Wx300D 7 5kW to 15kW 800Hx600Wx300D Sizes may vary for specials See Pumping detail pumps supplier Environmental Specification Operating Temp 10 to 50deg C Relative Humidity Do not install in areas of high humidity Location Vibration Located control panel internally where possible to help reduce heat 4 weather damage amp increase mechanical life The variable speed drives are heat emitting bodies Make sure to provide space amp ventilation around cabinet to allow for cooling Do not install in a location that is subject to large amounts of vibration 2 0 Installation Note If any damage to control panel is found please notify Pumps Supplier or Inca Control amp engineering as soon as possible prior to installation The control panel can be wall mounted separately from the pumping unit up to distance of 30metres away It is recommended that the control panel is within view of the pumping unit for safety reasons If not in view lockable isolating switches must be insta
17. press 0 press enter You have now entered 600kPa as the operational set point The PID figures are set during auto tune amp are not adjustable in this location 4 5 PID Controller Theory The pumping system is controlled via a PID loop controller Proportional Integral 8 Derivative is used to control devices such as drives to maintain control of a varying system This is in most cases done through the examination of signals from sensors placed in the system called feedback signals When the feed back signal is received it is compared with desired value or set point i e our GOOkPa set point above Based on this comparison a calculation of what the necessary response is in order to make the feedback signal match the set point The next three setting below Set Point on the Set Point amp PID page Prop Band Integral Time amp Derivative Time do not require adjusting as these parameters will be tuned as required during the auto tune process in 4 12 below 4 6 Modulating 1 or both pumps The pumping system can be set to modulate 1 or both pump as required If only 1 off pump is modulating the other will be locked in at full speed if a second pump is required If both pumps are set to modulate then when the second pump is called to run both pumps will ramp up amp down until the second pump is not required To select modulating 1 or both simply touch on the box marked modulating 1 amp it will change to modulating both amp vice
18. ropriate pump to manual see section 5 2 below on manual operation amp jack the system up to the approximate pressure set point required Once the system seems stable turn the pumps onto auto amp calibrate as per section 4 below 4 0 Calibration The calibration of the controller is carried out on pages accessed by pressing amp holding in the F1 button on the bottom left of the controller face for 5seconds The first calibration page will appear You can move through the calibration pages by pressing the NEXT PAGE touch point or adjust the settings as required by touching on the setting to be changed which will take you to a virtual enter screen Each input value is recorded once the enter button has been pressed The enter button is the return arrow located at the bottom right corner of the number buttons To get out of calibration pages press the NEXT PAGE touch point on each page until the MAIN PAGE is displayed 4 1 Pressure Sensor Calibration Sensor 0 the value in engineering terms related to the field device feedback signal The pressure transducer sends a 4 20mA signal to the controller This signal needs to be displayed in kPa to mean something to the operator The Sensor 0 is the engineering value when the transducer is at its lowest value i e 4mA amp will be factory set at OkPa This value can be altered to suit different applications as required Example 250kPa Enter the setting screen press 2 press 5 press 0 4 then
19. s enter the settings screen press 0 press 0 press 0 press 5 press enter to accept You have now set 5second as high start time General calibration is now complete Press the Next Page touch point to return to the main page 4 13 Auto Tuning After setting all the calibration setting above which may need small adjustments once auto tuning has been carried out carry out an auto tune which will set up the controller PID parameters to suit the live input from the field pressure transducer It is critical that the following is observed 1 Make shore pump is running at set point pressure amp is not wanting to call other pump online 2 Use only one pump in automatic Turn the remainder off Auto tuning takes from 5 to 20 seconds amp is a three stage process To carry out an auto tune press amp hold the F4 button for 5seconds or the Auto Tune Button the display will flash AUTO TUNE IN PROGRESS until auto tune is complete During this time you can not access other screens Operation 5 1 System Operation The system is designed to maintain a constant pressure in the discharge line of a pumping system The duty pump will start 8 ramp up 4 down in speed maintaining the set point pressure until this duty pump reaches amp maintains 100 speed for a short time delay At this point this pump will be locked in at full speed amp the first standby pump started The first standby pump will then ramp up 4 down maintaining the set point pressur
20. s the controller will select the appropriate pump pattern that leaves the faulty pump as last selected l e Pump 2 is the duty pump with the system selected to automatic alternation If Pump 2 fails the automatic sequence will become Pump 3 Duty Pump 1 standby Pump 2 2 standby although Pump 2 will not operate because it is tripped out on fault To select the alternation pattern touch on the DUTY SELECT box on the main page You will now be in the duty selector page At the top centre of the page will be the identification of which sequence has been selected l e Automatic 12 21 To select a sequence simply touch on the box displaying the appropriate sequence The selected sequence will now be displayed at the top of the page Note if a pump is in fault a manual selection of alternation must not be carried out Once fault condition has been rectified automatic sequence can again be manually selected 6 Variable Speed Drives The Variable speed drives used on this pumping unit are Toshiba VFS11 series The VSD will drive the pump motor at changing speeds controlled via the PLC controller The varying pump speed will maintain a constant system pressure on the discharge line The VSD has a vast number of internal parameter that has been factory set amp do not require any adjustment or fine tuning Any adjustments should be made as per section 4 above amp within the PLC controller 6 1 Manual Override The pumps can be run in a manu
21. scription The pressure control panel is designed to maintain a constant system discharge pressure of an adjustable set point entered by the operator The display shows the set point pressure required amp the actual live pressure input received from the system discharge pressure transducer These two numbers should general be around the same value The system automatically alternates the pump motors each time the draw off required falls to a level at which a desired pressure has been reached 8 a minimum speed on the duty motor has also been reach for a time period User Interface Display Graphical colour touch screen Display 320 x 240 pixels QVGA 3 5 active area Graphic TFT LCD 256 colours Keypad Operator keyboard 5 sealed membrane keys 4 virtual touch pad screen for setting adjustments Information View real time system data Performance Range 0 1000kpa generally programmable to suit transducer range Flow See pumping detail by pumps supplier Inputs 2 wire plus shield connected to terminals located on panel base plate for pressure transducer amp level transducers Outputs Motors 3 wire plus earth overall screened sized to suit motor FLC connected directly to each variable speed drive VFC Power Supply output terminals Proper shielding of motor cable on shield plate at drive Voltage free contacts relays outputs for each pump run each pump fail low discharge pressure power on 415V 3phase neutral am
22. versa Touch the next page touch point to move onto the next page 4 7 Wake up Pressure The wake up pressure is the value at which the system will restart after entering sleep mode This value must be set lower than the Set point value The system will automatically turn off amp go into sleep mode if the Set Point has been reached 5kPa 20second of maintaining this value The Pump Profile page will now be displayed To set wake up pressure to 575kPa Enter the setting screen press 5 press 7 Press 5 press enter The wake up pressure is now set at 575kpa 4 8 Standby Start Speed Standby Start speed is the speed at which the standby pump will be called to start after the duty pump has reached this speed plus a set time delay This speed is factory set at 100 full speed but can be adjusted to be lower if required say 90 Enter the setting screen press 9 press 0 press enter The standby start speed is now set at 90 4 9 Pump Stop Minimum Speed The pump stop minimum speed is the speed at which the standby pump is turned off after the duty pump has reached the pump stop minimum speed plus a short time delay This set point is critical to be set correctly so as to prevent short cycling To set the Pump stop Min Speed you must first operate 1 off pump in manual with a closed discharge to find out the pump speed required to maintain set point pressure Add 2 to ensure the system will get to the setpoint This speed value is then